ThermoCond 19 20 01 - simplified illustration
Air conditioning unit with cross-counterflow
heat exchanger for private swimming pool halls
Automatically selects the
most economical operating mode!
ThermoCond 19
Air volume flow: 1,100 - 3,500 m3/h
At a glance:
Dehumidifies, ventilates
and heats
Corrosion-free heat exchanger
made from polypropylene
Two-stage recuperative
heat recovery
The devices of the ThermoCond 19 series
are multifunctional compact systems for
air conditioning private swimming pool
halls. The design and functionality of all
systems are optimally adapted to your
requirements. The combination of firstclass components with precise control
and regulation systems guarantees
economical operation at all times, while
ensuring the highest degree of comfort air
conditioning. The ThermoCond systems
dehumidify, heat and ventilate the
swimming pool hall, and simultaneously
create good climate and ideal protection
for the material of the building. Additional components such as radiators or
panel heating systems are generally not
required.
Energy-saving EC fans
Constantly regulated recirculation
air heating damper
Further performance parameters and options:
Variable air duct connections
- Filtering the air in any operating mode
- pumped hot water air heater
- sound-optimised plastic impellers
for even quieter operation (from
19 20 01)
- Individually controllable performance
parameters
- Complete unit, ready to connect,
contains all structural elements for air
conditioning swimming pool hall air,
including all control and regulation
fittings
- Intensive quality inspection with
factory test run
Compact design for minimal
space requirements
Integrated control and
regulation system, compatible
with all conventional building
management systems
Optional: operation via
smartphone or tablet
Options
- bypass damper
- water/air temperature
interconnection
- design complies with VDI 6022
- remote maintenance
- and many more
Technical Catalogue v2.02/2015 | Subject to technical modifications. Menerga GmbH | www.menerga.com
17
ThermoCond
private
Indoor swimming pool air conditioning | ThermoCond 19
Indoor swimming pool air conditioning | ThermoCond 19
ThermoCond
private
Functional
description
Swimming pool hall
LPHW
RA
SA
OA
EA
RA
EA
DDC
MODEM
Recirculating Air Operation (heating)
If no requirements are placed on temperature regulation or dehumidification
when the device is in standby mode, the
system operates only in recirculation
mode with reduced air volume flow. The
air circulation in the swimming pool hall is
guaranteed. If heating is required, the return
air is heated up using the heating coil to
achieve the supply air temperature
set-point.
LPHW
RA
18
RA
SA
OA
Dehumidification
using outside air in winter
The swimming pool hall is dehumidified
through the addition of outside air to the
recirculated air volume flow. The
proportion of outside air depends on the
current evaporation of water (and
therefore the occupancy level of the
swimming pool hall), as well as the
outside air humidity. This is continuously
and automatically adjusted. If the waste
heat recovery is not sufficient for
achieving the desired supply air temperature, the supply air is reheated in
the heating coil.
LPHW
EA
EA
RA
RA
SA
OA
Dehumidification
using outside air in summer
In case of rising outside air humidity, the
recirculated air damper is continuously
closing as required. When the outside air
humidity is high, the damper closes completely. The system works at 100% outside air/exhaust air operation through
the heat exchanger.
LPHW
EA
EA
RA
SA
OA
EA
RA
Technical Catalogue v2.02/2015 | Subject to technical modifications. Menerga GmbH | www.menerga.com
EA
ThermoCond
private
Indoor swimming pool air conditioning | ThermoCond 19
ThermoCond Type 19
System dimensions and weights
L
W2
W2
W
W2
OA
SA
W2
80
120
W1
LPHW connection
RA
H1
EA
W2
85
EA
RA
80 120
RA
W2
120
Condensate drainage 25 (DN20)
SA
OA
EA
W1
EA
EA
RA
W1
Unit feet 100 mm
Optional: adjustable feet from 100 to 120 mm
In the case of controls cabinet, folding on
device: cabinet is folded on the front end for
transportation. This reduces the transportation
length by approx. 250 mm.
Cable duct
Return and exhaust air duct connection
possible on top of unit.
Mirror-image design possible.
Unit type
W1
H2
W1
W2
H1
Weight
19 11 01
1,530
570
1,590
350
200
1,370
215
150
150
135
410
19 15 01
1,530
730
1,590
500
200
1,370
215
150
150
135
440
19 20 01
1,690
730
1,910
500
300
1,690
80
105
120
105
540
19 25 01
1,690
890
1,910
600
300
1,690
80
105
120
105
610
19 35 01
1,690 1,210 1,910
920
300
1,690
80
105
120
105
720
For service work, a clearance corresponding to
dimension B is required on the operating side of
the unit. If dimension W is smaller than one metre,
please leave a clearance of one metre.
Please comply with the dimensions for body
size, air duct connections and electrical controls
cabinet.
Partitioning of unit for smaller apertures possible
(at extra cost).
All lengths are given in mm, weights in kg.
Controls cabinet
Unit Type
HxWxD
Position at unit
19 11 01
900 x 480 x 210
SA/RA side
19 15 01
900 x 480 x 210
SA/RA side
19 20 01
900 x 480 x 210
SA/RA side
19 25 01
900 x 480 x 210
SA/RA side
19 35 01
900 x 480 x 210
SA/RA side
1
2
Technical Catalogue v2.02/2015 | Subject to technical modifications. Menerga GmbH | www.menerga.com
Door fitting assembly increase unit width
by 25 mm each operating side
incl. 100 mm unit feet,
incl. 120 mm duct connection
19
Indoor swimming pool air conditioning | ThermoCond 19
ThermoCond
private
Technical specifications and services
Unit Type
Optimum flow rate
Heat recovery efficiency 1
Dehumidification capacity according to VDI 2089
Total electrical power rating
Max. current consumption 2
19 11 01
19 15 01
19 20 01
19 25 01
19 35 01
m/h
1,100
1,500
2,000
2,500
3,500
76
76
79
79
80
kg/h
6.6
9.0
12.1
15.1
21.1
kW
0.87
0.98
1.52
1.73
2.76
3.3
3.3
3.8
3.8
7.6
Operating voltage
3 / N / PE 400 V 50 Hz
Ext. pressure losses
Supply and fresh air channel
Pa
300
300
300
300
300
Return and exhaust air channel
Pa
300
300
300
300
300
Supply air vent
dB(A)
79
81
71
68
76
RA connection
dB(A)
71
70
61
61
64
Outside air vent
dB(A)
66
65
57
55
62
Sound power level
EA connection
dB(A)
71
70
60
59
64
Acoustic pressure at a distance of 1 m from the device 3
dB(A)
61
62
52
50
57
Fan units
Rated motor input for supply air 4
kW
0.51
0.56
0.84
0.96
1.58
Rated motor input for return air 4
kW
0.36
0.42
0.68
0.77
1.18
Rated motor input for supply air recirc mode 4
kW
0.18
0.22
0.37
0.49
0.66
Rated motor input for return air recirc mode 4
kW
0.18
0.22
0.37
0.49
0.66
1|1
1|1
1|1
1|1
1|1
kW
1.0 | 1.0
1.0 | 1.0
1.2 | 1.2
1.2 | 1.2
2.4 | 2.4
SFP category (supply air | return air) recirc mode
Nominal rating supply air | return air
Filtration according to DIN EN 779
Outside air
M5
Return air
M5
LPHW
Heating capacity 5 recirc mode
kW
8.2
11.7
13.9
18.1
25.8
Heating capacity 5, 6 OA-EA operation
kW
9.9
14.2
16.7
21.7
30.7
LPHW
m/h | kPa
0.43 | 3.6
0.62 | 7.9
0.73 | 3.8
0.95 | 6.9
1.34 | 6.4
LPHW valve
m/h | kPa
0.43 | 7.4
0.62 | 15.0
0.73 | 8.6
0.95 | 14.4
1.34 | 11.3
LPHW connection
DN
15
15
20
20
20
LPHW control valve connection
DN
10
10
15
15
20
Condensate drainage
DN
20
20
20
20
20
Floor drain
DN
20
20
20
20
20
Water flow rates and pressure losses 5, 6
Connections
Specifications of technical data relate to the optimum flow rate and return air
condition 30C / 53.7% r.h., outside air condition 15C / 84% r.h. and an altitude
height of zero metres above sea level, unless otherwise specified
1
2
3
4
5
6
depends on operating condition
depends on configuration of measurement and control system/unit
at 250 Hz mid-band frequency
with average filter contamination
FL = 70C, SA 50C
OA = -12C / 90% r.h., 2/3 proportion of air from outside
Please seek approval of technical data and specifications prior to start of the
planning process.
20