Current Transformer Quality Certificate

This document certifies that a current transformer passed tests according to standard IEC61869-2:2012 and its technical specifications. It provides details of the test results, including measurements of winding resistance, insulation resistance, withstand voltage testing, partial discharge testing, verification of terminal markings, and voltage-ampere performance testing. The current transformer achieved the rated accuracy classes of 0.5/5P20.

Uploaded by

Hoài Sơn Lê
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
88 views2 pages

Current Transformer Quality Certificate

This document certifies that a current transformer passed tests according to standard IEC61869-2:2012 and its technical specifications. It provides details of the test results, including measurements of winding resistance, insulation resistance, withstand voltage testing, partial discharge testing, verification of terminal markings, and voltage-ampere performance testing. The current transformer achieved the rated accuracy classes of 0.5/5P20.

Uploaded by

Hoài Sơn Lê
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

III、

III、Conclusion
This is to certify the subject product which is in conformity with the standard ISO9001 passed
IEC61869-2:2012 and its technical specifications.

Quality Certificate of Current Transformer

Tested

Approved
Dalian No.1 Instrument Transformer Co.,Ltd.
Date 2020-12-17 The People’s Republic of China
、Specifications
I、
Type LZZBJ9-36/250W3b Current ratio 400,800,1200/1/1 A
Accuracy classes 0.5/5P20 I (A)
Insulation level 40.5/70/170 kV Equipment type Indoor U (V)
Rated output 15/15 VA Frequency 50 Hz I (A)
Ith. 25/1 kA/s Polarity Negative U (V)
Serial No. 9120119764 Matched V-A No. / 8. Error test (cosφ=0.8 ) When the burden is less than 5VA,cosφ=1.0
Order No. 4507217641 Altitude / meters.
I1/In (%)
Current Accuracy Sec. Burden
、Test results
II、 ratio class markings (VA)
Error
1 5 20 100 120
(Indoor temperature: 17 ℃ Relative humidity: 50 %)
f (%) 0.00 0.05 0.15 0.15
15
1. DC resistance measurement. δ( ' ) 7.8 2.8 0.9 1.1
400/1 0.5 1S1,1S2
DC resistance measurement of primary winding R1= 17 µΩ. f (%) 0.20 0.20 0.20 0.20
3.75
DC resistance measurement of secondary winding δ( ' ) 5.1 3.8 1.4 1.2
Sec. markings 1S1,1S2 1S1,1S3 1S1,1S4 2S1,2S2 2S1,2S3 2S1,2S4 / / f (%) 0.05 0.05 0.10 0.10
15
R2(Ω) 1.374 2.816 4.327 3.167 6.418 9.747 / / δ( ' ) 3.2 1.6 0.3 0.4
800/1 0.5 1S1,1S3
2. Measurement of winding insulation resistance. f (%) 0.10 0.10 0.10 0.10
3.75
Pri.-sec.& ground: ≥ 2500 MΩ. δ( ' ) 1.9 1.3 0.5 0.5
Sec.-sec.& sec.-ground: ≥ 1000 MΩ. f (%) 0.05 0.05 0.05 0.05
15
3. Short time power frequency withstand voltage test. δ( ' ) 2.3 0.9 0.1 0.1
1200/1 0.5 1S1,1S4
Pri-sec.& ground: 70 kV, 5 min, passed. f (%) 0.05 0.10 0.10 0.10
3.75
Sec.-sec.& sec.-ground: 3 kV, 60 s, passed. δ( ' ) 1.5 0.8 0.3 0.3
4. Induced over -voltage withstand test≤ 4.5 kV(peak voltage), 1 min. f (%) -0.10
15
5. Measurement of partial discharge. δ( ' ) 9.2
400/1 5P20 2S1,2S2
Pre-set applied voltage: 56 kV, test voltage(1.2Um&1.2Um/√3): 48.6/28.1 kV f (%)
apparent discharge level: 24/4 pC. δ( ' )
6. Verification of terminal markings: correct. f (%) 0.05
15
7. V-A performance test δ( ' ) 3.7
800/1 5P20 2S1,2S3
I (A) 0.10 0.20 0.30 0.40 0.50 f (%)
2S1,2S2
U (V) 349 371 379 387 391 δ( ' )
I (A) 0.050 0.075 0.100 0.200 0.300 f (%) 0.10
2S1,2S3 15
U (V) 700 730 746 776 790 δ( ' ) 1.1
1200/1 5P20 2S1,2S4
I (A) 0.025 0.050 0.075 0.100 0.150 f (%)
2S1,2S4
U (V) 1015 1100 1131 1148 1174 δ( ' )