Emerging Technologies in Room (Suite) Pressure Control,
Performance Modeling and Design Practices
Wei Sun, P.E.
ASHRAE
Principal, Director of Engineering
Engsysco, Inc.
Ann Arbor, Michigan, USA
___________________________________
Emerging Technologies in Room (Suite)
Pressure Control, Performance
Modeling and Design Practices
___________________________________
___________________________________
___________________________________
Presented by
Wei Sun, P.E.
ASHRAE
Clean Spaces Technical Committee (TC9.11) Chairman
Healthcare Facilities Technical Committee (TC9.6) Member
Laboratory Systems Technical Committee (TC9.10) Member
Principal, Director of Engineering
Engsysco, Inc.
Ann Arbor, Michigan, USA
___________________________________
Engsysco
___________________________________
___________________________________
[Link]
___________________________________
Introduction
Room Pressurization Technique
___________________________________
Purposes
Direct desired flow patterns
Isolate airborne cross contamination
___________________________________
Definition
A technique that air pressure differences are created
mechanically between rooms to introduce intentional air
movement paths through room leakage openings. These
openings could be either designated, such as doorways, or
undesignated, such as air gaps around doorframes or other
duct/piping penetration cracks.
___________________________________
___________________________________
How to achieve
It can be achieved by arranging the controlled volumes of
supply, return, and exhaust airstreams to each room within the
space.
___________________________________
___________________________________
___________________________________
Introduction
___________________________________
Basic Rules
Air connection between two adjacent
rooms is through connecting opening(s).
If a door between two rooms is open, the
doorway will be the main designated flow
path.
If the door is closed, then the leakage will
be through undesignated paths, such as
air gaps along doorframes, joints, pipe
and duct penetrations and gaps around
ceiling panels etc. Most of these
controllable cracks (except for operable
doors) in typical controlled spaces are
required to be permanently sealed.
P1 > P2
Room 1
Room 2
RA1 + EA1
RA2 + EA2
___________________________________
Leakage Flows
Door Closed
P1
SA1
SA2
P2
___________________________________
P1 > P2
Room 1
Room 2
RA1 + EA1
RA2 + EA2
Leakage Flows
Door Opened
P1
SA1
SA2
P2
___________________________________
___________________________________
___________________________________
___________________________________
Introduction
___________________________________
Basic Rules
To Achieve P1 > P2 ,
Room 1
SA1 > (RA1+EA1), and
SA2 < (RA2+EA2)
Room 2
RA1 + EA1
___________________________________
RA2 + EA2
SA1 = (RA1+EA1) + Q
SA2 + Q = (RA2+EA2)
Leakage Flow
Q is the leakage (transfer) air
from Room 1 to Room 2, if
both rooms are tightly sealed,
except for the opening
between rooms.
Leakage Opening
SA1
P1
___________________________________
SA2
P2
___________________________________
___________________________________
___________________________________
___________________________________
Introduction
___________________________________
Relationship between Leakage Flow, Leakage Area
and Pressure Drop across Leakage Path
The pressure drop (differential)
across an opening (either a crack
or a doorway) is strongly related
with the leakage opening size
(effective leakage area) and
leakage flow through the opening.
To quantitatively achieve a
desired room pressure (or,
pressure differential between
rooms), leakage openings and
respective leakage airflows need
to be studied together.
___________________________________
Room 1
Room 2
RA1 + EA1
A
Leakage Area
SA1
P1
___________________________________
RA2 + EA2
Q
Leakage Flow
SA2
P2
___________________________________
___________________________________
Pressure Differential
___________________________________
___________________________________
Airflow through Leakage Opening
Power Equation: (Esq.. 1)
___________________________________
Room 1
Room 2
RA1 + EA1
RA2 + EA2
Q = C (P )n
Leakage Flow
P1
SA1
SA2
P2
where
Q = volumetric flow rate
P = pressure drop across opening
C = flow coefficient
n = flow exponent
___________________________________
Leakage Area
Pressure Differential
CFM (L/s)
in. of water (Pa)
CFM/(in. of watern) (L/s/Pan)
dimensionless
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Airflow through Large Designated Opening
Orifice Equation: (Esq.. 2)
Room 1
Room 2
RA1 + EA1
Q = 2610 A P
(I-P unit)
Q = 840 A P
(SI unit)
RA2 + EA2
Q
Leakage Flow
P1
SA1
SA2
P2
Pressure Differential
volumetric flow rate
pressure drop across opening
large designated opening area's)
unit conversion factor
unit conversion factor
___________________________________
Leakage Area
where
Q
=
P =
A
=
2610 =
840 =
___________________________________
CFM (L/s)
in. of water (Pa)
ft2 (m2)
dimensionless (I-P unit)
dimensionless (SI unit)
___________________________________
___________________________________
___________________________________
Orifice Equation is more popularly used in design community
___________________________________
___________________________________
Air Leakage Rate vs. Pressure Difference for
Various Leakage Areas (Based on Orifice Equation)
2,000
Leakage Area
(Sq. in.)
1,800
1,700
380
___________________________________
360
340
1,600
320
1,500
Leakage Flowrate (cfm)
___________________________________
400
1,900
300
1,400
280
1,300
260
1,200
240
1,100
___________________________________
220
1,000
200
900
180
800
160
700
140
600
120
500
100
400
80
300
60
200
40
20
100
0
0
___________________________________
___________________________________
0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06 0.065 0.07 0.075 0.08
Pressure Differential Between Rooms (in.)
___________________________________
___________________________________
Leakage Area Value Determination
Large designated openings such as doorway can be easily
measured. However irregular opening such as a crack can not
be measured physically, there is other means to estimate the
equivalent size, or called Effective Leakage Area (ELA).
___________________________________
___________________________________
For Existing Rooms:
Field Blower Door Test (ASTM 1987, CGSB 1986) to obtain
more precious data.
For Future Rooms during design phase:
Use ASHRAE ELA tables for building components (doors,
walls, joints, etc.) as estimated values.
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
ASTM Blower Door Test,
- Traditional Room Air-tightness Test
Portable Pressurization Blower Test can
produce a set of data of Q - P, and a
power equation curve fit with calculated
constants (C, n, ELA) that defines a rooms
unique and dynamic leakage characteristic.
Abnormal test ranges:
ASTM (1987):
12.5 - 75 Pa
(0.05 - 0.30 in.)
CGSB (1986):
5 - 50 Pa
(0.02 - 0.20 in.)
___________________________________
___________________________________
___________________________________
___________________________________
Labor intense, time consuming
___________________________________
Disruption to occupied spaces
___________________________________
___________________________________
Blower Door Test - Multiple-Point Test
Data for Power Equation Curve Fitting
Q = C ( P )
Power equation:
Once obtained Q - P data set, C and n can be calculated:
m
( ln Qk
ln Pk ) m (ln Qk ln Pk )
k =1
k =1
n = k =1
m
ln Pk )
k =1
(ln Pk )
k =1
m
m
ln Qk n
ln Pk
k =1
C = EXP k =1
m
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Opening Resistance Analysis
Define:
Leakage Flow Resistance R
___________________________________
1
R=
ELA
___________________________________
Leakage flow resistances connected in parallel and series
n
ELA = ELA
Q
Pi
P
i =1
___________________________________
ELAT =
2
i =1 (ELAi )
n
Qi
___________________________________
___________________________________
___________________________________
___________________________________
Room Pressurization Scenarios and
Variable Relationship
___________________________________
Scennario 1: Room Prerssurized
SA - (EA+RA) = V = Q > 0
Room
Positively
Pressurized
Offset
Flow
V
Total Leakage
Airflows
Q
___________________________________
___________________________________
Total Room Exhaust
and/or Return Airflow
(EA+RA)
Total Room
Exhaust and/or
Return Airflow
(EA+RA)
Total Room
Supply Airflow
(SA)
Total Room
Supply Airflow
(SA)
___________________________________
___________________________________
___________________________________
___________________________________
Room Pressurization Scenarios and
Variable Relationship
___________________________________
Total Room
Exhaust and/or
Return Airflow
(EA+RA)
Room
Non-Pressurized
Total Leakage
Airflows
Q = 0
Total Room Exhaust and/or
Return Airflow
(EA+RA)
Total Room
Supply Airflow
(SA)
Total Room
Supply Airflow
(SA)
Scennario 2: Room Non-Prerssurized
SA - (EA+RA) = V = Q = 0
___________________________________
Offset
Flow
V = 0
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Room Pressurization Scenarios and
Variable Relationship
Scennario 3: Room De-prerssurized
SA - (EA+RA) = V = Q < 0
Room
Negatively
De-pressurized
Offset
Flow
V
Total Leakage
Airflows
Q
___________________________________
Total Room Exhaust and/or Return
Airflow
(EA+RA)
Total Room
Exhaust and/or
Return Airflow
(EA+RA)
Total Room
Supply Airflow
(SA)
Total Room
Supply Airflow
(SA)
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Central Air Handling System &
Room Pressurization
SA =
Volume of total
supply air entering
the space/zone
RA = Volume of total
return air leaving the
space/zone
EA = Volume of total
exhaust air leaving
the space/zone
OA = Volume of outside air
drawn into the AHU
FA = Volume of relief air
released from return
air
RA-FA = Volume of
recalculated air
Q=
Volume of total
leakage air through
space shell/zone
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Central Air Handling Unit &
Room Pressurization
___________________________________
Two volumetric
balance equations
___________________________________
(Mass balance equation under
assumption of same air density)
SA = RA + EA + Q
(Volume balance for a space)
SA = OA + (RA FA)
___________________________________
___________________________________
(Volume balance for a typical AHU)
___________________________________
___________________________________
___________________________________
Space Pressurization Ratio (R)
Define as the Ratio between SA and (RA+EA), as an
indicator of pressurization scale:
SA
SA
R=
=
RA + EA SA Q
___________________________________
___________________________________
___________________________________
By specifying SA values, R will be a function of Q. R
Value Chart is convenient for design engineers to
determine SA and (RA+EA) ratio during air distribution
arrangement.
___________________________________
Chart
___________________________________
___________________________________
___________________________________
Pressurization Ratio vs. Air Leakage Rate
for Various Supply Air Rates
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Space versus Room Pressurization Ratios
The relationship between the space pressurization ratio
and its individual room pressurization ratios:
R=
1
(SAi SA)
i =1
___________________________________
___________________________________
Ri
___________________________________
The space pressurization ratio, an indicator of relative
pressurization level, can be used to adjust air gains or
losses among zones in order to arrange desired air
flows within a building.
___________________________________
___________________________________
___________________________________
___________________________________
Adjacent Rooms under Various Pressures
___________________________________
If a room has several leakage openings with adjacent
rooms, the rooms pressurization ratio is:
___________________________________
RR =
___________________________________
SAR
n
SAR Qi
___________________________________
i =1
___________________________________
___________________________________
___________________________________
Pressure Differential and Crack Air Velocity
Criterion 1 (Pressure Differential P)
For single room:
P: 0.05 in. of water (12.5 Pa)
___________________________________
For multiple-room space with staged pressurizations:
P: 0.02 in. ~ 0.03 in. (5 Pa ~ 7.5 Pa) for each pressure step
Criterion 2 (Average Crack Velocity V)
___________________________________
100 fpm (30 M/m)
From comparison below, the pressure criterion of P = 0.05 in. is much more
conservative than the velocity criterion of V = 100 fpm.
Pressurization
Criterion
Pressure
Differential P
Crack Leakage
Velocity V
Large Opening
Velocity V
Pressurization Criterion Comparison
Unit
___________________________________
0.06
0.0015 0.01
0.02
0.03
0.04
0.05
fpm
109
374
587
764
920
1,064 1,198 1,444 1,670
fpm
100
261
369
452
522
584
639
0.08
Basis
In
738
___________________________________
0.10
825
Eq. (1),
when n=0.65
Eq. (2a)
___________________________________
___________________________________
___________________________________
Room Pressurization Variables and
Control Strategies
Airflow differential between entering airflow (supply airflow,
SA) and leaving airflow (exhaust and/or return airflows,
EA+RA), normally called offset value (V), which equals the
total leakage airflow (Q) of the room.
To maintain a specific room pressure value, the rooms offset
airflow (V) must be controlled and maintained at the
appropriate value.
Rooms offset airflow can be controlled directly or indirectly.
The treatment of the room offset value defines a
pressurization control strategy. Typical pressurization control
techniques are: Direct Pressure-Differential Control,
Differential Flow Tracking Control, Hybrid Control and
Adaptive Control.
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Direct Pressure-Differential Control (DP)
Utilizes a pressure differential sensor to measure the pressure difference
between a controlled room and an adjacent space such as a corridor. It basically
ignores the specific offset value as required, instead, it directly controls the
airflow control devices to achieve the required pressure differential.
Room
Exhaust
Valve
Room
Supply
Valve
SUPPLY
AIR
Hood
Exhaust
Hood
Exhaust
Total Exhaust
Air from Room
DP
Leakage
Air
Hood
Valve &
Controller
ROOM
CONTROLLER
DS
Door
Switch
CORRIDOR
Leakage
Air
Velocity
Sensor
CHEMICAL
LAB
___________________________________
___________________________________
Total Supply
Air to Room
DP
Sensor
___________________________________
or
Fume
Hood
___________________________________
Sash
Sensor
Thermostat
Suitable for a tightly constructed room with limited traffics.
Door switch is recommended to trigger a reduced pressure differential setpoint if the door opens.
___________________________________
___________________________________
___________________________________
Differential Flow Tracking Control (DF)
Intuitively assumes an offset value which is used as a flow difference
___________________________________
between the entering and leaving airflows to control their respective
airflow devices. Maintain the same offset value throughout the operation
to keep pressurization constant, or maintain a constant percentage offset
value which creates a weaker pressurization at lower flow.
___________________________________
Room
Exhaust
Valve
Room
Supply
Valve
SUPPLY
AIR
DP
Monitor
Hood
Exhaust
Total Exhaust
Air from Room
Hood
Exhaust
___________________________________
Total Supply
Air to Room
DP
Flow
Sensor
Leakage
Air
Flow
Sensor
___________________________________
Hood
Valve &
Controller
ROOM
CONTROLLER
DS
Door
Switch
CORRIDOR
Leakage
Air
Velocity
Sensor
CHEMICAL
LAB
___________________________________
or
Fume
Hood
Sash
Sensor
Thermostat
Suitable for open-style rooms or rooms with frequent traffics
___________________________________
___________________________________
Hybrid Control (DP+DF)
Combines the pressure accuracy of the direct pressure differential control
and the stability of the flow tracking control. The offset value is reset-able
based on pressure differential reading. The offset value reset schedule is
pre-determined and controllers parameters are fixed manually in field.
This method is also called cascaded control.
Room
Supply
Valve
SUPPLY
AIR
Room
Exhaust
Valve
Hood
Exhaust
Hood
Exhaust
Total Exhaust
Air from Room
___________________________________
___________________________________
___________________________________
Total Supply
Air to Room
DP
Sensor
Flow
Sensor
DP
Flow
Sensor
ROOM
CONTROLLER
Leakage
Air
___________________________________
Hood
Valve &
Controller
DS
Door
Switch
CORRIDOR
Velocity
Sensor
CHEMICAL
LAB
Fume
Hood
Thermostat
Leakage
Air
or
Sash
Sensor
___________________________________
Suitable for open-style rooms or rooms with frequent traffics
___________________________________
___________________________________
Multiple-Room (Suite)
Pressure Control Strategies
___________________________________
Single room control technologies
often cause problems in Suite
Pressure Control during air
balancing, since the following
phenomena are often ignored:
___________________________________
Adjusting one rooms offset
value will impact adjacent
rooms air pressures if they
were just balanced earlier.
One rooms air gain could be
another rooms air loss
through leakages.
___________________________________
___________________________________
___________________________________
Example - Pharmaceutical Aseptic Suite
___________________________________
___________________________________
Adaptive Control (DP+DF+AD)
___________________________________
The three traditional methods (DP, DF and DP+DF) are
either to ignore, assume or manually fix in field the
offset value respectively.
The adaptive (DP+DF+AD) approach directly accounts for
leakage flows between the rooms in a suite. It controls all
rooms pressures all together as an optimized system,
instead of controlling each room pressure independently. It
actively adjusts the flow offset of each room according to an
on-line pressurization model. The model uses flow and
pressure differential measurements to estimate the leakage
values between the rooms and adjust flow offset of each
room automatically.
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Automated Room Air-tightness Test
Pre-condition for Truly Adaptive Control
___________________________________
Similarly as Blower Door
Test, but fully automated.
A rooms unique dynamic
leakage characterization can
also be automatically achieved
by digital controller, precision
pressure differential sensor
(0.001 in./0.25 Pa) and
airflow control devices (5%).
These devices are often
permanently installed in lab
and clean room environments.
This automated pressurization
test (Q-P data set) is faster
and cheaper, and can be
handled remotely.
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Adaptive Control (Example: Control of Multiple Rooms)
DP
Designated
Leakage Flow
CLEANER
ROOM
0.06 In.
DS
CLEANEST
ROOM
0.08 In.
SUITE
CONTROLLER
DS
Return
Air
Valve
___________________________________
Pressure
Differential
Sensor
___________________________________
Door Switch
DS
DS
Valve Position
Outputs
GENERAL
CHEMICAL LAB
- 0.02 In.
DP
Exhaust
Air
Valve
Minor Leaks
Thru. Cracks
DP
DS
DS
___________________________________
CONTAINMENT
LAB
- 0.06 In.
Supply
Air
Valve
AIRLOCK
0.03 In.
___________________________________
Legend
DP
DP
Valve
Flowrate
Inputs
SUITE
CONTROLLER
DP
CORRIDOR
0.00 In.
Manifolded or
Open to Corridor
Room Pressure
Inputs
Door
Switch
Inputs
___________________________________
___________________________________
___________________________________
Air Flows between Rooms
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Airflow Between Rooms
___________________________________
___________________________________
Personnel Flows between Rooms
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Personnel Flow Between Rooms
___________________________________
___________________________________
More Considerations
___________________________________
Correction and Safety Factors Add as required
Correction Factors
___________________________________
Safety Factors
Refer to ASHRAE Handbooks 1999 &
2001, detailed procedures will be included in
the next phase of the study)
(Detailed procedures will be included in the
next phase of the study)
Stack effect
Wind effect
Interior zones with high
temperature or humidity
differences
Room background leaks
Duct leaks
AHU unit leak
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Samples of Pressurization Control Devices
Flow Control & Measure
___________________________________
Pressure Measure
___________________________________
Static
Static Pressure
Pressure
Measuring
Measuring Probes
Probes
Control
Control
Damper
Damper
___________________________________
Air
Air Valve
Valve
Type
Type 11
Pressure
Pressure
Transmitter
Transmitter
___________________________________
Air
Air Valve
Valve
Type
Type 22
___________________________________
Pressure
Pressure
Transmitter
Transmitter
and
and Monitor
Monitor
Air
Air Valve
Valve -Type
Type 33
___________________________________
___________________________________
Case Study - Airflow Resistance and
Leakage Flow Simulation
___________________________________
Major and minor leakage openings, connection in parallel
and series
RM2
RM1
RM4
RM5
RM2
RM1
RM4
___________________________________
RM5
RM6
RM6
RM3
___________________________________
RM3
Network Flow with Major Openings Only
RMX
___________________________________
Network Flow with Major and Minor Openings
- Room Numbe
- Wall
- Flow Direction
- Induced Flow (by Pressurization)
- Node (Room)
- Flow Resistance @ Major Opening
- Flow Resistance @ Minor Opening
- Forced Flow (by Fan)
___________________________________
___________________________________
___________________________________
Modeling of Transient Pressurization
___________________________________
1. Pressurization Loss Characteristic During a Swing
Door Opening or Closing
(t )
= 2 W sin
2
(t )
t
A( t ) = H L( t ) = 2 H W sin
2
(t )
Room 2
(0 60 o )
P2
L
( 60 < 90 o )
= H W
___________________________________
Swing Door
P1
Room 1
___________________________________
P1 > P2
where,
L=width (gap) of door opening in. (cm)
W=width of door
in. (cm)
=angle of door opening degree
=speed of door turning degree/sec.
t=time
sec.
H=door height
in. (cm)
A=effective door opening width (gap) in2(cm2)
___________________________________
Wall
Transient Flow Through Swing Door
___________________________________
___________________________________
___________________________________
Modeling of Transient Pressurization
___________________________________
1. Pressurization Loss Characteristic During a Swing
Door Opening or Closing
___________________________________
Transient Pressure Differential Across When A Swing Door Opens
Pressure Drop Across Door
W idth of Door Opening
Autom atic Swing Door Opens to 90 in 3 Seconds; Door Size 4 ft. (W ) x 7 ft. (H).
Room s Across The Door/Wall Are Maintained with Cons tant Supply and Return Flows .
Initial Pressure Differential Ac ros s Door is 68.9 Pa, it drops to 1 Pa les s than 2 s ec onds.
Angle of Swing Door Opening (Degree)
0
10
20
30
40
50
60
70
80
90
60
40
40
30
30
20
20
10
10
Width (Gap) of Door Opening (in.)
50
50
Airlock Room Pressure Profile
0.100
0.095
First Door Opening
First Door Closing
1.5
2.5
Second Door Closing
0.080
Room Static Pressure (in. WC)
0.5
Second Door Opening
0.090
0.075
Both Doors Closed
0.085
0
3
Time of Door Opening (Second)
Cleanroom
0.070
___________________________________
0.065
0.060
0.055
0.050
___________________________________
0.045
Airlock
0.040
0.035
0.030
0.025
0.020
0.015
Corridor
0.010
0.005
0.000
-0.005
-0.010
___________________________________
Airlock Sliding Door Operation Cycle
___________________________________
Modeling of Transient Pressurization
___________________________________
2. Pressurization Loss Characteristic During a Sliding
Door Opening or Closing
___________________________________
Sliding Door
Room 2
P2
L
P
W
where,
Wall
W=width of door
P1 > P2
in. (cm)
Transient Flow Through Sliding Door
t=time
sec.
s=speed of door opening
in./sec. (cm/sec.)
H=door height
in. (cm)
___________________________________
P1
Room 1
L=width (gap) of door opening in. (cm)
___________________________________
___________________________________
A=effective door opening width (gap) in2(cm2)
___________________________________
___________________________________
Modeling of Transient Pressurization
___________________________________
2. Pressurization Loss Characteristic During a Sliding
Door Opening or Closing
___________________________________
Transient Pressure Differential Across W hen A Sliding Door Opens
Pressure Drop Across Door
W idth of Door Opening
Automatic Sliding Door Opens at Speed of 16 in./sec.; Door Size 4 ft. (W ) x 7 ft. (H);
Rooms Across The Door/W all Are Maintained with Constant Supply and Return Flows,
Initial Pressure Differential Across Door is 68.9 Pa, it drops to 1 Pa around 2 seconds.
60
70
60
___________________________________
40
40
30
30
20
20
10
10
0
0
0.5
1.5
T ime of Door Opening (Second)
2.5
Width (Gap) of Door O pening (in.)
50
50
Pressure Differentials Between Rooms
Pressure Differential between Rooms (in. WC)
Pressure Differential Across Door (Pa)
Pressure Differential Across Door (Pa)
___________________________________
60
70
0.100
0.095
0.090
0.085
0.080
0.075
0.070
0.065
0.060
0.055
0.050
0.045
0.040
0.035
0.030
0.025
0.020
0.015
0.010
0.005
0.000
-0.005
-0.010
First Door Opening
First Door Closing
Both Doors Closed
Second Door Opening
DP
(Cleanroom and Corridor)
DP (Door 1)
DP (Door 2)
Airlock Sliding Door Operation Cycle
Second Door Closing
___________________________________
___________________________________
___________________________________
___________________________________
Door Opening Transient Impact on
Pressurization Control
___________________________________
Any passive motor-driven or actuator-driven HVAC
system (such VAV box or valve) will not have enough
time to react effectively to prevent possible cross
contamination.
A single barrier door could cause a short duration of
backflow contamination until the motor or actuator
completes the modulation cycle of re-balancing,
additional means to prevent possible backflow
contamination, such as double-door airlock is necessary.
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Dynamic Pressurization Control Strategies
- Airlock
Air Lock Type
CORRIDOR
AIRFLOW
CORRIDOR
AIRFLOW
AIRLOCK
AIRLOCK
++
++
Cascading
Bubble
Sink
DualCompartment
AIRFLOW
AIRFLOW
CLEANROOM
CLEANROOM
+++
CASCADING AIRLOCK
CORRIDOR
AIRFLOW
AIRLOCK
AIRLOCK
--
++
AIRFLOW
___________________________________
___________________________________
BUBBLE AIRLOCK
CORRIDOR
AIRFLOW
___________________________________
CLEANROOM
CLEANROOM
--
AIRFLOW
SINK AIRLOCK
___________________________________
AIRLOCK
___________________________________
DUAL COMPARTMENT AIRLOCK
___________________________________
___________________________________
Dynamic Pressurization Control Strategies
- Airlock
Airlock Physical Model
Network Flow Simulation
Cleanroom
___________________________________
___________________________________
___________________________________
0.06 in.
___________________________________
-6 -3 0 3 6
Wait!
-6
-3
0
3
6
P
Door 2
Airlock (Cascading)
P
Door 1
0.03 in.
P
Rooms
___________________________________
-6 -3 0 3 6
Corridor
0.00 in.
___________________________________
___________________________________
Result of Network Flow Simulation
___________________________________
___________________________________
Clean room
0.06 in.
___________________________________
-6 -3 0 3 6
Wait!
P
Door 2
Airlock (Cascading)
P
0.03 in.
Door 1
-6
-3
0
3
6
P
Rooms
___________________________________
-6 -3 0 3 6
Corridor
0.00 in.
___________________________________
___________________________________
___________________________________
CFD Model to Study Airlock Transient
Performance - Physical Conditions
___________________________________
Case 2 Class 100
Case 1 Class 10,000
(12000 CFM, 75 ACH)
___________________________________
(48000 CFM, 300 ACH)
8400 CFM, 300 ACH)
(2100 CFM, 75 ACH)
(560 CFM, 10ACH)
___________________________________
560 (CFM, 10ACH)
11948 CFM
Leakage 73 CFM
Leakage 73 CFM
8378 CFM
2078 CFM
Leakage 52 CFM
Leakage 52 CFM
Clean Room: 10000
Airlock: 10,000
Corridor: 100000
47948 CFM
Clean Room: 100
Airlock: 100
Corridor: 100000
___________________________________
___________________________________
___________________________________
___________________________________
Steady State Airflow Distribution
Case 1 Class 10,000
Case 2 Class 100
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Steady State Cleanroom Particle
Concentration
Case 1 Class 10,000
Case 2 Class 100
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Corridor Particles Enter Airlock Room
Case 1 Class 10,000
Case 2 Class 100
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Airlock Particles Enter Clean Room and
Corridor
Case 2 Class 100
Case 1 Class 10,000
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Airlock Particles Enter Clean Room and
Corridor
Case 2 Class 100
Case 1 Class 10,000
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Variation of Corridor Particle Concentration
Case 2 Class 100
Case 1 Class 10,000
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Airlock Door Transient Performance
Pressure Differential Across Cleanroom Door During Walk-Through
Profile of Pressure Differential Across Door
When Door Is Opening & Closing
Profile of Pressure Differential Across Door
When Door Is Opening & Closing
(Initial Condition: -15 Pa = -0.06 In.)
(Initial Condition: 5 Pa = 0.02 In.)
Door Opening
Door Closing
Test 1
Test 2
Test 3
Average
-5
-10
-15
-20
0
10
11
12
13
14
15
20
15
10
Test 1
Test 2
Test 3
Average
5
0
-5
Door Opening
10
11
12
13
14
15
16
___________________________________
(Initial Condition: 10 Pa = 0.04 In.)
20
15
Door Opening
Door Closing
10
Test 1
Test 2
Test 3
Average
-5
-10
-15
Pressure Differential Across Door (Pa)
25
-20
20
15
10
Test 1
Test 2
Test 3
0
Door Opening
Average
Door Closing
-5
-10
-15
-20
10
11
12
13
14
15
16
Time (Sec.)
10
11
12
13
14
15
16
Profile of Pressure Differential Across Door
When Door Is Opening & Closing
(Initial Condition: -5 Pa = -0.02 In.)
(Initial Condition: 15 Pa = 0.06 In.)
25
20
15
Door Opening
Door Closing
10
Test 1
Test 2
Test 3
Average
-5
-10
-15
-20
1
10
11
12
13
14
15
Pressure Differential Across Door (Pa)
25
20
15
10
Test 1
Test 2
Test 3
Average
-5
Door Opening
Door Closing
-10
___________________________________
-15
-20
16
Time (Sec.)
10
11
12
13
14
15
16
14
15
16
Time (Sec.)
Profile of Pressure Differential Across Door
When Door Is Opening & Closing
Profile of Pressure Differential Across Door
When Door Is Opening & Closing
(Initial Condition: 0 Pa = 0 In.)
(Initial Condition: 20 Pa = 0.08 In.)
25
20
15
Door Closing
10
Test 1
Test 2
Test 3
Average
-5
-10
-15
-20
Pressure Differential Across Door (Pa)
25
Door Opening
___________________________________
Time (Sec.)
Profile of Pressure Differential Across Door
When Door Is Opening & Closing
Pressure Differential Across Door (Pa)
Time (Sec.)
Profile of Pressure Differential Across Door
When Door Is Opening & Closing
(Initial Condition: -10 Pa = -0.04 In.)
Pressure Differential Across Door (Pa)
Door Closing
-10
-15
-20
16
Time (Sec.)
Profile of Pressure Differential Across Door
When Door Is Opening & Closing
25
Pressure Differential Across Door (Pa)
___________________________________
25
20
15
10
Pressure Differential Across Door (Pa)
Pressure Differential Across Door (Pa)
25
20
15
10
Test 1
Test 2
Test 3
Average
5
0
___________________________________
-5
Door Opening
Door Closing
-10
-15
-20
Time (Sec.)
10
11
12
13
14
15
16
Time (Sec.)
10
11
12
13
___________________________________
___________________________________
Contamination Risk Factor (CRF)
CRF is a criterion which is to quantity the effectiveness of cleanroom particle
containment in preventing the airborne particles migration into cleanroom.
___________________________________
___________________________________
CRF = PC / PO
CRF = Contamination Risk Factor
PC = Number of Particles inside Protected Cleanroom Near Door
PO = Number of Particles at Corridor Entrance Near Door
___________________________________
This criterion is applied for a Barrier Device which is to minimize particle
migration. This barrier could be single door, an airlock (two doors in series),
mini environment, or glove box.
The lower of the CRF level, the better barriers performance, or the better decontamination effectiveness. This expression can not only apply for airborne
particle, but also for airborne microorganism egress, in which the particle
counts will be replaced with Colony Forming Unit (CFU).
___________________________________
___________________________________
___________________________________
___________________________________
Particle Concentrations & CRF Across Cleanroom
Door Under Various Pressure Differentials
Particle Concentrations Across Cleanroom Door
When Door is Opening & Closing
Particle Concentrations Across Cleanroom Door
When Door is Opening & Closing
(Initial Condition: Depressurization @ -15 Pa = -0.06 In. )
Inside Cleanroom Door Average
Inside Cleanroom Door Average
30,000
CRF
= 18.9%
20,000
10,000
70,000
Door
Opening
60,000
Door Opening & Closing W/O People Traffic
A Person Walks Through Door
CRF
= 2.2%
10,000
9 10 11 12 13 14 15 16 17 18 19 20 21 22
Particle Concentrations Across Cleanroom Door
When Door is Opening & Closing
(Initial Condition: Depressurization @ -10 Pa = -0.04 In. )
(Initial Condition: Pressurization @ 10 Pa = 0.04 In. )
Outside Cleanroom Door Average
Ins ide Cleanroom Door Av erage
80,000
Outside Cleanroom Door Average
80,000
70,000
Door
Opening
60,000
Particle Concentrations Across Door
3
(Counts / FT )
Door
Closing
50,000
40,000
30,000
CRF
= 8.5%
20,000
10,000
0
0
70,000
Door
Opening
Door
Cl osing
60,000
50,000
40,000
30,000
CRF
= 0.7%
20,000
Inside Cleanroom Door A ver age
Particle Concentrations Across Door
3
(Counts / FT )
Door
Ope ning
Door
Closing
50,000
CRF
= 6.9%
20,000
10,000
0
70,000
D oor
Opening
60,000
Door
Clos ing
Regression (A Person Walks Through Door)
9 10 11 12 13 14 15 16 17 18 19 20 21 22
Particle Concentrations Across Cleanroom Door
When Door is Opening & Closing
(Initial Condition: Pressurization @ 20 Pa = 0.08 In. )
(Initial Condition: Neutral @ 0 Pa = 0 In. )
Ins ide Cleanroom Door Av erage
Outside Cleanroom Door A ver age
Ins ide Cleanroom Door A ver age
Outside Cleanroom Door A verage
Door
C losing
CRF
= 4.2%
20,000
10,000
0
Particle Concentrations Across Door
3
(Counts / FT )
80,000
Door
Opening
40,000
70,000
Door
Opening
60,000
Door
Closing
50,000
40,000
30,000
20,000
CRF
= 0.3%
10,000
0
9 10 11 12 13 14 15 16 17 18 19 20 21 22
Time (Sec.)
20
Door Opening & Closing W/O People Traffic
Time (Sec.)
80,000
30,000
15
A Person Walks Through Door
Particle Concentrations Across Cleanroom Door
When Door is Opening & Closing
70,000
10
___________________________________
___________________________________
25%
0
Time (Sec.)
60,000
Regression (Door Opening & Closing W/O People Traffic)
CRF
= 0.8%
20,000
10,000
9 10 11 12 13 14 15 16 17 18 19 20 21 22
50,000
(Note: 5 Pa = 0.02 In., Particle Measured @ 0.5 m)
50,000
40,000
30,000
0
0
-5
Initial Pressure Differential Across Door (Pa)
Airborne Particle Contamination Risk Factor (CRF)
Under Various Pressure Differentials Across Cleanroom Door
Outside Cleanr oom Door Average
80,000
40,000
-10
(Initial Condition: Pressurization @ 15 Pa = 0.06 In. )
Outside Cleanroom Door A verage
30,000
5%
9 10 11 12 13 14 15 16 17 18 19 20 21 22
Time (Sec.)
(Initial Condition: Depressurization @ -5 Pa = -0.02 In. )
70,000
10%
Particle Concentrations Across Cleanroom Door
When Door is Opening & Closing
80,000
60,000
15%
-15
0
Time (Sec.)
Inside Cleanroom Door Average
20%
0%
10,000
0
9 10 11 12 13 14 15 16 17 18 19 20 21 22
Particle Concentrations Across Cleanroom Door
When Door is Opening & Closing
9 10 11 12 13 14 15 16 17 18 19 20 21 22
Time (Sec.)
Contamination Risk Factor (CRF, %)
Particle Concentrations Across Door
3
(Counts / FT )
10 11 12 13 14 15 16 17 18 19 20 21 22
Time (Sec.)
Time (Sec.)
Particle Concentrations Across Cleanroom Door
When Door is Opening & Closing
Ins ide Cleanroom Door Av erage
___________________________________
25%
30,000
20,000
Particle Concentrations Across Door
3
(Counts / FT )
(Note: 5 Pa = 0.02 In., Particle Measured @ 0.5 m)
D oor
Closing
50,000
40,000
Contamination Risk Factor (CRF, %)
Particle Concentrations Across Door
3
(Counts / FT )
Particle Concentrations Across Door
3
(Counts / FT )
Door
Clos ing
Particle Concentrations Across Door
3
(Counts / FT )
Outside Cleanroom Door A verage
80,000
D oor
Opening
60,000
50,000
40,000
___________________________________
Airborne Particle Contamination Risk Factor (CRF)
Under Various Pressure Differentials Across Cleanroom Door
(Initial Condition: Pressurization @ 5 Pa = 0.02 In. )
Outside Cleanroom Door A ver age
80,000
70,000
Regression Curve:
-0.1181*PD
CRF= 0.0332e
2
R = 0.9656
(No People Traffic)
20%
___________________________________
15%
Regression Curve:
-0.0703*PD
CRF = 0.0418e
2
R = 0.9129
(With People Traffic)
10%
5%
0%
-15
-10
-5
10
15
20
Initial Pressure Differential Across Door (Pa)
___________________________________
___________________________________
Dynamic Pressurization Control Strategies
Adjustable Pressure Stabilizer
A leakage regulator,
controllable pressure relief
damper across a wall to
maintain a minimum
required pressurization.
When a door is normally
closed, this damper should
stay open and maintain
normal pressure differential;
when the door opens, the
damper shall be
automatically closed either
by spring-loaded or counterweight gravity damper, and
maintain a lower while
acceptable pressure
differential.
___________________________________
___________________________________
___________________________________
___________________________________
Pressure
Stabilizer
___________________________________
___________________________________
___________________________________
Importance
In addition to design engineers and research
scientists, the information presented may also
benefit manufacturers in the fields of:
Air-handling unit control
Lab HVAC control
Prefabricated clean room
Precision environmental test chamber
Smoke management control
Air distribution system
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Pressurization Study
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
Q&A
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________
___________________________________