Glazed Elements - Fenestration Performance Requirements: Wall Roof

This document provides glazed element and fenestration performance requirements for a new residential and commercial building as per Green Building Regulations. It specifies that 53% of the glazed facade area is oriented predominantly north. Thermal bridges that enable heat transfer must be eliminated or insulated. Maximum and minimum requirements are provided for thermal transmittance, shading coefficient, and light transmittance based on the percentage of external wall area that is glazed. Six glazed elements are listed with their dimensions, area, orientation distribution, and thermal properties.

Uploaded by

Kashif Sani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
106 views1 page

Glazed Elements - Fenestration Performance Requirements: Wall Roof

This document provides glazed element and fenestration performance requirements for a new residential and commercial building as per Green Building Regulations. It specifies that 53% of the glazed facade area is oriented predominantly north. Thermal bridges that enable heat transfer must be eliminated or insulated. Maximum and minimum requirements are provided for thermal transmittance, shading coefficient, and light transmittance based on the percentage of external wall area that is glazed. Six glazed elements are listed with their dimensions, area, orientation distribution, and thermal properties.

Uploaded by

Kashif Sani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Glazed Elements - Fenestration Performance Requirements 1-3-2014 v1

Plot No. 117-0190 AL MURAR Thermal Bridges: for all new air conditioned buildings, Thermal
Glazed Elements - Fenestration Performance Requirements as Thermal Shading Coefficient Light Transmittance Bridges, such as connection points between concrete or steel beams,
Project G+4+2 ROOF RESIDENTIAL AND COMMERCIAL external walls and columns and around doors and windows, which
per Green Building Regulations & Specifications Transmittance -U - SC - LT
enable the flow of heat from outide into the building, must be eliminated
Consultant PIONEER OF EXPERTS ENGINEEERING CNSULTANT W/m2 K or insulated to reduce the amount of heat transfer.
(1) If percentage of total area of external walls that let lights to
Glazed Elements - Fenestration Percentage Orientation of Glazed Facades
the external wall area is:
Wall Glazing Elements Percentage to the External Glazing Portion of a Roof Percentage to the Total 1-1 Equal or less than 40% 2.10 (max) 0.40 (max) 0.25 (min) Perdominately North Orientation
Wall Area Roof Area 1-2 Between 40% - 60% 1.90 (max) 0.32 (max) 0.10 (min) Percentage Is: 53%
Total Glass Area 1469.64 m2 Total Glass Area m2 1-3 Equal or greater than 60% 1.90 (max) 0.25 (max) 0.10 (min)
(2) For shopfronts and showrooms, other than those at ground
Total External wall Area 7697.67 m2 Total Roof Area 2538.50 m2 1.90 (max) 0.76 (max)
floor level:

(3) If percentage of glazing portion of a roof to the roof area is:


19% As Per Regulation (304.04)
3-1 Equal or less than 10% 1.90 (max) 0.32 (max) 0.40 (min)
3-2 Greater than 10% 1.90 (max) 0.25 (max) 0.30 (min)

Hide Empty Rows

No. of Windows on the Exposed Orientation


Glazed Elements Height Width Item Area
Thermal
Shading Coefficient Light Transmittance
Perdominately North Orientation No. of Glass Layers Transmittance - U Color Type Note
SE S SW W H - SC - LT
2
Reference Name/No. m m m2
NW N NE E Horizontal W/m K
GD-01 2.50 1.40 3.50 10.00 50.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GD-02 2.50 1.60 4.00 40.00 20.00 45.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GD-03 3.50 3.60 12.60 5.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GD-04 3.50 3.00 10.50 2.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GD-05 3.50 3.30 11.55 1.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GD-06 3.50 2.00 7.00 1.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GD-07 2.20 1.10 2.42 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GD-08 3.50 4.20 14.70 1.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GD-09 3.50 4.00 14.00 1.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GD-10 3.50 3.00 10.50 4.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GD-11 3.50 4.90 17.15 1.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-01 1.60 1.40 2.24 50.00 20.00 10.00 11.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-02 3.10 2.20 6.82 5.00 5.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-03 3.10 5.80 17.98 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-04 1.60 1.60 2.56 10.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-05 1.60 1.00 1.60 10.00 20.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-06 1.30 1.40 1.82 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-07 3.60 3.00 10.80 1.00 1.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-08 3.60 4.50 16.20 10.00 1.00 5.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-09 1.60 2.00 3.20 4.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-10 2.50 4.00 10.00 1.00 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-11 2.60 0.50 1.30 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-12 1.00 0.50 0.50 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK
GW-13 2.60 1.00 2.60 2.00 1.90 0.32 0.25 M DOUBLE GLASS ALUM. THERMAL BREAK

Total Glazed Area at the Corresponding Orintation (m2): 503.10 279.20 538.90 148.44

Wall Consultant Comments:


Height Width Total Area Light Reflective Value
No.
Reference Name/No. m m m2 LRV (%)
GROUND 4.85 227.20 1.00 1101.92 45.00 Light Colors on the Outside of Buildings: For all new buildings, at least 75% of the area of
TYPICAL 3.50 358.80 5.00 6279.00 45.00 externally painted walls must have a minimum Light Reflective (LRV) Value of 45%
ROOF 3.50 90.50 1.00 316.75 45.00

Roof Total Area


Length Width Roof Solar Reflective
Type of Roof Urban Heat Island Effect: All opaque external roofing surfaces must comply with a minimum Roof
Reference Name/No. m m m2 Index - SRI
Solar Reflective Index (SRI) Value according to table below for a minimum of 75% of the roof area:
ROOF 2538.50 1.00 2538.50 Flat & or Low 78.00
Steep Sloped Enter SRI Value Type of Roof Min. Roof SRI

Steep Sloped
Enter SRI Value Steep Sloped Roofs (slopes steeper than 1:6) ≥ 29.00

Flat and Low Sloped Roofs ≥ 78.00