Humidity and temperature
transmitter
TH 210
KEY POINTS
- Configurable measuring ranges from 5 to 95%HR and from -40 to +180 °C (according the type
of probe)
- Functions : relative and absolute humidity, dew point, wet and dry temperature and enthalpy
- Stainless steel or polycarbonate probe
- 4 wires analogue output 0-5/10 V or 0/4-20 mA
- Power supply 24 Vdc/Vac or 115/230 Vac
- Trend indicator
- ABS V0 IP65 housing, with or without display
- “¼ turn” system mounting with wall-mount plate
FEATURES OF THE HOUSING
59.2 mm 125 mm
59.2 mm 125 mm Material : ABS V0 as per UL94
Protection : IP65
Display : 75 x 40 mm, LCD 20 digits 2 lines.
115 mm
Height of digits : Values : 10 mm ; Units : 5 mm
190 mm
Cable gland : For cables Ø 8 mm maximum
100 mm
Remote model Weight : 320 g
Ambient model
TECHNICAL FEATURES IN HUMIDITY FUNCTIONS
Class 210 transmitters have two analogue outputs which
Measuring range From 5 to 95%RH
correspond to both displayed parameters. It is possible to
Unit of measurement %RH activate one or two outputs and to select for each
between humidity, temperature and the functions
Accuracy* (Repeatability, linearity, hysteresis) ±1.5%RH (if 15°C ≤ T ≤ 25 °C) described above** :
Drift linked to temperature ±0.04 x (T-20)%RH (if T < 15°C or T > 25°C) Absolute humidity : from 2 to 30 000 g/kg ; unit : 1 g/kg
Resolution 0.1%RH Dew point : from -60 to +100 °Ctd ; unit : 0.1°Ctd / 0.1
°Ftd
Factory calibration uncertainty ±0.88%RH
Dry temperature : from -20 to +102 °C ; unit : 0.1°C /
Response time < 10 seconds (from 10 to 80%RH, Vair = 2 m/s) 0.1 °F
Enthalpy : from 0 to 15 000 Kj/kg ; unit : 0.1 Kj/kg
Type of sensor capacitive
Type of fluid Air and neutral gases
*All accuracies indicated in this technical datasheet were stated in laboratory conditions, and can be guaranteed for measurements carried out in the
same conditions, or carried out with calibration compensation.
As per NFX 15-113 and the Charter 2000/2001 HYGROMETERS, GAL (Guaranteed Accuracy Limit) which has been calculated with a coverage **The default configuration for the output 1 is 0-100%RH in
factor value of 2 is ±2.58%RH between 18 and 28°C on the measuring range from 3 to 98%RH. Sensor drift is less than 1%RH/year. hygrometry and 0-50°C in temperature for the output 2.
PART NUMBER
To order, just add the codes to complete the part number :
TH 210
Type of probe Probe length (mm)
Power supply / Output I : stainless steel 150 : remote
B : 24 Vac/Vdc P : polycarbonate
H : 115 or 230 Vac Display Mounting of the 300 : remote
O : with display probe
D : remote
N : without display
S : ambient
Example : TH210 - BNDP150
Temperature and humidity transmitter, power supply 24 Vac/Vdc, without display, with remote probe in polycarbonate of 150 mm length.
TECHNICAL FEATURES IN TEMPERATURE TECHNICAL SPECIFICATIONS
Measuring range Ambient model : from 0 to +50 °C Power supply
Remote model with polycarbonate probe : from -20 to +80 °C 24 Vac / Vdc ±10 %
Remote model with stainless steel probe : from -40 to +180 °C 115 Vac or 230 Vac ±10 %, 50-60 Hz
Unit of measurement °C / °F
Output
Accuracy* ±0.3 % of reading ±0.25 °C 2 x 4-20 mA or 2 x 0-20 mA ou 2 x 0-5 V ou 2 x 0-
10 V (4 wires)
Response time T90 = 0.9 second for Vair = 1 m/s Maximum load : 500 Ohms (0/4-20 mA)
Minimum load : 1 K Ohms (0-5/10 V)
Resolution 0.1 °C
Type of sensor Pt100 1/3 as per DIN IEC751 Galvanic isolation
Inputs and outputs (models 115 Vac/230 Vac)
Type of fluid Air and neutral gases Outputs (models 24 Vac/Vdc)
*All the accuracies indicated in this technical datasheet were stated in laboratory conditions, and can be guaranteed for
measurements carried out in the same conditions, or carried out with calibration compensation. Consumption
5 VA
TECHNICAL FEATURES OF THE PROBE
Electromagnetical compatibility
➢ White polycarbonate probe EN61326
Measuring range From -20 to +80 °C
Electrical connection
Length of standard probe 100 mm Screw terminal block for cable 2.5 mm²
Length of remote probe 150 or 300 mm (other on request)
PC communication
Cable Silicone Ø4.8 mm, length 2 m (other on request) Kimo USB-Mini Din cable
Environment
Polycarbonate probes are supplied with a flow-through polycarbonate protection tip with a
Air and neutral gases
stainless steel filter 25 µ (ref. : EPP2).
Type of fluid
➢ 316 L stainless steel prone Air and neutral gases
Measuring range From -40 to +180 °C Operating temperature
From 0 to +50 °C
Length of remote probe 150 or 300 mm (other on request)
Cable Silicone Ø4.8 mm, length 2 m (other on request) Storage temperature
From -10 to +70 °C
Stainless steel probes are supplied with a flow through stainless steel protection tip
with a stainless steel filter 25 µ (ref. : EPI25).
➢ Type of tips
Part number EPP2 EPI25 EPI100 EPFI EPFT EPH2O2
Specifications
Tip material PC(1) St. steel(2) St. steel(2) St. steel(2) PTFE(3) MnO2(4)
Filter material St. steel St. steel St. steel St. steel PTFE PTFE
Filter type Meshed Meshed Meshed Sintered Sintered Sintered
Maximum particle 25 µ 25 µ 100 µ 10 µ 50 µ 50 µ
Maximum air velocity 25 m/s 25 m/s 20 m/s 30 m/s 25 m/s 25 m/s
Maximum temperature 120 °C 180 °C 120 °C 180 °C 180 °C 180 °C
Relative humidity maximum 95%RH 95%RH 100%RH 90%RH 90%RH 95%RH External aggression :
Tips protect against the following external
Length 30 mm 30 mm 30 mm 30 mm 30 mm 33 mm
aggressions :
Application ●
Water droplets : EPFT
●
Shaving : EPI25 et EPFI
HVAC air-conditioning system x x x xx x x ●
Dust : EPFI
Cold storage room x x x x x x
●
Chemical product and grease :
EPFT
Industry x x x x x x ● H2O2 (hydrogen peroxide) :
Pharma plants / Microelectronics x x x x x x EPH2O2
(1)
Dryer x x x x x x PC : white polycarbonate
(2)
Stainless steel : 316 L
Curing x x x x x x (3)
PTFE : white Teflon®
(4)
MnO2 : manganese dioxide
Swimming-pool x x x x x x
CONNECTIONS
Analogue outputs (a)
DIP switch
(d)
Type of power
supply of the
transmitter (b)
Power supply
terminal block
(c)
LCC-S software connections
(a)
Cable glands
Analogue output 1 Analogue output 2
(out 1) (out 2)
(c) or (c) or (c)
For power supply 24 For power supply 24 For power supply 230 Vac, 115
Vdc models Vac models Vac models
Ground
0/4-20 mA – Current
0-5/10 V – Voltage
0-5/10 V – Voltage
0/4-20 mA – Current
- Neutral (N)~ Neutral (N)~
GND – Ground
GND – Ground
+ Phase (L)~ Phase (L)~
ELECTRICAL CONNECTIONS – as per NFC15-100 standard
This connection must be made by a qualified technician. To make the connection, the transmitter must not be energized.
Before making the connection, you must first check the power supply indicated on the transmitter board (see (b) on “Connections” part).
➢ For transmitters with 24 Vdc power supply : The selection of the output signal in voltage (0-10 V or 0-5 V) or in current (4-20 mA
or 0-20 mA) is made via the DIP switch (d) of the electronic board of the transmitter :
put the on-of switches as shown in the table below :
-
Power supply -
Configurations 4-20 mA 0-10 V 0-5 V 0-20 mA
24 Vdc
+ +
➢ For transmitters with 24 Vac power supply : Combinations
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Power supply 24 Vac ~
class II
~
Pe ~ Vac N~ ➢ Connection of the output ➢ Connection of output in
N
230 Vac Vac L~ in current 4-20 mA : voltage 0-10 V :
L ~
or 0-5/10 V 0/4-20 mA 0-5/10 V 0/4-20 mA
- + + -
Pe
N N
N
230 Vac
L L
L
Power supply
➢ For transmitters with 115 or 230 Vac power A V
supply : Regulator display or Regulator display or
Ground PLC/BMS passive PLC/BMS passive
Neutral type type
Power supply
115 / 230 Vac 4-20 mA output 0-10 V output
Phase
CONFIGURATION OF THE TRANSMITTERS
It is possible on the class 210 to configure all the parameters of the transmitter : units, measuring ranges, outputs, channels, calculation
functions, etc, via different methods :
●
Keypad for models with display : a code-locking system allows to secure the installation (See class 210 user manual).
● Software (optional) on all models. Simple user-friendly configuration. See LCC-SD user manual.
Configurable analogue output :
Range with center zero (-40/0/+40 °C), with offset zero (-30/0/+70 °C) or standard range (0/+100 °C), It is possible to configure your own
intermediary ranges
Caution : the minimum difference between the high range and the low range is 20.
Configure the range according to your needs : outputs are automatically adjusted to the new measuring range
-40 °C 0 +180 °C -40 °C 0 50 +180°C
FTang – transmitter_TH210 – 02/04/13 – RCS (24) Périgueux 349 282 095 Non-contractual document – We reserve the right to modify the characteristics of our products without prior notice.
New range
0V 10 V
4 mA 20 mA 0V 10 V
4 mA 20 mA
75 mm
MOUNTING 37.5 mm
40 mm
To mount the transmitter, mount the ABS plate on the wall (drilling : Ø6 mm, screws and
pins are supplied).
23.75 mm
Insert the transmitter on the fixing plate (see A on the drawing beside). Rotate the 8 mm
housing in clockwise direction until you hear a “click” which confirms that the transmitter
is correctly installed.
50 mm
68 mm
14 mm 4.5 mm
7.5 mm
CALIBRATION
Outputs diagnostic : With this function, you can check with a multimeter (or on a regulator / display, or a PLC / BMS) if the transmitter outputs
work properly. The transmitter generates a voltage of 0 V, 5 V and 10 V or a current of 4 mA, 12 mA and 20 mA
Certificate : Class 210 transmitters are supplied with adjusting certificates. Calibration certificates are available as an option.
MAINTENANCE
Please avoid any aggressive solvent. Please protect the transmitter and its probes from any cleaning product containing formalin, that may be
used for cleaning rooms or ducts.
OPTIONS AND ACCESSORIES
● LCC-S : configuration software with USB cable ●
Sliding fittings ●
Protections tips
●
Calibration certificate ●
Connection fittings ●
Wall-mounting support
●
Cable glands bracket for remote humidity
probe