PVC Building Wire Specs

This document provides information on PVC building wires. It lists technical specifications for NYM cables including rated voltage, temperature range, bending radius, fire properties, and applications. Tables show available wire configurations with the number of cores, cross sectional area, outer diameter, weight, and standard lengths. PVC building wires are suitable for fixed installation in dry and damp indoor premises, but not for outdoor or direct buried applications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
296 views2 pages

PVC Building Wire Specs

This document provides information on PVC building wires. It lists technical specifications for NYM cables including rated voltage, temperature range, bending radius, fire properties, and applications. Tables show available wire configurations with the number of cores, cross sectional area, outer diameter, weight, and standard lengths. PVC building wires are suitable for fixed installation in dry and damp indoor premises, but not for outdoor or direct buried applications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

PVC BUILDING WIRES

NYM
Installation cable

DESIGN TECHNICAL DATA

Standard:
DIN VDE 0250-204

Rated voltage:
300/500 V

Test voltage:
2 kV/50 Hz
4 3 2 1
Temperature range:
laying temperature: min. +5 °C
1| Copper conductor, round solid (RE) resp. round stranded (RM) operating temperature: –40 °C up to +70 °C
2| Core insulation (PVC) conductor temperature: max. +70 °C
3| Inner covering (EPDM) short-circuit temperature: max. +160 °C/5 s
4| Sheath (PVC grey) Bending radius (min.):
4 x ∅ of cable

Core identification:
HD 308 S2

Fire properties:
APPLICATION flame retardant:
EN 60332-1-2
For fixed installation in dry and damp premises. Not suitable
Certificate:
for unprotected installation in the open air or directly in tamped GOST-R Russia
concrete.

Number of cores x Max. conductor Outer diameter Total weight Standard lengths/
nominal cross section resistance (mm) ca. (kg/km) ca. packing
(mm²) (Ω/km) (m)
NYM
2 x 1.5 RE 12.100 8.5 115 100 R, 500 Sp
3 x 1.5 RE 12.100 8.9 130 100 R, 500 Sp
4 x 1.5 RE 12.100 9.5 170 100 R, 500 Sp
5 x 1.5 RE 12.100 10.2 180 100 R, 500 Sp
7 x 1.5 RE 12.100 11.0 235 1,000 D
2 x 2.5 RE 7.410 9.7 160 100 R, 500 Sp
3 x 2.5 RE 7.410 10.2 195 100 R, 500 Sp
4 x 2.5 RE 7.410 11.0 225 100 R, 500 Sp
5 x 2.5 RE 7.410 11.9 265 100 R, 500 Sp
7 x 2.5 RE 7.410 12.8 335 1,000 D
2 x 4 RE 4.610 11.1 220 1,000 D
3 x 4 RE 4.610 11.7 265 1,000 D
4 x 4 RE 4.610 13.0 330 1,000 D
5 x 4 RE 4.610 14.5 405 1,000 D
2 x 6 RE 3.080 12.1 215 1,000 D
3 x 6 RE 3.080 13.1 350 1,000 D
4 x 6 RE 3.080 14.6 445 1,000 D
5 x 6 RE 3.080 15.8 525 1,000 D

22
PVC BUILDING WIRES

PRAKAB PRAŽSKÁ KABELOVNA

NYM

Number of cores x Max. conductor Outer diameter Total weight Standard lengths/
nominal cross section resistance (mm) ca. (kg/km) ca. packing
(mm²) (Ω/km) (m) 2
NYM
2 x 10 RE 1.830 15.4 450 1,000 D
3 x 10 RE 1.830 16.3 550 1,000 D
4 x 10 RE 1.830 17.7 670 1,000 D
5 x 10 RE 1.830 19.3 800 1,000 D
2 x 16 RM 1.150 17.8 645 1,000 D
3 x 16 RM 1.150 19.3 815 1,000 D
4 x 16 RM 1.150 20.9 1,050 1,000 D
5 x 16 RM 1.150 23.3 1,280 1,000 D
2 x 25 RM 0.727 21.9 960 1,000 D
3 x 25 RM 0.727 23.2 1,210 1,000 D
4 x 25 RM 0.727 25.3 1,530 1,000 D
5 x 25 RM 0.727 28.1 1,820 1,000 D
2 x 35 RM 0.524 24.8 1,270 1,000 D
3 x 35 RM 0.524 26.3 1,590 1,000 D
4 x 35 RM 0.524 28.7 1,970 1,000 D
5 x 35 RM 0.524 31.5 2,400 1,000 D

Subject to technical changes.