Check List: Sl. No. Activity OK N/A Remarks NOT OK

The document is a checklist for testing the functionality of an FM 200 fire suppression system. It lists a series of steps to simulate alarm scenarios and ensure the correct components activate in the proper sequence. This includes checking that detectors trigger first and second stage alarms, the control panel initiates a pre-discharge timer, the master cylinder releases gas within 10 seconds or the standby cylinder activates, and the abort switch and manual release function properly. The checklist is used to verify the control panel and detection system trigger the suppression of gas as designed in emergency situations.

Uploaded by

JAIMANIKANDA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
601 views2 pages

Check List: Sl. No. Activity OK N/A Remarks NOT OK

The document is a checklist for testing the functionality of an FM 200 fire suppression system. It lists a series of steps to simulate alarm scenarios and ensure the correct components activate in the proper sequence. This includes checking that detectors trigger first and second stage alarms, the control panel initiates a pre-discharge timer, the master cylinder releases gas within 10 seconds or the standby cylinder activates, and the abort switch and manual release function properly. The checklist is used to verify the control panel and detection system trigger the suppression of gas as designed in emergency situations.

Uploaded by

JAIMANIKANDA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd

CHECK LIST

TESTING & COMMISSIONING OF


FM 200 SYSTEM- FUNCTIONAL TEST

NOT
SL. NO. ACTIVITY OK N/A REMARKS
OK

IF FM 200 PANEL IS IN AUTO MODE

WHEN ONE OF THE TWO DETECTOR ZONES OPERATED


1
WITHIN FM200 PROTECTED AREA
a CHECK THE FIRST STAGE ALARM BELL/ STROBE HAS OPERATED
b CHECK SMOKE DETECTOR SIGNAL LED HAS OPERATED
c CHECK INTERNAL PANEL BUZZER HAS OPERATED

WHEN SECOND DETECTOR ZONES OPERATED WITHIN


2
FM200 PROTECTED AREA
CHECK THE PANEL INITIATES A PRE-DISCHARGE AUDIABLE/ VISUAL
a ALARM (INTERMITTENT TONE ALARM)/ (DISCHARGE TIME 60 SECONDS
STARTS)
b CHECK SMOKE DETECTOR SIGNAL LED HAS OPERATED
c CHECK INTERNAL PANEL BUZZER HAS OPERATED

3 ONCE THE TIMER HAS ELAPSED

a CHECK THE PANEL SENDS A GAS RELEASE SIGNAL TO THE


ELECTRICAL ACTUATOR ON THE MASTER CYLINDER

IF GAS NOT RELEASED FROM MASTER CYLINDER WITHIN


4
10 SECONDS

a CHECK THE PANEL SENDS A GAS RELEASE SIGNAL TO THE STAND BY


CYLINDER
CHECK LIST
TESTING & COMMISSIONING OF
FM 200 SYSTEM- FUNCTIONAL TEST

NOT
SL. NO. ACTIVITY OK N/A REMARKS
OK

5 WHEN FM200 PANELS ABORT SWITCH ACTIVATED

a SIMULATE ALARM IN TWO DETECTOR ZONES

b KEEP THE ABORT SWITCH PRESSED & CHECK THE ELECTRICAL


ACTUATOR HAS NOT ENERGISED
ON RELEASE OF ABORT SWITCH, CHECK THE ELECTRICAL ACTUATOR
c
HAS ENERGISED AFTER 60 SECONDS

6 SYSTEM ACTUATED USING MANUAL RELEASE STATION

a CHECH THE MANUAL RELEASE STATION INDICATION HAS DISPLAYED IN


THE PANEL
b CHECK THE ALARM BELL/ STROBE HAS ENERGISED

c CHECK THE ELECTRICAL ACTUATOR HAS ENERGISED AFTER 30


SECONDS