1 BACnet Gateway---CCM08
Step1: Wiring with Central controller and indoor/outdoor units
Refrigerant System: V3V4D3D4
RS485 indoor units
Max.64 IDUs
CCM03 controller
RS485 indoor units
Max.8 refrigerant
systems
CCM02 controller
Refrigerant System: Full V4+
indoor units
MAX:64 indoor units
CCM03
MAX:8 systems
CCM02
indoor units
Step2: Wiring with gateway and central controllers
Useful port, Connect to PC
4*Port RS485,
Port reserved, each port
No useful connect one
CCM(indoor or
outdoor) and
corresponding
indoor or
outdoor units
Each gateway has a initial IP address, this one
is:192.168.208.231,Pls keep it
Power
Socket
Power
Switch
Take a PC, Connect to gateway
Ex. In this case, CCM08 connect one CCM03 and 8 IDUs
Step3: Modify IP address of PC to connect gateway
Modify the PC ip
address
to:192.168.208.232
under the same
address range
with CCM08.
Turn on IEinput 192.168.208.231 in the address bar
Initial user nameadmin
Initial PW 12345
After that, the web control interface appeared
In the web control interface, we can control and monitor the A/C
Step4: Connect the gateway to LAN
Firstly, Check the IP address of existed LAN
IP address of this PC is:
10.46.1.49, pls keep it
Next, Change the ip address of CCM08
Cannot choose
this item !!!
No useful, Dont
care about it
Change the ip address under the same address range. Pls ask
the IT administrator which ip address is available. In this case,
ip address of CCM08 have been changed to 10.46.1.2
After modified, Click Rebotbotton
Connect CCM08 to LAN by Hub
On any PC of LAN, input 10.46.1.2 on IE address bar, get
into the web control interface, So CCM08 has been
connected to LAN.
Additional: CCM08 cooperate with 3rd network software
Ex. In this case, IP address of PC is 10.46.1.253, ip address of
CCM08 is 10.46.1.251. There are 10 IDUs(Network address range:
(0054~0063), 1 ODU(Network address: 1800)
Turn on ACServer
1.This is PC ip address 2.In any case,
here have to be
19781
3.This is CCM08 ip
address range.
Max.256 CCM08 can 4.In any case,
be connected to LAN here have to be
19780
6.All existed CCM08 will 5.Finish all
be found. In this case, setting above,
only one. Click Scan
After configuration, Searching the
devices
After search, back to software
main interface