CHECK LIST
TESTING & COMMISSIONING OF
FM 200 SYSTEM- FUNCTIONAL TEST
NOT
SL. NO. ACTIVITY OK N/A REMARKS
OK
IF FM 200 PANEL IS IN AUTO MODE
WHEN ONE OF THE TWO DETECTOR ZONES OPERATED
1
WITHIN FM200 PROTECTED AREA
a CHECK THE FIRST STAGE ALARM BELL/ STROBE HAS OPERATED
b CHECK SMOKE DETECTOR SIGNAL LED HAS OPERATED
c CHECK INTERNAL PANEL BUZZER HAS OPERATED
WHEN SECOND DETECTOR ZONES OPERATED WITHIN
2
FM200 PROTECTED AREA
CHECK THE PANEL INITIATES A PRE-DISCHARGE AUDIABLE/ VISUAL
a ALARM (INTERMITTENT TONE ALARM)/ (DISCHARGE TIME 60 SECONDS
STARTS)
b CHECK SMOKE DETECTOR SIGNAL LED HAS OPERATED
c CHECK INTERNAL PANEL BUZZER HAS OPERATED
3 ONCE THE TIMER HAS ELAPSED
a CHECK THE PANEL SENDS A GAS RELEASE SIGNAL TO THE
ELECTRICAL ACTUATOR ON THE MASTER CYLINDER
IF GAS NOT RELEASED FROM MASTER CYLINDER WITHIN
4
10 SECONDS
a CHECK THE PANEL SENDS A GAS RELEASE SIGNAL TO THE STAND BY
CYLINDER
CHECK LIST
TESTING & COMMISSIONING OF
FM 200 SYSTEM- FUNCTIONAL TEST
NOT
SL. NO. ACTIVITY OK N/A REMARKS
OK
5 WHEN FM200 PANELS ABORT SWITCH ACTIVATED
a SIMULATE ALARM IN TWO DETECTOR ZONES
b KEEP THE ABORT SWITCH PRESSED & CHECK THE ELECTRICAL
ACTUATOR HAS NOT ENERGISED
ON RELEASE OF ABORT SWITCH, CHECK THE ELECTRICAL ACTUATOR
c
HAS ENERGISED AFTER 60 SECONDS
6 SYSTEM ACTUATED USING MANUAL RELEASE STATION
a CHECH THE MANUAL RELEASE STATION INDICATION HAS DISPLAYED IN
THE PANEL
b CHECK THE ALARM BELL/ STROBE HAS ENERGISED
c CHECK THE ELECTRICAL ACTUATOR HAS ENERGISED AFTER 30
SECONDS