0% found this document useful (0 votes)
298 views50 pages

ASI

Uploaded by

tad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
298 views50 pages

ASI

Uploaded by

tad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

AS-Interface Fieldbus Solutions

Fieldbus Communication
for Actuator Sensor
Interface Applications
Lumberg Automation™ Provides
Reliable Actuator Sensor Interface
Fieldbus Solutions for Industrial
Automation Applications Worldwide.
AS-Interface

Be Certain with Belden

Belden® Industrial Solutions — More Convenience and Solutions for Networks


in Harsh Environments and Large-scale Infrastructures

Belden Industrial Solutions Here are a few more good reasons why Belden We’ll consult with you to develop a strategy —
is your best choice for industrial networking, or we’ll develop and implement your full design
For mission-critical applications, Belden is communications and control: — either way our staff is available to you.
the signal transmission partner that delivers
confidence in signal availability, integrity and • We have the expertise to integrate your Training
performance because only Belden can offer industrial and commercial networks.
Backed by years of meeting and exceeding
solutions that satisfy any requirement. • Our products are engineered to perform in the needs of a broad range of end-user
A majority of system failures occur within the tough and difficult environments.
applications, Belden is ideally suited to offer
signal transmission space, and trouble-shooting • We offer the broadest selection of products, beginners and networking experts alike the
can be very difficult and time-consuming. We for a complete, end-to-end Ethernet opportunity to expand their understanding of
want everyone to “Be Certain” that when solution. mission-critical industrial networks.
choosing Belden you receive Signal Availability • Our sales and engineering professionals can Belden has developed a series of training
— always there, Signal Integrity — always audit, recommend/design, configure and programs that are given by Belden-certified
trusted and secure, and Signal Performance — assemble the products and systems to your individuals — all experts in industrial
always when and where you need it. specific requirements. networking and cabling.
Belden has brought together a comprehensive • Our global manufacturing and distribution
line of industrial cabling, connectivity and network make our products available to Technical Support
networking devices, offering the most reliable you globally.
At Belden, our personnel are poised to assist our
communications solutions for your application. customers — ensuring maximum uptime and
Whether you are networking your devices to Offering Comprehensive reliability. And with offices in North America,
Service & Support
the controllers, connecting the controllers to Asia and Europe, Belden can respond globally.
the control room, relaying data between the Belden recognizes that comprehensive know-
control room, the engineering department, how is necessary to ensure an optimized, System Performance
and remote manufacturing sites — or all of the homogenous solution. We also know that If Belden designs it, we guarantee performance
above — Belden has the products you need to consultation, support and training requires — period. We are committed to ensuring world-
seamlessly connect your communications. more than just a general understanding of class signal connectivity and to significantly
the products, technologies and market trends. improve your operational up-time. All
From the petrochemical, automotive,
It requires a solid understanding of the Belden components are “designed” to deliver
pharmaceutical, power generation, pulp
application and the ability to provide the type optimum performance: from connectors, to
and paper, metals, food and beverage, or
of support that is needed — when and where it cable, to routers and switches. Based on this
general manufacturing plant to the corporate
is needed. It requires the four key service and comprehensive product portfolio, we have the
headquarters — and everywhere in between —
support areas that are critical to success: necessary industrial solutions DNA to deliver
Belden has your signal transmission solution.
Belden offers the most dependable network and reliability.
• Network Design
communications system performance in tough For more information on our service and
• Training
and mission-critical environments. support offering, including our warranties,
• Technical Support please go to the Belden web site at
Our Synergy Ensures • System Performance www.belden.com/industrial to locate
Continuous Performance a Belden sales representative near you.
Network Design
With the Hirschmann™ and Lumberg
Automation™ product line additions to Belden eliminates your design challenges
the Belden offering, our line of Complete because we understand the issues surrounding
Industrial Solutions is uniquely positioned to the design and operation of networks in
provide the best network and communications industrial and mission-critical environments.
infrastructure possible. Belden products and Our engineers are available to work with you
systems expertise means that you can maintain to deliver high-availability networks that
ongoing operations without interruption and meet your enterprise-wide IT needs. Whether
costly downtime — in any environment. it’s designing systems for Greenfield facilities,
or integrating into existing industrial IT
environments, our highly-trained staff lifts the
design burden from your shoulders to ours.

www.lumberg-automationusa.com 1-717-217-2299 3
The Lumberg Automation™ Brand Sets the Standard for Quality, Reliability and Service.

Re-Useable Solutions Reliability is Maximized


OEM’s now have access to a set of standard Enclosure~less™ solutions can minimize wiring
products designed around the concept that errors because wiring is pre-manufactured with
everything is pluggable and interchangeable. quick-disconnect features. With less manual
wiring involved, there are fewer points of
Having the flexibility to re-configure or
failure.
expand an existing system without worrying
about customization is made possible with our Some studies suggest that a large portion of
Enclosure~less concept. Most importantly, our system failures come from installation rather
products are re-usable and can be adapted to than part failures. The decrease in errors
future designs or merely put back on the shelf associated with pre-manufactured wiring leads
for future use. to an increase in the overall reliability of the
control system.
About Our Solutions Improved Installation Time with
In the end, this helps speed installation and
Today, more than ever, manufacturing Less Mistakes
commissioning, maintenance, troubleshooting,
productivity depends upon seamless data A recent study by a group of European and ultimately boosts a plant’s production.
communication and automation systems. manufacturers concluded that Enclosure~less
Lumberg Automation has assembled one of assembly costs save as much as 30 percent over Maintenance/Repair Time is Reduced
the most diversified portfolios for industrial conventional installation methods.
connectivity and distributed I/O systems for Maintenance technicians and operators no
control applications. These savings are realized through not only the longer need to access the control panel since
Enclosure~less concept, but by the technology much of the maintenance and troubleshooting
With the advancements in technology and that is being employed. With a modular design can be done outside.
improved machine designs, industrial controls, approach and plug-and-play electronic features,
such as sensors, actuators, safety light curtains, With the simplicity of wiring layout and
less time will be spent running down errors or
pushbutton switches and the like are moving connections, end users can efficiently isolate
replacing parts from incorrect wiring.
closer to the application. problems and replace a starter or I/O locally,
rather than sorting through a complex panel.
Trouble-Shooting is Simplified
Our Enclosure~less™ Concept The result is significantly easier troubleshooting
Troubleshooting circuits can be a long process, and shorter Mean-Time-To-Repair (MTTR).
The Enclosure~less concept from Lumberg especially when one is dealing with several
Automation addresses these applications hundred termination points. Floor Space at a Premium
with an entire suite of industrial hardened
connectivity and distributed I/O products. Many of our products have integrated LED Control cabinets can occupy a substantial
function indicators which provide a visual amount of the production floor. The
Enhanced environmental characteristics, notification that a circuit is functioning Enclosure~less™ concept dramatically reduces
modular designs, plug-and-play electronics properly. the need for that real estate, allowing
with quick-disconnect designs are all integrated companies to leverage more of their facility.
to increase speed of installation, decrease By using products that have integrated LED
troubleshooting and maintenance while functions, mechanics and engineers alike can Industries like semiconductor and
reducing the overall complexity of the control quickly isolate and resolve the problem. pharmaceutical manufacturing have realized
application. These products provide the optimal the benefits of the On-Machine approach
solution in machine and equipment design and Testing Made Simple for years, as their clean-room space is at a
offer excellent opportunities and benefits to premium.
OEMs can cost-effectively build and pre-test
OEMs, system integrators, and end users alike. a machine at their facility, disassemble and
transport it to an end user’s plant knowing that
Easing the Design Process everything has been tested. This is primarily
Our system approach leads to decreased time made possible through the reduction of wiring
and money to develop complete integrated terminations throughout the system, which
connectivity solutions. Using our Enclosure~less makes testing a much simpler and quicker
concept is one of the most effective ways to process.
dramatically reduce the design time.

4 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

Table of Contents

Table of Contents
About Belden® Industrial Solutions ...................................................................................................... 3
About Our Solutions ............................................................................................................................. 4
AS-Interface Introduction ..................................................................................................................... 6-7

AS-Interface Fieldbus Solutions 8-94


AS-Interface Input/Output Modules ................................................................................................... 8-41
4 Inputs ................................................................................................................................................ 8-13
8 Inputs ................................................................................................................................................ 14-15
4 Outputs.............................................................................................................................................. 16-19
8 Outputs.............................................................................................................................................. 20-21
2 Inputs / 2 Outputs .............................................................................................................................. 22-25
4 Inputs / 3 Outputs .............................................................................................................................. 26-27
4 Inputs / 4 Outputs .............................................................................................................................. 28-39
Passive Modules ................................................................................................................................... 40-41
AS-Interface Junction Branches ........................................................................................................ 42
Accessories......................................................................................................................................... 43-47
Part Number Index .............................................................................................................................. 48

www.lumberg-automationusa.com 1-717-217-2299 5
AS-Interface Introduction

Common Industrial Protocol


AS-i (Actuator Sensor Interface) was designed
as a simple system for the quick data exchange
of binary signals. Research, spawned by market
AS-Interface Modules demands, has made it possible to transmit
analog data as well (also see “The new AS-i-
with Plug-N-Play specification V2.1”). That data, however, must
not be time-critical, since the transmission of
Connectivity Reduce an analog value requires several data cycles
The biggest advantage of AS-i is the quick
Overall Installation and and uncomplicated installation of the system.
Communication (Manchester Encoding) and
Maintenance Costs. power supply are transmitted via a 2-wire cable.
By using piercing technology for contacting the
cable it is possible to insert a new slave at any
point in the system. In addition, the arbitrary
structure of the bus (line, tree, star, ...) permits
the perfect adaptation to the relevant plant or
machine.
AS-i is mainly used for small machines, as a
subsystem for more complex bus systems (e.g.
PROFIBUS-DP) or as an easy introduction to bus
technology. AS-i Module dipicted with flat cabel and M12 field
attachable connectors and junctions.
AS-Interface is an open standard. Thus, it is
possible to operate different bus participants
made by different manufacturers in one Network Topology
network. The bus can be built arbitrarily (line, star, tree,
...). Terminating resistors are not required.
About Lumberg Automation
AS-i Products Bus Access
Lumberg Automation remains true to the AS-i • Monomaster system
easy installation concept and offers compact, • Master-slave access
solid module technology to the customer. The
IP67 components have been designed to use Number of Slaves
directly on machines.
• 31 slaves by using standard slaves
The flat cable shown below is commonly used • 62 slaves by using A/B slaves with profile 2.1
with AS-i. However, for some applications such
as C-tracks, Lumberg provides connections for Standard Transmission Rates and
round cable for all modules as well. Segment Lengths

Technical Data • Transmission rate: 167 kbaud

Transmission media: Unshielded 2-wire cable for • Max. segment length: 100 m Bus cycle time
power supply (module electronics and sensors) • Standard slaves max. 5 ms in case of full
and data transmission (Manchester Encoding arrangement (31 slaves)
and optionally mechanically encoded flat or
• Just A or B slave per address max. 5 ms in case
round cable.
of full arrangement (31 slaves)
• A and B slave per address max. 10 ms in case
of full arrangement (62 slaves)

6 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

Addressing Transmission Rate AS-i Specification AS-i Specification


AS-i slaves are generally addressed via software Version 2.0 Version 2.1
(the default address is generally “0” for all AS-i
Slave Standard A/B Slave
slaves). This can be done in several ways:
Max. Number of Slaves 31 64
• Via the master: The slaves are connected
to the master consecutively. The latter Max. Number of Inputs 4 Inputs x 31 slaves = 124 Inputs 4 Inputs x 62 slaves = 248 Inputs
automatically identifies the kind of slave and
starts communicating. Then the slave can be Max. Number of Outputs 4 Outputs x 31 slaves = 124 Outputs 3 Outputs x 62 slaves = 186 Outputs
(one output is needed for the A/B addressing)
addressed.
Cycle Time 5ms for 31 slaves 10ms for 62 slaves
• Via an addressing unit: All AS-i slaves can
be addressed with the standard addressing Analog Value Processing via functional blocks integrated in the master
unit “0913 ATL 003” (the Lumberg flat cable
modules require the adapter “0913 ATL 002
Table 1: Admissable transmission rates
/ 0.35M”; modules according to profile 2.1
require the adapter“ 0913 ATL 004 / 1 M).
• Automatic addressing: If a slave in a network Product Characteristics
fails, AS-i offers the option of auto-
addressing. The defective slave is replaced by
an identical one. The master identifies this Especially suitable for robotic applications (resistance to torsion).
slave and automatically addresses it to the
address of the missing slave. Very good resistance to oils, coolants and lubricants as well as emulsions.
Diagnostic system
Suitable for use in C-Tracks.
According to the AS-i specification 2.1 periphery
errors like short circuit or overload can be sent to Very good resistance to flying weld slag (e.g.) unfinished constructions).
the master in the form of a collective diagnostic.
In addition, there is a status LED on the relevant
slave. Very good resistance to acids, lye and chemical cleaning agents.

The New AS-i Specification Version 2.1 Very good electromagnetic resistance (EMC) and shieldedsystems.
With the introduced AS-i specification V. 2.1
Very good vibration and shock resistance.
some innovations have been integrated into the
AS-i system. The most important alteration is the
possibility to operate 62 (instead of 31) slaves UL approved.
in one network. This became possible by the
introduction of a differentiation between A and B UL/CSA approved.
slaves (e.g. 1A + 1B). To achieve that, the system
had to be designed with one output per slave less
(max. 4I/3O).
The new specification is downward compatible,
and old AS-i slaves can be operated in one
network together with new ones. In addition
to that, the processing of analog values was
improved. The transmission of analog values are
integrated in the master. This means that specific
function blocks need not be used any more.

Integrated AS-i application.

www.lumberg-automationusa.com 1-717-217-2299 7
AS-Interface Module with 4-Digital Inputs

0910 ASL 501 4 IN


AS-interface module with 4 digital inputs
to connect M8 standards sensors, M8 bus
connection.

– Version 2.1 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input 1..4 yellow channel status


Byte 0 - - - - I-4 I-3 I-2 I-1 green slave is involved in data transfer
red communications error, no data transfer (e.g., slave
address 0)
AS-i-DIA red flashing periphery error (e.g., sensor supply overload or
short circuit

Pin Assignment
Bus Connection M8 Input M8

1 = AS-interface + 1 = +24 V
2 = AS-interface - 2 = GND (0 V)
4 = n.c. 4 = IN

8 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Inputs


0910 ASL 501

Technical Data
Environmental
Degree of protection IP 67
Operating temperature range -15°C (+5°F) to +60°C (+140°F)
Weight 100 g
Housing material PUR

Bus system AS-Interface Version 2.1


AS-Interface profile S 0.A.E
I/O configuration 0 hex
ID code A hex
ID2 code (extended ID-code) E hex
Support A/B addressing yes

Electronics power supply AS-Interface


Rated voltage AS-Interface net
Voltage range 26.5–31.6 V DC
Power consumption max. 120 mA
Reverse polarity protection yes
Indication LED green

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 11 V / Is > 6 mA
Signal state “0” Is < 2 mA
Input current at 24 V 15 mA
Input circuit p-switching
Number of digital channels 4
Channel status indicator LED yellow per channel

Diagnostic
Indication LED red

Connection via cordset, double-ended


M8 / M8 e.g. RSMV-RKMV (please see product group cordsets, double-ended)
Included in delivery / Accessories
Dust covers M8 2 pieces
Attachable label 1 piece

Part Number

0910 ASL 501

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 9
AS-Interface Module with 4-Digital Inputs

0910 ASL 409 4 IN


AS-Interface flat cable module with 4 digital
inputs to connect standard sensors, combined
M12 socket, infrared interface for the
addressing.

– Version 2.1 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input I-1..4 yellow channel status


Byte 0 - - - - I-4 I-3/4 I-2 I-1/2 U-AS-i green AS-Interface power supply active
red communication error
FID
red flashing periphery error 9sensor/actuator short circuit

Pin Assignments
Input 1 M12 Input 2 M12 Input 3 M12 Input 4 M12
1 = +24 V 1 = +24 V 1 = +24 V 1 = +24 V
2 = IN 2 2 = n.c. 2 = IN 4 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = IN 1 4 = IN 2 4 = IN 3 4 = IN 3
5 = earth 5 = earth 5 = earth 5 = earth

The connection to earth for the inputs is implemented via the earthing contacts at the fastening holes.

10 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Inputs


0910 ASL 409

Technical Data Note


Environmental The input channels are connected together. That allows a greater connection
Degree of protection IP 67 flexibility (see pin assignment). In case of connection of a two-channel sensor to
Operating temperature range -25°C (-13°F) to +80°C (+176°F) input socket 1 or 3 a further sensor must not be plugged to input socket 2 or 4
Weight 200 g respectively due to the Y wiring of the inputs.
Housing material PUR

Bus system AS-Interface Version 2.1


AS-Interface profile S 0.A.E
I/O configuration 0 hex
ID code A hex
ID2 code (extended ID-code) E hex
Support A/B addressing yes

Electronics power supply AS-Interface


Rated voltage AS-Interface net
Voltage range 26.5–31.6 V DC
Power consumption max. 250 mA
Reverse polarity protection yes
Indication LED green

Input power supply


Voltage range (AS-Interface net) 17–30 V
Total current of all sensors max. 200 mA
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 11 V / Is > 6 mA
Signal state “0” Is < 2 mA
Input current at 15 mA
Input circuit p-switching
Number of digital channels 4
Channel status indicator LED yellow per channel

Diagnostic
Indication LED red

Included in delivery / Accessories


Dust covers M12 2 pieces
Attachable label 10 pieces

Part Number

0910 ASL 409

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 11
AS-Interface Module with 4-Digital Inputs

0910 ASL 132 4 IN


AS-Interface module with 4 digital inputs
to connect standard sensors, combined M12
socket, M12 bus connection.

– Replaces module 0910 ASL 112 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input I-1..4 yellow channel status


Byte 0 - - - - I-4 I-3 I-2 I-1 U-AS-i green AS-Interface power supply active

Pin Assignments
Bus connection M12 Input M12
1 = AS-Inerface + 1 = +24 V
2 = n.c. 2 = IN
3 = AS-Interface - 3 = GND (0 V)
4 = n.c. 4 = IN
5 = n.c.

12 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Inputs


0910 ASL 132

Technical Data Connection via cordset, double-ended


M12 / M12 0915 034 101/... M
Environmental
Degree of protection IP 67
Included in delivery / Accessories
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Dust covers M12 2 pieces
Weight 200 g
Attachable label 10 pieces
Housing material PUR

Bus system AS-Interface Version 2.1


AS-Interface profile S 0.A.E
I/O configuration 0 hex
ID code 0 hex
ID2 code (extended ID-code) F hex
Support A/B addressing yes

Electronics power supply AS-Interface


Rated voltage AS-Interface net
Voltage range 26.5–31.6 V DC
Power consumption max. 250 mA
Reverse polarity protection yes
Indication LED green

Input power supply


Voltage range (AS-Interface net) 17–30 V
Total current of all sensors max. 200 mA
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 11 V / Is > 6 mA
Signal state “0” Is < 2 mA
Input current at 15 mA
Input circuit p-switching
Number of digital channels 4
Channel status indicator LED yellow per channel

Diagnostic
Indication LED red

Part Number

0910 ASL 132

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 13
AS-Interface Module with 8-Digital Inputs

0910 ASL 412 8 IN


AS-Interface flat cable modulewith 8 digital
inputs to connect standard sensors, combined
M12 socket, infrared interface for the
addressing.

– Version 2.1 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input I-1..4 yellow channel status


Byte 0 / Slave 1 - - - - I-4 I-3 I-2 I-1 U-AS-i green AS-Interface power supply active
Byte 1 / Slave 2 I-4 I-3 I-2 I-1 red communication error
FID
red flashing periphery errot (sensor/actuator short circuit

Pin Assignments
Input 1 M12 Input 2 M12 Input 3 M12 Input 4 M12
1 = +24 V 1 = +24 V 1 = +24 V 1 = +24 V
2 = IN 2 2 = n.c. 2 = IN 4 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = IN 1 4 = IN 2 4 = IN 3 4 = IN 4
5 = earth 5 = earth 5 = earth 5 = earth

The connection to earth for the inputs is implemented via the earthing contacts at the fastening holes.

14 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 8-Digital Inputs


0910 ASL 412

Technical Data
Environmental
Note
Degree of protection IP 67
Operating temperature range -25°C (-13°F) to +80°C (+176°F) The input channels are connected together. That allows a greater connection
Weight 300 g flexibility (see pin assignment). In case of connection of a two-channel sensor to
Housing material PUR input socket 1 or 3 a further sensor must not be plugged to input socket 2 or 4
respectively due to the Y wiring of the inputs.
Bus system AS-Interface Version 2.1
AS-Interface profile S 0.A.E
I/O configuration 0 hex
ID code 1 hex
ID2 code (extended ID-code) E hex
Support A/B addressing yes

Electronics power supply AS-Interface


Rated voltage AS-Interface net
Voltage range 26.5–31.6 V DC
Power consumption max. 500 mA
Reverse polarity protection yes
Indication LED green

Input power supply


Voltage range (AS-Interface net) 17–30 V
Total current of all sensors max. 200 mA
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 11 V / Is > 6 mA
Signal state “0” Is < 2 mA
Input circuit p-switching
Number of digital channels 8
Channel status indicator LED yellow per channel

Diagnostic
Indication LED red

Included in delivery / Accessories


Dust covers M12 2 pieces
Attachable label 10 pieces

Part Number

0910 ASL 412

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 15
AS-Interface Module with 4-Digital Outputs

0910 ASL 403 4 OUT


AS-Interface flat cable module with 4 digital
outputs to connect standard actuators,
combined M12 socket.

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Output O-1..4 yellow channel status


Byte 0 - - - - O-4 O-3 O-2 O-1 U-AS-i green AS-Interface power supply active
AUX green actuator supply active

Pin Assignments
Output M12
1 = n.c.
2 = n.c.
3 = GND (0 V)
4 = OUT
5 = earth

16 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Outputs


0910 ASL 403

Technical Data
Environmental
Degree of protection IP 67
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Weight 200 g
Housing material PUR

Bus system AS-Interface


AS-Interface profile 8.0
I/O configuration 8 hex
ID code 0 hex
Support A/B addressing no

Electronics power supply AS-Interface


Rated voltage AS-Interface net
Voltage range 26.5–31.6 V DC
Power consumption max. 75 mA
Reverse polarity protection yes
Indication LED green

Output power supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Outputs Type 2 A acc. to IEC 61131-21-2


Rated output current 2 A per channel
Short circuit-proof yes
Max. output current 4 A per module
Overload-proof yes
Number of digital channels 4
Channel type N.O. p-switching
Channel status indicator LED yellow per channel

Included in delivery / Accessories


Dust covers M12 2 pieces
Attachable label 10 pieces

Part Number

0910 ASL 403

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 17
AS-Interface Module with 4-Digital Outputs

0910 ASL 133 4 OUT


AS-Interface module with 4 digital outputs to
connect standard actuators, combined M12
socket, M12 bus connection.

– Replaces module 0910 ASL 111 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Output O-1..4 yellow channel status


Byte 0 - - - - O-4 O-3 O-2 O-1 U-AS-i green AS-Interface power supply active
AUX green actuator supply active

Pin Assignments
Bus connection M12 Output M12
1 = AS-Inerface + 1 = n.c.
2 = 0 V AUX 2 = n.c.
3 = AS-Interface - 3 = GND (0 V)
4 = +24 V AUX 4 = OUT
5 = earth

18 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Outputs


0910 ASL 133

Technical Data Connection via cordset, double-ended


M12 / M12 0915 034 101/... M
Environmental
Degree of protection IP 67
Included in delivery / Accessories
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Dust covers M12 2 pieces
Weight 200 g
Attachable label 10 pieces
Housing material PUR

Bus system AS-Interface


AS-Interface profile S 8.0.F
I/O configuration 8 hex
ID code 0 hex
ID2 code (extended ID-code) F hex
Support A/B addressing no

Electronics power supply AS-Interface


Rated voltage AS-Interface net
Voltage range 26.5–31.6 V DC
Power consumption max. 75 mA
Reverse polarity protection yes
Indication LED green

Output power supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Outputs Type 2 A acc. to IEC 61131-21-2


Rated output current 2 A per channel
Short circuit-proof yes
Max. output current 4 A per module
Overload-proof yes
Number of digital channels 4
Channel type N.O. p-switching
Channel status indicator LED yellow per channel

Part Number

0910 ASL 133

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 19
AS-Interface Module with 8-Digital Outputs

0910 ASL 419 8 OUT


AS-Interface flat cable module with 8 digital
outputs (0.5 A, Y connected) to connect
standard actuators, combined M12 socket,
infrared interface for the addressing.

– Version 2.1 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input O-1..4 yellow channel status


Byte 0 / Slave 1 - - - - O-4 0-3 O-2 0-1 U-AS-i green AS-Interface power supply active
Byte 1 / Slave 2 O-4 0-3 O-2 0-1 AUX green actuator supply active
red communication error
FID
red flashing periphery error (actuator short circuit)

Pin Assignments
Output 1 M12 Output 2 M12 Output 3 M12 Output 4 M12
1 = n.c. 1 = n.c. 1 = n.c. 1 = n.c.
2 = OUT 2 2 = n.c. 2 = OUT 4 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = OUT 1 4 = OUT 2 4 = OUT 3 4 = OUT 4
5 = earth 5 = earth 5 = earth 5 = earth

The connection to earth for the outputs is implemented via the earthing contacts at the fastening holes.

20 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 8-Digital Outputs


0910 ASL 419

Technical Data Note


Environmental The output channels are connected together. That allows a greater connection
Degree of protection IP 67 flexibility (see pin assignment). When actuators are connected, this Y wiring
Operating temperature range -25°C (-13°F) to +80°C (+176°F) of the terminal sockets has to be taken into consideration with respect to
Weight 300 g current load.
Housing material PUR

Bus system AS-Interface Version 2.1


AS-Interface profile S 8.1.E
I/O configuration 8 hex
ID code 1 hex
ID2 code (extended ID-code) E hex
Support A/B addressing no

Electronics power supply AS-Interface


Rated voltage AS-Interface net
Voltage range 26.5–31.6 V DC
Power consumption max. 75 mA
Reverse polarity protection yes
Indication LED green

Output power supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Outputs Type 0.5 A acc. to IEC 61131-2


Rated output current 0.5 A per channel
Short circuit-proof yes
Max. output current 4 A per module
Overload-proof yes
Number of digital channels 8
Channel type N.O. p-switching
Channel status indicator LED yellow per channel

Included in delivery / Accessories


Dust covers M12 2 pieces
Attachable label 10 pieces

Part Number

0910 ASL 419

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 21
AS-Interface Module with 2-Digital Inputs and 2-Digital Outputs

0910 ASL 410 2 IN / 2 OUT


AS-Interface flat cable module with 2 digital
inputs to connect standard sensors and 2
digital outputs to connect standard actuators,
combined M12 socket, infrared interface for the
addressing.

– Version 2.1 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input O-1..4 / O-3..4 yellow channel status


U-AS-i green AS-Interface power supply active
Byte 0 - - - - - - I-2 I-1/2
AUX green actuator supply active
M12 Output
red communication error
Byte 0 - - - - O-4 O-3 - - FID
red flashing periphery error (actuator short circuit)

Pin Assignments
Input 1 M12 Input 2 M12 Output 3 M12 Output 4 M12
1 = +24 V 1 = +24 V 1 = n.c. 1 = n.c.
2 = IN 2 2 = n.c. 2 = n.c. 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = IN 1 4 = IN 2 4 = OUT 3 4 = OUT 4
5 = earth 5 = earth 5 = earth 5 = earth

The connection to earth for the inputs and outputs is implemented via the earthing contacts at the fastening holes.

22 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 2-Digital Inputs and 2-Digital Outputs


0910 ASL 410

Technical Data Outputs Type 2 A acc. to IEC 61131-2


Rated output current 2 A per channel
Environmental
Short circuit-proof yes
Degree of protection IP 67
Max. output current 4 A per module
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Overload-proof yes
Weight 200 g
Number of digital channels 2
Housing material PUR
Channel type N.O. p-switching
Bus system AS-Interface Version 2.1 Channel status indicator LED yellow per channel
AS-Interface profile S 3.F.E
Diagnostic
I/O configuration 3 hex
Indication LED red
ID code F hex
ID2 code (extended ID-code) E hex
Included in delivery / Accessories
Support A/B addressing no
Dust covers M12 2 pieces
Attachable label 10 pieces
Electronics power supply AS-Interface
Rated voltage AS-Interface net
Note
Voltage range 26.5–31.6 V DC
Power consumption max. 250 mA The input channels are connected together. That allows a greater connection
Reverse polarity protection yes flexibility (see pin assignment). In case of connection of a two-channel sensor
Indication LED green to input socket 1 a further sensor must not be plugged to input socket 2
respectively due to the Y wiring of the inputs.
Input power supply
Voltage range (AS-Interface net) 17–30 V
Total current of all sensors max. 200 mA
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 11 V / Is > 6 mA
Signal state “0” Is < 2 mA
Input current at 24 V 15 mA
Input circuit p-switching
Number of digital channels 2
Channel status indicator LED yellow per channel

Output power supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Part Number

0910 ASL 410

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 23
AS-Interface Module with 2-Digital Inputs and 2-Digital Outputs

0910 ASL 134 2 IN / 2 OUT


AS-Interface module with 2 digital inputs to
connect standard sensors and 2 digital outputs
to connect standard actuators, combined M12
socket, M12 bus connection.

– Replaces module 0910 ASL 110 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input O-1..4 / O-3..4 yellow channel status


U-AS-i green AS-Interface power supply active
Byte 0 - - - - - - I-2 I-1/2
AUX green actuator supply active
M12 Output

Byte 0 - - - - O-4 O-3 - -

Pin Assignments
Bus connection M12 Input M12 Output M12
1 = AS-Inerface + 1 = +24 V 1 = n.c.
2 = 0 V AUX 2 = IN 2 = n.c.
3 = AS-Interface - 3 = GND (0 V) 3 = GND (0 V)
4 = +24 V AUX 4 = IN 4 = OUT
5 = n.c. 5 = earth

24 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 2-Digital Inputs and 2-Digital Outputs


0910 ASL 134

Technical Data Outputs Type 2 A acc. to IEC 61131-2


Rated output current 2 A per channel
Environmental
Short circuit-proof yes
Degree of protection IP 67
Max. output current 4 A per module
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Overload-proof yes
Weight 200 g
Number of digital channels 2
Housing material PUR
Channel type N.O. p-switching
Bus system AS-Interface Version 2.1 Channel status indicator LED yellow per channel
AS-Interface profile S 3.F.E
Diagnostic
I/O configuration 3 hex
Indication LED red
ID code 0 hex
ID2 code (extended ID-code) F hex
Connection via cordset, double-ended
Support A/B addressing no
M12 / M12 0915 034 101/... M
Electronics power supply AS-Interface
Included in delivery / Accessories
Rated voltage AS-Interface net
Dust covers M12 2 pieces
Voltage range 26.5–31.6 V DC
Attachable label 10 pieces
Power consumption max. 250 mA
Reverse polarity protection yes
Indication LED green

Input power supply


Voltage range (AS-Interface net) 17–30 V
Total current of all sensors max. 200 mA
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 11 V / Is > 6 mA
Signal state “0” Is < 2 mA
Input current at 24 V 15 mA
Input circuit p-switching
Number of digital channels 2
Channel status indicator LED yellow per channel

Output power supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Part Number

0910 ASL 134

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 25
AS-Interface Module with 4-Digital Inputs and 3-Digital Outputs

0910 ASL 414 4 IN / 3 OUT


AS-Interface module with 2 digital inputs to
connect standard sensors and 2 digital outputs
to connect standard actuators, combined M12
socket, M12 bus connection.

– Version 2.1 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input O-1..4 / O-3..4 yellow channel status


AS-i green AS-Interface power supply active
Byte 0 - - - - I-4 I-3/4 I-2 I-1/2
AUX green actuator supply active
M12 Output
red communication error
Byte 0 - - - - - O-3 O-2 O-1 FID red flashing periphery error (actuator short circuit/sensor supply
error)

Pin Assignments
Input 1 M12 Input 2 M12 Input 3 M12 Input 4 M12
1 = +24 V 1 = +24 V 1 = +24 V 1 = +24 V
2 = IN 2 2 = n.c. 2 = IN 4 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = IN 1 4 = IN 2 4 = IN 3 4 = IN 4
5 = earth 5 = earth 5 = earth 5 = earth

Output 1 M12 Output 2 M12 Output 3 M12


1 = n.c. 1 = n.c. 1 = n.c.
2 = n.c. 2 = n.c. 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = OUT 1 4 = OUT 2 4 = OUT 3
5 = earth 5 = earth 5 = earth

The connection to earth for the outputs is implemented via the earthing contacts at the fastening holes.

26 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Inputs and 3-Digital Outputs


0910 ASL 414

Technical Data Outputs Type 2 A acc. to IEC 61131-2


Rated output current 2 A per channel
Environmental
Short circuit-proof yes
Degree of protection IP 67
Max. output current 4 A per module
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Overload-proof yes
Weight 300 g
Number of digital channels 3
Housing material PUR
Channel type N.O. p-switching
Bus system AS-Interface Version 2.1 Channel status indicator LED yellow per channel
AS-Interface profile S 7.A.E
Diagnostic
I/O configuration 7 hex
Indication LED red
ID code A hex
ID2 code (extended ID-code) E hex
Included in delivery / Accessories
Support A/B addressing yes
Dust covers M12 2 pieces
Attachable label 10 pieces
Electronics power supply AS-Interface
Rated voltage AS-Interface net
Note
Voltage range 26.5–31.6 V DC
Power consumption max. 100 mA The input channels are connected together. That allows a greater connection
Reverse polarity protection yes flexibility (see pin assignment). In case of connection of a two-channel sensor to
Indication LED green input socket 1 or 3 a further sensor must not be plugged to input socket 2 or 4
respectively due to the Y wiring of the inputs.
Input power supply
Voltage range (AS-Interface net) 17–30 V
Total current of all sensors max. 100 mA
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 10 V / Is > 4.7 mA
Signal state “0” Is < 1.5 mA
Input current at 24 V 15 mA
Input circuit p-switching
Number of digital channels 4
Channel status indicator LED yellow per channel

Output power supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Part Number

0910 ASL 414

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 27
AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs

0910 ASL 408 4 IN / 4 OUT


AS-Interface flat cable module with 4 digital
inputs to connect standard sensors and 4
digital outputs to connect standard actuators,
combined M12 socket, infrared interface for the
addressing.

– Version 2.1 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input O-1..4 / O-3..4 yellow channel status


AS-i green AS-Interface power supply active
Byte 0 - - - - I-4 I-3/4 I-2 I-1/2
AUX green actuator supply active
M12 Output
red communication error
Byte 0 - - - - O-4 O-3 O-2 O-1 FID
red flashing periphery error (actuator short circuit)

Pin Assignments
Input 1 M12 Input 2 M12 Input 3 M12 Input 4 M12
1 = +24 V 1 = +24 V 1 = +24 V 1 = +24 V
2 = IN 2 2 = n.c. 2 = IN 4 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = IN 1 4 = IN 2 4 = IN 3 4 = IN 4
5 = earth 5 = earth 5 = earth 5 = earth

Output 1 M12 Output 2 M12 Output 3 M12 Output M12


1 = n.c. 1 = n.c. 1 = n.c. 1 = n.c.
2 = n.c. 2 = n.c. 2 = n.c. 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = OUT 1 4 = OUT 2 4 = OUT 3 4 = OUT 4
5 = earth 5 = earth 5 = earth 5 = earth

The connection to earth for the inputs and outputs is implemented via the earthing contacts at the fastening holes.

28 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs


0910 ASL 408

Technical Data Outputs Type 2 A acc. to IEC 61131-2


Rated output current 2 A per channel
Environmental
Short circuit-proof yes
Degree of protection IP 67
Max. output current 4 A per module
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Overload-proof yes
Weight 300 g
Number of digital channels 4
Housing material PUR
Channel type N.O. p-switching
Bus system AS-Interface Version 2.1 Channel status indicator LED yellow per channel
AS-Interface profile S 7.A.E
Diagnostic
I/O configuration 7 hex
Indication LED red
ID code F hex
ID2 code (extended ID-code) E hex
Included in delivery / Accessories
Support A/B addressing yes
Dust covers M12 2 pieces
Attachable label 10 pieces
Electronics power supply AS-Interface
Rated voltage AS-Interface net
Note
Voltage range 26.5–31.6 V DC
Power consumption max. 250 mA The input channels are connected together. That allows a greater connection
Reverse polarity protection yes flexibility (see pin assignment). In case of connection of a two-channel sensor to
Indication LED green input socket 1 or 3 a further sensor must not be plugged to input socket 2 or 4
respectively due to the Y wiring of the inputs.
Input power supply
Voltage range (AS-Interface net) 17–30 V
Total current of all sensors max. 200 mA
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 11 V / Is > 6 mA
Signal state “0” Is < 2 mA
Input current at 24 V 15 mA
Input circuit p-switching
Number of digital channels 4
Channel status indicator LED yellow per channel

Output power supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Part Number

0910 ASL 408

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 29
AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs

0910 ASL 135 4 IN / 4 OUT


AS-Interface module with 4 digital inputs to
connect standard sensors and 4 digital outputs
to connect standard actuators, combined M12
socket, M12 bus connection.

– Replaces module 0910 ASL 109 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input O-1..4 / O-4..4 yellow channel status


U-AS-i green AS-Interface power supply active
Byte 0 - - - - I-4 I-3 I-2 I-1
AUX green actuator supply active
M12 Output

Byte 0 - - - - O-4 O-3 O-2 O-1

Pin Assignments
Bus connection M12 Input M12 Output M12
1 = AS-Inerface + 1 = +24 V 1 = n.c.
2 = 0 V AUX 2 = IN 2 = n.c.
3 = AS-Interface - 3 = GND (0 V) 3 = GND (0 V)
4 = +24 V AUX 4 = IN 4 = OUT
5 = n.c. 5 = earth

30 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs


0910 ASL 135

Technical Data Outputs Type 2 A acc. to IEC 61131-2


Rated output current 2 A per channel
Environmental
Short circuit-proof yes
Degree of protection IP 67
Max. output current 4 A per module
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Overload-proof yes
Weight 200 g
Number of digital channels 4
Housing material PUR
Channel type N.O. p-switching
Bus system AS-Interface Version 2.1 Channel status indicator LED yellow per channel
AS-Interface profile S 7.A.E
Diagnostic
I/O configuration 7 hex
Indication LED red
ID code 0 hex
ID2 code (extended ID-code) F hex
Connection via cordset, double-ended
Support A/B addressing yes
M12 / M12 0915 034 101/... M
Electronics power supply AS-Interface
Included in delivery / Accessories
Rated voltage AS-Interface net
Dust covers M12 2 pieces
Voltage range 26.5–31.6 V DC
Attachable label 10 pieces
Power consumption max. 250 mA
Reverse polarity protection yes
Indication LED green

Input power supply


Voltage range (AS-Interface net) 17–30 V
Total current of all sensors max. 200 mA
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 11 V / Is > 6 mA
Signal state “0” Is < 2 mA
Input current at 24 V 15 mA
Input circuit p-switching
Number of digital channels 4
Channel status indicator LED yellow per channel

Output power supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Part Number

0910 ASL 135

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 31
AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs

0910 ASL 424 4 IN / 4 OUT


AS-Interface module with housing and
receptacle shells in stainless steel, 4 digital
inputs (Y connected) to connect standard
sensors and 4 digital outputs (2 A, Y connected)
to connect standard actuators, M12 bus
connection.

– especially designed for food and


beverage equipment -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input O-1..4 / O-4..4 yellow channel status


AS-i green AS-Interface power supply active
Byte 0 - - - - I-4 I-3/4 I-2 I-1/2
AUX green actuator supply active
M12 Output
red communication error
Byte 0 - - - - O-4 O-3/4 O-2 O-1/2 DIA red flashing periphery error (actuator short circuit/sensor supply
error)

Pin Assignments
Bus connection M12 Input 1 M12 Input 2 M12 Input 3 M12 Input 4 M12
1 = AS-Interface + 1 = +24 V 1 = +24 V 1 = +24 V 1 = +24 V
2 = 0 V AUX 2 = IN 2 2 = n.c. 2 = IN 4 2 = n.c.
3 = AS-Interface - 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = +24 V AUX 4 = IN 1 4 = IN 2 4 = IN 3 4 = IN 4
5 = earth 5 = earth 5 = earth 5 = earth 5 = earth

Output 1 M12 Output 2 M12 Output 3 M12 Output 4 M12


1 = n.c. 1 = n.c. 1 = n.c. 1 = n.c.
2 = OUT 2 2 = n.c. 2 = OUT 4 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = OUT 1 4 = OUT 2 4 = OUT 3 4 = OUT 4
5 = earth 5 = earth 5 = earth 5 = earth

The connection to earth for the outputs is implemented via the earthing contacts at the fastening holes.

32 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs


0910 ASL 424

Technical Data Outputs Type 2 A acc. to IEC 61131-2


Rated output current 2 A per channel
Environmental
Short circuit-proof yes
Degree of protection IP 69K
Max. output current 4 A per module
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Overload-proof yes
Weight 550 g
Number of digital channels 4
Housing material stainless steel
Channel type N.O. p-switching
Bus system AS-Interface Version 2.1 Channel status indicator LED yellow per channel
AS-Interface profile S 7.A.E
Diagnostic
I/O configuration 7 hex
Indication LED red
ID code E hex
ID2 code (extended ID-code) F hex
Included in delivery / Accessories
Support A/B addressing no
Dust covers M12 4 pieces
Electronics power supply AS-Interface
Note
Rated voltage AS-Interface net
Voltage range 26.5–31.6 V DC The input and output channels are connected together. That allows a greater
Power consumption max. 310 mA connection flexibility (see pin assignment). On the input side the special
Reverse polarity protection yes characteristics of the Y wiring with one channel or two-channel sensors has
Indication LED green to be taken into consideration. On the output side the current load has to be
accounted for.
Input power supply
Voltage range (AS-Interface net) 17–30 V
Total current of all sensors max. 200 mA
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 10 V / Is > 4.7 mA
Signal state “0” Is < 1.5 mA
Input current at 24 V 15 mA
Input circuit p-switching
Number of digital channels 4
Channel status indicator LED yellow per channel

Output power supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Part Number

0910 ASL 424

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 33
AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs

0910 ASL 425 4 IN / 4 OUT


AS-Interface module with housing and
receptacle shells in stainless steel, 4 digital
inputs to connect standard sensors and 4 digital
outputs (2 A) to connect standard actuators,
M12 bus connection.

– especially designed for food and


beverage equipment -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition

M12 Input O-1..4 / O-4..4 yellow channel status


AS-i green AS-Interface power supply active
Byte 0 - - - - I-4 I-3 I-2 I-1
AUX green actuator supply active
M12 Output
red communication error
Byte 0 - - - - O-4 O-3 O-2 O-1 DIA red flashing periphery error (actuator short circuit/sensor supply
error)

Pin Assignments
Bus connection M12 Input 1 M12 Input 2 M12 Input 3 M12 Input 4 M12
1 = AS-Interface + 1 = +24 V 1 = +24 V 1 = +24 V 1 = +24 V
2 = 0 V AUX 2 = IN 2 2 = n.c. 2 = n.c. 2 = n.c.
3 = AS-Interface - 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = +24 V AUX 4 = IN 1 4 = IN 2 4 = IN 3 4 = IN 4
5 = earth 5 = earth 5 = earth 5 = earth 5 = earth

Output 1 M12 Output 2 M12 Output 3 M12 Output 4 M12


1 = n.c. 1 = n.c. 1 = n.c. 1 = n.c.
2 = n.c. 2 = n.c. 2 = n.c. 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = OUT 1 4 = OUT 2 4 = OUT 3 4 = OUT 4
5 = earth 5 = earth 5 = earth 5 = earth

The connection to earth for the outputs is implemented via the earthing contacts at the fastening holes.

34 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs


0910 ASL 425

Technical Data Outputs Type 2 A acc. to IEC 61131-2


Rated output current 2 A per channel
Environmental
Short circuit-proof yes
Degree of protection IP 69K
Max. output current 4 A per module
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Overload-proof yes
Weight 550 g
Number of digital channels 4
Housing material stainless steel
Channel type N.O. p-switching
Bus system AS-Interface Version 2.1 Channel status indicator LED yellow per channel
AS-Interface profile S 7.A.E
Diagnostic
I/O configuration 7 hex
Indication LED red
ID code E hex
ID2 code (extended ID-code) F hex
Included in delivery / Accessories
Support A/B addressing no
Dust covers M12 4 pieces
Electronics power supply AS-Interface
Rated voltage AS-Interface net
Voltage range 26.5–31.6 V DC
Power consumption max. 250 mA
Reverse polarity protection yes
Indication LED green

Input power supply


Voltage range (AS-Interface net) 17–30 V
Total current of all sensors max. 200 mA
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 24 V DC
Signal state “1” Us > 10 V / Is > 4.7 mA
Signal state “0” Is < 1.5 mA
Input current at 24 V 15 mA
Input circuit p-switching
Number of digital channels 4
Channel status indicator LED yellow per channel

Output power supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Part Number

0910 ASL 425

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 35
AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs

0910 ASL 146 4 IN / 4 OUT


AS-Interface flat cable module with 4 digital
inputs for 2-wire- or 3-wire sensors and 4
digital outputs to connect standard actuators,
combined FIXCON/M12 socket.

– Version 3.0 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition
M12 Input O-1...4 yellow channel status

Byte 0 - - - - I-4 I-3 I-2 I-1 U-AS-i green AS-Interface power supply active

M12 Output AUX green actuator supply active

Byte 0 - - - - 0-4 O-3 0-2 O-1 DIA red communication error


red flashing periphery error (sensor/actuator short circuit)

Pin Assignments
Input 1 M12 Input 2 M12 Input 3 M12 Input 4 M12
1 = +24 V 1 = +24 V 1 = +24 V 1 = +24 V
2 = IN 2 2 = n.c. 2 = IN 4 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = IN 1 4 = IN 2 4 = IN 3 4 = IN 4
5 = earth 5 = earth 5 = earth 5 = earth

Output 1 M12 Output 2 M12 Output 3 M12 Output 4 M12


1 = n.c. 1 = n.c. 1 = n.c. 1 = n.c.
2 = OUT 2 2 = n.c. 2 = OUT 4 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = OUT 1 4 = OUT 2 4 = OUT 3 4 = OUT 4
5 = earth 5 = earth 5 = earth 5 = earth

AS-i/Aux. PWR In (Plug M12) AS-i/Aux. PWR Out (Socket M12)


1 = AS-i (+) 1 = AS-i (+)
2 = Auxiliary power (-) 2 = Auxiliary power (-)
3 = AS-i (-) 3 = AS-i (-)
4 = Auxiliary power (+) 4 = Auxiliary power (+)
5 = n.c. 5 = n.c.

The connection to earth for the inputs and outputs is implemented via the earthing contacts at the fastening holes.

36 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs


0910 ASL 146

Technical Data
Environmental Outputs Type 2 A acc. to
IEC 61131-2
Degree of protection IP 67 Rated output current 2 A per channel
Temperature range -25°C / +80°C Short circuit-proof yes
Weight 300 g Max. output current 4 A per module
Housing PUR Overload-proof yes
Number of digital channels 4
Bus System AS-Interface V3.0 Channel type N.O. p-switching
AS-Interface profile S 7.A.7 Channel status indicator LED yellow per channel
I/O configuration 7 hex
ID code A hex Diagnostic
ID2 code (extended ID-code) 7 hex Indication LED red
Support A/B addressing yes
Included in delivery / accessories
Electronics Power Supply AS-Interface Dust covers M12 2 pieces
Rated voltage AS-Interface net Attachable labels 10 pieces
Voltage range 26.5–31.6 V DC
Power consumption max. 250 mA Note
Reverse polarity protection yes
The input- and output channels are connected together. That allows a greater
Indication LED green
connection flexibility (see pin assignment). In case of connection of a two-chan-
Input Power Supply nel sensor/actuator to input/output socket 1 or 3 a further sensor/actuator must
Voltage range (AS-Interface net) 17-30 V not be plugged to input/output socket 2 or 4 respectively due to the Y wiring of
Total current of all sensors max. 250 mA the inputs/outputs.
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 2 24 V DC
Signal state “1” Us>11 V / Is > 6 mA
Signal state “0” Is < 2 mA
Input current at 24 V 15 mA
Input circuit p-switching
Number of digital channels 4
Channel status indicator LED yellow per channel

Output Power Supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Part Number

0910 ASL 146 *


* = submitted
The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 37
AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs

0910 ASL 438 4 IN / 4 OUT


AS-Interface flat cable module with 4 digital
inputs for 2-wire or 3-wire sensors and 4
digital outputs to connect standard actuators,
combined FIXCON/M12 socket, infrared
interface for the addressing.

– Version 3.0 -

Bit Assignment Diagnostic Indication


Bit - - - - 3 2 1 0 LED Indication Condition
M12 Input I-1..4/O-1..4 yellow channel status

Byte 0 - - - - I-4 I-3/4 I-2 I-1/2 U-AS-i green AS-Interface power supply active

M12 Output AUX green actuator supply active

Byte 0 - - - - 0-4 O-3/4 0-2 O-1/2 FID red communication error


red flashing periphery error (sensor/actuator short circuit)

Pin Assignments
Input 1 M12 Input 2 M12 Input 3 M12 Input 4 M12
1 = +24 V 1 = +24 V 1 = +24 V 1 = +24 V
2 = IN 2 2 = n.c. 2 = IN 4 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = IN 1 4 = IN 2 4 = IN 3 4 = IN 4
5 = earth 5 = earth 5 = earth 5 = earth

Output 1 M12 Output 2 M12 Output 3 M12 Output 4 M12


1 = n.c. 1 = n.c. 1 = n.c. 1 = n.c.
2 = OUT 2 2 = n.c. 2 = OUT 4 2 = n.c.
3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V) 3 = GND (0 V)
4 = OUT 1 4 = OUT 2 4 = OUT 3 4 = OUT 4
5 = earth 5 = earth 5 = earth 5 = earth

The connection to earth for the inputs and outputs is implemented via the earthing contacts at the fastening holes.

38 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Module with 4-Digital Inputs and 4-Digital Outputs


0910 ASL 438

Technical Data
Environmental Outputs Type 2 A acc. to
IEC 61131-2
Degree of protection IP 67 Rated output current 2 A per channel
Temperature range -25°C / +80°C Short circuit-proof yes
Weight 300 g Max. output current 4 A per module
Housing PUR Overload-proof yes
Number of digital channels 4
Bus System AS-Interface V3.0 Channel type N.O. p-switching
AS-Interface profile S 7.A.7 Channel status indicator LED yellow per channel
I/O configuration 7 hex
ID code A hex Diagnostic
ID2 code (extended ID-code) 7 hex Indication LED red
Support A/B addressing yes
Included in delivery / accessories
Electronics Power Supply AS-Interface Dust covers M12 2 pieces
Rated voltage AS-Interface net Attachable labels 10 pieces
Voltage range 26.5–31.6 V DC
Power consumption max. 250 mA Note
Reverse polarity protection yes
The input- and output channels are connected together. That allows a greater
Indication LED green
connection flexibility (see pin assignment). In case of connection of a two-chan-
Input Power Supply nel sensor/actuator to input/output socket 1 or 3 a further sensor/actuator must
Voltage range (AS-Interface net) 17-30 V not be plugged to input/output socket 2 or 4 respectively due to the Y wiring of
Total current of all sensors max. 250 mA the inputs/outputs.
Short circuit-proof yes

Inputs Type 2 acc. to IEC 61131-2


Rated input voltage 2 24 V DC
Signal state “1” Us>11 V / Is > 6 mA
Signal state “0” Is < 2 mA
Input current at 24 V 15 mA
Input circuit p-switching
Number of digital channels 4
Channel status indicator LED yellow per channel

Output Power Supply AUX


Rated voltage 24 V DC
Voltage range 10–30 V
Potential separation present
Reverse polarity protection yes/electronic
Indication LED green

Part Number

0910 ASL 438 *


* = submitted
The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 39
AS-Interface Passive Modules, 4-Ports

0911 ANC 002 4 Ports / On-Board M23


AS-Interface passive module to connect 4
AS-Interface sensors, AS-Interface actuators
or ASInterface round cable modules, 4 ports,
combined M12 socket with connection for AS-
Interface standard round cables and on-board
M23 connection for aux power.

0911 ANC 403 4 Ports


AS-Interface passive module to connect 4
AS-Interface sensors, AS-Interface actuators
or ASInterface round cable modules, 4 ports,
combined M12 socket, with connection for AS-
Interface standard flat cables.

*a Standard flat cable


* b Additional power supply
(AS-Interface output levles)

Pin Assignments
Bus connection M12 Input 1 M12
1 = earth 1 = AS-Interface +
2 = +24 V 2 = 0 V AUX
3 = GND (0 V) 3 = AS-Interface -
4 = n.c. 4 = +24 V AUX
5 = n.c. 5 = earth
6 = n.c.

40 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Passive Modules, 4-Ports


0911 ANC 002 / 0911 ANC 403

Technical Data
Environmental
Degree of protection IP 67
Operating temperature range -25°C (-13°F) to +80°C (+176°F)
Housing material PUR

Cable Specifications 0911 ANC 002:


PUR/PVC - cable-no. 41
Further information please see
chapter “Cable specifications”

Part Number Outer Jacket Cable lenghts

0911 ANC 002/...M PUR/PVC 5 M / 10 M

0911 ANC 403

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 41
AS-Interface Junction Branches

0911 ANC 101


AS-Interface branch to connect AS-Interface
slaves via a M12 connector with a flat cable
system.

Technical Data
Environmental
Degree of protection IP 65
Housing material PA
Nominal current at 40°C 4A

Note
– insertion of the AS-Interface flat cable (yellow) in
cable shaft “LINE1“
– insertion of the additional voltage supply (black
flat cable) in cable shaft “LINE 2“

0911 ANC 401


AS-Interface branch to connect two flat
cables (opening of an AS-Interface branch or
additional voltage supply).

Technical Data
Environmental
Degree of protection IP 65
Housing material PA
Nominal current at 40°C 8A

Note
Please be aware that only two wires with the same
function may be inserted into this AS-Interface
branch. This means that either only the yellow or
only the black AS-Interface flat cable may be used.
Pin Assignments
Cable M12 - 5 Poles
1 = AS-Interface + brown
2 = 0 V AUX white
3 = AS-Interface - blue 1 = AS-Interface +
4 = +24 V AUX black 2 = 0 V AUX
5 = earth green/yellow 3 = AS-Interface -
4 = +24 V AUX
5 = earth

Part Number

0911 ANC 101

0911 ANC 401

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

42 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Accessories

0911 ANC 407/... M 0911 ANC 410/... M

AS-Interface connector for direct connection AS-Interface connector for direct connection
to a wired male connector: reusable access to two wired male connectors: reusable access
technology to IEC 60352-6. AS-Interface technology to IEC 60352-6. AS-Interface
connector. 0911 ANC 406 is included with the connector 0911 ANC 406 is included with the
delivered product. delivered product.

Technical Data Technical Data


Environmental Environmental
Degree of protection IP 67 Degree of protection IP 67
Housing material PA Housing material PA
Insert PUR Insert PUR
Nominal current at 40°C 2 A per contact Nominal current at 40°C 2 A per contact

Pin Assignments

2-Poles 2-Poles

1 = brown 1 = brown
2 = blue 2 = blue

Part Number Outer Jacket Standard Cable Lengths

0911 ANC 407/...M PUR/PVC 2 M / 5 M / 10 M

0911 ANC 410/...M PUR/PVC 0.3 M / 0.6 M / 1 M / 2 M / 5 M / 10 M / 15 M

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 43
AS-Interface Accessories

0911 ANC 408 0911 ANC 406 0911 ANC 413

AS-Interface cable connector, used for AS-Interface connector for AS-Interface cables. AS-Interface cable connector, used for
distribution of connections or as connector: distribution of connections or as connector:
reusable access technology to IEC 60352-6. AS- reusable access technology to IEC 68 and
Interface connector 0911 ANC 406 is included DIN 41611, hexagon screw in stainless steel, 4
with the delivered product. poles. AS-Interface connector 0911 ANC 415 is
included with the delivered product.
– especially designed for food and
beverage equipment –

Technical Data Technical Data Technical Data


Degree of protection IP 67 Molded body PA Degree of protection IP 67 / IP 69K
Molded body PA Molded body PBT
Insert PA Insert PBT
Nominal current at 40°C 4A Nominal current at 40°C 4A

0911 ANC 415

AS-Interface connector for AS-Interface cables.

Technical Data
Molded body PBT

Part Number

0911 ANC 408 0911 ANC 406

0911 ANC 413 0911 ANC 415

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

44 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Accessories

0913 ATL 003 0913 ATL 002/0.35 M

This AS-Interface Handheld controller serves The addressing adaptor is able to address the
to address the AS-Interface sensors, actuators AS-Interface flat cable modules with existing
and round cable modules. The mechanical handheld addressing units, length 0.35 m.
connection is made by a mating M12 connector.
– suitable to addressing unit 0913 ATL 003 –
AS-Interface flat cable modules are connected
using the addressing adaptor type 0913 ATL
002/0.35 M. With this addressing equipment,
all types of AS-Interface modules (including
equipment with ASInterface Version 2.1) can
be addressed.

Important Note
The equipment with AS-Interface Version 2.1 are
not addressable with the previous address module
0913 ATL 001.

Part Number

0913 ATL 003 0913 ATL 002/0.35 M

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 45
AS-Interface Accessories

0915 034 101/... M Technical Data

Environmental
Degree of protection IP 67
Temperature range -25°C / +80°C

Materials
Housing / Molded body TPU, self-extinguishing
Insert TPU, self-extinguishing
Contact Male connector: CuZn, prenickeled and
0.8 microns gold-plated
Female connector: CuZn, prenickeled and
0.3 microns gold-plated
AS-Interface cordset, doubleended, M12 male
Receptacle shell / knurled screw/
connector and M12 female connector with self-
nut / hexagon screw/nut / sleeve CuZn, nickel-plated
locking threaded joint.
O-ring FKM (only female connector)

Electrical data
Nominal current at 40°C 4A
Nominal voltage 240 V
Rated voltage 250 V
Test voltage 2.0 kV eff. / 60 s
Insulation resistance > 109 :
Pollution degree 3

Cable specification PUR/PVC - cable-no. 34


Further information please see chapter
”Cable specifications”

Pin Assignments

4-Poles

1 = brown
2 = white
3 = blue
4 = black

Part Number Poles Out Jacket Standard Cable Lengths

0915 034 101/...M 4 PUR 1M/3M/5M

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

46 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

AS-Interface Accessories

0911 ANC 409

Terminal sleeves for flat cable, packing


unit: 10 pieces.

Part Number

0913 ANC 409

The application of these products in harsh environments should always be checked before use.
Specifications subject to alteration.

www.lumberg-automationusa.com 1-717-217-2299 47
Part Number Index

Part Number Page No. Part Number Page No. Part Number Page No.
0910 ASL 132 12-13 0910 ASL 438 38-39 0911 ANC 410/1 M 43
0910 ASL 133 18-19 0910 ASL 501 8-9 0911 ANC 410/2 M 43
0910 ASL 134 24-25 0911 ANC 002/5 M 40-41 0911 ANC 410/5 M 43
0910 ASL 135 30-31 0911 ANC 002/10 M 40-41 0911 ANC 410/10 M 43
0910 ASL 146 36-37 0911 ANC 101 42 0911 ANC 410/15 M 43
0910 ASL 403 16-17 0911 ANC 401 42 0911 ANC 413 44
0910 ASL 408 28-29 0911 ANC 403 40-41 0911 ANC 415 44
0910 ASL 409 10-11 0911 ANC 406 44 0913 ANC 409 47
0910 ASL 410 22-23 0911 ANC 407/2 M 43 0913 ATL 002/0.35 M 45
0910 ASL 412 14-15 0911 ANC 407/5 M 43 0913 ATL 003 45
0910 ASL 414 26-27 0911 ANC 407/10 M 43 0915 034 101/1 M 46
0910 ASL 419 20-21 0911 ANC 408 44 0915 034 101/3 M 46
0910 ASL 424 32-33 0911 ANC 410/0.3 M 43 0915 034 101/5 M 46
0910 ASL 425 34-35 0911 ANC 410/0.5 M 43

48 1-717-217-2299 www.lumberg-automationusa.com
AS-Interface

Be Certain with Belden

Regarding the details in this catalog: Alterations may have been made to the product after the editorial deadline for this publication, namely 03/01/2011. The manufacturer
reserves the right to alter the construction and form, manufacture different shades and amend the scope of delivery during the delivery period insofar as the alterations
and differences are acceptable to the buyer while allowing for the seller’s interests. Insofar as the seller or the manufacturer uses signs or numbers to mark the order or
the ordered item, no rights may be derived from this alone. The illustrations may also contain accessories and special equipment which are not part of the mass-produced
scope of delivery. Color differences are attributable to technical aspects of the printing process. This publication may also contain types and support services that are not
made available/rendered in some countries. The information/details in this publication merely contain general descriptions or performance factors which, when applied in an
actual situation, do not always correspond with the described form and may be amended by way of the further development of products. The desired performance factors
shall only be deemed binding if these are expressly agreed on conclusion of the contract. This brochure will be used internationally. However, comments on statutory, legal,
and fiscal provisions and effects only apply to the Federal Republic of Germany at the time of the editorial deadline for this publication. Please consult your pertinent seller
about the provisions and effects that apply to your country and regarding the latest biding version.
www.lumberg-automationusa.com

GLOBAL LOCATIONS

For worldwide Industrial Sales


and Technical Support, visit:
www.belden.com/industrial

AMERICAS EUROPE/AFRICA/MIDDLE EAST (EMEA)

Belden Industrial Connectivity Belden Deutschland GmbH


1540 Orchard Drive Im Gewerbepark 2
Chambersburg, PA 17201 58579 Schalksmühle
Phone: 717-217-2299 GERMANY
Fax: 717-217-2279 Phone: +49-2355-8301
www.lumberg-automationusa.com Fax: +49-2355-83-3 33
www.lumberg-automation.com

© Copyright 2010 Belden, Inc.


Printed in U.S.A

AS-Interface Catalog 032011

You might also like