SUMMARY SHEET FOR STACK ADEQUACY Pressure
1 Overfire draft: 0.5000
(Given by manufacturer)
2 Boiler draft loss: 0.3000
(Given by manufacturer)
3 Total friction loss due to straight run of ducts: 0.0029
(Pages: 4,5,6)
4 Total friction loss due to bends: 0.2029
(Pages: 7,8)
5 Total pressure drops or gains due to area changes: 0.0000
(Pages: 9)
6 Other friction losses:
Item Qty.: friction loss (in w.g.)
Dampers: 1 0.0088
Entry Port: 1 0.1 0.1000
7 Stack Draft Effect: 0.2823
(Pages: 3)
TOTAL GAINS ( Sum of positive pressure differentials) 0.7823
TOTAL LOSSES ( Sum of negative pressure differentials) 0.6146
FACTOR OF SAFETY (note: e.g. 10% is to be entered as 1.1) 1.1
8 Net available draft:
(TOTAL GAINS) - (TOTAL LOSSES) x (FACTOR OF SAFETY): 0.1062
If line 8 is positive the stack is adequate.
If line 8 is negative and an I.D. fan is to be used to convert net
loss to equivalent loss at 70 deg. F and size I.D. fan accordingly;
9 Conclusion:
The Stack is adequate
Stack Adequacy 01/23/2018
[Link] 2 of 25
Pressure
in. w.c.
in. w.c.
in. w.c.
in. w.c.
in. w.c.
in. w.c.
in. w.c.
in. w.c.
in. w.c.
in. w.c.
in. w.c.
Stack Adequacy 01/23/2018
[Link] 3 of 25
Volume flow rate of flue gases Calculation (Method 1)
Assuming that one(1) cubic feet of 60 °F flue gas is produced for every 95 Btu of gross input
(Reference: Flow of flue gases, page 155, North American Combustion Handbook, 1965)
( assumed that the flue gas and air density are the same )
Boiler Horsepower 265 BHP
Total Btu of gross input: 8,857 MBH at 60 °F or 520
(data from vendor) 8,857,000 Btu/hr per one(1) boiler
Formula Constant 1 177,500,000
Assumed flue gas temp. where breeching joins chimney (Tbc): 430 °F
Assumed flue gas temp. at top of stack (Ts): 370 °F
Average stack flue gas temperature (Te): 400 °F
Flue gas volume rate (1) Boiler: 43 cfs
2,575 cfm
Number of Boilers 4
Total Flue gas volume rate (4) Boilers 172 cfs
10,299 cfm
Volume flow rate of flue gases Calculation (Method 2)
Using equation from page (ii) GK calculation notes)
Excess air 30 %
Average stack flue gas temperature (Te): 400 °F
(From Calculation Method 1)
Oil Fired Rate per (1) Boiler, light oil, EASCO Model 199 60 GPH
Number of Boilers: 4
After applying Formula in 3.a, Page (ii), Gary Krishnan Hand out copy, we found :
Flue gas volume rate, per one(1) boiler 3,083 cfm
Flue gas volume rate, per two(4) boilers 12,332.40 cfm
Volume flow rate of flue gases Calculation (Method 3)
Flue CFM 01/23/2018
[Link] 4 of 25
Based on GPH and CFM rule of thumb
(1) GPH is equivalent to: Flue Gas 53 cfm
Flue gas volume rate, per one(1) boiler 3,180 cfm
Flue gas volume rate, per two(4) boilers 12,720 cfm
USE: 3,250 cfm 1 boiler
13,000 cfm 4 boilers
Flue CFM 01/23/2018
[Link] 5 of 25
°R
Flue CFM 01/23/2018
[Link] 6 of 25
Flue CFM 01/23/2018
[Link] 7 of 25
Chimney Height
Refer to dwg. Elevations, Original Design, A-8, Sheet 8, Nov. 6,1956
Elev. (ft)
Finished Cellar Fl 44' - 0"
Bottom of Steel
Breeching 60'-0"
Finished First Fl 66' - 0" 6
Finished Second Fl
Finished Third Fl
Finished Fourth Fl
Top of Roof Slab
Tof of Penthouse Roof Slab 121'-4"
Top of Brick Chimney 124' - 4" 58.33 assumed
Chimney total height 64.33
Theoretical Chimney Draft Effect
Using equations from page (iii) GK calculation notes)
Formula Constant (C1) 2.96
Formula Constant (C2) 0.000388
Formula Constant (C3) 0.00126
Formula Constant (C4) 0.031
Formula Constant (C5) 0.029
Height of Chimney (H) 64.33
Barometric pressure (Bo) 29.92
Weight of air at 0°F and sea level pressure (Wo) 0.0863
Weight of stack gases at 0°F and sea level pressure (Wc) 0.09
Absolute temperature of outside air in worst condition (To) 555
Average stack flue gas temperature (Tc): 860
Weight of gases generated by boiler (W) 9.528
Coefficient of friction (F) 0.016
Stack Inside diameter (D)
Cross sectional dimensions of stack (W x H) Width: 60
Height: 60
Stack Effct Calc 01/23/2018
[Link] 8 of 25
Rectangular Stack Draft Effect (Dr) 0.282
Stack Effct Calc 01/23/2018
[Link] 9 of 25
ft
in. Hg
lbs/cf
lbs/cf
°R
°R
lbs/sec
in 5.00 ft
in 5.00 ft
Stack Effct Calc 01/23/2018
[Link] 10 of 25
in. w.c.
Stack Effct Calc 01/23/2018
[Link] 11 of 25
Breeching Straight Runs Friction Losses
Straight Run location: B-D
Type of duct: Rectangular 30 in Width
30 in Height
Breeching equivalent
diameter: 32.79 in Duct Design, Chapter 14, Table 14-2, SMACNA
Straight Duct Length 6.50 ft
Exhaust gas flow 3250 cfm One boiler
Flue velocity 520 fpm
Straight Run Friction Losses:
Friction Loss 0.015 in. w.c. /100ft from Fig.C-9, Calculation notes, GK
Correction for temperature 0.74 at 400 deg F from Fig.C-5, Calculation notes, GK
Correction for roughness 0.97 medium smooth from Fig.C-3C, Calculation notes, GK
Corrected Friction loss 0.011 in. w.c. /100ft
Friction Loss: 0.0007 in. w.c.
Straight Run location: C
Type of duct: Rectangular 30 in Width
30 in Height
Breeching equivalent
diameter: 32.79 ft Duct Design, Chapter 14, Table 14-2, SMACNA
Straight Duct Length 5.42 ft
Exhaust gas flow 3250 cfm One boiler
Flue velocity 520 fpm
Straight Run Friction Losses:
Friction Loss 0.015 in. w.c. /100ft from Fig.C-9, Calculation notes, GK
Correction for temperature 0.74 at 400 deg F from Fig.C-5, Calculation notes, GK
Correction for roughness 0.98 medium smooth from Fig.C-3C, Calculation notes, GK
Corrected Friction loss 0.011 in. w.c. /100ft
Friction Loss: 0.0006 in. w.c.
Straight Run Losses 01/23/2018
[Link] 12 of 25
Straight Run Losses 01/23/2018
[Link] 13 of 25
Straight Run location: E
Type of duct: Rectangular 26 in Width
34 in Height
Breeching equivalent
diameter: 32.43 in Duct Design, Chapter 14, Table 14-2, SMACNA
Straight Duct Length 6.50 ft
Exhaust gas flow 3250 cfm One boiler
Flue velocity 529 fpm
Straight Run Friction Losses:
Friction Loss 0.017 in. w.c. /100ft from Fig.C-9, Calculation notes, GK
Correction for temperature 0.7 at 400 deg F from Fig.C-5, Calculation notes, GK
Correction for roughness 0.98 medium smooth from Fig.C-3C, Calculation notes, GK
Corrected Friction loss 0.012 in. w.c. /100ft
Friction Loss: 0.001 in. w.c.
Straight Run location: G
Type of duct: Rectangular 32 in Width
32 in Height
Breeching equivalent
diameter: 34.98 in Duct Duct Design, Chapter 14, Table 14-2, SMACNA
Straight Duct Length 10.00 ft
Exhaust gas flow 3250 cfm One boiler
Flue velocity 457 fpm
Straight Run Friction Losses:
Friction Loss 0.01 in. w.c. /100ft from Fig.C-9, Calculation notes, GK
Correction for temperature 0.7 at 400 deg F from Fig.C-5, Calculation notes, GK
Correction for roughness 0.98 medium smooth from Fig.C-3C, Calculation notes, GK
Corrected Friction loss 0.007 in. w.c. /100ft
Friction Loss: 0.0007 in. w.c.
Straight Run Losses 01/23/2018
[Link] 14 of 25
Straight Run Losses 01/23/2018
[Link] 15 of 25
Straight Run location: G-H
Type of duct: Rectangular 50 in Width
28 in Height
Breeching equivalent
diameter: 40.48 in Duct Duct Design, Chapter 14, Table 14-2, SMACNA
Straight Duct Length 2.50 ft
Exhaust gas flow 13000 cfm Two boilers
Equivalent diameter 40.48 in 3.37 ft
Flue velocity 1455 fpm
Straight Run Friction Losses:
Friction Loss 0.01 in. w.c. /100ft from Fig.C-9, Calculation notes, GK
Correction for temperature 0.7 at 400 deg F from Fig.C-5, Calculation notes, GK
Correction for roughness 0.98 medium smooth from Fig.C-3C, Calculation notes, GK
Corrected Friction loss 0.007 in. w.c. /100ft
Friction Loss: 0.0002 in. w.c.
Total Straight Run Friction Losses: 0.0029 in. w.c.
Straight Run Losses 01/23/2018
[Link] 16 of 25
Bend Losses in Breeching
Bend location: B
Type of bend: Rectangular W= 30 in H= 30 in
Breeching equivalent
diameter: 32.79 in
R (ft) W (ft) H (ft) R/W H/W L/W L (ft)
Rectangular breeching: 2.50 2.50 0.000 1
Exhaust gas flow 3250 cfm One Boiler
Equivalent diameter 33 in 2.73 ft
Flue velocity 554 fpm
Bend Loss:
Elbow Loss Coefficent 0.1 from Table 3, Calculation notes, GK
Velocity Pressure 0.019 in. w.c.
Pressure Loss: 0.002 in. w.c.
Bend location: C
Type of bend: Rectangular W= 34 in H= 26 in
Breeching equivalent
diameter: 32.43 in
R (ft) W (ft) H (ft) R/W H/W L/W L (ft)
Rectangular breeching: 2.83 2.17 0.000 0.764706 0.176471 0.5
Exhaust gas flow 3200 cfm One Boiler
Equivalent diameter 32.43 in 2.70 ft
Flue velocity 558 fpm
Bend Loss:
Elbow Loss Coefficent 1.104 from Table CR3-8, Pag 200, Duct Fitting
Loss Coefficient Tables, ASHRAE
Velocity Pressure 0.019 in. w.c.
Pressure Loss: 0.021 in. w.c.
Bend Losses 01/23/2018
[Link] 17 of 25
Bend location: F-G
Type of bend: Rectangular W= 50 in H= 28 in
Breeching equivalent
diameter: 40.48 in
R (ft) W (ft) H (ft) H/W (ft) R/W (ft)
Rectangular breeching: 5.41 4.17 2.33 0.6 1.30
Exhaust gas flow 13000 cfm Two Boilers
Equivalent diameter 40.48 in 3.37 ft
Flue velocity 1455 fpm
Bend Loss:
Elbow Loss Coefficent 0.13 from Table 3, Calculation notes, GK
(Rectangular section)
Velocity Pressure 0.132 in. w.c.
Pressure Loss: 0.017 in. w.c.
Bend location: H
Type of bend: Rectangular W= 50 in H= 28 in
Breeching equivalent
diameter: 40.48 in
R (ft) W (ft) H (ft) H/W (ft) R/W (ft)
Rectangular breeching: 5.41 4.17 2.33 0.6 1.30
Exhaust gas flow 13000 cfm Two Boilers
Equivalent diameter 40.48 in 3.37 ft
Flue velocity 1455 fpm
Bend Loss:
Elbow Loss Coefficent 1.23 from Table CR3-6, Pag 198, Duct Fitting
Loss Coefficient Tables, ASHRAE
Velocity Pressure 0.132 in. w.c.
Pressure Loss: 0.162 in. w.c.
Total Bend Losses: 0.203 in. w.c.
Bend Losses 01/23/2018
[Link] 18 of 25
Transition and Area change Losses in Breeching
Fitting location: A-B
Type : Transition Wo = 46 in Ho = 20
W1 = 30 in H1 = 30
L= 48 in
Equivalent diameter Do: 34.23 in 2.85 ft
Equivalent diameter D1: 33.85 in 2.82 ft
Rectangular Transition: R (ft) Wo (ft) Ho (ft) W1-Wo (ft) L(ft) Deg.
3.83 1.67 1.333 4 18.4
Exhaust gas flow 3250 cfm One Boiler
Flue velocity at Do 509 fpm
Flue velocity at D1 520 fpm
Transition Friction Losses:
Loss Coefficent 0 from Table 4, Calculation notes, GK
(Gradual Contraction)
Velocity Pressure 0.017 in. w.c.
(at D1)
Pressure Loss: 0.000 in. w.c.
Total Transition Losses: 0.0000 in. w.c.
Trans. Loss Calc 01/23/2018
[Link] 19 of 25
Trans. Loss Calc 01/23/2018
[Link] 20 of 25
in
in
on notes, GK
Trans. Loss Calc 01/23/2018
[Link] 21 of 25
Trans. Loss Calc 01/23/2018
Dampers Losses in Breeching
Fitting location: C
Type : Rect Duct Wo = 30 in Ho = 30
Exhaust gas flow 3250 cfm One Boiler
Flue velocity at Duct 520 fpm
Damper Friction Loss
Using ASHRAE Duct Fitting Loss Coefficient Table CR9-4, for Damper, Opposed Blades (Brown 1957)
assuming: (N) Number of Damper Blades: 6
(W) Duct dimension parallel to blades axis, in 30
(H) Duct Height, in. 30
L Sum of Damper Blade length, in. (N x W)
R Perimeter of Duct, in (2 x (H + W)
L/R: 1.5
Blades Angle: 0 Degree
Loss Coefficent 0.52 from Table CR9-4
Velocity Pressure 0.017 in. w.c.
Pressure Loss: 0.009 in. w.c.
Total Damper Losses: 0.0088 in. w.c.
in