0% found this document useful (0 votes)
45 views8 pages

Perhitungan Daya dan Pemilihan Trafo

This document provides calculations and selections for electrical components for a power distribution system with total load of 1600 kVA. It includes: 1. Calculations of current, short circuit current, and cable sizing for each of 5 load groups. 2. Selection of MCCBs, cables, and busbars for each load group and main busbars. 3. Calculation of total current and selection of ATS, ACBs, and main cables between the utility and generator.

Uploaded by

Firdaus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views8 pages

Perhitungan Daya dan Pemilihan Trafo

This document provides calculations and selections for electrical components for a power distribution system with total load of 1600 kVA. It includes: 1. Calculations of current, short circuit current, and cable sizing for each of 5 load groups. 2. Selection of MCCBs, cables, and busbars for each load group and main busbars. 3. Calculation of total current and selection of ATS, ACBs, and main cables between the utility and generator.

Uploaded by

Firdaus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

Nama : Yogiswara Wahyu Erlianto

NIM : 1641150013
Kelas : SKL 2B

Diketahui : Faktor Koreksi


Grup 1 S = 600 kVA Suhu 50 ̊ = 0,71
Grup 2 S = 200 kVA Penataan = 0,96 (trikoil)
Grup 3 S = 400 kVA FK = 0,71 x 0,96
Grup 4 S = 300 kVA = 0,681
Grup 5 S = 100 kVA
G.Total S = 1600 kVA
Tegangan = 380 V
Ditanya :

 In, IKHA, IFK, Ipmt, busbar (tiap group)


 IFK, Ipmt, busbar sesuai katalog
 Pemilihan ATS
 Pemilihan Trafo
 Pemilihan Genset
Jawab :

Group 1
S = √3 . V. In
S 600 600
In = = = = 0,911 kA ≈ 911 A
√3.V √3 . 380 658,17

IKHA = 1,25 x In

= 1,25 x 911 A = 1138,75 A


IKHA 1138,75
IFK = = = 1672,17 A
FK 0,681
1672,17
Penentuan kabel = = 557,3 A (590 A, katalog Supreme)
3
Jadi 590 A x 3 = 1770 A
Katalog supreme LV NYY 220 mm² x 3 x 3

Ipmt = 1,15 x In

= 1,15 x 911 = 1138,75 A


Penentuan pemutus = 1250 A (Katalog Schnaider Compact NS 1250 A) MCCB

Setting 1 x 1250 = 1250 A

Group 2
S = √3 . V. In
S 200 200
In = = = = 0,303 kA ≈ 303 A
√3.V √3 . 380 658,17

IKHA = 1,25 x In

= 1,25 x 303 A = 348,45 A


IKHA 348,45
IFK = = = 556,16 A
FK 0,681
556,16
Penentuan kabel = = 189,3 A (205 A, katalog Supreme)
3
Jadi 205 A x 3 = 615 A
Katalog supreme LV NYY 50 mm² x 3 x 3
Ipmt = 1,15 x In

= 1,15 x 303 = 348,45 A


Penentuan pemutus = 400/630 A (Katalog Schnaider Kasy Dact (VS 400/630)) MCCB

Setting 0,9 x 400 = 360 A

Group 3
S = √3 . V. In
S 400 600
In = = = = 0,607 kA ≈ 607 A
√3.V √3 . 380 658,17

IKHA = 1,25 x In

= 1,25 x 607 A = 758,75 A


IKHA 758,75
IFK = = = 1114,17 A
FK 0,681
1114,17
Penentuan kabel = = 371,3 A (375 A, katalog Supreme)
3
Jadi 375 A x 3 = 1125 A
Katalog supreme LV NYY 120 mm² x 3 x 3

Ipmt = 1,15 x In

= 1,15 x 607 = 698,05 A


Penentuan pemutus = 800 A (Katalog Schnaider Compact NS 800 A) MCCB

Setting 0,9 x 800 = 720 A

Group 4
S = √3 . V. In
S 300 300
In = = = = 0,455 kA ≈ 455 A
√3.V √3 . 380 658,17

IKHA = 1,25 x In

= 1,25 x 455 A = 568,75 A


IKHA 568,75
IFK = = = 835,16 A
FK 0,681
835,16
Penentuan kabel = = 278,38 A (320 A, katalog Supreme)
3
Jadi 320 A x 3 = 960 A
Katalog supreme LV NYY 95 mm² x 3 x 3

Ipmt = 1,15 x In

= 1,15 x 455 = 523,25 A


Penentuan pemutus = 400/630 A (Katalog Schnaider Easy Past (VS 400/630)) MCCB

Setting 0,9 x 600 = 540 A

Group 5
S = √3 . V. In
S 100 100
In = = = = 0,152 kA ≈ 152 A
√3.V √3 . 380 658,17

IKHA = 1,25 x In

= 1,25 x 152 A = 190 A


IKHA 190
IFK = = = 279,001 A
FK 0,681
297,001
Penentuan kabel = = 93 A (100 A, katalog Supreme)
3
Jadi 100 A x 3 = 300 A
Katalog supreme LV NYY 16 mm² x 3 x 3

Ipmt = 1,15 x In

= 1,15 x 152 = 174,8 A


Penentuan pemutus = 100/160/250 A (Katalog Schnaider Easy Pact (VS 100/160/250))
MCCB

Setting 0,8 x 250 = 200 A


Busbar PLN

PLN = Sgroup1 + Sgroup2

Stot = 600 + 200 = 800 kVA ≈ 800.000 A

Stot = √3 . V. In

Stot 800.000 800.000


In = = = = 1215,49 A
√3.V √3 . 380 658,17

Busbar = 1,25 x In

= 1,25 x 1215,49 = 1519,36 A

Katalog Busbar (Puil 2011)

Dilapisi lapisan konduktif jumlah batang 3 = 1650 A

Berat = 1,08 kg/m , UK = 40x10 m, penampang = 400 mm2

IKHA PLN = 1,25 x In

= 1,25 x 1215,49 A = 1519,36 A

IKHA 1519,36
IFK = = = 2231,07 A
FK 0,681
2231,07
Penentuan kabel = = 743,6 A (825 A, katalog Supreme)
3
Jadi 825 A x 3 = 2475 A (katalog supreme LV NYY 400 mm2 x 3 x 3)

Ipmt = 1,15 x In

= 1,15 x 1215,49 = 1397,81 A


Penentuan pemutus = 1600 A (Katalog SchnaiderCompact NS 1600 A) MCCB

Setting 0,9 x 1600 = 1440 A


Busbar Genset

PLN = Sgroup3 + Sgroup4 + Sgroup5

Stot = 400 + 300 + 100 = 800 kVA ≈ 800.000 A

Stot = √3 . V. In

Stot 800.000 800.000


In = = = = 1215,49 A
√3.V √3 . 380 658,17

Busbar = 1,25 x In

= 1,25 x 1215,49 = 1519,36 A

Katalog Busbar (Puil 2011)

Dilapisi lapisan konduktif jumlah batang 3 = 1650 A

Berat = 1,08 kg/m , UK = 40x10 m, penampang = 400 mm2

IKHA Genset = 1,25 x In

= 1,25 x 1215,49 A = 1519,36 A

IKHA 1519,36
IFK = = = 2231,07 A
FK 0,681
2231,07
Penentuan kabel = = 743,6 A (825 A, katalog Supreme)
3
Jadi 825 A x 3 = 2475 A (katalog supreme LV NYY 400 mm2 x 3 x 3)

Ipmt Genset = 1,15 x In

= 1,15 x 1215,49 = 1397,81 A


Penentuan pemutus = 1600 A (Katalog SchnaiderCompact NS 1600 A) MCCB

Setting 0,9 x 1600 = 1440 A


Busbar Utama (PLN – Genset)

PLN - Genset = Sgroup1 + Sgroup2 + Sgroup3 + Sgroup4 + Sgroup5

= 600 + 200 + 400 + 300 + 100

Stot = 1600 kVA ≈ 1.600.000 A

Stot = √3 . V. Itot

Stot 1.600.000 1.600.000


Itot = = = = 2.430,98 A
√3.V √3 . 380 658,17

Busbar = 1,25 x In

= 1,25 x 2430,98 = 3038,72 A

Katalog Busbar (Puil 2011)

Dilapisi lapisan konduktif jumlah batang 4 = 3040 A

Berat = 1,62 kg/m , UK = 60x10 m, penampang = 600 mm2

IKHA Jalur (PLN – Genset) = 1,25 x Itot

= 1,25 x 2430,98 A = 3038,72 A

IKHA 3038,72
IFK = = = 4462,14 A
FK 0,681
4462,14
Penentuan kabel = = 743,69 A (825 A, katalog Supreme)
6
Jadi 825 A x 6 = 4950 A (katalog supreme LV NYY 400 mm2 x 3 x 6)

Ipmt ATS

= 1,2 x Itot

= 1,2 x 2430,98 = 2917,176 A


Penentuan pemutus ATS = 3000 A (Katalog ASCO 7000 series dower switching)
Ipmt Jalur PLN (ACB)

= 1,15 x Itot

= 1,15 x 2430,98 = 2795,62 A


Penentuan pemutus ACB = 800/4000 A (Katalog Schnaider Easy Pact MVS)

Setting =0,9 x 3200 = 2889 A

Ipmt Jalur Genset (ACB)