Liquid Sulphur
Temperature
145.0
Pressure
0.0000
kPag
Mass Flow
2762.5
kg/h
Thermal Conductivity
0.2440
W/m-K
Molecular Weight
32.07
Mass Density
1752
Master Comp Mole Frac (S_Liq_150)
Assume delta T heat loss for stream is 5 DegC
Stream Heat Loss Engy
Heat Flow
kg/m3
5.690
kW
Temperature
Pressure
1.0000
140.0
0.0000
C
kPag
Stream Heat Loss
Engy
Liquid
Sulphur
1
Stream
Heat
Loss
Melting point for liquid sulphur is 115.21 DegC at atmosphric conditions.
Use tank temperature of 145 DegC with margin over melting point.
1.0000
160.1
Pressure
517.0
kPag
Mass Flow
61.82
kg/h
LP
Steam
Supply
Pressure Drop
Heat Flow
36.24900
Inside Diameter (Inside Diameter_1)
kW
Outside Diameter (Outside Diameter_1)
Tank
Heating
Coil
LP Steam
Condensate
From tank heat loss calculations use a duty of
36.249 kW for 1" insulation and no wind.
1" Pipe
#1
psi
100.0
ft
0.9570
in
1.315
in
1" Pipe
#2
Tank Heating Coil
Engy
1.0000
Operating pressure of LP steam reported at 517 kPag.
Assume supply is saturated.
0.0055
Pipe Length (Pipe Length_1)
Tank Heating Coil Engy
Temperature
Master Comp Mole Frac (H2O)
1" Pipe #2
Tank heat loss of 36249 W
LP Steam Supply
Vapour Fraction
3
LP Steam Condensate
Vapour Fraction
0.0000
Temperature
158.7
Pressure
496.3
kPag
Molar Flow
1947
m3/d_(gas)
1" Pipe #2
Engy
Recommend insulating tank with 64 mm (2.5 inches) for heat
conservation.
2
1" Pipe #1
Engy
1" Pipe #1
Pressure Drop
Pipe Length (Pipe Length_1)
Inside Diameter (Inside Diameter_1)
Outside Diameter (Outside Diameter_1)
1.011
psi
100.0
ft
0.9570
in
1.315
in
Sat Oct 22 16:31:32
Case:
2016
C:\Users\Greg\Documents\Gregs Sherritt Files\Varadero Sulphur Plant Refurbishment\SulphurTank Heat Coil\Sizing to Tank Heating Coil.hsc
Flowsheet: Case (Main)