DOCUMENT NUMBER :
P3LA-EL-CAL-002
From To P P.F. P.F start
NO. CABLE NUMBER
TAG-NUMBER ITEM TAG-NUMBER ITEM (kW) (Cos j) (Cos j)
A PLTD HSD / LV POWER CABLE (0.6/1 KV)
MCC
PLTD HSD
1 MCC-01-P PLTD HSD MCC-01 PUMP 600,0 1,0 N/A
STATON
HOUSE
REMARKS
P = Power (kW) S = Selected Cable size (mm²)
In = Nominal Current (A) PF = Power Factor
L = Cable Length (m) Rac = AC Resistance of Cable at 90OC (ohm/km)
Is/In = Locked Rotor Current (A) Rdc = DC Resistance of Cable at 90OC (ohm/km)
PEMBANGUNAN INSTALASI BBC (BAHAN BA
ATTACHMENT 1 - POWER CABLE SIZING CALCULATIO
Eff Voltage IL Itr Is L
Is/In S
(h) (V) (A) (A) (A) (m) (mm²) Selec.
1,000 380 920,81 1058,94 N/A N/A 300 4C #240 14
X = Reactance of Cable (ohm/km)
Vd = Voltage drop of Cable (%)
C (ohm/km) I t = Cable Rated Current (A)
C (ohm/km) I tr = Trip Current (A)
NSTALASI BBC (BAHAN BAKAR CAIR)
CABLE SIZING CALCULATION
CABLE DATA
tSC ISCB K ISCC ILF It Parallel CF IZ
(Sec) (kA) ( PVC ) (kA) (kA) (A) (n) (k1 x k2) (A)
0,05 25 115 370,29 14,05 525 3 0,733 1154,79
ISCB = Current short circuit bus
ISCC = cable short circuit rating Iz
ILF = Load End Short Circuit Fault Current CF
tsc = time clearence breaking n
K = Short Circuit Density Coefficient ( '143' for XLPE Insulation ) n
DATE : REV:
0
15 - 03 - 2018
VOLTAGE DROP
o o
R AC (70 C) X (70 C) Allow. Vd Allow. Vd start SELECTED CABLES REMARK
(W / Km) (W / Km) Vd (%) (%) Vd start (%) (%)
Penambah
0,0930 0,0732 5 4,30 N/A N/A 3-4C #240 mm²
an
= Cable Corrected Current (A) Eff = Efficiency
= Correction Factor LRA = Locked rotor ampere
= Number of Parallel