Power Cable Sizing Guide

This document provides cable sizing calculations for a power cable connecting an MCC to a pump station. It includes information on the cable such as: - Cable number and connection points - Power load in kW - Voltage, current, and power factor specifications - Cable length - Calculations for voltage drop and selected cable size - Notes on cable data like insulation type and short circuit ratings

Uploaded by

Alry Purwariyadi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
218 views4 pages

Power Cable Sizing Guide

This document provides cable sizing calculations for a power cable connecting an MCC to a pump station. It includes information on the cable such as: - Cable number and connection points - Power load in kW - Voltage, current, and power factor specifications - Cable length - Calculations for voltage drop and selected cable size - Notes on cable data like insulation type and short circuit ratings

Uploaded by

Alry Purwariyadi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Document Overview
  • Power Cable Sizing
  • Short Circuit Calculation
  • Voltage Drop Analysis

DOCUMENT NUMBER :

P3LA-EL-CAL-002
From To P P.F. P.F start
NO. CABLE NUMBER
TAG-NUMBER ITEM TAG-NUMBER ITEM (kW) (Cos j) (Cos j)

A PLTD HSD / LV POWER CABLE (0.6/1 KV)


MCC
PLTD HSD
1 MCC-01-P PLTD HSD MCC-01 PUMP 600,0 1,0 N/A
STATON
HOUSE
REMARKS
P = Power (kW) S = Selected Cable size (mm²)
In = Nominal Current (A) PF = Power Factor
L = Cable Length (m) Rac = AC Resistance of Cable at 90OC (ohm/km)
Is/In = Locked Rotor Current (A) Rdc = DC Resistance of Cable at 90OC (ohm/km)
PEMBANGUNAN INSTALASI BBC (BAHAN BA

ATTACHMENT 1 - POWER CABLE SIZING CALCULATIO

Eff Voltage IL Itr Is L


Is/In S
(h) (V) (A) (A) (A) (m) (mm²) Selec.

1,000 380 920,81 1058,94 N/A N/A 300 4C #240 14

X = Reactance of Cable (ohm/km)


Vd = Voltage drop of Cable (%)
C (ohm/km) I t = Cable Rated Current (A)
C (ohm/km) I tr = Trip Current (A)
NSTALASI BBC (BAHAN BAKAR CAIR)

CABLE SIZING CALCULATION


CABLE DATA
tSC ISCB K ISCC ILF It Parallel CF IZ
(Sec) (kA) ( PVC ) (kA) (kA) (A) (n) (k1 x k2) (A)

0,05 25 115 370,29 14,05 525 3 0,733 1154,79

ISCB = Current short circuit bus


ISCC = cable short circuit rating Iz
ILF = Load End Short Circuit Fault Current CF
tsc = time clearence breaking n
K = Short Circuit Density Coefficient ( '143' for XLPE Insulation ) n
DATE : REV:
0
15 - 03 - 2018
VOLTAGE DROP
o o
R AC (70 C) X (70 C) Allow. Vd Allow. Vd start SELECTED CABLES REMARK
(W / Km) (W / Km) Vd (%) (%) Vd start (%) (%)

Penambah
0,0930 0,0732 5 4,30 N/A N/A 3-4C #240 mm²
an

= Cable Corrected Current (A) Eff = Efficiency


= Correction Factor LRA = Locked rotor ampere
= Number of Parallel