Power Factor Fundamentals
What we will learn:
l Most Industrial loads require both Real power and
Reactive power to produce useful work
l You pay for BOTH types of power
l Capacitors can supply the REACTIVE power thus
the utility doesn’t need to
l Capacitors save you money!
PqcA2.ppt 2
Why Apply PFC’s?
l Power Factor Correction Saves Money!
» Reduces Power Bills
» Reduces I2R losses in conductors
» Reduces loading on transformers
» Improves voltage drop
PqcA2.ppt 3
What is PF ?
l Introduction:
» Most plant loads are Inductive and require a magnetic field to
operate:
– Motors
– Transformers
– Florescent lighting
» The magnetic field is necessary, but produces no useful work
» The utility must supply the power to produce the magnetic field
and the power to produce the useful work: You pay for all of it!
» These two types of current are the ACTIVE and REACTIVE
components
PqcA2.ppt 4
The Basics:
The Power Triangle:
You pay for fuel for the VERTICAL
portion of flight, as well as the fuel
for the HORIZONTAL portion of flight.
Non-
Working
(Reactive)
Power
Working (Active) Power
PqcA2.ppt 5
The Power Triangle:
l Similarly, motors require REACTIVE power to set up the
magnetic field while the ACTIVE power produces the useful
work (shaft horsepower). Total Power is the vector sum of
the two & represents what you pay for:
Active Power (kW): Produces Useful Work
f Reactive Power (kVAR)
Sets up Magnetic Fields
Total Power (kVA)
What you Pay For!
PqcA2.ppt 6
The Power Triangle:
• Power Factor is the ratio of Active Power to Total
Power:
Power Factor = Active (Real) Power
Total Power
Active Power (kW)
= kW
f Reactive
Power kVA
Total Power (kVA) = Cosine (q)
l Power Factor is a measure of efficiency (Output/Input)
PqcA2.ppt 7
Why do we Install Capacitors?
l Capacitors supply, for free, the reactive energy required by
inductive loads.
» You only have to pay for the capacitor !
» Since the utility doesn’t supply it (kVAR), you don’t pay for it!
M M
Utility Supplies Capacitor Supplies
Reactive Current Reactive Current
PqcA2.ppt 8
Other Benefits:
l Released system capacity:
» The effect of PF on current drawn is shown below:
kW kVAR kW
100 100 100 kW
kVAR
75 100
kVA = 141 kVA = 125 kVA = 100
PF = 70% PF = 80% PF = 100%
q Decreasing size of conductors required
to carry the same 100kW load at P.F.
ranging from 70% to 100%
PqcA2.ppt 9
Other Benefits:
l Reduced Power Losses:
» As current flows through conductors, the conductors
heat. This heating is power loss
» Power loss is proportional to current squared (PLoss=I2
R)
» Current is proportional to P.F.:
» Conductor loss can account for as much as 2-5% of
total load
l Capacitors can reduce losses by 1-2% of the total
load
% Loss Reduction = 100 x 1- (Original P.F.)2
(Desired P.F.)2
PqcA2.ppt 10
Other Benefits:
l Voltage Improvement:
» When capacitors are added, voltage will increase
» Typically only a few percent
– Not a significant economic or system benefit
! Severe over-correction (P.F.>1) will cause a voltage
rise that can damage insulation & equipment; or result
in utility surcharges!
– Usually a result of large fixed capacitors at mains
% Voltage Rise = Capacitor kVAR x XFMR %Z
XFMR kVA
PqcA2.ppt 11
Summary of Benefits:
l Reduced Power Costs:
» Since Capacitors supply reactive power, you
don’t pay the utility for it
» You can calculate the savings
l Off-load transformers
» Defer buying a larger transformer when adding
loads
l Reduce voltage drop at loads
» Only if capacitors are applied at loads
» (minimal benefit at best)
PqcA2.ppt 12
A2
What we learned..
l Most Industrial loads (i.e. motors)are Inductive and draw
REACTIVE power
l The Utility supplies this energy therefore you pay for it
l Power Factor Capacitors supply REACTIVE energy thus
the utility doesn’t need to
l Power Factor Capacitors save money
l There are other benefits to correcting power factor,
» reduced heating in cables
» reduced heating in transformer(s)
» frees up system capacity
PqcA2.ppt 13
A2