100% found this document useful (1 vote)
754 views1 page

Rcug - 120ahyz1

This document provides specifications for an air-cooled screw type water chiller model RCUG120AHYZ1, including: - It has a nominal cooling capacity of 340 kW and design cooling capacity of 332.6 kW. - The evaporator is a shell-and-tube type with steel/copper material and 25mm polyethylene insulation. - It has a direct drive propeller fan made of aluminium alloy and uses an 8 pole direct-on-line starting semi-hermetic screw compressor. - The unit has dimensions of 418x342x342mm and a net weight of 178/178 kg.

Uploaded by

Tran Anh Tuan
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
754 views1 page

Rcug - 120ahyz1

This document provides specifications for an air-cooled screw type water chiller model RCUG120AHYZ1, including: - It has a nominal cooling capacity of 340 kW and design cooling capacity of 332.6 kW. - The evaporator is a shell-and-tube type with steel/copper material and 25mm polyethylene insulation. - It has a direct drive propeller fan made of aluminium alloy and uses an 8 pole direct-on-line starting semi-hermetic screw compressor. - The unit has dimensions of 418x342x342mm and a net weight of 178/178 kg.

Uploaded by

Tran Anh Tuan
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

[APPLICABLE MODEL FROM COMPUTER]

AIR-COOLED TYPE WATER CHILLER-Screw Type-H Series


MODEL NUMBER
Nominal cooling capacity Cooling capacity(design) kW kW RCUG120AHYZ1 340(12/7 & DB35) 332.6 Shell-and-Tube, Dry Expansion Type Steel/Copper Polyethylene(25mm) 7 12 57.2 53 0.018 Cross Fin Type(Aluminium/Copper) 37 Direct drive Propeller Fan(Aluminium Alloy) 8 960 Drip-Proof Enclosure 8 Direct-On-Line Starting 6 E 1.1 Semi-Hermetic Screw Type 60ASCCW-Z 2 2880 2 R407C 100~15(7.5),0 Three-Phase asynchronism Star Delta 2 F 45 380/3/50 418 342 342 178/178 197 125.6 4,490 1,940 2170 3,280

EVAPORATOR
Type Material shell/tube Insulation Chilled water outlet temperature Chilled water inlet temperature Chilled water flow rate Evaporator pressure drop Specific Fouling Factor

Deg.C Deg.C m3/h kPa [Link].C/kW

CONDENSER
Type(Material) Condenser air inlet temperature Deg.C

CONDENSER FAN
Type(Material) Quantity Revolutions

50Hz-r/min.

FAN MOTOR
Type Quantity Starting method Number of poles Insulation class Input power(motor)

kW

COMPRESSOR
Type Model Quantity Revolutions Circuits Refrigerant Capacity control Motor type Starting method Number of poles Insulation class Output power(motor) ELECTRICAL DATA Power supply Maximum unit voltage Minimum unit voltage Maximum unit current Starting current([Link].1-) Running current(Comp.) Input power(Comp.+fan) DIMENSIONS AND WEIGHT Depth Width Height Net weight

50Hz-r/min.

kW V/Phase/Hz V V A A A kW mm mm mm kg

NOISE The measuring point is 1 m from the centre of the machine's surface and 1.5 m from floor level. 45-90 90-180 180-355 355-710 710-1400 1400-2800 Octave band (Hz) 71.8 52.8 57.2 65.4 66.5 67.8 66.9 dB(A) OPERATING SPACE Front/rear side of unit(with electric box side) Right,left and back of unit(without electric box side) Note:Specifications in this sheet are just for reference [Link] shall reserve right to change specification in this sheet without any notice. mm mm