PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT
POP-UP FLOOR RECEPTACLE
GENERAL NOTES:
LEGEND AND SYMBOLS:
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE
WITH THE PROVISION OF THE LATEST EDITION OF THE
PHILIPPINE ELECTRICAL CODE, THE LAWS AND ORDINANCES
OF THE LOCAL CODE ENFORCING AUTHORITIES AND THE
REQUIREMENTS OF THE LOCAL POWER COMPANY.
FINISH FLOOR LINE
C.O/TEL OUTLET
CIRCUIT RUN CONCEALED IN WALL OR CEILING
LO
LIGHTING OUTLET
CO
CONVENIENCE OUTLET
CIRCUIT RUN CONCEALED IN CONCRETE SLAB
TEF
TOILET EXHAUST FAN
EWH
ELECTRIC WATER HEATER
WP
WEATHER PROOF
FCU
FAN COIL UNIT
ACCU
AIR COOLED CONDENSING UNIT
LP - 1 HOMERUN TO PANELBOARD
2. THE CONTRACTOR SHALL SECURE ALL PERMITS AND PAY
ALL FEES REQUIRED FOR THE WORK AND SHALL FURNISH THE
OWNER THROUGH THE ENGINEERS. FINAL CERTIFICATES OF
ELECTRICAL INSPECTION AND APPROVAL FROM PROPER
GOVERNMENT AUTHORITIES FOR COMPLETE WORK.
SURFACE MOUNTED LIGHTS, (BY ARCHITECTS'S SPECS
50W, HALOGEN LIGHTS, (BY ARCHITECT'S SPECS)
18W, PIN LIGHTS, (BY ARCHITECT'S SPECS)
4. ALL METALLIC CONDUITS, CABINETS AND EQUIPMENT SHALL
BE PROPERLY GROUNDED AND BONDED BY MEANS OF
COPPER STRAPS. CONNECTION TO GROUND ROD SHALL BE
RIGID STEEL CONDUIT. CONDUIT PIPES EMBEDDED IN DIRECT
CONTRACT WITH THE SOIL BE COATED WITH ASPHALT PAINT
WRAPPED IN ASPHALT TAPE, AND FINALLY ANOTHER COAT OF
ASPHALT PAINT, EXCEPT AS OTHERWISE NOTED.
RECESSED PINLIGHT, (BY ARCHITECT'S SPECS)
WALL MOUNTED LIGHTING FIXTURE, SCONCE
SINGLE GANG SWITCH, 10A, 230V WITH PLATE
TWO GANG SWITCH, 10A, 230V WITH PLATE
NOTE: LETTER DENOTES LIGHT CONTROLLED
3Sabc
3
EE-1
POP-UP FLOOR RECEPTACLE
SCALE
2
EE-1
NTS
GROUND ROD DETAIL
SCALE
KILO-WATT-HOUR METER WITH
CURRENT TRANFORMER
SERVICE ENTRANCE
OR
TWO GANG SWITCH, 15A, 230V WITH PLATE
NOTE: LETTER DENOTES LIGHT CONTROLLED
BRASS SCREW ON PLUG COVER
W/NEOPRENE GASKET
MOLDED CASE CIRCUIT BREAKER,
RATING AS INDICATED
20 AT,2P
CHIME, 230V 60Hz
2Sab
COPPER WELD
LP- LIGHTING PANEL
PP- POWER PANEL
ATS- AUTOMATIC TRANSFER SWITCH
MCB- MAIN CIRCUIT BREAKER
CEILING ELECTRIC FAN
SECTION
JUNCTION BOX
TEF
TOILET EXHAUST FAN (PROVISION)
EWH
ELECTRIC WATER HEATER (PROVISION)
CAPB
CATV PULLBOX, 300(L)x300(W)x100(D),GA.16
TIC
TELEPHONE TERMINAL CABINET
PLAN
FINISH FLOOR LINE
NEOPRENE GASKET
WATER SEALANT COMPOUND
CONDUIT PROVISION
FOR GROUND CONNECTION
SIZE AS SHOWN
GROUND CLAMP
GROUND WIRE 50s.q.m
BARE COPPER STRANDED
3M THK. MAT FOUNDATION
COPPER WELD
FLOOR MOUNTED VOICE & DATA OUTLET
S3W
9. PULLBOXES SHALL BE PROVIDED BY THE CONTRACTOR
WHENEVER NECESSARY. TO FACILITATE WIRE PULLING EVEN
IF WHERE NOT INDICATED ON THE PLANS.
2S3Wab
10. ELECTRICAL DEVICES AND MATERIALS SHALL BE
MANUFACTURED BY THE FOLLOWING.
WALL MOUNTED VOICE & DATA OUTLET
t
THREE GANG THREE WAYS SWITCH
NOTE: LETTER DENOTES LIGHT CONTROLLED
SECTION
VOICE & DATA CRICUIT RUN
"4t"- FOUR RUNS OF NUMBER 22/3C AWG PVS
DUPLEX CONVENIENCE OUTLET 15A, 230V PARALLEL
BLADES GROUNDING TYPE
C-COUNTER TOP OUTLET, 150MM A.C.
REF
2. CIRCUIT BREAKERS/DISCONNECT SWITCHES---- SQUARE D, G.E.
3. CONDUITS & FITTINGS (EACH TYPE)------------------ MATSUSHITA
TWO GANG THREE WAYS SWITCH
NOTE: LETTER DENOTES LIGHT CONTROLLED
COPPER WELD
"2t"- TWO RUNS OF NUMBER 22/3C AWG PVS
3S3Wabc
1. RECEPTACLES & SWITCHES ----------------------------- NATIONAL
THREE WAYS SWITCH
WM
4. DEVICE PLATES --------------------------------------------- NATIONAL
"6t"- FIVE RUNS OF NUMBER 22/3C AWG PVS
REFRIGERATOR SINGLE OUTLET 15A, 250V GROUNDING
TYPE UNIVERSAL OUTLET
ELECTRIC MOTOR
MOTOR CONTROLLER
WASHING MACHINE SINGLE OUTLET 20V, 250V
GROUNDING TYPE, UNIVERSAL OUTLET WEATHER
PROOF TYPE
MOUNTING HEIGHTS:
DRYER
DR
RANGE OUTLET, 50A, 250V, GROUND TYPE, NEMA 10-50R
5. CATV OUTLETS ---------------------------------------------- NATIONAL
1.
1.37M (4'-6") FROM CENTER OF DEVICE
TO FINISH FLOOR LINE.
RANGEHOOD
6. TELEPHONE OUTLETS ------------------------------------ NATIONAL
RH
7. INSULATED CONDUCTOR -------------------------------- PHILFLEX, COLUMBIA
SINGLE OUTLET 15A, 230V PARALLEL BLADES
GROUNDING TYPE, FLOOR MOUNTED (POP-UP)
8. HANGERS & SUPPORTS ---------------------------------- ERICO-CADDY
GROUND WELL
2.
XLVI
10. KILOWATT-HOUR-METER ------------------------------ FUJI, OMRON, G.E.
G
11. POWER & AUXILIARY SERVICE BOXES SHALL BE CONCRETE
PSB
PIPE TO CONNECTED TO NEAREST DRAINER LINE.
ASB
EXTRA LOW VOLTAGE TRANSFORMER
GENERATOR SET
POWER SERVICE BOX
500MM X 500MM X 500MM (D)
IN CONCRETE
CONVENIENCE & TEL OUTLET:
0.30M (1'-0") FROM CENTER OF PLATE
TO FINISH FLOOR LINE OR 0.15M(6")
ABOVE WORKING COUNTER OF FITTED
INTO BASEBOARD IF REQUIRED BY THE
ARCHITECT.
GROUND ROD
9. UTILITY & JUNCTION BOXES --------------------------- COUSEHINDS,FUMACO
LIGHT CONTROL SWITCHES:
2.
PANEL BOARD:
1.37M (4'-6") FROM CENTER OF PANEL
TO FINISH FLOOR LINE UNLESS
OTHERWISE REQUIRED BY THE FEILD
CONDITIONS.
AUXILIARY SERVICE BOX
400MM X 400MM X 500MM (D)
IN CONCRETE
THIS DRAWING IS THE PROPERTY OF THE ARCHITECT AND CAN NOT BE REPRODUCED WITHOUT PROPER CONSENT. IT IS AN
DESIGN SHOULD BE NOTIFIED BY THE USER.
PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT
PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT
8. ALL RECEPTACLE OUTLETS SHALL BE PROPERLY
GROUNDED TO THE BOX BY MEANS OF GROUNDING LUGS.
PANEL BOARD
1 X 36W FLUORESCENT LIGHTING FIXTURE RECESSED
MOUNTED INDUSTRIAL LIGHT
PUSH BUTTON SWITCH FOR CRIME, WEATHERPROOF
COPPER WELD
SQUARE BOX
RESIDUAL CURRENT CIRCUIT BREAKER
1 X 36W FLUORESCENT LIGHTING FIXTURE SURFACE
MOUNTED INDUSTRIAL LIGHT
20mm COUPLING,
SILICON ALUMINIUM
BRONZE
CABLE TV OUTLET
NOTE: USE 1RG59 COAX CABLE
7. EXPOSED CONDUIT RUNS SHALL BE INSTALLED PARALLEL
OR PERPENDICULAR WITH THE BUILDING LINE AND
SUPPORTED BY CONDUIT CLAMPS EVERY 1.5M DIAGONAL
CONDUIT RUNS SHALL NOT BE ACCEPTED.
15mm C
1
EE-1
GROUND ROD DETAIL
SCALE
NTS
NTS
PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT
UPLIGHT, (BY ARCHITECT'S SPECS)
BARE COPPER STRANDED
3M THK. MAT FOUNDATION
BOX
MAIN CIRCUIT BREAKER
MCB
PENDANT LIGHTS, (BY ARCHITECT'S SPECS)
3. ALL MATERIALS TO BE USED SHALL BE NEW AND INSTALLED
IN APPLICATIONS FOR WHICH THEY ARE INTENDED.
GROUND CLAMP