Air-Cooled Heat Exchanger Specs

This document provides specifications for an air-cooled heat exchanger including its size, design parameters, performance data for both the tube and air sides, materials, and mechanical equipment details. Key information includes it is an 11.9685 ft by 10.4409 ft unit with 1 bay and 200 finned tubes designed to transfer 1,135,139 BTU/h with inlet and outlet temperatures of 179.19°F and 115.04°F respectively on the tube side.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
461 views2 pages

Air-Cooled Heat Exchanger Specs

This document provides specifications for an air-cooled heat exchanger including its size, design parameters, performance data for both the tube and air sides, materials, and mechanical equipment details. Key information includes it is an 11.9685 ft by 10.4409 ft unit with 1 bay and 200 finned tubes designed to transfer 1,135,139 BTU/h with inlet and outlet temperatures of 179.19°F and 115.04°F respectively on the tube side.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Aspen Exchanger Design and Rating Air Cooled V11 Page 1

File: C:\Users\USUARIO\Desktop\Heat Exchanger Sizing AC-6050 #1.EDR Printed: 28/12/2020 at 09:15:47

API Sheet

Air-Cooled Heat Exchanger Specification Sheet


1 Company:
2 Location:
3 Service of Unit: Our Reference:
4 Item No.: Your Reference:
5 Date: Rev No.: Job No.:
6 Size & Type 11.9685 / 10.4409 ft Type Forced Number of Bays 1
7 Surf/Unit-Finned Tube 11992.7 ft² Bare area/bundle 510.5 ft² Ratio (Total/Bare) 23.49
8 Heat exchanged 1135139 BTU/h MTD, Eff 29.02 °F
9 Transfer Rate-Finned 3.41 Bare, Service 76.61 Clean 80.04 BTU/(h-ft²-F)
10 PERFORMANCE DATA - TUBE SIDE
11 Fluid Circulated 608->609 In / Out
12 Total Fluid Entering lb/h 7142 Density, Liq lb/ft³ / 28.577
13 In / Out Density, Vap lb/ft³ 1.859 / 2.26
14 Temperature °F 179.19 / 115.04 Specific Heat, Liq BTU/(lb-F) / 0.7762
15 Liquid lb/h 0 / 7141 Specific Heat, Vap BTU/(lb-F) 0.5174 / 0.5219
16 Vapor lb/h 7142 / 1 Therm. Cond, Liq BTU/(ft-h-F) / 0.048
17 Noncondensable lb/h 0 / 0 Therm. Cond, Vap BTU/(ft-h-F) 0.015 / 0.013
18 Steam lb/h / Freeze Point °F
19 Water / Bubble / Dew point °F 115.03 / 123.26
20 Molecular wt, Vap 44.23727 / 44.23727 Latent heat BTU/lb
21 Molecular wt, NC Inlet pressure (abs) psi 235.46
22 Viscosity, Liq cp / 0.0817 Pres Drop, Allow/Calc psi 5 / 0.25
23 Viscosity, Vap cp 0.0106 / 0.0098 Fouling resistance ft²-h-F/BTU 0
24 PERFORMANCE DATA - AIR SIDE
25 Air Quantity, Total 343880 lb/h Altitude 0 ft
26 Air Quantity/Fan 78681.9 ft³/min Temperature In 85 °F
27 Static Pressure 0.71 inH2O Temperature Out 98.75 °F
28 Face Velocity 13.51 ft/s Mass velocity 3542.4 lb/h/ft² Design Ambient 80 °F
29 DESIGN-MATERIALS-CONSTRUCTION
30 Design/Vac./Test Pres 300 / / psi Design temperature 400 °F
31 TUBE BUNDLE Header Tube
32 Size ft 11.9685 Type Box Material Carbon Steel
33 Number/bay 1 Material Carbon Steel Specifications
34 Tube Rows 4 Passes 2 OD 1 Min Thk. 0.065 in
35 Arrangement Plug Mat. No./Bun 200 Lng 10 ft
36 Bundles 1 par Gasket Mat. Pitch 2.3622 / 2.0457 30 Degrees
37 Bays 1 par Corr. Allow. in FIN
38 Bundle frame Inlet nozzle ( 1 ) 2.624 in Type G-finned
39 MISCELLANEOUS Outlet nozzle ( 1 ) 1.338 in Material Aluminum 1060
40 Struct. Mount. Special Nozzles OD 2.25 Tks 0.011 in
41 Surf.Prep Rating Program No. 11 #/in Design Temp °F
42 Louvers TI PI Code ASME Code Sec VIII Div 1
43 Vibration Switches Chem Cleaning Stamp Yes Specs
44 MECHANICAL EQUIPMENT
45 Fan,Mfr., Model Driver, Type Program Speed Reducer, Type
46 No./Bay 1 RPM Mfr. Mfr.&Model
47 Dia. 10 ft Blade(s) No./Bay No./Bay
48 Pitch Angle RPM Rating hp
49 Blade(s) Hub Enclosure Ratio
50 hp/Fan 14.4 hp MinAmb V/Phase/Hz / / Support
51 Control Action on Air Failure- Louvers
52 Degree Control of Outlet Process Temperature
53 Recirculation Steam Coil No
54 Plot Area ft² Drawing No. Wt.Bundle 7817.3 Wt. Unit 7817.3 lb
55 Notes:
56
57
58
Aspen Exchanger Design and Rating Air Cooled V11 Page 2
File: C:\Users\USUARIO\Desktop\Heat Exchanger Sizing AC-6050 #1.EDR Printed: 28/12/2020 at 09:15:47

Setting Plan

Inlet 54.1 12.9


& Outlet Tube length 120
Nozzles Bundle slope = 0 deg

274.1

82
234.3
214.3

214.3
98
108
108.1

124.1

Notes: Company:
Location:
Service of Unit: Our Reference:
Item No.: Your Reference:
120 Date: Rev No.: Job No.:
234.2

fan dia (Typ)

Company Name
City, State
Scale:
Rev: Date: Description Dwg. Chk. Appd. ASME VIII-1 2020
Setting Plan
Dwg No.: Rev:
Heat Exchanger Sizin 1