MiCOM P120-P123 Overcurrent Relay Guide
MiCOM P120-P123 Overcurrent Relay Guide
P120/P121/P122/P123
Overcurrent Relays
Version 6
Technical Guide
P12x/EN T/F75
Technical Guide P12x/EN T/F75
Contents
MiCOM P120/P121/P122/P123 Page 1/2
CONTENTS
BLANK PAGE
Pxxxx/EN SS/B11
SAFETY SECTION
Pxxxx/EN SS/B11
CONTENTS
1. INTRODUCTION 3
3.1 Symbols 4
3.2 Labels 4
7.4 Environment 8
8. CE MARKING 8
BLANK PAGE
Pxxxx/EN SS/B11
1. INTRODUCTION
This guide and the relevant operating or service manual documentation for the equipment
provide full information on safe handling, commissioning and testing of this equipment and
also includes descriptions of equipment label markings.
Documentation for equipment ordered from AREVA Energy Automation & Information is
despatched separately from manufactured goods and may not be received at the same time.
Therefore this guide is provided to ensure that printed information normally present on
equipment is fully understood by the recipient.
Before carrying out any work on the equipment the user should be familiar with
the contents of this Safety Guide.
Reference should be made to the external connection diagram before the equipment is
installed, commissioned or serviced.
Language specific, self-adhesive User Interface labels are provided in a bag for some
equipment.
• are familiar with the installation, commissioning, and operation of the equipment and
of the system to which it is being connected;
• are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorised to energize and de-energize equipment
and to isolate, ground, and label it;
• are trained in the care and use of safety apparatus in accordance with safety
engineering practices;
3.1 Symbols
*NOTE: THE TERM EARTH USED THROUGHOUT THIS GUIDE IS THE DIRECT
EQUIVALENT OF THE NORTH AMERICAN TERM GROUND.
3.2 Labels
See "Safety Guide" (SFTY/4L M) for equipment labelling information.
DANGER - CTs must NOT be fused since open circuiting them may
produce lethal hazardous voltages.
7.4 Environment
The equipment is intended for indoor installation and use only. If it is required for use in an
outdoor environment then it must be mounted in a specific cabinet or housing which will
enable it to meet the requirements of IEC 60529 with the classification of degree of
protection IP54 (dust and splashing water protected).
8. CE MARKING
Compliance with all relevant European
Marking Community directives:
Where applicable :
BLANK PAGE
Introduction P12x/EN IT/F75
MiCOM P120/P121/P122/P123
INTRODUCTION
Introduction P12x/EN IT/F75
CONTENTS
1. INTRODUCTION 3
4. MAIN FUNCTIONS 6
5. EQUIVALENCE TABLES 7
P12x/EN IT/F75 Introduction
BLANK PAGE
Introduction P12x/EN IT/F75
1. INTRODUCTION
The overcurrent relays of the MiCOM P120 range are AREVA T&D universal overcurrent
relays. MiCOM P120, P121, P122 and P123 relays have been designed to control, protect
and monitor industrial installations, public distribution networks and substations, and to be
used as back-up protection for EHV and HV transmission networks.
P12x/EN IT/F75 Introduction
4. MAIN FUNCTIONS
The following table shows the functions available for the different models of the MiCOM
P120 range of relays.
5. TABLE OF EQUIVALENCE
The following section describes the models of the MiCOM P120 range together with other
existing relays in the AREVA T&D' catalogue :
FUNCTIONAL EQUIVALENCE TABLE BETWEEN AREVA T&D' MiCOM P120 RANGE OF RELAYS AND
THE FORMER AREVA T&D OR GEC-ALSTHOM RANGE OF RELAYS
P12x/EN IT/F75 Introduction
BLANK PAGE
Handling, Installation and Case Dimensions P12x/EN IN/F75
MiCOM P120/P121/P122/P123
HANDLING, INSTALLATION
AND CASE DIMENSIONS
Handling, Installation and Case Dimensions P12x/EN IN/F75
CONTENTS
1. GENERAL CONSIDERATIONS 3
1.1 Receipt of relays 3
1.2 Electrostatic discharge (ESD) 3
3. RELAY MOUNTING 5
4. UNPACKING 6
5. STORAGE 7
6. DIMENSIONS 8
6.1 Connection of power terminals, and Signals terminals 8
6.2 Communication port RS485 9
6.3 Earthing 9
7. CASE DIMENSIONS 10
P12x/EN IN/F75 Handling, Installation and Case Dimensions
BLANK PAGE
Handling, Installation and Case Dimensions P12x/EN IN/F75
1. GENERAL CONSIDERATIONS
1.1 Receipt of relays
Protective relays, although generally of robust construction, require careful treatment prior to
installation on site. Upon receipt, relays should be examined immediately to ensure no
damage has been sustained in transit. If damage has been sustained during transit a claim
should be made to the transport contractor and AREVA T&D should be promptly notified.
Relays that are supplied unmounted and not intended to be installed immediately should be
returned with their protective polythene bags.
1.2 Electrostatic discharge (ESD)
The relays use components that are sensitive to electrostatic discharges.
The electronic circuits are well protected by the metal case and the internal module should
not be withdrawn unnecessarily. When handling the module outside its case, care should be
taken to avoid contact with components and electrical connections. If removed from the case
for storage, the module should be placed in an electrically conducting antistatic bag.
There are no setting adjustments within the module and it is advised that it is not
unnecessarily disassembled. Although the printed circuit boards are plugged together, the
connectors are a manufacturing aid and not intended for frequent dismantling; in fact
considerable effort may be required to separate them. Touching the printed circuit board
should be avoided, since complementary metal oxide semiconductors (CMOS) are used,
which can be damaged by static electricity discharged from the body.
P12x/EN IN/F75 Handling, Installation and Case Dimensions
3. RELAY MOUNTING
Relays are dispatched either individually or as part of a panel/rack assembly.
If an MMLG test block is to be included it should be positioned at the right-hand side of the
assembly (viewed from the front). Modules should remain protected by their metal case
during assembly into a panel or rack.
For individually mounted relays an outline diagram is supplied in section 6 of this chapter
showing the panel cut-outs and hole centres.
P12x/EN IN/F75 Handling, Installation and Case Dimensions
4. UNPACKING
Care must be taken when unpacking and installing the relays so that none of the parts is
damaged or the settings altered. Relays must only be handled by skilled personnel. The
installation should be clean, dry and reasonably free from dust and excessive vibration. The
site should be well lit to facilitate inspection. Relays that have been removed from their cases
should not be left in situations where they are exposed to dust or damp. This particularly
applies to installations which are being carried out at the same time as construction work.
Handling, Installation and Case Dimensions P12x/EN IN/F75
5. STORAGE
If relays are not to be installed immediately upon receipt they should be stored in a place
free from dust and moisture in their original cartons. Where de-humidifier bags have been
included in the packing they should be retained. The action of the de-humidifier crystals will
be impaired if the bag has been exposed to ambient conditions and may be restored by
gently heating the bag for about an hour, prior to replacing it in the carton.
Dust which collects on a carton may, on subsequent unpacking, find its way into the relay; in
damp conditions the carton and packing may become impregnated with moisture and the de-
humifier will lose its efficiency.
Storage temperature : –25°C to +70°C.
P12x/EN IN/F75 Handling, Installation and Case Dimensions
6. DIMENSIONS
6.1 Connection of power terminals, and Signals terminals
The individual equipment are delivered with sufficient M4 screws to connect the relay via
annular terminals, with a maximum recommended of two annular terminals per contact.
If necessary, AREVA T&D can provide annular terminals to crimp. 5 references exist
according to the section of the wire (see below). Each reference corresponds to a sachet of
100 terminals.
P0166ENb
P0167ENb
Handling, Installation and Case Dimensions P12x/EN IN/F75
To insure the insulation of the terminals and to respect the security and safety instructions,
an isolated sleeve can be used.
We recommend the following cable cross-sections:
7. CASE DIMENSIONS
MiCOM P120, P121, P122 and P123 relays are available in a 4U metal case for panel or
flush mounting.
Weight : 1.7 to 2.1 Kg
External size : Height case 152 mm
front panel 177 mm
Width case 97 mm
front panel 103 mm
Depth case 226 mm
front panel + case 252 mm
39 39
97 26 26
All dimensions
in mm
168 158
Panel cut-out
Flush mounting fiwing details
IA = 214.50A
Trip
Alarm C
Equip.fail
Auxiliary
supply 177 151.2 max.
AUX. 1
AUX. 2
AUX. 3
AUX. 4
Flush mounting
P0001ENa
MiCOM P120/P121/P122/P123
User Guide
User Guide P12x/EN FT/F75
CONTENTS
2. USER INTERFACE 6
2.1 LCD display and keypad description 6
2.1.1 LCD display 6
2.1.2 Keypad 6
2.2 LEDs 7
2.3 Description of the two areas under the top and bottom flaps 8
2.4 The battery box 8
3. PASSWORD 9
3.1 Password protection 9
3.1.1 Password entry 9
3.1.2 Changing the password 9
3.1.3 Change of setting invalidation 9
5. MENUS 14
5.1 Default display 14
5.2 Access to the menu 14
5.3 Menu contents description 14
5.4 OP PARAMETERS Menu 17
5.4.1 P121, P122 and P123 additional OP.PARAMETERS Menu 17
5.4.2 P122 and P123 additional OP.PARAMETERS Menu 18
5.5 Menu CONFIGURATION 18
5.5.1 Submenu DISPLAY 18
5.5.2 Submenu CT RATIO 19
5.5.3 LED 5 to 8 configuration submenus 19
5.5.4 Submenu Selecting Active Protection Group (P122 & P123 only) 23
5.5.5 Alarms sub-menu (P122 & P123 only) 23
5.5.6 Submenu Inputs Configuration (P122 & P123 only) 24
5.5.7 Configuration Relays Maintenance sub-menu (P122 & P123 only) 25
5.5.8 Configuration Phase Rotation sub-menu (P122 & P123 only) 25
P12x/EN FT/F75 User Guide
5.9.2 Latch of trip output relay by Function Submenu (P121, P122 & P123 relays) 41
5.9.2.1 P122 & P123 additional Latch functions sub-menu 42
5.9.2.2 P123 additional latch functions submenu 42
5.9.3 Latch functions submenu (P120 relay) 43
5.9.4 Blocking Logic submenu 44
5.9.4.1 P122 & P123 additional Blocking Logic menu 44
5.9.4.2 P123 additional Blocking Logic menu 45
5.9.5 Logic Select submenus (P122 & P123 only) 45
5.9.6 Outputs Relays submenu 46
5.9.6.1 P122 & P123 additional Outputs menu 47
5.9.7 Latch of the auxiliary output relays (RL2 to RL8) 49
5.9.7.1 P122 & P123 additional latch output relays menu 49
5.9.7.2 P123 additional latch output relays menu 49
5.9.8 Inputs submenu 50
5.9.8.1 P122 & P123 additional Inputs menu 51
5.9.8.2 P123 additional Inputs menu 51
5.9.9 BROKEN CONDUCTOR submenu (P122 & P123 only) 52
5.9.10 COLD LOAD PICK-UP submenu (P122 & P123 only) 52
5.9.11 CIRCUIT BREAKER FAILURE submenu (P122 & P123 only) 53
5.9.12 CIRCUIT BREAKER SUPERVISION sub-menu (P122 & P123 only) 54
5.9.13 Comm. Order Submenu (P122 & P123 only) 55
5.9.14 Submenu SOTF (Switch on to Fault) (P123 only) 55
5.10 RECORDS Menu (P122 & P123 only) 57
5.10.1 CB MONITORING submenu 57
5.10.2 Fault Record submenu for MiCOM P122 and P123 58
5.10.3 INSTANTANEOUS submenu 59
5.10.4 DISTURBANCE RECORD submenu 59
5.10.5 Time PEAK VALUE submenu 60
5.10.6 ROLLING DEMAND submenu 60
6. WIRING 61
6.1 Auxiliary supply 61
6.2 Current measurement inputs 61
6.3 Logic inputs 61
6.4 Output relays 61
6.5 Communication 62
6.5.1 RS485 rear communication port 62
6.5.2 RS232 front communication port (P122 & P123 only) 62
P12x/EN FT/F75 User Guide
BLANK PAGE
User Guide P12x/EN FT/F75
2. USER INTERFACE
MiCOM P120, P121, P122 and P123 relay front panel allows the user to easily enter relay
settings, display measured values and alarms and to clearly display the status of the relay.
Aux . 1
Aux . 2
+
Battery defghi
RS 232 P0002ENb
• Two keys located just under the screen (keys ! and ").
Keys ! and " are used to read and acknowledge alarms. To display successive alarms,
press key ". Alarms are displayed in reverse order of their detection (the most recent alarm
first, the oldest alarm last). To acknowledge the alarms, the user can either acknowledge
each alarm using ! or go to the end of the ALARM menu and acknowledge all the alarms at
the same time.
When navigating through submenus, key ! is also used to come back to the head line of
the corresponding menu.
NOTE : To acknowledge a relay latched refer to the corresponding submenu
section.
• Four main keys #, $, %, & located in the middle of the front panel.
They are used to navigate through the different menus and submenus and to do the setting
of the relay.
The key ' is used to validate a choice or a value (modification of settings).
User Guide P12x/EN FT/F75
2.2 LEDs
The LED labels on the front panel are by default written in English, however the user has
self-adhesive labels available with MiCOM relays on which it is possible to write using a ball
point pen.
The top four LEDs indicate the status of the relay (Trip condition, alarm LED, equipment
failure, auxiliary supply).
The four lower LEDs are freely programmable by the user and can be assigned to display a
threshold crossing for example (available for all models) or to show the status of the logic
inputs (P122 & P123 ONLY).The description of each one of these eight LEDs located in the
left side of the front view is given hereafter (numbered from the top to bottom from 1 to 8):
LED 1 Colour : RED Label : Trip
LED 1 indicates that the relay has issued a trip order to the cut-off element (circuit breaker,
contactor). This LED recopies the trip order issued to the Trip logic output. Its normal state is
unlit. As soon as a triggering order is issued, the LED lights up. It is cleared when the
associated alarm is acknowledged either through the front panel, or by a remote command,
a digital input, or by a new fault (CONFIGURATION/Alarms menu).
LED 2 Colour : ORANGE Label : ALARM
LED 2 indicates that the relay has detected an alarm. This alarm can either be a threshold
crossing (instantaneous), or a trip order (time delayed). As soon as an alarm is detected, the
LED starts blinking. After all the alarms have been read, the LED lights up continuously.
After acknowledgement of all the alarms, the LED is extinguished.
NOTE : It is possible to configure the instantaneous alarms to be self reset or
not by choosing Yes or No in the CONFIGURATION/Alarms Menu.
The alarm LED can be reset either through the front panel, or by remote command, by a
digital input, or by a new fault (CONFIGURATION/Alarms menu).
LED 3 Colour : ORANGE Label : Warning
LED 3 indicates internal alarms of the relay. When the relay detects a « non critical » internal
alarm (typically a communication failure), the LED starts blinking continuously. When the
relay detects a fault that is considered as « critical », the LED lights up continuously. Only
the disappearance of the cause of the fault can clear this LED (repair of the module,
clearance of the Fault).
LED 4 Colour : GREEN Label : Healthy
LED 4 indicates that the relay is powered by an auxiliary source at the nominal range.
LED 5 to 8 Colour : RED Label : Aux.1 to 4.
These LEDs are user programmable and can be set to display information about
instantaneous and time-delayed thresholds as well as the status of the logic inputs (for P122
& P123 only). Under the CONFIGURATION/LED menu of the relay, the user can select the
information he wishes to associate with each LED. He can affect more than one function to
one LED. The LED will then light up when at least one of the associated information is valid
(OR gate). The LED is cleared when all the associated alarms are acknowledged.
P12x/EN FT/F75 User Guide
2.3 Description of the two areas under the top and bottom flaps
Under the upper flap, a label identifies the relay according to its model number (order
number) and its serial number. This information defines the product in a way that is unique.
In all your requests, please make reference to these two numbers.
Under the model and serial number, you will find information about the level of voltage of the
auxiliary supply and the nominal earth current value.
Under the lower flap, a RS232 port is available in all MiCOM relays. Nonetheless, this
RS232 port is used differently depending on the model of the relay:
1. For MiCOM P120 and P121, this RS232 port can be used to download a new version
of the application software into the relay flash memory.
2. For MiCOM P122 and P123, this RS232 port can be used either to download a new
version of the application software version into the relay flash memory or to plug a
laptop loaded with AREVA T&D’ setting software MiCOM S1.
To withdraw more easily the active part of the MiCOM relay (i-e the chassis) from its case,
open the two flaps, then with a 3mm screwdriver, turn the extractor located under the upper
flap, and pull it out of its case pulling the flaps towards you.
2.4 The battery box
The battery box MiCOM E1 allows the user to be able to read and change the settings of the
relay when it is not powered by its auxiliary source.
P0005ENc
3. PASSWORD
3.1 Password protection
A password is required for relay settings, especially when changing the various thresholds,
time delays, communication parameters, allocation of inputs and outputs relays.
The password consists of four capital characters. When leaving factory, the password is set
to AAAA. The user can define his own combination of four characters.
Should the password be lost or forgotten, the modification of the stored parameters is
blocked. It is then necessary to contact the manufacturer or his representative and a stand-
by password specific to the relay may be obtained.
The programming mode is indicated with the letter "P" on the right hand side of the display
on each menu heading. The letter "P" remains present as long as the password is active
(5 minutes if there is no action on the keypad).
3.1.1 Password entry
The input of the password is requested as soon as a modification of a parameter is made for
any one of the six/eight menus and the submenus. The user enters each one of the 4
characters and then validates the entire password with '.
After 5 seconds, the display returns to the point of the preceding menu.
If no key is pressed inside of 5 minutes, the password is deactivated. A new password
request is associated with any subsequent parameter modification.
3.1.2 Changing the password
To change an active password, go to the OP. PARAMETERS menu and then to the
Password submenu. Enter the current password and validate it. Then press ' and enter the
new password character by character and validate the new password using '.
The message NEW PASSWORD OK is displayed to indicate that the new password has
been accepted.
3.1.3 Change of setting invalidation
The procedure to modify a setting is described in the following sections of this manual.
If there is a need to get back to the old setting push key ! before validating the setting
change. The following message will then appear on the LCD for a few seconds and the old
setting will remain unchanged.
UPGRADE
CANCEL
P12x/EN FT/F75 User Guide
NOTE : The <<Battery backed RAM memory>> and <<Battery failure>> alarm
messages can be configured to be displayed or not by selecting yes
or no, in the CONFIGURATION/Alarms menu.
<< DEFAULT SETTINGS (*) >>
<< SETTING ERROR (**) >>
(*) DEFAULT SETTINGS: Each time the relay is powered ON it will check its memory
contents to determine whether the settings are set to the factory defaults. If the relay detects
that the default settings are loaded an alarm is raised. The ALARM LED (YELLOW) will light
up and the Watch Dog contact will be activated.
Only one parameter in the relay's menu needs to be changed to suppress these messages
and to reset the watch dog. This alarm is only an indication to the user that the relay has its
default settings applied.
(**) SETTING ERROR: Should the CPU fails to get correctly store data to the EEPROM
during a setting change, a "HARDWARE" ALARM will appear on the LCD display followed
by "SETTING ERROR" message (when pushing on the button). In addition, the ALARM LED
(YELLOW) will light up and the Watch Dog contact will be activated To reset this alarm it is
necessary to power ON and OFF the relay. Following this, the last unsuccessful setting
change will then need to be re-applied. If the alarm persists, i.e. the "SETTING ERROR"
alarm is still displayed, please contact AREVA After Sales Services for advice and
assistance.
P12x/EN FT/F75 User Guide
5. MENUS
The menu of MiCOM P120, P121, P122 and P123 relays is divided into main menus and
submenus. The available content depends on the model of the relay.
5.1 Default display
By default, the LCD displays the current value measured (selected phase or earth). As soon
as an alarm is detected by the relay, that information is considered as more important and
the alarm message is then displayed instead of the default value.
The user can configure the information he wants to display by default going under the
CONFIGURATION/Display menu.
5.2 Access to the menu
Navigation through the different menus is done pressing the keys & # $ %. The
organisation of the menus is shown in figure 2 for P120 and P121 and figure 3 for P122 and
P123.
There is no need of a password when reading parameters and measured values.
Modification of a parameter requires entering a password.
Should an error be made in entering a parameter, press ! to cancel.
NOTE : The letter P is displayed when the password needs to be entered. If
no key is pushed during 5 minutes, the password needs to be entered
again.
5.3 Menu contents description
The menu of MiCOM P122 & P123 relays is divided into 8 main sections (6 for P120 and
P121):
⇒ OP PARAMETERS
⇒ CONFIGURATION
⇒ MEASUREMENTS
⇒ COMMUNICATION
⇒ PROTECTION G(1)
⇒ AUTOMAT. CTRL
To return to the default display from these menus or sub-menus press &.
CONFIGURATION
MEASUREMENTS
COMMUNICATION
PROTECTION
AUTOMAT. CTRL
P0003ENa
CONFIGURATION
MEASUREMENTS
COMMUNICATION
PROTECTION G1
PROTECTION G2
AUTOMAT. CTRL
RECORDS
P0004ENa
Date Displays the date. Press ' to modify this date then use
12/08/02 $ to enter another date. Press ' to validate your choice.
In this example the date is : 12 August 2002.
Time Displays the time. Press ' to modify the time then
13:57:44 press $ to enter another value. Press ' to validate your
choice . In this example the time is : 13 hours, 57
minutes, 44 seconds.
⇒ Display
⇒ CT Ratio
⇒ Led 5
⇒ Led 6
⇒ Led 7
⇒ Led 8
Phase C Text Choose a label for phase C. The possible choices are
C C, L3, or T. This value can be modified after entering the
password and is displayed with the associated
measurement value.
E/Gnd Text Choose a label for the earth phase. The possible choices
E are N, E, or G. This value can be modified after entering
the password and is displayed with the associated
measurement value.
Line CT primary Choose the rated primary current of the line CT.
1000 The setting range is from 1 to 9999.
Line CT sec Choose the rated secondary current of the line CT.
5 The setting value is either 1or 5.
E/Gnd CT primary Choose the rated primary current of the earth CT.
1000 The setting range is from 1 to 9999.
E/Gnd CT sec Choose the rated secondary current of the earth CT.
5 The setting value is either 1 or 5.
The following table lists the protection functions that can be assigned to the LEDs (5 to 8) for
each model of relay.
TEXT Information
I> Instantaneous first phase threshold
I>> Instantaneous second phase threshold
I>>> Instantaneous third phase threshold
tI> Time delayed first phase threshold
tI>> Time delayed second phase threshold
tI>>> Time delayed third phase threshold
Ie> Instantaneous first earth threshold
Ie>> Instantaneous second earth threshold
Ie>>> Instantaneous third earth threshold
tIe> Time delayed first earth threshold
tIe>> Time delayed second earth threshold
tIe>>> Time delayed third earth threshold
Therm Trip Trip on Thermal overload
Brkn Cond. Broken conductor detection
CB Fail Detection of a Circuit Breaker failure (CB not open at the end
of tBF timer)
tI2> Time delayed negative phase sequence (1st threshold)
Input 1 Copy of the status of the Logic Input n°1
Input 2 Copy of the status of the Logic Input n°2
Input 3 Copy of the status of the Logic Input n°3
Input 4 Copy of the status of the Logic Input n°4
Input 5 Copy of the status of the Logic Input n°5
Recloser Run Signal that Autoreclose cycle is working
Recloser Blocked Auto-recloser function blocked
t SOTF Switch on to fault timer expired
t Aux 1 Copy of the status of the Logic Input delayed by t Aux 1
t Aux 2 Copy of the status of the Logic Input delayed by t Aux 2
tI2>> Time delayed negative phase sequence (2nd threshold)
Example of LED 5 setting (information available only for P122 & P123) :
Led Therm. Setting choice Yes: LED 5 lights up when Thermal Trip
Trip No occurs.
Setting choice No: No operation when Thermal Trip
occurs.
Led Brkn. Cond Setting choice Yes: LED 5 lights up when Brkn. Cond is
Yes detected.
Setting choice No: No operation when Brkn. Cond is
detected.
Led CB Fail Setting choice Yes: LED 5 lights up when CB failure
Yes occurs.
Setting choice No: No operation when CB failure occurs.
Led Input 1 Setting choice Yes: LED 5 lights up with signal present
No at logic input 1.
Setting choice No: No operation with signal present at
logic input 1.
Led Input 2 Setting choice Yes: LED 5 lights up with signal present
Yes at logic input 2.
Setting choice No: No operation with signal present at
logic input 2.
Led Input 3 Setting choice Yes: LED 5 lights up with signal present
No at logic input 3.
Setting choice No: No operation with signal present at
logic input 3.
Led t Aux 1 Setting choice Yes: LED 5 lights up when time Aux1 has
Yes elapsed.
Setting choice No: No operation when time Aux1 has
elapsed.
Led t Aux 2 Setting choice Yes: LED 5 lights up when time Aux2 has
No elapsed.
Setting choice No: No operation when time Aux2 has
elapsed.
Led tI2> Setting choice Yes: LED 5 lights up when tI2> delay time
No has elapsed.
Setting choice No: No operation when tI2> delay time
has elapsed.
Led tI2>> Setting choice Yes: LED 5 lights up when tI2>> delay
No time has elapsed.
Setting choice No: No operation when tI2>> delay time
has elapsed.
User Guide P12x/EN FT/F75
Led Input 4 Setting choice Yes: LED 5 lights up with signal present
No at logic input 4.
Setting choice No: No operation with signal present at
logic input 4.
Led Input 5 Setting choice Yes: LED 5 lights up with signal present
No at logic input 5.
Setting choice No: No operation with signal present at
logic input 5.
Led Recloser Setting choice Yes: LED 5 lights up when Recloser Run
Run No cycle is active.
Setting choice No: No operation when Recloser Run
cycle is active.
Led Recloser Setting choice Yes: LED 5 lights up when Recl. Blocked
Blocked No function is active.
Setting choice No: No operation when Recl. Blocked
function is active.
Led Setting choice Yes: LED 5 lights up when time tSOTF
Conf SOTF has expired.
No Setting choice No: No operation when time tSOTF has
expired.
5.5.4 Submenu Selecting Active Protection Group (P122 & P123 only)
Change Group Press ' and use 1 or 2 and & # to select if the change
Input = INPUT of the group is done through an INPUT or through the
MENU. Press ' to confirm your choice.
If MENU is selected, the following menu is displayed:
Setting Group To select active setting protection group 1 or 2 press '
1 and & or #.
Press ' to confirm choice.
Inst. Self-reset ? Setting choice Yes: the alarms that are instantaneous
No will be self reset when they come back to a normal value
(below the threshold).
Setting choice No: the alarms that are instantaneous will
be need to be acknowledged by the user to be reset.
Press ' to modify and use & to select your choice.
Press ' to validate the setting.
P12x/EN FT/F75 User Guide
Reset led on Setting choice Yes: the LED associated with an old
fault ? No alarm will be automatically reset when a new fault
occurs. This is done to avoid a display of numerous
alarms that are not active any more.
Setting choice No: the appearance of a new fault will not
automatically reset LEDs associated with an old fault.
To reset or not the LED when a new fault occurs. Press
' to modify the value and use keys & # to select your
choice. Press ' to validate the setting.
Alarm Battery To display or not the alarm "RAM ERROR" or
No "BATTERY FAIL" in case of RAM error or battery failure.
Press ' to modify and use & # keys to select your
choice. Press ' to validate the setting.
The user has to set under the Menu CONFIGURATION the auxiliary voltage (AC or DC) for
the digital inputs. This setting is necessary because of the time filtering which is different in
DC and AC.
NOTE : If the V4 or V5 software is used with a V3 hardware the setting has to
be DC.
Inputs 54321 Press ' to modify and use & # % $ to assign active
10110 high or low functionality to each logic input. Press ' to
validate your choice.
0 = active low 1 = active high
Voltage input Press ' to modify and use & # to select AC or DC
DC power supply for the digital input. Press ' to confirm the
setting. The power supply for any input is the same as
the power supply of the relay.
Max & Average I Allows the user to clear the maximum (peak) and
RST = [C] average (rolling) memorised values of the current.
Press ! to clear these values(password required).
Max IA Rms Displays the peak value for phase A. The value is the
127.36 A true RMS maximum value.
Max IB Rms Displays the peak value for phase B. The value is the
156.28 A true RMS maximum value.
Max IC Rms Displays the peak value for phase C. The value is the
139.01 A true RMS maximum value.
Average IA Rms Displays the rolling value for phase A. The value is the
98.25 A true RMS average value.
Average IB Rms Displays the rolling value for phase B. The value is the
97.88 A true RMS average value.
User Guide P12x/EN FT/F75
Average IC Rms Displays the rolling value for phase C. The value is the
99.02 A true RMS average value.
MAX. SUBPERIOD Allows the user to clear the maximum subperiod values
RST = [C] of the 3 currents.
MAX. SUBPERIOD Displays the IA peak value demand. The value is the
IA Rms = 245A true RMS maximum value on a subperiod.
MAX. SUBPERIOD Displays the IB peak value demand. The value is the
IB Rms = 240A true RMS maximum value on a subperiod.
MAX. SUBPERIOD Displays the IC peak value demand. The value is the
IC Rms = 250A true RMS maximum value on a subperiod.
ROLLING AVERAGE Allows the user to clear the rolling average values of the
RST = [C] 3 currents.
ROLLING AVERAGE Displays the IA average value demand. The value is the
IA Rms = 0A true RMS average value on a number of subperiod set in
Record menu.
ROLLING AVERAGE Displays the IB average value demand. The value is the
IB Rms = 0A true RMS average value on a number of subperiod set in
Record menu.
ROLLING AVERAGE Displays the IC average value demand. The value is the
IC Rms = 0A true RMS average value on a number of subperiod set in
Record menu.
Reclose Stats Allows the user to clear the statistics stored for the
RST = [C] autoreclose function. Press ! to clear these values.
Total Trip & Displays the total number of definitive trips issued by the
Lockout 2 autoreclose function.
P12x/EN FT/F75 User Guide
Stop Bits Choose the number of stop bits in the ModBus data
1 frame.
Select stop bit: 0 or 1.
Relay Address Choose the network address of the relay in the ModBus
29 network.
Select an address from 1 to 255.
Date format Choose the format of the date, either PRIVATE or IEC
Private protocol.
Stop Bits Choose the number of stop bits in the MODBUS frame.
1 Select 0 or 1 using &. Press ' to validate your choice.
Delay Type Shows that the delay time type chosen is DMT.
DMT
tI > Set the value for thetime delay associated with I>. The
100 ms setting range is from 0 to 150 s. Use & to change
setting and press ' to validate your choice .
t Reset Set the reset time value. The setting range isfrom 0 to
0 ms 600 s. Use & to change setting and press ' to validate
your choice (only for P122, P123).
Idmt Select the type of curve. Select your choice from IEC SI,
IEC SI IEC STI, IEC VI, IEC EI, IEC LTI, CO2, IEEE MI, CO8,
IEEE VI, IEEE EI using & and press ' to validate your
choice.
Tms Set the TMS value for the curve. The setting range is
0,025 from 0.025 to 1.5. Use & to change setting and press '
to validate your choice.
5.8.1.2.1 P122 & P123 additional I> DMT reset time, IEC curves menu
t Reset Set the reset time setting value. The setting range is
60 ms from 40 ms to 100 s. Use & to change setting and press
' to validate your choice.
5.8.1.2.2 P122 & P123 additional I> DMT reset time, ANSI curves menu
Type Tempo Select the reset delay time type.. Select between DMT
Reset DMT (Definitive Time) and IDMT (Inverse Time) using & and
press ' to validate your choice.
t Reset Set the Reset time setting value . Select from 40 ms to
40 ms 100 s using & and press ' to validate your choice.
User Guide P12x/EN FT/F75
5.8.1.2.3 P122 & P123 additional I> IDMT reset time, ANSI curves menu
Type Tempo Select the type of reset time delay. Select between DMT
Reset IDMT (Definitive Time) and IDMT (Inverse Time) using & and
press ' to validate your choice.
Rtms Set the Rtms value associated with the IDMT reset time
0.025 choice. Select from 0.025 to 1.5 using & and press ' to
validate your choice.
5.8.1.3.1 P122 & P123 additional I> DMT reset time, Electromechanical RI curves menu
t Reset Set the value for the time reset. The setting range is from
60 ms 40 ms to 100 s. Use & to change setting and press ' to
validate your choice.
tIe > Set the time delay associated with Ie>. The setting
100 ms range is from 0 to 150 s. Use & to change setting and
press ' to validate your choice.
t Reset Set the value for the time reset. Press & to modify this
0 ms value. The setting range is from 0 to 600 s. Press ' to
validate your choice (only P122, P123).
Delay Type Display of the Ie> inverse time delay (IEC or IEEE/ANSI
DMT curves).
Idmt Select the Ie> type of curve. Select from IEC SI, IEC STI,
IEC SI IEC VI, IEC EI, IEC LTI, CO2, IEEE MI, CO8, IEEE VI,
IEEE EI using & and press ' to validate your choice.
Tms Setthe value for the time multiplier setting Tms of the
0,025 selected curve. Select from 0.025 to 1.5 using & and
press ' to validate your choice.
5.8.2.2.1 P122 & P123 additional Ie> DMT reset time, IEC curves menu
t Reset Set the value for the time reset. Press & to modify this
60 ms value. The setting range is from 40 ms to 100 s. Press
' to validate your choice.
User Guide P12x/EN FT/F75
5.8.2.2.2 P122 & P123 additional Ie> DMT reset time, ANSI curves menu
Type Tempo Select the type of reset time delay. Setting choices are:
Reset DMT DMT for definite time and IDMT for inverse time curves.
t Reset Set the value for the time reset associated with the DMT
40 ms reset time choice. Press & to modify this value. The
setting range is from 40 ms to 100 s. Press ' to validate
your choice (only P122, P123).
5.8.2.2.3 P122 & P123 additional Ie> IDMT reset time, ANSI curves menu
Type Tempo Select the reset time type. Setting choices are: DMT for
Reset IDMT definite time and IDMT for inverse time curves.
Rtms Set the value for the Rtms factor associated to IDMT
0.025 delay type reset.
5.8.2.3.1 P122 & P123 additional Ie> DMT reset time, RI curves menu
t Reset Set the value for the time reset. Press & to modify this
60 ms value. The setting range is from 40 ms to 100 s. Press
' to validate your choice.
5.8.3 [46] NEGATIVE Phase SEQUENCE I2> submenu (P122 & P123 only)
[46] Neg Seq OC Heading of the [46] NEGATIVE Phase SEQUENCE I2>
submenu.
t I2 > Set the time delay associated with I2>. The setting
100 ms range is from 0 to 150 s. Use & to change setting and
press ' to validate your choice.
User Guide P12x/EN FT/F75
Delay Type Display of the I2> inverse time delay (IEC or IEEE/ANSI
IDMT curves).
Curve Selection of the I2> curve. Select from IEC SI, IEC STI,
IEC SI IEC VI, IEC EI, IEC LTI, CO2, IEEE MI, CO8, IEEE VI,
IEEE EI using & and validate your choice using the key
'.
Tms Set the time multiplier setting value associated to the
0,025 selected curve. Setting range is from 0.025 to 1.5.
t Reset Set the value for the time reset. The setting range is from
60 ms 40 ms to 100 s. Use & to change setting and press ' to
validate your choice.
Type Tempo Select the type of reset time delay. Select between DMT
Reset DMT (Definitive Time) and IDMT (Inverse Time) using & and
press ' to validate your choice.
t Reset Set the value for the time reset. The setting range is from
40 ms 40 ms to 100 s. Use & to change setting and press ' to
validate your choice (only P122, P123).
Type Tempo Select the type of reset time delay. Select between DMT
Reset IDMT (Definitive Time) and IDMT (Inverse Time) using & and
press ' to validate your choice.
Rtms Select the Rtms value associated to the IDMT curve.
0.025 Setting range is from 0.025 to 1.5. Use & to change
setting and press ' to validate your choice.
t Reset Set the value for the reset time. The setting range is from
60 ms 40 ms to 100 s. Use & to change setting and press ' to
validate your choice.
P12x/EN FT/F75 User Guide
Ext CB Fail Allows the use of a dedicated input (CB FLT) to inform
Yes the autoreclose function of the state of the CB (failed or
operational).
Ext CB Fail Time Set the value for the external CB failure time delay tCFE.
10000 ms Once this set time has elapsed, the information Ext CB
Fail is validated. Setting range is from 10 ms to 600 s.
Use & to change setting and press ' to validate your
choice.
Dead Time Set the value for the First Cycle Dead Time (tD1)
tD1 60 ms associated with the autoreclose function. Setting range is
from 10 ms to 300 s in steps of 10 ms. Use & to change
setting and press ' to validate your choice.
Dead Time Set the value for the second Cycle Dead Time (tD2)
tD2 100 ms associated with the autoreclose function. Setting range is
from 10 ms to 300 s in steps of 10 ms. Use & to change
setting and press ' to validate your choice.
Dead Time Set the value for the third Cycle Dead Time (tD3)
tD3 200 ms associated with the autoreclose function. Setting range is
from 10 ms to 600 s in steps of 10 ms. Use & to change
setting and press ' to validate your choice.
Dead Time Set the value for the fourth Cycle Dead Time (tD4)
tD4 60 ms associated with the autoreclose function. Setting range is
from 10 ms to 600 s in steps of 10 ms. Use & to change
setting and press ' to validate your choice.
Reclaim Time Set the Reclaimer time value (tR) associated with the
tR 120 ms autoreclose function. Setting range is from 20 ms to 600
s in steps of 10 ms. Use & to change setting and press
' to validate your choice.
Inhib Time Set the value for the Inhibit Time (tI) associated with the
tI 120 ms autoreclose function. Setting range is from 20 ms to 600
s in steps of 10 ms. Use & to change setting and press
' to validate your choice.
Phase Cycles Select the number of cycles associated with the phase
4 autoreclose function. Select from 0 to 4 using & and
press ' to validate your choice.
E/Gnd Cycles Select the number of cycles associated with the earth
4 autoreclose function. Select from 0 to 4 using & and
press ' to validate your choice.
⇒ Trip Commands
⇒ Latch of the trip output relay RL1 by function (P121, P122, P123 only)
⇒ Outputs Relays
⇒ Inputs
Trip tI> Setting choice Yes: Assign the first phase overcurrent
Yes time delay threshold to the trip output relay RL1. Then
the trip output relay (RL1) will be activated at the end of
the time delay tI>.
Setting choice No: the trip output relay (RL1) will never
be activated, even at the end of the time delay tI>.
Trip tI>> Assign the second phase time delay overcurrent
Yes threshold (tI>>) to the trip output relay RL1.
Setting choice: Yes or No.
Trip tI>>> Assign the third phase time delay overcurrent threshold
No (tI>>>) to the trip output relay RL1.
Setting choice: Yes or No.
Trip tIe> Assign the first earth fault overcurrent (tIe>) to the trip
Yes output relay RL1.
Setting choice: Yes or No.
Trip tIe>> Assign the second earth fault overcurrent (tIe>>) to the
No trip output relay RL1.
Setting choice: Yes or No.
Trip tIe>>> Assign the third earth fault overcurrent (tIe>>>) to the trip
No output relay RL1.
Setting choice: Yes or No.
Trip tI < Assign the minimum current threshold (tI<) to the trip
No output relay RL1. This information is generated in less
than a cycle of the network frequency (50 or 60 Hz).
Setting choice: Yes or No.
Trip tI2 > Assign the first negative phase sequence overcurrent
No time delayed threshold (tI2>) to the trip output relay RL1.
Setting choice: Yes or No.
Trip tI2 >> Assign the second negative phase sequence overcurrent
No time delayed threshold (tI2>>) to the trip output relay
RL1.
Setting choice: Yes or No.
Trip Thermal θ Assign the thermal overload trip threshold (θTrip) to the
No trip output relay RL1.
Setting choice: Yes or No.
Trip Brkn.Cond Assign the broken conductor detection signal to the trip
Yes output relay RL1.
Setting choice: Yes or No.
User Guide P12x/EN FT/F75
Trip t Aux 1 Assign the delayed auxiliary input Aux 1 to the trip output
No relay RL1.
Setting choice: Yes or No.
Trip t Aux 2 Assign the delayed auxiliary input Aux 2 to the trip output
No relay RL1.
Setting choice: Yes or No.
Trip t Aux 3 Assign the delayed auxiliary input Aux 3 to the trip output
No relay RL1.
Setting choice: Yes or No.
Trip CB Fail Assign the Breaker failure signal to the trip output relay
No RL1.
Setting choice: Yes or No.
Trip t Aux 4 Assign the delayed auxiliary input Aux 4 to the trip output
No relay RL1.
Setting choice: Yes or No.
Trip SOTF Assign the SOTF function to the trip output. When the t
No SOTF has elapsed, the trip command is ordered.
Setting choice: Yes, No
Ctrl Trip Assign the control Trip function to the trip output relay
No RL1.
Setting choice: Yes, No
Trip CB Fail Assign the CB Fail function to the trip output relay RL1.
No Setting choice: Yes, No
5.9.2 Latch of trip output relay by Function Submenu (P121, P122 & P123 relays)
With this submenu the user can program the trip output relay RL1associated with one or
many thresholds so that it stays latched after the cause for activating these functions has
disappeared.
Latch tI> Setting choice Yes: Latch the trip output relay RL1
Yes associated with first phase overcurrent time delay
threshold. The relay will be remain latched after tI> has
disappeared.
Setting choice No: The trip output relay RL1 will be
active when the relevant command is active; the relay
will not be active if the relevant command is reset.
Latch tI>> Latch the trip output relay RL1 associated with the
Yes second phase time delay overcurrent threshold (tI>>).
Setting choice: Yes or No.
Latch tI>>> Latch the trip output relay RL1 associated with the third
No phase time delay overcurrent threshold (tI>>>).
Setting choice: Yes or No.
P12x/EN FT/F75 User Guide
Latch tIe> Latch the trip output relay RL1 associated with the first
No earth time delay overcurrent threshold (tIe>).
Setting choice: Yes or No.
Latch tIe>> Latch the trip output relay RL1 associated with the
No second earth time delay overcurrent threshold (tIe>>).
Setting choice: Yes or No.
Latch tIe>>> Latch the trip output relay RL1 associated with the third
No earth fault time delay overcurrent threshold (tIe>>>).
Setting choice: Yes or No.
Latch tI < Latch the trip output relay RL1 associated with the time
Yes delay minimum current threshold (tI<).
Setting choice: Yes or No.
Latch tI2 > Latch the trip output relay RL1 associated with the time
No delay negative phase sequence overcurrent threshold
(tI2>) to the trip output.
Setting choice: Yes or No.
Latch tI2 >> Latch the trip output relay RL1 associated with the time
No delay negative phase sequence overcurrent threshold
(tI2>>) to the trip output.
Setting choice: Yes or No.
Latch Thermal θ Latch the trip output relay RL1 associated with the
No thermal overload Trip information (θ Trip).
Setting choice: Yes or No.
Latch Brkn.Cond Latch the trip output relay RL1 associated with the
No broken conductor function.
Setting choice: Yes or No.
Latch t Aux 1 Latch the trip output relay RL1 associated with the
No delayed auxiliary input Aux 1.
Setting choice: Yes or No.
Latch t Aux 2 Latch the trip output relay RL1 associated with the
No delayed auxiliary input Aux 2.
Setting choice: Yes or No.
Latch t Aux 3 Latch the trip output relay RL1 associated with the
No delayed auxiliary input Aux 3.
Setting choice: Yes or No.
Latch t Aux 4 Latch the trip output relay RL1 associated with the
No delayed auxiliary input Aux 4.
Setting choice: Yes or No.
Latch SOTF Latch the trip output relay RL1 associated with the SOTF
No function.
Setting choice: Yes or No.
Latch CB Fail Latch the trip output relay RL1 associated with the CB
No Fail function.
Setting choice: Yes or No.
User Guide P12x/EN FT/F75
Latch tI> Setting choice Yes: Latch the output relays associated
Yes with first phase overcurrent time delay threshold. The
relay will be remain latched after tI> has disappeared.
Setting choice No: The output relay will be active when
the relevant command is active; the relays will not be
active if the relevant command is reset.
Latch tI>> Setting choice Yes: Latch the output relays associated
Yes with second phase overcurrent time delay threshold. The
relay will be remain latched after tI>> has disappeared.
Setting choice No: The output relay will be active when
the relevant command is active; the relays will not be
active if the relevant command is reset.
Latch tI>>> Setting choice Yes: Latch the output relays associated
Yes with third phase overcurrent time delay threshold. The
relay will be remain latched after tI>>> has disappeared.
Setting choice No: The output relay will be active when
the relevant command is active; the relays will not be
active if the relevant command is reset.
Block 1 tI2 > Enables/disables Blocking Logic of the first time delay
No negative phase sequence overcurrent threshold (tI2>)
from locking on the level (logic state = 1) of logic input
"Blk Log".
Setting choice: Yes, No.
Block 1 tI2 >> Enables/disables Blocking Logic of the second time
No delay negative phase sequence overcurrent threshold
(tI2>>) from locking on the level (logic state = 1) of logic
input "Blk Log".
Setting choice: Yes, No.
Block 1 Thermal θ Enables/disables Blocking Logic of the trip threshold for
Yes thermal overload from locking on the level (logic state 1)
of logic input "Blk Log".
Setting choice: Yes, No.
User Guide P12x/EN FT/F75
RL2 relay is a change over relay. The others RL3 to RL8 are normally open relays.
t Aux 3 8765432 Assign delayed auxiliary input Aux 3 to the output relays;
1010101 i.e. to output 3, 7 & 8 (RL3, RL7 & RL8). Setting choice:
1 assigns the output relay; 0 no assignment.
Order 1 8765432 Assign remote command 1 to the output relays; i.e. to
Comm. 0000100 output 4 (RL4). Setting choice: 1 assigns the output
relay; 0 no assignment.
Order 2 8765432 Assign remote command 2 to the output relays; i.e. to
Comm. 0000010 output 3 (RL3). Setting choice: 1 assigns the output
relay; 0 no assignment.
Order 3 8765432 Assign remote command 3 to the output relays; i.e. to
Comm. 0000001 output 2 (RL2). Setting choice: 1 assigns the output
relay; 0 no assignment.
Order 4 8765432 Assign remote command 4 to the output relays; i.e. to
Comm. 1000000 output 8 (RL8). Setting choice: 1 assigns the output
relay; 0 no assignment.
Active 8765432 Assign the Active Group indication to the output relays;
Group 0010000 i.e. to output 6 (RL6). Setting choice: 1 assigns the
output relay; 0 no assignment.
t Aux 4 8765432 Assign the delayed auxiliary input Aux 4 to the output
0010000 relays. Setting choice: 1 assigns the output relay; 0 no
assignment.
79 Run 8765432 Assign the "autorecloser in progress" signal to the output
1100010 relays. Setting choice: 1 assigns the output relay; 0 no
assignment.
79 Trip 8765432 Assign the autoreclose final trip function to the output
1100010 relays. Setting choice: 1 assigns the output relay; 0 no
assignment.
79 Locked 8765432 Assign the autoreclose final close function to the output
1100010 relays. Setting choice: 1 assigns the output relay; 0 no
assignment.
SOTF 8765432 Assign the SOTF functionality to the output relays; i.e. to
Group 0000010 output 3 (RL3). When the tSOTF has elapsed the
assigned relay is activated. Setting choice 1 assigns the
output relay, 0 no assignment.
CONTROL 8765432 Assign the Control trip command to the output relays; i.e.
Trip 0000100 to output 4 (RL4). Setting choice 1 assigns the output
relay, 0 none assignment.
CONTROL 8765432 Assign the Control close command to the output relays;
Close 0000100 i-e to output 4 (RL4). Setting choice: 1 assigns the output
relay; 0 no assignment
User Guide P12x/EN FT/F75
COLD LOAD P/UP Assign the tI2> time delay threshold with the cold load
tI2> Yes pick up function.
Setting choice: Yes, No.
COLD LOAD P/UP Assign the tI2>> time delay threshold with the cold load
tI2>> No pick up function.
Setting choice: Yes, No.
Cold Load PU Assign the Thermal overload time delay threshold with
t Therm. ? Yes the cold load pick up function.
Setting choice: Yes, No.
Cold Load PU Displays scaling value, in percent, for the cold load pick
level 200 % up assigned to the selected thresholds.
Setting range is from 100% to 500%, in steps of 1%.
Cold Load PU Displays delay timer setting (tCL) for the Cold Load Pick-
tCL = 400 ms up function.
Setting range is from 0.1 to 3600 s, in steps of 10 ms.
Block I> ? Select the possibility to block the instantaneous signal I>
No in case of circuit breaker failure detection.
Select Yes or No.
Block Ie> ? Select the possibility to block the instantaneous signal
Yes Ie> in case of circuit breaker failure detection.
Select Yes or No.
P12x/EN FT/F75 User Guide
t Close Pulse Displays and sets the closing pulse time. Setting range is
100 ms from 0.1 to 5 s, in steps of 10 ms.
⇒ CB Monitoring
⇒ fault record
⇒ Instantaneous
⇒ Disturb record
⇒ Time peak value
⇒ Rolling demand
To access the RECORDS menu, press & then $ 7 times.
5.10.1 CB MONITORING submenu
Through the CB Monitoring submenu, it is possible to read and clear counter values
associated with the circuit breaker.
Faulted Phase Displays the phase, where a fault occurred, for the
Phase A chosen fault record. (NONE, phase A, B, C, EARTH, AB,
AC, BC, or ABC).
Threshold Displays the origin of the fault that generated the trip
I>> order.
Disturb Rec Trig Select which criteria will start the disturbance record
ON INST. function. Setting choices are ON INST. (starts recording
on instantaneous thresholds) or ON TRIP (starts
recording after a trip happened). Use & to modify the
criteria then press ' to validate your choice.
P12x/EN FT/F75 User Guide
Time Window Set the value for the time window during which peak
5 mn and average values are stored. Select from 5mn, 10mn,
15mn, 30mn, or 60mn using & and press ' to validate
your choice.
5.10.6 ROLLING DEMAND submenu
The Rolling Demand submenu makes it possible to set the values for rolling sub-period and
number of the sub-period used for the calculation of the 3 phase Rolling Average and peak
demand values, available in the Measurement menu.
6. WIRING
MiCOM P120 range of relays have the same terminal layout for common elements. The
wiring diagram for each model is provided in Appendix 1 of the Technical Guide.
6.1 Auxiliary supply
The auxiliary power supply for the MiCOM P120, P121, P122 & P123 relays can be either
direct current with a voltage range of 24-60 VDC, 48-150 VDC, 130-250 VDC, or alternative
current with a voltage range of 110-250 VAC/ 50-60 Hz. The voltage range (Ua) is specified
on the adhesive paper label under the top hinged cover on the front of the relay.
The auxiliary power supply must be connected only to terminals 33 and 34.
6.2 Current measurement inputs
MiCOM P120, P121, P122 and P123 have 3 phase and 1 earth current inputs available for 1
and 5 Amps rated CTs. On each one of these relays, it is possible to combine 1 and 5 Amp
current inputs together (i-e a mix between 1A for earth fault and 5A for phase connections)
(refer to the wiring diagram).
NOTE : All phase inputs must have the same rating (1 or 5 Amps).
6.3 Logic inputs
The number of logic inputs depends on the relay model. The relays have programmable
opto-isolated logic inputs, which can be assigned to any available label or function.
Logic inputs for each relay model:
The voltage range of the inputs is identical to the DC (or AC) auxiliary supply range of the
MiCOM relay (e.g. Uaux = 48-150 Vdc, logic input voltage range = 48-150 Vdc).
On the same MiCOM P12x relay, the user can mix different voltage levels for the logic inputs
(e.g. Uaux = 48-150 Vdc, Input 1= 48 Vdc, Input 2-5= 110 Vdc).
If the user sets the supply of the logic input as AC they are active from 24 to 220Vac.
The automation functions that can be assigned to these logic inputs can be selected from the
AUTOMAT. CTRL Menu.
NOTE : Do not forget to select in the CONFIGURATION/Configuration Inputs
Menu weither the voltage input is "AC" or "DC". .
6.4 Output relays
The number of logic outputs depends on the relay model. The relays have configurable logic
outputs, which can be assigned to any available function.
The number of logic outputs available for each relay model is presented in the following
table:
The first logic output (RL0) is dedicated to indicate a relay fault (Watchdog, WD) and is not
part of this table.
The normally closed (NC) contact of the Watchdog (RL0) can not be configured. The other
contacts can be configured to be activated on activation of the different functions available in
the relay. A basic output matrix is included in the relay.
Some logic outputs have changeover contacts (RL1 and RL2). The other relays (RL3, to RL
9) are normally open contacts.
The protection and control functions that can be assigned to these output relays can be
selected from the AUTOMAT. CTRL Menu.
P12x/EN FT/F75 User Guide
6.5 Communication
MiCOM P120/P121/P122/P123
CONTENTS
BLANK PAGE
1.
DEFAULT DISPLAY
IL1 = 1245 A
Relay 4321
Status 1011
Page 3/32
DEFAULT DISPLAY
IL1 = 1245 A
Page 4/32
[50/51] Phase OC Trip Commands Latch Functions Blocking Logic Output Relays Inputs 1/2
Idmt
IEC SI
Tms
0.025
I>> ?
Yes
I>>
2.0 In
MiCOM P120 - V4 Software
t I>>
300 ms Menu content
I>>> ?
Yes
Menu Content Tables
MiCOM P120/P121/P122/P123
2.
DEFAULT DISPLAY
IL1 = 1245 A
tI>>> Y/N
Ie> Y/N
Software version E/Gnd CT primary tIe> Y/N IL3 Stop bits Delay Type I>>>
5.D 1000 Ie>> Y/N 257.50 A 1 IDMT 10.0 In
MiCOM P121 – V5 SOFTWARE
tIe>> Y/N
Ie>>> Y/N
Frequency E/Gnd CT sec tIe>>> Y/N IN Relay Address Idmt t I>>>
50 Hz 1 20.00 A 12 IEC SI 110 ms
Input 21 Tms
Status 01 0.025
I>> ?
Yes
I>>
2.0 In
Page 5/32
DEFAULT DISPLAY
IL1 = 1245 A
Page 6/32
[50N/51N] E/Gnd Trip Commands Latch Functions Blocking Logic Output Relays
Ie >> ?
Yes
Ie >>
0.01 Ien
Delay Type
DMT
t Ie >>
300 ms MiCOM P121 - V5 Software
Menu content
Menu Content Tables
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IL1 = 1245 A
AUTOMAT. CTRL
Output 2 None
No
Unlatch
52 a
Output 3 52 b
MiCOM P120/P121/P122/P123
Yes CB FLT
Aux 1
Aux 2
Output 4 Blk Log
No
Page 7/32
3.
DEFAULT DISPLAY
IA = 1245 A
Page 8/32
OP PARAMETERS CONFIGURATION
P12x/EN HI/F75
Password
Display CT Ratio Led 5 / 6 / 7 / 8 Group Select Alarms Inputs
****
Description Default Display Line CT primary Led Change Group Inst. Self-reset ? Inputs : 321
P122-1 RMS I A 1000 I> Y/N INPUT = EDGE No 001
tI> Y/N
l>> Y/N
Reference Phase A Text Line CT sec tI>> Y/N Setting Group Reset led on Voltage input =
ALST A 1 I>>> Y/N 1 fault? No DC
tI>>> Y/N
Ie> Y/N
Software version Phase B Text E/Gnd CT primary tIe> Y/N Alarm Battery =
5.F B 1000 Ie>> Y/N No
MiCOM P122 – V5 SOFTWARE
tIe>> Y/N
Ie>>> Y/N
Frequency Phase C Text E/Gnd CT sec tIe>>> Y/N
50 Hz C 1 Therm Trip Y/N
Brkn. Cond Y/N
CB Fail Y/N
Active Group = E/Gnd Text tI2> Y/N
1 N tI2>> Y/N
Input 1 Y/N
Input 2 Y/N
Input 321 Input 3 Y/N
Status 101 tAux 1 Y/N
tAux 2 Y/N
Relay 654321
Status 001011
Date
14/08/02
Time
MiCOM P122 - V5 Software
13 : 15 : 33
Menu content
Menu Content Tables
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
PROTECTION
CONFIGURATION MEASUREMENTS COMMUNICATION
G1/G2
Maintenance Mode Phase rotation = 257.05 A 0.00 A Baud Rate Yes Yes
oui A-B-C 19200 Bd
IB Average IA RMS = I> I>>>
258.80 A 150 A 0.1 In 10.0 In
RELAYS 65W4321 Parity
CMD 0000000 None
IC Average IB RMS = Delay Type t I>>>
MiCOM P120/P121/P122/P123
ROLLING AVERAGE
MiCOM P122 - V5 Software
I C RMS= 0.00 A
Menu content
P12x/EN HI/F75
Page 9/32
DEFAULT DISPLAY
IA = 1245 A
PROTECTION
Page 10/32
G1/G2
P12x/EN HI/F75
Ie > I2 >
Iθ> I<
0.01 Ien Ie >>> ? 0.1 In
0.1 In 0.2 In
Yes
Delay Type Delay Type
INV IDMT Te tI <
Ie >>>
1 mn 200 ms
1.0 Ien
Idmt Curve
IEC SI IEC SI k
t Ie >>>
1.05
300 ms
Tms Tms
0.025 0.025 θ Trip
100 %
t Reset t Reset
60 ms 60 ms θ Alarm ?
Yes
Ie >> ? I2 >> ?
Yes Yes θ Alarm
100 %
Ie >> I2 >>
0.01 Ien 0.5 In
t Ie >>
300 ms
MiCOM P122
V5 Software - Menu content
Menu Content Tables
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
AUTOMAT. CTRL
Trip Commands Latch Functions Blocking Logic 1/2 Logic Select 1/2 Output Relays
Page 11/32
DEFAULT DISPLAY
IA = 1245 A
AUTOMAT. CTRL
Page 12/32
Comm.Ord. Latch
Latch Output Relays Inputs 1/2/3 Broken Conductor Cold Load PU CB Fail CB Supervision times
P12x/EN HI/F75
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
RECORDS
CB Monitoring Fault Record Instantaneous Disturb Record Time Peak Value Rolling Demand
Menu Content Tables
CB Opening Time Record Number Number Pre-Time Time Window Sub Period
83 ms 4 5 1.3 s 5 mn 1mn
IA Magnitude
1200 A MiCOM P122 - V5 Software
IB Magnitude Menu content
500 A
IC Magnitude
480 A
IN Magnitude
103 A
P12x/EN HI/F75
Page 13/32
4.
DEFAULT DISPLAY
IA = 1245 A
OP PARAMETERS CONFIGURATION
Page 14/32
P12x/EN HI/F75
Password
Display CT Ratio LED 5 / 6 / 7 / 8 Group Select Alarms Inputs
****
Description Default Display Line CT primary Led Change Group Inst. Self-reset ? Inputs : 54321
P123-1 RMS I A 1000 I> Y/N Input = EDGE No 00001
tI> Y/N
l>> Y/N
Reference Phase A Text Line CT sec tI>> Y/N Setting Group Reset led on Voltage input =
ALST A 1 I>>> Y/N 1 fault? No DC
tI>>> Y/N
Ie> Y/N
Software version Phase B Text E/Gnd CT primary tIe> Y/N Alarm Battery =
5.F B 1000 Ie>> Y/N No
MiCOM P123 – V5 SOFTWARE
tIe>> Y/N
Ie>>> Y/N
Frequency Phase C Text E/Gnd CT sec tIe>>> Y/N
50 Hz C 1 Therm Trip Y/N
Brkn. Cond Y/N
CB Fail Y/N
Active Group = E/Gnd Text tI2> Y/N
1 N Input 1 Y/N
Input 2 Y/N
Input 3 Y/N
Input 54321 Input 4 Y/N
Status 00101 Input 5 Y/N
Recloser Run Y/N
Recloser Blocked Y/N
Relay 87654321 tAux 1 Y/N
Status 00001011 tAux 2 Y/N
tI2>> Y/N
Date
14/08/02
Time
MiCOM P123 - V5 Software
14 : 15 : 34 Menu content
Menu Content Tables
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
PROTECTION
CONFIGURATION MEASUREMENTS COMMUNICATION
G1/G2
Maintenance Mode Phase rotation = IA Max IC RMS = Reclose Stats Baud Rate I>?
oui A-B-C 257.05 A 0.00 A RST = [C] 19200 Bd Yes
Menu Content Tables
I>>>
10.0 In
t I>>>
MiCOM P123 - V5 Software - Menu content 110 ms
P12x/EN HI/F75
Page 15/32
DEFAULT DISPLAY
IA = 1245 A
PROTECTION
G1/G2
Page 16/32
P12x/EN HI/F75
[50N/51N] E/Gnd [46] Neg Seq OC [49] Therm OL [37] Undercurrent [79] Autoreclose
t Ie >>
300 ms
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
AUTOMAT. CTRL
Trip Commands Latch Functions Blocking Logic 1/2 Logic Select 1/2 Output Relays
Yes
1000100
No Yes
I>
Trip tI >> Latch tI >> Block 1 tI >> Sel 1 tI >>> tl >
Yes Trip tAux 1 Yes Latch tAux 1 Yes Yes I >>
Yes Yes tl >>
Trip tI >>> Latch tI >>> Block 1 tI >>> Sel1 tle >> I >>>
Trip tAux 2 Latch tAux 2
MiCOM P120/P121/P122/P123
Page 17/32
DEFAULT DISPLAY
IA = 1245 A
AUTOMAT. CTRL
Page 18/32
Relays times
Aux3 Time
Cold Load PU ΣAmps (n) tOpen Pulse
tAux3 300 ms tTherm ? Yes 3 E6 300ms
Cold Load PU
MiCOM P123 - V5 Software - Menu content tCL 2s
Menu Content Tables
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
RECORDS
CB Monitoring Fault Record Instantaneous Disturb Record Time Peak Value Rolling Demand
Menu Content Tables
CB Opening Time Record Number Number Pre-Time Time Window Sub Period
83 ms 4 5 1.3 s 5 mn 1mn
IA Magnitude
1200 A
IB Magnitude
MiCOM P123 V5 Software
500 A
Menu content
IC Magnitude
480 A
IN Magnitude
103 A
P12x/EN HI/F75
Page 19/32
5.
DEFAULT DISPLAY
IA = 1245 A
OP PARAMETERS CONFIGURATION
Page 20/32
Password
P12x/EN HI/F75
Description Default Display Line CT primary Led Change Group Inst. Self-reset ? Inputs : 321
P122-1 RMS I A 1000 I> Y/N Input = MENU No 001
tI> Y/N
l>> Y/N
Reference Phase A Text Line CT sec tI>> Y/N Setting Group Reset led on Voltage input =
ALST A 1 I>>> Y/N 1 fault? No DC
tI>>> Y/N
Ie> Y/N
Software version Phase B Text E/Gnd CT primary tIe> Y/N Alarm Battery =
5.D B 1000 Ie>> Y/N No
MiCOM P122 – V6 SOFTWARE
tIe>> Y/N
Ie>>> Y/N
Frequency Phase C Text E/Gnd CT sec tIe>>> Y/N
50 Hz C 1 Therm Trip Y/N
Brkn. Cond Y/N
CB Fail Y/N
Active Group = E/Gnd Text tI2> Y/N
1 N tI2>> Y/N
Input 1 Y/N
Input 2 Y/N
Input 321 Input 3 Y/N
Status 101 tAux 1 Y/N
tAux 2 Y/N
Relay 654321
Status 001011
Date
04/03/02
Time
MiCOM P122 - V6 Software
14 : 15 : 34
Menu content
Menu Content Tables
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
IN - fn = MAX. SUBPERIOD
RST = [C] 0.00A I C RMS=254.1 A
Page 21/32
DEFAULT DISPLAY
IA = 1245 A
PROTECTION
G1/G2
Page 22/32
[50/51] Phase OC [50N/51N] E/Gnd [46] Neg Seq OC [49] Therm OL [37] Undercurrent
P12x/EN HI/F75
I>>> ?
I> Ie > I2 > Iθ> I<
Yes
0.1 In 0.01 Ien 0.1 In 0.1 In 0.2 In
Ie >>> ?
Yes
Delay Type I>>> sample
Delay Type Delay Type Te tI <
IDMT Yes
IDMT IDMT 1 mn 200 ms
Ie >>> sample
I>>> Yes
Idmt Idmt Curve k
IEC SI 10.0 In
IEC SI IEC SI 1.05
Ie >>>
Tms t I>>> 1.0 Ien
110 ms Tms Tms θ Trip
0.025
0.025 0.025 100 %
t Ie >>>
tReset 300 ms
t Reset t Reset θ Alarm ?
60 ms
60 ms 60 ms Yes
I>> ?
Ie >> ? I2>> ? θ Alarm
Yes
Yes Yes 100 %
I>>
2.0 In Ie >> I2>>
0.01 Ien 0.5 In
Delay Type
DMT Delay Type t I2>>
DMT 110 ms
t I>>
300 ms
t Ie >>
300 ms
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
AUTOMAT. CTRL
Trip Commands Latch Functions Blocking Logic 1/2 Logic Select 1/2 Output Relays
No Yes I>
Trip tI >> Latch tI >> Block 1 tI >> Sel 1 tI >>> tl >
Yes Trip tAux 1 Yes Latch tAux 1 Yes Yes I >>
Yes Yes tl >>
Trip tI >>> Latch tI >>> Block 1 tI >>> Sel1 tle >> I >>>
Yes Trip tAux 2 Yes Yes Yes tl >>>
MiCOM P120/P121/P122/P123
Page 23/32
DEFAULT DISPLAY
IA = 1245 A
AUTOMAT. CTRL
Page 24/32
Latch Output
Inputs 1/2/3 Broken Conductor Cold Load PU CB Fail CB Supervision
Relays
P12x/EN HI/F75
Cold Load PU n
Level 120 % 2
Cold Load PU
tCL 2s
MiCOM P122 - V6 Software - Menu content
Menu Content Tables
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
RECORDS
CB Monitoring Fault Record Instantaneous Disturb Record Time Peak Value Rolling Demand
Record Number
83 ms 4 5 1.3 s 5 mn 1mn
IA Magnitude
1200 A
IB Magnitude
MiCOM P122 - V6 Software -
500 A
IC Magnitude
Menu content
480 A
IN Magnitude
103 A
P12x/EN HI/F75
Page 25/32
6.
DEFAULT DISPLAY
IA = 1245 A
OP PARAMETERS CONFIGURATION
Page 26/32
Password
P12x/EN HI/F75
Description Default Display Line CT primary Led Change Group Inst. Self-reset ? Inputs : 54321
P123-1 RMS I A 1000 I> Y/N Input = Input No 00001
tI> Y/N
l>> Y/N
Reference Phase A Text Line CT sec tI>> Y/N Setting Group Reset led on Voltage input =
ALST A 1 I>>> Y/N 1 fault? No DC
tI>>> Y/N
Ie> Y/N
Software version Phase B Text E/Gnd CT primary tIe> Y/N Alarm Battery =
6.E B 1000 Ie>> Y/N No
MiCOM P123 – V6 SOFTWARE
tIe>> Y/N
Ie>>> Y/N
Frequency Phase C Text E/Gnd CT sec tIe>>> Y/N
50 Hz C 1 Therm Trip Y/N
Brkn. Cond Y/N
CB Fail Y/N
Active Group = E/Gnd Text tI2> Y/N
1 N tI2>> Y/N
Input 1 Y/N
Input 2 Y/N
Input 54321 Input 3 Y/N
Status 00101 Input 4 Y/N
Input 5 Y/N
Recloser Run Y/N
Relay 87654321 Recloser Blocked Y/N
Status 00001011 tAux 1 Y/N
tAux 2 Y/N
Conf Soft Y/N
Date
04/03/02
Time
MiCOM P123 - V6 Software
14 : 15 : 34
Menu content
Menu Content Tables
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
PROTECTION
CONFIGURATION MEASUREMENTS COMMUNICATION
G1/G2
Maintenance Mode Phase rotation = IA Max IC RMS = Reclose Stats Baud Rate I>?
Yes A-B-C 257.05 A 0.00 A RST = [C] 19200 Bd Yes
Menu Content Tables
Tms
I1= MAX. SUBPERIOD Cycle 3 Recloses Date format =
0.025
103 A RST =[C] 0 PRIVATE
tReset
I2= MAX. SUBPERIOD Cycle 4 Recloses
60 ms
50 A I A RMS=254.2 A 0
I>> ?
RATIO I 2 / I 1 = MAX. SUBPERIOD Total Trip &
Yes
50 % I B RMS=254.2 A Lockout 0
I>>
IN - fn = MAX. SUBPERIOD 2.0 In
RST = [C] 0.00A I C RMS=254.1 A
Delay Type
Thermal θ ROLLING AVERAGE DMT
RST = [C] 0% RST=[C]
t I>>
Max & Average I ROLLING AVERAGE 300 ms
RST = [C] I A RMS= 0.00 A
tReset
0 ms
Max IA RMS ROLLING AVERAGE
350 A I B RMS= 0.00 A I>>>
I>>> ?
10.0 In
Yes
t I>>>
110 ms I>>> sample
MiCOM P123 - V6 Software - Menu content Yes
P12x/EN HI/F75
Page 27/32
DEFAULT DISPLAY
IA = 1245 A
PROTECTION
G1/G2
Page 28/32
[50N/51N] E/Gnd [46] Neg Seq OC [49] Therm OL [37] Undercurrent [79] Autoreclose
P12x/EN HI/F75
t Ie >>
300 ms
tReset
0 ms
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
AUTOMAT. CTRL
Trip Commands Latch Functions Blocking Logic 1/2 Logic Select 1/2 Output Relays
No Yes I>
Trip tI >> Latch tI >> Block 1 tI >> Sel 1 tI >>> tl >
Yes Trip tAux 1 Yes Latch tAux 1 Yes Yes I >>
Yes Yes tl >>
Trip tI >>> Latch tI >>> Block 1 tI >>> Sel1 tle >> I >>>
Yes Trip tAux 2 Yes Yes Yes tl >>>
MiCOM P120/P121/P122/P123
Page 29/32
DEFAULT DISPLAY
IA = 1245 A
AUTOMAT. CTRL
Page 30/32
Relays
MiCOM P120/P121/P122/P123
DEFAULT DISPLAY
IA = 1245 A
RECORDS
CB Monitoring Fault Record Instantaneous Disturb Record Time Peak Value Rolling Demand
Record Number
83 ms 4 5 1.3 s 5 mn 1mn
IA Magnitude
1200 A
IB Magnitude
MiCOM P123 - V6 Software
500 A
IC Magnitude
Menu content
480 A
IN Magnitude
103 A
P12x/EN HI/F75
Page 31/32
P12x/EN HI/F75 Menu Content Tables
BLANK PAGE
Technical Data P12x/EN TD/F75
MiCOM P120/P121/P122/P123
CONTENT
1. RATINGS 3
1.1 Power Supply 3
1.2 Frequency 3
1.3 Current Inputs 3
1.4 Logic Inputs 4
1.4.1 Supply 4
1.5 Output Relay Characteristic 4
2. INSULATION 5
3. EMC TESTS 5
4. ENVIRONMENT 5
7. DEVIATION OF MEASUREMENTS 7
11. COMMUNICATION 17
12. CURVES 18
12.1 General 18
12.1.1 Inverse Time Curves: 18
12.1.2 Reset Timer 19
12.2 Thermal Overload Curves 20
Technical Data P12x/EN TD/F75
1. RATINGS
1.1 Power Supply
1.2 Frequency
1.4.1 Supply
The logic inputs shall be powered with a DC voltage, excepted the M auxiliary voltage range
which acccepts both DC and AC voltage as logic input control voltage.
(*) The tolerance on the auxiliary voltage variations for the logic inputs is ±20% in DC voltage
and −20%, +10% in AC voltage.
(**) Logic input recognition time for EA approval. Dedicated filtering on 24 samples (15 ms at
50 Hz)
1.5 Output Relay Characteristic
Contact rating
Contact relay Dry contact Ag CdO
Make current Max. 30A and carrry for 3s
Carry capacity 5A continuous
Rated Voltage 250Vac
Breaking characteristic
Breaking capacity AC 1250 VA resistive
1250 VA inductive (P.F. = 0.5)
220 Vac, 5A (cos ϕ = 0.6)
Breaking capacity DC 135 Vdc, 0.3A (L/R = 30 ms)
250 Vdc, 50W resistive or
25W inductive (L/R=40ms)
Operation time <7ms
Durability
Loaded contact 10000 operation minimum
Unloaded contact 100000 operation minimum
Technical Data P12x/EN TD/F75
2. INSULATION
Dielectric withstand IEC 60-255-5 2 kV common mode
1 kV differential mode
Impulse voltage IEC 60-255-5 5 kV common mode
1 kV differential mode
3. EMC TESTS
High frequency IEC 61000-4-1 2.5 kV common mode, class 3
disturbance 1 kV differential mode, class 3
Fast transient IEC 61000-4-4 4 kV common mode, class 4
ANSI C37.90.1 2 kV others, class 4
Electrostatic IEC 61000-4-2 8 kV, class 4
discharge
RFI immunity ANSI C37.90.2 35 v/M
radiated IEC 61000-4-3 10 V/m
4. ENVIRONMENT
Temperature IEC 600-68-2-1 Storage –25 °C to +70 °C
IEC 600-68-2-2 Operation -25 °C to + 55 °C
Humidity dam heat IEC 600-68-2-3 56 days at 93% RH and 40 °C
Enclosure protection IEC 60-529 IP 52, IK 07
Sinusoidal Vibrations IEC 60-255-21-1 Response and endurance, class 2
Shocks IEC 60-255-21-2 Response and withstand, class 1
Bump IEC 60-255-21-2 Response and withstand, class 1
Seismic IEC 60-255-21-3 Class 1
P12x/EN TD/F75 Technical Data
7. DEVIATION OF MEASUREMENTS
Measurement Range Deviation
Phase current 0.1 to 40 In Typical ±0.5% at In
Earth current 0.002 to 1Ien Typical ±0.5% at Ien
0.01 to 8 Ien Typical ±0.5% at Ien
0.1 to 40 Ien Typical ±0.5% at Ien
P12x/EN TD/F75 Technical Data
Setting Range
[51] Phase OC Min Max Step
I> ? No or Yes
I> 0.1 In 25 In 0.01 In
Delay type DT or IDMT (IEC_STI, IEC_SI,
IEC_VI, IEC_EI, IEC_LTI, C02, C08,
IEEE_MI, IIEEE_VI, IEEE_EI, RI,
RECT curve)
tI> 0s 150 s 0.01 s
I> TMS 0.025 1.5 0.025
I> Reset Delay Type DT or IDMT
I> RTMS 0.025 3.2 0.025
I> tReset 0.00 s 100 s 0.01 s
I>> ? No or Yes
I>> 0.5 In 40 In 0.01 In
Delay type DT or IDMT (IEC_STI, IEC_SI,
IEC_VI, IEC_EI, IEC_LTI, C02, C08,
IEEE_MI, IIEEE_VI, IEEE_EI, RI,
RECT curve)
tI>> 0s 150 s 0.01 s
I>> TMS 0.025 1.5 0.025
I>> Reset Delay Type DT or IDMT
I>> RTMS 0.025 3.2 0.025
I>> tReset 0.00 s 100 s 0.01 s
I>>> ? No or Yes or Peak
I>>> 0.5 In 40 In 0.01 In
tI>>> 0s 150 s 0.01 s
8.2 [50N/51N] Earth fault protection (P120, P121, P122 & P123)
Setting Range
[Earth] OC Min Max Step
High sensitivity current set Cortec code P12-C-X---X
Ie> 0.002 Ien 1 Ien 0.001 Ien
Ie>> 0.002 Ien 1 Ien 0.001 Ien
Ie>>> 0.002 Ien 1 Ien 0.001 Ien
Med. sensitivity current set Cortec code P12-B-X---X
Ie> 0.01 Ien 1 Ien 0.005 Ien
Ie>> 0.01 Ien 8 Ien 0.005 Ien
Ie>>> 0.01 Ien 8 Ien 0.005 Ien
Low sensitivity current set Cortec code P12-A-X---X
Ie> 0.1 Ien 25 Ien 0.1 Ien
Ie>> 0.5 Ien 40 Ien 0.1 Ien
Ie>>> 0.5 Ien 40 Ien 0.1 Ien
Ie> ? No or Yes
Delay type DT or IDMT (IEC_STI, IEC_SI,
IEC_VI, IEC_EI, IEC_LTI, C02, C08,
IEEE_MI, IIEEE_VI, IEEE_EI, RI,
RECT curve)
tIe> 0s 150 s 0.01 s
Ie> TMS 0.025 1.5 0.025
Ie> Reset Delay Type DT or IDMT
Ie> RTMS 0.025 3.2 0.025
Ie> tReset 0.00 s 100 s 0.01 s
Ie>> ? No or Yes
Delay type DT or IDMT (IEC_STI, IEC_SI,
IEC_VI, IEC_EI, IEC_LTI, C02, C08,
IEEE_MI, IIEEE_VI, IEEE_EI, RI,
RECT curve)
tIe>> 0s 150 s 0.01 s
Ie>> TMS 0.025 1.5 0.025
Ie>> Reset Delay Type DT or IDMT
Ie>> RTMS 0.025 3.2 0.025
Ie>> tReset 0.04 s 100 s 0.01 s
tIe>> 0s 150 0.01 s
Ie>>> ? No or Yes
tIe>>> 0s 150 s 0.01 s
Ie>>> tReset 0.00 s 100 s 0.01 s
P12x/EN TD/F75 Technical Data
Setting ranges
[37] Under Current Min Max Step
I< ? Yes or No
I< 0.2 In 1 In 0.01 In
tI< 0s 150 s 0.01 s
Setting ranges
[46] Neg.Seq. OC Min Max Step
I2> ? No or Yes
I2> 0.1 In 40 In 0.01 In
Delay Type DT or IDMT (IEC_STI, IEC_SI,
IEC_VI, IEC_EI, IEC_LTI, C02, C08,
IEEE_MI, IIEEE_VI, IEEE_EI, RI,
RECT curve)
tI2> 0s 150s 0.01s
I2> TMS 0.025 1.5 0.025
I2> Reset Delay Type DT or IDMT
I2> RTMS 0.025 1.5 0.025
I2> tReset 0.04 s 100 s 0.01 s
I2>> ? No or Yes
I2>> 0.1 In 40 In 0.01 In
tI2>> 0s 150s 0.01s
Technical Data P12x/EN TD/F75
Setting range
[79] Autoreclose Min Max Step
Autoreclose ? Yes or No
Ext. CB Fail ? Yes or No
Ext. CB Fail time 0.01 s 600 s 0.01 s
Aux1 ((I>) ? Yes or No
Aux2 (Ie>) ? Yes or No
Ext Block ? Yes or No
Dead time
tD1 0.01 s 300 s 0.01 s
tD2 0.01 s 300 s 0.01 s
tD3 0.01 s 600 s 0.01 s
tD4 0.01 s 600 s 0.01 s
Reclaim time
tR 0.02 s 600 s 0.01 s
Inhib time
tI 0.02 s 600 s 0.01 s
Phase Cycles 0 4 1
E/Gnd Cycles 0 4 1
Cycles 4321 Settings
tI> 1111 0 or 1 or 2
tI>> 1111 0 or 1 or 2
tI>>> 1111 0 or 1 or 2
tIe> 1111 0 or 1 or 2
tIe>> 1111 0 or 1 or 2
tIe>>> 1111 0 or 1 or 2
tAux1 1111 0 or 1 or 2
tAux2 1111 0 or 1 or 2
Setting range
Cold Load PU Min Max Step
Cold Load PU ? Yes or No
Level 20% 500% 1%
tCL 0.1 s 3600 s 0.1 s
Setting range
Auxiliary timers Min Max Step
tAux1 0 200 s 0.01 s
tAux2 0 200 s 0.01 s
tAux3 0 200 s 0.01 s
tAux4 0 200 s 0.01 s
Setting range
Broken Conductor Min Max Step
Brkn.Cond ? Yes or No
Ratio I2/I1 20% 100% 1%
Brkn.Cond Time tBC 1s 14400 s 1s
Setting range
CB Fail Min Max Step
CB Fail ? Yes or No
I< BF 0.02 In 1In 0.01 In
CB Fail Time tBF 0.03 s 10 s 0.01 s
Block I> No Yes Yes or No
Block Ie> No Yes Yes or No
Technical Data P12x/EN TD/F75
Setting range
TC Supervision Min Max Step
TC Supervision ? Yes or No
t trip circuit tSUP 0.1 s 10 s 0.05 s
(*)Note: The tOpen/Close Pulse is available in the P123 for the Local /Remote functionality
9.7 SOTF/TOR Switch on to fault / Trip on reclose (P123)
9.7.1 Setting Ranges
Capacity 75 events
Time-tag 1 millisecond
Triggers Any selected protection alarm and
threshold
Logic input change of state
Setting changes
Self test events
Capacity 5 faults
Time-tag 1 millisecond
Triggers Any selected protection alarm and
threshold
Data Fault date
Protection thresholds
Setting Group
AC inputs measurements (RMS)
Fault measurements
11. COMMUNICATION
Type Relay
Physical Link Connectors Data Rate Protocol
Port position
RS485 Rear port Screened twister Screws or 300 to 38400 baud ModBus RTU, Courier,
pair snap-on (programmable) IEC60870-5-103,
DNP3.0
RS232 Front port Screened twister Sub–D 9 pin 300 to 38400 baud ModBus RTU
pair female (programmable)
(P122 &
connector
P123)
P12x/EN TD/F75 Technical Data
12. CURVES
12.1 General
Although the curves tend towards infinite when the current approaches Is (general
threshold), the minimum guaranteed value of the operating current for all the curves with the
inverse time characteristic is 1.1Is (with a tolerance of ± 0.05Is).
12.1.1 Inverse Time Curves:
The first stage thresholds for phase (earth) overcurrent can be selected with an inverse
definite minimum time (IDMT) characteristic. The time delay is calculated with a
mathematical formula.
In all, there are eleven IDMT characteristics available.
The mathematical formula applicable to the first ten curves is:
K
t = T × + L
(I I S )α − 1
Where:
t Operation time
K Factor (see table)
I Value of measured current
Is Value of the programmed threshold (pick-up value)
α Factor (see table)
L ANSI/IEEE constant (zero for IEC and RECT curves)
T Time multiplier setting from 0.025 to 1.5
1
t= K ⋅
0.236
0 .339 −
( )
I
Is
K setting is from 0.10 to 10 in steps of 0.05.
The equation is valid for 1.1 ≤ I/Is ≤ 20.
Technical Data P12x/EN TD/F75
K² - θ²
t Trip = Te In
K ² − θtrip²
Where :
t Trip = Time to trip (in seconds)
Te = Thermal time constant of the equipment to be protected (in seconds)
Iθ> = Full load current rating given by the national standard or by the supplier
k = Factor associated to the thermal state formula
² −t −t
Ieq 1− e
Te
Te
Θ τ +1 = + Θ τe
kxIΘ >
θ being calculated every 20ms.
Technical Data P12x/EN TD/F75
1
TIME IN SECONDS
0,1
0,01
0,001
1 10 100
A
B
C
TIME IN SECONDS
0,1
D
0,01 E
0,001
1 10 100
P0007ENb
Technical Data P12x/EN TD/F75
100
10
A
B
TIME IN SECONDS
C
1
0,1
0,01
1 10 100
P0008ENa
P12x/EN TD/F75 Technical Data
10
TIME IN SECONDS
1 A
B
0,01
0,001
1 10 100
P0009ENa
Technical Data P12x/EN TD/F75
10000
1000
100
TIME IN SECONDS
10
A
B
0,1 C
0,01
0,001
1 10 100
P00010ENa
P12x/EN TD/F75 Technical Data
10000
1000
100
TIME IN SECONDS
A
B
D
1
E
0,1
1 10 100
P0011ENb
Technical Data P12x/EN TD/F75
12.4 RI Curves
RI CURVES
100
10
TIME IN SECONDS
0,1
1 10 100
P0012ENa
P12x/EN TD/F75 Technical Data
10
1
TIME IN SECONDS
0,1
0,01
0,001
0,0001
0,01 0,1 1 10 100
10
1
TIME IN SECONDS
0,1
A
A B
B C
C
D
0,01
D
E
0,001 E
0,0001
0,01 0,1 1 10 100
B : TMS/RTMS=1 A : TMS/RTMS=1.25
1000
100
10
TIME IN SECONDS
A
1
A B
B C
C
D
D
0,1
E
E
0,01
0,01 0,1 1 10 100
100
10
A
B
C
D
1
TIME IN SECONDS
A
E B
0,1 C
0,01
0,001
0,01 0,1 1 10 100
1000
100
B
C
TIME IN SECONDS
10
1
A
E B
0,1
D
E
0,01
0,01 0,1 1 10 100
1000
100
A
B
10 C
D
TIME IN SECONDS
A
B
0,1 C
0,01
0,001
0,01 0,1 1 10 100
10000
1000
100
TIME IN SECONDS
45900
t=
(I/Is)5.6-1
1
0,1
1 1.6 10 100
TMS = 1
P0019ENa
Technical Data P12x/EN TD/F75
50
P0020ENa
1.5
1.0
0.5
40
Primary zero sequence current (A)
30
20
3
10
5
1
5
Time (sec)
P12x/EN TD/F75 Technical Data
1000
100
TIME IN SECONDS
A
10
B
C
D
E
1
0,1
1 10
MiCOM P120/P121/P122/P123
APPLICATION GUIDE
Application Guide P12x/EN AP/F75
CONTENTS
1. INTRODUCTION 5
1.1 Protection of Underground and Overhead Lines 5
1.2 MiCOM Overcurrent Relays 6
7. RECTIFIER PROTECTION 22
31. ROLLING AND PEAK VALUE DEMANDS (P122 & P123 ONLY) 72
31.1 Rolling demand 72
31.2 Peak value demand 73
32. CT REQUIREMENTS 74
32.1 Definite time / IDMT overcurrent & earth fault protection 74
32.2 Instantaneous overcurrent & earth fault protection 74
32.3 Definite time / IDMT sensitive earth fault (SEF) protection 74
32.4 Low impedance restricted earth fault (REF) protection 75
32.5 High Impedance Restricted Earth Fault Protection 75
P12x/EN AP/F75 Application Guide
BLANK PAGE
Application Guide P12x/EN AP/F75
1. INTRODUCTION
1.1 Protection of Underground and Overhead Lines
The secure and reliable transmission and distribution of power within a network is heavily
dependent upon the integrity of underground cables and overhead lines, which link the
various sections of the network together. Therefore the associated protection system must
also provide both secure and reliable operation.
The most common fault conditions, on underground cables and overhead lines, are short
circuit faults. These faults may occur between the phase conductors but will most often
involve one or more phase conductor becoming short-circuited to earth.
Faults caused by short circuits require the fastest faulted conductor clearance times but at
the same time allowing for suitable co-ordination with other downstream protection devices.
Fault sensitivity is an issue common to all voltage levels. For transmission systems, tower-
footing resistance can be high. Also, high resistance faults might be prevalent where lines
pass over sandy or rocky terrain. Fast, discriminative faulted conductor clearance is required
for these fault conditions.
The effect of fault resistance is more pronounced on lower voltage systems, resulting in
potentially lower fault currents, which in turn increases the difficulty in the detection of high
resistance faults. In addition, many distribution systems use earthing arrangements designed
to limit the passage of earth fault current.
Earthed methods as such as using resistance, Petersen coil or insulated systems make the
detection of earth faults arduous. Special protection equipment is often used to overcome
these problems.
Nowadays, the supply continuity in the energy distribution is of paramount importance.
On overhead lines most of faults are transient or semi-permanent in nature.
In order to increase system availability multi-shot autoreclose cycles are commonly used in
conjunction with instantaneous tripping elements. For permanent faults it is essential that
only the faulted section of the network is isolated. High-speed, discriminative fault clearance
is therefore a fundamental requirement of any protection scheme on a distribution network.
Power transformers are installed at all system voltage levels and have their own specific
requirements with regard to protection. In order to limit the damage incurred by a transformer
under fault conditions, fast clearance of the windings with phase to phase and phase to earth
faults is a primary requirement.
Damage to electrical plant equipment such as transformers, cables and lines may also be
incurred by excessive loading conditions, which leads directly to overheating of the
equipment and subsequent degradation of their insulation. To protect against such fault
conditions, protective devices require thermal characteristics too.
Uncleared faults, arising either from the failure of the associated protection system or of the
switchgear itself, must also be considered. The protection devices concerned should be
fitted with logic to deal with breaker failure and relays located upstream must be able to
provide adequate back-up protection for such fault conditions.
Other situations may arise on overhead lines, such as broken phase conductors.
Traditionally, a series fault has been difficult to detect.
With today's digital technology, it is now possible to design elements, which are responsive
to such unbalanced system, conditions and to subsequently issue alarm and trip signals.
On large networks, time co-ordination of the overcurrent and earth fault protection relays can
often lead to problematic grading situations or, as is often the case, excessive fault
clearance times. Such problems can be overcome by relays operating in blocked overcurrent
schemes.
P12x/EN AP/F75 Application Guide
MiCOM P120, P121, P122 and P123 relays have been designed to provide higher
functionality in terms of protections, measuring, automatic operation and order control. They
can be applied to industrial and distribution network applications, as well as in high voltage
and extremely high voltage protection applications.
They can operate in networks with neutral earthed by impedance, by resonant system such
as Petersen coil, in insulated system and in system with neutral earthed.
The protection functions can be used associated with the blocking feature in order to
optimise the performance of the protection schemes, thus reducing operating times.
The earth and phase protection functions include instantaneous and time delay information.
The delay time for the first and second stage for phase and earth fault protections can be
chosen to be in definite or inverse delay time (IEC, ANSI/IEEE, CO, RI and RECT).
This wide choice of characteristics of triggering times makes it possible to easily integrate
these relays to an existing protection scheme, irrespective of other relays already installed
on the network.
Application Guide P12x/EN AP/F75
The protection and additional features of each model are listed in the following table.
Inst. I>
Block. tI>
&
Inst. I>>
Block. tI>>
&
Inst. I>>>
Block. tI>>>
&
Blocking logic
P0022ENa
The logic associated to the earth fault threshold is identical to the one described above. The
different thresholds I> & tI>, I>> & tI>> and I>>> & tI>>> are respectively replaced by
thresholds Ie> & tIe>, Ie>> & tIe>> and Ie>>> & te>>>.
Thanks to the «Blocking Logic» function, it is possible to freeze the timer as long as the "Blk
Log" signal is active.
As soon as the blocking “Blk Log" signal disappears, if the overcurrent value is still over the
set threshold, the time delay resumes its countdown considering the value prior to the
activation of the blocking function as its new initial value. This allows a faster clearance of
the fault after a reset of the “Blk Log" signal.
2.1 Instantaneous function (50/50N)
For P122 and P123 relays :
In order to ensure fast tripping on highly saturated current signal, it has been decided that
I>>> and Ie>>> should operate on a current sample base in addition to the Fast Fourier
transformation bases (see User Guide chapter). Both algorithms can operate on a highly
saturated current signal. However with a high X/R ratio, it is recommended to use the sample
base method.
As soon as a phase (or earth) threshold is running, the instantaneous output associated with
this threshold is activated. This output indicates that the protection element has detected a
phase (or earth) fault and that the time delay associated with the threshold has started. This
time delay can be blocked via the logic input "Blk Log" associated with this threshold. If this
blocking input is activated by an output contact of a downstream relay, the logic that will lead
to the trip command is then blocked only if the relay that is the closest to the fault can see
and therefore eliminate the fault. This principle is known as «Blocking logic» or «Blocking». It
is described in more detail in this document.
2.2 DMT thresholds
The three phase (earth) overcurrent thresholds can be selected with a time constant delay.
The time to operate is equal to the time delay set, plus the time for the output contact to
operate (typically about 20 to 30 ms ; 20ms for a current exceeding or equal to 2 times the
threshold) and the time required to detect the overcurrent state (maximum 20ms at 50Hz).
For DMT curves, a reset timer "t Reset" is associated with the first and second thresholds
(phase and earth elements).
2.3 IDMT thresholds
2.3.1 Inverse time curves
The first and second phases (earth) overcurrent threshold can be selected with a dependent
time characteristic. The time delay is calculated with a mathematical formula.
There are eleven inverse time characteristics available.
The mathematical formula applicable to the first ten curves is :
K
t=T x ( +L )
(I/IS)α–1
Where:
t = Tripping time
K = Coefficient (see table)
I = Value of measured current
IS = Value of the programmed threshold (Pick-up value)
1
t = K ×
0. 339 − 0 .236 /( I / Is)
Type of curve a b
LABORELEC 1 – 0.0897 4.0897
LABORELEC 2 – 0.0897 4.5897
LABORELEC 3 – 0.0897 5.0897
In order to be compliant with Laborelec specifications the relay should be used with:
− A rated current of 1A
The reset timer "t Reset" for MiCOM P122 & P123 can be found in the following menu :
− If the first phase (earth) threshold is selected with an IDMT IEC or RI curve, the reset
timer "t Reset" with DMT characteristic can be set under the menu :
− If the first phase (earth) threshold is selected with an IDMT IEEE or CO curve, the
reset timer "t Reset" with a DMTor IDMT characteristic can be set under the menu :
K
t = T ×
1 − (I I s )α
Where :
t = Reset time
K = Coefficient (see table)
I = Value of the measured current
IS = Value of the programmed threshold (pick-up value)
Incomer
I>/t> Block short time overcurrent
I>>/t>>
I>>>/t>>>
Trip
Back trip
Busbar
P0023ENa
P0024ENa
• P122 and P123 : The user can use all the thresholds for REF application. Note that
the results of the third threshold will be greater due to the fact that a sample base
algorithm is used.
• P120 and P121 : The user can use all the threshold for REF application. The results of
the third threshold will be similar to one of the first and second threshold (since all the
thresholds are based on Fast Fourier Transformation).
NOTE: For P122 and P123, the maximum internal fault level for the third
threshold (for the 0.002 to 1In range) must not exceed 20In.
6.1 Introduction
The restricted earth fault relay is a high impedance differential scheme which balances zero
sequence current flowing in the transformer neutral against zero sequence current flowing in
the transformer phase windings. Any unbalance for in-zone fault will result in an increasing
voltage on the CT secondary and thus will activate the REF protection.
This scheme is very sensitive and can then protect against low levels of fault current in
resistance grounded systems where the earthing impedance and the fault voltage limit the
fault current.
In addition, this scheme can be used in a solidly grounded system. It provides a more
sensitive protection, even though the overall differential scheme provides a protection for
faults over most of the windings.
The high impedance differential technique ensures that the impedance of the circuit is of
sufficiently high impedance such that the differential voltage that may occur under external
fault conditions is lower than the voltage required to drive setting current through the relay.
This ensures stability against external fault conditions and then the relay will operate only for
faults occurring inside the protected zone.
Application Guide P12x/EN AP/F75
Healthy CT Saturated CT
Protected
circuit
Zm Zm A-G
RCT1 RCT2
IF
R L1 R L3
VS R ST
R L2 R R L4
C
STAB
E/F Input
P0343ENa
Current setting should be selected for a high impedance element so that the primary current
reaches its nominal current with a given CT, according to the following equation:
Is < {(Iop / CTRatio) - n.Ie}
It is also possible to determine the maximum inrush current of the CT to reach a specific
primary operating current with a given relay setting.
The setting of the stabilising resistor must be calculated according to the above formula,
where the setting depends on the required stability voltage setting Vs and the relay setting Is
Vs k If (RCT+2RL)
=
Is IS
with
K= 1 for Vk/Vs less or equal to 16 and
K= 1.2 for Vk/Vs > 16.
Application Guide P12x/EN AP/F75
So
k If (RCT+2RL)
RST =
Ie>
with Vk ќ 4.Is.RST (A typical value to ensure the high speed operation for an internal fault).
6.3.1 CT requirements for High Impedance Restricted Earth Fault Protection
The High Impedance Restricted Earth Fault element shall remain stable for through faults
and operate in less than 40ms for internal faults provided that the following equations are
met in determining CT requirements and the value of the associated stabilising resistor:
Rs = [k* (If) * (RCT + 2RL)] / IS
VK ≥ 4 * Is * Rs
with
K= 1 for Vk/Vs less or equal to 16 and
K= 1.2 for Vk/Vs > 16.
6.4 Use of METROSIL non linear resistors
Metrosils are used to limit the peak voltage developed by the current transformers under
internal fault conditions, to a value below the insulation level of the current transformers,
relay and interconnecting leads, which are normally able to withstand 3KV peak.
The following formula should be used to estimate the peak transient voltage that could be
induced by an internal fault. This peak voltage depends on:
− CT ratio
Where
V = C.I0.25
Where
− Vs(rms) : RMS value of the sinusoidal voltage applied across the Metrosil.
This is due to the fact that the current waveform through the Metrosil is not sinusoidal but
appreciably distorted.
For satisfactory application of the non-linear resistor (Metrosil), its characteristics should
comply with the following requirements:
− At the relay voltage setting, the non-linear resistor (Metrosil) current should be as
low as possible, but no greater than approximately 30mA rms for 1A current
transformers and approximately 100mA rms for 5A current transformer.
− At the maximum secondary current, the non-linear resistor (Metrosil) should limit
the voltage to 1500V rms or 2120V peak for 0.25 second. At higher relay voltage
settings, it is not always possible to limit the fault voltage to 1500V rms, so higher
fault voltage may have to be tolerated.
The following tables show the typical types of Metrosil that will be required, depending on
relay current rating, REF voltage setting etc.
Application Guide P12x/EN AP/F75
− At the relay voltage setting, the Metrosil current should be less than 30mA rms.
− At the maximum secondary internal fault current, the Metrosil unit should limit the
voltage to 1500V rms if possible.
The Metrosil units normally recommended to be used with 1Amp CTs are shown in the
following table:
NOTE: Single pole Relay Metrosil Units are normally supplied without
mounting brackets unless otherwise specified by the customer.
6.4.2 Metrosil units for relays with 5A CT
These Metrosil units have been designed to comply with the following requirements:
− At the relay voltage setting, the Metrosil current should be less than 100mA rms (the
actual maximum currents passed by the units shown below their type description)
− At the maximum secondary internal fault current the Metrosil unit should limit the
voltage to 1500V rms for 0.25 second. At the higher relay settings, it is not possible to
limit the fault voltage to 1500V rms, hence higher voltage have to be tolerated
( indicated by * ,** , *** ).
The Metrosil units normally recommended for the used with 5 Amps CTs and single pole
relays are shown in the following table:
Amps rms Up to 200V rms 250V rms 275V rms 300V rms
600A/S1/S1213 600A/S1/S1214 600A/S1/S1214 600A/S1/S1223
50A C= 540/640 C= 670/800 C= 670/800 C= 740/870*
35mA rms 40mA rms 50mA rms 50mA rms
600A/S2/P/S1217 600A/S2/P/S1215 600A/S2/P/S1215 600A/S2/P/S1196
100A C= 470/540 C= 570/670 C= 570/670 C= 620/740*
35mA rms 75mA rms 100mA rms 100mA rms
600A/S3/P/S1219 600A/S3/P/S1220 600A/S3/P/S1221 600A/S3/P/S1222
150A C= 430/500 C= 520/620 C= 570/670** C= 620/740***
100mA rms 100mA rms 100mA rms 100mA rms
7. RECTIFIER PROTECTION
Rectifiers require a specific inverse time protection curve.
Protecting a rectifier is different from protecting conventional overcurrent applications. In fact,
a large number of rectifiers can withstand relatively long periods of overcharge without being
damaged. To give an idea, they can generally withstand 150 % of the load for 2 hours and
300 % for 1 minute.
A typical application is shown on the diagram below.
A +
B
C -
A B C N
Rs
Transformer Rectifier
Protection P0025ENa
10000
Protection curve
100 Instantaneous
Time (seconds)
overcurrent
10
Typical
1 load area
0.1
1 2 3 4 5 6 7 8
Multiple of rated current P0026ENa
The current threshold I> should be set to the rated rms value of the current that flows into the
transformer when the rectifier is delivering its rated load. The relay will give a start indication
when the current exceeds this setting but this is of no consequence because this function is
not used in this application. The rectifier curve should be an inverse time curve and should
cut-off currents below 1.6 times allowing the rectifier to carry 150% overload for long periods.
If this is not acceptable, the I> setting can be adjusted to move the cut-off point relative to
the current scale. The operation time can be modified by adjusting the time multiplier setting
(TMS) so that the time lies between limiting characteristic of the rectifier and the tolerated
load area.
Typical settings for the TMS area :
Light industrial service TMS = 0.025
Medium duty service TMS = 0.1
Heavy duty traction TMS = 0.8
The high set is typically set at 8 times the rated current as this ensures HV AC protection will
discriminate with faults covered by the LV protection. However, the high set could be set to 4
or 5 times the rated current if the AC protection is not trustworthy.
Use of the thermal element to provide protection between 70% and 160% of rated current
could enhance the protection. It is also common practice to provide restricted earth fault
protection for the transformer feeding the rectifier. Refer to the corresponding section dealing
with restricted earth fault protection.
P12x/EN AP/F75 Application Guide
Incomer
Feeder 1 Feeder n
P0027ENa
− 3rd threshold: tI>>> time delay at 60ms (active threshold for the high phase faults)
− 2nd threshold: tI>> time delay selectively greater than for the third threshold, i.e.
360ms.
The output contact associated with the 2nd threshold is wired in serie with the watchdog
contact of the downstream relays, so that it can activate the trip coil of the circuit breakers of
the feeders. Regarding the output contact associated with the 2nd and 3rd threshold, this
contact is directly wired to the trip coil of the incomer circuit breaker.
Busbar
Distance protection
Circuit Breaker
21
P 121
50/51
Feeder P0028ENa
Busbar
Circuit
Breaker
Circuit Breaker
CT
P121
50/51
CT
Circuit
Breaker
Busbar
Contactor
Feeder
P0029ENa
−t
e τ =
(I 2
− (k × I FLC )2 )
(I 2
− I 2p )
Where:
t = Time to trip, following application of the overload current, I
τ = Heating and cooling time constant of the protected plant equipment
I = Largest phase current
IFLC = Full load current rating (relay setting ‘Thermal Trip’)
k = 1.05 constant, allows continuous operation up to < 1.05 IFLC
IP = Steady state pre-loading current before application of the overload
The time to trip varies depending on the load current carried before application of the
overload, i.e. whether the overload was applied from “hot” or “cold”.
Curves of the thermal overload time characteristic are presented in the chapter
P12x/EN TD/C55 of the Technical Guide.
Application Guide P12x/EN AP/F75
K 2 − θ2
Ttrip = Te In 2
K − θtrip²
With :
Ttrip = Time to trip (in seconds)
Te = Thermal time constant of the protected element (in seconds)
Iθ > = Full load current rating given by the national standard or by the supplier.
k = Factor associated to the thermal state formula.
θ2 = Initial thermal state. If the initial thermal state = 30% then θ2 = 0.3
θtrip2 = Trip thermal state. If the trip thermal state is set at 100%,
then θ trip2 = 1
The settings of these parameters are available in the menus :
PROTECTION G1/ [49] Therm OL
PROTECTION G2/ [49] Therm OL
The calculation of the thermal state is given by the following formula :
2 −t
−t
I eq 1 − e Te + Θ e Te
Θ τ +1 =
τ
k × IΘ >
Thermal Trip (θtrip) = Permissible continuous loading of the plant equipment / CT ratio.
Typical time constant values are given in the following tables. The ‘Time Constant’
parameter is given in minutes.
Paper insulated lead sheathed cables or polyethylene insulated cables are placed above the
ground or in conduits. The table shows τ in minutes, for different cable rated voltages and
conductor cross-sectional areas:
An alarm can be raised when reaching a thermal state corresponding to a percentage of the
trip threshold. A typical setting might be ‘Thermal Trip’ = 70% of thermal capacity.
Application Guide P12x/EN AP/F75
The timer tCL in the CLP menu controls the time for which the relevant protections elements
in CLP menu (%) are altered following an external input signal (e.g. circuit breaker closure.
When the set tCL time has elapsed, all relevant settings revert back to their original values
or are unblocked.
tCL is initiated thanks to a dedicated logic input signal (refer to AUTOMAT. CTRL/INPUTS
menu), that is generated by connecting an auxiliary contact from the circuit breaker (52a or
52b) or starting device to the logic relevant inputs of the relay.
The following sections describe applications where the CLP logic may be useful and the
settings that need to be applied.
P12x/EN AP/F75 Application Guide
SOTF/TOR
tI >
tI >> >
tI >>>
I>> Trip
Enable SOTF/TOR of
I>> >
AR close &
MAN close > t
0 t
TC close > 0
500 ms
Settable delay time
from 0 to 500ms
I>>> in steps of 0.001 ms
Enable SOTF/TOR of
I>>>
AR close &
MAN close > t
0
TC close 500 ms
P0572ENa
When at least one of these 3 signals have been detected, a fixed timer starts and lasts
500ms.
Once this fixed timer has elapsed and I>> or I>>> thresholds have been crossed, the
configurable timer named “t Sotf” starts. This configurable timer is particularly useful in
applications where selectivity for fault occurring in stage two or three is requested.
P12x/EN AP/F75 Application Guide
This timer is also useful for cases where serious transient happen, where the three poles of
the CB do not close at the same time and in cases where the CB may not instantaneously
close.
This “t SOFT” can also be considered a trip delay time that substitutes the trip timer of the
threshold that has been crossed so that the time to trip is accelerated.
If a trip due to switch on to fault occurs during the reclaim time of the ARC, the trip will be
definitive and the ARC will be locked.
If the I>> and I>>> reset during the settable timer “t Sotf”, the SOTF/TOR function is reset.
The user can set the SOTF function under the AUTOMATIC CTRL/TRIP COMMAND
submenu and the AUTOMATIC CTRL/Output relays submenu.
Application Guide P12x/EN AP/F75
Local trip
3 4
Local close 5 6
RL 3
7 8
Control close
RL 2
AR close
RL TRIP
Protection trip
P0573ENb
To avoid any false trip, the change of setting group is only carried out when no protection
function is running (except the thermal overload function).
If a setting group change is received during any protection or automation function, it is stored
and executed after the last timer has elapsed.
The user can check which one of the active group is active looking under the OP
PARAMETERS menu.
The user can also assign the active group to an output relay. Using a normally open contact,
this means that:
Priority
When changing parameters through the front panel, the priority is given to the user that
takes local control of the relay when entering a password. Change of setting group done via
a remote command is not allowed for as long as the password is active (5mn).
Maintenance Mode
YES
When this menu is activated (set to YES), the Alarm led will start to flash and the alarm
message “MAINTENANCE MODE” will be displayed. In this case, all the output contacts are
blocked, and no command can be issued to these contacts, even if a protection threshold
associated to one of these output contacts has been crossed.
(If a protection threshold is crossed, all associated LEDs will be ON, even the TRIP LED, if
the threshold is associated to the RL1).
RELAYS 8765W4321
CMD 000000000
This window allows the user to verify the external wiring to the relay output contacts. To do
this, the user just has to assign a 1 to any of the output contacts, and this will close the
contact and the continuity of the wiring can be verified.
Application Guide P12x/EN AP/F75
P0024ENa
• In some applications, an earth fault relay may not be able to detect a residual current
because of the configuration of the network. For example, an earth fault relay
connected on the delta side of a delta-star transformer is unable to detect earth faults
on the star side. However, negative sequence current will be present on both sides of
the transformer in any fault condition, independently of the transformer configuration.
Therefore, negative phase sequence overcurrent element may be used to provide
time-delayed back-up protection for any uncleared asymmetrical faults.
• Where fuses are used to protect motors on rotating machines, a blown fuse produces
a large amount of negative sequence current. This is a dangerous condition for the
machine because negative phase sequence current generates overheating. Then, a
negative phase sequence overcurrent element may be used to back-up motor
protection relays.
It is essential to set correctly the time delay associated to this function. It should also be
noted that this element is used primarily as a back-up protection to other protective devices
or to provide an alarm. Therefore, this function is usually set with a long time delay.
Care must be made to ensure that the time delay is set above the operating time of any
other protection device (at minimum fault level) present on the system and that may react to
unbalanced faults, such as:
–EgZ0
I2F =
Z1Z2+Z1Z0+Z2Z0
Where :
Eg = System Voltage
Z0 = Zero sequence impedance
Z1 = Positive sequence impedance
Z2 = Negative sequence impedance
Therefore :
I2F Z0
=
I1F Z0+Z2
As a consequence, for an open circuit in a particular part of the system, I2/I1 can be
determined from the ratio between the zero sequence and the negative sequence
impedance. It must be noted however, that this ratio may vary depending on the location of
the fault. It is therefore desirable to apply a setting that is as sensitive as possible.
Practically, the levels of standing negative phase sequence current present on the system
guide the choice of this minimum setting. A system study, or the use of measurement data of
Application Guide P12x/EN AP/F75
the relay during commissioning stage are two ways to determine this minimum setting. If the
latter method is chosen, it is important to take measurements during maximum load
conditions, to be sure that all single phase loads are taken into account.
When sensitive settings are used, it is probable that the element will operate for any
unbalance condition occurring on the system (for example, during a single pole autoreclose
cycle). Therefore, a long time delay is necessary to ensure co-ordination with other
protective devices. It is common to set the time delay to 60 seconds.
The setting range of the Broken Conductor feature is described in the following table:
AUTOMAT. CTRL
Brkn Cond.? NO NO YES
tBC 1 1s 14 400 s 1s
RATIO I2/I1 20 % 20 % 100 % 1%
Set tBC at 60s to allow short circuits to be cleared by time delayed protections.
P12x/EN AP/F75 Application Guide
• Reduces operating costs. Indeed, less man hours are needed to repair damages
caused by the fault and it offers the possibility to have running substations unattended.
Thanks to the automatic autorecloser, instantaneous protection can be used, which
means shorter time to clear the fault and so helps to minimise damages and to reduce
the number of permanent faults.
As 80% of faults in overhead lines are transient, the use of the autorecloser is very
advantageous. Automatic autorecloser allow a substation to operate unattended. The
number of visits on site to manually reclose a circuit breaker after a fault can then be
substantially reduced. This feature constitutes therefore an important advantage for
substations supervised remotely.
The autorecloser is of great benefit function gives an important benefit on circuits using time
graded protection, in that it allows the use of instantaneous protection to give a high speed
first trip. With fast tripping, the duration of the power arc resulting from an overhead line fault
is reduced to a minimum, thus lessening the chance of damage to the line, which might
otherwise cause a transient fault to develop into a permanent fault.
Using short time delay protection also prevents blowing of fuses and reduces circuit breaker
maintenance by eliminating pre-arc heating when clearing transient faults.
Application Guide P12x/EN AP/F75
The next figure shows an example of 4 autoreclose cycles (maximum numbers of allowed
cycles) to the final trip:
tD1, tD2, tD3, tD4 = dead time 1, 2, 3 and 4 timers
tR = Reclaim time
O = CB open
C = CB closed
Current
O C O C O C O C O final trip
I threshold
Time
Fault P0031ENa
• The auxiliary contact of the CB status 52a must be connected to the relay.
Refer to the AUTOMAT. CTRL/Inputs menu
• The trip output relay RL1 must not be latched to the earth and/or phase protection
function.
Refer to the AUTOMAT. CTRL/Latch functions menu
NOTE : If the auxiliary supply is lost during an autoreclose cycle, the
autoreclose function is totally disabled.
21.2.2 Autoreclose menu
The setting of the Autoreclose function is described in the following table:
The same settings apply for the Menu PROTECTION G2.
Example of setting :
CYCLES 4321
tI> 1201
4321 are the cycles associated to the trip on tI> pick up
1201 are the actions to be executed after the tI> time delay has elapsed :
0= no action on autorecloser : definitive trip
1= trip on tI> pick up, followed by a reclosing cycle
2= no trip on tI> pick up : and this whatever the setting is in the AUTOMAT.
CRTL/Trip commands/Trip tI> menu.
In addition to these settings, the user will be able to fully link the autoreclose function to the
protection function using the menus PROTECTION G1/Phase OC and
PROTECTION/E/Gnd. Refer to Chapter 3 of the Technical Guide.
21.2.3 Logic Functions
21.2.3.1 Logic Inputs
The autoreclose function has four inputs that can be assigned to the autoreclose logic.
These inputs can be opto-isolated inputs configured for that under the AUTOMAT. CTRL
menu. External contacts can then be wired to be used as an input and influence the
autorecloser scheme. These 4 inputs are described hereafter.
21.2.3.2 External CB fail
Most of circuit breakers are only able to provide only one trip-close-trip cycle. As a
consequence, it is necessary to verify if there is enough power to reclose the CB. The state
of the CB (healthy or failed) can be checked using an input that has been assigned to the
“CB FLT” function. If on completion of the dead time, the CB FLT input indicates that there is
not enough energy availableduring the time tCFE, a lockout occur and the CB remains open.
This function is disabled if not assigned under the PROTECTION G1/Autoreclose menu
(function CB FLT set to NO).
21.2.3.3 External starting orders
Two independent and programmable inputs (AUTOMAT.CTRL/INPUTS menu) can be used
to initiate the autorecloser function from an external device (such as an existing overcurrent
relay). These logic inputs may be used independently and also in parallel with the MiCOM
P123 Overcurrent settings.
These external orders can be independently disabled by not assigning the functions in the
PROTECTION G1/Autoreclose/CYCLES tAux1 and PROTECTION
G1/Autoreclose/CYCLES tAux2 menus.
21.2.3.4 External blocking order
The Block –79 input can be set under the AUTOMAT.CTRL/INPUTS menu. This input can
block the autoreclose function and cause a lock-out if the autorecloser function is in
progress. It can be used when a protection is needed without requiring the use of the
autorecloser function.
A typical example is on a transformer feeder, where the autoreclose may be initiated from
the feeder protection but need to be blocked from the transformer protection side.
These external orders can be disabled by not assigning the function in the
PROTECTION/Autoreclose/Ext Block menu.
21.2.3.5 Autoreclose Logic Outputs
The following output signals can be assigned to relay outputs or to LEDs to provide
information about the status of the auto Reclose cycle. These outputs are described
hereafter.
P12x/EN AP/F75 Application Guide
The "Final trip" signal can be assigned to the output relays under the menu
AUTOMAT.Ctrl/Output Relays/79 Trip.
The "Final trip" signal can be assigned to a LED under the menu
CONFIGURATION/Led/Recloser Blocked.
21.2.4 Autoreclose logic description
The autoreclose function provides the ability to automatically control the autorecloser. This
function can perform two, three or four shot cycle. The parameters Phase Cycles numbers
and E/Gnd Cycles numbers are used to enter the number of shots chosen. Dead times for
all the shots (reclose attempts) can be independently adjusted.
The number of shots is directly related to the type of faults likely to occur on the system and
the voltage level of the system. Generally, on medium voltage networks where the
percentage of transient and non-permanent faults is likely to be high, a multi-shot
autoreclose device will increase the possibility for the distribution line to be successfully re-
energised after the reclosure of the circuit breaker.
The crossing of a protection element (phase or earth) will trigger the autoreclose provided
circuit breaker was closed before that. The dead time (Dead Time tD1, Dead Time tD2,
Dead Time tD3, Dead Time tD4) starts when the CB has tripped (when the 52a input has
disappeared).
At the end of the relevant dead time, a CB close signal is sent, provided that certain system
conditions are met. For example, the spring that allows the circuit breaker to close should be
fully charged. The CB FLT input provides this information . The CB close signal dropped off
as soon as the circuit breaker closes.
The reclaim time (Reclaim Time) starts when the CB has closed.
If the circuit breaker does not trip again, the autoreclose function resets at the end of the
reclaim time.
If the protection operates during the reclaim time, the relay either advances to the next shot
that is programmed in the autoreclose cycle, or, if all the programmed reclose attempts have
been accomplished, it locks out.
The total number of reclosures is displayed under the MEASUREMENT menu. This value can
be reset to zero pressing the key "C" (Clear) in the MEASUREMENTS/Reclose Stats menu.
21.2.5 Autoreclose Inhibit Following Manual Close
The “Inhib Time tI” timer can be used to block the autoreclose being initiated after the CB is
manually closed onto a fault. The Autoreclose is blocked during the “Inhib Time tI“ following
manual CB Closure.
Application Guide P12x/EN AP/F75
The Autoreclose can also be locked out using a CB FLT input. The external information can
be generated by the spring of the CB is not charged or suffers a low gas.This CB FLT
information can be issued from the "not charged" or "Low gas pressure" indications of CB
springs.
Note that Autoreclose can also be locked by :
• The fact that the CB doesn’t open after tBf delay (CB Fail)
21.3.2.1 Load
Due to the great diversity of load which may exist on a system, it may be very difficult to
optimise the dead time. However, it is possible to study each type of load separately and
thereby be able to define a typical dead time. Hereafter are presented the most common
types of loads.
Synchronous motors tolerate only extremely short interruptions of supply without loss of
synchronism. In practice, it is desirable to disconnect the motor from the supply in the event
of a fault; the dead time should be sufficient to allow the motor no-volt device to operate.
Typically, a minimum dead time of 0.2-0.3 seconds is recommended to allow this device to
operate.
Induction motors, on the other hand, can withstand supply interruptions, up to a maximum of
0.5 seconds and re-accelerate successfully. In general dead times of 3-10 seconds are
normally satisfactory, but there may be special cases for which additional time is required to
allow the reset of manual controls and safety devices.
Loss of supply of lighting circuits, such as street lighting, can lead to important safety
problems. A 10 seconds loss of supply may be dangerous for car circulation. Regarding
domestic customers, the main consideration is linked to the inconvenience caused.
An important criteria for many power utilities is the number of minutes lost per year to
customers which will be reduced on feeders using the autorecloser and will also be affected
by the dead time settings used.
21.3.2.2 Circuit Breaker
For high speed autoreclose, the minimum dead time of the power system depends on the
minimum time delay imposed by the circuit breaker during a trip and reclose operation.
Since a circuit breaker is a mechanical device, it has an inherent contact separation time.
This operating time for a modern circuit breaker is usually within the 50-100ms range, but
could be longer with older designs.
After a trip, the mechanism need some time to reset before applying a close pulse. This
reset time varies depending on the circuit breaker, but lasts typically 0.1 seconds.
Once the circuit breaker has reset, the breaker can start to close. The period of time
between the energisation of the closing mechanism and the making of the contacts is called
closing time. Because of the time constant of a solenoid closing mechanism and the inertia
of the plunger, a solenoid closing mechanism may take 0.3s. A spring operated breaker, on
the other hand, can close in less than 0.2 seconds.
Where high speed reclosing is required, for the majority of medium voltage applications, the
circuit breaker mechanism dictates itself the minimum dead time. However, the fault de-
ionising time may also have to be considered.
High speed autoreclose may be required to maintain stability on a network that has two or
more power sources. For high speed autoreclose, the system disturbance time should be
minimised using fast protection, <50 ms, such as distance or feeder differential protection
and fast circuit breakers < 100 ms. Fast fault clearance can reduce the time for the fault arc
to de-ionise.
To ensure stability between two sources, a dead time of <300 ms is typically required.
Considering only the CB, this minimum time corresponds to the reset time of the the
mechanism plus the CB closing time. Thus, a solenoid mechanism is not adapted for high
speed autoreclose due to the fact that the closing time is generally too long.
Application Guide P12x/EN AP/F75
• Supply continuity - Large reclaim times can result in unnecessary lockout for transient
faults.
• Fault incidence/Past experience - Small reclaim times may be required where there is
a high incidence of lightning strikes to prevent unnecessary lockout for transient faults.
• Charging time of the spring - For high speed autoreclose, the reclaim time may be set
longer than the spring charging time to ensure that there is sufficient energy in the
circuit breaker to perform a trip-close-trip cycle. For delayed autoreclose, this setting is
of no need as the dead time can be extended by an extra CB healthy check window
time if there is insufficient energy in the CB. If there is insufficient energy after the
check window time the relay will lockout.
• Switchgear Maintenance - Excessive operation resulting from short reclaim times can
mean shorter maintenance periods. A minimum reclaim time of 5s may be needed to
give sufficient time to the CB to recover after a trip and close before it can perform
another trip-close-trip cycle.
The reclaim time must be long enough to allow any time delayed protection leading to
autoreclose to operate. Failure to do so can cause the autoreclose scheme to reset too soon
and the reactivation of the instantaneous protection.
If that were the case, a permanent fault would look like some transient faults, caused by
continuous autorecloses. Applying a protection against excessive fault frequency lockout is
an additional precaution that can solve this problem.
It is possible to obtain short reclaim times by blocking the reclaim time from the protection
start signals. If short reclaim times are to be used, then the switchgear rating may dictate the
minimum reclaim time. The advantage of a short reclaim time is that there are less lockouts
of the CB, and therefore the number of maintenance visits periods would be reduced.
P12x/EN AP/F75 Application Guide
Sensitive earth fault protection is used to detect high resistance earth faults. The time delay
of such protections is usually a long time delay, typically about 10-15s. If autoreclose is
generated by the SEF protection, this timer must be taken into account when deciding the
value of the reclaim time, if the reclaim time is not blocked by an SEF protection start signal.
Sensitive earth faults, caused by a broken overhead conductor in contact with dry ground or
a wood fence are rarely transient faults and may be dangerous to people.
It is therefore common practice to block the autoreclose using the sensitive earth fault
protection and lockout the circuit breaker.
Where motor-wound spring closed circuit breakers are used, the reclaim time must be at
least as long as the spring winding time for high speed autoreclose to ensure that the
breaker can perform a trip-close-trip cycle.
A typical 11/33kV reclaim time is 3-10 seconds, this prevents unnecessary lockout during
thunderstorms. However, times up to 60-180 seconds maybe used.
Application Guide P12x/EN AP/F75
MENU TEXT
CB Monitoring
CB Opening Time Display the CB opening time (Note 1)
CB Closing Time Display the CB closing time (Note 2)
CB Operations Display the number of opening commands executed by the CB
ΣAmps(n) IA Display the summation of the Amps (or square Amps)
interrupted by the CB phase A
Σ Amps(n) IB Display the summation of the Amps (or square Amps)
interrupted by the CB phase B
Σ Amps(n) IC Display the summation of the Amps (or square Amps)
interrupted by the CB phase C
NOTE 1: the CB opening time is measured between the trip command (Trip
output relay) and the change of position of O/O (52a).
NOTE 2: the CB closing time is measured between the closing command
(output auxiliary relay) and the change of position of O/O (52a).
The above counters in the CB condition monitoring function may be reset to zero, for
example, following a maintenance inspection and overhaul.The following table, detailing the
options available for the CB condition monitoring, is taken from the relay menu. It includes
the setup of the current broken facility and those features which can be set to raise an alarm
or CB lockout.
Application Guide P12x/EN AP/F75
SETTING RANGE
MENU TEXT STEP SIZE
MIN MAX
CB Supervision
CB Open S’vision No Yes
CB Open Time 50 ms 1 000 ms 50 ms
CB Close S’vision No Yes
CB Close Time 50 ms 1 000 ms 50 ms
CB Open Alarm ? No Yes
CB Open NB 0 50 000 1
ΣAmps (n) ? No Yes
ΣAmps (n) 0 4 000 E6 1 E6
n 1 2 1
t Open Pulse 100 ms 5 000 ms 100 ms
t Close Pulse 100 ms 5 000 ms 100 ms
The circuit breaker condition monitoring counters will be updated every time the relay issues
a trip command. In cases where the breaker is tripped by an external protection device it is
also possible to update the CB condition monitoring. This is achieved by allocating one of the
logic inputs or via the communication to accept a trigger from an external device.
23.2 Setting guidelines
The Σ In counter monitors the cumulative severity of the duty placed on the interrupter
allowing a more accurate assessment of the circuit breaker condition to be made.
For OCB’s, the dielectric withstand of the oil generally decreases as a function of Σ I2t. This
is where ‘I’ is the fault current broken, and ‘t’ is the arcing time within the interrupter tank (not
the interrupting time). As the arcing time cannot be determined accurately, the relay would
normally be set to monitor the sum of the broken current squared, by setting n = 2.
For other types of circuit breaker, especially those operating on higher voltage systems,
practical evidence suggests that the value of n = 2 may be inappropriate. In such
applications n’ may be set to 1.
An alarm in this instance may be indicative of the need for gas/vacuum interrupter HV
pressure testing, for example.
It is imperative that any maintenance programme must be fully compliant with the switchgear
manufacturer’s instructions.
P12x/EN AP/F75 Application Guide
Alarm
indication
Ia under
I< threshold
Ib under tI< 0
I< threshold >=1
& Output
Ic under Relays
I< threshold Digital
Input 52a P0032ENa
− at least one of the 3 phase current is detected under the threshold I<
25. CIRCUIT BREAKER FAILURE PROTECTION : CBF (P122 & P123 ONLY)
When a fault is detected, one or more main protection elements will issue a trip order to the
associated circuit breaker(s). To isolate the fault, and prevent (heavier) damage on the
power system it is essential that the circuit breaker operates correctly.
On power systems, a fault that is not clear quickly enough threatens the stability of the
system. It is therefore common practice to install circuit breaker failure protection, which
monitors that the circuit breaker has opened within a reasonable period of time. If the fault
current has not been eliminated after the set time delay, the breaker failure protection (CBF)
will send a signal.
The CBF protection can be used to back-trip upstream circuit breakers to ensure that the
fault is correctly isolated. The CBF protection can also eliminate all blocking orders
associated to logic selectivity.
CB Fail Enabled
Any Trip
tBF CB Fail Alarm
1 S
Q
External CBF R
Initiate
CBF Ia<
CBF Ib<
CBF Ic<
P0428ENa
• If there is no current signal going out in opposite way compared to the first one, the
relay considers that there is an opened CB pole condition. The « CB pole open »
internal signal is initiated.
Application Guide P12x/EN AP/F75
• If there is a current signal going out in opposite way compared to the first one, the
relay considers that the pole of the CB is not yet open. The « CB pole closed » internal
signal is maintained.
Once the t BF time delay has elapsed, the relay checks the internal state of each pole of the
circuit breaker. If one or several internal poles are not opened, the relay then declares that
the CB has failed. The “CB FAIL” message is displayed.
Note that it is possible to initiate the CB fail detection function by a digital input without
having any trip order being given by the relay. In this case, the tBF timer starts its countdown
when receiving this digital input signal. If the CB is not opened (by an another protection
relay) once the tBF has elapsed, the relay declares that the CB has failed.
The user can associate the digital input to the "CB Fail detection" under the AUTOMAT.
CTRL/Inputs menu.
Figure 17 hereafter shows the start of the CB Fail detection after a trip order was sent:
Trip order
t BF timer
20 samples 20 samples 20 samples 20 samples 20 samples 20 samples
I< threshold
I< threshold
CB pole opened
detection
« CB pole closed » internal signal
Trip order
t BF timer
20 samples 20 samples 20 samples
I< threshold
I< threshold
P0034ENa
20 samples 20 samples 20 samples 20 samples
Figure 19 hereafter shows a CB failure condition. After the t BF timer elapses, the relay
doesn’t detect the opening of the CB pole. Therefore, a CB FAIL signal is given.
CB failed
« CB FAIL » signal
Trip order
t BF timer
20 samples 20 samples 20 samples 20 samples 20 samples
I< threshold
I< threshold
« CB pole opened »
detection
« CB pole closed» internal signal
Trip order
t BF timer
20 samples 20 samples 20 samples 20 samples
I< threshold
I< threshold
SETTING RANGE
MENU TEXT STEP SIZE
MIN MAX
CB Fail ? No Yes
tBF 0.03 s 10 s 10 ms
I< 0.02 In In 0.01 In
SETTING RANGE
MENU TEXT STEP SIZE
MIN MAX
TC Supervision ? Yes No
tSUP 100ms 10s 50ms
+Vdc
52a
2 6 Trip
order Opto-
input
MiCOM P123
- Vdc
P0038ENa
+Vdc
2 6
Trip
order Opto-
input
MiCOM P123
52a 52b
- Vdc
P0039ENa
Example 3
In this example both 52a and 52b auxiliary contacts are available, the MiCOM P122 and
P123 relays monitor the complete trip circuit whatever the CB status (CB open or CB
closed).
In this case it is necessary to insert a R1, if either the output (RL1) trip is latched, or it stays
involuntarily closed, or a long time trip pulse is programmed.
+Vdc
2 6
Trip
order Opto-
input
MiCOM P123
52a 52b
Resistor R1
Trip Coil
- Vdc
P0040ENa
FIGURE 24 : TRIP COIL AND AUXILIARY CONTACTS MONITORING WHATEVER THE POSITION OF
THE CB
EXTERNAL RESISTOR R1 CALCULATION
The calculation of the R1 resistor value will take into account that a minimum current is
flowing through the logic input. This minimum current value is a function of the relay auxiliary
voltage range (Ua).
1 - Case of example No 2 :
The R1 resistor maximum value (in Ohm) is defined by the following formula:
0,8 × U a − U min
R1 < [Ohm]
I min
Where:
Ua = auxiliary voltage value (in this case a DC voltage; range is given on label under the
top hinged cover. See table below).
Umin = internal minimum voltage value needed for the opto logic input to operate.
Imin = minimum current value needed for the opto logic input to operate.
PR1 > 2 ×
(1,2 × U a ) 2 [W]
R1
Application Guide P12x/EN AP/F75
2 - Case of example No 3 :
The R1 resistor maximum value (in Ohm) is defined by the following formula:
0,8 × U a − U min
R1 < − R Coil [Ohm ]
I min
Where:
Ua = auxiliary voltage value (in this case a DC voltage; range is given on label under
the top hinged cover. See table below).
Umin = internal minimum voltage value needed for the opto logic input to operate.
Imin = minimum current value needed for the opto logic input to operate.
Rcoil = Trip coil resistance value.
PR1 > 2 ×
(1,2 × U a ) 2 [W]
(R1 + R Coil )
NOTES: – The presence of auxiliary relays, such as an anti-pumping system
for instance, in the trip circuit must be taken into account for the R1
resistance values specification.
– We consider that the maximum variations of the auxiliary voltage
value is ±20%.
P12x/EN AP/F75 Application Guide
SETTING RANGE
MENU TEXT STEP SIZE
MIN MAX
Disturb Record
Pre-Time 100 ms 3000 ms 100 ms
Post-Time 100 ms 3000 ms 100 ms
Disturb Rec Trig On Instantaneous On Trip
The total disturbance recording time is 3.0 s (pre-trigger plus post-trigger). For example,
default settings show that if the pre-time time is set to 100 ms and the post -time to 2.5 s,
than the total disturbance recording time will be 2.6 s.
P12x/EN AP/F75 Application Guide
31. ROLLING AND PEAK VALUE DEMANDS (P122 & P123 ONLY)
MiCOM P122 and P123 relays can store the 3 phases rolling average and maximum
subperiod values. The description and principle of calculation are presented hereafter.
31.1 Rolling demand
Calculation of the rolling demand value for IA, Ib and IC currents is done the following way:
• Calculation of the average of the RMS values on a "Rolling Sub Period" period.
The width of the period "Rolling Sub Period" can be set under the "RECORDS/Rolling
Demand/Sub Period" menu.
Setting range : from 1 to 60 minutes.
• Display of the first result under the MEASUREMENTS menu only after the storage of
"Num of Sub Periods" periods. The 3 phases Rolling average value are displayed :
Rolling Average IA RMS
Rolling Average IB RMS
Rolling Average IC RMS
The calculation is reset either via the front operator interface (Key c) without entering a
password, or by a remote command.
NOTE : In case of loss of power supply the rolling demand are not stored.
A modification of the settings (either "Rolling Sub Period" or "Num of
Sub Periods" parameter) reset the calculation.
Example :
Sub Period = 5 mn
Num of Sub Period = 2
32. CT REQUIREMENTS
Hereafter are presented the CT requirements for MiCOM P12x Overcurrent. Current
transformer requirements are based on a potential maximum fault current that is 50 times
the relay rated current (In) and on the setting of the instantaneous at 25 times rated current
(In). The current transformer requirements are designed to provide operation of all protection
elements.
When the criteria for a specific application are higher than the criteria described above, or
when the actual lead resistance exceeds the limiting value recommended, it may be
desirable to increase the CT requirements according to the following formula.
VK ≥ 48 * In * (RCT + 2RL) for X/R < 40, 15In < If < 40In
and 40 <X/R < 120, If < 15In
Where :
VK = Required CT knee point voltage (volts),
In = Rated secondary current (amps),
RCT = Resistance of current transformer secondary winding (ohms)
RL = Resistance of a single lead from relay to current transformer (ohms),
If = Maximum through fault current level (amps).
32.5 High Impedance Restricted Earth Fault Protection
The High Impedance Restricted Earth Fault element shall remain stable for through faults
and shall operate in less than 40ms for internal faults provided that following equations are
met when determining CT requirements and the value of the associated stabilising resistor:
Rs = [K * (If) * (RCT + 2RL)] / IS
VK ≥ 4 * Is * Rs
K = 1 for Vk/Vs less or equal to 16
K = 1.2 for Vk/Vs greater than 16
Where :
VK = Required CT knee-point voltage (volts),
Rs = Value of Stabilising resistor (ohms),
If = Maximum through fault current level (amps).
VK = CT knee point voltage (volts),
IS = Current setting of REF element (amps),
RCT = Resistance of current transformer secondary winding (ohms),
RL = Resistance of a single lead from relay to current transformer (ohms).
P12x/EN AP/F75 Application Guide
BLANK PAGE
Communications P12x/EN CT/F75
MiCOM P120/P121/P122/P123
MODBUS DATABASE
COURIER DATABASE
IEC 60870-5-103
DNP 3.0 DATABASE
MiCOM P120 - P121 - P122 - P123
VERSION V6.G
Communications P12x/EN CT/F75
MiCOM P120/P121/P122/P123
MODBUS DATABASE
MiCOM P120 - P121 - P122 - P123
VERSION V6
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 1/170
CONTENT
1. INTRODUCTION 3
1.1 Purpose of this document 3
1.2 Glossary 3
2. MODBUS PROTOCOL 4
2.1 Technical characteristics of the MODBUS connection 4
2.1.1 Parameters of the MODBUS connection 4
2.1.2 Synchronisation of exchanges messages 4
2.1.3 Message validity check 4
2.1.4 Address of the MiCOM relays 4
2.2 MODBUS functions of the MiCOM relays 5
2.3 Presentation of the MODBUS protocol 5
2.3.1 Format of frames sent by the MiCOM relays 5
2.3.2 Messages validity check 6
1. INTRODUCTION
1.1 Purpose of this document
This document describes the characteristics of the MODBUS, K-Bus/COURIER and IEC
60870-5-103 communication protocol of MiCOM P120, P121, P122 and P123 relays.
1.2 Glossary
Ir, Is, It : currents measured on the concerned phases (r, s, t)
IE : residual current measured by earth input (= 3.I zero sequence)
pf : soft weight of a word of 16 bits
PF : heavy weight of a word of 16 bits
P12x/EN CT/F75 Communications
Modbus Database
Page 4/170 MiCOM P120/P121/P122/P123
2. MODBUS PROTOCOL
MiCOM P120, P121, P122 and P123 relays can communicate by a RS 485 link behind the
unit following the MODBUS RTU protocol.
2.1 Technical characteristics of the MODBUS connection
2.1.1 Parameters of the MODBUS connection
The different parameters of the MODBUS connection are as follows:
Baud rate
300
600
1200
2400
4800
9600
19200
38400
Mode
1 start / 8 bits / 1 stop: total 10 bits
1 start / 8 bits / even parity / 1 stop: total 11 bits
1 start / 8 bits / odd parity / 1 stop: total 11 bits
1 start / 8 bits / 2 stop: total 11 bits
Slave number:
The slave number is situated between 1 and 255.
A frame transmitted with a slave number 0 is globally addressed to all pieces of equipment
(broadcast frame )
Function code:
Requested MODBUS function (1 to 16)
Information:
Contains the parameters of the selected function.
CRC16:
Value of the CRC16 calculated by the master.
NOTE: The MiCOM relay does not respond to globally broadcast frames sent
out by the master.
2.3.1 Format of frames sent by the MiCOM relays
Frame sent by the MiCOM relay ( response)
Slave number:
The slave number is situated between 1 and 255.
P12x/EN CT/F75 Communications
Modbus Database
Page 6/170 MiCOM P120/P121/P122/P123
Function code:
Processed MODBUS function (1 to 16) .
Data:
Contains reply data to master query .
CRC 16:
Value of the CRC 16 calculated by the slave.
2.3.2 Messages validity check
When MiCOM P120, P121, P122 and P123 relays receive a master query, it validates the
frame:
If the CRC is false, the frame is invalid. MiCOM P120, P121, P122 and P123 relays do not
reply to the query. The master must retransmit its query. Excepting a broadcast message,
this is the only case of non-reply by MiCOM P120, P121, P122 and P123 relays to a master
query.
If the CRC is good but the MiCOM relay can not process the query, it sends an exception
response.
Warning frame sent by the MiCOM relay (response)
Slave number:
The slave number is situated between 1 and 255.
Function code:
The function code returned by the MiCOM relay in the warning frame is the code in which the
most significant bit (b7) is forced to 1.
Warning code:
On the 8 warning codes of the MODBUS protocol, the MiCOM relay manages two of them:
Values Fault
Address Group Description Step Unit Format Range
range Value
0000 Product Relay description 32-127 1 - F10 P120 to P123
Information characters 1 and 2
0001 Relay description 32-127 1 - F10 P1 P120 to P123
characters 3 and 4
0002 Relay description 32-127 1 - F10 23 P120 to P123
characters 5 and 6
0003 Unit reference 32-127 1 - F10 AL P120 to P123
characters 1 and 2
0004 Unit reference 32-127 1 - F10 ST P120 to P123
characters 3 and 4
0005 Software version 10-xx 1 - F21 P120 to P123
0006 Front communication 0-3 1 - F41 P122-P123
0007 Internal phase ratio - F1 P122-P123
0008 Internal earth ratio - F1 P122-P123
0009 General start info. 0-1 1 - F1 P120 to P123
000A to Reserved P120 to P123
000C
000D Real Active Setting 1-2 F1 P122-P123
Group (after taking into
account the protection
flags)
000E Password active* - F24 0 P120 to P123
000F Relay status - F45 P120 to P123
0010 Remote Logical inputs 0 to 7 or 1 - F12 P120 to P123
signalling to 31
0011 Logical data 0 to 2n - F20 P120 to P123
FFFF
0012 Internal Logic 0 to 2n - F22 P120 to P123
FFFF
0013 Output contacts 0 to 127 1 - F13 P120 to P123
or to 511
0014 Output information: I> 0 to 1 - F17 P121-P122-
FFFF P123
0015 Output information: 0 to 1 - F17 P121-P122-
I>> FFFF P123
0016 Output information: 0 to 1 - F17 P121-P122-
I>>> FFFF P123
0017 Output information: IE> 0 to 1 - F16 P120 to P123
FFFF
0018 Output information: 0 to 1 - F16 P120 to P123
IE>> FFFF
0019 Output information: 0 to 1 - F16 P120 to P123
IE>>> FFFF
Values Fault
Address Group Description Step Unit Format Range
range Value
001A I> memorisation 0 to 1 - F17 P121-P122-
FFFF P123
001B I>> memorisation 0 to 1 - F17 P121-P122-
FFFF P123
001C I>>> memorisation 0 to 1 - F17 P121-P122-
FFFF P123
001D tI> memorisation 0 to 1 - F17 P121-P122-
FFFF P123
001E tI>> memorisation 0 to 1 - F17 P121-P122-
FFFF P123
001F tI>>> memorisation 0 to 1 - F17 P121-P122-
FFFF P123
0020 Thermal state 0 to 1 1 - F37 P122-P123
information
0021 Output information: I< 0 to 1 - F17 P122-P123
FFFF
0022 Output information: 0 to 1 - F16 P122-P123
I2> FFFF
0023 Output information: 0 to 1 - F38 P122-P123
broken conductor FFFF
/ CB failure
/ CB alarm
0024 tI< memorisation 0 to 1 - F17 P122-P123
FFFF
0025 Memorised flag for non - F36 P122-P123
acknowledged alarms
0026 Number of disturbance 0 to 5 1 - F31 P122-P123
records available
0027 Tripping output (RL1) 0 to 1 1 - F1 P122-P123
status
0028 CB supervision flag - F43 P122-P123
0029 memorised flag 2 for - F44 P122-P123
non acknowledged
alarms
002A Reserved Logical 0 to 2n - F20 P120 to P123
data FFFF bis
002B Threshold information: 0 to 1 - F16 P122-P123
Iinv>> FFFF
002C to Reserved P120 to P123
002F
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 11/170
Values Fault
Address Group Description Step Unit Format Range
range Value
0030 Remote Phase A current RMS 0 to 1 A/100 F18 P121-
measurements value 600 000 P122-P123
0032 Phase B current RMS 0 to 1 A/100 F18 P121-
value 600 000 P122-P123
0034 Phase C current RMS 0 to 1 A/100 F18 P121-
value 600 000 P122-P123
0036 Earth current RMS 0 to 1 A/100 F18 P120 to
value 120 000 P123
0038 to Reserved P120 to
0039 P123
003A Thermal state (saved) % F1 P122-P123
003B Frequency 4500 to 1 1/100 F1 P120 to
6500 Hz P123
003C Max RMS value phase 0 to 600 1 A/100 F18 P122-P123
A 000
003E Max RMS value phase 0 to 600 1 A/100 F18 P122-P123
B 000
0040 Max RMS value phase 0 to 600 1 A/100 F18 P122-P123
C 000
0042 Average RMS value 0 to 600 1 A/100 F18 P122-P123
Phase A 000
0044 Average RMS value 0 to 600 1 A/100 F18 P122-P123
Phase B 000
0046 Average RMS value 0 to 600 1 A/100 F18 P122-P123
Phase C 000
0048 Harmonic IO* 0 to 600 1 A/100 F18 P122-P123
000
004A Inverse Current 1 A/100 F18 P122-P123
(fundamental)
004C Direct current 1 A/100 F18 P122-P123
004E I2/I1 ratio % F1 P122-P123
004F Reserved P120 to
P123
0050 Fourier Module IA - F1 P121-
Module P122-P123
0051 Module IB - F1 P121-
P122-P123
0052 Module IC - F1 P121-
P122-P123
0053 Module IE - F1 P120 to
P123
Values Fault
Address Group Description Step Unit Format Range
range Value
0054 Fourier Argument IA - F1 P121-P122-
Argument P123
0055 Argument IB - F1 P121-P122-
P123
0056 Argument IC - F1 P121-P122-
P123
0057 Argument IO - F1 P120 to
P123
0058 Module I2** - F1 P122-P123
0059 Module I1** - F1 P122-P123
005A Recloser Cycle total number - F1 P123
statistics
005B Cycle 1 number - F1 P123
005C Cycle 2 number - F1 P123
005D Cycle 3 number - F1 P123
005E Cycle 4 number - F1 P123
005F Definitive tripping - F1 P123
number
0060 Closing order number - F1 P123
0061 Rolling Average sliding time 0 to 600 1 A/100 F18 P122-P123
Demand window- RMS IA 000
0063 Average sliding time 0 to 600 1 A/100 F18 P122-P123
window- RMS IB 000
0065 Average sliding time 0 to 600 1 A/100 F18 P122-P123
window- RMS IC 000
0067 Maximum of the sub 0 to 600 1 A/100 F18 P122-P123
period average value 000
RMS phase A
0069 Maximum of the sub 0 to 600 1 A/100 F18 P122-P123
period average value 000
RMS phase B
006B Maximum of the sub 0 to 600 1 A/100 F18 P122-P123
period average value 000
RMS phase C
006D to Reserved P122-P123
006F
0070 Output information: 0 to 1 - F54 P123
SOTF FFFF
3.3 Page 1h
Read and write access
Values Fault
Address Group Description Step Unit Format Range
range Value
0100 Remote Address 1 to 255 1 - F1 1 P120 to
parameters P123
0101 Reserved P120 to
P123
0102 Password characters 1 32 -127 1 - F10 AA P120 to
and 2 P123
0103 Password characters 3 32 -127 1 - F10 AA P120 to
and 4 P123
0104 Frequency 50-60 10 Hz F1 50 P120 to
P123
0105 Phase A label ** L1-A-R VTA - F25 A P121-
P122-P123
0106 Phase B label ** L2-B-S VTA - F25 B P121-
P122-P123
0107 Phase C label ** L3-C-T VTA - F25 C P121-
P122-P123
0108 Earth label *** N-G-E VTA - F25 N P120 to
P123
0109 Fault display *** 1-4 1 - F26 1 P120 to
P123
010A User reference 32-127 1 F10 AL P120 to
(characters 1 and 2) P123
010B User reference 32-127 1 F10 ST P120 to
(characters 3 and 4) P123
010C Fault number to be 1-5 1 F31 5 P122-P123
displayed
010D Configuration of EDGE 0 F12 0 P122-P123
validation of logic inputs
010E Instantaneous fault 1-5 1 F31 5 P122-P123
number to be displayed
010F Voltage Type applied to 0-1 1 F50 0 P122-P123
the logic inputs
0110 CB monitoring Operation number 1 - F1 P122-P123
measurements
0111 CB Operating time 1 1/100 F1 P122-P123
sec
0112 Switched square Amps An F18 P122-P123
phase A sum
0114 Switched square Amps An F18 P122-P123
phase B sum
0116 Switched square Amps An F18 P122-P123
phase C sum
P12x/EN CT/F75 Communications
Modbus Database
Page 14/170 MiCOM P120/P121/P122/P123
Values Fault
Address Group Description Step Unit Format Range
range Value
0118 CB Closing time 1/100 F1 P122-P123
sec
0119 to Reserved P120 to
011D P123
011E Maintenance mode P122-P123
011F Relays Latching F14 P121-
P122-P123
0120 Ratio Primary phase CT value 1 to 1 - F1 1000 P121-
50000* P122-P123
0121 Secondary phase CT 1 to 5 4 - F1 1 P121-
value P122-P123
0122 Primary earth CT value 1 to 1 - F1 1000 P120 to
50000* P123
0123 Secondary earth CT 1 to 5 4 - F1 1 P120 to
value P123
0124 to Reserved P120 to
012E P123
012F Rotation phase sequence 0 to 1 1 - F51 0 P121-
P122-P123
0130 Communication Speed 0 to 7 1 - F4 6= P120 to
19200 P123
bds
0131 Parity 0 to 2 1 - F5 0= P120 to
without P123
0132 Data bits 0 to 1 1 - F28 1 = 8 bits P120 to
P123
0133 Stop bit 0 to 1 1 - F29 0=1 P120 to
stop bit P123
0134 COM available 0 to 1 1 - F30 1=COM P120 to
available P123
0135 Date Format 0 to 1 1 - F48 0= P122-P123
Private
0136 to Reserved 0 P120 to
013F P123
0140 Configuration Setting group 1 to 2 1 - F1 1 P122-P123
0141 Validation of 0 to 1 1 - F1 0 P122-P123
instantaneous alarms
auto reset
0142 Configuration of change 0 to 1 1 - F47 1 P122-P123
of group selection
0143 Battery alarm and RAM 0 to 1 1 - F1 0 P122-P123
error configuration
0144 Configuration of LED 0 to 1 1 F1 0 P122-P123
reset on fault
0145 to Reserved 0 P120 to
0149 P123
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 15/170
Values Fault
Address Group Description Step Unit Format Range
range Value
014A Output Relay Max I2>> 0 to 31 1 - F14 0 P122-P123
allocation
014B to Reserved P120 to
014F P123
0150 LEDs Led 5 1 - F19 4 P120 to
allocation P123
0151 Led 6 1 - F19 16 P120 to
P123
0152 Led 7 1 - F19 32 P120 to
P123
0153 Led 8 1 F19 64 P120 to
P123
0154 Led PF 5 1 F19' 0 P122-P123
0155 Led PF 6 1 F19' 0 P122-P123
0156 Led PF 7 1 F19' 0 P122-P123
0157 Led PF 8 1 F19' 0 P122-P123
0158 to Reserved P122-P123
015A
015B Logic input Logic input 1 VTA - F15 0 P122-P123
allocation Bis
015C Logic input 2 VTA - F15 0 P122-P123
Bis
015D Logic input 3 VTA - F15 0 P122-P123
Bis
015E Logic input 4 VTA - F15 0 P122-P123
Bis
015F Logic input 5 VTA - F15 0 P122-P123
Bis
Values Fault
Address Group Description Step Unit Format Range
range Value
0160 Logic input Logic input 1 VTA - F15 0 P120 to
allocation P123
0161 Logic input 2 VTA - F15 0 P120 to
P123
0162 Logic input 3 VTA - F15 0 P122-P123
0163 Logic input 4 VTA - F15 0 P123
0164 Logic input 5 VTA - F15 0 P123
0165 Output relay Broken conductor 0-31 1 - F14 0 P122-P123
allocation detection
0166 CB failure 0 - 31 1 - F14 0 P122-P123
0167 I< 0 - 31 1 - F14 0 P122-P123
0168 I2> 0 - 31 1 - F14 0 P122-P123
0169 Thermal overload alarm 0 - 31 1 - F14 0 P122-P123
016A Thermal overload trip 0-31 1 - F14 0 P122-P123
016B CB close 0-31 1 - F14 0 P121-
P122-P123
016C tAUX1 0-31 1 - F14 0 P122-P123
016D tAUX2 0-31 1 - F14 0 P122-P123
E
016 CB alarms 0-31 1 - F14 0 P122-P123
016F Trip circuit 0-31 1 - F14 0 P123
0170 Active setting group 0 - 31 1 - F14 0 P122-P123
If active group =2 than
output =1
0171 Trip 0 - 31 1 - F14 1 P120 to
P123
0172 tI> 0 - 31 1 - F14 0 P121-
P122-P123
0173 tI>> 0 - 31 1 - F14 0 P121-
P122-P123
0174 tI>>> 0 - 31 1 - F14 0 P121-
P122-P123
0175 tIE> 0 - 31 1 - F14 0 P120 to
P123
0176 tIE>> 0 - 31 1 - F14 0 P120 to
P123
0177 tIE>>> 0 - 31 1 - F14 0 P120 to
P123
0178 I> 0 - 31 1 - F14 0 P121-
P122-P123
0179 I>> 0 - 31 1 - F14 0 P121-
P122-P123
017A I>>> 0 - 31 1 - F14 0 P121-
P122-P123
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 17/170
Values Fault
Address Group Description Step Unit Format Range
range Value
017B IE> 0 - 31 1 - F14 0 P120 to
P123
017C IE>> 0 - 31 1 - F14 0 P120 to
P123
017D IE>>> 0 - 31 1 - F14 0 P120 to
P123
017E Recloser running 0 - 31 1 - F14 0 P123
017F Recloser final trip 0 - 31 1 - F14 0 P123
0180 Automation Trip 0 to 63 1 - F6 1 P120 to
P123
0181 Relay latching 0 to 63 1 - F8 0 P120 to
P123
0182 Blocking logic 1 0 to 63 1 - F8' 0 P120 to
P123
0183 Blocking logic 2 0 to 63 1 - F8' 0 P122-P123
0184 Broken conductor 0-1 1 - F24 0 P122-P123
detection
0185 tBC 0 to 14400 1 - F1 0 P122-P123
0186 Cold load start 0-1 1 - F24 0 P122-P123
0187 Cold load start thresholds 0 to 255 1 - F33 0 P122-P123
0188 Cold load start % 100 to 500 1 F1 50 P122-P123
0189 Cold load start delay 1 to 36000* 1 1/10 s F1 10 P122-P123
018A CB failure 0-1 1 F24 0 P122-P123
018B tBF 0 to 1000 1 1/100 F1 10 P122-P123
s
018C Logic Selectivity1 0 to 15 1 - F40 0 P122-P123
018D tSEL1 0 to 15000 1 1/100 F1 0 P122-P123
s
018E Logic Selectivity2 0 to 15 1 - F40 0 P122-P123
018F tSEL2 0 to 15000 1 1/100 F1 0 P122-P123
s
0190 Disturbance Pre-time 1 to 30 1 - F1 1 P122-P123
0191 Post-time 1 to 30 1 - F1 1 P122-P123
0192 Disturbance starting 0-1 1 - F32 0 P122-P123
condition
Values Fault
Address Group Description Step Unit Format Range
range Value
0193 CB monitoring Operating time 0-1 1 - F24 0 P122-P123
0194 Operating time threshold 5 to 100 5 1/100 s F1 5 P122-P123
0195 Operation number 0-1 1 - F24 0 P122-P123
0196 Operation number 0 - 50000 1 - F1 0 P122-P123
threshold
0197 CB switched Amps sum 0-1 1 - F24 0 P122-P123
(Power n)
0198 CB switched Amps sum 0 to 10E6 An F3 P122-P123
threshold 4000
0199 Amps or square Amps 1-2 1 F1 1 P122-P123
019A Closing time threshold 5 to 100 5 1/100 s F1 0 P122-P123
019B Auxiliary timer 1 0 to 20000 1 1/100 s F1 0 P122-P123
019C Auxiliary timer 2 0 to 20000 1 1/100 s F1 0 P122-P123
019D Peak value 5 to 60 VTA min F42 5 P122-P123
019E I2/I1 threshold 20 to 100 1 % F1 20 P122-P123
019F Tripping time 10 to 500 5 1/100 s F1 10 P122-P123
01A0 Closing time 10 to 500 5 1/100 s F1 10 P122-P123
01A1 Closing time threshold 0-1 1 F24 0 P122-P123
validation
01A2 Trip circuit supervision 0-1 1 F24 0 P122-P123
validation
01A3 t SUP 10 to 1000 5 1/100 s F1 10 P122-P123
01A4 I< threshold CB failure 10 - 100 1 %In F1 10 P122-P123
01A5 Instantaneous phase 0–1 1 - F24 0 P122-P123
blocking if CB failure
01A6 Instantaneous earth 0–1 1 - F24 0 P122-P123
blocking if CB failure
01A7 Rolling Sub period 0 – 60 1 min F1 P122-P123
Demand
01A8 Sub period number 0 – 24 1 - F1 P122-P123
01A9 Output relay Communication Order 1* 0 - 31 1 - F14 0 P122-P123
allocation
01AA Communication Order 2* 0 - 31 1 - F14 0 P122-P123
01AB Communication Order 3* 0 - 31 1 - F14 0 P122-P123
01AC Communication Order 4* 0 - 31 1 - F14 0 P122-P123
01AD T comm 1* 10 – 500 5 1/100s F1 10 P122-P123
01AE T comm 2* 10 – 500 5 1/100s F1 10 P122-P123
01AF T comm 3* 10 – 500 5 1/100s F1 10 P122-P123
01B0 T comm 4* 10 – 500 5 1/100s F1 10 P122-P123
01B1 tEXT 3 0 – 31 1 - F14 0 P122-P123
01B2 tEXT 4 0 – 31 1 - F14 0 P123
01B3 Auxiliary timer3 0 – 20000 1 1/100s F1 0 P122-P123
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 19/170
Values Fault
Address Group Description Step Unit Format Range
range Value
01B4 Auxiliary timer4 0 – 20000 1 1/100s F1 0 P123
01B5 to Reserved P120 to
01BF P123
01C0 to Reserved ** P123
01F5
01F6 Remote trip** 0 – 31 1 - F14 0 P123
01F7 Remote close** 0 – 31 1 - F14 0 P123
01F8 SOFT function** 0–1 1 - F52 0 P123
01F9 SOFT timer** 0 - 500 1 1/1000s F1 0 P123
01FA SOFT parameter I>> or 0-1 1 - F53 0 P123
I>>>**
01FB Trip bis** 0 to 63 1 - F6’ 0 P123
01FC Relay latching bis** 0 to 63 1 - F7 0 P123
01FD Output relay SOFT** 0 - 31 1 - F14 0 P123
allocation
01FE Output relay Locked recloser *** 0 - 31 1 - F14 0 P123
allocation
* From V5.D
** From V6.C
*** From V6.G
P12x/EN CT/F75 Communications
Modbus Database
Page 20/170 MiCOM P120/P121/P122/P123
Values Fault
Address Group Description Step Unit Format Range
range Value
0200 Setting group I> 0-1 1 - F24 0 P121-P122-
1 P123
0201 I> threshold 10 to 2500 1 In/100 F1 10 P121-P122-
P123
0202 I> time delay type 0 to 2 1 - F27 0 P121-P122-
P123
0203 I> IDMT Curve Type 0 to 10 1 - F3 1 P121-P122-
P123
0204 I> TMS value 25 to 1500 25 1/1000 F1 25 P121-P122-
P123
0205 I> K value (RI curve) 100 to 10000 5 1/1000 F1 100 P121-P122-
P123
0206 tI> value 0 to 15000 1 1/100 s F1 4 P121-P122-
P123
0207 I> Reset type 0-1 1 F27 0 P122-P123
0208 I> RTMS value 25 to 3200 25 1/1000 F1 25 P122-P123
0209 I> tRESET value 4 to 10000 1 1/100 s F1 4 P122-P123
020A to Reserved 0 P120 to
020F P123
0210 I>> 0-1 1 - F24 0 P121-P122-
P123
0211 I>> Threshold 50 to 4000 5 In/100 F1 50 P121-P122-
P123
0212 tI>> value 0 to 15000 1 1/100 s F1 1 P121-P122-
P123
0213 I>> time delay type 0–2 1 - F27 0 P122-P123
0214 I>> IDMT curve type 0 – 10 1 - F3 1 P122-P123
0215 I>> TMS value 25 – 1500 25 1/1000 F1 25 P122-P123
0216 K value (RI curve) 100 – 10000 5 1/1000 F1 100 P122-P123
0217 I>> Reset Type 0–1 1 - F27 0 P122-P123
0218 I>> RTMS value 25 – 3200 25 1/1000 F1 25 P122-P123
0219 I>> tRESET value 4 – 10000 1 1/100 s F1 4 P122-P123
021A to Reserved 0 P120 to
021F P123
0220 I>>> 0-1 1 - F24 0 P121-P122-
P123
0221 I>>> Threshold 50 to 4000 5 In/100 F1 50 P121-P122-
P123
0222 tI>>> value 0 to 15000 1 1/100 s F1 1 P121-P122-
P123
0223 I>>> on sample 0–1 1 - F24 0 P122-P123
0223 to Reserved 0 P120 to
022F P123
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 21/170
Values Fault
Address Group Description Step Unit Format Range
range Value
0230 IE> 0-1 1 - F24 0 P120 to
P123
0231 IE> Threshold 10 to 1000 5 1/1000 F1 10 P120 to
I0n P123
0232 IE> time delay type 0 to 3 1 - F27’ 0 P120 to
P123
0233 IE> IDMT curve type 0 to 10 1 - F3 1 P120 to
P123
0234 IE> TMS value 25 to 1500 25 1/1000 F1 25 P120 to
P123
0235 IE> K value (RI curve) 100 to 10000 5 1/1000 F1 100 P120 to
P123
0236 tIE> value 0 to 15000 1 1/100 s F1 4 P120 to
P123
0237 IE> reset type 0-1 1 F27 0 P122-P123
0238 IE> RTMS value 25 to 3200 25 1/1000 F1 25 P122-P123
0239 IE> tRESET value 4 to 10000 1 1/100 s F1 4 P122-P123
023A IE> Curve type 0–2 0 1 F3’ 0 P122-P123
(Belgium)
023B to Reserved P120 to
023F P123
0240 IE>> 0-1 1 - F24 0 P120 to
P123
0241 IE>> Threshold 10 to 8000 5 1/1000 F1 10 P120 to
I0n P123
0242 tIE>> value 0 to 15000 1 1/100 s F1 1 P120 to
P123
0243 IE>> time delay type 0 to 3 1 - F27’ 0 P122-P123
0244 IE>> IDMT curve type 0 to 10 1 - F3 1 P122-P123
0245 IE>> TMS value 25 to 1500 25 1/1000 F1 25 P122-P123
0246 IE>> K value 100 to 10000 5 1/1000 F1 100 P122-P123
(RI curve)
0247 TReset Type 0–1 1 - F27 0 P122-P123
0248 Time Multiplier 25 – 3200 25 1/1000 F1 25 P122-P123
TDMS
0249 TReset 4 – 10000 1 1/100 s F1 4 P122-P123
024A Curve Type 0–2 0 1 F3’ 0 P122-P123
(Belgium)
024B to Reserved 0 P120 to
024E P123
024F IE>> on sample 0–1 1 - F24 0 P122-P123
0250 IE>>> 0-1 1 - F24 0 P120 to
P123
0251 IE>>> Threshold 10 to 8000 5 1/1000 F1 10 P120 to
I0n P123
P12x/EN CT/F75 Communications
Modbus Database
Page 22/170 MiCOM P120/P121/P122/P123
Values Fault
Address Group Description Step Unit Format Range
range Value
0252 tIE>>>value 0 to 15000 1 1/100 s F1 1 P120 to
P123
0253 Ith> 0-1 1 F24 0 P122-P123
0254 Ith> Threshold 10 to 320 5 1/100 F1 8 P122-P123
0255 Ith> k value 100 to 150 1 1/100 F1 105 P122-P123
0256 Ith> trip threshold 50 to 200 1 % F1 100 P122-P123
0257 Ith> alarm 0-1 1 F24 0 P122-P123
0258 Ith> alarm threshold 50 to 200 1 % F1 90 P122-P123
0259 Thermal overload time 1 to 200 1 mn F1 1 P122-P123
constant
025A I< 0-1 1 - F24 0 P122-P123
025B I< threshold 0 to 100 1 % In F1 20 P122-P123
025C I2> 0-1 1 - F24 0 P122-P123
025D I2> threshold 10 to 4000 1 In/100 F1 10 P122-P123
025E I2> time delay type 0 to 2 1 - F27 0 P122-P123
025F I2> IDMT type 0 to 9 1 - F3 1 P122-P123
0260 I2> TMS value 25 to 1500 25 1/1000 F1 25 P122-P123
0261 I2> K value (RI) 100 to 10000 5 1/1000 F1 100 P122-P123
0262 tI2> value 0 to 15000 1 1/100 s F1 P122-P123
0263 I2> Reset type 0-1 1 F27 0 P122-P123
0264 I2> RTMS value 25 to 3200 25 1/1000 F1 25 P122-P123
0265 I2> tRESET value 4 to 10000 1 1/100 s F1 4 P122-P123
0266 Iinv>> 0–1 1 - F24 0 P122-P123
0267 Iinv>> Threshold 10 – 4000 1 1/100 In F24 10 P122-P123
0268 tIinv>> value 0 to 15000 1 1/100 s F1 P122-P123
0269 to Reserved 0 P120 to
026E P123
026F tI< value 0 to 15000 1 1/100 s F1 P122-P123
0270 AR Recloser valid 0-1 1 F24 0 P123
0271 CB position active 0-1 1 F1 0 P123
0272- Supervision window 1 to 60000 1 1/100 s F18 1 P123
0273
0274 External blocking input 0 – 1 1 F24 0 P123
0275 to Reserved P120 to
0276 P123
0277 Dead time 1 0 to 30000 1 1/100 s F1 1 P123
0278 Dead time 2 0 to 30000 1 1/100 s F1 1 P123
0279- Dead time 3 0 to 60000 1 1/100 s F18 1 P123
027A
027B- Dead time 4 0 to 60000 1 1/100 s F18 1 P123
027C
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 23/170
Values Fault
Address Group Description Step Unit Format Range
range Value
027D- Reclaim time 2 to 60000 1 1/100 s F18 2 P123
027E
027F- Inhibit time 2 to 60000 1 1/100 s F18 2 P123
0280
0281 Recloser cycles for 0 to 4 1 F1 0 P123
phase faults
0282 Recloser cycles for 0 to 4 1 F1 0 P123
earth faults
0283 I> Phase cycle 0 – 2222 1 F49 0 P123
configuration
0284 I>> Phase cycle 0 – 2222 1 F49 0 P123
configuration
0285 I>>> Phase cycle 0 – 2222 1 F49 0 P123
configuration
0286 IE> Phase cycle 0 – 2222 1 F49 0 P123
configuration
0287 IE>> Phase cycle 0 – 2222 1 F49 0 P123
configuration
0288 IE>>> Phase cycle 0 – 2222 1 F49 0 P123
configuration
0289 TAUX1 cycle 0 – 2222 1 F49 0 P123
configuration
028A TAUX2 cycle 0 – 2222 1 F49 0 P123
configuration
P12x/EN CT/F75 Communications
Modbus Database
Page 24/170 MiCOM P120/P121/P122/P123
3.6 Page 4h
Access in writing
Values Fault
Address Group Description Step Unit Format Range
range Value
0400 Remote Remote control word 1 0 to 31 1 - F9 0 P120 to
control P123
0401 Reserved 0 P120 to
P123
0402 Remote control word 2 0 to 511 1 - F39 0 P122-P123
(single output command)
0403 Remote control word 3 0 to 1 1 - F46 0 P122-P123
3.8 Page 7h
Access in quick reading only (MODBUS 07 function)
Values Fault
Address Group Description Step Unit Format
range Value
0700 Quick Description of the 1 - F23 0
reading byte protection autocontrol
Addresses Contents
0900h to 09FAh 250 disturbance data words
0A00h to 0AFAh 250 disturbance data words
0B00h to 0BFAh 250 disturbance data words
0C00h to 0CFAh 250 disturbance data words
0D00h to 0DFAh 250 disturbance data words
0E00h to 0EFAh 250 disturbance data words
0F00h to 0FFAh 250 disturbance data words
1000h to 10FAh 250 disturbance data words
1100h to 11FAh 250 disturbance data words
1200h to 12FAh 250 disturbance data words
1300h to 13FAh 250 disturbance data words
1400h to 14FAh 250 disturbance data words
1500h to 15FAh 250 disturbance data words
1600h to 16FAh 250 disturbance data words
1700h to 17FAh 250 disturbance data words
1800h to 18FAh 250 disturbance data words
1900h to 19FAh 250 disturbance data words
1A00h to 1AFAh 250 disturbance data words
1B00h to 1BFAh 250 disturbance data words
1C00h to 1CFAh 250 disturbance data words
1D00h to 1DFAh 250 disturbance data words
1E00h to 1EFAh 250 disturbance data words
1F00h to 1FFAh 250 disturbance data words
2000h to 20FAh 250 disturbance data words
2100h to 21FAh 250 disturbance data words
NB: The disturbance data pages contain values of one channel from one
given disturbance record.
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 31/170
• Frequency channel:
Time between two samples in microseconds
• Logic channels:
Addresses Contents
2200h Disturbance data index frame
Word Contents
n° 1 Disturbance record number
n° 2 Disturbance record finish date (second)
n° 3 Disturbance record finish date (second)
n° 4 Disturbance record finish date (millisecond)
n° 5 Disturbance record finish date (millisecond)
n° 6 Disturbance record starting condition:
1: tripping command (RL1)
2: instantaneous
3: remote command
4: logic input
n° 7 Frequency at the post-time beginning
n° 8 (=0) Optional
n° 9 (=0) Optional
MODBUS COURIER
Code Meaning of the event Type
address Cell
00 No event - -
01 Remote closing F9 013h 021
02 Remote tripping F9 013h 021
03 Disturbance recording start F9 -
04 Trip output delatch F9 013h 021
05 Setting change Address -
06 Remote thermal reset F9 -
07 Maintenance Mode F9 ↑ ↓ 0400h -
08 Control relay in maintenance mode F39 ↑ ↓ 013h -
09 I> F17 ↑ ↓ 014h 023
10 I>> F17 ↑ ↓ 015h 023
11 I>>> F17 ↑ ↓ 016h 023
12 IE> F16 ↑ ↓ 017h 023
13 IE>> F16 ↑ ↓ 018h 023
14 IE>>> F16 ↑ ↓ 019h 023
15 Thermal overload alarm F37 ↑ ↓ 020h 023
16 Thermal overload threshold F37 ↑ ↓ 020h 023
17 tI> F17 ↑ ↓ 014h 023
18 tI>> F17 ↑ ↓ 015h 023
19 tI>>> F17 ↑ ↓ 016h 023
20 tIE> F16 ↑ ↓ 017h 023
21 tIE>> F16 ↑ ↓ 018h 023
22 tIE>>> F16 ↑ ↓ 019h 023
23 tI< F16 ↑ ↓ 021h 023
24 Broken conductor F38 ↑ ↓ 023h 024
25 t Aux 1 F38 ↑ ↓ 023h 024
26 t Aux 2 F38 ↑ ↓ 023h 024
27 CB failure F38 ↑ ↓ 023h 024
28 Selective scheme logic 1 F20 ↑ ↓ 011h 020
29 Selective scheme logic 2 F20 ↑ ↓ 011h 020
30 Blocking logic 1 F20 ↑ ↓ 011h 020
31 Blocking logic 2 F20 ↑ ↓ 011h 020
32 Setting group change F20 011h 020
33 52a F20 ↑ ↓ 011h 020
34 52b F20 ↑ ↓ 011h 020
35 Acknowledgement of the output F20 ↑ ↓ 011h 020
relay latched, by logic input,
P12x/EN CT/F75 Communications
Modbus Database
Page 34/170 MiCOM P120/P121/P122/P123
MODBUS COURIER
Code Meaning of the event Type
address Cell
36 SF6 F20 ↑ ↓ 011h 020
37 Cold load start F20 ↑ ↓ 011h 020
38 Change of input logic state F12 ↑ ↓ 010h 020
39 Thermal overload trip F37 013h 021
40 tI> trip F13 013h 021
41 tI>> trip F13 013h 021
42 tI>>> trip F13 013h 021
43 tIE> trip F13 013h 021
44 tIE>> trip F13 013h 021
45 tIE>>> trip F13 013h 021
46 tI< trip F13 013h 021
47 Broken conductor trip F13 013h 021
48 tAUX 1 trip F13 013h 021
49 tAUX 2 trip F13 013h 021
50 Output relays command F39 ↑ ↓ 013h 021
51 Front panel single alarm acknowl. - -
52 Front panel all alarms acknowledge - -
53 Remote single alarm acknowledge - -
54 Remote all alarms acknowledge - -
55 Major material alarm F45 ↑ ↓ 00Fh 022
56 Minor material alarm F45 ↑ ↓ 00Fh 022
57 I2> F16 ↑ ↓ 022h 024
58 tI2> F16 ↑ ↓ 022h 024
59 Operation time F43 ↑ ↓ 028h 024
60 Operation numbers F43 ↑ ↓ 028h 024
61 Sum of switched square amps F43 ↑ ↓ 028h 024
62 Trip circuit supervision F43 ↑ ↓ 028h 024
63 Closing time F43 ↑ ↓ 028h 024
64 Reclose successful F43 ↑ ↓ 028h 024
65 Recloser final trip F43 ↑ ↓ 028h 025
66 Recloser settings error or F43 ↑ ↓ 028h 024
configuration error
67 I2> trip F16 ↑ ↓ 013h 021
68 General Starting (IEC103) F1 ↑ ↓ 009h -
69 Recloser active (IEC103) F43 ↑ ↓ 028h -
70 CB Closed by autoreclosure -
(IEC103)
71 Relays latching F13 02Eh -
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 35/170
MODBUS COURIER
Code Meaning of the event Type
address Cell
72 External CB failure F20 bis ↑ ↓ 02Ah 020
73 I< F16 ↑ ↓ 021h 023
74 I2>> F16 ↑ ↓ 022h 024
75 tI2>> F16 ↑ ↓ 022h 024
76 I2>> Trip F16 ↑ ↓ 013h 021
77 Reserved
78 Latching Trip Relay (RL1) - - -
79 t AUX3 F38 023h 025
80 t AUX3 TRIP F13 013h 021
81 t AUX4 F38 023h 025
82 t AUX4 TRIP F13 013h 021
83 t Reset I> F17 ↑ ↓ 014h 025
84 t Reset I>> F17 ↑ ↓ 015h 025
85 t Reset Ie> F16 ↑ ↓ 017h 025
86 t Reset Ie>> F16 ↑ ↓ 018h 025
87 t Reset I2> F16 ↑ ↓ 022h 025
88 TRIP Breaker Failure F13 013h 021
89 t BF / Ext. Breaker Failure F38 023h 025
90 Manual Close (input) F20 bis ↑ ↓ 02Ah 020
91 t SOTF F54 070h 025
92 TRIP t SOTF F13 013h 021
93 Local Mode (IEC 103) F20 bis ↑ ↓ 02Ah 020
94 Reset leds (IEC103)
95 Recloser locked F43 ↑ ↓ 028h 024
96 Recloser in progress F43 ↑ ↓ 028h 025
Addresses Contents
3600h Most older event data
P12x/EN CT/F75 Communications
Modbus Database
Page 36/170 MiCOM P120/P121/P122/P123
Addresses Contents
3700h Fault value record n°1
3701h Fault value record n°2
3702h Fault value record n°3
3703h Fault value record n°4
3704h Fault value record n°5
Addresses Contents
3E00h Most older Fault record
Addresses Contents
3D00h Number of disturbance records available
CODE DESCRIPTION
F1 Unsigned integer – numerical data: 65535
F2 Signed integer – numerical data: -32768 – 32767
F3 Unsigned integer – curves type
0: STI (IEC)
1: SI (IEC)
2: VI (IEC)
3: EI (IEC)
4: LTI (IEC)
5: STI (C02)
6: MI (ANSI)
7: LTI (CO8)
8: VI (ANSI)
9: EI (ANSI)
10: RC (IEC) Rectifier curve
F3’ Unsigned integer –Belgium curves type for Earth sensitive version
0: Network 1 (Laborellec)
1: Network 2 (Laborellec)
2: source 3 (Laborellec)
F4 Unsigned integer: MODBUS speed
0: 300
1: 600
2: 1200
3: 2400
4: 4800
5: 9600
6: 19200
7: 38400
F5 Unsigned integer: parity
0: without
1: even
2: odd
F6 Unsigned integer: Tripping configuration
bit 0: tI>
bit 1: tI>>
bit 2: tI>>>
bit 3: tIE>
bit 4: tIE>>
bit 5: tIE>>>
bit 6: I<
bit 7: tIth>
bit 8: Broken conductor detection
bit 9: t Aux 1
bit 10: t Aux 2
bit 11: tI2>
bit 12: tI2>>
bit 13: t Aux 3
bit 14: t Aux 4
bit 15: Breaker Failure
F6’ Unsigned integer: Tripping configuration
bit 0: SOFT
bit 1: Remote Trip
bit 2 to 15: Reserved
P12x/EN CT/F75 Communications
Modbus Database
Page 42/170 MiCOM P120/P121/P122/P123
CODE DESCRIPTION
F7 Unsigned integer: Latching configuration
bit 0: SOFT
bit 1 to 15: Reserved
F8 Unsigned integer: Latching configuration
bit 0: I> latching
bit 1: I>>
bit 2: I>>>
bit 3: IE>
bit 4: IE>>
bit 5: IE>>>
bit 6: I<
bit 7: tIth>
bit 8: Broken conductor detection
bit 9: t Aux 1
bit 10: t Aux 2
bit 11: tI2>
bit 12: tI2>>
bit 13: t Aux 3
bit 14: t Aux 4
bit 15: Breaker Failure
F8' Unsigned integer: Blocking logic configuration
bit 0: I> blocking
bit 1: I>>
bit 2: I>>>
bit 3: IE>
bit 4: IE>>
bit 5: IE>>>
bit 6: reserved
bit 7: tIth>
bit 8: Broken conductor detection
bit 9: t Aux 1
bit 10: t Aux 2
bit 11: tI2>
bit 12: tI2>>
bit 13: t Aux 3
bit 14: t Aux 4
bit 15: reserved
F9 Unsigned integer: Remote control 1
bit 0: Tripping contact delatched
bit 1: 1st alarm acknowledge
bit 2: All alarms acknowledge
bit 3: Remote tripping
bit 4: Remote closing
bit 5: Setting group change
bit 6: Thermal state reset
bit 7: Peak and rolling value reset
bit 8: Disturbance record remote start
bit 9: Maintenance mode
bit 10: Recloser counter reset
bit 11: Recloser reset
bit 12: Local manual acknowledge
bit 13: Oldest event acknowledge
bit 14: Oldest fault acknowledge
bit 15: Hardware RAM alarm acknowledge
F10 2 characters ASCII
32 –127 = ASCII character1
32 – 127 = ASCII character 2
F11 Reserved
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 43/170
CODE DESCRIPTION
F12 Unsigned integer: Logic input status
bit 0: logic input number 1
bit 1: logic input number 2
bit 2: logic input number 3
bit 3: logic input number 4
bit 4: logic input number 5
bits 5 to 15: reserved
F13 Unsigned integer: logic outputs status
bit 0: logic output number RL1 (tripping)
bit 1: logic output number RL2
bit 2: logic output number RL3
bit 3: logic output number RL4
bit 4: logic output number RL0 (watchdog)
bit 5: logic output number RL5
bit 6: logic output number RL6
bit 7: logic output number RL7
bit 8: logic output number RL8
bits 9 to 15: reserved
F14 Unsigned integer: logic outputs configuration
bit 0: selection logic output number RL2
bit 1: selection logic output number RL3
bit 2: selection logic output number RL4
bit 3: selection logic output number RL5
bit 4: selection logic output number RL6
bit 5: selection logic output number RL7
bit 6: selection logic output number RL8
F15 Unsigned integer: logical input allocation
bit 0: delatch allocation
bit 1: allocation 52 a
bit 2: allocation 52 b
bit 3: allocation Lack of SF6
bit 4: allocation external input 1
bit 5: allocation external input 2
bit 6: allocation logic blocking 1
bit 7: allocation logic blocking 2
bit 8: allocation disturbance start
bit 9: allocation cold load start
bit 10: allocation selective scheme logic 1
bit 11 allocation selective scheme logic 2
bit 12: allocation change of setting group
bit 13: allocation recloser locked
bit 14: allocation thermal state reset
bit 15: allocation trip circuit supervision
F15bis bit 0: allocation Circuit Breaker Failure
bit 1: Reset of LEDs alarms
bit 2: Maintenance mode
bit 3: allocation external input 3
bit 4: allocation external input 4
bit 5: SOFT/TOR (from V6.C)
bit 6: Local/remote (from V6.C)
P12x/EN CT/F75 Communications
Modbus Database
Page 44/170 MiCOM P120/P121/P122/P123
CODE DESCRIPTION
F16 Unsigned integer: threshold earth information status
bit 0: information threshold exceeded (IE> or IE>> or IE>>>)
bit 1: reserved
bit 2: reserved
bit 3: reserved
bit 4: reserved
bit 5: Instantaneous information IE> or IE>> or IE>>>
bit 6: Tripping information tIE> or tIE>> or tIE>>>
bits 7 to 15: reserved
F17 Unsigned integer: threshold phase information status
bit 0: information thresold exceeded (I>, I>>, I>>>)
bit 1: Instantaneous IA
bit 2: Instantaneous IB
bit 3: Instantaneous IC
bit 4: reserved
bit 5: Instantaneous information I> or I>> or I>>>
bit 6: Tripping information tI> or tI>> or tI>>>
bits 7 to 15: reserved
F18 Long integer
F19 Unsigned integer: LEDs allocation
bit 0: I>
bit 1: tI>
bit 2: I>>
bit 3: tI>>
bit 4: I>>>
bit 5: tI>>>
bit 6: IE>
bit 7: tIE>
bit 8: IE>>
bit 9: tIE>>
bit 10: IE>>>
bit 11: tIE>>>
bit 12: Thermal overload trip
bit 13: tI2>
bit 14: Broken conductor trip
bit 15: CB failure
bit 16: Logic input 1
bit 17: Logic input 2
bit 18: Logic input 3
bit 19: Logic input 4
bit 20: Logic input 5
bit 21: Recloser running
bit 22: Recloser locked
bit 23: tAUX1
bit 24: tAUX2
bit 25: tI2>>
bit 26: SOFT (from V6.C)
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 45/170
CODE DESCRIPTION
F20 Unsigned integer: logic input data status
bit 0: Selective scheme logic 1
bit 1: Selective scheme logic 2
bit 2: Relay delatch
bit 3: CB position (52 a)
bit 4: CB position (52 b)
bit 5: Lack of SF6
bit 6: External 1
bit 7: External 2
bit 8: Blocking logic 1
bit 9: Blocking logic 2
bit 10: Disturbance record start
bit 11: Cold load start
bit 12: Setting group change
bit 13: Recloser locked
bit 14: Thermal state reset
bit 15: Trip circuit supervision
F20 bis bit 0: CB Failure by external signalisation
bit 1: LEDs alarms reset
bit 2: maintenance mode
bit 3: External 3
bit 4: External 4
bit 5: Manual Close (SOFT/TOR)
bit 6: Local Mode
CODE DESCRIPTION
F28 0: 7 data bits
1: 8 data bits
F29 0: 1 stop bit
1: 2 stop bits
F30 0: Communication non-available
1: Communication available
F31 Unsigned integer: Number of available event records
0: None
1: 1 event record available
2: 2 event records available
3: 3 event records available
4: 4 event records available
5: 5 event records available
F32 Unsigned integer:
0: Disturbance record start condition on INSTANTANEOUS
1: Disturbance record start condition on TRIPPING
F33 Cold load start thresholds
bit 0: tI>
bit 1: tI>>
bit 2: tI>>>
bit 3: tIE>
bit 4: tIE>>
bit 5: tIE>>>
bit 6: Thermal overload trip
bit 7: tI2>
bit 8: tI2>>
bit 9 to 15: reserved
F34 Reserved
F35 0: No disturbance record uploaded
1: Disturbance record upload running
F36 Memorised flags of non acknowledged alarms:
bit 0: IE>
bit 1: tIE>
bit 2: IE>>
bit 3: tIE>>
bit 4: IE>>>
bit 5: tIE>>>
bit 6: Thermal overload alarm
bit 7: Thermal overload trip
bit 8: Broken conductor
bit 9: CB failure
bit 10: I2>>
bit 11: I2>
bit 12: tI2>
bit 13: t Aux 1
bit 14: t Aux 2
bit 15: tI2>>
F37 Unsigned integer: Thermal overload information
bit 0: Thermal overload alarm
bit 1: Thermal overload trip
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 47/170
CODE DESCRIPTION
F38 Unsigned integer:
bit 0: reserved
bit 1: CB failure
bit 2: Pole A opening
bit 3: Pole B opening
bit 4: Pole C opening
bit 5: Broken conductor
bit 6: t Aux 1
bit 7: t Aux 2
bit 8: Broken conductor time delay
bit 9: CB failure time delay
bit 10: Cold load pick up time delay
bit 11: CB alarms or bits 0,1,2,4 of F43
bit 12: t Aux 3
bit 13: t Aux 4
F39 Unsigned integer: output relay remote word in maintenance mode
bit 0: RL1 (trip)
bit 1: RL2
bit 2: RL3
bit 3: RL0 (watch-dog)
bit 4: RL4
bit 5: RL5
bit 6: RL6
bit 7: RL7
bit 8: RL8
F40 Unsigned integer: selective scheme logic configuration
bit 0: tI>>
bit 1: tI>>>
bit 2: tIE>>
bit 3: tIE>>>
F41 0: Front and rear MODBUS communication
1: Front MODBUS and rear Courier communication
2: Front MODBUS and rear IEC103 communication
3: Front MODBUS and rear DNP3 communication
F42 5, 10, 15, 30 or 60 minutes
F43 bit 0: CB operating time overreach
bit 1: CB operation number overreach
bit 2: Square Amps sum overreach
bit 3: Trip circuit self-test
bit 4: CB closing time overreach
bit 5: Recloser locked
bit 6: Recloser successful
bit 7: Recloser in progress
bit 8: Closing command issued from recloser cycle
bit 9: Recloser configuration error
bit 10: Recloser in service
bit 11: Recloser final trip
F44 bit 0: CB, operating time overreach, memorised alarm
bit 1: CB operation number overreach, memorised alarm
bit 2: Square Amps sum overreach, memorised alarm
bit 3: Trip circuit self-test, memorised alarm
bit 4: CB closing time overreach, memorised alarm
Bit 5: t Aux 3, Memorised alarm
Bit 6: t Aux 4, Memorised alarm
Bit 7: reserved
bit 8: SOFT
P12x/EN CT/F75 Communications
Modbus Database
Page 48/170 MiCOM P120/P121/P122/P123
CODE DESCRIPTION
F45 Unsigned integer: relay status
bit 0: Watchdog
bit 1: Communication failure
bit 2: EEPROM data failure
bit 3: Analogue failure
bit 4: Datation failure
bit 5: EEPROM calibration failure
bit 6: SRAM failure
bit 7: Battery failure
bit 8: Reserved
bit 9: Default settings alarm
bit 10 to 15: reserved
F46 bit 0: Launching IO harmonic calculation
bit 1: internally reserved for delatching of tripping relay only (RL1), and not like
bit 0 in F9.
bit 2: Acknowledgement of the oldest disturbance record
bit 3: End of maintenance mode
bit 4: Reset of Rolling Demands Data (average avlues and timers)
bit 5: Reset of maximum values of the averages in sub period
bit 6: LEDs reset
bit 7: Internal reset of non latched tripping LED
bit 8: communication Order 1
bit 9: communication Order 2
bit 10: communication Order 3
bit 11: communication Order 4
F47 0: user wishes working on EDGE (Rising or Falling) of the logic inputs
(configuration can be done by communication or by the front panel)
1: user wishes working on LEVEL (High or Low) of the logic inputs
F48 0: Private Format Date
1: IEC Format Date
F49 bit 0: Cycle 1 configuration ( trip and initialise the reclosure)
bit 1: Cycle 1 configuration ( block the tripping on cycle )
bit 2, 3: reserved
bit 4: Cycle 2 configuration ( trip and initialise the reclosure)
bit 5: Cycle 2 configuration ( block the tripping on cycle )
bit 6, 7: reserved
bit 8: Cycle 3 configuration ( trip and initialise the reclosure)
bit 9: Cycle 3 configuration ( block the tripping on cycle )
bit 10, 11: reserved
bit 12: Cycle 4 configuration ( trip and initialise the reclosure)
bit 13: Cycle 4 configuration ( block the tripping on cycle )
F50 0: DC Voltage
1: AC Voltage
F51 0: Direct phase rotation ABC
1: Inverse phase rotation ACB
F52 Status of SOFT functions (Switch On To Fault)
0: Disabled
1: Enabled
F53 SOFT parameters
0: Start I>>
1: Start I>>>
F54 Bit 0: SOFT in progress
Bit 1: Instantaneous information
Bit 2: Tripping information
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 49/170
This request may be answered an error message with the error code:
EVT_NOK(OF): No record available
NOTA: If there is less than 5 records available, the answer will contains zero
in the non-used words.
4.1.3 Service requests
This request must be send before uploading the disturbance record channel samples. It
allows to know the record number and the channel number to upload. It allows also to know
the number of samples in the channel.
This request may be answered an error message with two different error codes:
CODE_DEF_RAM(02): SRAM failure
CODE_EVT_NOK(03): No disturbance record available in SRAM
4.1.4 Disturbance record upload request
This request may be answered an error message with two different error codes:
CODE_DEP_DATA(04): The required disturbance data number is
greater than the memorised number.
CODE_SERV_NOK(05): The service request for disturbance record and
channel number has not been send.
P12x/EN CT/F75 Communications
Modbus Database
Page 50/170 MiCOM P120/P121/P122/P123
This event request may be answered an error message with the error code:
EVT_EN_COURS_ECRIT (5): An event is being written into the saved RAM.
NOTE: On event retrieval, two possibilities exist regarding the event record
acknowledgement:
a) Automatic event record acknowledgement on event retrieval.
b) Non automatic event record acknowledgement on event
retrieval.
a) Automatic event record acknowledgement on event retrieval:
The bit12 of the remote order frame (format F9 – mapping address 0400h) shall be set to 0.
On event retrieval, this event record is acknowledged.
b) Non automatic event record acknowledgement on event retrieval:
The bit12 of the remote order frame (format F9 – mapping address 0400h) shall be set to 1.
On event retrieval, this event record is not acknowledged.
To acknowledge this event, an other remote order shall be sent to the relay. The bit 13 of
this frame (format F9 – mapping address 0400h) shall be set to 1.
4.1.7 Request to retrieve a dedicated event
This event request may be answered an error message with the error code:
EVT_EN_COURS_ECRIT (5): An event is being written into the saved RAM.
NOTA: This event retrieval does not acknowledge this event.
4.1.8 Modbus request definition used to retrieve the fault records
Two ways can be followed to retrieve a fault record:
Send a request to retrieve the oldest non-acknowledge fault record.
Send a request to retrieve a dedicated fault record.
Communications P12x/EN CT/F75
Modbus Database
MiCOM P120/P121/P122/P123 Page 51/170
NOTA: On fault retrieval, two possibilities exist regarding the fault record
acknowledgement:
a) Automatic fault record acknowledgement on event retrieval.
b) Non automatic fault record acknowledgement on event
retrieval.
a) Automatic fault record acknowledgement on fault retrieval:
The bit12 of the remote order frame (format F9 – mapping address 0400h) shall be set to 0.
On fault retrieval, this fault record is acknowledged.
b) Non automatic fault record acknowledgement on fault retrieval:
The bit12 of the remote order frame (format F9 – mapping address 0400h) shall be set to 1.
On fault retrieval, this fault record is not acknowledged.
To acknowledge this fault, an other remote order shall be sent to the relay. The bit 14 of this
frame (format F9 – mapping address 0400h) shall be set to 1.
4.1.10 Request to retrieve a dedicated fault record
NOTA: This fault value retrieval does not acknowledge this fault record.
Communications P12x/EN CT/F75
MiCOM P120/P121/P122/P123
COURIER DATABASE
MiCOM P120 - P121 - P122 - P123
VERSION V6.E
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 1/170
CONTENT
BLANK PAGE
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 3/170
The following table presents the list of the protection indications of the cell 0024:
The following table presents the list of the protection indications of the cell 0025:
settings, on the changes of the setting groups, on the remote control of the circuit breaker,
as well as on the functions and the locking of the selected output relays.
The remote control is limited in the control functions selected in the table of the relays menu.
The CRC and the controls of the message length are used on each received message. No
response is given for messages received with an error detection. The principal unit can be
re-initialised in order to resent an order as often as wanted if he is not receiving any
response or if he receives a response with an error detection.
NOTE: The control commands are generally materialised by the change of
the cell value. They dispose the same inherent security. No response
is allowed for the global orders to avoid any user conflict of the Bus.
For this type of order, a double start is used for the verification of the
message by the relay.
The relay transmits then a confirmation indicating that the control
order or the change of setting has been accepted.
If this is not the case, the relay is sending an error message.
1.4.11 Change of remote measurements
The relay is only responding to the orders of a setting change through the serial port if the
SD0 link = 1 is selected. The selection of the SD0 link = 1 is blocking all the changes of
remote setting with the exception of the SC logical links and the password capture. When the
SD0 link = 0 is selected, the remote setting are protected by the password.
For changing the remote links, the password has to be first remote captured and the SD and
SD0 function links have to be settled on 1.
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 9/170
• Alarm condition
• Setting Change
• Cell Reference
• Timestamp
• Cell Text
• Cell Value
Paragraph 2 contains a table of the events created by the relay and indicates how the
contents of the above fields are interpreted. Fault records will return a Courier Type 3 event
which contains the above fields together with two additional fields:
• Event number
These events contain additional information which is extracted from the relay using the
referenced extraction column. Row 01 of the extraction column contains a setting which
allows the fault record to be selected. This setting should be set to the event number value
returned within the record, the extended data can be extracted from the relay by uploading
the text and data from the column.
P12x/EN CT/F75 Communications
Courier Database
Page 10/170 MiCOM P120/P121/P122/P123
NOTA: When the cell reference is different of zero this means that the event
is generated on event occurrence and another is generated on event
disappearance.
When the cell reference is equal to zero, only the event on edging edge is generated.
Twelve bits are available in the string of characters to describe the contain of the Courier
cell:
On event occurrence, the corresponding bit of the associated format is set to « 1 ».
On event disappearance, the corresponding bit of the associated format is set to « 0 ».
P12x/EN CT/F75 Communications
Courier Database
Page 14/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
10 Circuit Breaker Control Binary flag (3 bits) 0: No operation Data
1: Trip
2: Close
11 Software Reference ASCII Text (16 characters) Data
12-1F Unused, reserved
20 Logic Input Status Binary flag (3 bits) 0: log input 1 Data
1: log input 2
21 Relay Output Status Binary flag (5 bits) 0: relay 1 (trip) Data
1: relay 2
2: relay 3
3: relay 4
4: watchdog relay
22 Alarm Binary flag (16 bits) 0: Ana output err Data
1: Comm err
2: Eeprom err data
3: Ct error
4: reserved
5: Eeprom err calib
6: reserved
7: reserved
8: reserved
9: Default settings
10 to 15: reserved
23 Pseudo Logic Input Binary flag (12 bits) 3: I0> Data
Status group 1 4: I0>>
5: I0>>>
9: t I0>
10: t I0>>
11: t I0>>>
P12x/EN CT/F75 Communications
Courier Database
Page 16/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
01 00 USER CONTROL
01 Remote control 1 Binary flag (5 bits) 0: Unlock trip cont.* Setting 0/ 31/1
1: Ack first alarm
2: Ack all alarms
3: TRIP
4: CLOSE
5 to 15: Reserved
03 00 MEASUREMENTS
01 I0 RMS Courier floating point Data
number
09 FREQUENCY Courier floating point Data Starting from V5.F
number
0E 00 CT RATIOS
01 CT Primary Unsigned Integer (2 bytes) 1000 * Setting 1/3000/1
02 CT Secondary Unsigned Integer (2 bytes) 1* Setting 1/5/4
Protection Group n° 1
21 00 EARTH FAULT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I> Courier floating point 0.01 I0n* 2102=1 Setting 0.01/1.0/0.005
number
04 Tempo Type I> Indexed String 0 0: definite time * 2102=1 Setting 0/3/1
1 1: inverse time
2 2: RI curve
3 3: Laborelec curves
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 17/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
05 Curve Type I> Indexed String 0 STI (CEI) * 2104=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
07 TMS I> Courier floating point 0.025 * 2104=1 Setting 0.025/1.5/0.025
number
08 K I> Courier floating point 0.1 * 2104=2 Setting 0.1/10.0/0.005
number
09 Tempo I> Courier floating point 0.01 s * 2104=0 Setting 0 /150.0/0.01
number
0C-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I>> Courier floating point 0.01 I0n* 2111=1 Setting 0.01/8.0/0.005
number
18 Tempo I>> Courier floating point 0.01 s * 2113=0 Setting 0 /150.0/0.01
number
1C-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I>>> Courier floating point 0.01 I0n * 2121=1 Setting 0.01/8.0/0.005
number
P12x/EN CT/F75 Communications
Courier Database
Page 18/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
23 Tempo I>>> Courier floating point 0.01 s * 2121=1 Setting 0 /150.0/0.01
number
60 00 AUTOMATISM
01 Trip Configuration Binary (16 bits) 0: t I> * Setting 0 / 65535 / 1
1: t I>>
2: t I>>>
6 to 15: reserved
02 Latched Configuration Binary (16 bits) 0: Latch I> * Setting 0 / 65535 / 1
1: Latch I>>
2: Latch I>>>
6 to 15: reserved
03 Blocking 1 Configuration Binary (16 bits) 0: Blocking t I> * Setting 0 / 65535 / 1
1: Blocking t I>>
2: Blocking t I>>>
6 to 15: reserved
61 00 TS SETTINGS
01 Logical input allocation 1 Indexed String 0 0: nothing * Setting 0/7/1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: CB failure
5 5: External input 1
6 6: External input 2
7 7: Logic blocking
02 Logical input allocation 2 Indexed String 0 0: nothing * Setting 0/7/1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: CB failure
5 5: External input 1
6 6: External input 2
7 7: Logic blocking
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 19/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
62 00 TC SETTINGS
01 GENERAL TRIP Binary (3 bits) 000 * Setting 0/7/1
02 I> Binary (3 bits) 000 * Setting 0/7/1
03 tI> Binary (3 bits) 000 * Setting 0/7/1
04 I>> Binary (3 bits) 000 * Setting 0/7/1
05 t I>> Binary (3 bits) 000 * Setting 0/7/1
06 I>>> Binary (3 bits) 000 * Setting 0/7/1
07 t I>>> Binary (3 bits) 000 * Setting 0/7/1
63 00 LEDS SETTINGS
01 Led 5 Binary (16 bits) 0: I> Setting 0/65535/1
1: t I>
2: I>> *
3: t I>>
4: I>>>
5: t I>>>
12 to 15: Reserved
02 Led 6 Binary (16 bits) 0: I> Setting 0/65535/1
1: t I>
2: I>>
3: t I>>
4: I>>> *
5: t I>>>
12 to 15: Reserved
03 Led 7 Binary (16 bits) 0: I> Setting 0/65535/1
1: t I>
2: I>>
3: t I>>
4: I>>>
5: t I>>> *
12 to 15: Reserved
P12x/EN CT/F75 Communications
Courier Database
Page 20/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
04 Led 8 Binary (16 bits) 0: I> Setting 0/65535/1
1: t I>
2: I>>
3: t I>>
4: I>>>
5: t I>>>
12 to 15: Reserved
BF 00 COMM SYSTEM DATA
03 Setting Transfert Setting 0/1/1
04 Reset Demand Timers NOT IMPLEMENTED
05 Reset Event Report NOT IMPLEMENTED
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 21/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
10 Circuit Breaker Control Binary flag (3 bits) 0: No operation Data
1: Trip
2: Close
11 Software Reference ASCII Text (16 characters) Data
12-1F Unused, reserved
20 Logic Input Status Binary flag (3 bits) 0: log input 1 Data
1: log input 2
2: log input 3
21 Relay Output Status Binary flag (5 bits) 0: relay 1 (trip) Data
1: relay 2
2: relay 3
3: relay 4
4: watchdog relay
22 Alarm Binary flag (16 bits) 0: Ana output err Data
1: Comm err
2: Eeprom err data
3: Ct error
4: reserved
5: Eeprom err calib
6: reserved
7: reserved
8: reserved
9: Default settings
10 to 15: reserved
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 23/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
23 Pseudo Logic Input Binary flag (12 bits) 0: I> Data
Status group 1 1: I>>
2: I>>>
3: I0>
4: I0>>
5: I0>>>
6: t I>
7: t I>>
8: t I>>>
9: t I0>
10: t I0>>
11: t I0>>>
01 00 USER CONTROL
01 Remote control 1 Binary flag (5 bits) 0: Unlock trip cont.* Setting 0/ 31/1
1: Ack first alarm
2: Ack all alarms
3: TRIP
4: CLOSE
5 to 15: Reserved
03 00 MEASUREMENTS
01 IA RMS Courier floating point Data
number
02 IB RMS Courier floating point Data
number
03 IC RMS Courier floating point Data
number
04 I0 RMS Courier floating point Data
number
09 FREQUENCY Courier floating point Data
number
P12x/EN CT/F75 Communications
Courier Database
Page 24/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
0D 00 GENERAL SETTING
01 Phase rotation sense Indexed string 0: Direct (A/B/C) Setting 0 (A/B/C)
1: Inverse (A/B/C) 1 (A/B/C)
0E 00 CT RATIOS
01 Phase CT Primary Unsigned Integer (2 bytes) 1000 * Setting 1/3000/1
02 Phase CT Secondary Unsigned Integer (2 bytes) 1* Setting 1/5/4
03 Neutral CT Primary Unsigned Integer (2 bytes) 1000 * Setting 1/3000/1
04 Neutral CT Secondary Unsigned Integer (2 bytes) 1* Setting 1/5/4
Protection Group n° 1
20 00 PHASE OVERCURRENT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I> Courier floating point 0.1 In * 2002=1 Setting 0.1/25.0/0.1
number
04 Temporisation Type I> Indexed String 0 0: definite time * 2002=1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
05 Curve type I> Indexed String 0 STI (CEI) * 2004=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 25/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
06 TMS I> Courier floating point 0.025 * 2004=1 Setting 0.025/1.5/0.025
number
07 K I> Courier floating point 0.1 * 2004=2 Setting 0.1/10.0/0.005
number
08 Tempo I> Courier floating point 0.01 s * 2004=0 Setting 0 /150.0/0.01
number
0C-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I>> Courier floating point 0.50 In * 2011=1 Setting 0.5/40.0/0.05
number
13 Temporisation Type I>> Indexed String 0 0: definite time * 2011=1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
14 Curve type I>> Indexed String 0 STI (CEI) * 2013=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
15 TMS I>> Courier floating point 0.025 * 2013=1 Setting 0.025/1.5/0.025
number
16 K I>> Courier floating point 0.1 * 2013=2 Setting 0.1/10.0/0.005
number
P12x/EN CT/F75 Communications
Courier Database
Page 26/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
17 Tempo I>> Courier floating point 0.01 s * 2013=0 Setting 0 /150/0.01
number
1B-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I>>> Courier floating point 0.50 In * 2021=1 Setting 0.5/40.0/0.05
number
23 Tempo I>>> Courier floating point 0.01 s * 2021=1 Setting 0 /150/0.01
number
21 00 EARTH FAULT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I0> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I0> Courier floating point 0.01 I0n* 2102=1 Setting 0.01/1.0/0.005
number
04 Tempo Type I0> Indexed String 0 0: definite time * 2102=1 Setting 0/3/1
1 1: inverse time
2 2: RI curve
3 3: Laborelec curves
05 Curve Type I0> Indexed String 0 STI (CEI) * 2104=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 27/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
06 Curve Type 2 Indexed String 0 Curve type 1 * 2104=3 Setting 0/2/1
(Laborelec) I0> 1 Curve type 2
2 Curve type 3
07 TMS I0> Courier floating point 0.025 * 2104=1 Setting 0.025/1.5/0.025
number
08 K I0> Courier floating point 0.1 * 2104=2 Setting 0.1/10.0/0.005
number
09 Tempo I0> Courier floating point 0.01 s * 2104=0 Setting 0 /150.0/0.01
number
0C-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I0>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I0>> Courier floating point 0.01 I0n* 2111=1 Setting 0.01/8.0/0.005
number
13 Tempo Type I0>> Indexed String 0 0: definite time * 2111=1 Setting 0/3/1
1 1: inverse time
2 2: RI curve
3 3: Laborelec curves
14 Curve Type I0>> Indexed String 0 STI (CEI) * 2113=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
P12x/EN CT/F75 Communications
Courier Database
Page 28/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
15 Curve Type 2 Indexed String 0 Curve type 1 * 2113=3 Setting 0/2/1
(Laborelec) I0>> 1 Curve type 2
2 Curve type 3
16 TMS I0>> Courier floating point 0.025 * 2113=1 Setting 0.025/1.5/0.025
number
17 K I0>> Courier floating point 0.1 * 2113=2 Setting 0.1/10.0/0.005
number
18 Tempo I0>> Courier floating point 0.01 s * 2113=0 Setting 0 /150.0/0.01
number
1C-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I0>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I0>>> Courier floating point 0.01 I0n * 2121=1 Setting 0.01/8.0/0.005
number
23 Tempo I0>>> Courier floating point 0.01 s * 2121=1 Setting 0 /150.0/0.01
number
60 00 AUTOMATISM
01 Trip Configuration Binary (16 bits) 0: t I> * Setting 0 / 65535 / 1
1: t I>>
2: t I>>>
3: t I0>
4: t I0>>
5: t I0>>>
6 to 15: reserved
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 29/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
02 Latched Configuration Binary (16 bits) 0: Latch I> * Setting 0 / 65535 / 1
1: Latch I>>
2: Latch I>>>
3: Latch I0>
4: Latch I0>>
5: Latch I0>>>
6 to 15: reserved
03 Blocking 1 Configuration Binary (16 bits) 0: Blocking t I> * Setting 0 / 65535 / 1
1: Blocking t I>>
2: Blocking t I>>>
3: Blocking t I0>
4: Blocking t I0>>
5: Blocking t I0>>>
6 to 15: reserved
61 00 TS SETTINGS
01 Logical input allocation 1 Indexed String 0 0: nothing * Setting 0/7/1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: CB failure
5 5: External input 1
6 6: External input 2
7 7: Logic blocking
02 Logical input allocation 2 Indexed String 0 0: nothing * Setting 0/7/1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: CB failure
5 5: External input 1
6 6: External input 2
7 7: Logic blocking
P12x/EN CT/F75 Communications
Courier Database
Page 30/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
62 00 TC SETTINGS
01 GENERAL TRIP Binary (3 bits) 000 * Setting 0/7/1
02 I> Binary (3 bits) 000 * Setting 0/7/1
03 tI> Binary (3 bits) 000 * Setting 0/7/1
04 I>> Binary (3 bits) 000 * Setting 0/7/1
05 t I>> Binary (3 bits) 000 * Setting 0/7/1
06 I>>> Binary (3 bits) 000 * Setting 0/7/1
07 t I>>> Binary (3 bits) 000 * Setting 0/7/1
08 I0> Binary (3 bits) 000 * Setting 0/7/1
09 t I0> Binary (3 bits) 000 * Setting 0/7/1
0A I0>> Binary (3 bits) 000 * Setting 0/7/1
0B t I0>> Binary (3 bits) 000 * Setting 0/7/1
0C I0>>> Binary (3 bits) 000 * Setting 0/7/1
0D t I0>>> Binary (3 bits) 000 * Setting 0/7/1
15 Reclosing Binary (3 bits) 000 * Setting 0/7/1
1D TC lock setting Binary (3 bits) 000 * Setting 0/7/1
bit 0 to 2 =1: TC Locked
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 31/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
63 00 LEDS SETTINGS
01 Led 5 Binary (16 bits) 0: I> Setting 0/65535/1
1: t I>
2: I>> *
3: t I>>
4: I>>>
5: t I>>>
6: I0>
7: t I0>
8: I0>>
9: t I0>>
10: I0>>>
11: t I0>>>
12 to 15: Reserved
02 Led 6 Binary (16 bits) 0: I> Setting 0/65535/1
1: t I>
2: I>>
3: t I>>
4: I>>> *
5: t I>>>
6: I0>
7: t I0>
8: I0>>
9: t I0>>
10: I0>>>
11: t I0>>>
12 to 15: Reserved
P12x/EN CT/F75 Communications
Courier Database
Page 32/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
03 Led 7 Binary (16 bits) 0: I> Setting 0/65535/1
1: t I>
2: I>>
3: t I>>
4: I>>>
5: t I>>> *
6: I0>
7: t I0>
8: I0>>
9: t I0>>
10: I0>>>
11: t I0>>>
12 to 15: Reserved
04 Led 8 Binary (16 bits) 0: I> Setting 0/65535/1
1: t I>
2: I>>
3: t I>>
4: I>>>
5: t I>>>
6: I0> *
7: t I0>
8: I0>>
9: t I0>>
10: I0>>>
11: t I0>>>
12 to 15: Reserved
BF 00 COMM SYSTEM DATA
03 Setting Transfert
04 Reset Demand Timers NOT IMPLEMENTED
05 Reset Event Report NOT IMPLEMENTED
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 33/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
00 00 SYSTEM DATA
01 Language Ver>: Indexed String 0 Lang1 (French) Setting 0/3/1
1 Lang2 (English)*
2 Lang3 (German)
3 Lang4 (Spanish)
02 Password ASCII Password (4 bytes) AAAA Setting 32/127/1
03 Fnlinks:
NOT IMPLEMENTED
04 Description ASCII Text (6 bytes) “ P123 ”* Setting 32/127/1
05 Plant Reference ASCII Text (4 bytes) “ Pref ” Setting 32/127/1
06 Model Number ASCII Text (16 bytes) “ Model Number ” Data
07 Firmware Number ASCII Text (16 bytes) “ Firmware Number ” Data
08 Serial Number ASCII Text (16 bytes) “ Serial Number ” Data
09 Frequency Unsigned Integer (2 bytes) XXXX Hz Setting 50/60/10
0A Communication Level Unsigned Integer (2 bytes) 1 Data
0B Address Unsigned Integer (2 bytes) 1* Setting 1/255/1
0C Plant Status Word:
NOT IMPLEMENTED
0D Control Status Word:
NOT IMPLEMENTED
0E Setting Group Unsigned Integer Data
0F Load shed Stage:
NOT IMPLEMENTED
P12x/EN CT/F75 Communications
Courier Database
Page 34/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
10 Circuit Breaker Control Indexed String 0*: No operation Setting 0/2/1
1: Trip
2: Close
11 Software Reference ASCII Text (16 characters) Data
12-1F Unused, reserved
20 Logic Input Status Binary flag (5 bits) 0: log input 1 Data
1: log input 2
2: log input 3
3: log input 4
4: log input 5
21 Relay Output Status Binary flag (9 bits) 0: relay 1 (trip) Data
1: relay 2
2: relay 3
3: relay 4
4: watchdog relay
5: relay 5
6: relay 6
7: relay 7
8: relay 8
22 Alarm Binary flag (16 bits) 0: Ana output err Data
1: Comm err
2: Eeprom err data
3: Ct error
4: Clock error
5: Eeprom err calib
6: Ram error
7: Battery error
8: reserved
9: Default settings
10 to 15: reserved
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 35/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
23 Pseudo Logic Input Binary flag (16 bits) 0: I> Data
Status group 1 1: I>>
2: I>>>
3: I0>
4: I0>>
5: I0>>>
6: t I>
7: t I>>
8: t I>>>
9: t I0>
10: t I0>>
11: t I0>>>
12: Thermal Alarm
13: Therm. Overload
14: t I<
15: I<
24 Pseudo Logic Input Binary flag (16 bits) 0: Broken Conductor Data
Status group 2 1: t Aux 1
2: t Aux 2
3: Breaker Fail.
4: Iinv >
5: t Iinv>
6: Open operating time
7: Trip operation Nb
8: SA 2 n
9: SW Trip Circuit
10: Close operating time
11: Successful autoreclose
12: Locked autorecloser
13: Autorecloser conf. fail
14: Iinv>>
15: t Iinv>>
P12x/EN CT/F75 Communications
Courier Database
Page 36/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
25 Pseudo Logic Input Binary flag (16 bits) 0: t Aux 3 Data
Status group 3 1: t Aux 4
2: t Reset I>
3: t Reset I>>
4: t Reset I0>
5: t Reset I0>>
6: t Reset I2>
7: t BF
8: t SOTF
9: Final Trip
10: Autoreclos. in progress
11 à 15: reserved
01 00 USER CONTROL
01 Remote control 1 Binary flag (16 bits) 0: Unlock trip cont.* Setting 0/65535/1
1: Ack first alarm
2: Ack all alarms
3: TRIP
4: CLOSE
5: Setting Change
6: Th. State Reset
7: RMS aver&max Reset
8: Dist. Rec. Trig
9: Maintenance Start
10: Recloser timer Reset
11: Recloser Reset
12: Reserved
13: Reserved
14: Reserved
15: SRAM def . ack
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 37/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
02 Remote control 2 Binary flag (9 bits) 0: Relay 0: TRIP* Setting 0/511/1
1: Relay 1
2: Relay 2
3: Relay 3
4: Watchdog Relay
5: Relay 4
6: Relay 5
7: Relay 6
8: Relay 7
P12x/EN CT/F75 Communications
Courier Database
Page 38/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
03 Remote control 3 Binary flag (6 bits) 0: Reset I0 Harmonic Setting 0/63/1
1: Reserved
2: Reserved
3: Maintenance stop
4: Reset rolling averages
5: Reset sub-period
average peaks.
02 00 VIEW RECORDS
01 Record number Unsigned Integer (2 bytes) 5* Setting 1/5/1
02 Occur date Unsigned Integer (2 bytes)
03 Active set group Unsigned Integer (2 bytes)
04 Phase in fault ASCII Text
05 Fault Id ASCII Text
06 Magnitude Courier floating point
number
07 Ia magnitude Courier floating point
number
08 Ib magnitude Courier floating point
number
09 Ic magnitude Courier floating point
number
0A In magnitude Courier floating point
number
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 39/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
03 00 MEASUREMENTS
01 IA RMS Courier floating point Data
number
02 IB RMS Courier floating point Data
number
03 IC RMS Courier floating point Data
number
04 I0 RMS Courier floating point Data
number
05 Idirect Courier floating point Data
number
06 IINV Courier floating point Data
number
07 Ratio Idir / Iinv Courier floating point Data
number
08 THERMAL STATE (Rst) Unsigned Integer (2 bytes) Data
(%)
09 FREQUENCY Courier floating point Data
number
0A RST RMS MAX &
AVERAGE
0B MAX RMS IA Courier floating point Data
number
0C MAX RMS IB Courier floating point Data
number
0D MAX RMS IC Courier floating point Data
number
P12x/EN CT/F75 Communications
Courier Database
Page 40/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
0E IA RMS AVERAGE Courier floating point Data
number
0F IB RMS AVERAGE Courier floating point Data
number
10 IC RMS AVERAGE Courier floating point Data
number
11 IN – Fn (Rst) Courier floating point Data
number
20 RST Sub-period
average Peaks
21 IA RMS Sub-period Courier floating point Data
average Peak number
22 IB RMS Sub-period Courier floating point Data
average Peak number
23 IC RMS Sub-period Courier floating point Data
average Peak number
24 RST Rolling Averages
25 IA RMS Rolling Average Courier floating point Data
number
26 IB RMS Rolling Average Courier floating point Data
number
27 IC RMS Rolling Average Courier floating point Data
number
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 41/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
04 00 RECLOSER
STATISTICS (Rst)
01 TOTAL CYCLE Unsigned Integer (2 bytes) Data
NUMBER
02 CYCLE 1 NUMBER Unsigned Integer (2 bytes) Data
03 CYCLE 2 NUMBER Unsigned Integer (2 bytes) Data
04 CYCLE 3 NUMBER Unsigned Integer (2 bytes) Data
05 CYCLE 4 NUMBER Unsigned Integer (2 bytes) Data
06 DEFINITIVE TRIP Unsigned Integer (2 bytes) Data
NUMBER
07 RECLOSE ORDER Unsigned Integer (2 bytes) Data
NUMBER
05 00 PROCESS: in versions >
06 00 SW MONITORING
01 RST SAn Ix
02 SAn IA Courier floating point Data
number
03 SAn IB Courier floating point Data
number
04 SAn IC Courier floating point Data
number
05 SW operation nb (Rst) Unsigned Integer (2 bytes) Data
06 SW operation time Courier floating point 0.0 s Data
number
07 SW Closing time Courier floating point Data
number
P12x/EN CT/F75 Communications
Courier Database
Page 42/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
08 00 TIME:
01 Date/Time IEC870 Time & Date Data
02 Date Format (IEC/no) Indexed String 0: Private * Setting 0 (Private) / 1
1: IEC (IEC)
0D 00 GENERAL SETTING
01 Phase Rotation sense Indexed String 0: Direct (A/B/C) * Setting 0 (A/B/C) / 1
1: Inverse (A/C/B) (A/C/B)
0E 00 CT RATIOS
01 Phase CT Primary Unsigned Integer (2 bytes) 1000 * Setting 1/50000/1
02 Phase CT Secondary Unsigned Integer (2 bytes) 1* Setting 1/5/4
03 Neutral CT Primary Unsigned Integer (2 bytes) 1000 * Setting 1/50000/1
04 Neutral CT Secondary Unsigned Integer (2 bytes) 1* Setting 1/5/4
0F 00 SETTING GROUPS
01 Setting group toggle Indexed String 0: Edge * Setting 0 (Edge) / 1
1: Level (Level)
02 Select setting group Unsigned Integer (2 bytes) 1* 0F01=0 Setting 1/2
03 Group 1 visible Indexed String 0: YES * Setting 0 (YES) /
1: NO 1 (NO)
04 Group 2 visible Indexed String 0: YES Setting 0 (YES) /
1: NO * 1 (NO)
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 43/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
Protection Group n° 1
20 00 PHASE
OVERCURRENT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I> Courier floating point 0.1 In * 2002=1 Setting 0.1/25.0/0.1
number
04 Temporisation Type I> Indexed String 0 0: definite time * 2002=1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
05 Curve type I> Indexed String 0 STI (CEI) * 2004=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
06 TMS I> Courier floating point 0.025 * 2004=1 Setting 0.025/1.5/0.025
number
07 K I> Courier floating point 0.1 * 2004=2 Setting 0.1/10.0/0.005
number
08 Tempo I> Courier floating point 0.01 s * 2004=0 Setting 0 /150.0/0.01
number
09 Tempo reset type I> Indexed String 0: definite time 2004=1 & Setting 0/1
1: inverse time 2005>= 5 &
2005 <=9
P12x/EN CT/F75 Communications
Courier Database
Page 44/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
0A RTMS I> Courier floating point 0.025 2009 = 1 Setting 0.025/3.2/0.025
number
0B T RESET I> Courier floating point 0.04 2009 = 0 or Setting 0/600.0/0.01
number 2004 =0 or
2004 =2
or (2004=1 &
2005 < 5 &
2005 > 9)
0C-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I>> Courier floating point 0.50 In * 2011=1 Setting 0.5/40.0/0.05
number
13 Temporisation Type I>> Indexed String 0 0: definite time * 2011=1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
14 Curve type I>> Indexed String 0 STI (CEI) * 2013=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
15 TMS I>> Courier floating point 0.025 * 2013=1 Setting 0.025/1.5/0.025
number
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 45/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
16 K I>> Courier floating point 0.1 * 2013=2 Setting 0.1/10.0/0.005
number
17 Tempo I>> Courier floating point 0.01 s * 2013=0 Setting 0 /150/0.01
number
18 Tempo reset type I>> Indexed String 0: definite time 2013=1 & Setting 0/1
1: inverse time 2014>= 5 &
2014 <=9
19 RTMS I>> Courier floating point 0.025 2018 = 1 Setting 0.025/3.2/0.025
number
1A T RESET I>> Courier floating point 0.04 2018 = 0 or Setting 0/600.0/0.01
number 2013 = 0 or
2013 =2
or (2013=1 &
2014 < 5 &
2014 > 9)
1B-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I>>> Courier floating point 0.50 In * 2021=1 Setting 0.5/40.0/0.05
number
23 Tempo I>>> Courier floating point 0.01 s * 2021=1 Setting 0 /150/0.01
number
24 Sample I>>> Binary (1 bit) 0 Disabled * / Enabled 2021=1 Setting 0/1/1
P12x/EN CT/F75 Communications
Courier Database
Page 46/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
21 00 EARTH FAULT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I0> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I0> Courier floating point 0.01 I0n* 2102=1 Setting 0.01/1.0/0.005
number or 0.002 I0n* if great or 0.1/25.0/0.01 if
sensivity normal sensitivity
or 0.002/1.0/0.001
if great sensivity
04 Tempo Type I0> Indexed String 0 0: definite time * 2102=1 Setting 0/3/1
1 1: inverse time
2 2: RI curve
3 3: Laborelec curves
05 Curve Type I0> Indexed String 0 STI (CEI) * 2104=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
06 Curve Type 2 Indexed String 0 Curve type 1 * 2104=3 Setting 0/2/1
(Laborelec) I0> 1 Curve type 2
2 Curve type 3
07 TMS I0> Courier floating point 0.025 * 2104=1 Setting 0.025/1.5/0.025
number
08 K I0> Courier floating point 0.1 * 2104=2 Setting 0.1/10.0/0.005
number
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 47/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
09 Tempo I0> Courier floating point 0.01 s * 2104=0 Setting 0 /150.0/0.01
number
0A Tempo reset Type I0> Indexed String 0: definite time 2104=1 & Setting 0/1
1: inverse time 2105>= 5 &
2105 <=9
0B RTMS I0> Courier floating point 0.025 210A = 1 Setting 0.025/3.2/0.025
number
0C T RESET I0> Courier floating point 0.04 210A = 0 or Setting 0/600.0/0.01
number 2104 = 0 or
2104 =2
or 2104 =3
or (2104=1 &
2105 < 5 &
2105 > 9)
0D-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I0>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I0>> Courier floating point I0n* 2111=1 Setting 0.01/8.0/0.005
number or 0.50 I0n* if normal or 0.50/40.0/0.01
sensitivity if normal
or 0.002 I0n* if great sensitivity
sensivity or 0.002/1.0/0.001
if great sensivity
13 Tempo Type I0>> Indexed String 0 0: definite time * 2111=1 Setting 0/3/1
1 1: inverse time
2 2: RI curve
3 3: Laborelec curves
P12x/EN CT/F75 Communications
Courier Database
Page 48/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
14 Curve Type I0>> Indexed String 0 STI (CEI) * 2113=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
15 Curve Type 2 Indexed String 0 Curve type 1 * 2113=3 Setting 0/2/1
(Laborelec) I0>> 1 Curve type 2
2 Curve type 3
16 TMS I0>> Courier floating point 0.025 * 2113=1 Setting 0.025/1.5/0.025
number
17 K I0>> Courier floating point 0.1 * 2113=2 Setting 0.1/10.0/0.005
number
18 Tempo I0>> Courier floating point 0.01 s * 2113=0 Setting 0 /150.0/0.01
number
19 Tempo reset Type I0>> Indexed String 0: definite time 2113=1 & Setting 0/1
1: inverse time 2114>= 5 &
2114 <=9
1A RTMS I0>> Courier floating point 0.025 2119 = 1 Setting 0.025/3.2/0.025
number
1B T RESET I0>> Courier floating point 0.04 2119 = 0 or Setting 0/600.0/0.01
number 2113 = 0 or
2113 =2
or 2113 =3
or (2113=1 &
2114 < 5 &
2114 > 9)
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 49/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
1C-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I0>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I0>>> Courier floating point I0n* 2121=1 Setting 0.01/8.0/0.005
number or 0.50 I0n* if normal or 0.50/40.0/0.01
sensitivity if normal
or 0.002 I0n* if great sensitivity
sensivity or 0.002/1.0/0.001
if great sensivity
23 Tempo I0>>> Courier floating point 0.01 s * 2121=1 Setting 0 /150.0/0.01
number
24 Sample I0>>> Binary (1 bit) 0 Disabled * / Enabled 2121=1 Setting 0/1/1
22 00 THERMAL OVERLOAD
01 Ith> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold Ith> Courier floating point 0.10 Ith* 2201=1 Setting 0.01/3.2/0.01
number
03 K Ith> Courier floating point 1.05 * 2201=1 Setting 1.0/1.50/0.01 In
number
04 θ TRIP Unsigned Integer (2 bytes) 100 % * 2201=1 Setting 50 / 200/ 1 %
05 θ ALARM ? Binary (1 bit) 0 Disabled * / Enabled 2201=1 Setting 0/1/1
06 θ ALARM Unsigned Integer (2 bytes) 90 % * 2205 =1 Setting 50 / 200/ 1 %
07 Thermal constant Unsigned Integer (2 bytes) 1* 2201=1 Setting 1/ 200 / 1 mn
23 00 MIN I<
01 I< Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold I< Unsigned Integer (2 bytes) 20 %In * 2301=1 Setting 2 / 100 / 1 %In
03 Tempo I < Courier floating point 0.01 s * 2301=1 Setting 0 /150.0/0.01
number
P12x/EN CT/F75 Communications
Courier Database
Page 50/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
24 00 NEGATIVE CURRENT
01 Iinv> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold Iinv> Courier floating point 0.1 In * 2401 = 1 Setting 0.1/40.0/0.01 In
number
03 Temporisation Type Indexed String 0 0: definite time * 2401 = 1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
04 Curve type Indexed String 0 STI (CEI) * 2403 = 1 Setting 0/9/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
05 TMS Courier floating point 0.025 * 2403=1 Setting 0.025/1.5/0.025
number
06 K (RI) Courier floating point 0.1 * 2403=2 Setting 0.1/10.0/0.005
number
07 Tempo Iinv> Courier floating point 0.01 s * 2403=0 Setting 0 /150.0/1.0
number
08 Reset tempo type Indexed String 0: definite time 2403=1 & Setting 0/1/1
1: inverse time 2404>= 5 &
2404 <=9
09 RTMS Courier floating point 0.025 * 2408 = 1 Setting 0.025/3.2/0.025
number
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 51/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
0A T RESET Courier floating point 0.04 * 2408 = 0 Setting 0.04/100/0.01
number or 2403 =2
or (2403=1 &
2404 < 5 &
2404 > 9)
10 Iinv>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
11 Threshold Iinv>> Courier floating point 0.1 In * 2410 = 1 Setting 0.1/40.0/0.01 In
number
12 Tempo Iinv>> Courier floating point 0.01 s * 2410 = 1 Setting 0 /150.0/1.0
number
25 00 AUTORECLOSER
01 Autorecloser Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 State circuit breaker Binary (1 bit) Disabled * / Enabled 2501 = 1 Setting 0/1/1
03 Control window Courier floating point 0.01 s * 2502 = 1 Setting 0.01 / 600.00 /
number 0.01 s
04 External blocking Binary (1 bit) Disabled * / Enabled 2501 = 1 Setting 0/1/1
07 Temporisation cycle 1 Courier floating point 0.05 s * 2501 = 1 Setting 0.05 / 300.00 /
number 0.01 s
08 Temporisation cycle 2 Courier floating point 0.05 s * 2501 = 1 Setting 0.05 / 300.00 /
number 0.01 s
09 Temporisation cycle 3 Courier floating point 0.05 s * 2501 = 1 Setting 0.05 / 600.00 /
number 0.01 s
0A Temporisation cycle 4 Courier floating point 0.05 s * 2501 = 1 Setting 0.05 / 600.00 /
number 0.01 s
0B Reclaim TIME Courier floating point 0.02 s * 2501 = 1 Setting 0.02 / 600.00 /
number 0.01 s
0C Inhibition time Courier floating point 0.02 s * 2501 = 1 Setting 0.02 / 600.00 /
number 0.01 s
P12x/EN CT/F75 Communications
Courier Database
Page 52/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
0D Number of short circuit Unsigned Integer (2 bytes) 0* 2501 = 1 Setting 0/4/1
cycle
0E Number of earth fault Unsigned Integer (2 bytes) 0* 2501 = 1 Setting 0/4/1
cycle
0F Cycles tI> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4
bit group
10 Cycles tI>> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4
bit group
11 Cycles tI>>> Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4
configuration bit group
12 Cycles tI0> configuration Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4
bit group
13 Cycles tI0>> Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4
configuration bit group
14 Cycles tI0>>> Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4
configuration bit group
15 Cycles tAux1> Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4
configuration bit group
16 Cycles tAux2> Unsigned Integer (2 bytes) 0x1111 * 2501 = 1 Setting 0/2/1 on each 4
configuration bit group
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 53/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
Protection Group n° 2
40 00 PHASE
OVERCURRENT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I> Courier floating point 0.1 In * 4002=1 Setting 0.1/25.0/0.1
number
04 Tempo Type I> Indexed String 0 0: definite time * 4002=1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
05 Curve Type I> Indexed String 0 STI (CEI) * 4004=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
06 TMS I> Courier floating point 0.025 * 4004=1 Setting 0.025/1.5/0.025
number
07 K I> Courier floating point 0.1 * 4004=2 Setting 0.1/10.0/0.005
number
08 Tempo I> Courier floating point 0.01 s * 4004=0 Setting 0.01/150.0/1.0
number
09 Reset tempo type I> Indexed String 0: definite time 4004=1 & Setting 0/1
1: inverse time 4005>= 5 &
4005 <=9
P12x/EN CT/F75 Communications
Courier Database
Page 54/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
0A RTMS I> Courier floating point 0.025 4009 = 1 Setting 0.025/3.2/0.025
number
0B T RESET I> Courier floating point 0.04 4009 = 0 Setting 0/600.0/0.01
number or 4004 =0
or 4004 =2
or (4004=1 &
4005 < 5 &
4005 > 9)
0C-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I>> Courier floating point 0.50 In * 4011=1 Setting 0.5/40.0/0.05
number
13 Tempo Type I>> Indexed String 0 0: definite time * 4011=1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
14 Curve Type I>> Indexed String 0 STI (CEI) * 4013=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
15 TMS I>> Courier floating point 0.025 * 4013=1 Setting 0.025/1.5/0.025
number
16 K I>> Courier floating point 0.1 * 4013=2 Setting 0.1/10.0/0.005
number
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 55/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
17 Tempo I>> Courier floating point 0.01 s * 4013=0 Setting 0 /150/0.01
number
18 Reset tempo type I>> Indexed String 0: definite time 4013=1 & Setting 0/1
1: inverse time 4014>= 5 &
4014 <=9
19 RTMS I>> Courier floating point 0.025 4018 = 1 Setting 0.025/3.2/0.025
number
1A T RESET I>> Courier floating point 0.04 4018 = 0 Setting 0/600.0/0.01
number or 4013 =0
or 4013 =2
or (4013=1 &
4014 < 5 &
4014 > 9)
1B-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I>>> Courier floating point 0.50 In * 4021=1 Setting 0.5/40.0/0.05
number
23 Tempo I>>> Courier floating point 0.01 s * 4021=1 Setting 0 /150/0.01
number
24 Sample I>>> Binary (1 bit) 0 Disabled * / Enabled 4021=1 Setting 0/1/1
P12x/EN CT/F75 Communications
Courier Database
Page 56/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
41 00 EARTH FAULT
01 Stage 1 Overcurrent (Sub Heading)
02 Max I0> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold I0> Courier floating point 0.01 I0n* 4102=1 Setting 0.01/1.0/0.005
number or 0.002 I0n* if great or 0.1/25.0/0.01if
sensivity normal sensitivity
or 0.002/1.0/0.001
if great sensivity
04 Temporisation Type I0> Indexed String 0 0: definite time * 4102=1 Setting 0/3/1
1 1: inverse time
2 2: RI curve
3 3: Laborelec curve
05 Curve type I0> Indexed String 0 STI (CEI) * 4104=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
06 Curve Type 2 Indexed String 0 Curve type 1 * 4104=3 Setting 0/2/1
(Laborelec) I0> 1 Curve type 2
2 Curve type 3
07 TMS I0> Courier floating point 0.025 * 4104=1 Setting 0.025/1.5/0.025
number
08 K I0> Courier floating point 0.1 * 4104=2 Setting 0.1/10.0/0.005
number
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 57/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
09 Tempo I0> Courier floating point 0.01 s * 4104=0 Setting 0 /150.0/0.01
number
0A Tempo reset Type I0> Indexed String 0: definite time 4104=1 & Setting 0/1
1: inverse time 4105>= 5 &
4105 <=9
0B RTMS I0> Courier floating point 0.025 4109 = 1 Setting 0.025/3.2/0.025
number
0C T RESET I0> Courier floating point 0.04 4109 = 0 Setting 0/600.0/0.01
number or 4104 =0
or 4104 =2
or 4104 =3
or (4104=1 &
4105 < 5 &
4105 > 9)
0D-0F Reserved
10 Stage 2 Overcurrent (Sub Heading)
11 Max I0>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold I0>> Courier floating point I0n* 4111=1 Setting 0.01/8.0/0.005
number or 0.50 I0n* if normal or 0.50/40.0/0.01
sensitivity if normal
or 0.002 I0n* if great sensitivity
sensivity or 0.002/1.0/0.001
if great sensivity
13 Temporisation Type Indexed String 0 0: definite time * 4111=1 Setting 0/3/1
I0>> 1 1: inverse time
2 2: RI curve
3 3: Laborelec curve
P12x/EN CT/F75 Communications
Courier Database
Page 58/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
14 Curve type I0>> Indexed String 0 STI (CEI) * 4113=1 Setting 0/10/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
10 RC (CEI)
15 Curve Type 2 Indexed String 0 Curve type 1 * 4113=3 Setting 0/2/1
(Laborelec) I0>> 1 Curve type 2
2 Curve type 3
16 TMS I0>> Courier floating point 0.025 * 4113=1 Setting 0.025/1.5/0.025
number
17 K I0>> Courier floating point 0.1 * 4113=2 Setting 0.1/10.0/0.005
number
18 Tempo I0>> Courier floating point 0.01 s * 4113=0 Setting 0 /150.0/0.01
number
19 Tempo reset Type I0>> Indexed String 0: definite time 4113=1 & Setting 0/1
1: inverse time 4114 >= 5 &
4114 <=9
1A RTMS I0>> Courier floating point 0.025 4119 = 1 Setting 0.025/3.2/0.025
number
1B T RESET I0>> Courier floating point 0.04 4119 = 0 Setting 0/600.0/0.01
number or 4113 =0
or 4113 =2
or 4113 =3
or (4113=1 &
4114 < 5 &
4114 > 9)
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 59/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
1C-1F Reserved
20 Stage 3 Overcurrent (Sub Heading)
21 Max I0>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold I0>>> Courier floating point I0n* 4121=1 Setting 0.01/8.0/0.005
number or 0.50 I0n* if normal or 0.50/40.0/0.01
sensitivity if normal
or 0.002 I0n* if great sensitivity
sensivity or 0.002/1.0/0.001
if great sensivity
23 Tempo I0>>> Courier floating point 0.01 s * 4121=1 Setting 0 /150.0/0.01
number
24 Sample I0>>> Binary (1 bit) 0 Disabled * / Enabled 4121=1 Setting 0/1/1
42 00 THERMAL OVERLOAD
01 Ith> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold Ith> Courier floating point 0.10 Ith* 4201=1 Setting 0.01/3.2/0.01
number
03 K Ith> Courier floating point 1.05 * 4201=1 Setting 1.0/1.50/0.01 In
number
04 θ TRIP Unsigned Integer (2 bytes) 100 % * 4201=1 Setting 50 / 200/ 1 %
05 θ ALARM ? Binary (1 bit) 0 Disabled * / Enabled 4201=1 Setting 0/1/1
06 θ ALARM Unsigned Integer (2 bytes) 90 % * 4205 =1 Setting 50 / 200/ 1 %
07 Thermal constant Unsigned Integer (2 bytes) 1* 4201=1 Setting 1/ 200 / 1 mn
43 00 MIN I<
01 I< Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold I< Unsigned Integer (2 bytes) 20 %In * 4301=1 Setting 2 / 100 / 1 %In
03 Tempo I < Courier floating point 0.01 s * 4301=1 Setting 0 /150.0/0.01
number
P12x/EN CT/F75 Communications
Courier Database
Page 60/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
44 00 NEGATIVE CURRENT
01 Iinv> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Threshold Iinv> Courier floating point 0.1 In * 4401 = 1 Setting 0.1/40.0/0.01 In
number
03 Temporisation type 0 0: definite time * 4401 = 1 Setting 0/2/1
1 1: inverse time
2 2: RI curve
04 Curve Type Indexed String 0 STI (CEI) * 4401 = 1 Setting 0/9/1
1 SI (CEI)
2 VI (CEI)
3 EI (CEI)
4 LTI (CEI)
5 STI (CO2)
6 MI (ANSI)
7 LTI (CO8)
8 VI (ANSI)
9 EI (ANSI)
05 TMS Courier floating point 0.025 * 4403=1 Setting 0.025/1.5/0.025
number
06 K (RI) Courier floating point 0.1 * 4403=2 Setting 0.1/10.0/0.005
number
07 Tempo Iinv> Courier floating point 0.01 s * 4403=0 Setting 0 /150.0/1.0
number
08 Temporisation reset type Indexed String 0: definite time 4403=1 & Setting 0/1/1
1: inverse time 4404>= 5 &
4404 <=9
09 RTMS Courier floating point 0.025 * 4408 = 1 Setting 0.025/3.2/0.025
number
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 61/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
0A T RESET Courier floating point 0.04 * 4408 = 0 or Setting 0.04/100/0.01
number 4403 =2 or
(4403=1 &
4404 < 5 &
4404 > 9)
10 Iinv>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
11 Threshold Iinv>> Courier floating point 0.1 In * 4410 = 1 Setting 0.1/40.0/0.01 In
number
12 Tempo Iinv>> Courier floating point 0.01 s * 4410 = 1 Setting 0 /150.0/1.0
number
45 00 AUTORECLOSER
01 Autorecloser Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 State circuit breaker Binary (1 bit) Disabled * / Enabled 4501 = 1 Setting 0/1/1
03 Control window Courier floating point 0.01 s * 4502 = 1 Setting 0.01 / 600.00 /
number 0.01 s
04 External blocking Binary (1 bit) Disabled * / Enabled 4501 = 1 Setting 0/1/1
07 Temporisation cycle 1 Courier floating point 0.05 s * 4501 = 1 Setting 0.05 / 300.00 /
number 0.01 s
08 Temporisation cycle 2 Courier floating point 0.05 s * 4501 = 1 Setting 0.05 / 300.00 /
number 0.01 s
09 Temporisation cycle 3 Courier floating point 0.05 s * 4501 = 1 Setting 0.05 / 600.00 /
number 0.01 s
0A Temporisation cycle 4 Courier floating point 0.05 s * 4501 = 1 Setting 0.05 / 600.00 /
number 0.01 s
0B Reclaim TIME Courier floating point 0.02 s * 4501 = 1 Setting 0.02 / 600.00 /
number 0.01 s
0C Inhibition time Courier floating point 0.02 s * 4501 = 1 Setting 0.02 / 600.00 /
number 0.01 s
P12x/EN CT/F75 Communications
Courier Database
Page 62/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
0D Number of short circuit Unsigned Integer (2 bytes) 0* 4501 = 1 Setting 0/4/1
cycle
0E Number of earth fault Unsigned Integer (2 bytes) 0* 4501 = 1 Setting 0/4/1
cycle
0F Cycles tI> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4
bit group
10 Cycles tI>> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4
bit group
11 Cycles tI>>> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4
bit group
12 Cycles tI0> configuration Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4
bit group
13 Cycles tI0>> Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4
configuration bit group
14 Cycles tI0>>> Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4
configuration bit group
15 Cycles tAux1> Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4
configuration bit group
16 Cycles tAux2> Unsigned Integer (2 bytes) 0x1111 * 4501 = 1 Setting 0/2/1 on each 4
configuration bit group
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 63/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
60 00 AUTOMATISM
01 Trip Configuration Binary (15 bits) 1* 0: t I> * Setting 0 / 65535 / 1
1: t I>>
2: t I>>>
3: t I0>
4: t I0>>
5: t I0>>>
6: t I<
7: t Therm
8: Broken Conductor
9: t Aux1
10: t Aux2
11: t I2>
12: t I2>>
13: t Aux3
14: t Aux4
15: reserved
02 Latch Configuration Binary (15 bits) 0* 0: Latch I> Setting 0 / 65535 / 1
1: Latch I>>
2: Latch I>>>
3: Latch I0>
4: Latch I0>>
5: Latch I0>>>
6: Latch I<
7: Latch Therm. Ov.
8: Latch Broken Conductor
9: Latch Aux1
10: Latch Aux2
11: Latch I2>
12: Latch I2>>
13: Latch Aux3
14: Latch Aux
15: reserved
P12x/EN CT/F75 Communications
Courier Database
Page 64/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
03 Blocking 1 Configuration Binary (16 bits) 0* 0: Blocking t I> * Setting 0 / 65535 / 1
1: Blocking t I>>
2: Blocking t I>>>
3: Blocking t I0>
4: Blocking t I0>>
5: Blocking t I0>>>
6: Blocking t I<
7: Blocking t Therm
8: Blocking Broken
Conductor
9: Blocking t Aux1
10: Blocking t Aux2
11: Blocking t I2>
12: Blocking t I2>>
13: Blocking t Aux3
14: Blocking t Aux4
15: reserved
04 Blocking 2 Configuration Binary (16 bits) 0* 0: Blocking t I> * Setting 0 / 65535 / 1
1: Blocking t I>>
2: Blocking t I>>>
3: Blocking t I0>
4: Blocking t I0>>
5: Blocking t I0>>>
6: Blocking t I<
7: Blocking t Therm
8: Blocking Broken
Conductor
9: Blocking t Aux1
10: Blocking t Aux2
11: Blocking t I2>
12: Blocking t I2>>
13: Blocking t Aux3
14: Blocking t Aux4
15: reserved
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 65/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
05 Broken conductor Binary (1 bit) Disabled * / Enabled Setting 0/1/1
detection
06 Tempo tBC Unsigned Integer (2 bytes) 0* 6005 = 1 Setting 0 / 144.0 / 0.01 s
07 Threshold mod Courier floating point 20 % * 6005 = 1 Setting 20 / 100 / 1 %
iinv/idirect in % number
08 Cold load start Binary (1 bit) Disabled * / Enabled Setting 0/1/1
09 Threshold of cold load Binary (8 bits) 0* 6008 = 1 Setting 0 / 255 / 1
start
0A % of cold load start Unsigned Integer (2 bytes) 50 % * 6008 = 1 Setting 100 / 500 / 1
0B Cold load start Tempo Courier floating point 1.0 s * 6008 = 1 Setting 0.1 / 3600.0 / 0.1
number s
0C Breaker failure Binary (1 bit) Disabled * / Enabled Setting 0/1/1
0D I< Threshold for Breaker Courier floating point 10 % * 600C = 1 Setting 2 / 100/ 1 %
failure number
0E Tempo tBF Unsigned Integer (2 bytes) 0.1 s * 600C = 1 Setting 0.03 / 10.0 / 0.01
s
0F Phase instant blocking Binary (1 bit) Disabled * / Enabled 600C = 1 Setting 0 / 1/ 1
10 Earth instant blocking Binary (1 bit) Disabled * / Enabled 600C = 1 Setting 0 / 1/ 1
11 Logic selectivity 1 Binary (4 bits) Setting 0 / 15/ 1
12 Tempo selectivity1 Courier floating point 6011 = 1 Setting 0 / 150.0 / 0.01 s
number
13 Logic selectivity 2 Binary (4 bits) Setting 0 / 15 / 1
14 Tempo selectivity 2 Courier floating point 6013 = 1 Setting 0 / 150.0 / 0.01 s
number
15 Trip Configuration 2/2 Binary (2 bits) 0* 0: Trip SOTF Setting 0/3/1
1: Control TRIP
16 Latch Configuration 2/2 Binary (2 bits) 0* 0: Latch SOTF Setting 0/3/1
1: Reserved
P12x/EN CT/F75 Communications
Courier Database
Page 66/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
61 00 TS SETTINGS
01 Logical input allocation 1 Indexed String 0 0: nothing * Setting 0 / 23 / 1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: CB failure
5 5: External input 1
6 6: External input 2
7 7: Logic blocking 1
8 8: Logic blocking 2
9 9: Disturbance start
10 10: Cold load start
11 11: Log Selectivity 1
12 12: Log Selectivity 2
13 13: Change of group
14 14: Recloser locked
15 15: Thermal reset
16 16: Trip circuit supervision
17 17: external CB failure
18 18: Leds reset
19 19: Maintenance mode
20 20: External input 3
21 21: External input 4
22 22: Manual Close
23 23: Local Mode
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 67/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
02 Logical input allocation 2 Indexed String 0 0: nothing * Setting 0 / 23 / 1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: CB failure
5 5: External input 1
6 6: External input 2
7 7: Logic blocking 1
8 8: Logic blocking 2
9 9: Disturbance start
10 10: Cold load start
11 11: Log Selectivity 1
12 12: Log Selectivity 2
13 13: Change of group
14 14: Recloser locked
15 15: Thermal reset
16 16: Trip circuit supervision
17 17: external CB failure
18 18: Leds reset
19 19: Maintenance mode
20 20: External input 3
21 21: External input 4
22 22: Manual Close
23 23: Local Mode
P12x/EN CT/F75 Communications
Courier Database
Page 68/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
03 Logical input allocation 3 Indexed String 0 0: nothing * Setting 0 / 23 / 1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: CB failure
5 5: External input 1
6 6: External input 2
7 7: Logic blocking 1
8 8: Logic blocking 2
9 9: Disturbance start
10 10: Cold load start
11 11: Log Selectivity 1
12 12: Log Selectivity 2
13 13: Change of group
14 14: Recloser locked
15 15: Thermal reset
16 16: Trip circuit supervision
17 17: external CB failure
18 18: Leds reset
19 19: Maintenance mode
20 20: External input 3
21 21: External input 4
22 22: Manual Close
23 23: Local Mode
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 69/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
04 Logical input allocation 4 Indexed String 0 0: nothing * Setting 0 / 23 / 1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: CB failure
5 5: External input 1
6 6: External input 2
7 7: Logic blocking 1
8 8: Logic blocking 2
9 9: Disturbance start
10 10: Cold load start
11 11: Log Selectivity 1
12 12: Log Selectivity 2
13 13: Change of group
14 14: Recloser locked
15 15: Thermal reset
16 16: Trip circuit supervision
17 17: external CB failure
18 18: Leds reset
19 19: Maintenance mode
20 20: External input 3
21 21: External input 4
22 22: Manual Close
23 23: Local Mode
P12x/EN CT/F75 Communications
Courier Database
Page 70/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
05 Logical input allocation 5 Indexed String 0 0: nothing * Setting 0 / 23 / 1
1 1: delatch
2 2: 52 a
3 3: 52 b
4 4: CB failure
5 5: External input 1
6 6: External input 2
7 7: Logic blocking 1
8 8: Logic blocking 2
9 9: Disturbance start
10 10: Cold load start
11 11: Log Selectivity 1
12 12: Log Selectivity 2
13 13: Change of group
14 14: Recloser locked
15 15: Thermal reset
16 16: Trip circuit supervision
17 17: external CB failure
18 18: Leds reset
19 19: Maintenance mode
20 20: External input 3
21 21: External input 4
22 22: Manual Close
23 23: Local Mode
06 Timer aux 1 Courier floating point number 0* Setting 0 / 200.0 / 0.01
07 Timer aux 2 Courier floating point number 0* Setting 0 / 200.0 / 0.01
08 TS setting (Edge type) Binary (5 bits) Bit 0 to 4 = 0: Rising edge Setting 0 / 31 / 1
Bit 0 to 4 = 1: Falling edge
09 TS voltage Indexed String 0 * = DC Setting 0/1/1
1 = AC
0A Timer aux 3 Courier floating point number 0* Setting 0 / 200.0 / 0.01
0B Timer aux 4 Courier floating point number 0* Setting 0 / 200.0 / 0.01
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 71/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
62 00 TC SETTINGS
01 GENERAL TRIP Binary (7 bits) 0000000 * Setting 0/127/1
02 I> Binary (7 bits) 0000000 * Setting 0/127/1
03 tI> Binary (7 bits) 0000000 * Setting 0/127/1
04 I>> Binary (7 bits) 0000000 * Setting 0/127/1
05 t I>> Binary (7 bits) 0000000 * Setting 0/127/1
06 I>>> Binary (7 bits) 0000000 * Setting 0/127/1
07 t I>>> Binary (7 bits) 0000000 * Setting 0/127/1
08 I0> Binary (7 bits) 0000000 * Setting 0/127/1
09 t I0> Binary (7 bits) 0000000 * Setting 0/127/1
0A I0>> Binary (7 bits) 0000000 * Setting 0/127/1
0B t I0>> Binary (7 bits) 0000000 * Setting 0/127/1
0C I0>>> Binary (7 bits) 0000000 * Setting 0/127/1
0D t I0>>> Binary (7 bits) 0000000 * Setting 0/127/1
0E Broken conductor Binary (7 bits) 0000000 * Setting 0/127/1
0F Breaker failure Binary (7 bits) 0000000 * Setting 0/127/1
10 t I< Binary (7 bits) 0000000 * Setting 0/127/1
11 t Iinv> Binary (7 bits) 0000000 * Setting 0/127/1
12 t Iinv>> Binary (7 bits) 0000000 * Setting 0/127/1
13 Thermal alarm Binary (7 bits) 0000000 * Setting 0/127/1
14 Thermal trip Binary (7 bits) 0000000 * Setting 0/127/1
15 Reclosing Binary (7 bits) 0000000 * Setting 0/127/1
16 tAux 1 Binary (7 bits) 0000000 * Setting 0/127/1
17 tAux 2 Binary (7 bits) 0000000 * Setting 0/127/1
P12x/EN CT/F75 Communications
Courier Database
Page 72/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
18 Breaker alarm Binary (7 bits) 0000000 * Setting 0/127/1
19 Trip circuit alarm Binary (7 bits) 0000000 * Setting 0/127/1
1A Autoreclose in progress Binary (7 bits) 0000000 * Setting 0/127/1
1B Definitive trip Binary (7 bits) 0000000 * Setting 0/127/1
1C TC Active Setting Group Binary (7 bits) 0000000 * Setting 0/127/1
bit 0 to 6 =0: Group 1
bit 0 to 6 =1: Group 2
1D TC lock setting Binary (7 bits) 0000000 * Setting 0/127/1
bit 0 to 6 =1: TC Locked
1E tAux 3 Binary (7 bits) 0000000 * Setting 0/127/1
1F tAux 4 Binary (7 bits) 0000000 * Setting 0/127/1
20 tCOMM1 Binary (7 bits) 0000000 * Setting 0/127/1
21 tCOMM2 Binary (7 bits) 0000000 * Setting 0/127/1
22 tCOMM3 Binary (7 bits) 0000000 * Setting 0/127/1
23 tCOMM4 Binary (7 bits) 0000000 * Setting 0/127/1
24 SOTF Binary (7 bits) 0000000 * Setting 0/127/1
25 CONTROL TRIP Binary (7 bits) 0000000 * Setting 0/127/1
26 CONTROL CLOSE Binary (7 bits) 0000000 * Setting 0/127/1
27 Locked Autorecloser Binary (7 bits) 0000000 * Setting 0/127/1
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 73/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
63 00 LEDS SETTINGS
01 Led 5 Binary (16 bits) 4* 0: I> Setting 0/65535/1
1: t I>
2: I>> *
3: t I>>
4: I>>>
5: t I>>>
6: I0>
7: t I0>
8: I0>>
9: t I0>>
10: I0>>>
11: t I0>>>
12: Thermal Overload
13: t I2>
14: Broken Conductor
15: Breaker Failure
02 Led 6 Binary (16 bits) 16 * 0: I> Setting 0/65535/1
1: t I>
2: I>>
3: t I>>
4: I>>> *
5: t I>>>
6: I0>
7: t I0>
8: I0>>
9: t I0>>
10: I0>>>
11: t I0>>>
12: Thermal Overload
13: t I2>
14: Broken Conductor
15: Breaker Failure
P12x/EN CT/F75 Communications
Courier Database
Page 74/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
03 Led 7 Binary (16 bits) 32 * 0: I> Setting 0/65535/1
1: t I>
2: I>>
3: t I>>
4: I>>>
5: t I>>> *
6: I0>
7: t I0>
8: I0>>
9: t I0>>
10: I0>>>
11: t I0>>>
12: Thermal Overload
13: t I2>
14: Broken Conductor
15: Breaker Failure
04 Led 8 Binary (16 bits) 64 * 0: I> Setting 0/65535/1
1: t I>
2: I>>
3: t I>>
4: I>>>
5: t I>>>
6: I0> *
7: t I0>
8: I0>>
9: t I0>>
10: I0>>>
11: t I0>>>
12: Thermal Overload
13: t I2>
14: Broken Conductor
15: Breaker Failure
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 75/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
05 Led PF5 Binary (9 bits) 0* 0: Input 1 Setting 0/2047/1
1: Input 2
2: Input 3
3: Input 4
4: Input 5
5: Locked Autorecloser
6:Autorecloser in progress
7: t Aux1
8: t Aux2
9: t I2>>
10: SOTF
06 Led PF6 Binary (9 bits) 0* 0: Input 1 Setting 0/2047/1
1: Input 2
2: Input 3
3: Input 4
4: Input 5
5: Locked Autorecloser
6:Autorecloser in progress
7: t Aux1
8: t Aux2
9: t I2>>
10: SOTF
07 Led PF7 Binary (9 bits) 0* 0: Input 1 Setting 0/2047/1
1: Input 2
2: Input 3
3: Input 4
4: Input 5
5: Locked Autorecloser
6:Autorecloser in progress
7: t Aux1
8: t Aux2
9: t I2>>
10: SOTF
P12x/EN CT/F75 Communications
Courier Database
Page 76/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
08 Led PF8 Binary (9 bits) 0* 0: Input 1 Setting 0/2047/1
1: Input 2
2: Input 3
3: Input 4
4: Input 5
5: Locked Autorecloser
6:Autorecloser in progress
7: t Aux1
8: t Aux2
9: t I2>>
10: SOTF
64 00 ALARMS
01 Instant. alarm self-reset Binary (1 bits) Disabled * / Enabled Setting 0/1/1
02 Reset leds on Fault Binary (1 bits) Disabled * / Enabled Setting 0/1/1
03 Battery alarm Binary (1 bits) Disabled * / Enabled Setting 0/1/1
69 00 SW SUPERVISION
01 Trip circuit supervision ? Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 Trip circuit time ? Courier floating point 0.1 s * 6901 = 1 Setting 0.1/10.0/0.05 s
number
03 SW Operating time? Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
04 SW Operating time Courier floating point 0.05 s* 6903 = 1 Setting 0.05/1.0/0.05 s
number
05 SW Operating number? Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
06 SW Closing time ? Courier floating point 0.05 s* 6905 = 1 Setting 0.05/1.0/0.05 s
number
07 SW Closing time Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
08 SW Operating number Unsigned Integer (2 bytes) 0* 6907 = 1 Setting 0/50000/1
09 SA2n? Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 77/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
0A SA2n Courier floating point 0 exp+06 A² * 6909 = 1 Setting 0/4000/1
number (*exp+06)
0B N Unsigned Integer (2 bytes) 1* Setting 1/2/1
0C TRIP t Courier floating point 0.1 s* Setting 0.1/5.0/0.05 s
number
0D CLOSE t Courier floating point 0.1 s* Setting 0.1/5.0/0.05 s
number
6A 00 COMM ORDER LATCH
TIMES
01 t COMM1 Courier floating point 0.1 s* 6220 != 0 Setting 0.1/5.0/0.05 s
number
02 t COMM2 Courier floating point 0.1 s* 6221 != 0 Setting 0.1/5.0/0.05 s
number
03 t COMM3 Courier floating point 0.1 s* 6222 != 0 Setting 0.1/5.0/0.05 s
number
04 t COMM4 Courier floating point 0.1 s* 6223 != 0 Setting 0.1/5.0/0.05 s
number
6B 00 SWITCH ON TO FAULT
01 SOTF function ? Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
02 TManual close Courier floating point 0.1 s* 6B01 = 1 Setting 0/0.50/0.01 s
number
03 Start I>> / I>>> Binary (2 bit) 0 0*: Start I>> 6B01 = 1 Setting 0/3/1
1 1: Start I>>>
P12x/EN CT/F75 Communications
Courier Database
Page 78/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
70 00 RECORDER CONTROL VERSION P122 & P123
01 Start/Trigger recorder Indexed String 0 Stopped Setting 1/2/1
1 Trigerred
2 Running *
02 Recorder Source Indexed String 0 Samples * Data
20 Pretemps Courier floating point 0.1 secondes Setting 0.1/3.0/0.1
number
21 Postemps Courier floating point 0.1 secondes Setting 0.1/3.0/0.1
number
22 Trigger Indexed String 0 On Inst* / On Trig Setting 0/1/1
30 Measurement period Indexed String 0 5* / 10 / 15 / 30 / 60 min Setting 0/4/1
40 Rolling Demands
41 Rolling sub-period Courier floating point 1 min* Setting 1/60/1
number
42 Rolling sub-period Courier floating point 1* Setting 1/24/1
number number
80 00 DISTURBANCE REC
01 Record Number Unsigned integer (1 byte) 0* Setting 0/5/1 (selon
contexte)
02 Trigger Time IEC870 Time & Date dd/mm/yy hh:mm Data
03 Available Channel Bit Binary Flag 11111 Data
Mask Indexed String 0 “ Ia ”
1 “ Ib ”
2 “ Ic ”
3 “ I0 ”
4 “ Inputs/Outputs ”
04 Channel Types Binary Flag 0: digital, 1: 01111 Data
analogue
Communications P12x/EN CT/F75
Courier Database
MiCOM P120/P121/P122/P123 Page 79/170
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
05 Channel Offsets Repeated group of Courier Upload Offsets Data
numbers
06 Scaling Factors Repeated group of Courier Upload Scal. Factors Data
numbers
07-0F NOT IMPLEMENTED –
reserved
10 Record Length Integer (2 bytes) Data
11 Trigger position Integer (2 bytes) Data
12 Time Base Courier floating point Data
number
13 NOT IMPLEMENTED –
reserved
14 Upload Timer Repeated group of Integers Data
15-1F NOT IMPLEMENTED –
reserved
20 Upload Channel 0 Repeated group of Integers Data
21 Upload Channel 1 Repeated group of Integers Data
22 Upload Channel 2 Repeated group of Integers Data
23 Upload Channel 3 Repeated group of Integers Data
24 Upload Channel Repeated group of Data
Inputs/Outputs Integer/Bin. flags
90 00 AUTOMAT. FLT
01 Record number Unsigned Integer (2 bytes) Setting
(automatic)
02 Occur fault date Unsigned Integer (2 bytes) Data
03 Active set group Unsigned Integer (2 bytes) 1 Data
P12x/EN CT/F75 Communications
Courier Database
Page 80/170 MiCOM P120/P121/P122/P123
Values
Col Row Menu Text Data Type Ind Depend Cell Type Min/Max/Step
(*: default)
04 Phase in fault ASCII Text (10 bytes) “ PHASE A ” Data
05 Fault Id ASCII Text (18 bytes) “ I >> ” Data
06 Magnitude Courier floating point 12.34 A Data
number
07 Ia Magnitude Courier floating point 12.34 A Data
number
08 Ib Magnitude Courier floating point 12.34 A Data
number
09 Ic Magnitude Courier floating point 12.34 A Data
number
0A In Magnitude Courier floating point 12.34 A Data
number
BF 00 COMM SYSTEM DATA
01 Dist Record Cntrl Ref Menu Cell (2) 0x7000 Data
02 Dist Record Extract Ref Menu Cell (2) 0x8000 Data
03 Setting Transfert
04 Reset Demand Timers NOT IMPLEMENTED
05 Reset Event Report NOT IMPLEMENTED
Communications P12x/EN CT/F75
MiCOM P120/P121/P122/P123
IEC 60870-5-103
MiCOM P120 - P121 - P122- P123
VERSION V5
Communications P12x/EN CT/F75
IEC 60870-5-103
MiCOM P120/P121/P122/P123 Page 1/170
CONTENTS
1. IEC60870-5-103 INTERFACE 3
1.1 Physical connection and link layer 3
1.2 Initialisation 3
1.3 Time synchronisation (P122 & P123 only) 3
1.4 Spontaneous events (P122 & P123 only) 4
1.5 General interrogation 4
1.6 Cyclic measurements 4
1.7 Commands 4
1.8 Disturbance records (P122 & P123 only) 4
1.9 Blocking of monitor direction 4
2. APPENDIX 1 5
P12x/EN CT/F75 Communications
IEC 60870-5-103
Page 2/170 MiCOM P120/P121/P122/P123
BLANK PAGE
Communications P12x/EN CT/F75
IEC 60870-5-103
MiCOM P120/P121/P122/P123 Page 3/170
1. IEC60870-5-103 INTERFACE
The IEC60870-5-103 interface is a master/slave interface with the relay as the slave device.
This protocol is based on the VDEW communication protocol. The relay conforms to
compatibility level 2, compatibility level 3 is not supported.
The following IEC60870-5-103 facilities are supported by this interface:
• Initialisation (Reset)
• Time Synchronisation
• General Interrogation
• Cyclic Measurements
• General Commands
1.1 Physical connection and link layer
Connection is available for IEC60870-5-103 through the rear RS485 port. It is possible to
select both the relay address and baud rate using the front panel interface. Following a
change, a reset command is required to re-establish communications.
The parameters of the communication are the following:
• Even Parity
• 8 Data bits
• 1 stop bit
• Common Address
• Function Type
• Information number
APPENDIX 1 contains a complete listing of all events produced by the relay. The common
address is used to differentiate in circumstances where the relay produces more events of a
certain type than can be passed using the standardised messages. For example if the relay
produces starts and trips for three stages of overcurrent only two stages can be passed
using the standardised messages.
Using the different common address for two of the overcurrent stages allows each stage to
be indicated. The table in APPENDIX 1 shows the common address as an offset value. The
common address offset will be added to the station address in order to pass these events.
1.5 General interrogation
The GI request can be used to read the status of the relay, the function numbers, information
numbers and common address offsets that will be returned during the GI cycle are indicated
in APPENDIX 1.
1.6 Cyclic measurements
The relay will produce measured values using ASDU 9 on a cyclical basis, this can be read
from the relay using a Class 2 poll (note ADSU 3 is not used).
It should be noted that the measurands transmitted by the relay are sent as a proportion of
either 1.2 or 2.4 times the rated value of the analogue value. The selection of either 1.2 or
2.4 for a particular value is indicated in APPENDIX 1.
1.7 Commands
A list of the supported commands is contained in APPENDIX 1. The relay will respond to
other commands with an ASDU 1, with a cause of transmission (COT) of negative
acknowledgement of a command.
1.8 Disturbance records (P122 & P123 only)
The disturbance records stored by the relay cannot be extracted using the mechanism
defined in the IEC60870-5-103 standard. The relay maintains compatibility with the VDEW
control system by transmitting an ASDU 23 with no disturbance records at the start of every
GI cycle.
1.9 Blocking of monitor direction
The relay does not support a facility to block messages in the Monitor direction.IEC 60870-5-
103 DATABASES
Communications P12x/EN CT/F75
IEC 60870-5-103
MiCOM P120/P121/P122/P123 Page 5/170
2. APPENDIX 1
2.1 Spontaneous messages managed by MiCOM P12x
These messages includes a sub-assembly of events which are generated on the relay,
because some generated events are not registered in VDEW. They are the most priority
messages.
An event is always generated on the rising edge of the information.
Some events can be generated on the rising or lowering edge.
In the list below, events only generated on rising edge will be tagged with a ‘*’.
Two types of ASDU can be generated for events: ASDU 1 (time-tagged message) or ASDU
2 (time-tagged message with relative time).
The following list of processed events is the list with the private messages option active,
for all Overcurrent protection functions, with the associated FUNCTION Type,
INFORMATION NUMBER, ASDU TYPE, CAUSE OF TRANSMISSION and COMMON
ADDRESS OF ASDU (The corresponding numbers with private messages option inactive
are given just below).
FUN <160>: Function type in Public range for Overcurrent Protections (compatible).
FUN <168>: Function type in Private range (Reserved for Overcurrent Protections).
P12x/EN CT/F75 Communications
IEC 60870-5-103
Page 6/170 MiCOM P120/P121/P122/P123
− Local parameter Setting active: FUN<160>;INF <22>; TYP <1>; COT<1>,<ADDR>↑↓ P120 to P123
− Setting Group number 1 active: FUN<160>;INF <23>; TYP <1>; COT<1>,<ADDR>↑↓ P122-P123
− Setting Group number 2 active: FUN<160>;INF <24>; TYP <1>; COT<1>,<ADDR>↑↓ P122-P123
− Start / pick-up I>: FUN<168>;INF <9>; TYP <2>; COT<1>,<ADDR>↑↓ P121 to P123
− Start / pick-up I>>: FUN<168>;INF <10>; TYP <2>; COT<1>,<ADDR>↑↓ P121 to P123
− Start / pick-up I>>>: FUN<168>;INF <11>; TYP <2>; COT<1>,<ADDR>↑↓ P121 to P123
− Start / pick-up IN>: FUN<168>;INF <12>; TYP <2>; COT<1>,<ADDR>↑↓ P120 to P123
P12x/EN CT/F75 Communications
IEC 60870-5-103
Page 8/170 MiCOM P120/P121/P122/P123
− Start / pick-up IN>>: FUN<168>;INF <13>; TYP <2>; COT<1>,<ADDR>↑↓ P120 to P123
− Start / pick-up IN>>>: FUN<168>;INF <14>; TYP <2>; COT<1>,<ADDR>↑↓ P120 to P123
− General Start / pick-up: FUN<160>;INF <84>; TYP <2>; COT<1>,<ADDR>↑↓ P120 to P123
NOTE: The double arrow ↑↓ means that the event generated on event occurrence and another event is generated on event disappearing.
− Local parameter Setting active: FUN<160>;INF <22>; TYP <1>; COT<9>,<ADDR> P120 to P123
− Setting Group number 1 active: FUN<160>;INF <23>; TYP <1>; COT<9>,<ADDR> P122-P123
− Setting Group number 2 active: FUN<160>;INF <24>; TYP <1>; COT<9>,<ADDR> P122-P123
Communications P12x/EN CT/F75
IEC 60870-5-103
MiCOM P120/P121/P122/P123 Page 11/170
− General Start / pick-up: FUN<160>;INF <84>; TYP <2>; COT<9>,<ADDR> P120 to P123
Auto-recloser Indications in monitor direction: Availability
− CB in O/O (« closed ») position: FUN<168>;INF <33>; TYP <1>; COT<9>,<ADDR> P121 to P123
with private option inactive: FUN<160>;INF <140>; TYP <1>; COT<9>,<ADDR>
− CB in F/O (« open ») position: FUN<168>;INF <34>; TYP <1>; COT<9>,<ADDR> P121 to P123
with private option inactive: FUN<160>;INF <141>; TYP <1>; COT<9>,<ADDR>
− LEDs Reset: This command acknowledge all alarms on Front Panel on MiCOM P12x products:
FUN<160>;INF<19>, TYP<20>, COT <20>,<ADDR> P120 to P123
− A message indicating relay start/restart (FUN<160>;INF <5>; TYP <5> COT <5>) P120 to P123
− or a message indicating Reset CU (FUN<160>;INF <5>; TYP <3> COT <4>) P120 to P123
− or a message indicating Reset FCB (FUN<160>;INF <5>; TYP <2> COT <3>) P120 to P123
Each identification message of the relay (ASDU 5) contains the manufacturer name in 8 ASCII characters et 4 free characters containing: « P122 » or
« P123 ».
MiCOM P120/P121/P122/P123
CONTENTS
1. INTRODUCTION 3
1.1 Purpose of this document 3
1.2 DNP V3.00 device Profile 3
1.3 Implementation Table 6
1.4 Point List 8
1.4.1 Binary Input Points 8
1.4.2 Binary Output Status Points and Control Relay Output Blocks 11
1.4.3 Counters 12
1.4.4 Analog Inputs 13
P12x/EN CT/F75 Communications
DNP 3.0 Database
Page 2/170 MiCOM P120/P121/P122/P123
BLANK PAGE
Communications P12x/EN CT/F75
DNP 3.0 Database
MiCOM P120/P121/P122/P123 Page 3/170
1. INTRODUCTION
1.1 Purpose of this document
The purpose of this document is to describe the specific implementation of the Distributed
Network Protocol (DNP) 3.0 within P12x MiCOM relays.
P12x uses the Triangle MicroWorks, Inc. DNP 3.0 Slave Source Code Library Version 2.18.
This document, in conjunction with the DNP 3.0 Basic 4 Document Set, and the DNP Subset
Definitions Document, provides complete information on how to communicate with P12x via
the DNP 3.0 protocol.
This implementation of DNP 3.0 is fully compliant with DNP 3.0 Subset Definition Level 2,
contains many Subset Level 3 features, and contains some functionality even beyond
Subset Level 3.
1.2 DNP V3.00 device Profile
The following table provides a “Device Profile Document” in the standard format defined in
the DNP 3.0 Subset Definitions Document. While it is referred to in the DNP 3.0 Subset
Definitions as a “Document,” it is only a component of a total interoperability guide. This
table, in combination with the following should provide a complete
interoperability/configuration guide for P12x:
• the Point List Tables provided in Section 1.4 (beginning on page 8),
DNP V3.00
DEVICE PROFILE DOCUMENT
(ALSO SEE THE IMPLEMENTATION TABLE IN SECTION 1.3, BEGINNING ON PAGE 6).
Vendor Name: AREVA T&D Antomation & Information
Device Name: SERIAL 20 Platform using the Triangle MicroWorks, Inc. DNP 3.0 Slave
Source Code Library, Version 2.18.
Highest DNP Level Supported: Device Function:
For static (non-change-event) object requests, request qualifier codes 00 and 01 (start-
stop), 07 and 08 (limited quantity), and 17 and 28 (index) are supported in addition to
request qualifier code 06 (no range – or all points).
Static object requests received with qualifiers 00, 01, 06, 07, or 08, will be responded with
qualifiers 00 or 01. Static object requests received with qualifiers 17 or 28 will be
responded with qualifiers 17 or 28.
For change-event object requests, qualifiers 17 or 28 are always responded.
16-bit and 32-bit Analog Change Events with Time may be requested.
The read function code for Object 50 (Time and Date), variation 1, is supported.
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted: 292 Transmitted: 2048
Received 292 Received: 2048
Maximum Data Link Re-tries: Maximum Application Layer Re-tries:
. None
" Fixed at 2 " None
. Configurable . Configurable
P12x/EN CT/F75 Communications
DNP 3.0 Database
Page 4/170 MiCOM P120/P121/P122/P123
DNP V3.00
DEVICE PROFILE DOCUMENT
(ALSO SEE THE IMPLEMENTATION TABLE IN SECTION 1.3, BEGINNING ON PAGE 6).
Requires Data Link Layer Confirmation:
" Never
Always
Sometimes
Configurable
Requires Application Layer Confirmation:
Never
Always
" When reporting Event Data
" When sending multi-fragment responses
Sometimes
Configurable
Timeouts while waiting for:
Others:
Binary input change scanning period: 5ms
Analog input change scanning period: 1s
Sends/Executes Control Operations:
DNP V3.00
DEVICE PROFILE DOCUMENT
(ALSO SEE THE IMPLEMENTATION TABLE IN SECTION 1.3, BEGINNING ON PAGE 6).
Default Counter Object/Variation: Counters Roll Over at:
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Codes Qualifier Function Qualifier
Description (dec)
Number Number Codes (hex) Codes (dec) Codes (hex)
1 0 Binary Input (Variation 0 is used 1 (read) 00, 01 (start-stop)
06 (no range, or all)
to request default variation) 07, 08 (limited qty)
17, 28 (index)
1 1 Binary Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 22 06 (no range, or all) 17, 28 (index –
see note 1) 07, 08 (limited qty) see note 2)
17, 28 (index)
1 2 Binary Input with Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 28 (index
2 0 Binary Input Change (Variation 0 1 (read) 06 (no range, or all)
07, 08 (limited qty)
is used to request default
variation)
2 1(default – Binary Input Change without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
see note 1 for 07, 08 (limited qty)
Time
P120 - P121)
2 2 Binary Input Change with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(only P122- (default – 07, 08 (limited qty)
P123) see note 1)
10 0 Binary Output Status (Variation 0 1 (read) 00, 01 (start-stop)
06 (no range, or all)
is used to request default 07, 08 (limited qty)
variation) 17, 28 (index)
10 2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) 07, 08 (limited qty) see note 2)
17, 28 (index)
12 1 Control Relay Output Block 3 (select) 00, 01 (start-stop) 129 (response) echo of request
4 (operate) 07, 08 (limited qty)
5 (direct op) 17, 28 (index)
6 (dir. op, noack)
20 0 Binary Counter (Variation 0 is 1 (read) 00, 01 (start-stop)
(only P122- 7 (freeze) 06 (no range, or all)
used to request default variation) 8 (freeze noack) 07, 08 (limited qty)
P123)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. Noack)
20 1 32-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(only P122- 7 (freeze) 06 (no range, or all) 17, 28 (index –
P123) 8 (freeze noack) 07, 08 (limited qty) see note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. Noack)
20 2 16-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(only P122- 7 (freeze) 06 (no range, or all) 17, 28 (index –
P123) 8 (freeze noack) 07, 08 (limited qty) see note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. Noack)
20 5 32-Bit Binary Counter without 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(only P122- 7 (freeze) 06 (no range, or all) 17, 28 (index –
Flag 8 (freeze noack) 07, 08 (limited qty) see note 2)
P123)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. Noack)
20 6 16-Bit Binary Counter without 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(only P122- 7 (freeze) 06 (no range, or all) 17, 28 (index –
Flag 8 (freeze noack) 07, 08 (limited qty) see note 2)
P123)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. Noack)
21 0 Frozen Counter (Variation 0 is 1 (read) 00, 01 (start-stop)
(only P122- 06 (no range, or all)
used to request default variation) 07, 08 (limited qty)
P123)
17, 28 (index)
21 1 32-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(only P122- 06 (no range, or all) 17, 28 (index –
P123) 07, 08 (limited qty) see note 2)
17, 28 (index)
Communications P12x/EN CT/F75
DNP 3.0 Database
MiCOM P120/P121/P122/P123 Page 7/170
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Codes Qualifier Function Qualifier
Description (dec)
Number Number Codes (hex) Codes (dec) Codes (hex)
21 2 16-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(only P122- 06 (no range, or all) 17, 28 (index –
P123) 07, 08 (limited qty) see note 2)
17, 28 (index)
21 9 32-Bit Frozen Counter without 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(only P122- 06 (no range, or all) 17, 28 (index –
Flag 07, 08 (limited qty) see note 2)
P123)
17, 28 (index)
21 10 16-Bit Frozen Counter without 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(only P122- 06 (no range, or all) 17, 28 (index –
Flag 07, 08 (limited qty) see note 2)
P123)
17, 28 (index)
30 0 Analog Input (Variation 0 is used 1 (read) 00, 01 (start-stop)
06 (no range, or all)
to request default variation) 07, 08 (limited qty)
17, 28 (index)
30 1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1 07, 08 (limited qty) see note 2)
17, 28 (index)
30 2 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 28 (index)
30 3 32-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 28 (index)
30 4 16-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 28 (index)
32 0 Analog Change Event (Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
0 is used to request default
variation)
32 1 32-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – 07, 08 (limited qty)
without Time
see note 1)
32 2 16-Bit Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty)
without Time
32 3 32-Bit Analog Change Event with 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(only P122- 07, 08 (limited qty)
Time
P123)
32 4 16-Bit Analog Change Event with 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(only P122- 07, 08 (limited qty)
Time
P123)
50 0 Time and Date 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(only P122- 06 (no range, or all) 17, 28 (index –
P123) 07, 08 (limited qty) see note 2)
17, 28 (index)
50 1 Time and Date 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(only P122- (default – 2 (write) 06 (no range, or all) 17, 28 (index –
P123) see note 1) 07 (limited qty=1) see note 2)
08 (limited qty)
17, 28 (index)
52 2 Time Delay Fine 129 (response) 07 (limited qty)
(qty = 1)
60 0 Class 0, 1, 2, and 3 Data 1 (read) 06 (no range, or all)
1.4.2 Binary Output Status Points and Control Relay Output Blocks
The following table lists both the Binary Output Status Points (Object 10) and the Control
Relay Output Blocks (Object 12). Binary Output Status points are not included in class 0
polls.
1.4.3 Counters
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21).
When a freeze function is performed on a Binary Counter point, the frozen value is available
in the corresponding Frozen Counter point.
Binary Counters and Frozen Counters are not included in class 0 polls.
P120 and P121 do not support binary Counters and Frozen Counters.
Binary Counters
Static (Steady-State) Object Number: 20
Change Event Object Number: not supported
Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack)
9 (freeze and clear), 10 (freeze and clear, noack)
Static Variation reported when variation 0 requested: 5 (32-Bit Binary Counter without Flag
Change Event Variation reported when variation 0 requested: none-not supported
Frozen Counters
Static (Steady-State) Object Number: 21
Change Event Object Number: not supported
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 9 (32-Bit Frozen Binary without Flag)
Change Event Variation reported when variation 0 requested: none-not supported
P122 P123
Point Point Name/Description Data type
Index Index
0 0 Max RMS current phase A D1
1 1 Max RMS current phase B D1
2 2 Max RMS current phase C D1
3 3 Average RMS current phase A D1
4 4 Average RMS current phase B D1
5 5 Average RMS current phase C D1
6 6 CB operation number D2
7 7 sa2n ia D3
8 8 sa2n ib D3
9 9 sa2n ic D3
10 Total number of autoreclosure cycle D2
11 Number of cycles 1 D2
12 Number of cycles 2 D2
13 Number of cycles 3 D2
14 Number of cycles 4 D2
15 Definitive Tripping number D2
16 Number of closing order D2
10 17 Rolling demand(average) RMS phase A D1
11 18 Rolling demand(average) RMS phase B D1
12 19 Rolling demand(average) RMS phase C D1
13 20 Maximum RMS phase A (after a new initialization) D1
14 21 Maximum RMS phase B (after a new initialization) D1
15 22 Maximum RMS phase C (after a new initialization) D1
Communications P12x/EN CT/F75
DNP 3.0 Database
MiCOM P120/P121/P122/P123 Page 13/170
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o
Time)
Change Event Scan Rate: The scan rate for analog input change events is fixed at 1s
Scaling Initial
and Units Change Change
P120 P121 P122 P123
Initial (represent Valid Event Event
Point Point Point Point Name/Description
Value ation of Range Dead- Class (1,
Index Index Index Index
32767 – band 2, 3 or
see above) none)
0 0 Active Group 1 32767 1à2 1 1
0 1 1 Magnitude IA 0 40 In 0 to 40 In 0.02 In 3
1 2 2 Magnitude IB 0 40 In 0 to 40 In 0.02 In 3
2 3 3 Magnitude IC 0 40 In 0 to 40 In 0.02 In 3
0 3 4 4 Magnitude IN 0 40 I0n 0 to 40 I0n 0.02 I0n 3
4 5 5 rms IA 0A 327.67A 0 to 3
40000000 2%
A/100
5 6 6 rms IB 0A 327.67A 0 to 3
40000000 2%
A/100
6 7 7 rms IC 0A 327.67A 0 to 3
40000000 2%
A/100
1 7 8 8 rms IN 0A 327.67A 0 to 3
40000000 2%
A/100
9 9 Thermal State 0% 32767% 0 to 65535 10 3
10 10 Frequency 0 327,67 Hz 45Hz to 1Hz 3
65 Hz and
99.99Hz ==
ERROR
11 11 Magnitude I2 0 40 In 0 to 40 In 0.1 In 3
12 12 Magnitude I1 0 40 In 0 to 40 In 0.1 In 3
13 13 Tripping Time 0 327.67s 0 to 10.00s 10 ms 3
14 14 Closing Time 0 327.67s 0 to 10.00s 10 ms 3
15 15 Fault number 0 32767 0 to 65535 1 2
16 16 group 0 32767 1 to 2 each new 2
fault
17 17 phase fault 0 32767 0 to 8 (F1) each new 2
fault
P12x/EN CT/F75 Communications
DNP 3.0 Database
Page 14/170 MiCOM P120/P121/P122/P123
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o
Time)
Change Event Scan Rate: The scan rate for analog input change events is fixed at 1s
Scaling Initial
and Units Change Change
P120 P121 P122 P123
Initial (represent Valid Event Event
Point Point Point Point Name/Description
Value ation of Range Dead- Class (1,
Index Index Index Index
32767 – band 2, 3 or
see above) none)
18 18 origin fault 0 32767 0 to each new 2
16 (P122) fault
17 (P123)
(F2)
19 19 Fault magnitude 0 40 In 0 to 40 In each new 2
fault
20 20 Fault magnitude IA 0 40 In 0 to 40 In each new 2
fault
21 21 Fault magnitude IB 0 40 In 0 to 40 In each new 2
fault
22 22 Fault magnitude IC 0 40 In 0 to 40 In each new 2
fault
23 23 Fault magnitude IN 0 40 I0n 0 to 40 I0n each new 2
fault
Format:
F1:
0: None, 1: Phase A, 2: Phase B, 3: Phase C, 4: Phase AB, 5: Phase AC, 6: Phase BC, 7:
Phase A B C, 8: Terre
F2:
0: Null, 1: Remote trip, 2: thermal overload, 3: tI>, 4: tI>>, 5: tI>>>, 6: tIN>, 7: tIN>>, 8:
tIN>>>, 9: tI<, 10: broken conductor, 11: taux1, 12: taux2, 13: tIinv>, 14: tIinv>>, 15:taux2,
16: taux3(only p123), 17:breaker failure, 18: SOFT (only P123)..
Commissioning and Maintenance P12x/EN CM/F75
MiCOM P120/P121/P122/P123
COMMISSIONING AND
MAINTENANCE GUIDE
Commissioning and Maintenance P12x/EN CM/F75
CONTENTS
4. SETTING CHECK 9
4.1 Settings 9
4.2 Measurements 9
4.2.1 MiCOM P120 9
4.2.2 MiCOM P121, P122 and P123 9
4.3 Phase overcurrent (I> and I>>) 10
4.3.1 Test wiring diagram 10
4.3.2 MiCOM settings 10
4.4 Final checks 14
P12x/EN CM/F75 Commissioning and Maintenance
5. MAINTENANCE 15
5.1 Equipment failure 15
5.1.1 Minor fault 15
5.1.2 Major fault 15
5.2 Method of repair 16
5.2.1 Replacing the active part 16
5.2.2 Replacing the complete relay 16
5.2.3 Changing the battery (MiCOM P122 & P123 only) 17
5.3 Problem solving 17
5.3.1 Password lost or not accepted 17
5.3.2 Communication 18
Commissioning and Maintenance P12x/EN CM/F75
• Extracting the settings applied to the relay using the appropriate setting software
MiCOM S1 (preferred method)
− Test plugs and wires to carry out injections to the CT's secondary (dimension
according to the currents injected).
2.1.3 Communication
For all commissioning tests, the records can be made by using the RS 485 communication
on the rear connector of the MiCOM P120, P121, P122 and P123 relays or for MiCOM P122
and P123 using the RS232 front port.
According to each RS 485 communication protocol (MODBUS, Courier, IEC 60870-5-103,
DNP3).
2.2 Commissioning test sheets
Commissioning test sheets are available in the APPENDIX 2 of the Technical Guide.
The presentation of the Commissioning test sheets follows the description of the tests of this
chapter.
The contents of these Commissioning test sheets enable you to log :
The name of the relay, station and circuit
The characteristics of the MiCOM P120, P121, P122 and P123 relays
The various settings
The results of the protection and automation checks
The result of the test records after commissioning.
Commissioning and Maintenance P12x/EN CM/F75
P1 S1
P2 S2
Other ends
of electrical cables
P0041ENa
Busbar 1 Busbar 2
Circuit Breaker 1 Electrical line Circuit Breaker 2
P121
with CT core
Earthing 1 Earthing 2
P0042ENa
_
P1 S1 + mA
+
_
P2 S2
P0043ENa
OP. PARAMETERS/Inputs
Input MiCOM P12x models
Status cell value
Opto input 1
P120,P121, P122, P123 00001
22-24 Terminals
Opto input 2
P120,P121, P122, P123 00010
26-28 Terminals
Opto input 3
P122, P123 00100
17-19 Terminals
Opto input 4
P123 01000
21-23 Terminals
Opto input 5
P123 10000
25-27 Terminals
The status of the outputs can be viewed using menu OP. PARAMETERS/ Relay Status, an
indicating an close output relay and a 0 indicating a open output relay. When each output
relay is closed one of the characters on the bottom line of the menu display will change to
the value show in the following table to indicate the new state of the inputs.
OP. PARAMETERS/Relay
OUTPUT MiCOM P12x models
Status cell value
RL 1 P120,P121, P122, P123 00000001
RL 2 P120,P121, P122, P123 00000010
RL 3 P120,P121, P122, P123 00000100
RL 4 P120,P121, P122, P123 00001000
RL 5 P122, P123 00010000
RL 6 P122, P123 00100000
RL 7 P123 01000000
RL 8 P123 10000000
4. SETTING CHECK
The setting checks ensure that all of the application-specific relay setting for the particular
installation have been correctly applied to the relay.
Transfer the setting file to the relay using a laptop PC running the appropriate software via
the RS232 front port (MiCOM P122 and P123) or the RS485 rear port (all MiCOM models).
This method is preferred transfer function settings because it is much faster and there is less
margin for error.
If the setting software is not used then enter manually via the relay front panel interface.
The commissioning is following the points below:
− Apply current to input terminals 55-56 or 47-48 and verify the value on the LCD
display.
− Carry forward the results to the Commissioning test sheets (Applied value and relay
value displayed)
4.2.2 MiCOM P121, P122 and P123
− Apply current to input (as per wiring diagram) and verify the values on the LCD
display.
− Carry forward the results to the Commissioning test sheets (Applied values and relay
values displayed).
P12x/EN CM/F75 Commissioning and Maintenance
INJECTION
TEST SET
AUXILIARY +Uaux 33
-Uaux
SUPPLY 34
A 49
1A
50
51
1A
CURRENT
MiCOM
52
53
1A 1A
N
P121
54
41
A 5A
42
43
CURRENT 5A
5A 44
45
5A
N 46
35 Case earth
36 WD Watchdog
29
6 -
TIMER Stop 4
2 RL1 Trip output * 30
12 31
+ RS 485 communication port
10
RL2 Programmable output 32
8 -
P0044ENa
Ie> YES
Ie> 1 In
tIe> DMT or IDMT or RI
tIe> (if DMT) 20 s
Type of curve (if IDMT) IEC VI or IEEE VI
TMS value (if IDMT) 1
K value (if RI) 1
Ie>> YES
Ie>> 12 In
tIe>> 10 s
Commissioning and Maintenance P12x/EN CM/F75
I> YES
I> 1 In
tI> DMT or IDMT or RI
tI> (if DMT) 20 s
Type of curve (if IDMT) IEC VI or IEEE VI
TMS value (if IDMT) 1
K value (if RI) 1
I>> YES
I>> 12 In
IEEE/ANSI curves
RI electromechanical curve
Rectifier curve
Laborelec curve
For other injected current values, compare the values found with the theoretical values
calculated according to the formulae of the curves.
NOTE : Equations of IEC, IEEE/ANSI, RI, RC and Laborelec curves are given
in Chapter "Application Guide" of the present Technical Guide.
Checks :
Display of an alarm message on the front panel LCD.
Alarm LED flashes.
Trip LED on
I> threshold LED on (if programmed).
Trip output closes.
I> threshold output closes (if programmed).
P12x/EN CM/F75 Commissioning and Maintenance
5. MAINTENANCE
5.1 Equipment failure
MiCOM P120, P121, P122 and P123 relays are full digital and self-diagnosing. As soon as
an internal fault is detected, depending on its type (minor or major), an alarm message is
displayed as a priority on the front panel LCD before the fault LED is illuminated (fixed or
flashing) and the watchdog relay is closed (if the fault is a major one).
An equipment failure (major or minor) cannot be acknowledged on the front panel (using the
dedicated tactile button keypad). Only the disappearance of the cause will acknowledge the
fault and hence reset the fault LED.
All tests are performed during relay boot and permanently in the background software task
excepted EEPROM tests performed only when relay boots and on any setting change.
All tests are performed during relay boot and permanently in the background software task
excepted EEPROM tests performed only when relay boots and on any setting change.
5.1.1 Minor fault
Regarded by the MiCOM P120, P121, P122 and P123 relays as a minor fault is a
communication failure. If the communication is in fault, MiCOM P120, P121, P122 and P123
protection and automation modules are not affected. The MiCOM relay is fully operational.
The watchdog relay is energised (35-36 contact open and 36-37 contact closed).
Message :
"COMM.ERROR" : Communication fault
Cause :
Hardware or software failure of the communication module
Action :
Withdraw the active part and return it to the factory for repair.
Alternative : If communication is not used, disable communication in the COMMUNICATION
menu (Communication ? = No).
Message :
"RAM ERROR" : Ram supplied by battery in fault.
"Battery Fail" : Battery in fault.
Cause :
See Section 5.2.3 of this Commissioning and Maintenance Guide.
If the message still remain after restart, return the module to the factory for repair.
5.1.2 Major fault
Major fault for MiCOM P120, P121, P122 and P123 relays are all software and hardware
failures except the communication faults. As soon as this type of failure is detected, the
watchdog (WD) is de-energised (35-36 contact closed and 36-37 contact open) and all
operations are stopped (protection, automation, communication).
P12x/EN CM/F75 Commissioning and Maintenance
• Gently extract the battery from its socket. If necessary, use a small screwdriver.
• Ensure that metal terminals in the battery socket are free from corrosion, grease and
dust.
• The replacement battery should be removed from its packaging and placed into the
battery holder, ensure that the polarity markings on the battery agree with those
adjacent to the socket.
NOTE :
ONLY USE A TYPE 1/2AA LITHIUM BATTERY WITH A NOMINAL VOLTAGE OF 3.6 V.
• Ensure that the battery is securely held in its socket and that the battery terminals are
making good contact with the metal terminals of the socket.
• The battery that has been removed should be disposed of in accordance with the
disposal procedure for Lithium batteries in the country in which the relay is installed.
5.3 Problem solving
5.3.1 Password lost or not accepted
Problem :
Password lost or not accepted
Cause :
MiCOM P120, P121, P122 and P123 relays are supplied with the password set to AAAA.
This password can be changed by the user ( refer OP PARAMETERS menu).
Action :
There is an additional unique recovery password associated to the relay which can be
supplied by the factory or service agent, if given details of its serial number (under the upper
flap of the front panel). With this serial number, contact your AREVA T&D'S Automation &
Information Systems Business local dealer or AREVA T&D'S Automation & Information
Systems Business After Sales Dept.
P12x/EN CM/F75 Commissioning and Maintenance
5.3.2 Communication
5.3.2.1 Values measured locally and remotely
Problem :
The measurements noted remotely and locally (via RS485 communication) differ.
Cause :
The values accessible on the front face via the Measurement menu are refreshed every
second. Those fed back via the communication and accessible by the AREVA T&D'S
Automation & Information Systems Business Setting software generally have skeletal
refreshing frequencies. If the refreshing frequency of the supervision software differs from
that of MiCOM P120, P121, P122 and P123 relays (1s), there may be a difference between
indicated values.
Action:
Adjust the frequency for refreshing the measurements of the supervision software or of the
setting software to 1 second.
5.3.2.2 MiCOM relay no longer responds
Problem :
No response from MiCOM P120, P121, P122 and P123 relays when asked by the
supervision software without any communication fault message.
Cause :
Mainly, this type of problem is linked to an error in the MiCOM P120, P121, P122 and P123
communication parameters.
Action :
Check MiCOM P120, P121, P122 and P123 communication parameters (data rate, parity,
etc.) are in accordance with the supervision settings.
Check MiCOM P120, P121, P122 and P123 network address.
Check that this address is not used by another device connected on the same LAN.
Check that the other devices on the same LAN answer to supervision requests.
5.3.2.3 A remote command is not taken in account
Problem :
The communication between the relay and the PC is correct, but the relay does not accept
any remote command or file downloading.
Cause :
Generally this is due to the fact that the relay is in programming situation. This means that
the password is active.
Action :
Check that the password is not active in the relay since the last 5 minutes.
Connection Diagrams P12x/EN CO/F75
MiCOM P120/P121/P122/P123
Connection Diagrams
Alternative : The earth current input is connected to the sommation of the three phase CTs. The current inputs are connected to 3 phase CTs + a core balanced CT.
P2 P1 P2 P1 P2 P1 37
A A 33 35
S2 S1 S2 S1 Auxiliary + WD Watch dog (4)
B B 36
voltage
}
C C _ 6
S2 S1 34
49 49 4
Programmable tripping
P121 RL1
2
} output
1A 1A
50 50 12
51 51 10
RL2 Programmable output
1A 1A P121 8
}
A only
52 52 16
53 53 RL3 Programmable output
14 }
1A 1A 20
54 54 RL4 18 Programmable output
55 55 }
Connection Diagrams
C B
1A 1A
Phase rotation
56 56
41 P121 41
5A 5A
42 42
43 43
5A 5A P121
only
44 44
MiCOM P120/P121/P122/P123
45 45
5A 5A
46 46
47 47
5A 5A MiCOM
48 48
+ P120/121
Programmable 22
input L1 Case earth connection
24
-
Alternative (P121 only): Connection to 2 phases CTs + a core balanced CT.
{ +
Programmable 26
P2 P1 P2 P1 input L2
28
A -
{
S2 S1 Case earth
B 29
Communication
C 30 cable shield
S2 S1 1 2 29 30 *
49
3 4 31 32
1A 31 _ RS 485
5 6 33 34
50 Port communication
7 8 35 36
51
9 10 37 38 32
1A +
11 12 39 40
}
( : terminating resistor for the
52 13 14 41 42 *
53 last relay to be connected
15 16 43 44 between 30-32)
1A
17 18 45 46
54
42
43 (b) Short terminals break before (c)
Module terminal blocks
5A (c) Long terminals
viewed from rear
44 (d)
45 (with integral case earth link) Pins terminals (pcb type)
48
P0045ENb
Page 1/4
P12x/EN CO/F75
Alternative : The earth current input is connected to the sommation of the three phase CTs. The current inputs are connected to 3 phase CTs + a core balanced CT.
P2 P1 P2 P1 P2 P1 37
A A 33 35
S2 S1 S2 S1 Auxiliary + Watch dog (4)
B B WD 36
}
voltage
_
Page 2/4
C C 6
S2 S1
{ 34
Programmable tripping
49 49 4
RL1 output
2
1A 1A
}
50 50 12
51 51 10
RL2 Programmable output
1A 1A 8
A
}
52 52 16
53 53
P12x/EN CO/F75
+ P122/123
Programmable 22
input L1
24 Case earth connection
-
Alternative : Connection to 2 phases CTs + a core balanced CT.
{ +
Programmable 26
P2 P1 P2 P1 input L2
28
A -
{ +
S2 S1 Case earth Programmable 17
B L3 29
input 19 Communication
C -
S2 S1 1 2 29 30
{ + 30 cable shield
49 Programmable 21 *
3 4 31 32 input L4
1A 23 31 _
5 6 33 34 - RS 485
{ +
50 Programmable 25 Port communication
7 8 35 36
51 input L5
9 10 37 38 27 32
- +
1A
{ }
11 12 39 40 ( : terminating resistor for the
52 13 14 41 42 *
53 P123 only last relay to be connected
15 16 43 44 between 30-32)
1A
17 18 45 46
54
19 20 47 48
42
43 (b) Short terminals break before (c)
Module terminal blocks
5A (c) Long terminals
viewed from rear
44 (d)
45 (with integral case earth link) Pins terminals (pcb type)
48
P0046ENb
Connection Diagrams
MiCOM P120/P121/P122/P123
Connection Diagrams P12x/EN CO/F75
29
30
32 31
shield
RS485 cable
P0253ENa
P12x/EN CO/F75 Connection Diagrams
EARTH
MiCOM P120/P121/P122/P123
CONTENTS
BLANK PAGE
Commissioning Test & Record Sheets P12x/EN RS/F75
Commissioning date :
Engineer :
Substation :
Circuit :
Network nominal frequency:
Serial number :
Rated current In :
Auxiliary voltage Uaux :
Communication protocol :
Language :
Insulation tested ?
Watchdog contacts
With auxiliary supply off Terminals 35 and 36
Measurements
Applied value Relay value
PHASE CT INPUT
Phase A current _______________ A A
Phase B current _______________ A A
Phase C current _______________ A A
EARTH CT INPUT
Earth current _______________ A A
Phase protection test
Theoretical value Relay value
I> threshold _______________ A
I> threshold A
I> drop threshold A
Time delay
Time delay at 2 x I> ______________ ms A
Time delay at 10 x I> ______________ ms A
I>> threshold _______________ A
I>> threshold _______________A
I>> drop threshold _______________A
Time delay
Time delay at 2 x I>> _______________ A A
Time delay at 10 x I>> _______________ A A
Earth protection test
Theoretical value Relay value
Ie> threshold _______________ A
Ie> threshold _______________A
Ie> drop threshold _______________A
Time delay
Time delay at 2 x Ie> ______________ ms ms
Time delay at 10 x Ie> ______________ ms ms
Ie>> threshold _______________ A
Ie>> threshold _______________A
Ie>> drop threshold _______________A
Time delay
Time delay at 2 x Ie>> ______________ ms ms
Time delay at 10 x Ie>> ______________ ms ms
_________________________ ______________
Commissioning Test & Record Sheets P12x/EN RS/F75
Password :
Reference :
Frequency :
! 50 Hz ! 60 Hz
E/Gnd text ! N ! E ! G
2.1.2.2 CT Ratio
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
Communication ?
! YES ! NO
Relay Address
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
Ie> ?
! YES ! NO
Ie> Ien
Delay Type
! IDMT ! DMT ! RI
2.1.4.1.1 [51N] Ie > DMT
tIe> ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
Commissioning Test & Record Sheets P12x/EN RS/F75
Ie>>
! YES ! NO
Ie>> Ien
tIe>> ms
Ie>>> ?
! YES ! NO
Ie>>> Ien
tIe>>> ms
Trip tIe>
! YES ! NO
Trip tIe>>
! YES ! NO
Trip tIe>>>
! YES ! NO
2.1.5.2 Latch Function allocation
Latch tIe>
! YES ! NO
Latch tIe>>
! YES ! NO
Latch tIe>>>
! YES ! NO
2.1.5.3 Blocking logic allocation
Block tIe> =
! YES ! NO
Block tIe>> =
! YES ! NO
Block tIe>>> =
! YES ! NO
2.1.5.4 Output Relays allocation (RL2 to RL4)
Functions RL 2 RL 3 RL 4
Input 1
! None ! Unlatch ! 52a
Password :
Reference :
Software version :
Frequency :
! 50 Hz ! 60 Hz
Phase A Text ! A ! L1 ! R
Phase B Text ! B ! L2 ! S
Phase C Text ! C ! L3 ! T
E/Gnd Text ! N ! E ! G
2.2.2.2 CT Ratio
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
Communication ?
! YES ! NO
Relay Address
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
I>?
! YES ! NO
I> In
Delay Type
! IDMT ! DMT ! RI
2.2.4.1.1.1 [51] I> DMT
tI> ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
I>>?
! YES ! NO
I>> In
tI>> ms
I>>>?
! YES ! NO
I>>> In
tI>>> ms
Ie>?
! YES ! NO
Ie> Ien
Delay Type
! IDMT ! DMT ! RI
2.2.4.2.1.1 [51N] Ie > DMT
tIe> ms
P12x/EN RS/F75 Commissioning Test & Record Sheets
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
Ie>>?
! YES ! NO
Ie>> Ien
tIe>> ms
Ie>>> ?
! YES ! NO
Ie>>> Ien
tIe>>> ms
Trip tI>
! YES ! NO
Trip tI>>
! YES ! NO
Trip tI>>>
! YES ! NO
Trip tIe>
! YES ! NO
Trip tIe>>
! YES ! NO
Trip tIe>>>
! YES ! NO
2.2.5.2 Latch function allocation
Latch tI>
! YES ! NO
Latch tI>>
! YES ! NO
Latch tI>>>
! YES ! NO
Latch tIe>
! YES ! NO
Latch tIe>>
! YES ! NO
Latch tIe>>>
! YES ! NO
Commissioning Test & Record Sheets P12x/EN RS/F75
Block tI>
! YES ! NO
Block tI>>
! YES ! NO
Block tI>>>
! YES ! NO
Block tIe>
! YES ! NO
Block tIe>>
! YES ! NO
Block tIe>>>
! YES ! NO
2.2.5.4 OUTPUT RELAYS allocation (RL2 to RL4)
Functions RL 2 RL 3 RL 4
Input 1
! None ! Unlatch ! 52a
Password :
Reference :
Software version :
Frequency :
! 50 Hz ! 60 Hz
Phase A Text ! A ! L1 ! R
Phase B Text ! B ! L2 ! S
Phase C Text ! C ! L3 ! T
E/Gnd Text ! N ! E ! G
2.3.2.2 CT Ratio
Inputs 3 2 1
! ! !
Voltage input DC ! DC ! AC
Relays 6 5 W 4 3 2 1
CMD
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
Communication ?
! YES ! NO
Relay Address
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
I> ?
! YES ! NO
I> In
Delay Type
! IDMT ! DMT ! RI
2.3.4.1.1.1 [51] I> DMT
tI> ms
t Reset ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
P12x/EN RS/F75 Commissioning Test & Record Sheets
I>> ?
! YES ! NO
I>> In
Delay Type
! IDMT ! DMT ! RI
2.3.4.1.2.1 [51] I>> DMT
tI>> ms
t Reset ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
I>>>?
! YES ! NO
I>>> Sample
! YES ! NO
I>>> In
tI>>> ms
Commissioning Test & Record Sheets P12x/EN RS/F75
Ie>?
! YES ! NO
Ie> Ien
Delay Type
! IDMT ! DMT ! RI ! LABOR.
2.3.4.2.1.1 [51N] Ie > DMT
tIe> ms
t Reset ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
Idmt
! 1 ! 2 ! 3
2.3.4.2.2 [51N] Ie>>
Ie>>?
! YES ! NO
Ie>> Ien
Delay Type
! IDMT ! DMT ! RI ! LABOR.
2.3.4.2.2.1 [51N] Ie >> DMT
tIe>> ms
t Reset ms
P12x/EN RS/F75 Commissioning Test & Record Sheets
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
Idmt
! 1 ! 2 ! 3
2.3.4.2.3 [51N] Ie>>>
Ie>>> ?
! YES ! NO
Ie>>> Sample
! YES ! NO
Ie>>> Ien
tIe>>> ms
Therm OL ?
! YES ! NO
Iθ> In
Te mn
k
θ Trip %
θ Alarm ? ! YES ! NO
θ Alarm %
I< ?
! YES ! NO
I< %
tI< ms
Commissioning Test & Record Sheets P12x/EN RS/F75
I2> ?
! YES ! NO
I2> In
Delay Type
! IDMT ! DMT ! RI
2.3.4.5.1 [46] I2> DMT
tI> ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
t Reset ms
Rtms
K
t Reset ms
I2>> ?
! YES ! NO
I2>> In
tI2>> ms
P12x/EN RS/F75 Commissioning Test & Record Sheets
I> ?
! YES ! NO
I> In
Delay Type
! IDMT ! DMT ! RI
2.3.5.1.1.1 [51] I> DMT
tI> ms
t Reset ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
I>> ?
! YES ! NO
I>> In
Delay Type
! IDMT ! DMT ! RI
2.3.5.1.2.1 [51] I>> DMT
tI>> ms
t Reset ms
Commissioning Test & Record Sheets P12x/EN RS/F75
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
I>>>?
! YES ! NO
I>>> Sample
! YES ! NO
I>>> In
tI>>> ms
Ie>?
! YES ! NO
Ie> Ien
Delay Type
! IDMT ! DMT ! RI ! LABOR.
2.3.5.2.1.1 [51N] Ie > DMT
tIe> ms
t Reset ms
P12x/EN RS/F75 Commissioning Test & Record Sheets
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
Idmt
! 1 ! 2 ! 3
2.3.5.2.2 [51N] Ie>>
Ie>>?
! YES ! NO
Ie>> Ien
Delay Type
! IDMT ! DMT ! RI ! LABOR.
2.3.5.2.2.1 [51N] Ie >> DMT
tIe>> ms
t Reset ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Commissioning Test & Record Sheets P12x/EN RS/F75
Rtms
K
t Reset ms
Idmt
! 1 ! 2 ! 3
2.3.5.2.3 [51N] Ie>>>
Ie>>> ?
! YES ! NO
Ie>>> Sample
! YES ! NO
Ie>>> Ien
tIe>>> ms
Therm OL ?
! YES ! NO
Iθ> In
Te mn
k
θ Trip %
θ Alarm ? ! YES ! NO
θ Alarm %
I< ?
! YES ! NO
I< %
tI< ms
I2> ?
! YES ! NO
I2> In
Delay Type
! IDMT ! DMT ! RI
2.3.5.5.1 [46] I2> DMT
tI> ms
P12x/EN RS/F75 Commissioning Test & Record Sheets
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
t Reset ms
Rtms
K
t Reset ms
I2>> ?
! YES ! NO
I2>> In
tI2>> ms
Trip tI>
! YES ! NO
Trip tI>>
! YES ! NO
Trip tI>>>
! YES ! NO
Trip tIe>
! YES ! NO
Trip tIe>>
! YES ! NO
Trip tIe>>>
! YES ! NO
Trip tI<
! YES ! NO
Trip tI2>
! YES ! NO
Trip tI2>>
! YES ! NO
Trip Thermal θ ! YES ! NO
Trip Brkn. Cond
! YES ! NO
Trip tAux1
! YES ! NO
Trip tAux2
! YES ! NO
Trip tAux3
! YES ! NO
Commissioning Test & Record Sheets P12x/EN RS/F75
Latch tI>
! YES ! NO
Latch tI>>
! YES ! NO
Latch tI>>>
! YES ! NO
Latch tIe>
! YES ! NO
Latch tIe>>
! YES ! NO
Latch tIe>>>
! YES ! NO
Latch tI<
! YES ! NO
Latch tI2>
! YES ! NO
Latch tI2>>
! YES ! NO
Latch Thermal θ ! YES ! NO
Latch Brkn .Cond
! YES ! NO
Latch tAux1
! YES ! NO
Latch tAux2
! YES ! NO
Latch tAux3
! YES ! NO
2.3.6.3 Blocking Logic 1 function allocation
Block 1 tI>
! YES ! NO
Block 1 tI>>
! YES ! NO
Block 1 tI>>>
! YES ! NO
Block 1 tIe>
! YES ! NO
Block 1 tIe>>
! YES ! NO
Block 1 tIe>>>
! YES ! NO
Block 1 tI<
! YES ! NO
Block 1 tI2>
! YES ! NO
Block 1 tI2>>
! YES ! NO
Block 1 Thermal θ ! YES ! NO
Block 1 Brkn .Cond
! YES ! NO
Block 1 tAux1
! YES ! NO
Block 1 tAux2
! YES ! NO
Block 1 tAux3
! YES ! NO
P12x/EN RS/F75 Commissioning Test & Record Sheets
Block 2 tI>
! YES ! NO
Block 2 tI>>
! YES ! NO
Block 2 tI>>>
! YES ! NO
Block 2 tIe>
! YES ! NO
Block 2 tIe>>
! YES ! NO
Block 2 tIe>>>
! YES ! NO
Block 2 tI<
! YES ! NO
Block 2 tI2>
! YES ! NO
Block 2 tI2>>
! YES ! NO
Block 2 Thermal θ ! YES ! NO
Block 2 Brkn .Cond
! YES ! NO
Block 2 tAux1
! YES ! NO
Block 2 tAux2
! YES ! NO
Block 2 tAux3
! YES ! NO
2.3.6.5 SELECTIVE SCHEME LOGIC1 function allocation
Logic Select 1
! YES ! NO
Sel1 tI>>
! YES ! NO
Sel1 tI>>>
! YES ! NO
Sel1 tIe>>
! YES ! NO
Sel1 tIe>>>
! YES ! NO
t SeL1 ms
Logic Select 2
! YES ! NO
Sel2 tI>>
! YES ! NO
Sel2 tI>>>
! YES ! NO
Sel2 tIe>>
! YES ! NO
Sel2 tIe>>>
! YES ! NO
t Sel2 ms
Commissioning Test & Record Sheets P12x/EN RS/F75
Functions RL 2 RL 3 RL 4
Trip ! YES ! NO ! YES ! NO ! YES ! NO
I> ! YES ! NO ! YES ! NO ! YES ! NO
tI> ! YES ! NO ! YES ! NO ! YES ! NO
I>> ! YES ! NO ! YES ! NO ! YES ! NO
tI>> ! YES ! NO ! YES ! NO ! YES ! NO
I>>> ! YES ! NO ! YES ! NO ! YES ! NO
tI>>> ! YES ! NO ! YES ! NO ! YES ! NO
Ie> ! YES ! NO ! YES ! NO ! YES ! NO
tIe> ! YES ! NO ! YES ! NO ! YES ! NO
Ie>> ! YES ! NO ! YES ! NO ! YES ! NO
tIe>> ! YES ! NO ! YES ! NO ! YES ! NO
Ie>>> ! YES ! NO ! YES ! NO ! YES ! NO
tIe>>> ! YES ! NO ! YES ! NO ! YES ! NO
tI< ! YES ! NO ! YES ! NO ! YES ! NO
tI2> ! YES ! NO ! YES ! NO ! YES ! NO
tI2>> ! YES ! NO ! YES ! NO ! YES ! NO
Therm Alarm ! YES ! NO ! YES ! NO ! YES ! NO
Therm Trip ! YES ! NO ! YES ! NO ! YES ! NO
CB Alarm ! YES ! NO ! YES ! NO ! YES ! NO
52 Fail ! YES ! NO ! YES ! NO ! YES ! NO
Brkn cond ! YES ! NO ! YES ! NO ! YES ! NO
CB Fail ! YES ! NO ! YES ! NO ! YES ! NO
CB Close ! YES ! NO ! YES ! NO ! YES ! NO
tAux1 ! YES ! NO ! YES ! NO ! YES ! NO
tAux2 ! YES ! NO ! YES ! NO ! YES ! NO
tAux3 ! YES ! NO ! YES ! NO ! YES ! NO
Order COM 1 ! YES ! NO ! YES ! NO ! YES ! NO
Order COM 2 ! YES ! NO ! YES ! NO ! YES ! NO
Order COM 3 ! YES ! NO ! YES ! NO ! YES ! NO
Order COM 4 ! YES ! NO ! YES ! NO ! YES ! NO
Active Group ! YES ! NO ! YES ! NO ! YES ! NO
P12x/EN RS/F75 Commissioning Test & Record Sheets
Functions RL 5 RL 6
Trip ! YES ! NO ! YES ! NO
I> ! YES ! NO ! YES ! NO
tI> ! YES ! NO ! YES ! NO
I>> ! YES ! NO ! YES ! NO
tI>> ! YES ! NO ! YES ! NO
I>>> ! YES ! NO ! YES ! NO
tI>>> ! YES ! NO ! YES ! NO
Ie> ! YES ! NO ! YES ! NO
tIe> ! YES ! NO ! YES ! NO
Ie>> ! YES ! NO ! YES ! NO
tIe>> ! YES ! NO ! YES ! NO
Ie>>> ! YES ! NO ! YES ! NO
tIe>>> ! YES ! NO ! YES ! NO
tI< ! YES ! NO ! YES ! NO
tI2> ! YES ! NO ! YES ! NO
tI2>> ! YES ! NO ! YES ! NO
Therm Alarm ! YES ! NO ! YES ! NO
Therm Trip ! YES ! NO ! YES ! NO
CB Alarm ! YES ! NO ! YES ! NO
52 Fail ! YES ! NO ! YES ! NO
Brkn cond ! YES ! NO ! YES ! NO
CB Fail ! YES ! NO ! YES ! NO
CB Close ! YES ! NO ! YES ! NO
tAux1 ! YES ! NO ! YES ! NO
tAux2 ! YES ! NO ! YES ! NO
tAux3 ! YES ! NO ! YES ! NO
Order COM 1 ! YES ! NO ! YES ! NO
Order COM 2 ! YES ! NO ! YES ! NO
Order COM 3 ! YES ! NO ! YES ! NO
Order COM 4 ! YES ! NO ! YES ! NO
Active Group ! YES ! NO ! YES ! NO
Commissioning Test & Record Sheets P12x/EN RS/F75
2.3.6.8.1 Inputs
tCL ms
CB Fail ?
! YES ! NO
I< In
tBF ms
Block I> ?
! YES ! NO
Block Ie> ?
! YES ! NO
2.3.6.12 CIRCUIT BREAKER SUPERVISION
TC Supervision ?
! YES ! NO
t SUP s
CB Open S'vision
! YES ! NO
CB Open Time ms
CB Close S'vision
! YES ! NO
CB Close Time ms
CB Open Alarm ?
! YES ! NO
CB Open NB
Σ Amps (n) ? ! YES ! NO
Σ Amps (n)
n
t Open Pulse ms
t Close Pulse ms
Commissioning Test & Record Sheets P12x/EN RS/F75
Pre-Time ms
Post-Time ms
Disturb Rec Trig
! ON INST. ! ON TRIP
2.3.7.2 TIME PEAK VALUE
Time Window mn
Sub Period mn
Num of Sub Per.
P12x/EN RS/F75 Commissioning Test & Record Sheets
Password :
Reference :
Software version :
Frequency :
! 50 Hz ! 60 Hz
2.4.2 CONFIGURATION Menu
2.4.2.1 Display
Phase A Text ! A ! L1 ! R
Phase B Text ! B ! L2 ! S
Phase C Text ! C ! L3 ! T
E/Gnd Text ! N ! E ! G
2.4.2.2 CT Ratio
Setting group ! 1 ! 2
P12x/EN RS/F75 Commissioning Test & Record Sheets
Inputs 3 2 1
! ! !
Voltage input DC ! DC ! AC
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
Communication ?
! YES ! NO
Relay Address
Commissioning Test & Record Sheets P12x/EN RS/F75
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
Communication ?
! YES ! NO
Baud Rate
! 300 bds ! 600 bds
I> ?
! YES ! NO
I> In
Delay Type
! IDMT ! DMT ! RI
2.4.4.1.1.1 [51] I> DMT
tI> ms
t Reset ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
P12x/EN RS/F75 Commissioning Test & Record Sheets
t Reset ms
Rtms
K
t Reset ms
I>> ?
! YES ! NO
I>> In
Delay Type
! IDMT ! DMT ! RI
2.4.4.1.2.1 [51] I>> DMT
tI>> ms
t Reset ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
I>>>?
! YES ! NO
I>>> Sample
! YES ! NO
I>>> In
tI>>> ms
Commissioning Test & Record Sheets P12x/EN RS/F75
Ie> ?
! YES ! NO
Ie> Ien
Delay Type
! IDMT ! DMT ! RI ! LABOR.
2.4.4.2.1.1 [51N] Ie > DMT
tIe> ms
t Reset ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
t Reset ms
Rtms
K
t Reset ms
Idmt
! 1 ! 2 ! 3
2.4.4.2.2 [51N] Ie>>
Ie>> ?
! YES ! NO
Ie>> Ien
Delay Type
! IDMT ! DMT ! RI ! LABOR.
2.4.4.2.2.1 [51N] Ie >> DMT
tIe>> ms
t Reset ms
P12x/EN RS/F75 Commissioning Test & Record Sheets
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
t Reset ms
Rtms
K
t Reset ms
Idmt
! 1 ! 2 ! 3
2.4.4.2.3 [51N] Ie >>>
Ie>>> ?
! YES ! NO
Ie>>> Sample
! YES ! NO
Ie>>> Ien
tIe>>> ms
[49] Therm OL ?
! YES ! NO
Iθ> In
Te mn
k
θ Trip %
[49] θ Alarm ? ! YES ! NO
θ Alarm %
I< ?
! YES ! NO
I< %
tI< ms
Commissioning Test & Record Sheets P12x/EN RS/F75
I2>?
! YES ! NO
I2> In
Delay Trip
! IDMT ! DMT ! RI
2.4.4.5.1 [46] I2> DMT
tI2> ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
t Reset ms
Rtms
K
t Reset ms
I2>>?
! YES ! NO
I2>> In
tI2>> ms
P12x/EN RS/F75 Commissioning Test & Record Sheets
I> ? ! YES ! NO
I> In
Delay Type ! IDMT ! DMT ! RI
2.4.5.1.1.1 [51] I> DMT
tI> ms
t Reset ms
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
I>> ? ! YES ! NO
I>> In
Delay Type ! IDMT ! DMT ! RI
2.4.5.1.2.1 [51] I>> DMT
tI>> ms
t Reset ms
P12x/EN RS/F75 Commissioning Test & Record Sheets
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
I>>>?
! YES ! NO
I>>> Sample
! YES ! NO
I>>> In
tI>>> ms
Ie> ?
! YES ! NO
Ie> Ien
Delay Type
! IDMT ! DMT ! RI ! LABOR.
2.4.5.2.1.1 [51N] Ie > DMT
tIe> ms
t Reset ms
Commissioning Test & Record Sheets P12x/EN RS/F75
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
t Reset ms
Rtms
K
t Reset ms
Idmt
!1 !2 !3
2.4.5.2.2 [51N] Ie>>
Ie>> ?
! YES ! NO
Ie>> Ien
Delay Type
! IDMT ! DMT ! RI ! LABOR.
2.4.5.2.2.1 [51N] Ie >> DMT
tIe>> ms
t Reset ms
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
! IEEE RC
Tms
P12x/EN RS/F75 Commissioning Test & Record Sheets
t Reset ms
Rtms
K
t Reset ms
Idmt
! 1 ! 2 ! 3
2.4.5.2.3 [51N] Ie >>>
Ie>>> ?
! YES ! NO
Ie>>> Sample
! YES ! NO
Ie>>> Ien
tIe>>> ms
[49] Therm OL ?
! YES ! NO
Iθ> In
Te mn
k
θ Trip %
[49] θ Alarm ? ! YES ! NO
θ Alarm %
I< ?
! YES ! NO
I< %
tI< ms
I2>?
! YES ! NO
I2> In
Delay Trip
! IDMT ! DMT ! RI
2.4.5.5.1 [46] I2> DMT
tI2> ms
Commissioning Test & Record Sheets P12x/EN RS/F75
Idmt
! IEC SI ! IEC STI
! IEC VI ! IEC EI
! IEEE MI ! CO8
! IEEE VI ! IEEE EI
Tms
t Reset ms
Rtms
K
t Reset ms
I2>>?
! YES ! NO
I2>> In
tI2>> ms
[79] Autoreclose ?
! YES ! NO
Ext CB Fail ?
! YES ! NO
Ext CB Fail Time ms
Ext Block ?
! YES ! NO
Aux 1 (I>)
! YES ! NO
Aux 2 (Ie>)
! YES ! NO
Dead Time tD1 ms
Dead Time tD2 ms
Dead Time tD3 ms
Dead Time tD4 ms
Reclaim Time tR ms
Inhib Time tI ms
Phase Cycles
E/Gnd Cycles
4 3 2 1
CYCLES tI>
! ! ! !
P12x/EN RS/F75 Commissioning Test & Record Sheets
4 3 2 1
CYCLES tI>>
! ! ! !
4 3 2 1
CYCLES tI>>>
! ! ! !
4 3 2 1
CYCLES tIe>
! ! ! !
4 3 2 1
CYCLES tIe>>
! ! ! !
4 3 2 1
CYCLES tIe>>>
! ! ! !
4 3 2 1
CYCLES tAux 1
! ! ! !
4 3 2 1
CYCLES tAux 2
! ! ! !
2.4.6 AUTOMAT.CTRL Menu
2.4.6.1 TRIP Command allocation
Trip tI>
! YES ! NO
Trip tI>>
! YES ! NO
Trip tI>>>
! YES ! NO
Trip tIe>
! YES ! NO
Trip tIe>>
! YES ! NO
Trip tIe>>>
! YES ! NO
Trip tI<
! YES ! NO
Trip tI2>
! YES ! NO
Trip tI2>>
! YES ! NO
Trip Thermal θ ! YES ! NO
Trip Brkn Cond
! YES ! NO
Trip tAux1
! YES ! NO
Trip tAux2
! YES ! NO
Trip tAux3
! YES ! NO
Trip tAux4
! YES ! NO
Trip SOTF
! YES ! NO
Ctrl Trip
! YES ! NO
Trip CB Fail
! YES ! NO
Commissioning Test & Record Sheets P12x/EN RS/F75
Latch tI>
! YES ! NO
Latch tI>>
! YES ! NO
Latch tI>>>
! YES ! NO
Latch tIe>
! YES ! NO
Latch tIe>>
! YES ! NO
Latch tIe>>>
! YES ! NO
Latch tI<
! YES ! NO
Latch tI2>
! YES ! NO
Latch tI2>>
! YES ! NO
Latch Thermal θ ! YES ! NO
Latch Brkn . Cond
! YES ! NO
Latch tAux1
! YES ! NO
Latch tAux2
! YES ! NO
Latch tAux3
! YES ! NO
Latch tAux4
! YES ! NO
Latch SOTF
! YES ! NO
Latch CB FAIL
! YES ! NO
2.4.6.3 Blocking Logic 1 function allocation
Block 1 tI>
! YES ! NO
Block 1 tI>>
! YES ! NO
Block 1 tI>>>
! YES ! NO
Block 1 tIe>
! YES ! NO
Block 1 tIe>>
! YES ! NO
Block 1 tIe>>>
! YES ! NO
Block 1 tI<
! YES ! NO
Block 1 tI2>
! YES ! NO
Block 1 tI2>>
! YES ! NO
Block 1 Thermal θ ! YES ! NO
Block 1 Brkn. Cond
! YES ! NO
Block 1 tAux1
! YES ! NO
Block 1 tAux2
! YES ! NO
Block 1 tAux3
! YES ! NO
Block 1 tAux4
! YES ! NO
P12x/EN RS/F75 Commissioning Test & Record Sheets
Block 2 tI>
! YES ! NO
Block 2 tI>>
! YES ! NO
Block 2 tI>>>
! YES ! NO
Block 2 tIe>
! YES ! NO
Block 2 tIe>>
! YES ! NO
Block 2 tIe>>>
! YES ! NO
Block 2 tI<
! YES ! NO
Block 2 tI2>
! YES ! NO
Block 2 tI2>>
! YES ! NO
Block 2 Thermal θ ! YES ! NO
Block 2 Brkn. Cond
! YES ! NO
Block 2 tAux1
! YES ! NO
Block 2 tAux2
! YES ! NO
Block 2 tAux3
! YES ! NO
Block 2 tAux4
! YES ! NO
2.4.6.5 Selective Scheme Logic1 function allocation
Logic Select 1
! YES ! NO
Sel1 tI>>
! YES ! NO
Sel1 tI>>>
! YES ! NO
Sel1 tIe>>
! YES ! NO
Sel1 tIe>>>
! YES ! NO
t Sel1 ms
Logic Select 2
! YES ! NO
Sel2 tI>>
! YES ! NO
Sel2 tI>>>
! YES ! NO
Sel2 tIe>>
! YES ! NO
Sel2 tIe>>>
! YES ! NO
tSel2 = ms
Commissioning Test & Record Sheets P12x/EN RS/F75
Functions RL 2 RL 3 RL 4
Functions RL 2 RL 3 RL 4
Functions RL 5 RL 6 RL 7 RL8
Functions RL 5 RL 6 RL 7 RL8
2.4.6.8.1 Inputs
Input 1
! None ! Unlatch ! 52a
! Strt tBF
Input 3
! None ! Unlatch ! 52a
! Strt tBF
Input 4
! None ! Unlatch ! 52a
! Strt tBF
P12x/EN RS/F75 Commissioning Test & Record Sheets
Input 5
! None ! Unlatch ! 52a
Ratio I2/I1 %
tCL ms
Commissioning Test & Record Sheets P12x/EN RS/F75
CB Fail ? ! YES ! NO
tBF ms
I< In
Block I> ? ! YES ! NO
Block Ie> ? ! YES ! NO
2.4.6.12 CIRCUIT BREAKER SUPERVISION
TC Supervision? ! YES ! NO
t SUP s
Σ Amps(n)? ! YES ! NO
Σ Amps(n)
t Open Pulse ms
t Close Pulse ms
2.4.6.13 SOTF
SOTF? ! YES ! NO
t SOTF ms
I>> ! YES ! NO
I>>> ! YES ! NO
P12x/EN RS/F75 Commissioning Test & Record Sheets
Pre-time ms
Post-time ms
Disturb Rec Trig
! ON INST. ! ON TRIP
2.4.7.2 TIME PEAK VALUE
Time Window mn
Sub Period mn
Num of Sub Per.
Hardware/Software Version P12x/EN VC/F75
History and Compatibility
MiCOM P120/P121/P122/P123
HARDWARE/SOFTWARE
VERSION
P120 P121 P122 P123
HISTORY AND
COMPATIBILITY
Hardware/Software Version P12x/EN VC/F75
History and Compatibility
MiCOM P120/P121/P122/P123 Page 1/18
(HARD 2 → *)
V6.A 18/06/03 Add periodic self test of EEPROM data / V2.09 Two versions
calibration every 24 hours with safeguard of the
HARD 3 or
results in safeguarded RAM.
HARD 4
Add a new major alarm “Default settings” which
is set after an EEPROM data error, and the
following reloading of the default settings, and
automatically reset after the following parameter (HARD 2 → *)
write.
IEC870-5-103 communication :
- add ASDU 3.4 for measurement IN, instead of
private ASDU 77, for setting in conformity with
the standard (cf P127).
V6.B 18/07/03 Improvement of the reading of the alarm V2.09 Two versions
"EEPROM DATA FAULT" when much access
HARD 3 or
EEPROM is done :
HARD 4
- Optimization of the readings in E2PROM
(writing of the value of the checksums in
internal RAM).
(HARD 2 → *)
- The function of access to the E2PROM
becomes protected from the interruptions.
V6.C 28/11/03 Software changes implemented in this version V2.10 Two versions
- Modif. treatment of the thermal model: 20 HARD 3 or
milliseconds instead of 100.
HARD 4
- Evolutions communication MODBUS:
addition of the read quick byte (Function 7)
by reading of words (Function 03 or 04), and (HARD 2 → *)
of the reading of the date (on page 8).
- Communication MODBUS Front Face:
addition of the filtering of address.
Software improvement done in this version
Fix on RI curves processing in certain cases.
V6.D 11/12/03 Software improvement done in this version V2.10 Two versions
Modification to remove the taking into account HARD 3 or
of the number of defect in the calculation of
HARD 4
checksum of page 1 of E2PROM, like in
autotest E2PROM.
(HARD 2 → *)
Hardware/Software Version P12x/EN VC/F75
History and Compatibility
MiCOM P120/P121/P122/P123 Page 5/18
(HARD 2 → *)
V6.A 18/06/03 Add periodic self test of EEPROM data / V2.09 Two versions
calibration every 24 hours with safeguard of
HARD 3 or
the results in safeguarded RAM.
HARD 4
Add a new major alarm “Default settings”
which is set after an EEPROM data error,
and the following reloading of the default
settings, and automatically reset after the (HARD 2 → *)
following parameter write.
Add "tReset" events for the thresholds I>,
I>>, IN>, IN>> and I2>, and "tReset"
parameter for the constant time
temporization (thresholds I>, I>>, IN> and
IN>>).
Add "sample" parameter (Yes=Sample or
No=RMS values) for the third thresholds
I>>> and IN>>>.
Add "CB Fail" choice for the "Trip functions"
and "Latch functions" parameters. Add "tBF"
event.
IEC870-5-103 communication :
- add ASDU 3.4 for measurement IN, instead
of private ASDU 77, for setting in conformity
with the standard (cf P127).
- various improvements : in the management
of the validity of the date and season in the
messages, modifications in
acknowledgement of the orders and time
synchronization.
Hardware/Software Version P12x/EN VC/F75
History and Compatibility
MiCOM P120/P121/P122/P123 Page 9/18
(HARD 2 → *)
V6.A 18/06/03 Add periodic self test of EEPROM data / V2.09 Two versions
calibration every 24 hours with safeguard of
Patch HARD 3 or
the results in safeguarded RAM.
Modbus
HARD 4
Add a new major alarm “Default settings” V2.08.005
which is set after an EEPROM data error,
and the following reloading of the default
settings, and automatically reset after the (HARD 2 → *)
following parameter write.
Add "tReset" events for the thresholds I>,
I>>, IN>, IN>> and I2>, and "tReset"
parameter for the constant time
temporization (thresholds I>, I>>, IN> and
IN>>).
Add "sample" parameter (Yes=Sample or
No=RMS values) for the third thresholds
I>>> and IN>>>.
Add "CB Fail" choice for the "Trip functions"
and "Latch functions" parameters. Add "tBF"
event.
IEC870-5-103 communication :
- add ASDU 3.4 for measurement IN, instead
of private ASDU 77, for setting in conformity
with the standard (cf P127).
- various improvements : in the management
of the validity of the date and season in the
messages, modifications in
acknowledgement of the orders and time
synchronization.
P12x/EN VC/F75 Hardware/Software Version
History and Compatibility
Page 14/16 MiCOM P120/P121/P122/P123