HEAT LOAD CALCULATION HOTTEST MONTH 5 Location-BANGALORE
project PIZZAHUT-CMH Lattitude Altitude Daily Range condition DB(°F) WB(°F) Rh(%) w(gr/lb)
area KITCHEN 13.18 °N 821ft 22°F outside air 99 78 45 110
length(ft) width(ft) area(sq ft) height(ft) volume(cu ft) room 75 64 50 64
Room size
500 9.5 4750 Diff 24 14 -5 46
SENSIBLE HEAT BTU/HR OUTSIDE AIR cfm
SOLAR GAIN-glass 500 sq ft X 0.3 cfm/sqft 150
Direction Area(sqft) Solar gain solar factor 20 people 16 cfm/person 320
NORTH 0 41 0.78 0 470
EAST 0 165 0.78 0
WEST 0 165 0.78 0
SOUTH 0 14 0.78 0
TRANSMISSION GAIN -Walls and Roof INFILTRATION
Direction Area(sqft) ETD U Value 4750 vol/60 0.5 Air ch/hr 39.583333
NORTH 0 21 0.34 0
EAST 160 24 0.34 1305.6
WEST 0 50 0.34 0
SOUTH 420 32 0.34 4569.6 0
ROOF 0 49 0.21 0
TRANSMISSION GAIN -OTHER NET OUTSIDE AIR 430.4167
space area temp diff uvalue
All glasses 0.0 24 1.13 0 EFFECTIVE SHF AND ADP
Non ac partions-glass 0 19 0.5 0
Non ac partions 200 19 0.42 1596
Non ac floor 0 19 0.39 0 ESHF = ERSH/ 31350.37
0.7554525
INFILTRATION AND OUTSIDE AIR ERTH 41498.8
CFM temp diff B.F C.F SEL ADP 50.99 °f
INFILTRATION 39.58333 24 1.08 1026 DEHUMDIFICATION AIR RISE
BYPASSED OUTSIDE
430.4167 24 0.1 1.08 1115.64 = 21.609
AIR
INTERNAL HEAT DEHUMIDIFIED AIR QUANTITY
BTU/HR/PR;BALLAST
NOS;HP;WATT FACTOR;USAGE
C.F FACTOR = 1343.3349102 CFM
People 20 305 6100 Check figures
lights 1500 1.25 3.41 6393.75 SQFT/TON 92.64329
Appliance 2500 0.75 3.41 6393.75 CFM/SQFT 2.68667
miscellaneous 0 0.75 0
TOTAL ROOM SENSIBLE HEAT 28500.34
CORRECTION FACTOR 9
SAFETY FACTOR 2850.034
EFFECTIVE ROOM SENSIBLE HEAT 31350.374 ACH VALUE
LATENT HEAT EXPWALL SUMMER WINTER
NOS;CFM
BTU/HR/PR;GRAIN DIFF
C.F BF 1 0.25 0.5
People 20 345 6900 2 0.5 0.75
INFILTRATION 39.583333 46 0.68 1238.1666667 3 0.75 1
BYPASSED
430.41667 46 0.68 0.1 1346.3433333 4 1 1.25
OUTSIDE AIR
TOTAL ROOM LATENT HEAT 9484.51
SAFETY FACTOR 663.9157
EFFECTIVE ROOM LATENT HEAT 10148.4257 U VALU E
EFFECTIVE ROOM TOTAL HEAT 41498.7997 ROOF 0.21
OUTSIDE AIR HEAT FLOOR 0.39
CFM
TEMP DIFF/GRAIN DIFF
C.F (1-BF) PARTN WALL 0.42
Sens Heat 430.41667 24 1.08 0.9 10040.76 WALL 0.36
Latent Heat 430.41667 46 0.68 0.9 12117.09
TOTAL OUTSIDE HEAT 22157.85
SAFETY FACTOR 1107.8925
EFFECTIVE OUTSIDE HEAT 23265.7425
GRAND TOTAL HEAT 64764.5422 EQUIPMENT LOAD 0
FOOD LOAD 0
TON OF REFRIGERATION 5.397045 TR
HOTTEST
HEAT LOAD CALCULATION MONTH 5 Location-BANGALORE
project PIZZAHUT-CMH Lattitude Altitude Daily Range condition DB(°F) WB(°F) Rh(%) w(gr/lb)
area LOBBY 13.18 °N 821ft 22°F outside air 99 78 45 110
length(ft) width(ft) area(sq ft) height(ft) volume(cu ft) room 75 64 50 64
Room size
700 8 5600 Diff 24 14 -5 46
SENSIBLE HEAT BTU/HR OUTSIDE AIR cfm
SOLAR GAIN-glass 700 sq ft X 0.18 cfm/sqft 126
Direction Area(sqft) Solar gain solar factor 56 people 7.5 cfm/person 420
NORTH 400 33 0.78 10296 546
EAST 150 165 0.78 19305
WEST 0 165 0.78 0
SOUTH 0 14 0.78 0
TRANSMISSION GAIN -Walls and Roof INFILTRATION
Direction Area(sqft) ETD U Value 5600 vol/60 0 Air ch/hr 0
NORTH 0 21 0.34 0
EAST 0 24 0.34 0
WEST 0 50 0.34 0
SOUTH 0 32 0.34 0 0
ROOF 0 45 0.21 0
TRANSMISSION GAIN -OTHER NET OUTSIDE AIR 546
space area temp diff uvalue
All glasses 550.0 24 1.13 14916 EFFECTIVE SHF AND ADP
Non ac partions-glass 0 19 0.5 0
Non ac partions 200 19 0.42 1596
Non ac floor 0 19 0.39 0 ESHF = ERSH/ 78934.06
0.8244498
INFILTRATION AND OUTSIDE AIR ERTH 95741.5
CFM temp diff B.F C.F SEL ADP 51.32 °f
INFILTRATION 0 24 1.08 0 DEHUMDIFICATION AIR RISE
BYPASSED OUTSIDE
546 24 0.1 1.08 1415.232 = 21.312
AIR
INTERNAL HEAT DEHUMIDIFIED AIR QUANTITY
BTU/HR/PR;BALLAST
NOS;HP;WATT FACTOR;USAGE
C.F FACTOR = 3429.3866 CFM
People 56 250 14000 Check figures
lights 1500 1.25 3.41 6393.75 SQFT/TON 61.55876
Appliance 1500 0.75 3.41 3836.25 CFM/SQFT 4.899124
miscellaneous 0 0.75 0
TOTAL ROOM SENSIBLE HEAT 71758.232
CORRECTION FACTOR 9
SAFETY FACTOR 7175.8232
EFFECTIVE ROOM SENSIBLE HEAT 78934.0552 ACH VALUE
LATENT HEAT EXPWALL SUMMER WINTER
NOS;CFM
BTU/HR/PR;GRAIN DIFF
C.F BF 1 0.25 0.5
People 56 250 14000 2 0.5 0.75
INFILTRATION 0 46 0.68 0 3 0.75 1
BYPASSED
546 46 0.68 0.1 1707.888 4 1 1.25
OUTSIDE AIR
TOTAL ROOM LATENT HEAT 15707.888
SAFETY FACTOR 1099.55216
EFFECTIVE ROOM LATENT HEAT 16807.44016 U VALU E
EFFECTIVE ROOM TOTAL HEAT 95741.49536 ROOF 0.21
OUTSIDE AIR HEAT FLOOR 0.39
CFM
TEMP DIFF/GRAIN DIFF
C.F (1-BF) PARTN WALL 0.42
Sens Heat 546 24 1.08 0.9 12737.088 WALL 0.36
Latent Heat 546 46 0.68 0.9 15370.992
TOTAL OUTSIDE HEAT 28108.08
SAFETY FACTOR 1405.404
EFFECTIVE OUTSIDE HEAT 29513.484
GRAND TOTAL HEAT 136454.97936
FOOD LOAD 11200
TON OF REFRIGERATION 11.3712 TR