N2LPS LIGHT-PAK™ Cl. I, Div.
2, Groups B, C, D
Cl. I, Zone 2
2L
Emergency Lighting System Cl. II, Div. 2, Groups F, G
Wet Locations, Marine
NEMA 3, 3R, 4X
Ambient 0ºC to 55ºC
Applications: Certifications and
LED N2LPS Light-Pak™ emergency Compliances:
lighting systems are used:
NEC/CEC:
• To provide reliable illumination for egress • Class I, Division 2, Groups B, C, D,
areas during failure or interruption of Zone 2
power to the normal lighting system
UL Standards:
• In areas where flammable gases or
vapors may become present due to • 1598A (Supplemental Requirements for
abnormal, unusual, or accidental Luminaires for Installation on Marine
conditions Vessels)
• In manufacturing plants, refineries, • 924 (Emergency Lighting and Power
petrochemical and chemical plants, Equipment)
waste and sewage treatment facilities, oil • 844 (Electric Luminaires Hazardous
terminals, food processing facilities, Locations)
breweries, and other industrial CSA Standards:
manufacturing or process industry • C22.2 No. 141-M1985 unit equipment for
facilities subject to wet or corrosive emergency lighting
conditions • C22.2 No. 137-M1981 non-incendive
• To illuminate machinery or panels during electrical equipment for use in Class I,
a loss of AC power Division 2 hazardous locations
Electrical Ratings:
• Where moisture, dirt, dust, or corrosion • Life Safety Code NFPA101® – • Power supply –
will limit the life and reliability of ordinary Section 5-9 (Emergency Lighting) Input: 120, 220, 230, 240, or 277 VAC,
emergency lighting systems • Marine wet locations suitability, Type 4X 50 or 60 Hz; 9 watts max.
• Where required by the National Electrical Output: 18 watts max. at 12 VDC
Code®, the Life Safety Code® or other • Luminaire heads –
applicable codes Standard Materials:
Voltage: 12 VDC; Lamp: 3 watt LED
• Outdoor applications • Power supply and remote luminaire
enclosures – Krydon® fiberglass- Total lumen output: 80
reinforced polyester
Features: • LED lamp head assembly – epoxy Unit Net Weights:
• Compact, factory-assembled luminaire powder coated stainless steel • N2LPS12222 – 16 lbs.
featuring LED lamps for improved lumen • Exterior hardware – nylon, plastic coated,
performance, on-time, and lamp life • N2LPS12220 – 12 lbs.
and stainless steel • N2RF1221 – 8 lbs.
• Nonmetallic, enclosed, and gasketed • Cover gasket – Hypalon® synthetic
housing provides corrosion protection in • N2RF1222 – 9 lbs.
rubber
the most extreme environments
• Durable and marine rated LED lamp
Temperature Performance Options:
head assemblies provide protection Description Suffix
against water ingress, corrosion, and Data: 55°C suitability . . . . . . . . . . . . . . . . .S904
impact Based on 55°C ambient
2L
• High temperature rated nickel cadmium Class I, Class II,
battery for reliable operation up to 55ºC Cat. # Division 2 Division 1
ambient 40ºC - T5;
• Solid state battery charger for long life N2LPS (all) T6
55ºC - T4A
and reliable battery operation prevents N2RF (all) T5 T6
deep discharge by automatically Note: Ambient temperature at which the Light-Pak
disconnecting the battery from the system is rated is 0°C to 55°C. Operation at
luminaire temperatures outside this range will affect the
battery life and/or charging performance.
• Factory-installed "push-to-test" button
Note: Battery time in emergency mode is 90 minutes.
• Self-test, monitoring, and diagnostics National Electrical Code and Life Safety Code are
reduce costly maintenance checks registered trademarks of the National Fire Protection
Association, Inc.
• Remote luminaire head assemblies Noryl is a registered trademark of General Electric
(one or two) are available for mounting of Company.
luminaire heads away from main power
system
• Stainless steel drain minimizes moisture
collection
• Standard battery disconnect switch
(Krydon® unit)
[Link] US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business 937
2L N2LPS LIGHT-PAK™ Cl. I, Div. 2, Groups B, C, D
Cl. I, Zone 2
Emergency Lighting System Cl. II, Div. , Groups F, G
Wet Locations, Marine
NEMA 3, 3R, 4X
Ambient 0ºC to 55ºC
Ordering Information:
Description Cat. #
28 watt, 12 volt power supply assembly with two 3 watt LED lamp heads N2LPS12222
28 watt, 12 volt stainless steel power supply assembly with two 3 watt LED lamp heads N2LPS12222 SS
28 watt, 12 volt power supply assembly less luminaire heads N2LPS12220*
Remote luminaire assembly with one 3 watt LED lamp head N2RF1221*
Remote luminaire assembly with two 3 watt LED lamp heads N2RF1222*
28 watt, 120V LED Light-Pak with single sided exit sign** N2LPS12222/120 EXS DR0391734
28 watt, 277V LED Light-Pak with single sided exit sign** N2LPS12222/277 EXS DR0391734
28 watt, 120V LED Light-Pak with double sided exit sign** N2LPS12222/120 EXD DR0391734
28 watt, 277V LED Light-Pak with double sided exit sign** N2LPS12222/277 EXD DR0391734
*Not cUL approved. UL Listed only.
**Exit sign operates in both normal and emergency mode.
Note: Up to four (4) remote LED lamp assemblies can be connected to the N2LPS12222. Up to six (6) remote LED lamp assemblies can be
connected to the N2LPS12220.
Wire Sizing for Remote Installation:
For Copper Wire –
Running Distance† (ft.) Between Power Supply and Remote Luminaire
Load In Watts Load In Watts
Wire Size 8 16 24 32 Wire Size 8 16 24 32
16 AWG 26 13 6 3 10 AWG 106 53 26 13
14 AWG 42 21 10 5 8 AWG 168 84 42 21
12 AWG 66 33 16 8 6 AWG 270 135 67 33
†Maximum distance to limit line voltage drop to 5%.
Dimensions (N2LPS):
1.1
13.5
2L
16.0
7.5
5.0
7.4 13.8
14.5
18.0
Standard – N2LPS LED Light-Pak™
938 [Link] US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
N2LPS LIGHT-PAK™ Cl. I, Div. 2, Groups B, C, D
Cl. I, Zone 2
2L
Emergency Lighting System Cl. II, Div. , Groups F, G
Wet Locations, Marine
NEMA 3, 3R, 4X
Ambient 0ºC to 55ºC
Dimensions (N2LPS):
EXS, EXD Option – N2LPS LED Light-Pak™ with Optional Emergency Exit Luminaire
Dimensions (N2RF):
9.50
9.50
2L
3.83 3.83
7.27 4.38 11.77
Detail Indication Logic:
Status Indication Status Description Status Definition
No Light AC Power Removed from Circuit
* Steady Light (No Blinks) Fully Charged
*-* Light Blinks Once Battery Charging
**-** Light Blinks Twice Battery Failure
***-*** Light Blinks Three Times Circuit Failure
[Link] US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business 939