Data sheet 3RT1034-1BB44
Power contactor, AC-3 32 A, 15 kW / 400 V 24 V DC, 2 NO + 2 NC,
3-pole, Size S2 Screw terminal !!! Phased-out product !!! Successor
is SIRIUS 3RT2 Preferred successor type is >>3RT2027-1BB44<<
Product brand name SIRIUS
Product designation power contactor
General technical data
Size of contactor S2
Insulation voltage
● rated value 690 V
Degree of pollution 3
Surge voltage resistance rated value 6 kV
maximum permissible voltage for safe isolation
● between coil and main contacts acc. to EN 400 V
60947-1
Protection class IP
● on the front IP20
● of the terminal IP00
Shock resistance at rectangular impulse
● at DC 10g / 5 ms, 5g / 10 ms
Shock resistance with sine pulse
● at DC 15g / 5 ms, 8g / 10 ms
Mechanical service life (switching cycles)
3RT1034-1BB44 Subject to change without notice
Page 1/8 11/22/2019 © Copyright Siemens
● of contactor typical 10 000 000
● of the contactor with added electronics- 5 000 000
compatible auxiliary switch block typical
● of the contactor with added auxiliary switch 10 000 000
block typical
Reference code acc. to DIN EN 81346-2 Q
Ambient conditions
Installation altitude at height above sea level
● maximum 2 000 m
Ambient temperature
● during operation -25 ... +60 °C
● during storage -55 ... +80 °C
Main circuit
Number of poles for main current circuit 3
Number of NO contacts for main contacts 3
Number of NC contacts for main contacts 0
Operating current
● at AC-1 at 400 V
— at ambient temperature 40 °C rated value 50 A
● at AC-1
— up to 690 V at ambient temperature 40 °C 50 A
rated value
— up to 690 V at ambient temperature 60 °C 45 A
rated value
● at AC-3
— at 400 V rated value 32 A
— at 690 V rated value 20 A
● at AC-4 at 400 V rated value 29 A
Connectable conductor cross-section in main circuit
at AC-1
● at 60 °C minimum permissible 10 mm²
● at 40 °C minimum permissible 16 mm²
Operating current for approx. 200000 operating
cycles at AC-4
● at 400 V rated value 15.6 A
● at 690 V rated value 11 A
Operating current
● at 1 current path at DC-1
— at 24 V rated value 45 A
— at 110 V rated value 4.5 A
● with 2 current paths in series at DC-1
— at 24 V rated value 45 A
3RT1034-1BB44 Subject to change without notice
Page 2/8 11/22/2019 © Copyright Siemens
— at 110 V rated value 25 A
● with 3 current paths in series at DC-1
— at 24 V rated value 45 A
— at 110 V rated value 45 A
Operating current
● at 1 current path at DC-3 at DC-5
— at 24 V rated value 35 A
— at 110 V rated value 2.5 A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V rated value 45 A
— at 110 V rated value 25 A
● with 3 current paths in series at DC-3 at DC-5
— at 24 V rated value 45 A
— at 110 V rated value 45 A
Operating power
● at AC-1
— at 230 V at 60 °C rated value 18 kW
— at 400 V rated value 31 kW
— at 690 V rated value 54 kW
— at 690 V at 60 °C rated value 54 kW
● at AC-2 at 400 V rated value 15 kW
● at AC-3
— at 230 V rated value 7.5 kW
— at 400 V rated value 15 kW
— at 500 V rated value 18.5 kW
— at 690 V rated value 18.5 kW
Operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value 8.2 kW
● at 690 V rated value 10 kW
Thermal short-time current limited to 10 s 320 A
No-load switching frequency
● at DC 1 500 1/h
Operating frequency
● at AC-1 maximum 1 200 1/h
● at AC-2 maximum 750 1/h
● at AC-3 maximum 1 000 1/h
● at AC-4 maximum 250 1/h
Control circuit/ Control
Type of voltage of the control supply voltage DC
Control supply voltage at DC
3RT1034-1BB44 Subject to change without notice
Page 3/8 11/22/2019 © Copyright Siemens
● rated value 24 V
Operating range factor control supply voltage rated
value of magnet coil at DC
● initial value 0.8
● Full-scale value 1.1
Closing power of magnet coil at DC 13.3 W
Holding power of magnet coil at DC 13.3 W
Closing delay
● at DC 50 ... 95 ms
Opening delay
● at DC 20 ... 30 ms
Arcing time 10 ... 15 ms
Auxiliary circuit
Number of NC contacts for auxiliary contacts
● instantaneous contact 2
Number of NO contacts for auxiliary contacts
● instantaneous contact 2
Operating current at AC-12 maximum 10 A
Operating current at AC-15
● at 230 V rated value 6 A
● at 400 V rated value 3 A
Operating current at DC-12
● at 60 V rated value 6 A
● at 110 V rated value 3 A
● at 220 V rated value 1 A
Operating current at DC-13
● at 24 V rated value 10 A
● at 60 V rated value 2 A
● at 110 V rated value 1 A
● at 220 V rated value 0.3 A
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
Contact rating of auxiliary contacts according to UL A600 / Q600
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required fuse gL/gG: 125 A
— with type of assignment 2 required fuse gL/gG: 63 A
● for short-circuit protection of the auxiliary switch fuse gL/gG: 10 A
required
Installation/ mounting/ dimensions
3RT1034-1BB44 Subject to change without notice
Page 4/8 11/22/2019 © Copyright Siemens
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 50022
● Side-by-side mounting Yes
Height 112 mm
Width 55 mm
Depth 179 mm
Required spacing
● for grounded parts
— at the side 6 mm
Connections/ Terminals
Type of electrical connection
● for main current circuit screw-type terminals
● for auxiliary and control current circuit screw-type terminals
Type of connectable conductor cross-sections
● for main contacts
— solid 2x (0.75 ... 16 mm²)
— stranded 2x (0.75 ... 25 mm²)
— single or multi-stranded 2x (0,75 ... 16 mm²)
— finely stranded with core end processing 2x (0.75 ... 16 mm²)
— finely stranded without core end 2x (0.75 ... 16 mm²)
processing
● at AWG conductors for main contacts 2x (18 ... 2)
Type of connectable conductor cross-sections
● for auxiliary contacts
— solid 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG conductors for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14), 1x 12
Certificates/ approvals
3RT1034-1BB44 Subject to change without notice
Page 5/8 11/22/2019 © Copyright Siemens
General Product Approval EMC Functional
Safety/Safety
of Machinery
Type Examination
Certificate
Declaration of Conformity Test Certificates Marine / Ship-
ping
Miscellaneous Type Test Certific- Special Test Certi- Miscellaneous
ates/Test Report ficate
Marine / Shipping other
Miscellaneous Confirmation
Railway
Special Test Certi-
ficate
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
www.siemens.com/sirius/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT1034-1BB44
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT1034-1BB44
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT1034-1BB44
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT1034-1BB44&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT1034-1BB44/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT1034-1BB44&objecttype=14&gridview=view1
3RT1034-1BB44 Subject to change without notice
Page 6/8 11/22/2019 © Copyright Siemens
55 173
35 125
17 5 79
52
45
111
95
64
38
18
3RT103__00000108_000_ALL
Format / Size: DIN A3 Massstab / Scale: 1:1
3RT1034-1BB44 Subject to change without notice
Page 7/8 11/22/2019 © Copyright Siemens
-Q A1(+) 1 /L1 3 /L2 5 /L3 13 21 31 43
A2(-) 2 /T1 4 /T2 6 /T3 14 22 32 44
last modified: 11/19/2019
3RT1034-1BB44 Subject to change without notice
Page 8/8 11/22/2019 © Copyright Siemens