Envirotemp 360 fluid ™
Synthetic Ester Fluid
Product Description
Envirotemp 360 fluid is a less flammable dielectric liquid ideally suited for use in free-breathing transformers (both new
and retrofill) and is also proven in traction transformers. Envirotemp 360 fluid has been thoroughly evaluated and
conforms to IEC 61099 “Specifications for Unused Synthetic Organic Esters for Electrical Purposes.”
Advantages
• The high fire point (315°C vs 160°C for mineral oil) allows its classification as a K-Class, less flammable liquid.
• It is a high thermal class dielectric liquid, suitable for use in free-breathing applications.
• It continues to flow even in extremely cold climates.
• Envirotemp 360 fluid is optimized for oxidative stability. It surpasses the required performance of the
oxidative stability test of synthetic ester liquidsa even when tested for a period almost 5x longer.
• It is readily biodegradable according to OECD 301B and not classified as hazardous according to GHS.
Envirotemp 360 fluid values and specification units
™
IEC 61099
PROPERTY TEST METHOD PERMISSIBLE VALUES TYPICAL
PHYSICAL
ISO 2211 ≤ 200 Hazen ≤ 100 Hazen
Color
ISO 2049 0.1
Appearance Visually clear, free from water, suspended matter and sediment
Density at 20˚C (kg/dm3) ISO 3675,ISO 12185 ≤ 1000 960
Kinematic viscosity (mm2/s) ISO 3104
100˚C --- 6
40˚C ≤ 35 34
-20˚C ≤ 3000 1700
Flash-point (˚C) ISO 2719 ≥ 250 >283
Fire-point (˚C) ISO 2592 ≥ 300 >315
Pour-point (˚C) ISO 3016 ≤ -45 < -48
CHEMICAL
Water content (mg/kg) IEC 60814 ≤ 200b ≤ 50
Acidity (mg KOH/g) IEC 62021 -1, IEC 62021 -2 ≤ 0.03 0.01 – 0.02
OXIDATION STABILITY
164 h @ 120°C IEC 61125, Method C
Total acidity (mg KOH/g) ≤ 0.3 0.13
Total sludge (% mass) ≤ 0.01 <0.01
800 h @ 120°C IEC 61125, Method C
Total acidity (mg KOH/g) --- 0.21
Total sludge (% mass) --- <0.01
ELECTRICAL
Break down voltage (kV) IEC 60156 ≥ 45b 68
ASTM D1816 59
Dielectric dissipation factor(tanδ) IEC 60247, IEC 61620
90˚C and 50 Hz ≤ 0.03b 0.01
DC resistivity at 90˚C(GΩ.m) IEC 60247 ≥2 60
ª IEC 61099 requires testing synthetic ester liquids according to IEC 61125 method C for 164h. Envirotemp 360 was tested for 800h.
b
for untreated liquid, as received
envirotempfluids.com
Material Compatibility CONTACT
Envirotemp®™ 360 fluid is compatible with most materials used in conventional mineral oil filled transformers.
Some restrictions may exist with materials such as PVC’s, certain silicone rubber formulations, and Contact your sales representative for
polyurethanes. It is recommended to verify the chemical compatibility for each application. pricing and availability of the product
Storage Location Europe (The Netherlands)
Indoor tank storage is preferable. Since the fluid viscosity increases at low temperatures, indoor Cargill Bioindustrial
controlled temperatures reduce the need for heating the fluid to proper pumping and filtering Evert van de Beekstraat 378
temperatures. 1118 CZ Schiphol
The Netherlands
+31 20 500 6695
For outdoor installations, a thermal insulating backfill should be considered for economic advantages.
[email protected] Despite having a low pour point temperature, increased fluid viscosity at low temperatures may make it
difficult to handle.
Europe (Turkey)
Cargill Bioindustrial
Storage Temperature Dilovası 5. Kimya Organize
Envirotemp 360 fluid can be pumped directly from storage tanks. If suction line lengths or suction lift heights San.Bölgesi
Çerkeşli Köyü Yolu, Dilovası,
are excessive, warming of the Envirotemp 360 fluid may be desired to reduce the viscosity.
Kocaeli, Turkey
If heating of Envirotemp 360 fluid is required, the following systems are recommended: Tel: +90 (262) 754 03 03
Faks: +90 (262) 754 03 10
• A circulating pump and piping with a low watt density electric heater (in line) can be attached to the
[email protected] storage tank to maintain temperatures of 38°C (100°F) or higher (i.e., a 76 liter/min (20 GPM) pump
with a 10 kW heater will maintain a temperature of 43°C (110°F) in a 19 m3 (5,000 gal) storage tank if www.envirotempfluids.com
heat losses to the environment are not excessive). The tank and piping should be insulated if ambient
temperatures are low, to help minimize heating costs.
Tanks
Standard steel storage tanks conventionally used for transformer oil are satisfactory. Tanks should conform
to local codes and standards. New tanks are preferred, should have at least one manhole, and should be
protected from moisture by nitrogen blanketing. Before use, the inside of tanks should be sandblasted and
primed with a coating compatible with synthetic ester fluid. Primers used for transformers’ interiors are
recommended. Existing storage tanks that have been used for conventional transformer oil can be used for
Envirotemp 360 fluid if the following conditions are met:
• The tank is of proper capacity and the lines for filling and suction areadequate.
• The tank is thoroughly cleaned and inspected closely for any rusting condition or leakage.
Drum Handling Storage
• The Envirotemp 360 fluid-filled drums are sealed at the factory to protect against foreign
material and moisture contamination during shipping. Seals over the bung plugs assure that the
drum has not been opened.
• When drums of Envirotemp 360 fluid are to be stored, it is good practice to store them in a dry,
temperature-controlled building. It is recommended the drum be stored horizontally with the bungs of
the drum below the level of the fluid inside.
• A drip pan or basin is always recommended for drum storage.
This document is provided for your information and convenience only. All information, statements, recommendations and suggestions are believed to be true and
accurate but are made without guarantee, express or implied. WE DISCLAIM, TO THE FULLEST EXTENT PERMITTED BY LAW, ALL WARRANTIES, EXPRESS OR
IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE and FREEDOM FROM
INFRINGEMENT and disclaim all liability in connection with the storage, handling or use of our products or information, statements, recommendations and suggestions
made by Cargill. All such risks are assumed by you/user. The labeling, substantiation and decision making relating to the regulatory approval status of, the labeling on and