Complex Transmission Circuit Protection
Complex Transmission Circuit Protection
Protection of Complex
Transmission Circuits
331
NRJED311332EN 331
NRJED311332EN
Network Protection & Automation Guide
Protection of Complex Contents
Transmission Circuits
1. Introduction 333
7. Examples 353
8. References 360
12
332 NRJED311332EN
Protection of Complex 1. Introduction
Transmission Circuits
Bus A Bus B For economic reasons, transmission and distribution lines can be
much more complicated, maybe having three or more terminals
(multi-ended feeder), or with more than one circuit carried on a
Figure 12.1: common structure (parallel feeders), as shown in Figure 12.1.
Parallel and Multi-ended feeders Other possibilities are the use of series capacitors or direct-
connected shunt reactors. The protection of such lines is more
complicated and requires the basic schemes described in the
above chapters to be modified.
The purpose of this chapter is to explain the special requirements of
some of these situations in respect of protection and identify which
protection schemes are particularly appropriate for use in these
situations.
12
NRJED311332EN 333
Protection of Complex 2. Parallel Feeders
Transmission Circuits
Z< Z<
334 NRJED311332EN
Protection of Complex 2. Parallel Feeders
Transmission Circuits
(cont.)
( I B 0 I A 0 ) M
Z A = nZ L1 1 +
2 ( I A1 I A 0 ) + K
...Equation 12.1
where:
M =ZM 0
Z L1
The true impedance to the fault is where n is the per unit fault
position measured from and is the positive sequence
impedance of a single circuit.
NRJED311332EN 335
Protection of Complex 2. Parallel Feeders
Transmission Circuits
(cont.)
I A0 =
(2 − n )ZSO′′ + (1 − n )(ZSO′ + Z L 0 + Z M 0 ) I
2 (ZSO ′′ ) + Z L 0 + Z M 0
0
′ + ZSO
and
and = zero sequence mutual impedance
between the two circuits
Note: For earth faults
Line B
ZM0
12 Line A
n
Fault
Relay
location
(a) Single line diagram
IA0
R
336 NRJED311332EN
Protection of Complex 2. Parallel Feeders
Transmission Circuits
(cont.)
100
Limit of n' 5
=0.67 67
50 when y ' = 0.
n 68
x 0
= 0.
n'
.7
=0
n'
75
10 = 0.
n' .8
=0 85
n'
)
0.
e1
5 =
on
n'
(Z
g
in
.9
tt
=0
se
n'
al
in
m
1
5
No
.9
=0
n'
0.5
Limit of
n'=1
when y 0
x
0.1 0.5 1 5 10 50 100 12
Figure 12.4:
Typical reach curves illustrating the effect of
mutual coupling
NRJED311332EN 337
Protection of Complex 2. Parallel Feeders
Transmission Circuits
(cont.)
V A = I A1Z L1 + I A 2 Z L 2 + I A 0 Z L 0 + I B 0 Z M 0
I A = I A1 + I A 2 + I A 0
...Equation 12.2
The voltage and current fed into the relay are given by:
V R =V A
I R = I A + K R I A 0 + K M I B 0
...Equation 12.3
where:
is the residual compensation factor
12 is the mutual compensation factor:
Thus:
Z L 0 − Z L1
KR =
Z L1
ZM 0
KM =
Z L1
338 NRJED311332EN
Protection of Complex 2. Parallel Feeders
Transmission Circuits
(cont.)
NRJED311332EN 339
Protection of Complex 3. Multi-Ended Feeders –
Transmission Circuits
Unit Protection Schemes
340 NRJED311332EN
Protection of Complex 3. Multi-Ended Feeders –
Transmission Circuits
Unit Protection Schemes
(cont.)
End A End B
A
B
C
12
Quadrature CT
A1 A1
1
A C1 A C C1
C
N1 N N1 N
End C
A1
S1 S2 1
C1 S1 S2
A C
N1 N
Relay
S1 S2
Pilots
Figure 12.6:
Balanced voltage Tee’d feeder scheme
NRJED311332EN 341
Protection of Complex 3. Multi-Ended Feeders –
Transmission Circuits
Unit Protection Schemes
(cont.)
End A End B
End C
12
Quadrature
CT
D E D E D E
Operating pilots
Figure 12.7: D Operating coil E Restraints coil Bias pilots
Type DSB7 fast tee’d feeder protection
342 NRJED311332EN
Protection of Complex 3. Multi-Ended Feeders –
Transmission Circuits
Unit Protection Schemes
(cont.)
NRJED311332EN 343
Protection of Complex 3. Multi-Ended Feeders –
Transmission Circuits
Unit Protection Schemes
(cont.)
344 NRJED311332EN
Protection of Complex 4. Multi-Ended Feeders -
Transmission Circuits
Distance Relays
A B
T
Fault
Figure 12.12:
Fault at substation B busbars
Z A = Z LA + Z LB +
(ZSB + Z LB ) Z
(ZSC + Z LC ) LB
NRJED311332EN 345
Protection of Complex 4. Multi-Ended Feeders -
Transmission Circuits
Distance Relays
(cont.)
X
The magnitude of the third term in this expression is a function of
the total impedances of the branches and and can reach a
B'
relatively high value when the fault current contribution of branch
is much larger than that of branch . Figure 12.13 illustrates how a
distance relay with a mho characteristic located at with a Zone 2
B
element set to 120% of the protected feeder , fails to see a fault
at the remote busbar . The ’tee’ point T in this example is halfway
between substations and and the fault currents and
have been assumed to be identical in magnitude and phase
T angle. With these conditions, the fault appears to the relay to be
located at instead of at - i.e. the relay appears to under-reach.
The under-reaching effect in tee’d feeders can be found for any kind
R of fault. For the sake of simplicity, the equations and examples
A
mentioned so far have been for balanced faults only. For
unbalanced faults, especially those involving earth, the equations
Figure 12.13: become somewhat more complicated, as the ratios of the sequence
Apparent impedance presented to the relay fault current contributions at terminals and may not be the same.
at substation A for a fault at substation B An extreme example of this condition is found when the third
busbars terminal is a tap with no generation but with the star point of the
primary winding of the transformer connected directly to earth, as
shown in Figure 12.14. The corresponding sequence networks are
illustrated in Figure 12.15.
Figure 12.14:
Transformer tap with primary winding A B
solidly earthed T
12 Phase A
to ground fault
C
M Load
It can be seen from Figure 12.15 that the presence of the tap has
little effect in the positive and negative sequence networks.
However, the zero sequence impedance of the branch actually
shunts the zero sequence current in branch . As a result, the
distance relay located at terminal tends to under-reach. One
solution to the problem is to increase the residual current
compensating factor in the distance relay, to compensate for the
reduction in zero sequence current. However, the solution has two
possible limitations:
i. over-reach will occur when the transformer is not connected,
and hence operation for faults outside the protected zone may
occur
ii. the inherent possibility of maloperation of the earth fault
elements for earth faults behind the relay location is increased
Figure 12.15:
Sequence networks
for a phase A to ground fault at busbar B in
the system shown in Figure 13.14
346 NRJED311332EN
Protection of Complex 4. Multi-Ended Feeders -
Transmission Circuits
Distance Relays
(cont.)
12
A B
T
Fault
C
Figure 12.17:
Internal Fault at busbar B with current
flowing out at terminal
NRJED311332EN 347
Protection of Complex 4. Multi-Ended Feeders -
Transmission Circuits
Distance Relays
(cont.)
A B
T
Fault
12 C
Figure 12.18:
Internal fault near busbar B with current
flowing out at terminal C
348 NRJED311332EN
Protection of Complex 4. Multi-Ended Feeders -
Transmission Circuits
Distance Relays
(cont.)
A B
T
Fault
Figure 12.19:
External fault behind the relay at terminal A
Relevant figure
Case Description
number
Under-reaching effect for internal faults due to current
1 13.12 to 13.15
infeed at the T point
Effect of pre-fault load on the impedance seen’ by
2 13.16
the relay
Over-reaching effect for external faults, due to current
3 13.17
flowing outwards at one terminal
Failure to operate for an internal fault, due to current
4 13.18
flowing out at one terminal
Incorrect operation for an external fault, due to high
5 3.19
current fed from nearest terminal 1
Table 12.2:
Main problems met in the application of distance protection to tee’d
feeders.
NRJED311332EN 349
Protection of Complex 5. Multi-Ended Feeders –
Transmission Circuits
Application of Distance
Protection Schemes
350 NRJED311332EN
Protection of Complex 5. Multi-Ended Feeders –
Transmission Circuits
Application of Distance
Protection Schemes (cont.)
NRJED311332EN 351
Protection of Complex 6. Protection of Series
Transmission Circuits
Compensated Lines
352 NRJED311332EN
Protection of Complex 7. Examples
Transmission Circuits
120MVA 220/110/11kV
12
transformers
=0.15 ; =0.35;
=0.25
=0.125 ; =0.025
=0.225 on 120MVA
110kV Substation P
Current transformer
ratio 600/1A
Voltage transformer
Figure 12.23: 45MVA ratio 110kV/110V
Example network for distance relay setting Line 1 132/33kV Line 2
transformers
calculation XT=0.125
110kV
Substation Q
45MVA 132/33kV
transformers
XT=0.125
Line 3 Line 4
33kV
busbars
NRJED311332EN 353
Protection of Complex 7. Examples
Transmission Circuits
(cont.)
K ZO =
(Zo − Z1 )
3 Z1
∠K ZO =∠
(Zo − Z1 )
3 Z1
For Lines 1 and 2,
Z L1 = 0.177 + j0.402 Ω
(0.439 ∠66.236 Ω)
o
Z LO = 0.354 + j1.022 Ω
(1.082 ∠70.895 Ω)
o
Hence,
K ZO = 0.490
12 ∠K ZO =7.8 o
354 NRJED311332EN
Protection of Complex 7. Examples
Transmission Circuits
(cont.)
(
Z1 = 0.8 ×50 × 0.439 ∠66.236 o Ω )
= 0.8 ×21.95 ∠66.236 o Ω
=17.56 ∠66.236 o Ω
Use a value of 17.56∠66.3 o Ω
It is clear that condition (ii) governs the setting, and therefore the
initial Zone 2 reach setting is:
Z2 = 30.73 ∠66.3 o Ω
The effect of parallel Line 2 is to make relay 1 underreach for faults
on adjacent line sections, as discussed in Chapter “Distance
Protection Schemes” (Section 9.3). This is not a problem for the
phase fault elements because Line 1 will always be protected.
NRJED311332EN 355
Protection of Complex 7. Examples
Transmission Circuits
(cont.)
356 NRJED311332EN
Protection of Complex 7. Examples
Transmission Circuits
(cont.)
NRJED311332EN 357
Protection of Complex 7. Examples
Transmission Circuits
(cont.)
and hence
% Under-reach = 14.3%
358 NRJED311332EN
Protection of Complex 7. Examples
Transmission Circuits
(cont.)
Parameter Parameter
Relay Parameter Units
Description Value
(mag) Line positive sequence impedance (magnitude) 21.95
(ang) Line positive sequence impedance (phase angle) 66.236 deg
(mag) Line zero sequence impedance (magnitude) 54.1
(ang) Line zero sequence impedance (phase angle) 70.895 deg
(mag) Default residual compensation factor (magnitude) 0.49 - 12
(ang) Default residual compensation factor (phase angle) 7.8 deg
(mag) Zone 1 reach impedance setting (magnitude) 17.56
(ang) Zone 1 reach impedance setting (phase angle) 66.3 deg
(mag) Zone 2 reach impedance setting (magnitude) 30.73
(ang) Zone 2 reach impedance setting (phase angle) 66.3 deg
(mag) Zone 3 reach impedance setting (magnitude) 131.8
(ang) Zone 3 reach impedance setting (phase angle) 66.3 deg
Phase fault resistive reach value - Zone 1 84.8
Phase fault resistive reach value - Zone 2 84.8
Phase fault resistive reach value - Zone 3 84.8
(mag) Zone 1 residual compensation factor (magnitude) 0.426 -
(ang) Zone 1 residual compensation factor (phase angle) 9.2 deg
(mag) Zone 2 residual compensation factor (magnitude) not used -
(ang) Zone 2 residual compensation factor (phase angle) not used deg
Time delay - Zone 1 0 s
Time delay - Zone 2 0.25 s
Time delay - Zone 3 0.45 s
Ground fault resistive reach value - Zone 1 84.8
Table 12.3: Ground fault resistive reach value - Zone 2 84.8
Distance relay
settings Ground fault resistive reach value - Zone 3 84.8
NRJED311332EN 359
Protection of Complex 8. References
Transmission Circuits
12.1
Some factors affecting the accuracy of distance type protective
equipment under earth fault conditions.
Davison, E.B. and Wright, A.
Proc. IEE Vol. 110, No. 9, Sept. 1963, pp. 1678-1688.
12.2
Distance protection performance under conditions of single-circuit
working in double-circuit transmission lines.
Humpage, W.D. and Kandil, M.S.
Proc. IEE. Vol. 117. No. 4, April 1970, pp. 766-770.
12.3
Distance protection of tee’d circuits.
Humpage, W.A. and Lewis, D.W.
Proc. IEE, Vol. 114, No. 10, Oct. 1967, pp. 1483-1498.
12
360 NRJED311332EN