DATASHEET - DS7-340SX032N0-N
Soft starter, 32 A, 200 - 480 V AC, Us= 24 V AC/DC, Frame size FS2
Part no. DS7-340SX032N0-N
Catalog No. 134914
Alternate Catalog DS7-340SX032N0-N
No.
EL-Nummer 4134266
(Norway)
Delivery program
Description With internal bypass contacts
Function Soft starters for three-phase loads
Mains supply voltage (50/60 Hz) ULN V AC 200 - 480
Supply voltage Us 24 V AC/DC
Control voltage UC 24 V AC
24 V DC
Assigned motor rating (Standard connection, In-Line)
at 400 V, 50 Hz P kW 15
at 460 V, 60 Hz P HP 25
Rated operational current
AC-53 Ie A 32
Rated operational voltage Ue 200 V
230 V
400 V
480 V
Connection to SmartWire-DT no
Frame size FS2
Technical data
General
Standards IEC/EN 60947-4-2
UL 508
CSA22.2-14
Approvals CE
Approvals UL
CSA
C-Tick
UkrSEPRO
Climatic proofing Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-10
Ambient temperature
Operation ϑ °C -5 - +40
up to 60 at 2% derating per Kelvin temperature rise
Storage ϑ °C -25 - +60
Altitude m 0 - 1000 m, above that 1 % derating per 100 m , up to 2000 m
Mounting position Vertical
Degree of protection
Degree of Protection IP20
Protection against direct contact Finger- and back-of-hand proof
Overvoltage category/pollution degree II/2
Shock resistance 8 g/11 ms
Vibration resistance to EN 60721-3-2 2M2
Radio interference level (IEC/EN 55011) B
Static heat dissipation, non-current-dependent Pvs W 1.5
Weight kg 0.4
Main conducting paths
Rated operating voltage Ue V AC 200 - 480
11/04/2019 Eaton 134914 ED2019 V61.0 EN 1/5
Supply frequency fLN Hz 50/60
Rated operational current Ie A
AC-53 Ie A 32
Assigned motor rating (Standard connection, In-Line)
at 230 V, 50 Hz P kW 7.5
at 400 V, 50 Hz P kW 15
at 200 V, 60 Hz P HP 10
at 230 V, 60 Hz P HP 10
at 460 V, 60 Hz P HP 25
Overload cycle to IEC/EN 60947-4-2
AC-53a 32 A: AC-53a: 3 - 5: 75 - 10
Internal bypass contacts ✓
Short-circuit rating
Type “1” coordination PKM0-32 (+ CL-PKZ0)
Type „2“ coordination (additional with the fuses for coordination type „1“) 3 x 170M1366
Fuse base (number x part no.) 3 x 170H1007
Terminal capacities
Cable lengths
Solid mm
2 1 x (0.75 - 16)
2 x (0.75 - 10)
Flexible with ferrule mm
2 1 x (0.75 - 16)
2 x (0.75 - 10)
Stranded mm
2 1 x 16
Solid or stranded AWG 18 - 6
Tightening torque Nm 3.2
Screwdriver (PZ: Pozidriv) mm PZ2; 1 x 6 mm
Control cables
Solid mm
2 1 x (0.5 - 2.5)
2 x (0.5 - 1.0)
Flexible with ferrule mm
2 1 x (0.5 - 1.5)
2 x (0.5 - 0.75)
Stranded mm
2 1 x (0.5 - 1.5)
2 x (0.5 - 1.0)
Solid or stranded AWG 1 x (21 - 14)
2 x (21 - 18)
Tightening torque Nm 1.2
Screwdriver mm 0,6 x 3,5
Control circuit
Digital inputs
Control voltage
DC-operated V DC 24 V DC +10 %/- 15 %
AC operated V AC 24 V AC +10 %/- 15 %
Current consumption 24 V mA
External 24 V mA 1.6
Pick-up voltage x Us
DC-operated V DC 17.3 - 27
AC operated V AC 17.3 - 27
Drop-out voltage x Us
DC operated V DC 0-3
AC operated V AC 0-3
Pick-up time
DC operated ms 250
AC operated ms 250
Drop-out time
DC operated ms 350
Regulator supply
Voltage Us V 24 V AC/DC +10 %/- 15 %
11/04/2019 Eaton 134914 ED2019 V61.0 EN 2/5
Current consumption Ie mA 50
Notes External supply voltage
Relay outputs
Number 2 (TOR, Ready)
Voltage range V AC 250
AC-11 current range A 1 A, AC-11
Soft start function
Ramp times
Acceleration s 1 - 30
Deceleration s 0 - 30
Start voltage (= turn-off voltage) % 30 100
Start pedestal % 30 - 100
Fields of application
Fields of application Soft starting of three-phase asynchronous motors
1-phase motors ●
3-phase motors ✓
Functions
Fast switching (semiconductor contactor) - (minimum ramp time 1s)
Soft start function ✓
Reversing starter External solution required
Suppression of closing transients ✓
Suppression of DC components for motors ✓
Potential isolation between power and control sections ✓
Notes
Rated impulse withstand voltage:
• 1.2 µs/50 µs (rise time/fall time of the pulse to IEC/EN 60947‐2 or ‐3)
• Applies for control circuit/power section/enclosure
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation In A 32
Heat dissipation per pole, current-dependent Pvid W 0
Equipment heat dissipation, current-dependent Pvid W 1.5
Static heat dissipation, non-current-dependent Pvs W 1.5
Heat dissipation capacity Pdiss W 0
Operating ambient temperature min. °C -5
Operating ambient temperature max. °C 40
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
11/04/2019 Eaton 134914 ED2019 V61.0 EN 3/5
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Soft starter (EC000640)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Load breakout, motor breakout / Semiconductor motor controller or soft starter
([email protected] [ACO300011])
Rated operation current Ie at 40 °C Tu A 32
Rated operating voltage Ue V 230 - 460
Rated power three-phase motor, inline, at 230 V kW 7.5
Rated power three-phase motor, inline, at 400 V kW 15
Rated power three-phase motor, inside delta, at 230 V kW 0
Rated power three-phase motor, inside delta, at 400 V kW 0
Function Single direction
Internal bypass Yes
With display No
Torque control No
Rated surrounding temperature without derating °C 40
Rated control supply voltage Us at AC 50HZ V 24 - 24
Rated control supply voltage Us at AC 60HZ V 24 - 24
Rated control supply voltage Us at DC V 24 - 24
Voltage type for actuating AC/DC
Integrated motor overload protection No
Release class Other
Degree of protection (IP) IP20
Degree of protection (NEMA) 1
Approvals
Product Standards IEC/EN 60947-4-2; GB 14048.6; UL 508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE
marking
UL File No. E251034
CSA File No. 2511305
CSA Class No. 321106
Specially designed for North America No
Suitable for Branch circuits
Current Limiting Circuit-Breaker No
Max. Voltage Rating 480 V
Degree of Protection IP20; UL/CSA Type 1
11/04/2019 Eaton 134914 ED2019 V61.0 EN 4/5
Dimensions
11/04/2019 5/5