Condenser Design
This document shows how Thermo Utilities, MS Excel Add-ins can be
used for condenser design.
A surface condenser is required to deal with 15 000 kg/h wet steam.
Wet steam temperature is 37 C and enters the condenser with 0.95
quality (dryness fraction is 0.95). The water used for cooling has the
following data:
-inlet pressure 1.20 bar, inlet temperature 7 C
-outlet pressure 1.013 bar, outlet temperature 22 C
Calculate the flow rate of cooling water and tube surface of the
condenser. Assume that the cooling water velocity through tubes is
1.5 m/s
Inputs Units Error ?
Wet steam inlet temperature 37 Err:511
Steam quality 0.95
Cooling water inlet temperature 7 Err:511
Cooling water inlet pressure 1.2 Err:511
Cooling water outlet temperature 22 Err:511
Cooling water outlet pressure 1.013 Err:511
Steam mass flow 15000 kg/h
Cooling water speed 1.5 m/s
Outputs
Wet steam pressure Err:511 Err:511 Err:511
Enthalpy of steam at inlet Err:511 Err:511 Err:511
Enthropy of condensate Err:511 Err:511 Err:511
Rejected heat/hour Err:511 kJ/h
Rejected heat/second Err:511 kW
Enthalpy of water at inlet Err:511 Err:511 Err:511
Enthalpy of water at outlet Err:511 Err:511 Err:511
Water mass flow Err:511 kg/h Err:511
The overall heat tranfer coefficient can be calculated according to BEAMA or HEI standards.
BEAMA : British Electrical and Allied Manufacturers Association
BEAMA publication on the recomended practice for design of surface type steam condenser
HEI : Heat Exchanger Institute
HEI standards for steam surface condensers
file:///conversion/tmp/activity_task_scratch/535045733.xls
Condenser Design
Outputs Unit
Heat transfer coeff.(BEAMA) 2.95235 kW/m2,K
Logarithmic mean temp. diff. 49.83 degree K
Required area Err:511 m2 Err:511
If we use the less conservative HEI method we obtain the following:
Outputs Unit
Heat transfer coeff.(HEI) 3.60991 kW/m2,K
Required area Err:511 m2 Err:511