Date:05-11-2014
Kawai NDCT,ADANI POWER GAMMON INDIA LIMITED Prepared By:P.L.Sreenivasu
Checked By:Anand Desai
S.No Description Details Remarks
1 Owner name Adani Power Limited
2 Clinet -
Owners Consultant -
2x800MW(Phase-II),KAWAI
3 Project name
TPP,Rajasthan,INDIA.
4 Numbers of NDCT Two nos.
5 Finished Ground Level RL+308.5 Pre bid Reply
Cl.no.2.10 point no.13,
Mechanical Page 5 of
6 Site grade level 308.5m above MSL 47,Vol-II,NDCT Technical
Spec. 5305-E-EPC-NCT-
BM-Y-I-001
7 Founding level for tower foundation NA Not Available
Cl.no.3.1.6, Mechanical
Page 14 of 47,Vol-
II as per IS-1893,Importence
8 Seismic zone II,NDCT Technical Spec.
factor- 1.75
5305-E-EPC-NCT-BM-Y-I-
001
9 Site spectra NA Not Available
Wind data
11 Basic wind speed 47m/sec Cl.no.3.1.6, Mechanical
Page 13 of 47,Vol-
II,NDCT Technical Spec.
12 Terrain cat K2 Cat-2 5305-E-EPC-NCT-BM-Y-I-
13 K1 1.07 001
14 K3 1
15 Height of NDCT
16 Dia at sill level
17 Throat level GAD
18 Throat dia
19 Top dia
20 Top Shell thickness NA
Cl.no.3.1.7, Mechanical
Page 15 of 47,Vol-
21 Load combinations II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Date:05-11-2014
Kawai NDCT,ADANI POWER GAMMON INDIA LIMITED Prepared By:P.L.Sreenivasu
Checked By:Anand Desai
Cl.no.3.1.7, Mechanical
Page 19,21,22 of 47,Vol-
22 Crack width Limit in shell and other RCC crackedwidth limited to II,NDCT Technical Spec.
structures 0.3mm
5305-E-EPC-NCT-BM-Y-I-
001
Cl.no.3.1.9, Mechanical
Page 21 of 47,Vol-
23 Foundation uplift II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
24 Uplift on basin slab As IS codes
Modeling of shell
Cl.no.3.1.9, Mechanical
Done By using FEM Page 17 of 47,Vol-
25 Shell analysis softwares such as NISA - II,NDCT Technical Spec.
2,Ansys etc., 5305-E-EPC-NCT-BM-Y-I-
001
Cl.no.3.1.6, Mechanical
Temperature loads shall be
considered(9 to 50 degree). Page 14 of 47,Vol-
Neverthless an Effective II,NDCT Technical Spec.
temp. 5305-E-EPC-NCT-BM-Y-I-
001
Cl.no.3.1.9, Mechanical
Page 18 of 47,Vol-
26 Minimum shell thickness 275mm II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Cl.no.3.1.9, Mechanical
Page 17 of 47,Vol-
27 Buckling of shell A factor of safety 5 against II,NDCT Technical Spec.
buckling shall be adopted
5305-E-EPC-NCT-BM-Y-I-
001
Cl.no.3.1.9, Mechanical
Page 22 of 47,Vol-
28 Grade of concrete II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Cl.no.3.1.9, Mechanical
Page 18 of 47,Vol-
29 Cover for shell 50mm II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Date:05-11-2014
Kawai NDCT,ADANI POWER GAMMON INDIA LIMITED Prepared By:P.L.Sreenivasu
Checked By:Anand Desai
Cl.no.3.1.9, Mechanical
Page 22 of 47,Vol-
30 Reinforcment Grade Fe 415 II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Addendum to Vol II,
SBC considered as 52t/sqm
for depth of 0.50m to 3.0m Mechanical Page 13 of
31 Soil Data 47,Vol-II,NDCT Technical
and 83t.sqm for depth from Spec. 5305-E-EPC-NCT-
3.0m to 7.50m
BM-Y-I-001
32 Borlogs NA Not Available
Cl.no.3.1.9, Mechanical
Page 22 of 47,Vol-
33 Exposure condition Sever Exposure II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Cl.no.3.1.9, Mechanical
Page 18 of 47,Vol-
34 Min % of Reinforcement for shell II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Grillage structure details
Cl.no.3.1.2, and 3.1.9
Mechanical Page 11,20
35 Basin slab thickness 300mm of 47,Vol-II,NDCT
Technical Spec. 5305-E-
EPC-NCT-BM-Y-I-001
36 Hot water duct dimensions NA 3mx3m
37 Screens & Stop log gate NA Not Available
38 Monorail capacity NA Not Available
Cl.no.3.1.9 Mechanical
Page 27 of 47,Vol-
39 M.S cage ladder details 2no's II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Cl.no.3.1.9 Mechanical
Page 27 of 47,Vol-
40 Stari case 2 no's II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Date:05-11-2014
Kawai NDCT,ADANI POWER GAMMON INDIA LIMITED Prepared By:P.L.Sreenivasu
Checked By:Anand Desai
Cl.no.3.1.9 Mechanical
Page 27 of 47,Vol-
41 Peripheral plat form details 1500,1200mm II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Considered 160kg/Sqm
42 Fill load NA as per previous
experience
Cl.no.3.2.3.3 Mechanical
Page 29 of 47,Vol-
43 Type of fill PVC film type fill II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Cl.no.3.1.9 Mechanical
Page 26 of 47,Vol-
44 All around pavement 2000mm II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
Cl.no.3.1.9 Mechanical
Page 26 of 47,Vol-
45 Access door 2100 x1200 II,NDCT Technical Spec.
5305-E-EPC-NCT-BM-Y-I-
001
no increase in allowable
bearing capacity is
permitted under seismic and Cl.no.3.1.6 Mechanical
wind load condition. Page 14 of 47,Vol-
46 Increase in permissible stresses However, for design of fill II,NDCT Technical Spec.
support columns 5305-E-EPC-NCT-BM-Y-I-
increase in allowable 001
bearing capacity as per IS
1893 is permitted.
S.No Description Details Remarks
1 Owner name NTPC Limited
2 Clinet -
Owners Consultant -
TANDA THERMAL POWER
3 Project name PROJECT STAGE-II (2 X 660
MW)
4 Numbers of NDCT Two nos.
5 Finished Ground Level NA Not Available
6 Site grade level NA Not Available
7 Founding level for tower foundation NA Not Available
site specific design ANNEXURE-I Criteria for
accleration spectra shall be earthquake resistant
8 Seismic zone
used hence design spectra design of structures and
does not require zone factor equipment
ANNEXURE-I Criteria for
earthquake resistant
design of structures and
site specific design equipment and Site
9 Site spectra accleration spectra shall be
specific seismic
used given in annexure I parameters for design of
structures and
equipment
ANNEXURE-I Site
specific seismic
10 PGA (Peak Ground Acceleration) 0.24g parameters for design of
structures and
equipment
Wind data
11 Basic wind speed 47 m/sec
12 Terrain cat K2 Cat-2 ANNEXURE-II Site
specific design
13 K1 1.07 parameters
14 K3 Not Available
15 Height of NDCT
16 Dia at sill level
17 Throat level GAD
18 Throat dia
19 Top dia
20 Top Shell thickness NA
21 Load combinations Cl.no.3.8.0, Section-VI
For limiting the crack width Cl.no.3.10.6 (b), Design
22 Crack width Limit in shell and other RCC the stress for reinforcement criteria for
structures steel shall be limited to 130 structures(Other than
MPa shell foundations)
Cl.no.3.10.6 - II, Design
23 Foundation uplift criteria for tower shell
foundations
Cl.no.3.10.6 (e), Design
The factor of safety against criteria for
24 Uplift on basin slab
uplift shall be as per IS:3370 structures(Other than
shell foundations)
Modeling of shell
Done By using proven FEM
softwares or an approved
25 Shell analysis alternative method Cl.no.3.10.1, General (a)
including validation of
software used for analysis
Cl.no.3.10.3, D.
26 Minimum shell thickness 350 mm Minimum thickness of
shell
A factor of safety 5 against Cl.no.3.10.3, B. Buckling
27 Buckling of shell
buckling shall be adopted of tower shells
28 Grade of concrete M-30 Cl.no.4.2.0, (b)
Cl.no.3.10.3, E.
29 Cover for shell 45 mm Minimum reinforcement
in shell, spacing and
placement
30 Reinforcment Grade Fe 415/500 as per IS: 1786 Cl.no.4.1.0 and Cl. No.
4.8.0
31 Soil Data
32 Borlogs NA Not Available
33 Exposure condition Sever Exposure Cl.no.4.1.0
Top one third portion of
shell- 0.4 % of c/s along
Cl.no.3.10.3, E.
circumferential direction
Minimum reinforcement
34 Min % of Reinforcement for shell and 0.35 % along meridional
in shell, spacing and
direction, Remaining two
placement
third portion of shell- 0.35 %
in both direction
Grillage structure details
35 Basin slab thickness 300mm Cl.no.3.10.6 ,(I), (h)
36 Hot water duct dimensions NA 3mx3m
37 Screens & Stop log gate Cl.no. 7.2.0
38 Monorail capacity NA Not Available
2 diametrically opposite
galvanized MS caged
ladders. 600 mm wide,
39 M.S cage ladder details Cl.no. 7.11.0
made out of 6 mm X 10 mm
flats for full height shall be
provided
40 Stair case 2 no.s RCC stair case Cl. No. 7.9.0
RCC platform of 1500 mm
clear width should be
41 Peripheral plat form details provided around tower Cl.no. 7.10.0 and Cl. No.
periphery and 1.2 m clear 7.11.0
width all around the tower
circumference
42 Fill load Cl.no. 3.2.0 Dead load
43 Type of fill PVC/ PP/ Prestressed Cl.no.5.0.0 Construction
precast concrete Features
FGL shall be paved for 10 m
width all round outer edge
of cold water basin. Paving
44 All around pavement Cl. No. 7.13.0
shall consist of 150 mm
thick RCC Slab of M-20
Grade
min. size 2100 mm high and Cl. No. 7.9.0
45 Access door
1200 mm wide
46 Increase in permissible stresses NA Not Available