Rosemount 648 Wireless Temperature Transmitter: Reference Manual
Rosemount 648 Wireless Temperature Transmitter: Reference Manual
00809-0100-4648, Rev BA
August 2007
www.rosemount.com
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
NOTICE
Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure to thoroughly understand the contents before
installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1-800-999-9307 (7:00 a.m. to 7:00 P.M. CST)
National Response Center
1-800-654-7768 (24 hours a day)
Equipment service needs
International
1-(952) 906-8888
The products described in this document are NOT designed for nuclear-qualified
applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware
or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact a Emerson Process
Management Sales Representative.
Rosemount 648 Wireless Temperature Transmitter may be protected by one or more U.S.
Patents pending. Other foreign patents pending.
www.rosemount.com
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
NOTICE
The Rosemount 648 and all other wireless devices should be installed only after the
1420 Wireless Gateway has been installed and is functioning properly. Wireless devices
should also be powered up in order of proximity from the 1420 Wireless Gateway,
beginning with the closest. This will result in a simpler and faster network installation.
NOTICE
Shipping considerations for wireless products (Lithium Batteries):
The unit was shipped to you without the battery installed. Please remove the battery pack
from the unit prior to shipping.
Primary lithium batteries are regulated in transportation by the U. S. Department of
Transportation, and are also covered by IATA (International Air Transport Association),
ICAO (International Civil Aviation Organization), and ARD (European Ground
Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure
compliance with these or any other local requirements. Please consult current regulations
and requirements before shipping.
The battery pack with the wireless unit contains two “C” size primary
lithium/thionyl chloride batteries. Each battery contains approximately 2.5
grams of lithium, for a total of 5 grams in each pack. Under normal conditions,
the battery materials are self-contained and are not reactive as long as the
batteries and the pack integrity are maintained. Care should be taken to
prevent thermal, electrical or mechanical damage. Contacts should be
protected to prevent premature discharge.
Battery hazards remain when cells are discharged.
Batteries should be stored in a clean and dry area. For maximum battery life,
storage temperature should not exceed 30° C.
Reference Manual
00809-0100-4648, Rev AA
August 2007 Rosemount 648
Table of Contents
Shipping considerations for wireless products (Lithium Batteries):. 0-2
TOC-1
Reference Manual
00809-0100-4648, Rev AA
Rosemount 648 August 2007
TOC-2
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Section 1 Overview
SAFETY MESSAGES Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
www.rosemount.com
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
OVERVIEW
1-2
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
• The integral LCD conveniently displays the primary sensor input and
diagnostics of the transmitter
• Simple and easy installation practices already used today for robust
installations
Refer to the following literatures for a full range of compatible connection
heads, sensors, and thermowells provided by Emerson Process
Management.
• English Temperature Sensors and Assemblies Product Data Sheet,
Volume 1 (document number 00813-0100-2654)
• Temperature Sensors and Accessories (Metric Sensors) Product Data
Sheet, Volume 2 (document number 00813-0200-2654)
CONSIDERATIONS
Mechanical Location
When choosing an installation location and position, take into account the
need for access to the transmitter. For best performance, the antenna should
be vertical with some space between objects in a parallel metal plane such as
a pipe or metal framework, as the pipes or framework may adversely affect
the performance of the antenna.
Electrical Battery
The Rosemount 648 Wireless Temperature transmitter is battery powered.
The battery pack with the wireless unit contains 2 “C” size primary
lithium/thionyl chloride batteries. Each battery contains approximately 2.5
grams of lithium, for a total of 5 grams in each pack. Under normal conditions,
the battery materials are self-contained and are not reactive as long as the
batteries and the battery pack are maintained. Care should be taken to
prevent thermal, electrical or mechanical damage. Contacts should be
protected to prevent premature discharge.
Use caution when handling the battery pack. The battery pack may be
damaged if dropped from heights in excess of 20 feet.
Sensor
Make sensor connections through the cable entry in the side of the
connection head. Be sure to provide adequate clearance for cover removal.
1-3
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
Environmental Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Temperature Effects
The transmitter will operate within specifications for ambient temperatures
between –40 and 185 °F (–40 and 85 °C). Heat from the process is
transferred from the thermowell to the transmitter housing. If the expected
process temperature is near or beyond specification limits, consider the use of
additional thermowell and extension, or remote mounting the transmitter to
thermally isolate it from the process.
Figure 1-1 provides an example of the relationship between transmitter
housing temperature rise and thermowell extension length.
40 (72)
815 °C (1500 °F) Process Temperature
55 30 (54)
20 (36)
540 °C (1000 °F) Process Temperature
10 (18)
250 °C (482 °F) Process Temperature
0
3 4 5 6 7 8 9
4.2 Extension Length (in.)
Example
The transmitter specification limit is 85 °C. If the ambient temperature is 55 °C
and the max process temperature to be measured is 815 °C, the maximum
permissible connection head temperature rise is the transmitter specification
limit minus the ambient temperature (moves 85 to 55 °C), or 30 °C.
In this case, an extension of 5” meets this requirement, but 6” provides an
additional margin of thermowell protection, thereby reducing risk of ambient
thermal damage.
Temperature Limits
Operating Limit Storage Limit
With LCD Display –4 to 175 °F –40 to 185 °F
–20 to 80 °C –40 to 85 °C
Without LCD Display –40 to 185 °F –40 to 185 °F
–40 to 85 °C –40 to 85 °C
1-4
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
RETURN OF MATERIALS To expedite the return process in North America, call the Emerson Process
Management National Response Center toll-free at 800-654-7768. This
center, available 24 hours a day, will assist you with any needed information
or materials.
The center will ask for the following information:
• Product model
• Serial numbers
• The last process material to which the product was exposed
The center will provide
• A Return Material Authorization (RMA) number
• Instructions and procedures that are necessary to return goods that
were exposed to hazardous substances
For other locations outside North America, please contact an Emerson
Process Management sales representative for further instructions.
NOTE
If the device has been exposed to a hazardous substance, a Material Safety
Data Sheet (MSDS) must be included with the returned materials. An MSDS
is required by law to be available to people exposed to specific hazardous
substances.
1-5
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
1-6
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Section 2 Configuration
SAFETY MESSAGES Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
www.rosemount.com
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
Sensor Connections The 648 is compatible with a number of RTD and thermocouple sensor types.
Figure 2-1 shows the correct input connections to the sensor terminals on the
transmitter. To ensure a proper sensor connection, anchor the sensor lead
wires into the appropriate compression terminals and tighten the screws.
Thermocouple or Millivolts Inputs
The thermocouple can be connected directly to the transmitter. Use
appropriate thermocouple extension wire if mounting the transmitter remotely
from the sensor. Make millivolt inputs connections with copper wire. Use
shielding for long runs of wire.
RTD or Ohm Inputs
The transmitters will accept a variety of RTD configurations, including 2-wire,
3-wire, 4-wire. If the transmitter is mounted remotely from a 3-wire or 4-wire
RTD, it will operate within specifications, without recalibration, for lead wire
resistances of up to 5 ohms per lead (equivalent to 500 feet of 20 AWG wire).
In this case, the leads between the RTD and transmitter should be shielded. If
using only two leads, both RTD leads are in series with the sensor element,
so significant errors can occur if the lead lengths exceed three feet of 20 AWG
wire (approximately 0.05 °C/ft.). For longer runs, attach a third or fourth lead
as described above.
Sensor Lead Wire Resistance Effect—RTD Input
When using a 4-wire RTD, the effect of lead resistance is eliminated and has
no impact on accuracy. However, a 3-wire sensor will not fully cancel lead
resistance error because it cannot compensate for imbalances in resistance
between the lead wires. Using the same type of wire on all three lead wires
will make a 3-wire RTD installation as accurate as possible. A 2-wire sensor
will produce the largest error because it directly adds the lead wire resistance
to the sensor resistance. For 2- and 3-wire RTDs, an additional lead wire
resistance error is induced with ambient temperature variations. The table and
the examples shown below help quantify these errors.
2-2
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Figure 2-1. Sensor Wiring
Diagrams Thermocouple/mV 4 Wire RTD and Ω
*Emerson Process Management provides 4-wire sensors for all single element RTDs.
Use these RTDs in 3-wire configurations by leaving the unneeded leads disconnected
and insulated with electrical tape.
Red (3)
Red (4)
2-3
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
Red (3)
Red (4)
Type K
+ Green (2)
– White (3)
Note:
Wire color examples apply to Emerson sensors, but will vary by manufacturer.
2-4
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Examples of Approximate Lead Wire Resistance Effect Calculations
Given:
Total cable length 150 m
Imbalance of the lead wires at 20 °C 0.5 Ω
Resistance/length (18 AWG Cu): 0.025 Ω/m
Temperature coefficient of Cu (αCu) 0.039 Ω/Ω °C
Temperature coefficient of Pt (αPt) 0.00385 Ω/Ω °C
Change in Ambient Temperature (ΔTamb) 25 °C
RTD Resistance at 0 °C (R0) 100 Ω (for Pt 100 RTD)
0.5 Ω
Basic Error = (0.00385 Ω / Ω °C) x (100 Ω) = 1.3 °C
2-5
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
Sensor Leads
If the sensor is installed in a high-voltage environment and a fault condition or
installation error occurs, the sensor leads and transmitter terminals could
carry lethal voltages. Use extreme caution when making contact with the
leads and terminals.
Use the following steps to wire the sensor and supply power to the
transmitter:
1. Remove the transmitter enclosure cover (if applicable).
2. Attach the sensor leads according to the wiring diagrams.
3. Connect the battery.
4. Verify the connection by observing the LCD.
5. Reattach and tighten the cover (if applicable).
DEVICE SENSOR Every temperature sensor has unique characteristics. In order to ensure the
CONFIGURATION most accurate measurement, the Rosemount 648 should be configured to
match the specific sensor that it will be connected to.
Begin by removing the battery-side housing cover. This will expose the
terminal block and HART communication terminals. Connect the battery to
supply power for configuration.
The Rosemount 648 will receive any HART communications from a handheld
Field Communicator, or AMS. When using a Field Communicator, any
configuration changes must be sent to the transmitter by using the Send key
(F2). AMS configuration changes are implemented when the Apply button is
clicked.
AMS Wireless and Direct Connections
AMS is capable of connecting to devices either directly, using a HART
modem, or wirelessly via the 1420. When configuring on the bench using a
HART modem, double click the device icon (or right click and select
Configure/Setup), then choose the Configure/Setup tab. Configure the device
settings using the Direct Connection menu. When configuring wirelessly via
the 1420, double click the device icon (or right click and select
Configure/Setup), then choose the Configure/Setup tab. Configure the device
settings using the Wireless Connection menu.
To check or change sensor configuration using a 375 Field Communicator,
enter the following Fast Key Sequence: 1, 3, 2, 1.
When the device configuration is 2 wire or 3 wire, terminal 4 of the device
must be left disconnected. If connected, a configuration error may be
indicated, which then prevents the device from providing process temperature
measurements.
DEVICE NETWORK In order to communicate with the 1420 Wireless Gateway, and ultimately the
CONFIGURATION Information System, the transmitter must be configured to communicate with
the wireless network. This step is the wireless equivalent of connecting wires
from a transmitter to the information system.
2-6
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Using a Field Communicator or AMS, enter the Network ID and Join Key so
that they match the Network ID and Join Key of the gateway and other
devices in the network. If the Network ID and Join Key are not identical, the
transmitter will not communicate with the network. The Network ID and Join
Key may be obtained from the 1420 Wireless Gateway on the
Setup>Network>Settings page on the web server.
The final device network configuration piece is the Update Rate. This by
default is 5 minutes. This may be changed at commissioning, or at any time
via AMS or the 1420 Wireless Gateway’s web server. The Update Rate
should be between 15 seconds and 60 minutes. For networks of up to 100
wireless devices, fastest Update Rate is 60 seconds. For networks of 50 or
fewer devices, the fastest Update Rate is 15 seconds
When device configuration is completed, remove the battery and replace the
battery cover. Tighten the cover to the proper tension for safety approvals.
To access the Network Settings using a 375 Field Communicator, enter the
following Fast Key Sequence: 1, 3, 3.
3
4
P/N 00753-9200-0020
3
4 COMM
2-7
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
HART Menu Tree Options listed in bold type indicate that a selection provides other options. For
ease of operation, changing calibration and setup, such as sensor type,
number of wires, and range values, can be completed in several locations.
2-8
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Fast Key Sequence Table 2-2 lists the fast key sequences for common transmitter functions.
NOTE:
The fast key sequences assume that DD Dev v1, DD v4 is being used.
2-9
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
Perform a sensor trim if the transmitters digital value for the primary variable
does not match the plant’s standard calibration equipment. The sensor trim
function calibrates the sensor to the transmitter in temperature units or raw
units. Unless your site-standard input source is NIST-traceable, the trim
functions will not maintain the NIST-traceability of the system.
The Sensor Input Trim command allows the transmitter’s interpretation of the
input signal to be digitally altered. The sensor reference command trims, in
engineering (°F, °C,°R, K) or raw (Ω, mV) units, the combined sensor and
transmitter system to a site standard using a known temperature source.
Sensor trimming is suitable for validation procedures or for applications that
require calibrating the sensor and transmitter together.
Use the following procedure to perform a sensor trim with a 648:
1. Connect the calibration device or sensor to the transmitter. Refer to
Figure 2-1 on page 2-3 or on the device terminal block for sensor
wiring diagrams.
2. Connect the communicator to the transmitter.
3. From the Home screen, select 1 Device Setup, 2 Diagnostics and
Service, 2 Calibration, 1 Sensor Trim to prepare to trim the sensor.
4. Select 1 Lower Sensor Trim or 2 Upper Sensor Trim. (Note: It is
recommended to perform lower offset trims first, before performing
upper slope trims).
5. Answer the question about using an active calibrator or not.
6. Adjust the calibration device to the desired trim value (must be within
the selected sensor limits). If a combined sensor and transmitter
system are being trimmed, expose the sensor to a known
temperature and allow the temperature reading to stabilize. Use a
bath, furnace or isothermal block, measured with a site-standard
thermometer, as the known temperature source.
7. Select OK once the temperature stabilizes. The communicator
displays the output value the transmitter associates with the input
value provided by the calibration device.
8. Select the appropriate sensor trim units at the prompt.
9. Enter the trim point.
AMS
For AMS, configure the sensor as indicated above.
Right click on the device and select “Methods>Calibrate>Sensor Calibration”
from the menu. Select “Lower Input Trim” or “Upper Limit Trim.”
The wizard will continue through the process.
The transmitter may be restored to the factory default by selecting:
“Methods>Calibrate>Sensor Calibration>Revert to Factory Trim.”
The wizard will recall the factory trim for a given sensor.
Apply changes
2-10
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Transmitter-Sensor Matching
Perform the Transmitter Sensor Matching procedure to enhance the
temperature measurement accuracy of the system (see the comparison
below) and if you have a sensor with Callendar-Van Dusen constants. When
ordered from Emerson Process Management, sensors with Callendar-Van
Dusen constants are NIST-traceable.
The 648 accepts Callendar-Van Dusen constants from a calibrated RTD
schedule and generates the actual curve to match that specific sensor curve.
Actual Curve
Resistance, Ohm
0 °C
Temperature, °C
(1) The Actual Curve is identified from the Callendar-Van Dusen equation.
2-11
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
NOTE
When the transmitter-sensor matching is disabled, the transmitter reverts to
factory trim. Make certain the transmitter engineering units default correctly
before placing the transmitter into service.
Alerts Alerts allow the user to configure the transmitter to output a HART message
Fast Keys 1, 3, 4, 4 when the configured data point is exceeded. A process alert will be
transmitter continuously if the set points are exceeded and the alert mode is
ON. An alert will be displayed on a Field Communicator, AMS status screen or
in the error section of the LCD display. The alert will reset once the value
returns within range.
NOTE
HI alert value must be higher than the LO alert value. Both alert values must
be within the temperature sensor limits.
Assigned Value
Time
Deadband
Time
2-12
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Field Communicator
To configure the process alerts with a Field Communicator, perform the
following procedure:
1. From the HOME screen, follow the fast key sequence “Alerts” (1
Device Setup, 3 Configuration, 4 Device Output Configuration, 4
Alerts).
2. Select 1 for HI-HI Alert.
Select 2 for HI Alert
Select 3 for LO Alert
Select 4 for LO-LO Alert
3. Select 1 to configure the alert.
AMS
Right click on the device and select “Configure/Setup” from the menu.
1. On the “Alerts” Page, press the “Configure Alert” button for each of
the process alerts desires (1 per tab). Follow the prompts from the
alert configuration wizard.
REMOVE BATTERY After the sensor and network have been configured, remove the battery pack
and replace the transmitter cover. The battery pack should be inserted only
when the device is ready to be commissioned.
2-13
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
2-14
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Section 3 Mounting
SAFETY MESSAGES Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
www.rosemount.com
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
MOUNTING The Rosemount 648 can be installed in one of two configurations: Direct
Mount, where the sensor is connected directly to the 648 housing’s conduit
entry, or Remote Mount, where the sensor is mounted separate from the 648
housing, then connected to the 648 via conduit. Choose the installation
sequence that corresponds to the mounting configuration.
Figure 3-1 provides an example of the relationship between transmitter
housing temperature rise and extension length.
Ambient °C (°F)
40 (72)
815 °C (1500 °F) Process Temperature
55 30 (54)
20 (36)
540 °C (1000 °F) Process Temperature
10 (18)
250 °C (482 °F) Process Temperature
0
3 4 5 6 7 8 9
4.2 Extension Length (in.)
Example
The transmitter specification limit is 85 °C. If the ambient temperature is 55 °C
and the max process temperature to be measured is 815 °C, the maximum
permissible connection head temperature rise is the transmitter specification
limit minus the ambient temperature (moves 85 to 55 °C), or 30 °C.
In this case, an extension of 5” meets this requirement, but 6” provides an
additional margin of thermowell protection, thereby reducing risk of ambient
thermal damage.
Direct Mount The direct mount installation should not be used when installing with a
Swagelok® fitting.
1. Install the sensor/thermocouple according to standard installation
practices. Be sure to use thread sealant on all connections.
2. Attach the 648 housing to the sensor/thermocouple using the
threaded conduit entry.
3. Attach the sensor/thermocouple wiring to the terminals as indicated
on the wiring diagram.
4. Connect the battery pack if commissioning the device.
NOTE
Use caution when handling the battery pack. The battery pack may be
damaged if dropped from heights in excess of 20 feet.
3-2
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
NOTE:
Wireless devices should be powered up after the 1420 Wireless Gateway and
in order of proximity from the 1420, beginning with the closest device to the
1420. This will result in a simpler and faster network installation.
3-3
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
NOTE
Use caution when handling the battery pack. The battery pack may be
damaged if dropped from heights in excess of 20 feet.
NOTE:
Wireless devices should be powered up after the 1420 Wireless Gateway and
in order of proximity from the 1420, beginning with the closest device to the
1420. This will result in a simpler and faster network installation.
3-4
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
LCD Display Transmitters ordered with the LCD display will be shipped with the display
installed.
The optional LCD display can be rotated in 90-degree increments by
squeezing the two tabs, pulling out, rotating and snapping back into place.
If LCD pins are inadvertently removed from the interface board, carefully
re-insert the pins before snapping the LCD display back into place.
Use the following procedure and Figure 3-2 to install the LCD display:
1. Remove the LCD cover. Do not remove the instrument covers in
explosive environments when the circuit is live.
2. Put the four-pin connector into the LCD display, rotate to the desired
position and snap into place.
Note the following LCD temperature limits:
Operating:–4 to 175 °F (–20 to 80 °C)
Storage:–40 to 185 °F (–40 to 85 °C)
3. Replace the transmitter cover.
NOTE
Only use Rosemount Wireless LCD Part Number: 00753-9004-0002.
LCD
Cover
Ground the Transmitter The transmitter will operate with the housing either floating or grounded.
However, the extra noise in floating systems affects many types of readout
devices. If the signal appears noisy or erratic, grounding the transmitter at a
single point may solve the problem.
The electronics enclosure should be grounded in accordance with local and
national installation codes. This can be accomplished via the process
connection, via the internal case grounding terminal, or via the external
grounding terminal.
Thermocouple, mV, and RTD/Ohm Inputs
Each process installation has different requirements for grounding. Use the
grounding options recommended by the facility for the specific sensor type, or
begin with grounding Option 1 (the most common).
3-5
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
Option 1:
1. Connect sensor wiring shield to the transmitter housing (only if the
housing is grounded).
2. Ensure the transmitter housing is electrically isolated from the sensor
wiring.
Transmitter
Sensor Wires
Option 2:
1. Ground sensor wiring shield at the sensor.
2. Ensure that the sensor wiring and shield is electrically isolated from
the transmitter housing.
Transmitter
Sensor Wires
NOTE:
Always use facility recommended wiring practices.
3-6
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Section 4 Commissioning
SAFETY MESSAGES Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
NOTE
The Rosemount 648 and all other wireless devices should be installed only
after the 1420 Wireless Gateway has been installed and is functioning
properly.
Wireless devices should also be powered up in order of proximity from the
1420 Wireless Gateway, beginning with the closest device to the 1420. This
will result in a simpler and faster network installation.
www.rosemount.com
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
VERIFY OPERATION Operation can be verified in three locations, at the device via the Local
Display, using the 375 Field Communicator, or at the Gateway via the 1420
Wireless Gateway’s integrated web server.
Local Display
During normal operation, the LCD will display the PV value at the wireless
transmit rate up to as fast as 1 minute intervals. Refer to LCD Screen
Messages on page 5-2 for error codes and other LCD messages. Press the
Diagnostic button to display the TAG, Device ID, Network ID, Network Join
Status and Device Status screens. For Device Status screens, see LCD
Screen Messages on page 5-2
4-2
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
If the Rosemount 648 was configured with the Network ID and Join Key and
sufficient time for network polling has passed, the transmitter will be
connected to the network. To verify connectivity, open the 1420 Wireless
Gateway’s integral web interface and navigate to the Explorer>Status page.
This page will display the transmitter’s tag, PV, SV, TV, QV, Last Update,
Update Rate, Battery Voltage, and Status. A green status indicator means that
the device is working properly. A red indicator means that there is a problem
with either the device or its communication path. For more detail on a specific
device, click on the tag name.
Troubleshooting
The most common cause of incorrect operation is the Network ID and Join
Key. The Network ID and Join Key in the device must match that of the 1420
Wireless Gateway. The Network ID and Join Key may be obtained from the
1420 Wireless Gateway on the Setup>Network>Settings page on the web
server.
4-3
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
4-4
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
SAFETY MESSAGES Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
www.rosemount.com
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
LCD SCREEN
MESSAGES
Startup Screen The following screens will display when the battery is first connected to the
Sequence Rosemount 648.
5-2
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
TERM
SV Screen - terminal temperature value
2 5. 0 0
deg c
DEV
TV Screen - feature board temperature value
2 5. 2 5
deg c
Diagnostic Button The following five screens will display when the device is operating properly
Screen Sequence and the Diagnostic Button has been pressed.
5-3
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
id - XX
Device Identification: used to determine Device ID
XXXXXX
Network Diagnostic These screens display the network status of the device. Only one will be
Status Screens shown during the startup sequence or diagnostic sequence.
5-4
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
a -srch
p -srch
5-5
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
sync
reset
Device Diagnostic The following screens will show the device diagnostics depending on the state
Screens of the device.
5-6
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
TERM
SV Screen - terminal temperature value
2 5. 0 0
deg c
DEV
TV Screen - feature board temperature value
2 5. 2 5
deg c
5-7
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
5-8
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
NOTE
Use the Rosemount Wireless LCD Part Number: 00753-9004-0002.
(1) Reference conditions are 70° F (21° C), transmit rate of once per minute, and routing data
for three additional network devices.
5-9
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
Handling Considerations
The battery pack with the wireless unit contains 2 “C” size primary
lithium/thionyl chloride batteries. Each battery contains approximately 2.5
grams of lithium, for a total of 5 grams in each pack. Under normal conditions,
the battery materials are self-contained and are not reactive as long as the
batteries and the battery pack integrity are maintained. Care should be taken
to prevent thermal, electrical or mechanical damage. Contacts should be
protected to prevent premature discharge.
Use caution when handling the battery pack. The battery pack may be
damaged if dropped from heights in excess of 20 feet.
Battery hazards remain when cells are discharged.
Environmental Considerations
As with any battery, local environmental rules and regulations should be
consulted for proper management of spent batteries. If no specific
requirements exist, recycling through a qualified recycler is encouraged.
Consult the materials safety data sheet for battery specific information.
Shipping Considerations
The unit is shipped to you without the battery installed. Unless specifically
instructed to do otherwise, remover the battery pack from the unit prior to
shipping.
Primary lithium batteries are regulated in transportation by the U.S.
Department of Transportation, and are also covered by International Air
Transport Association (IATA), International Civil Aviation Organization (ICAO),
and European Ground Transportation of Dangerous Goods (ARD). It is the
responsibility of the shipper to ensure compliance with these or any other
local requirements. Please consult current regulations and requirements
before shipping.
5-10
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
SPECIFICATIONS
Functional Input
Specifications Supports Thermocouple, RTD, millivolt and ohm input types. See Accuracy on
page A-3 for sensor options.
Output
Wireless enabled, linear with temperature or input.
Local Display
The optional five-digit integral LCD Display can display engineering units (°F,
°C, °R, K, Ω, and millivolts). Display updates at transmit rate up to once per
minute.
Humidity Limits
0–100% relative humidity
Transmit Rate
User selectable, 15 sec. to 60 min.
Accuracy
(PT 100 @ reference conditions: 20 °C)
±0.45 °C (±0.81 °F)
(1) Reference conditions are 70° F (21° C), transmit rate of once per minute, and routing data
for three additional network devices.
www.rosemount.com
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
Materials of Construction
Enclosure
Housing
• Low-copper aluminum
Paint
• Polyurethane
Cover O-ring
• Buna-N
Terminal Block and Battery Pack
• PBT
Antenna
• PBT/PC integrated omnidirectional antenna
Mounting
Transmitters may be attached directly to the sensor. Mounting brackets also
permit remote mounting. See “Dimensional Drawings” on page A-5.
Weight
648 without LCD - 4.6 lbs. (2 kg)
648 with M5 LCD - 4.7 lbs (2.1 kg)
Transmitter Stability
The 648 has a stability of ±0.3% of output reading or 0.3 °C (whichever is
greater) for 24 months
Self Calibration
The analog-to-digital measurement circuitry automatically self-calibrates for
each temperature update by comparing the dynamic measurement
to extremely stable and accurate internal reference elements.
Vibration Effect
Less than ±0.1% of URL when tested per the requirements of IEC60770-1
field with general application or pipeline with low vibration level (10-60 Hz
0.15 mm displacement peak amplitude/60-500 Hz 2g).
A-2
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Accuracy
TABLE 1. Rosemount 648 Input Options and Accuracy.
Sensor Sensor Input Digital
Options Reference Ranges Accuracy(1)
2-, 3-, 4-wire RTDs °C °F °C °F
Pt 50 (α = 0.003910) GOST 6651-94 -200 to 550 -328 to 990 ± 0.9 ± 1.62
Pt 100 (α = 0.00385) IEC 751, 1995 (α = 0.00385) –200 to 850 –328 to 1562 ± 0.45 ± 0.81
Pt 100 (α = 0.003910) GOST 6651-94 -200 to 550 -328 to 990 ± 0.45 ± 0.81
Pt 100 (α = 0.003916) JIS 1604, 1981 (α = 0.003916) –200 to 645 –328 to 1193 ± 0.45 ± 0.81
Pt 200 (α = 0.00385) IEC 751, 1995 (α = 0.00385) –200 to 850 –328 to 1562 ± 0.81 ± 1.458
Pt 200 (α = 0.003916) JIS 1604, 1981 (α = 0.003916) –200 to 645 –328 to 1193 ± 0.81 ± 1.458
Pt 500 IEC 751, 1995 (α = 0.00385) –200 to 850 –328 to 1562 ± 0.57 ± 1.026
Pt 1000 IEC 751, 1995 (α = 0.00385) –200 to 300 –328 to 572 ± 0.57 ± 1.026
Ni 120 Edison Curve No. 7 –70 to 300 –94 to 572 ± 0.45 ± 0.81
Cu 10 Edison Copper Winding No. 15 –50 to 250 –58 to 482 ± 4.16 ± 7.488
Cu 50 (α = 426) GOST 6651-94 -50 to 200 -122 to 392 ±1.44 ± 2.592
Cu 50 (α = 428) GOST 6651-94 -185 to 200 -365 to 392 ±1.44 ± 2.592
Cu 100 (α = 426) GOST 6651-94 -50 to 200 -122 to 392 ±0.72 ± 1.296
Cu 100 (α = 428) GOST 6651-94 -185 to 200 -365 to 392 ±0.72 ± 1.296
Thermocouples(2)
Type B(3) NIST Monograph 175, IEC 584 100 to 1820 212 to 3308 ± 2.25 ± 4.05
Type E NIST Monograph 175, IEC 584 –50 to 1000 –58 to 1832 ± 0.60 ± 1.08
Type J NIST Monograph 175, IEC 584 –180 to 760 –292 to 1400 ± 1.05 ± 1.89
Type K(4) NIST Monograph 175, IEC 584 –180 to 1372 –292 to 2502 ± 1.46 ± 2.628
Type N NIST Monograph 175, IEC 584 –200 to 1300 –328 to 2372 ± 1.46 ± 2.628
Type R NIST Monograph 175, IEC 584 0 to 1768 32 to 3214 ± 2.25 ± 4.05
Type S NIST Monograph 175, IEC 584 0 to 1768 32 to 3214 ± 2.1 ± 3.78
Type T NIST Monograph 175, IEC 584 –200 to 400 –328 to 752 ± 1.05 ± 1.89
GOST L GOST R 8.585-2001 -200 to 800 -392 to 1472 ± 1.80 ± 3.24
DIN Type L DIN 43710 –200 to 900 –328 to 1652 ± 1.05 ± 1.89
DIN Type U DIN 43710 –200 to 600 –328 to 1112 ± 1.05 ± 1.89
Type W5Re/W26Re ASTM E 988-96 0 to 2000 32 to 3632 ± 2.1 ± 3.78
Millivolt Input –10 to 100 mV ± 0.045 mV
2-, 3-, 4-wire Ohm Input 0 to 2000 ohms ± 1.35 ohm
(1) The published digital accuracy applies over the entire sensor input range. Digital output can be accessed by HART Communications or wireless protocol.
(2) Total digital accuracy for thermocouple measurement: sum of digital accuracy +0.8 °C. (cold junction accuracy)
(3) Digital accuracy for NIST Type B T/C is ±9.0 °C (±16.2 °F) from 100 to 300 °C (212 to 572 °F).
(4) Digital accuracy for NIST Type K T/C is ±2.1 °C (±3.79 °F) from –180 to –90 °C (–292 to –130 °F).
A-3
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
Transmitters can be installed in locations where the ambient temperature is between –40 and 85 °C (–40 and 185 °F). In order to maintain
excellent accuracy performance, each transmitter is individually characterized over this ambient temperature range at the factory.
A-4
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
DIMENSIONAL DRAWINGS
648 Remote Mount
3.457
(87.8)
A-5
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
ORDERING INFORMATION
Model Product Description
648 Temperature Transmitter
Code Transmitter Type
D Wireless Field Mount
Code Output
X Wireless
Code Measurement
1 Single Sensor
Code Housing Metal
D Dual Compartment Housing - Aluminum AL
Code Conduit Threads
1 1/2-14 NPT
Code Certifications
I5 FM Intrinsically Safe, Non-incendive
I6 CSA Intrinsically Safe
I1 ATEX Intrinsically Safe
I7 IECEx Intrinsically Safe
NA No Approval
Code Wireless Options
Wireless Transmit Rate
WA User Configurable Transmit Rate
Operating Frequency and Protocol
1 2.4 GHz DSSS, HART
2 900 MHz FHSS, HART
Antenna
WK Omnidirectional, Integral Antenna
SmartPower™
1 Long-life Intrinsically Safe Battery Pack
Meter
M5 LCD Meter
Configuration
C1 Factory Configure Date, Descriptor, & Message Fields
Filter
F6 60 Hz Line Voltage Filter
F5 50 Hz Line Voltage Filter
Trim
C2 Transmitter-Sensor Matching - Trim to specific Rosemount RTD Calibration Schedule (CVD Constants)
5-Point Calibration
C4 5-Point Calibration (requires Q4 option code to generate a calibration certificate)
Calibration Certificate
Q4 Calibration Certificate (3-Point Calibration with Certificate)
Cable Gland
G2 Cable Gland (7.5 mm - 11.9 mm)
G4 Thin Wire Cable Gland (3 mm - 8 mm)
Sensor Options
XA Assemble to Transmitter, Sensor Specified Separately
Typical Model Number: 648 D X 1 D 1 NA WA 2 WK 1 M5 C1 F6
A-6
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Telecommunication All wireless devices require certification to ensure that they adhere to
Compliance regulations regarding the use of the RF spectrum. Nearly every country
requires this type of product certification. Emerson is working with
governmental agencies around the world to supply fully compliant products
and remove the risk of violating country directives or laws governing wireless
device usage. To see which countries our devices have received certification
for use in, see www.rosemount.com/smartwireless.
FCC and IC This device complies with Part 15 of the FCC Rules. Operation is subject to
the following conditions: This device may not cause harmful interference, this
device must accept any interference received, including interference that may
cause undesired operation.
This device must be installed to ensure a minimum antenna separation
distance of 20 cm from all persons.
European Union The EC declaration of conformity for all applicable European directives for this
Directive Information product can be found on the Rosemount website at www.rosemount.com. A
hard copy may be obtained by contacting your local sales representative.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
Electro Magnetic Compatibility (EMC) (89/336/EEC)
EN 50081-1: 1992; EN 50082-2: 1995;
EN 61326-1: 1997 — Industrial
Radio and Telecommunications Terminal Equipment Directive (R&TTE)
(1999/5/EC)
Emerson Process Management complies with the R&TTE Directive.
www.rosemount.com
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
Ordinary Location As standard, the transmitter has been examined and tested to determine that
Certification for FM the design meets basic electrical, mechanical, and fire protection requirements
by FM, a nationally recognized testing laboratory (NRTL) as accredited by the
Federal Occupational Safety and Health Administration (OSHA).
B-2
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
IECEx Certifications
I7 IECEx Intrinsic Safety
Certificate No.: IECEx BAS 07.0007
Ex ia IIC T6 (Tamb = -60 °C to 50 °C)
Ex ia IIC T5 (Tamb = -60 °C to 75 °C)
IP66
For use with Rosemount battery pack P/N 753-9220-XXXX only
Table B-2. Sensor Parameters
Sensor
Uo = 6.6 V
Io = 3.6 mA
Po = 23.3 mW
Co = 11 uF
Lo = 500 mH
Table 1.
Country Restriction
Bulgaria General authorization required for outdoor use and public service
France Outdoor use limited to 10mW e.i.r.p.
Italy If used outside of own premises, general authorization is required.
Norway May be restricted in the geographical area within a radius of 20 km
from the center of Ny-Alesund.
Romania Use on a secondary basis. Individual license required.
Radio Power Label - see Figure B1- indicates output power configuration of
the radio. Devices with this label are configured for output power less than 10
mW e.i.r.p. At time of purchase the customer must specify ultimate country of
installation and operation.
Figure B-1.
B-3
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
B-4
Reference Manual
00809-0100-4648, Rev BA
August 2007 Rosemount 648
Figure B-3. CSA Installation Drawing
B-5
Reference Manual
00809-0100-4648, Rev BA
Rosemount 648 August 2007
B-6
Reference Manual
00809-0100-4648, Rev BA
August 2007
The Emerson logo is a trade mark and service mark of Emerson Electric Co.
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
PlantWeb is a registered trademark of one of the Emerson Process Management group of companies.
HART is a registered trademark of the HART Communication Foundation.
Lexan and Noryl are registered trademark of General Electric.
All other marks are the property of their respective owners.
¢00809-0100-4728g¤
© 2007 Rosemount Inc. All rights reserved.