文档名称 文档密级
DC Distribution Board
Specifications
1 Scope
This specification describes the requirements on the DCDB unit for the communication
shelters.
2 Terminology and Abbreviations
Term Explanation
AC Alternating Current
DC Direct Current
DCDB DC Distribution Board
MTBF Mean Time between Failures
Shall Indicates that the statement is mandatory.
Should Indicates a recommendation.
3 Element Specifications – DC Distribution Board
In this section the performance requirements for the DC Distribution Board are specified.
Each requirement
is numbered and the term “shall” is used to indicate that the requirement is mandatory. The
term
“should” is used when the requirement indicates a recommendation as an optional extra that
can be
added on to the basic unit by means of a modular design.
3.1 Main Technical Parameters
The DC Distribution Board “shall” have the following parameters:
Rated working voltage: DC48V
Maximum input load current: 63A
Output:4 branches 10A, 6 branches 16A, total 10 branches.
All Circuit Breaker must be DC type.
Installation code: install on 19’’ frame.
Insulation resistance: insulation resistance between each live circuit and ground ≥10M
Ω
3.2 Distribution principle
Electric schematic
2021-12-8 华为机密,未经许可不得扩散 第 1 页, 共 3 页
文档名称 文档密级
DC48V
1QF
63A/1P
QF1 QF2 QF3 QF4 QF5 QF6 QF7 QF8 QF9 QF10
10A/1P 10A/1P 10A/1P 10A/1P 16A/1P 16A/1P 16A/1P 16A/1P 16A/1P 16A/1P
Configuration specification of circuit-breaker
SN Name of breaker load Capacity (A) Purpose Remark
1QF Input circuit 63A main breaker single pole
QF1~QF4 DC load 10A branch breaker single pole
QF5~QF10 DC load 16A branch breaker single pole
3.3 The appearance of DC distribution board
The dimension of DCDB: 482.6(L)*170(H)*73.2(D)
The weight of DCDB is about 3.8kg.
2021-12-8 华为机密,未经许可不得扩散 第 2 页, 共 3 页
文档名称 文档密级