Elements of the LSN network
LSN couplers
GENERAL FEATURES
- monitored via LSN line,
- Powered from LSN bus
- Additional powering for external
equipment
- 2 direction FET isolation
-
surface mounted design
LSN couplers
NAK 100 LSN Branch coupler
- to connect a derivation branch to LSN elements
- max. 32 detectors or 10 LSN push button
on branch (VdS regulation)
- device deck contact
INSTALLING OF COUPLERS
LSN couplers
NBK 100 LSN fire coupler
- to contact 2 wire conventional detectors to
LSN line, EOLR
- Up to 32 detectors or manual call point
- built in buzzer
INSTALLING OF COUPLERS
INSTALLING OF COUPLERS
LSN couplers
NSB 100 LSN Control coupler
Consist of a control and monitoring module
- 3 variants of connection:
a) Amplification (without acknowledgement)
via relay
b) Controlling sounder, strobe (EOLR or
depolarisation)
c) Controlling sprinkler system (with
acknowledgement)
LSN couplers
NSB 100 LSN for connecting
- Sounder, strobe (monitored)
- 4 wire detectors with contact output,
- Smoke flaps,
- door magnet of fire compartment doors
- Special detectors (line smoke detector, flame
detector),
- Extinguishing system (control and monitoring)
INSTALLING OF COUPLERS
INSTALLING OF COUPLERS
INSTALLING OF COUPLERS
LSN couplers
NTK 100 LSN panel coupler
- up to 8 open collector outputs,
- connection LED or relay
- up to 100 mA/output
- 2 input points (one for tamper and a free
programmable)
INSTALLING OF COUPLERS
LSN couplers
NKK 100 LSN input module
- up to 8 surveillance NO or NC contacts
- built in buzzer
Elements of the LSN network