Duct Pressure Loss Calculation

This document provides a calculation sheet for the pressure loss in the duct system for FCU Nos F-T1/B0-03. It includes a description of the duct sections and fittings, including dimensions, airflow rates, and pressure losses. The total pressure loss calculated is 41.85 Pa, with a 20% margin added of 50.22 Pa. The proposed total static pressure for the FCU is 97 Pa.

Uploaded by

Kyi Lwin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
144 views1 page

Duct Pressure Loss Calculation

This document provides a calculation sheet for the pressure loss in the duct system for FCU Nos F-T1/B0-03. It includes a description of the duct sections and fittings, including dimensions, airflow rates, and pressure losses. The total pressure loss calculated is 41.85 Pa, with a 20% margin added of 50.22 Pa. The proposed total static pressure for the FCU is 97 Pa.

Uploaded by

Kyi Lwin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

YCP (LANDMARK) PROJECT

3. Calculation Sheet of Pressure Loss in Duct ( FCU Nos - F-T1/B0-03)

Reference Dwg No. LMK-FC-LB1-B00-ICE-M-MEC-202-C Calculation Sheet of Pressure Loss in Duct (a) (b)

Description Duct Duct Airflow Duct Size (Rect.) Duct Size Air Velocity Duct Fitting Duct Duct Fitting
Pressure Pressure Pressure
Building / Room Name Type Tag No. Section Element Shape Rate width high (Equivalent Velocity Pressure Length Loss Remark
Loss, Loss, Loss,
L/S mm. mm. Round) m/s Pa m Coefficients Pa / m Pa Pa (ASHRAE Ref.) Roughness dh Re F F' Parameters

Car Park Lift Lobby FCU F-T1/B0-03 A Slot Diffuser 3-SL 106.0 1200 63 244 1.40 1.18 5.00 Appendix (C) Page-C-15

Model FWC-06H B Chamber 212.0 1200 500 827 0.35 0.08 0.50 0.04 Appendix (B) Page-B-22 Table-SD1-2 L/D = 0.6 ꝋ = 180'
Air Flow (L/S) 212 C Duct Canvas 212.0 800 300 520 0.88 0.47 0.15 0.04 0.0 Roughness in Table-1 (Page-12) 3 436.4 21178.82 0.034859 0.034859

Medium Speed FCU FCU

1 Duct Canvas 212.0 800 300 520 0.88 0.47 0.15 0.04 0.0 Roughness in Table-1 (Page-12) 3 436.4 21178.82 0.034859 0.034859

2 Contraction 212.0 250 200 244 4.24 10.82 0.06 0.65 Appendix (B) Page-B-36 Table-SR4-1 A0/A1 = 0.2 ꝋ = 45'
3 Straight Duct 212.0 250 200 244 4.24 10.82 1.8 1.87 3.4 3 222.2 51770.45 0.038376 0.038376

4 Tee 45 106.0 250 200 244 2.12 2.71 0.40 1.08 Appendix (B) Page-38 Table-SR5-5 Qs/Qc = 0.5

5 Elbow 90 90 106.0 250 200 244 2.12 2.71 0.87 2.35 Appendix (B) Page-B-36 Table-SR3-1 H/W1 = 0.8 W0/W1= 0.8

6 VD VD 100.0 200 200 219 2.50 3.76 0.13 0.49 Appendix (B) Page-B-31 Table-CR9-1 H/W = 1 ꝋ = 5'
7 Contraction 100.0 200 200 219 2.50 3.76 0.07 0.26 Appendix (B) Page-B-23 Table-SD4-2 A0/A1 = 0.8 ꝋ = 15'
8 Flex. Duct 100.0 Dia. 200 200 3.18 6.09 1 1.60 1.6 Appendix (C ) Page-C-21

9 Slot Diffuser 3‐SL 100.0 1200 63 244 1.32 1.05 27.00 Appendix (C) Page-C-14

Air 20 °C Total (a) + (b) 41.85

Viscosity 18.2 10^-6 m2/s Total External Static Pressure Loss with 20% margin 50.22

Density 1.204 kg/m3 #Selection of Supply Fan 212.0 L/S x 50.00 Pa 50.00

Proposed External FCU Static Pressure 50 Pa Appendix (E ) Page-E-02

Proposed Internal FCU Static Pressure 47 Pa Appendix (E ) Page-E-02

Proposed Total FCU Static Pressure 97 Pa Appendix (E ) Page-E-02

Damper VD ꝋ = 0' Appendix G - Example Static Calculation Sheet of ASHRAE Standard