800/900 Series
Linear Heat Detectors
Models Available
JTW-LD-85/105-889
JTW-LD-70-887
JTW-LD-85-887 JTW-LD-85-887
JTW-LD-85/105-889
JTW-LC-996
JTW-LD-70-887
JTW-LD-997
JTW-LCD-998
JTW-LC-996
JTW-LD-997
JTW-LCD-998
Features and Specifications
The 800/900 Series Linear Heat Detector is uniquely designed for protecting cable fields or similar style environments where
normal spot type detectors are difficult or impossible to install and maintain. The Linear Heat Series can be used to provide
early warning in dangerous environments such as Petrochemical Plants, Atypical Industry Processes, Material Conveyor Sys-
tems, and Oil Reserve Tanks.
JTW-LD-70-887 JTW-LD-85-887 JTW-LD-85/105-889
Two single temperature models (70,85 C) and one rate-of-rise (85-105 C) available, fewer false alarms with products for all
environments
Metal matted housing coat provides strong and reliable protection from electromagnetic interference as well as mechanical,
tensile, water, or corrosion damage
Long detection range, detection line can extend 3-500m
Microcomputer modulator monitors transducer cable fault and/or alarm signal for 1-4 loops
Attachment mounting parts available for 887/M and 889/M cable box
Compatible with any control panel
JTW-LC-996(Rate-of-Rise) JTW-LD-997(Fixed) JTW-LCD-998(Rate-of-Rise and Fixed)
Adjustable alarm temperature 70-180 C, + 4% change tolerance
Reusable transducer cable
Temperature compensation tolerance allows for fewer false alarms
Multi level alarms for one loop transducer cable can monitor short and/or broken circuit faults, as well as temperature
changes
Metal matted housing coat provides strong and reliable protection from electromagnetic interference as well as mechanical,
tensile, water, or corrosion damage
Compatible with any control panel or temperature monitoring system
This document is not intended to be used for installation purposes. A06-100-01C
900 Series Linear Heat Detectors Wiring diagram
Power
Isolator
FIRE
CONTROL
Monitor Monitor Monitor Monitor
PANEL
Module Module Module Module
997/MO1 997/MO1
Microcomputer
Microcomputer
Modulator Modulator
Fire pre-alarm (fault)
Fire pre-alarm (fault)
Line Heat Detector
Comment:
The fire pre-alarm (fault)signal
only applied to the multi-level
997/EOL 997/EOL
alarm (fault)
Linear Heat Microcomputer Modulator and EOL Box
The Microcomputer Modulator and the EOL box 996/MOI 997/MOI
are the main parts of the Liner Heat Detector. The
ymainly monitor the temperature variety of the
safety zone or protective objects, deal with the
signal,the signal output and alarm output. In
addition, the microcomputor modulator can also
monitor the open or short fault of the linear heat
detector with the EOL Box.
998/MOI EOL