III、
III、Conclusion
This is to certify the subject product which is in conformity with the standard ISO9001 passed
IEC61869-2:2012 and its technical specifications.
Quality Certificate of Current Transformer
Tested
Approved
Dalian No.1 Instrument Transformer Co.,Ltd.
Date 2020-12-17 The People’s Republic of China
、Specifications
I、
Type LZZBJ9-36/250W3b Current ratio 400,800,1200/1/1 A
Accuracy classes 0.5/5P20 I (A)
Insulation level 40.5/70/170 kV Equipment type Indoor U (V)
Rated output 15/15 VA Frequency 50 Hz I (A)
Ith. 25/1 kA/s Polarity Negative U (V)
Serial No. 9120119764 Matched V-A No. / 8. Error test (cosφ=0.8 ) When the burden is less than 5VA,cosφ=1.0
Order No. 4507217641 Altitude / meters.
I1/In (%)
Current Accuracy Sec. Burden
、Test results
II、 ratio class markings (VA)
Error
1 5 20 100 120
(Indoor temperature: 17 ℃ Relative humidity: 50 %)
f (%) 0.00 0.05 0.15 0.15
15
1. DC resistance measurement. δ( ' ) 7.8 2.8 0.9 1.1
400/1 0.5 1S1,1S2
DC resistance measurement of primary winding R1= 17 µΩ. f (%) 0.20 0.20 0.20 0.20
3.75
DC resistance measurement of secondary winding δ( ' ) 5.1 3.8 1.4 1.2
Sec. markings 1S1,1S2 1S1,1S3 1S1,1S4 2S1,2S2 2S1,2S3 2S1,2S4 / / f (%) 0.05 0.05 0.10 0.10
15
R2(Ω) 1.374 2.816 4.327 3.167 6.418 9.747 / / δ( ' ) 3.2 1.6 0.3 0.4
800/1 0.5 1S1,1S3
2. Measurement of winding insulation resistance. f (%) 0.10 0.10 0.10 0.10
3.75
Pri.-sec.& ground: ≥ 2500 MΩ. δ( ' ) 1.9 1.3 0.5 0.5
Sec.-sec.& sec.-ground: ≥ 1000 MΩ. f (%) 0.05 0.05 0.05 0.05
15
3. Short time power frequency withstand voltage test. δ( ' ) 2.3 0.9 0.1 0.1
1200/1 0.5 1S1,1S4
Pri-sec.& ground: 70 kV, 5 min, passed. f (%) 0.05 0.10 0.10 0.10
3.75
Sec.-sec.& sec.-ground: 3 kV, 60 s, passed. δ( ' ) 1.5 0.8 0.3 0.3
4. Induced over -voltage withstand test≤ 4.5 kV(peak voltage), 1 min. f (%) -0.10
15
5. Measurement of partial discharge. δ( ' ) 9.2
400/1 5P20 2S1,2S2
Pre-set applied voltage: 56 kV, test voltage(1.2Um&1.2Um/√3): 48.6/28.1 kV f (%)
apparent discharge level: 24/4 pC. δ( ' )
6. Verification of terminal markings: correct. f (%) 0.05
15
7. V-A performance test δ( ' ) 3.7
800/1 5P20 2S1,2S3
I (A) 0.10 0.20 0.30 0.40 0.50 f (%)
2S1,2S2
U (V) 349 371 379 387 391 δ( ' )
I (A) 0.050 0.075 0.100 0.200 0.300 f (%) 0.10
2S1,2S3 15
U (V) 700 730 746 776 790 δ( ' ) 1.1
1200/1 5P20 2S1,2S4
I (A) 0.025 0.050 0.075 0.100 0.150 f (%)
2S1,2S4
U (V) 1015 1100 1131 1148 1174 δ( ' )