Thatch Roof Guard House

The document provides details of the construction plans for a rammed earth house with the following key elements: 1. It will have rammed earth walls that are 300mm thick on the north and west sides supported by reinforced concrete foundation walls. 2. Columns made of 200mm diameter H4 CCA treated gum poles will support the structure and be installed in compliance with SANS 10407 standards. 3. Other elements include a sliding gate, driveways, and a thatched grass roof.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (5 votes)
3K views2 pages

Thatch Roof Guard House

The document provides details of the construction plans for a rammed earth house with the following key elements: 1. It will have rammed earth walls that are 300mm thick on the north and west sides supported by reinforced concrete foundation walls. 2. Columns made of 200mm diameter H4 CCA treated gum poles will support the structure and be installed in compliance with SANS 10407 standards. 3. Other elements include a sliding gate, driveways, and a thatched grass roof.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Floor Plan and Elevations: Illustrates the overall layout of the building, including floor plan and all four elevations (north, south, east, and west).
  • Detail Sections: Contains detailed sectional views and architectural details focusing on specific construction elements.

sand cement ridge capping

A B

fine thatching grass roof


driveway driveway

200mm Ø H4 CCA

3000
treated gum pole
existing game 300x700mm column - in compliance
rammed earth wall rammed rammed earth wall

3180
farm fence reinforced concrete with SANS 10407
earth wall

300
foundation wall
300

sliding gate 200mm Ø H4 CCA treated gum pole


5200 column- in compliance with SANS 10407 reinforced concrete
NGL reinforced concrete foundation wall driveway driveway reinforced concrete foundation wall NGL
foundation wall
D1 guard D1
300mm thick
5000
house North Elevation
4400
rammed earth wall
ceramic
tiles 300mm thick 300mm thick existing game 1 : 100
rammed earth wall rammed earth wall farm fence
100 000
W1 W1 5200
200mm Ø H4 CCA treated gum pole

300
column- in compliance with SANS 10407 sliding gate
150 150

300

reinforced concrete foundation wall

300 1400 300 200 300 200


fine thatching grass roof
700 3000 700 2000 700 3000 700

driveway driveway

A B rammed earth wall

NORTH rammed earth wall 200mm Ø H4 CCA


treated gum pole
W1 column - in compliance
with SANS 10407
D1

Floor Plan
1 : 100
NGL reinforced concrete foundation wall NGL

East Elevation
1 : 100

40mm sand cement capping, slightly


thickendat the ridge sand cement ridge capping
100mm Ø H4 CCA treated gum pole ridge brace
- in compliance with SANS 10407
03 100mm Ø H4 CCA treated gum pole ridge collar
- in compliance with SANS 10407 fine thatching grass roof
2
100mm Ø H4 CCA treated gum pole king post
- in compliance with SANS 10407
100mm Ø H4 CCA treated gum pole rafter brace
- in compliance with SANS 10407
1920

100mm Ø H4 CCA treated gum pole rafter


- in compliance with SANS 10407 200mm Ø H4 CCA

3000
treated gum pole
150mm Ø H4 CCA treated gum pole bottom column - in compliance

3085
rammed earth wall rammed rammed earth wall
longitudinal brace - in compliance with SANS 10407 with SANS 10407 earth wall
150mm Ø H4 CCA treated gum pole bottom
02 chord tie beam - in compliance with SANS 10407
2 200mm Ø H4 CCA treated gum pole ring beam reinforced concrete foundation wall reinforced concrete
NGL driveway driveway reinforced concrete foundation wall NGL
- in compliance with SANS 10407 foundation wall

175mm thick fine thatching grass layer with South Elevation


1 : 100
Micon Thatchsayf high-pressure
spray as per specialist

25mm Ø H4 CCA treated gum pole laths


- in compliance with SANS 10407
3000

W1 sand cement ridge capping Name


300mm thick rammed earth wall
Trisha van der Merwe
Student number
D1
2100

213002244
01 fine thatching grass roof
200mm Ø H4 CCA treated gum pole column Project description
2
- in compliance with SANS 10407
40mm thick granolithic screed on 85mm thick concrete
surface bed on 250 micron pollylethen damp proof
membrane on 150mm compacted filling Assignment 6
385

300mm thick reinforced concrete foundation wall Thatch Roof Construction


NGL NGL rammed earth wall
670

rammed earth wall 200mm Ø H4 CCA


treated gum pole
W1
column - in compliance
D1 with SANS 10407
300x800mm concrete 300x800mm concrete Drawing number & description
strip foundation strip foundation
reinforced concrete foundation wall Plan, Elevations, Section and 3 Details
NGL NGL
Date OUT Date IN Sheet No./No
28 September 2021 26 October 2021
Section A-A
1 : 50
West Elevation
1 : 100
Scale
1:100 1:50
1/2
40mm sand cement capping, slightly
thickendat the ridge
100mm Ø H4 CCA treated gum pole ridge brace 175mm thick fine thatching grass layer with 3,15mm thick galvanized wire
- in compliance with SANS 10407 sways covering 70mm fine thatching grass fixed to 25mm Ø
100mm Ø H4 CCA treated gum pole ridge collar H4 CCA treated gum pole laths with tar-treated sisal binding
- in compliance with SANS 10407 twine spaced 110mm c/c
100mm Ø H4 CCA treated gum pole rafter
100mm Ø H4 CCA treated gum pole king post - in compliance with SANS 10407
- in compliance with SANS 10407
100mm Ø H4 CCA treated gum pole rafter brace
Micon Thatchsayf high-pressure
0.6mm Galvanised corrogated - in compliance with SANS 10407
spray as per specialist
sheetmetal roof covering with flashings fixed M12 bolt and nut fixing rafter to tie beam
100mm Ø H4 CCA treated gum pole rafter
to 38x38mm H4 CCA treated SA Pine purlins on
- in compliance with SANS 10407
a 38x114mm H4 CCA treated SA Pine truss with
38x114mm H4 CCA treated SA Pine wall plate 150mm Ø H4 CCA treated gum pole bottom 25mm Ø H4 CCA treated gum pole laths 200mm Ø H4 CCA treated gum pole ring beam
longitudinal brace - in compliance with SANS 10407 spaced 200mm c/c fixed to rafter with - in compliance with SANS 10407
150mm Ø H4 CCA treated gum pole bottom 75x2,8mm round wire nails
chord tie beam - in compliance with SANS 10407 - in compliance with SANS 10407
200mm Ø H4 CCA treated gum pole ring beam 150mm Ø H4 CCA treated gum pole bottom
- in compliance with SANS 10407 chord tie beam - in compliance with SANS 10407

175mm thick fine thatching grass layer with


Micon Thatchsayf high-pressure
6.4mm thick gypsum plaster ceiling board fixed to spray as per specialist
38x38mm H4 CCA treated SA Pine brandering
25mm Ø H4 CCA treated gum pole laths
- in compliance with SANS 10407
base nail plate rammed earth wall
W1

400x16mm thread bar with sharpened point


D1 300mm thick rammed earth wall driven into post fixed woth M16 nut and washer

20mm thick ceramic tiles on 30mm thick cement screed on


85mm thick concrete surface bed on 250 micron pollylethen damp
proof membrane on 150mm compacted filling
300mm thick reinforced concrete foundation wall
NGL NGL 200mm Ø H4 CCA treated gum pole column
- in compliance with SANS 10407

300x800mm concrete 300x800mm concrete


strip foundation strip foundation

Section B-B
1 : 50
Detail 2
1 : 10

200mm Ø H4 CCA treated gum pole column


D1
- in compliance with SANS 10407

300mm thick rammed earth wall

10mm thick mild steel purpose made guide support


braket welded to 260x660x20mm mild steel base plate

40mm sand cement capping, RS PRO carbon steel anchor system fixed with
slightly thickendat the ridge M20x260mm net and washer

20
galvanised wire mesh reinforcement

260
250 micron pollylethen damp proof
membrane

385
100mm overlap with polyoefin membrane

300mm thick reinforced concrete foundation wall


Micon Thatchsayf high-pressure

85
spray as per specialist bull nose edge
40mm thick granolithic screed
85mm thick concrete surface bedon 250 micron
175mm thick fine thatching grass layer pollylethen damp proof membrane
with 3,15mm thick galvanized wire
sways covering 70mm fine
thatching grass fixed to 25mm Ø NGL 150mm compacted filling
H4 CCA treated gum pole laths
with tar-treated sisal binding
twine spaced 110mm c/c

Name

670
Trisha van der Merwe
Student number
213002244
100mm Ø H4 CCA treated gum
Project description
25mm Ø H4 CCA treated gum pole laths pole ridge collar
spaced 200mm c/c fixed to rafter with - in compliance with SANS 10407
75x2,8mm round wire nails 300
- in compliance with SANS 10407 Assignment 6
100mm Ø H4 CCA treated gum pole
ridge brace- in compliance with SANS 10407 Thatch Roof Construction
100mm Ø H4 CCA treated gum pole rafter 100mm Ø H4 CCA treated gum pole king post
- in compliance with SANS 10407 - in compliance with SANS 10407

300
300x800mm concrete
strip foundation Drawing number & description
Plan, Elevations, Section and 3 Details

Date OUT Date IN Sheet No./No


28 September 2021 26 October 2021

Detail 3
1 : 10
Detail 1
1 : 10
800
Scale
1:50 1:10
2/2

NORTH
200mm Ø H4 CCA treated gum pole
column- in compliance with SANS 10407
sliding gate
sliding gate
200mm Ø H4 CCA treated
100mm Ø H4 CCA treated gum pole rafter
- in compliance with SANS 10407
200mm Ø H4 CCA treated gum pole ring beam
- in complia