ARP Users Manual E200-T7A
ARP Users Manual E200-T7A
Users manual
Users manual
Users manual
Table of Contents
1 INTRODUCTION 3
1.1 System description 3
1.2 Plant design 3
1.3 Control Components 3
2 PICTURE HIERARCHY 10
2.1 Menu structure 10
2.2 Main menu 11
2.3 Plant overview 13
2.4 Compressor control 18
2.5 AHU control 26
2.6 AHU detail view 35
2.7 Operation setup 57
2.8 Configuration 63
3 PI REGULATOR FUNCTION 79
4 ALARM LIST 80
5 WORD LIST 82
Johnson Controls
Marine Copyright
Christian X`s Vej 201, 8270 Højbjerg, Denmark Johnson Controls
Phone: +45 87 36 35 00 - Fax: +45 87 36 35 01
www.johnsoncontrols.dk - [email protected] All Rights Reserved
Table of Contents Marine Controls
Revision: 2.0 · Updated:10-06-2014 Author: Emil Aurvig Svendsen · Owner: Emil Aurvig Svendsen
Project : Air-condition Refrigeration Plant E200-T7A Page 2 of 83
Users manual
1 INTRODUCTION
All the values on the display pictures are only examples and cannot be used as actual values.
Not all functions, shown in this manual, are available on all plants.
Additional functions that may have been added to a specific plant, are placed in the “ 7 Additional functions”
part.
• Compressor control.
• AHU fan control.
• AHU heating regulation.
• AHU cooling regulation.
• Expansion valve control.
• AHU re-heating regulation.
• AHU Exhaust fan control.
• AHU Enthalpy exchanger control.
• Outdoor compensation.
• Humidity regulation.
• Alarm system.
• Cross connected control.
PLC
A FX3U PLC and a MAC T7A operator panel control the air-condition plant.
The inputs on the PLC are both digital and analogue.
All outputs on the PLC are digital.
On the PLC there are LEDs indicating the status of the PLC inputs and outputs.
Four LEDs on the PLC front indicate the status of the PLC itself.
Operator Panel
From the operator panel, the operator may start/stop all fans and compressors, all the measuring values can
be read and the set point and limit values for the control may be entered.
PLC
A movement key.
Tap this key to jump to (in this case) the “Compr 1” menu.
A status text.
Example: Status of the compressor.
A monitored value.
Example: Actual temperature.
Push buttons.
Example: Stop / start of a compressor.
Tap button to activate.
Alphanumeric input
1.3.3.1 Password
Some inputs require a password. This password is “JCI”.
A request similar to the alphanumeric input field pops up when the password is required.
User: Operator
Password: 1266
“Compressor” key.
Displays the compressor display.
Note: The key is drawn differently from the other keys to indicate that this menu is now being displayed.
“AHU” key.
Jumps to the AHU display.
“Next” key.
Moves to next menu of the same component in same level.
Example: Moves from “Compressor 1” to “Compressor 2”
Sensor failures will always activate an alarm and will be explained in an error message code.
When an alarm occurs the alarm lamp, on the front of the switchboard, flashes. The lamp will continue to
flash as long as at least one of the present alarms remain unacknowledged.
After all alarms have been acknowledged, the alarm lamp will remain lid until all failures are fixed.
In case that new alarms do occur, the alarm lamp will start to flash again.
All alarms will activate the common alarm relay, which is a digital outlet to the central alarm system of the
ship.
The common alarm is "high" as long as there is no alarm, and goes "low" when an alarm is detected and
stays "low" until the alarm is acknowledged in the alarm system.
If another alarm occurs before the system has been acknowledged, the output goes “high” for 5 seconds and
then “low” again, as shown on the figure below.
No alarm 5 sec
Main
ALARM
Tap
”ALARM”
1
2 3 4 5
6 7 8 9 10 11
Colour Status
Back ground Text
Active, Not acknowledged
Not active, Not acknowledged
Active, Acknowledged
Not active, Acknowledged
Information
2 PICTURE HIERARCHY
START/STOP START/STOP
Control level START/STOP START/STOP
SET-POINTS SET-POINTS
10
11
12
5 6 7 8 13
4
Indication of whether this panel is the local (mounted on the switchboard) or an optional remote panel.
Plant
Tap overview
”PLANT”
The number of expansion valves does not inflict on the plant overview displays..
7 8 9
7 8 9
7 8 9
7 8 9
2 4
1
3
5
7 9
6
8
Compressor 1.
Tap to access the compressor display,
Symbol Description
The compressor is stopped.
AHU 1
Tap to access the AHU display.
AHU 1 fan.
Symbol Description
The fan is stopped.
Compressor 2.
Tap to access the compressor display,
Symbol Description
The compressor is stopped.
AHU 2
Tap to access the AHU display.
AHU 2 fan.
Symbol Description
The fan is stopped.
2.4.1 Shut-downs
The compressor is fitted with five shutdown functions.
On the switches KP2, KP61, KP98 and motor winding protection the wiring is made fail-safe (all switches are
normally closed when they are error free).
If one of the above-mentioned limits cuts out, the input on the PLC is shut down, the compressor will stop,
and alarm is given.
If the over current relay has switched off, or the interlock signal is open, the compressor will be stopped, and
the alarm list will indicate Compr1 Running feedback Alarm.
All alarms must be reset on the operator panel and/or on the component.
2.4.2 Anti-recycling
On the compressor start an anti-recycling timer is started.
If a restart of the compressor is attempted within five minutes (default) of last start, the system rejects to
carry out the restart command.
In auto mode the compressor is restarted when the timer runs out.
The anti-recycling timer is implanted to protect the motor from the consequences of many repeating starts.
The upper and lower limits for the saturated suction pressure [°C/R] are calculated on basis of follow ing
parameters:
[A] Supply air set point (°C).If more then one AHU is connected to the compressor; the lowest set point will
be used in the calculation. E.g. 15°C
[B] Saturated suction temperature offset (°C). E.g. 10°C
[C] Saturated suction temperature neutral zone (°C) . E.g. 5°C
Upper limit Upper limit = [A] – [B] Example: Upper limit = 15°C – 10°C = 5°C
Lower limit Lower limit = [Upper limit] – [C] Example: Lower limit = 5°C – 5°C = 0°C
Increase of capacity If [F] > [D] for [G] seconds then increase capacity by one step.
Example:
Suction pressure = 6.2 bar => ~6°C/R404a
The capacity will be increased after 180 seconds, because 6°C > 5°C.
Decease of capacity If [F] < [E] for [H] seconds then decrease capacity by one step.
If the compressor is at its lowest capacity step (fully unloaded): No nothing.
Example:
Suction pressure = 4.8 bar => ~-1°C/R404a
The capacity will be decreased after 20 seconds, because -1°C < 0°C
2.4.5 Compressor
Main
Compr 1
Tap
”COMPR1”
Compressor status.
Symbol Description
The compressor is stopped.
The condenser.
Main
Tap ””
Compr 1 Compr 2
Tap
”COMPR1”
Tap ””
Compr 1 Compr 2
Tap on the Control Control
compressor
2
9
2 3
4 5
Automatic mode.
Changes control method from manual to automatic.
Manual mode.
Changes control method from automatic to manual.
Parameter key.
Tap to access the compressor parameter menu.
Main
Tap ””
Compr 1 Compr 2
Tap
”COMPR”
Tap ””
Compr 1 Compr 2
Tap on the Control Control
compressor
Compr 1
Tap on Parameter
”PARAM”
The max suction temperature where the compressor step up after the delay. (Increase delay)
Anti-recycle timer.
Time left when a start is possible.
10
11
12
13
14
15
Number of starts.
Accumulated number of compressor starts.
Adjust field for compressor start counter.
The “Super-user” password is required.
16
• Off mode
• Manually selected cooling.
• Manually selected heating.
• Manually selected cooling with limits.
• Change over limit
Outdoor temperature
°C
Start cooling
mode high limit
Start heating
mode low limit
The fan cannot be restarted before the KP61 temperature switch is reset and alarm is acknowledged.
The valve will be closed automatically at normal stop of the air-handling unit.
During the superheat protection mode the air temperature is unlikely to be maintained at set point, but the
risk of mechanical damage is minimized.
To superheat protection Superheat temperature is lower than the superheat set point - 2 °C
Supply temperature is above the supply temperature set point.
To supply air mode Supply temperature is less than the supply temperature set point.
Too low temperature is an indication of possible presents of liquid drops in the suction line.
If the superheat of the cooler is lower than the low limit superheat limit, the valve will be closed. When the
superheat has become higher than the low limit superheat, the valve will be switched back in the regulation.
This feed-forward function will change the position of the expansion valve, if there is a sudden change of the
compressor capacity. The expansion valve position will then be changed before the superheat temperature
regulator is able to measure this disturbance in the compressor capacity, and it will result in a more stable
superheat regulation.
Example increased
If FF gain is 50.0 and the compressor capacity difference between the two latest samplings is 25.0%, the
position of the valve will be moved by the following percentage:
Example decreased
If FF gain is 50.0 and the compressor capacity difference between the two latest samplings is 33.0%, the
position of the valve will be moved by the following percentage:
2.5.4.8 MOP
Maximum Operation Pressure
To protect the compressor from the consequences of running at a high suction pressure, a MOP function is
implanted.
When the suction pressure is greater than MOP high limit (set in compressor options menu), the expansion
valves will decrease its opening percentage until the suction pressure is maintained below the MOP high
limit.
When the suction pressure has dropped below the MOP high limit, the valve returns to normal operation.
Example of operation:
MOP
High Limit [Bar]
Expansion
valve [%]
Time
MOP mode
• No compensation (disabled).
• Compensation according to the outdoor or return air temperature.
• Compensation according to a manually set offset (pot-meter).
The regulation set point for the supply air will be increased by a percentage of the temperature difference
between the outdoor temperature and the start temperature for compensation.
Summer Compensation
The compensation calculation is started when the outdoors temperature is higher than “summer start” and
lower than “summer stop”.
Winter Compensation
The compensation calculation is started when the outdoor temperature is lower than “winter start” and higher
than “winter stop”.
The formula for the set point for the supply air temperature regulation is:
When the outdoor temperature is -20.0°C, “winter st art” is 14.0°C, “winter stop” is -30.0°C, “winter f actor” is
25 and supply air set point is 15.0°C, the regulati on supply air set point will be:
If the factor value is negative the curves lowers the SP instead of raising it.
Example:
Supply SP = 15.0°C
Pot-meter value = -3.5°C
AHU 1 AHU 2
Tap
”AHU1”
Text Description
Fan stopped The fan is stopped.
Ready for cooling. The fan is running, cooling conditions are achieved, but the
compressor is not started.
Heating The fan is running and the heating system is activated.
Superheat regulation The cooling system is activated in “superheat”-mode.
Supply regulation The cooling system is activated in “supply air”-mode.
Sensor error One or more sensors are failing. See alarm list.
Ventilation The fan is only running.
Symbol Description
The fan is stopped.
Heating coil.
Humidity system.
Tap to access the humidity display.
10
& 12
The opening percentage of the expansion valves.
Expansion valve 12 is only shown on plant types “xx2”.
11
& 13
Evaporators for the cooling system.
Tap
p to access the expansion valve menus.
Evaporator 13 is only shown on plant types “xx2”.
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
Tap ””
AHU 1 AHU 2
Tap on the Control Control
fan
Parameter key.
Tap to access the AHU parameter menu.
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
Tap ””
AHU 1 AHU 2
Tap on the Control Control
fan
AHU 1
Tap on Parameter
”PARAM”
5
& 6
In order for the software to determine whether the supply air is to be cooled or heated, two outdoor
temperature limits is set.
When the outdoor temperature is below “Start heating low limit”, the heating system is activated and the
cooling system is disabled.
The opposite happens when the outdoor temperature rises above the “Start cooling high limit”; the cooling
system is enabled and the heating system is disabled.
See “2.5.1 Supply air ” for more information.
Delay for releasing regulation after superheat temperature has raised above superheat shut-off low limit.
This feed-forward function will change the position of the expansion valve, if there is a sudden change of the
compressor capacity. The expansion valve position will then be changed before the superheat temperature
regulator is able to measure this disturbance in the compressor capacity, and it will result in a more stable
superheat regulation.
See “2.5.4.7 Feed Forward (FF)” for more information.
2 3
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
AHU 1
Tap on the Humidity
humidifier
symbol
One valve system Steam or water is applied with a single solenoid valve.
Two valve system Water and air is mixed from separate supply lines and applied to the airflow.
External system An output is set when external humidity control system may be activated.
Detailed information regarding the external humidity system is to be found in the
systems own manual.
Outdoor temperature
°C
Maximum outdoor
temperature limit
Dose
Pause
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
AHU 1
Tap on the Humidity
humidifier
symbol
System status.
Text Description
Inactive The AHU main fan is stopped or outdoor temperature is between limits.
Dose Humidity system is applying moisture to the air.
Pause Humidity system is active, but awaiting dose conditions.
Error Humidity sensor or outdoor sensor is failing.
The humidity system is activated at temperatures lower than the maximum outdoor value.
The AHU fan must also be running.
The Humidity.
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
AHU 1
Tap on the Humidity
humidifier
symbol
System status.
Text Description
Inactive The AHU main fan is stopped or outdoor temperature is between limits.
Dose Humidity system is applying moisture to the air.
Pause Humidity system is active, but awaiting dose conditions.
Error Humidity sensor or outdoor sensor is failing.
The humidity system is activated at temperatures lower than the maximum outdoor value.
The AHU fan must also be running.
The Humidity.
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
AHU 1
Tap on the Humidity
humidifier
ymbol
System status.
Text Description
Inactive The AHU main fan is stopped or outdoor temperature is between limits.
Active External humidity system is allowed to operate.
Error Humidity sensor or outdoor sensor is failing.
The humidity system is activated at temperatures lower than the maximum outdoor value.
The AHU fan must also be running.
The Humidity.
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
AHU 1
Tap on the Humidity
humidifier
System status.
Text Description
Inactive The AHU main fan is stopped or outdoor temperature is between limits.
Warm-Up The steam generator is heating up.
Dose Humidity system is applying moisture to the air.
Pause Humidity system is active, but awaiting dose conditions.
Error Humidity sensor or outdoor sensor is failing.
The Humidity.
“PARAM”-key.
Tap to access the humidity parameter menus.
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
AHU 1
Tap on the Humidity
humidifier
symbol
Humidity
Tap parameter
”PARAM”
The humidity system is activated at temperatures lower than the maximum outdoor value.
The AHU fan must also be running.
Inactive Time: If the steam generator is stopped for more than XX min. the WarmUp time is enabled (0 – 50
minutes)
Warm Up Time: the warm up time for the steam generator (0 – 50 minutes).
OFF Time: the time where the steam generator is paused (0 – 50 minutes).
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
AHU 1
Tap on the Exhaust
”EXHAUST”
2
4
3
Exhaust fan.
Tap to access the control menu.
Symbol Description
The fan is stopped.
Enthalpy exchanger.
Symbol Description
The exchanger is stopped.
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
AHU 1
Exhaust
Tap on the
”EXHAUST”
Exhaust
Tap on the control
exhaust fan
Manual mode.
Automatic mode.
“TIMERS”-key.
Tap to access the Exhaust timer menu.
Main
Tap ””
AHU 1 AHU 2
Tap
”AHU1”
AHU 1
Exhaust
Tap on the
”EXHAUST”
Exhaust
Tap on the control
exhaust fan
Exhaust
Tap on Timer
”TIMERS”
Number of starts.
Accumulated number of fan starts.
Adjust field for compressor start counter.
The “Super-user” password is required.
When cross connection is enabled, the compressor selected as cross connector will take the control of both
of the AHU’s the cross connection is useful, if one compressor breaks down and operation of the AHU is
needed.
Mode: Disabled (No cross connection) Mode: Compressor 1 to all AHU’s Mode: Compressor 2 to all AHU’s
Cross-connection mode.
Mode Description
Disabled Normal operation.
Each compressor supplies its “own” AHU.
Compressor 1 to all AHU’s Compressor 1 is taking over for compressor 2.
Compressor 1 is supplies both AHU’s.
Compressor 2 is disabled.
Compressor 2 to all AHU’s Compressor 2 is taking over for compressor 1.
Compressor 2 is supplies both AHU’s.
Compressor 1 is disabled.
Sequence mode.
Mode Description
Compr1 #1 – Compr2 #2 Compr. 1 is master and Compr. 2 is slave
Compr1 #2 – Compr2 #1 Compr. 1 is slave and Compr. 2 is master
Compr1 #1 – Compr2 manual Compr. 1 is master and Compr. 2 is set to
manual.
Compr1 manual – Compr2 #1 Compr. 1 is set to manual and Compr. 2 is
master
Compr1 manual – Compr2 manual Compr. 1 is set to manual and Compr. 2 is set to
manual.
1 AHU with 2 evaporators 1 on each compr 2 AHU with 2 evaporators 1 on each compr
Cascade mode.
Mode Description
Disabled But compressors will be set to manual. the
user will be able to control both compressors
at the same time.
Compr 1 Master. Compr 2 Slave. Compr 1 is master and will be the first to start.
Compr 2 is slave and will be interlocked until
Compr 1 is at max cap.
Compr 2 Slave. Compr 2 Master. Compr 2 is master and will be the first to start.
Compr 1 is slave and will be interlocked until
Compr 2 is at max cap.
Evaporators are.
- Intertwined
- Not intertwined
- This function shall only be changed together will JCI employee.
Note!
If the evaporator is not intertwined and compressor 1 is connected to evaporator, the cascade mode is set to
compr 2 master. When the slave compr starts the mode will change so compressor 1 is master.
Control description:
When the compressor operation mode is selected to cascade, the master compressor will start up as normal.
Then the system will monitor 3 different scenarios to see when to start the slave compressor.
If the master exp. valve is in supply air mode, then the following condition must be true to start the slave
compressor:
Superheat mode:
If the master exp. valve is in superheat mode, then the following condition must be true to start he slave
compressor:
Force mode:
Force mode is to start the slave compressor if the master exp. valve is in superheat mode , but the
compressor cap. level will not increase. Then the following condition must be true to start he slave
compressor:
ATTENTION!
To prevent damage, plant must be stopped, and all valves must be manually set to correct position for the
decided cross connection mode before selecting the mode. To change mode see 2.7.3 system.
2.8 Configuration
2.8.1 System
Error code
Table of Contents Marine Controls
Revision: 2.0 · Updated:10-06-2014 Author: Emil Aurvig Svendsen · Owner: Emil Aurvig Svendsen
Project : Air-condition Refrigeration Plant E200-T7A
Page 63 of 83
Users manual
CPU
Normal condition is “running”.
Condition “stopped”:
To the left of the circular plug is placed a “Run / Stop” switch.
The switch must be in “Run” position.
Flipping the switch from “Run” to “Stop” and back may solve the problem.
Project number.
The internal JCI Marine project number. When contacting JCI, all these values must be supplied.
Logout key.
4 mA calibration value.
20 mA calibration value.
4 mA calibration value.
20 mA calibration value.
2.8.4 Options
1
Plant Basic plant configuration.
2
Compressor Options regarding the compressor system.
3
Air handling unit Options regarding the AHU.
Plant type.
Text Description
ARP 111 One compressor.
One AHU with one expansion valve.
ARP 112 One compressor.
One AHU with two expansion valves.
ARP 121 One compressor.
Two AHU with one expansion valve.
ARP 122 One compressor.
Two AHU with two expansion valves.
ARP 211 Two compressors.
One AHU with one expansion valve.
ARP 212 Two compressors.
One AHU with two expansion valves.
ARP 221 Two compressors.
Two AHU with one expansion valve.
ARP 222 Two compressors.
Two AHU with two expansion valves.
Compressor type.
Text Description
CMO 24 JCI type Sabroe CMO 24.
4 capacity steps.
25.0%, 50.0%, 75.0%, 100.0%
CMO 26 JCI type Sabroe CMO 26.
4 capacity steps
33.3%, 50.0%, 66.7%, 100.0%
CMO 28 JCI type Sabroe CMO 28.
4 capacity steps.
25.0%, 50.0%, 75.0%, 100.0%
Text Description
CMO 34 JCI type Sabroe CMO 34.
4 capacity steps .
12.5%, 50.0%, 75.0%, 100.0%
CMO 36 JCI type Sabroe CMO 36.
4 capacity steps.
33.3%, 50.0%, 66.7%, 100.0%
CMO 38 JCI type Sabroe CMO 38.
4 capacity steps.
12.5%, 50.0%, 75.0%, 100.0%
SMC 106 JCI type Sabroe SMC 106.
3 capacity steps.
33.3%, 66.7%, 100.0%
SMC 108 JCI type Sabroe SMC 108.
4 capacity steps.
25.0%, 50.0%, 75.0%, 100.0%
Bitzer Bitzer semi-hermetic compressor.
1 capacity step.
100.0%
Bitzer w/cap Bitzer semi-hermetic compressor.
2 capacity steps.
50.0% 100.0%
Temperature compensation.
Text Description
Disable No compensation.
Outdoor Supply air SP is compensated according to the outdoor air
temperature.
Return Supply air SP is compensated according to the return air duct
temperature.
Potmeter A pot meter is used to adjust the supply air SP.
Antirecycling delay.
Protects the motor from overheating if exposed to frequent starts.
A minimum delay between starts is recommended to be set to 5 minutes.
Refrigerant type.
Select between:
R 22.
R 404 A.
R 407 C.
R 507.
R 134 A.
Only available to JCI personnel and/or representatives.
Min and max key-in value for supply air set point.
Humidity system.
Select mode of humidity control.
Frost supervision.
Enable, if plant is equipped with frost protection thermostat on the heating coil.
Reheating system.
Enable, if the plant is equipped with a reheating system.
If the outdoor temperature is between the limits the enthalpy exchanger runs in low speed.
NOTE! The navigation keys “File” is only available on the local display.
Load.
Tap key to load the Settings defined plant configuration.
WARNING: Changes will take place immediately.
Save.
Tap key to save the Settings defined plant configuration.
May be used as a backup function when adjusting the configuration.
Import.
Tap key to restore plant configuration from a USB memory device.
(See 2.7.4.1.1 “Import plant configuration from USB memory device”)
Export .
Tap key to backup plant configuration on a USB memory device.
(See 2.7.4.1.2 “Export plant configuration to USB memory device”)
5
Navigation keys for the configuration pages.
Step 1 Insert USB stick into the USB port on the display.
Step 2 Wait for a few seconds while the panel connects the USB stick.
Step 3 If asked for, accept creation of file structure on the memory card.
Wait for a few seconds until the file structure is updated.
Step 1 Insert USB stick into the USB port on the display.
Step 2 Wait for a few seconds while the panel connects the USB stick.
The plant configuration is now restored, it is necessary to tap “Load” key to load the restored plant
configuration.
3 PI REGULATOR FUNCTION
The regulator calculates the difference between the set point and the actual temperature. The output from
the regulator is a new calculated position set point for the actuator.
SP + e u
PI
Regulator Algorithm
After each Ts a new value (un) for the actuator is calculated according to the following formula:
un = (P + I) gain + un-1
P = en - en-1
I = en * Ts/Ti
Ts = sampling time
Ti = integral time
Gain = gain factor
Calculated values
4 ALARM LIST
Alarm text Description
AHU1 Enthalpy exchanger feedback Alarm The motor has tripped the over current relay.
The relay must be manually reset inside the switchboard.
AHU1 Evaporator 1 suction temp Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU1 Evaporator 2 suction temp Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU1 Exhaust fan feedback Alarm The motor has tripped the over current relay.
The relay must be manually reset inside the switchboard.
AHU1 Exhaust fan service Warning Service reminder.
Reset by altering the limit.
AHU1 Fan start failure Alarm The motor has tripped the over current relay.
The relay must be manually reset inside the switchboard.
AHU1 Heating coil freezing risk Alarm Temperature on heating coil is too cold.
Risk of severe freezing damage to the coil is imminent.
AHU1 Humidity sensor Error Humidity sensor failing or missing signal.
Check sensor and wires.
AHU1 Outdoor temperature sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU1 Reheat air temperature HT Alarm Reheated air temperature is higher than alarm limit.
AHU1 Reheat air temperature LT Alarm Reheated air temperature is lower than alarm limit.
AHU1 Reheat temperature sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU1 Return temperature sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
AHU1 Service interval Warning Service reminder.
Reset by altering the limit.
AHU1 Supply air temperature HT Alarm Supply air temperature is higher than alarm limit.
AHU1 Supply air temperature LT Alarm Supply air temperature is lower than alarm limit.
AHU1 Supply temperature sensor Error Temperature sensor failing or missing signal.
Check sensor and wires.
Compr1 Cooling water LP Alarm No condenser cooling water flow or too low pressure.
Compr1 Discharge HP Discharge pressure above alarm limit.
The switch must be manually reset on the switch.
Compr1 Discharge pressure sensor Error Pressure sensor failing or missing signal.
Check sensor and wires.
Compr1 Lube oil LP Alarm Low lubrication oil pressure.
Low or missing oil level.
Compr1 Motor winding protection Alarm Motor winding temperature too high.
Motor must be cool off before restarting.
Compr1 Oil Filter Warning Oil filter is blocked. Replace or clean.
Compr1 Oil pressure sensor Error Pressure sensor failing or missing signal.
Check sensor and wires.
Compr1 Oil/Discharge HT Alarm The oil or discharge temperature is to high.
Compr1 Overcurrent relay Alarm The motor has tripped the over current relay.
The relay must be manually reset inside the switchboard.
Compr1 Running feedback Alarm The motor contactor that is not activated. Interlocked.
Compr1 Service interval Warning Service reminder.
Reset by altering the limit.
Table of Contents Marine Controls
Revision: 2.0 · Updated:10-06-2014 Author: Emil Aurvig Svendsen · Owner: Emil Aurvig Svendsen
Project : Air-condition Refrigeration Plant E200-T7A
Page 80 of 83
Users manual
5 WORD LIST
General
Text Description
SP Regulator set point
Compressor
Text Description
Compr Compressor
CMO, SMC Sabroe compressor type. I.e. CMO 28 or SMC 106
MOP Maximum Operation Pressure. See section 2.5.4.8 MOP
Text Description
AHU Air Handling Unit
EXP Expansion valve