HEAT LOAD
The Input Data And Calculation
Space Data
Machine No
GF-9
Space No
Kitchen
Floor No.
Ground
Units Type
DUCTED
Solar &Trans Gain Glass
GLASS
H
N
NE
E
7.00
SE
S
1.00
SW
W
NW
HORIZONTAL
Height (ft)
Area ( ft2)
Volume ( ft3)
10.00
96.00
Trans Gain -Except Glass
WALL
H
N
NE
E
12.00
SE
S
12.00
SW
W
NW
14.20
H
1.00
W
383.00
12.00
26.00
ROOF
FLOOR
PARTITION
CEILING
26.00
12.00
383.00
4596.00
Glass Area Ft2
0.00
0.00
70.00
0.00
96.00
0.00
0.00
0.00
0.00
B-117
G + 1 Villa
Elite Consulting Engineers
Condition Data
Month
8
Yearly Range
50.00
Daily Range
25.00
Time
16.00
Latitude
25 N
Altitude
26.00
External Load
U
0.58
0.58
0.58
0.58
0.58
0.58
0.58
0.58
0.58
Total Wall Area Ft2
0.00
0.00
170.40
0.00
312.00
0.00
0.00
0.00
Net Wall Area Ft2
0.00
0.00
100.40
0.00
216.00
0.00
0.00
0.00
Area Ft2
383.00
0.00
312.00
0.00
EX OR NO
1.00
1.00
1.00
Outdoor
115.00
85.00
30%
135.00
72
(0 to .15)
Design Data
dB F
WB F
0
% RH
GR./LB
Dew point
Haze Factor
SC
0.40
0.40
0.40
0.40
0.40
0.40
0.40
0.40
0.40
External Load
U
Mass Ib/Ft2
0.10
43.62
0.10
43.62
0.10
43.62
0.10
43.62
0.10
43.62
0.10
43.62
0.10
43.62
0.10
43.62
External Load
U
Mass Ib/Ft2
0.08
153.50
0.43
98.33
0.24
44.56
COLOR
Frame Factors
L
0.00
L
0.00
L
0.00
L
0.00
L
0.00
L
0.00
L
0.00
L
0.00
L
0.00
Total Solar &Trans Gain Glass
Color
D
L
D
L
D
D
D
L
Color
L
D
L
D
Trans Gain -Wall
heat to space%
Exposure
100%
100%
100%
Trans Gain- Roof & Others
SENSIBLE
0.00
0.00
0.00
0.00
Internal Load
ELEMENTS
LIGHTS
PEOPLE
MOTORS
REHEAT
APPLIANCES
MISC.
STEAM
W/FT2
2.00
FT2/ Person
63.83
HP
WATT
WATT
WATT
LB/H
Watt
766.00
Persons
6.00
0.00
0.00
0.00
0.00
Light Factor
1.25
Activity Level
1
VENTILATION
CFM/Person
Air Change /Hr
Infiltration
15.00
1.00
SAFETY FACTOR s
SH %
LH %
Others%
10.00%
5.00%
3.00%
UNITS DATA
Operat. Time
24.00
No Of Units
1.00
TOTAL LOAD
Total Grand Load
Total Sensible Heat
Total Latent Heat
TONS
2.82
T adb
54.00
BTU/HR
33807.02
23623.55
10183.47
BTU/HR.FT2
88.27
by-pass F(BF)
0.15
Supply Air
Return Air
Out Door Air
CFM/FT2
2.57
Total Watt
957.50
CFM
No
%
Operat %
100%
Attendance %
100%
Heat to space%
100%
90.00
76.60
0.00
6/24/2015 13:46
Revised
( 2 )- 1/4/2003
Indoor
72.00
60.10
50%
58.00
52
0.15
SOLAR GAIN
BTU/HR
0.00
0.00
154.00
0.00
249.60
0.00
0.00
0.00
0.00
403.60
Out Door Air
Sub-Total
Safety Factor
Difference
43.00
24.90
77.00
20
TRANS GAIN
BTU/HR
0.00
0.00
1745.80
0.00
2394.24
0.00
0.00
0.00
0.00
4140.04
TRANS GAIN
0.00
0.00
341.36
0.00
1036.80
0.00
0.00
0.00
1378.16
TRANS GAIN
1659.16
0.00
1478.88
0.00
3138.04
LATENT
0.00
0.00
SENSIBLE
3255.50
SENSIBLE
1470.00
13785.34
V
INF.
BTU/HR
LATENT
1230.00
1230.00
583.20
0.00
14368.54
1436.85
651.78
0.00
1881.78
94.09
Duct Losses+ Fan HP
Trm - Tsa
20.00
CFM
985.21
785.21
200.00
SHF
0.70
Off Coil Air ToF
55.00
THERMAL
PI
Losses
2.00
INSULATION
Effective Room Heat
Effective Room Total Heat
Out Door Air Heat
A PERFECT SOLUTION FOR A PERFECT LIFE
Roof Load To Plenum
Lights Load To Plenum
Sensible Heat (Plenum)
474.16
SENSIBLE
16279.55
LATENT
1975.87
18255.42
7344.00
0
0
0
8207.60