DUNPHY COMBUSTION LTD.
Queensway
Rochdale
\England
OL11 2SL
+44 (0) 1706 649217
+44 (0) 1706 655512
www.dunphy.co.uk
DATA SHEET
Model: TG3
Revision Date: March 2013
Output: 450 2950 kW
Revision Number: DS.TG3.16
All models approved to current British and European Standards.
All burners in the T.G. range are of the fan assisted, nozzle mix
type and operation is fully automatic.
All models have been independently tested to the European
Standard BS EN676 Automatic forced draught burners for
gaseous fuels.
CE approval numbers for the TG3 Series burners are:
TG35
CE 86/AQ/269
TG37
CE 86/AQ/270
TG310
CE 86/AQ/271
DS.TG3.16
BURNER DIMENSIONS - HIGH / LOW & ELECTRO / PNEUMATIC
MODULATION - VGD40. GAS VALVE
All dimensions in mm unless otherwise stated.
The minimum standard dimension for 'PROJ' is 230mm. However, it
can be varied to suit application. Requirements should be
stated when unit is ordered.
Dimension E is the average swing radius; this can vary on
non-standard burners.
Burner shown is right-hand hinge; left-hand hinge is an available
option.
Please check the issue number to ensure validity.
DS.TG3.16
BURNER DIMENSIONS - HIGH / LOW & ELECTRO / PNEUMATIC
MODULATION - VGD20.503 GAS VALVE
All dimensions in mm unless otherwise stated.
The minimum standard dimension for 'PROJ' is 230mm. However, it can
be varied to suit application. Requirements should be
stated when unit is ordered.
Dimension E is the average swing radius; this can vary on
non-standard burners.
Burner shown is right-hand hinge; left-hand hinge is an available option.
Please check the issue number to ensure validity.
DS.TG3.16
BURNER DIMENSIONS - ELECTRONIC MODULATION
All dimensions in mm unless otherwise stated.
The minimum standard dimension for 'PROJ' is 230mm. However, it can
be varied to suit application. Requirements should be
stated when unit is ordered.
Dimension E is the average swing radius; this can vary on
non-standard burners.
Burner shown is right-hand hinge; left-hand hinge is an available option.
Please check the issue number to ensure validity.
DS.TG3.16
BURNER RATING GRAPH
DS.TG3.16
BURNER SCHEMATICS - HIGH / LOW & PNEUMATIC MODULATING
Typical Gas Line Schematic for High / Low & Pneumatic Modulating
Burners with Gas Pilot Line
Typical Gas Line Schematic for High / Low & Pneumatic Modulating
Burners without Gas Pilot Line
DS.TG3.16
BURNER SCHEMATICS - ELECTRICAL MODULATING
Typical Gas Line Schematic for Electronic Modulating Burners
without Gas Pilot Line
Typical Gas Line Schematic for Electronic Modulating Burners with
Gas Pilot Line (Single Valve)
DS.TG3.16
Typical Gas Line Schematic for Electronic Modulating Burners with
Gas Pilot Line (Twin Valve)
Typical Gas Line Schematic for Electronic Modulating Burners with
Gas Pilot Line (Twin Valve) and Optional LPG / Propane Connection
DS.TG3.16
STANDARD SPECIFICATION DATA
BURNER
TYPE
Firing Rate kW
GAS VOLUME
(m3/HR) *1
MIN
MAX
MIN
MAX
TG35Z
450
2000
43
192
TG37Z
500
2200
48
211
TG310Y
600
2950
77
283
FIRING MODE OPTIONS
High / Low
Electro / Pneumatic
Modulation
Electronic
Modulation*2
Motor kW
Voltage
Hz
Ph
Running
Current
Starting
Current
3.0
380-420
50
9 Amp
53 Amp
4.0
380-420
50
11 Amp
79 Amp
5.5
380-420
50
16 Amp
36 Amp
*1 Based on Nat. Gas C.V 10.4 kW/m3
*2 - Fitted with a Ratiotronic 6000 system
COMBUSTION HEAD
ULTRA LOW NOx BURNERS
The Dunphy dual fuel combustion head incorporates a
two-stage fuel/air mixing system which eliminates low
frequency resonance and allows maximum combustion
efficiency with minimum emission levels.
All Dunphy T-Series burners are fitted with low NOx
combustion heads as standard equipment.
As an optional extra all burners in this range can be fitted
with an internal flue gas recirculation system to achieve
ultra low NOx emissions.
This system combined with smooth ignition and extreme
reliability make Dunphy combustion equipment the most
sensible choice for all heating and process applications.
Dunphy Combustion Ltd have a policy of continuous
development and reserve the right to change prices and
specifications without prior notice.
Dunphy Combustion Ltd. has a policy of continuous development and reserve the right to change prices and specifications without prior notice