Join Probie Manual
Join Probie Manual
DANIEL A. NIGRO
Fire Commissioner
Updated: 03/12/2021
PROBATIONARY FIREFIGHTERS MANUAL
TABLE OF CONTENTS – VOLUME ONE
CHAPTER SUBJECT
INTRODUCTION
ORIENTATION
1. GENERAL DEPORTMENT: SUBSTANCE POLICY
2. CHEMISTRY OF FIRE
3. FIRE DEPARTMENT APPARATUS
4. SAFETY
5. ROPE
6. SELF CONTAINED BREATHING APPARATUS (SCBA)
7. COMMUNICATIONS
8. BUILDING CONSTRUCTION
9. BUILDING DESCRIPTIONS
Probationary Firefighters Manual
INTRODUCTION
It was not until 74 years later, in 1731, that fire brigades were put into service. Two hand-drawn
pumpers, brought from distant London were the first fire engines to be used in the colony. They
were designated as Engine Company 1 and Engine Company 2. All able bodied citizens were
required to respond to alarms and perform duty under the supervision of the Aldermen.
Faced with the problem of a fast growing colony, the General Assembly established the
volunteer Fire Department of the City of New York, in December of 1737. Able, discreet and
sober men were appointed as firemen to be ready for service by night and day and be diligent,
industrious and vigilant.
Following the Revolutionary War, the Department was reorganized and incorporated as the
Fire Department of the City of New York.
The volunteer Fire Department continued to protect the lives and property of the citizens of the
city until after the close of the Civil War when, in 1865, they were superseded by the paid
Metropolitan Fire Department. The change created resentment and bitter actions were taken by
some who opposed the elimination of the volunteers. This resulted in rough and tumble battles
fought on both personal and political levels.
The introduction of the steam engine spelled the final doom of the volunteer department in New
York. The steam apparatus eliminated the need for men to pump the water, and the horses ended
the problem of hauling engines by hand.
1
At the beginning, the paid fire service extended
only to certain parts of New York City
(Manhattan). The Act of 1865 united Brooklyn
and New York (cities) to form a Metropolitan
District. By the end of 1865 the department
consisted of 13 Chief Officers and 552
Company Officers and firemen. They worked a
continuous tour of duty, with 3 hours a day for
meals and one day off a month. They were paid
salaries according to their rank or grade. The
first regulations were also formulated and they
were fairly strict and straight-laced.
First Company of paid Fire Department to go "in
The volunteers, despite their disappointment, service" was Engine Co. 1, located in lower Manhattan
at 4 Centre Street. Apparatus was horse-drawn
accepted the decision and publicly declared that Amoskeag steam-powered pumper which was same
they would continue to function and serve until type issued to later companies. Wheels were steel
rimmed.
properly relieved by paid units.
The Act provided that members of the volunteers were to be given preference over all others in
filling the rolls of the paid department.
Due to major fires, which resulted in excessive fire losses and a rise in insurance rates, the
department was reorganized in 1866 under the command of General Alexander Schaler. Under
military discipline, the department began to realize its full potential and fire losses began to
generally reduce.
The merit system of promotion in the Fire Department was instituted in 1870.
In 1874 Westchester County (later called the Bronx) was annexed and gradually volunteers there
were replaced by companies of the paid department, until the last volunteer unit was disbanded
in 1928.
A further consolidation occurred in 1887 covering what we now know as the Borough of
Queens. Again volunteer units were gradually replaced by paid companies until, by 1929, this
Borough was protected by the paid department of the City of New York.
Richmond became a part of the greater City of New York in 1898. No change in the volunteer
status took place, except for nominal supervision, until 1905 when the first group of volunteers
was disbanded and replaced by paid units. More paid companies were installed in 1915, 1928,
1932 and 1937, when all but two volunteer companies were disbanded. These two were the only
legal volunteer companies still active in the City of New York.
New Year's Day 1898 heralded the consolidation of the different areas of the city and the
beginning of a new era for the Fire Department. All fire forces in the various sections were
brought under the unified command of the first Commissioner of the Fire Department.
Following this amalgamation many changes took place involving many aspects of the job
including installation of the high pressure systems, motorization of fire apparatus, creation of a
Marine fleet, adoption of vastly improved working conditions and the utilization of perfected
radio communications.
2
Today the Fire Department protects more than 8,000,000 residents in an area of 320 square
miles. The department is administered by the Fire Commissioner appointed by and responsible to
the Mayor. The uniformed force is under the command of the Chief of Department and consists
of more than 11,400 Fire Officers and fire fighters. In addition, the Department includes 2,800
Emergency Medical Technicians, Paramedics and Supervisors assigned to the Bureau of
Emergency Medical Service (EMS), as well as 1200 civilian employees.
3
PROBATIONARY
FIREFIGHTERS SCHOOL
ORIENTATION
ORIENTATION
On behalf of the Fire Commissioner and the Chief of Department, welcome to the
New York City fire Academy. Each of you have passed the written and physical
examinations and further being qualified both mentally and medically, have demonstrated
a fine potential for service to the city of New York and to the people who live and work
here.
Your success in training can make you part of the greatest firefighting force in the
world.
1
ORIENTATION
WORK HOURS: ______________________
REPORTING TIME: ______________________
Above items shall be worn to and from the Fire Academy each day.
We suggest you compose a PERSONAL DATA SHEET to assist you in
completing the many forms that you will be receiving during orientation. Some of the
information that will be needed is listed below.
2
ORIENTATION
Probies shall park their automobiles in the parking lot located outside the
Academy. The parking lot is across from the main gate as you enter the Fire Academy
grounds.
1) Automobiles belonging to Firefighters 6th Grade are prohibited from
parking inside the Academy Gates.
2) Commercial vehicles – such as tow trucks, dump trucks, trucks with
advertising, etc. are prohibited.
Probies requesting medical leave shall promptly notify, or where necessary, have
a responsible person notify, Probationary Firefighter School and the medical leave desk
prior to 0700 by telephone of any injury or illness that requires the granting of medical
leave.
Probies shall report to the Bureau of Health Services at headquarters on the same
day unless otherwise instructed.
When a trainee is admitted to or discharged from a hospital, he/she shall
promptly notify the P.F.S. Office. If personal notification can not be made, notification
shall be made by a responsible person.
Any notices received which might be of interest to the Fire Department must be
delivered to the P.F.S. office as soon as possible. Such notices might include but are
not limited to: military orders, subpoenas, jury notices and court appearances.
The P.F.S. shall be immediately notified of any change of residence, signature or
telephone number.
GENERAL GUIDELINES
♦ Always wear the complete uniform and PPE as prescribed by the Officer in Charge of
the Probationary Firefighter School (PFS) while attending the Fire Academy.
♦ Conduct yourself at all times in a manner which will not bring reproach or discredit
upon the Department.
♦ Extend military courtesy to all officers and instructors at the Fire Academy.
♦ Not engage in a physical or verbal altercation, or perform any act which may be, or
intend to be, detrimental in arousing religious or racial matters.
♦ Not engage in any activity, whether by actions, speech, writings, or dissemination of
material which may cause sexual harassment as defined in Title VII of the Civil
Rights Act of 1964 and Mayoral Directive 80-5, which are set forth in the
Supplement to Department Order No. 28, dated February 27, 1981. (D.O. 60/84).
3
ORIENTATION
♦ You will not use the FDNY logo or name on any social media websites or on any
webpages. You will not make any postings that will bring discredit upon the FDNY
or will bring this Department or any of its members into disrepute if viewed by other
members or the public. You will be held responsible for what you post.
♦ You will not post photographs of yourself or any other member in PPE or uniform
unless worn during an event for which the uniform is required.
♦ You will not consume, or be under the influence of, alcohol while on duty.
♦ You will not use, or have in your possession, narcotics, tranquilizers, methadone,
drugs of the amphetamine group, barbiturate derivatives or non-prescribed
medications. Paraphernalia used to administer the above are also banned.
♦ Not make a false statement, report or record with the intent to deceive.
♦ Not maliciously damage any Department property, tools or equipment.
♦ Not engage in any extra departmental employment, profession, occupation, or
business while attending Probationary Firefighter School, including working as a
Volunteer Firefighter or on a Volunteer Ambulance.
♦ Not carry, possess, store or use any firearm while on Departmental property.
♦ Report loss of badge and/or I.D. card or other Department property immediately to
the Administrative Officer of the PFS.
♦ Remain with their squads at all times and not absent themselves from an assigned
class or other duty unless otherwise directed by an official of PFS.
♦ You will not use first or second floor bathrooms, except for auditorium and the
designated restroom in the second tube.
♦ You will not fraternize with field units.
♦ You will not read newspapers on Fire Department grounds. Read your proby manual.
♦ No walking on or crossing sidewalks except passage between bldgs. 11 and 12,
bunker locker room, and auditorium.
♦ Do not use glass doors to enter or exit building 11 or 12.
♦ Be at least one hour early for roll call. Lateness will not be tolerated and could lead
to your termination.
♦ Stay hydrated, drink plenty of fluids. You will always carry a water bottle.
♦ “MAKE WAY” – First Proby to See an Instructor shall yell “MAKE WAY” and
promptly step aside. Everyone else will repeat the command loudly and step to the
side, back to the wall.
♦ You will follow all orders from instructors, exactly as they are given.
♦ You will form up in roll call area 15 minutes prior to scheduled roll call.
♦ You will yell “good morning/afternoon, sir/ma'am”, whenever you make eye contact
with any FD member on the rock.
4
ORIENTATION
♦ Always have kneepads on your bunker pants and always wear your suspenders.
♦ If one person makes a mistake, everyone pays the price. You are a team. You will act
like a team.
♦ You will never travel alone.
♦ You will show respect to all superiors. Everyone is senior to you.
♦ No sitting, lying or leaning on objects outside during evolutions.
♦ Raise your hand if you have a question and speak up. Begin with “sir, probationary
firefighter _______” then your question.
♦ When your name is called, sound off loud and clear “here sir / ma’am”.
♦ When asked a question, your response will be “yes/no sir / ma’am”.
♦ Squad leaders are an extension of the drill instructors. You will treat them with the
same respect.
♦ Always utilize the chain of command.
♦ When you hear the command “LOCK IT UP” you will repeat the command loudly,
stop moving and stop speaking, until given the command “carry on”.
♦ Take the initiative to empty garbage cans and pick up trash from the floor. Don’t wait
for someone to tell you.
♦ Police the locker room every day prior to final formation.
♦ You will make sure to maintain clearly and neatly marked gear.
♦ We are always there for you if you show us you want to learn. Don’t be afraid to ask
for help.
♦ Give 110% every day in everything you do here. Poor attitudes will not be tolerated.
♦ Always finish on this job. Quitting prior to completing your task is not an option.
♦ If someone asks for a volunteer, everyone should step up.
♦ Committee work will be performed every day (instructor and common areas).
♦ You will enter the academy everyday carrying only your black bag in your left hand
♦ You will enter and leave the rock in your class A uniform every day.
♦ Use or possession of cigarettes, cigars or smokeless tobacco of any kind is prohibited
on the Rock or at Fort Totten at any time. This includes electronic cigarettes or
vapors.
♦ Absolutely no cell phones on the Rock or Fort Totten at any time, unless special
permission is obtained from the DI’s.
♦ You will not wear jewelry of any kind, earrings, body piercings, etc. This includes
wedding rings.
5
ORIENTATION
♦ Medical leave or light duty will result in missed training days and could result in your
termination.
♦ You will maintain Fire Dept. grooming standards. Your face will be clean shaven
daily, your uniform clean and pressed and your shoes polished. You will have your
hair cut weekly to the required specifications.
♦ You will provide your own lunch every day, and it will be secured in the large
refrigerators located outside of the auditorium. Make sure your belongings are clearly
marked.
♦ You will need a black bag with no markings, a notebook, 3 black pens, 3 sharpened
#2 pencils and a black permanent marker with you at all times.
♦ You will bring your entire proby manual to every class every day unless otherwise
instructed.
6
Probationary Firefighters Manual
Chapter 1
GENERAL DEPORTMENT
CONTENTS: • Definitions
• Prohibited Conduct
• Duties regarding substance policies
• Testing Procedures
• Guidelines for Violations of this Policy
• Social Media Policy
1
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
1. PRELIMINARY STATEMENT
This Circular:
1.1 Sets forth Department policy concerning the use and possession of illegal drugs; use and
possession of legally prescribed drugs in a manner or purpose other than that which is
lawfully prescribed; and use and possession of alcohol by Department members.
1.2 Sets forth prohibited conduct related to illegal drugs and alcohol.
1.4 Establishes conditions for mandatory testing for the presence of illegal drugs or alcohol.
2. POLICY
2.1 As first responders to fires, public safety and medical emergencies, disasters and terrorist
acts, the FDNY protects the lives and property of New York City residents and visitors.
The Department advances public safety through its fire prevention, investigation and
education programs. The timely delivery of these services enables the FDNY to make
significant contributions to the safety of New York City and homeland security efforts.
The efficient performance of this mission demands the highest level of mental and
physical fitness of Department members. The lives of citizens and co-workers are
dependent upon the fitness, stamina and alertness of firefighters and fire officers. Drugs
and alcohol alter alertness, judgment, physical agility and the ability to fulfill one’s work
responsibilities. Any impairment of the member’s physical and mental capabilities
increases the danger of accidents and injuries, not only to the member, but to fellow
firefighters and to the public. Accordingly, this circular sets forth the Department's
policy with respect to alcohol and illegal drugs. The purposes of this policy are as
follows:
2.1.4 To provide assistance to any member who seeks the Fire Department's help in
overcoming addiction to, dependence upon or problems with alcohol or drugs.
2.1.5 To maintain the reputation of the Fire Department and its members as responsible
public servants worthy of public trust.
1
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
2.2 All members are required to be familiar with and to follow the policies and procedures
set forth in this AUC and any addenda.
2.3 All members must be cognizant that time is of the essence with respect to substance-
related misconduct, and that their duties as set forth below in Section 5 must be fulfilled
immediately.
2.4 Violation of this policy may result in disciplinary action up to and including termination.
A range of penalties is set forth in Section 8, below.
3. DEFINITIONS
3.1 Alcohol: any substance, including medication, that contains alcohol in any amount.
3.2.1 Marijuana (cannabis) as currently defined in section 3302 of the N.Y.S. Public
Health Law.
3.2.2 Any substance listed in Section 3306 of the N.Y.S. Public Health Law (including,
but not limited to, amphetamines, anabolic steroids, barbiturates, cocaine, codeine,
hashish, heroin, LSD, mescaline, methadone, methylenedioxymethamphetamine
(ecstasy), morphine, narcotics, opiates, PCP, tranquilizers) that are:
a. obtained without a lawful prescription, or
b. used in a manner or for a purpose other than that which is lawfully prescribed.
3.2.3 Marijuana (as defined above) and certain substances (e.g. ecstasy, heroin) listed in
Section 3306 of the N.Y.S. Public Health Law may not be used or possessed
lawfully.
3.2.4 Any substance used in a manner prohibited by Federal, State and local laws, rules
and regulations.
3.3 Level of alcohol that elicits a positive test result: .05 blood alcohol concentration
(“BAC”) (this is the amount of alcohol in your blood) as determined by a urine, blood or
saliva test.
2
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
3.5 Positive test result: A laboratory test result that is certified by the Chief Medical Officer,
or his or her designee, after reviewing the laboratory report and the completed Drug
and/or Alcohol Testing Questionnaire (BHS-1) form or the Random Drug Testing
Questionnaire (T-1) form, as applicable.
3.6 Premises: any FDNY division or battalion office, firehouse, ambulance station, or other
location owned, leased or operated by FDNY including parking facilities adjacent to such
premises.
3.7 Substance: alcohol or illegal drugs as defined in Sections 3.1. and 3.2.
3.8 Substance Test: A test for the presence of alcohol and/or illegal drugs analyzed by a
laboratory facility licensed by the New York State Department of Health to perform
forensic toxicology and approved by the Department.
3
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
4. PROHIBITED CONDUCT
The following conduct by members is strictly prohibited:
4.1 Use, positive presence, possession, attempted possession, sale, transport or delivery of
any illegal drug as defined in Section 3.2 while on-duty or off-duty; or while in uniform;
or while in any Department premises, property or vehicle(s).
4.2 Use, possession, sale, transport or delivery of any drug paraphernalia (e.g. hypodermic
needles used to inject illegal substances) while on-duty; or while in uniform; or while in
any Department premises, property or vehicle(s).
4.3 Use, positive presence, possession, sale, transport or delivery of alcohol or related
paraphernalia (e.g. beer taps, beer kegs) while on-duty; or while in uniform; or while in
any Department premises, property or vehicle(s).
4.4 Any use of alcohol that may elicit a positive test result while on-duty.
4.5 Refusal to cooperate in any substance test ordered by the Fire Department, including the
completion and signing of any required forms.
4
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
5.3 Every officer on-duty or while in any Department premises, property or vehicle(s) will be
held accountable for compliance by their subordinates with these policies. Failure on the
part of officers to enforce these regulations will result in appropriate disciplinary action
and will be reflected in the officer's performance evaluation.
5.4 Every officer who observes a member exhibiting possible signs of alcohol or drug abuse
shall consult with the Counseling Service Unit (“CSU”) and may refer the member to CSU.
5.5 Every officer (whether on-duty or while in any Department premises, property or
vehicle(s)) who reasonably suspects or knows that any member has engaged in conduct
prohibited by this AUC or any addenda shall immediately:
1. Prohibit on and off-duty members present at the time of discovery of any violation
of this policy from leaving premises without permission of the investigating officer.
If any member is permitted to leave premises during an investigation, the
investigating officer shall document the reason for the release in a report to be sent
to the Chief of Department via the chain of command.
2. Immediately relieve the on-duty member(s) from emergency response duty.
3. Immediately have the affected unit placed out of service.
4. Notify the administrative Battalion Chief or, if appropriate, the next superior officer.
5. Notify the Bureau of Investigations and Trials (“BITs”).
6. Document the incident in the company journal.
5.6 Every Chief (whether on-duty or while in any Department premises, property or
vehicle(s)) who reasonably suspects or knows that any member has engaged in conduct
prohibited by this AUC or any addenda shall immediately:
1. Notify the Borough Command through the chain of command weekdays 0800 hours
to 1600 hours or the Command Chief at all other times, i.e. nights, weekends and
holidays and ensure that the affected unit has been placed out of service;
2. Ensure that all notifications required under section 5.5 have been made, and
3. Consult with Command Chief to designate an officer as the investigating officer.
5
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
5.7 The officer charged with investigating a suspected or known violation of this policy shall
immediately:
1. Conduct a roll call. All on-duty and off-duty members present in premises shall be
part of the roll call.
2. Advise all officers and firefighters whom the investigating officer reasonably
believes may be subject to charges of their right to representation before being
questioned.
3. Following notification, conduct an investigation to ascertain which member(s) may
have engaged in any conduct prohibited under this policy.
4. If the officer has reason to believe that any member(s) has violated this policy, the
officer shall immediately order that such member(s) be tested for alcohol and illegal
drugs. If the officer orders testing, he or she shall document the reasons for the
determination in a report to the Chief of Department via the Chain of Command.
If the officer determines that there is no reason to believe that this policy has been
violated, he or she shall not order testing and shall document the reasons for his or her
determination in a report to the Chief of Department via the Chain of Command.
5.8 After a suspected or known violation of this policy has been reported, Fire Officers,
Medical Officers, BITs and the Testing Unit are authorized to order testing for alcohol
and illegal drugs. All testing ordered by a Fire Officer, BHS, BIT or the Testing Unit
may be conducted by BHS, BIT or the Testing Unit. All reasons for testing shall be
properly documented by the person or unit ordering the testing.
6. TESTING OF MEMBERS
6.1.1 Every member ordered for testing pursuant to Section 5 of this policy.
6.1.2 Every member who has been arrested on or off-duty for any reason related to the
prohibited conduct specified in section 4.3.
6.1.3 Every member who has been arrested on or off-duty for any reason related to the
use or possession of an illegal drug.
6.1.4 Every member whose on-duty conduct leads to a reasonable suspicion that he or
she is violating any provision of this policy.
6
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
6.1.5 Every member who has been on disciplinary leave or suspension that resulted from
(a) the alleged use or possession of alcohol or illegal drugs, or (b) any violation of
this AUC or any addenda (including the Random Drug Testing Policy). The BHS
shall ensure that the testing takes place prior to the member’s return to duty.
Such testing may be conducted by BHS or the Testing Unit.
6.1.6 Every member who has operated a Department vehicle that has been involved in a
major accident as defined in Safety Bulletin 56. The highest ranking officer who has
responded to the accident shall ensure that the testing takes place in an expeditious
manner and shall coordinate such testing with the Testing Unit. If any personnel
required to be tested are immediately transported to a hospital, the Medical Officer
on-duty shall ensure that the personnel transported are tested in an expeditious
manner, and shall coordinate such testing with the Testing Unit, BIT or other required
BHS personnel. The highest ranking officer (or where applicable, the Medical
Officer), shall document the reasons for the failure to test a member via the chain of
command in a written report to the Fire Commissioner and Chief of Department.
6.1.7 Every member who, after a supervisory referral to the CSU, fails to comply with
the treatment recommendations of the CSU. CSU will send the employee to BHS
for a duty status evaluation that will include a substance test. The employee's
noncompliance will be reported by BHS to the BITs. Any member who receives a
supervisory referral and fails or refuses to comply with the treatment program
recommended or approved by CSU will be deemed:
A. To have disobeyed an order to comply with the treatment plan recommended;
B. To have exhausted this treatment opportunity.
6.1.8 Every Probationary Firefighter, Firefighter, Wiper, Marine Engineer, Pilot, Fire
Marshal, Lieutenant, Captain, Supervising Fire Marshal, Battalion Chief, Medical
Officer, Deputy Chief, Deputy Assistant Chief, Assistant Chief Fire Marshal,
Assistant Chief, Chief of Staff, Chief Fire Marshal, Chief of Operations, and Chief
of Department shall be subject to illegal drug testing on a random basis.
6.1.9 Every member ordered for testing by a Fire Officer, BHS, BITs or the Testing Unit.
6.2.1 Every applicant to the position of Fire Marshal shall be subject to a substance test.
6.3.1 Every probationary firefighter shall be administered an alcohol and illegal drug
test as part of the 5th Grade medical examination.
7
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
6.4.1 Every member who has signed an agreement to be tested for illegal drugs and
alcohol as a condition of employment or in settlement of a disciplinary matter
shall be tested according to the terms of the agreement at the discretion of the
Department and without prior notice.
6.4.2 Members subject to drug and alcohol testing pursuant to agreements with the
Department may be tested while on-duty at any work locations. Testing Unit
personnel shall administer such testing. Upon arrival of the Testing Unit, all
personnel at the work location of the member to be tested shall comply with the
instructions of the Testing Unit. The member’s supervisor shall be responsible for
promptly locating the member and for ensuring full and prompt cooperation with
Testing Unit personnel.
6.4.3 Members shall not make any public announcement over the intercom or otherwise
regarding the arrival of the Testing Unit personnel assigned to conduct substance
testing of members.
7. TESTING PROCEDURES
7.1 The Department shall test members according to the following procedures, unless the
Department is conducting random drug testing.
7.1.1 In all instances, the Department will make every effort to ensure the integrity of
the testing procedure and the privacy and dignity of members being tested.
7.1.3 Trained personnel assigned to BITs or the Testing Unit will administer a urine test.
7.1.4 A doctor or nurse assigned to BHS will administer any blood tests.
8
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
7.1.5 BHS, BITs or the Testing Unit shall confirm the identity of the employee being
tested by checking the member’s:
♦ FDNY photo identification card; or
♦ New York State Driver license.
7.1.6 Members shall list on the Drug and/or Alcohol Testing Questionnaire (BHS-1) form:
♦ all prescriptions, over-the-counter medications or dietary supplements ingested,
inhaled or injected, or otherwise taken within the previous 72 hours; and
♦ all substances containing alcohol consumed within the last twenty-four (24)
hours, and
♦ all food ingested within the previous 24 hours. The information must be as
specific and exhaustive as possible.
7.2.1 The FDNY shall comply with the random drug testing procedures set forth in
AUC 202, Addendum 1. Every member who is subject to testing and other
Department personnel shall comply with random drug testing as defined in
AUC 202, Addendum 1.
9
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
7.3 Substance Testing for Members Who Have Signed Testing Agreements
7.3.1 Testing Unit personnel will call the officer on-duty, after the start of the tour, to
ascertain that the member is working. The member is not to be notified until the
tester arrives.
7.3.2 When the Testing Unit arrives at the work location, the officer on-duty should
direct the member to report to the company office where the member will receive
further instructions in connection with the testing to be administered.
The following are guidelines only and are not meant to abrogate in any way the due
process rights provided under the N.Y.S. Civil Service Law, the N.Y.C. Administrative
Code or any applicable collective bargaining agreement. In addition, the Department's
use of these guidelines will take into consideration any findings and recommendations
made by an Administrative Law Judge after a N.Y.C. Office of Administrative Trials and
Hearings trial or by a Hearing Officer after a disciplinary proceeding.
8.1 Suspensions
Pre-Penalty Administrative Action
Members may be suspended for up to thirty (30) days in the following situations:
- Any violation of Section 4 and 5 of this policy
- Positive test result for Illegal Drug or Alcohol (on-duty)
- Drug or Alcohol Related arrest
- DWI / DWAI arrest
- Any other violations of existing Fire Department policies, rules or regulations
First Offense: Up to 90 days pay, 2 years testing, referral to CSU, final warning for
substance-related misconduct
10
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
8.3 Positive Test Result for Illegal Drug/Refusal to Provide Specimen: Penalties
First Offense (involving a motor vehicle accident, any injury or other aggravating
factor(s)):
30 to 60 days’ pay, 2 years of testing, referral to CSU, final warning for
violations of substance-related misconduct
8.6.2 A probationary firefighter may be terminated for any violation of this policy.
11
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
1.1 The New York City Fire Department (FDNY or the Department) has established for all
FDNY employees the guidelines below concerning the use of social media (Policy). This
Policy is based on the New York City Social Media Policy (published by the Office of
the Mayor in April 2010), which provides overall guidance for the use of social media by
employees of City agencies.
1.2 The improper use of social media can undermine the confidence of the public in the
integrity of the Fire Department and its employees, and can impact our ability to
effectively deliver life-saving services. As such, this Policy applies to both official and
personal use of social media by FDNY employees. All employees are reminded that they
are accountable for their conduct while on duty and are accountable for off duty conduct
when it could reasonably be expected to be disruptive of the workplace or agency
operations, or bring the agency into disrepute.
1.3 All supervisors, including civilian managers, and Fire and EMS officers, must familiarize
themselves with this policy and ensure that this policy is distributed to all employees
within their bureaus, units, commands or companies.
1.4 Nothing in this policy is meant to interfere with or limit any rights of any employee
organization or its members to engage in protected union activity as defined in the Taylor
Law and the New York City Collective Bargaining Law (NYCCBL).
1.5 Violations of this Policy may subject employees to disciplinary action, up to and
including termination from the Department.
2. DEFINITIONS
2.1 "Social media" is defined as virtual communities and networks used to exchange
information that includes but is not limited to messaging and data transmission, blogging
and/or photo and video-sharing. Social media include proprietary sites or applications
such as Facebook, Instagram, Tumblr, YouTube and Twitter, websites and other content-
rich sites, instant messaging, video conferencing and collaboration services such as
Wikipedia or any emergent social media platform or service.
2.2 Common social media outlets to which this Policy applies include, but are not limited to:
2.2.2 Blogs: A blog is an online journal to which the host regularly posts material on
which other users can comment; some blogs, such as microblogs, limit entries to
short, text-message-like entries (e.g., Twitter).
12
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
2.2.4 RSS feeds: An RSS (Really Simple Syndication) feed is an online alert system that
notifies subscribers of new content on a website.
2.2.5 Podcasts: A podcast is an audio file that has been published on the internet and can
be downloaded to a computer or a mobile-listening device.
3.1 The Department’s Office of Public Information (OPI) has been designated as the point of
contact for the New York City Department of Information Technology and
Telecommunications (DoITT) for operation of existing Department social media sites. OPI
is required to register with DoITT any social media pages, sites or outlets related to the FDNY
that are maintained by Department employees, as directed by the New York City Social Media
Policy. OPI will be responsible for the registration of any social media pages, sites and outlets
relating to the Department that are created in the future. Assigned managers of approved
social media will be required to adhere to the New York City Social Media Policy and
will be bound by the same rules and standards governing all New York City social media
managers.
3.2 OPI is responsible for posting official content on the Department’s official social media sites
and will ensure that the Department's official social media usage comports with the New York
City Social Media Policy.
4.1 All FDNY employees must be aware of and abide by the following:
13
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
5.1 FDNY employees are responsible for what they write or post on social media. Activities
and statements made on social media sites are done in an online domain where users have
no reasonable expectation of privacy. Even if an FDNY member has created ''private'' or
"limited access" accounts or has customized ''privacy settings", any statements,
photographs, video clips or information that are sent over the internet may still be viewed
and disseminated by third parties, even after the content has been edited or deleted by the
user. Whether intended to be private or not, postings will be available on the web for a
long time and may spread to large audiences by re-posting, sometimes without the
knowledge or consent of the original poster. Before posting, consideration should be
given to whether the post will disrupt operations or bring the Department or any of its
members into disrepute if viewed by supervisors, co-workers, or members of the public.
5.2 Employees participating in social media are subject to all applicable Department and City
policies even when using social media while off duty or not at work. Department and/or
City policy prohibits engaging in conduct tending to bring the City or the FDNY into
disrepute, including engaging in harassing or discriminatory conduct. Engaging in such
behavior on-line, even in a personal capacity, may subject an employee to disciplinary
action. In addition, all postings on social media must comply with all laws and FDNY
policies regarding the confidentiality of information. Accordingly, FDNY members will
comply with the following:
5.2.3 Employees may not use the FDNY’s logo or name (e.g., FDNY) in any postings
or feature the logo or name on any web page (e.g., a website/social media banner
or profile photo) for commercial purposes.
5.2.4 FDNY personnel shall not post photographs of themselves in uniform, unless the
uniform was worn during an event for which a uniform is required. FDNY
personnel are prohibited from posting a photograph of themselves if, at the time,
the wearing of a uniform is prohibited. These prohibitions will not apply to
photographs taken at official Department ceremonies (e.g., promotions, Medal
Day). Employees must ensure that any photographs posted on social media sites
pursuant to this exception must comply with the regulations set forth in Section
5.2.2 above.
14
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
5.2.5 Employees are prohibited from posting on the Internet nonpublic items (e.g.,
information about, or photos or videos of, patients or fire scenes) that were
obtained as a result of their position with the Department. Members of the
Department are prohibited from taking photographs, videotaping or recording
audio while working unless authorized to do so by OPI.
5.2.6 Employees are prohibited from engaging in any type of social media contact with
patients, fire victims or any members of the public with whom they interact in
their capacity as FDNY employees, to the same extent contact is prohibited by
other means of communication. Such communications may be deemed
inappropriate, a breach of confidentiality or an invasion of privacy.
5.2.7 Employees are prohibited from engaging in any type of social media contact (e.g.,
"friending,” or "following") with minors with whom they interact in the course of
their FDNY employment, unless specifically authorized by a Department
Assistant Commissioner (or higher rank) or Deputy Chief (or higher rank). Such
unauthorized communications may be deemed inappropriate and create an
appearance of impropriety.
5.2.8 Employees should never use their City e-mail addresses when participating in
social media. Inasmuch as the FDNY monitors employee Internet use, employees
have no right to privacy with respect to any information transmitted, received,
created, accessed, obtained, viewed, stored or otherwise found at any time on the
FDNY’s computer system.
5.2.9 Employees currently using social media must immediately ensure that all of their
personal social media pages, sites and outlets are reviewed and in compliance
with the regulations set forth in this Policy.
5.2.10 Employees who identify themselves as FDNY employees, or hold positions with
the FDNY that are known to the general public, must make sure that their profile,
comments and other postings are consistent with how they want to present
themselves publicly. Employees should make a clear disclaimer that the
statements and views expressed are theirs and do not reflect the views of the
FDNY. Managers and others with leadership responsibilities, in particular, must
consider whether their personal thoughts and views may be misconstrued by
virtue of their position as expressing the FDNY’s view.
5.2.11 Employees – including work units such as Fire companies and EMS stations -- are
prohibited from posting their own web or other media sites, without prior
authorization from the Fire Commissioner and OPI, if such site creates the
appearance of being affiliated with or sponsored by the FDNY. Requests for
authorization are to be submitted to OPI via the Website/Social Media
Registration Form attached to this policy.
5.2.12 Guidelines set forth in this Policy will not apply to social media outlets used for
investigative purposes.
15
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
6.1 Employees are encouraged to seek guidance from the OPI (718-999-2056) or the
Bureau of Legal Affairs (718-999-2040) if they have questions regarding
compliance with this policy.
7. RELATED PROCEDURES
• HIPAA (AUC 334, EMSC OGP 113-05 and Title 45 of the Code of Federal
Regulations Parts 160 and 164 and NYS Public Health Law)
16
FDNY Probationary Firefighters Manual
Chapter One SUBSTANCE POLICY, DRUGS & ALCOHOL, SOCIAL MEDIA
Name
Unit
Phone
Email Address
Page Name
Page URL
Please complete one form for each website and/or social media page.
Return completed forms to the Office of Public Information.
Fax: 718-999-0033
Email: FDNYdigital@[Link]
17
GENDER-NEUTRAL SINGLE-OCCUPANT
RESTROOM POLICY AND POSTING
1. PURPOSE
1.1 To establish policy governing single-occupant restrooms in accordance with Local Law No.
871-A, which amended the administrative, plumbing, and building codes of New York City,
and went into effect on June 28, 2016.
2. SCOPE
2.1 This policy applies to all Department facilities that contain single-occupant restroom(s).
3. DEFINITION
3.1 Single-occupant restroom: A restroom containing no more than one water closet and one
urinal, except where egress from it is through a male- or female-designated changing area.
4. POLICY
4.1 To the extent that they exist at a given facility, all single-occupant restrooms must be made
available for use by persons of any gender.
5. PROCEDURES
5.1 The sign shown in (Photo 1) must remain affixed on or near the entrance to the restroom if it
is an Americans with Disabilities Act (ADA) accessible restroom.
(Photo 1)
18
FDNY Probationary Fire School
Chapter One Gender-Neutral Single-Occupant Restroom Policy and Posting
5.2 The sign shown in (Photo 2) must remain affixed on or near the entrance to the restroom if it
is not an ADA accessible restroom.
(Photo 2)
Note: Any questions or concerns regarding this policy should be directed to the EEO Office:
Phone: (718) 999-1446 (Monday through Friday 9 a.m. to 5 p.m.) or (718) 999-7900
(after hours); Fax: (718) 999-1289; Email: eeo@[Link].
19
ANTI-HAZING/ANTI-BULLYING POLICY
1. PURPOSE
1.1 The New York City Fire Department expects all of its employees to treat one another
with dignity and respect. Consistent with that principle, this policy prohibits employees
from engaging or participating in, or encouraging others to engage or participate in, any
act of hazing or bullying.
1.2 The Department seeks to foster a professional, welcoming and safe work environment for
all of its employees. Hazing and bullying are contrary to this goal, as well as to the
FDNY’s core values of honor, dedication and service. Such acts can impact an
employee’s ability to function at work and damage trust and confidence among
co-workers, undermining the cohesiveness of the work unit. Every employee must be
afforded the opportunity to be a productive and contributing member of their work unit,
free of hazing or bullying.
1.3 Hazing and bullying have no place in any workplace or organization and will not be
tolerated by the Department.
2. DEFINITION
2.1 Hazing is an act that, includes, but is not limited to, any form of initiation or a “rite of
passage” into an employee group, unit, or work location that involves the potential for,
or causes, physical injury, mental harm or personal humiliation. It includes but is not
limited to conduct that is cruel, abusive, humiliating, intimidating, oppressive,
demeaning or harmful. Soliciting, coercing, participating in, or condoning others to
engage in any such activity is also considered hazing. Hazing need not involve any
physical contact among or between employees; it can be, in part or wholly, verbal or
psychological in nature.
2.3 Examples of hazing/bullying include, but are not limited to, the following types of
conduct:
20
FDNY Probationary Fire School
Chapter One ANTI-HAZING/ANTI-BULLYING POLICY
2.3.17 Forcing or requiring the consumption of food, alcohol, drugs or any other
substance.
2.5 Hazing/Bullying does not include authorized activities such as required operational or
training exercises/activities (but not including abuse of those activities as listed in
Section 2.3); remedial training selected by the employee or as directed by Training
Academy staff or other training or instruction authorized by the Chief of Training,
Chief of Operations or Chief of Department; as well as daily work, e.g., roll call,
inspection of equipment, housewatch duties, committee work (maintaining the bunkroom,
cleaning bathrooms, preparing meals, etc.).
21
FDNY Probationary Fire School
Chapter One ANTI-HAZING/ANTI-BULLYING POLICY
3. POLICY
3.1 The FDNY prohibits hazing/bullying of any of its employees by another employee, while
on and off duty. Aiding and abetting another person who is engaged in such conduct is
prohibited. No FDNY employee may engage in hazing/bullying or consent to be a victim
of hazing/bullying. Anyone who witnesses or is made aware of any act or allegation of
hazing/bullying must immediately report such information (see Section 4.1). Actual or
implied consent to acts of hazing/bullying is not a defense to a violation of this policy.
3.3 It is the responsibility of the officer or supervisor to set the tone and maintain a safe and
welcoming workplace environment. No officer or supervisor may condone or ignore
hazing/bullying if the officer or supervisor knows, or reasonably should have known that
the conduct has occurred. Once informed or made aware of any such incident or
allegation, all officers and supervisors must report the incident through the chain of
command and, where applicable, directly to the Equal Employment Opportunity (EEO)
or to the Bureau of Investigations and Trials (BITs). Failure of an officer or supervisor to
enforce this policy will result in disciplinary action against the officer or supervisor.
3.4 The FDNY strictly prohibits retaliation against any complainant of hazing/bullying, or
any witness who reported such an incident. The Fire Department will not tolerate any
such retaliation. Employees are prohibited from subjecting individuals to threats,
reprimands, negative evaluations, harassment, or engaging in other adverse treatment that
may have the effect of discouraging individuals from reporting or cooperating with
investigations into any alleged violations of this policy. Offenders will be subject to
discipline, up to and including termination of employment.
4. REPORTING
4.1 Alleged violations of this policy will be handled confidentially. Information obtained
will be disclosed only to those who need to know for purposes of investigation and/or
remediation.
4.2 The ability to investigate reports and enforce this policy depends on the accuracy and
specificity of the information provided. Employees are encouraged to provide as much
specific detail as possible so that appropriate action can be taken to address the reported
behavior. Employees have the option to submit a report anonymously to BITs or EEO.
However, providing one’s name and contact information is encouraged.
22
FDNY Probationary Fire School
Chapter One ANTI-HAZING/ANTI-BULLYING POLICY
4.5 Hazing/Bullying allegations that may also implicate or violate the Department’s
EEO policy shall be reported directly to the EEO Office in accordance with the
Department’s EEO policy. BITs and/or the EEO Office will investigate reported hazing
incidents as necessary.
4.6 Any reported hazing/bullying incident that would also be considered a crime will be
reported by the FDNY directly to the Department of Investigation. Additionally, every
officer and employee has an affirmative obligation to report, directly and without
delay, to the Inspector General any and all information concerning conduct involving
criminal activity. Notifications should be made directly to the Inspector General's
Office at 212-825-2402.
4.7 Any FDNY employee who has been hazed or bullied, or whom a supervisor or officer
believes may have been subjected to hazing or bullying, may be considered a victim and
will be offered the assistance of the Bureau of Health Services (BHS) and Counseling
Service Unit (CSU). An officer or supervisor who has been made aware of any acts of
hazing must advise the victim of the services available to him or her that are provided by
BHS and CSU.
4.8 No person shall prevent, seek to prevent, interfere with, obstruct, or otherwise hinder any
study or investigation being conducted pursuant to this policy. Full cooperation shall be
afforded by every officer and member during the investigation.
5.1 The Department regards violations of this policy as serious offenses, and has established
action guidelines for its violations. These guidelines are designed to cover the most
common infractions, but there may be cases that do not fit precisely within them.
The Department reserves the right to depart from these guidelines as the exacerbating or
extenuating circumstances of each individual case requires. The following are guidelines
only and are not meant to abrogate in any way the due process rights provided under the
NYS Civil Service Law, the NYC Administrative Code or any applicable collective
bargaining agreement. In addition, the Department’s use of these guidelines will take
into consideration any findings and recommendations made by an Administrative Law
Judge after a NYC Office of Administrative Trials and Hearings trial or by a Hearing
Officer after a disciplinary proceeding.
23
FDNY Probationary Fire School
Chapter One ANTI-HAZING/ANTI-BULLYING POLICY
5.2 The Department may take the following actions, including but not limited to, pending the
completion of an investigation:
5.2.3 Immediate detail of the commanding officer(s) of the company, Battalion Chief,
and/or Division Chief, where appropriate;
5.3 Any employee found to be in violation of this policy will be subject to discipline, up to
and including termination of employment.
24
Probationary Firefighters Manual
Chapter 2
FDNY REFERENCE:
2
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
P eople first learn about fire as children. They know that fire consumes fuel, needs air, and
gives off heat and light. Normally, that degree of understanding is all that one needs.
Firefighters, however, have to take their understanding of this process a step or two
further. In particular, they have to know more about the chemical process that goes on,
the methods of heat transfer a fire can use, the makeup and nature of the fuels, and the
environment the fire needs. It is this knowledge that arms the firefighter to fight fire and win.
Fire is actually a by-product of a larger process called combustion. Fire and combustion are two
words used interchangeably by most people; however, firefighters should understand the
difference. Combustion is the self-sustaining process of rapid oxidation of a fuel, which
produces heat and light. Fire is the result of a rapid combustion reaction.
IMPORTANT TERMS
Flammable or explosive limits – The percentage of a substance (vapor) in air that will burn once
it is ignited. Most substances have an upper (too rich) and a lower (too lean) flammable limit.
Flash Point – The minimum temperature at which a liquid fuel gives off sufficient vapors to
form an ignitable mixture with the air near the surface. At this temperature, the ignited vapors
will flash but will not continue to burn.
Heat – The form of energy that raises temperature. Heat can be measured by the amount of work
it does; for example, the amount of heat needed to make a column of mercury expand inside a
glass thermometer.
Ignition temperature – The minimum temperature to which a fuel in air must be heated to start
self-sustained combustion without a separate ignition source.
HEAT TRANSFER
A number of natural laws of physics are involved in the transmission of heat. One is called the
Law of Heat Flow; it specifies that heat tends to flow from a hot substance to a cold substance.
The colder of two bodies in contact will absorb heat until both objects are at the same
temperature. Heat can travel throughout a burning building by on or more of three methods:
conduction, convection, and radiation. The following sections describe how this transfer takes
place.
1
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Conduction
Heat may be conducted from one body to another by direct contact of the two bodies or by an
intervening heat-conducting minimum. An example of this type of heat transfer is a basement
fire that heats pipes enough to ignite the wood inside walls several rooms away (See Figure 1-1).
The amount of heat that will be transferred and its rate of travel depend upon the conductivity of
the material through which the heat is passing. Not all materials have the same heat
conductivity. Aluminum, copper, and iron are good conductors; however, fibrous materials,
such as felt, cloth, and paper, are poor conductors.
Figure 1-1
Liquids and gas are poor conductors of heat because of the movement of their molecules, and air
is a relatively poor conductor. This factor is why double building walls and storm windows that
contain an airspace provide additional insulation from outside air temperatures. Certain solid
materials, such as fiberglass, shredded into fibers and packed into batts make good insulation
because the material itself is a poor conductor and there are air pockets within the batting.
Convection
Convection is the transfer of heat by the movement of air or liquid. When water is heated in a
glass container, the movement within the vessel can be observed through the glass. If sawdust is
added to the water, the movement is more apparent. As the water is heated, it expands and
grows lighter, hence, the upward movement. In the same manner, as air near a steam radiator
becomes heated by conduction, it expands, becomes lighter, and moves upward. As the heated
air moves upward, cooler air takes its place at the lower levels. When liquids and gases are
heated, they begin to move within themselves. This movement is different from the molecular
motion discussed in conduction of heat and is responsible for heat transfer by convection.
2
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Figure 1-2
Heated air in a building will expand and rise (See Figure 1-2). For this reason, fire spread by
convection is mostly in an upward direction; however, air currents can carry heat in any
direction. Convection currents are generally the cause of heat movement from floor to floor,
from room to room, and from area to area. The spread of fire through corridors, up stairwells
and elevator shafts; between walls, and through attics is caused mostly by the convection of heat
currents. If the convecting heat encounters a ceiling or other barrier that keeps it from rising, it
will spread out laterally (sideways) along the ceiling. If it runs out of ceiling space, it will travel
down the wall toward the floor, being pushed by more heated air hat is rising behind it.
Convected heat encountering a ceiling is commonly referred to as mushrooming. Convection
has more influence upon the positions for fire attack and ventilation than either radiation or
conduction.
Although often mistakenly thought to be a separate form of heat transfer, direct flame contact is
actually a form of convective heat transfer. When a substance is heated to the point where
flammable vapors are given off, these vapors may be ignited, creating a flame. As other
flammable materials come in contact with the burning vapors, or flame, they may be heated to a
temperature where they, too, will ignite and burn.
3
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Radiation
Although air is a poor conductor, it is obvious that heat can travel where matter does not exist.
The warmth of the sun reaches us even though it is not in direct contact with us (conduction), nor
is it heating up gases that travel to us (convection). This method of heat transmission is known
as radiation of heat waves. Heat and light waves are similar in nature, but they differ in length
per cycle. Heat waves are longer than light waves, and they are sometimes called infra-red
waves. Radiated heat will travel through space until it reaches as opaque object (See Figure 1-3).
As the object is exposed to heat radiation, it will in return radiate heat from its surface. Radiated
heat is one of the major sources of fire spread to exposures, and its importance as a source of fire
spread demands immediate attention at location where radiation exposure is severe.
Figure 1-3
Fire Tetrahedron
For many years, the fire triangle (oxygen, fuel, and heat) was used to teach the components of
fire (Figure 1-5). While this simple example is useful, it is not technically correct. For
combustion to occur, four components are necessary:
4
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
These components can be graphically described as the fire tetrahedron (Figure 1-4). Each
component of the tetrahedron must be in place for combustion to occur. This concept is
extremely important to students of fire suppression, prevention, and investigation. Remove any
one of the four components and combustion will not occur. If ignition has already occurred, the
fire is extinguished when one of the components is removed from the reaction.
Fuel may be found in any of three states of matter; solid, liquid, or gas. Only gases burn. The
initiation of combustion of a liquid or solid fuel require their conversion into a gaseous state by
heating. Fuel gases are evolved from solid fuels by pyrolysis. Pyrolysis is the chemical
decomposition of a substance through the action of heat (Figure 1-5).
Fuel gases are evolved from liquids by vaporization. This process is the same for water
evaporating by boiling or water in a container evaporating in sunlight. In both cases, heat causes
the liquid to vaporize. Generally, the vaporization process of liquid fuels requires less heat input
than does the pyrolysis process for solid fuels. This places considerable restraints on the control
and extinguishment of liquid fuel fires because their reignition is much more likely.
Gaseous fuels can be the most dangerous, because they are already in the natural state required
for ignition. No pyroplysis or vaporization will be needed to ready the fuel. These fuels are also
the most difficult to contain.
Figure 1-4
5
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Figure 1-5
6
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
PHASES OF FIRE
Fires may start at any time of the day or night if a hazard exists. If the fire happens when the
area is occupied and/or protected by automatic suppression and detection systems, chances are
that it will be discovered and controlled in the beginning (incipient) phase. If the fire occurs
when the building is closed, deserted, and without fixed protection systems, the fire may go
undetected until it has gained major headway. The phase of a fire in a closed building is of chief
importance when determining ventilation requirements.
Fire in a confined room or building has two particularly important characteristics. The first
characteristic is that there is a limited amount of oxygen. This differs from an outside fire, where
the oxygen supply is unlimited. The second characteristic is that the fire gases that are given off
are trapped inside the structure and build up, unlike outdoors where they can dissipate. When
fire is confined in a building or room, the situation requires carefully thought-out and executed
ventilation procedures if further damage is to be prevented and danger reduced. Fire confined to
a building or room can be best understood by an investigation of its three main progressive
phases: incipient, steady-state burning, and hot smoldering. A firefighter may be confronted by
one or all of the phases of fire at any time, therefore, a working knowledge of these phases is
important for understanding ventilation procedures. Firefighters must also be aware of the
variety of potentially hazardous conditions that may be intertwined within the three main phases.
These hazards include rollover, flashover, and backdraft.
Incipient Phase
The incipient phase is the earliest phase of a fire beginning with the actual ignition. The fire is
limited to the original materials of ignition (Figure 1-6). In the incipient phase, the oxygen
content in the air has not been significantly reduced, and the fire is producing water vapor
(H2O), carbon dioxide (CO2), perhaps a small quantity of sulfur dioxide (SO2), carbon
monoxide (CO), and other gases. Some heat is being generated, and the amount will increase as
the fire progresses. The fire may be producing a flame temperature well above 1,000°F (537°C),
yet the temperature in the room at this stage may be only slightly increased.
Figure 1-6
7
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Rollover
Rollover, sometimes referred to as flameover, takes place when unburned combustible gases
released during the incipient or early steady-state phase accumulate at the ceiling level (Figure 1-
7). These superheated gases are pushed, under pressure, away from the fire area and into
uninvolved areas where they mix with oxygen. When their flammable range is reached, they
ignite and a fire front develops, expanding very rapidly and rolling over the ceiling (Figure 1-8).
This is one of the reasons firefighters must stay low when advancing hoselines. Rollover differs
from flashover in that only the gases are burning and not the contents of the room. The rollover
will continue until its fuel is eliminated. This is done by extinguishing the main body of fire.
The rollover will cease when the fire itself stops producing the flammable gases that are feeding
the rollover.
Figure 1-7
Figure 1-8
For purposes of simplicity, the steady-state burning phase (sometimes referred to as the free-
burning phase) can generally be considered the phase of the fire where sufficient oxygen and fuel
are available for fire growth and open burning to a point where total involvement is possible.
During the early portions of this phase, oxygen rich air is drawn into the flame, as convection (the
rise of heated gases) carries the heat to the uppermost regions of the confined area (Figure 1-9).
8
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
If conditions are perfect, and they rarely are, the fire may achieve what is commonly referred to
as “clear burning.” Clear burning is accompanied by high temperatures and complete
combustion. Little or no smoke is given off. This fire is usually seen only when very clean
fuels, such as methanol-based race car fuels, burn.
Thermal columns will normally occur with rapid air movements upward from the base of the
fire. As the fire progresses (in a confined space) through the latter portions of the steady-state
burning phase, the fire continues to consume the free oxygen until it reaches the point where
there is insufficient oxygen to react with the fuel. The fire is then reduced to the smoldering
phase, but this fire needs only a fresh supply of oxygen to burn rapidly.
Flashover
9
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Backdraft
Firefighters responding to a confined fire that is late in the steady-state burning phase or in the
hot smoldering phase risk causing a backdraft (also known as a smoke explosion) if the science
of fire is not considered in opening the structure.
Figure 1-12
10
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Combustion is oxidation, and oxidation is a chemical reaction in which oxygen combines with
other elements. Carbon is a naturally abundant element present in wood and most plastics,
among other things. When the wood burns, carbon combines with oxygen to form carbon
dioxide (CO2) or carbon monoxide (CO), depending on the availability of oxygen. When
enough oxygen is no longer available, large quantities of free carbon are released in the smoke.
Thus a warning sign of possible backdraft is dense, black (carbon-filed) smoke.
Figure 1-13
The following characteristics may indicate the potential for a backdraft to occur:
This situation can be made less dangerous by proper ventilation. If the room or building is
opened at the highest point involved, the heated gases and smoke will be released, reducing the
possibility of an explosion.
The thermal layering of gases is the tendency of gases to form into layers, according to
temperature.
Other terms sometimes used to describe this layering of gases by heat are heat stratification and
thermal balance. The hottest gases tend to be in the top layer, while the cooler ones form the
bottom layer. Smoke is a heated mixture of air, gases, and particles, and it rises. If a hole is
made in the roof, the smoke will rise from the building or room to the outside.
11
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Thermal layering is critical to fire fighting activities. As long as the hottest air and gases are
allowed to rise the lower levels will be safer for firefighters (Figure 1-14). This normal layering
of the hottest gases to the top and out the ventilation opening can be disrupted if water is
improperly applied.
Figure 1-14
If water is improperly applied to the fire area and the area is not ventilated, the water will cool
and condense, the steam generated by the initial fire attack. This reaction causes the smoke and
steam to circulate within all levels of the fire area. This swirling of smoke and steam is the result
of disrupted normal thermal layering (Figure 1-15). This process is sometimes referred to as
disrupting the thermal balance or creating a thermal imbalance. Many firefighters have been
needlessly burned when thermal layering was disrupted. Once the normal layering is disrupted,
forced ventilation procedures must be used to clear the area.
Figure 1-15
12
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
PRODUCTS OF COMBUSTION
Incomplete combustion, of course, also leaves behind some unburned or charred school. When a
material (fuel) burns, it undergoes a chemical change. None of the elements making up the
material are destroyed in the process, but all of the material is transformed into another form or
state. For example, when a piece of paper burns, the gases and moisture contained within the
paper are liberated. The remaining solids take on the appearance of carbonized, charred flakes.
Although it was once thought that the weight of various byproducts was the same as the original
weight of the fuel, it is now known that a tiny amount of fuel is indeed converted into energy, so
the by-products weigh slightly less than the fuel did.
When a fuel burns, there are four products of combustion: heat, light, smoke, and fire gases
(Figure 1-16). Heat is a form of energy that is measured in degrees of temperature to signify its
intensity. Heat is the product of combustion that is responsible for the spread of fire. It is also
the direct cause of burns, dehydration, heat exhaustion, and injury to the respiratory tract.
13
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
The extinguishment of fire is carried out by limiting or interrupting one or more of the essential
elements in the combustion process. With flaming combustion, the fire may be extinguished by
reducing temperature, eliminating fuel or oxygen, or by stopping the uninhibited chemical chain
reaction. If a fire is in the smoldering mode of combustion, only three extinguishment options
exist: reduction of temperature, elimination of fuel, or elimination of oxygen.
One of the most common methods of extinguishment is by cooling with water (Figure 1-17).
This process of extinguishment is dependent on reducing the temperature of the fuel to a point
where it does not produce sufficient vapor to burn. Solid fuels and liquid fuels with high flash
points can be extinguished by cooling. Fires involving low flash point liquids and flammable
gases cannot be extinguished by cooling with water, because vapor production cannot be
sufficiently reduced. Reduction of temperature is dependent on the application of an adequate
flow in proper form to establish a negative heat balance.
In some cases, a fire is effectively extinguished by removing the fuel source (Figure 1-18).
Removal of the fuel sources may be accomplished by stopping the flow of liquid or gaseous fuel
or by removing solid fuel in the path of the fire. Another method of fuel removal is to allow the
fire to burn until all fuel is consumed.
14
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Reducing the oxygen content in an area also puts out the fire (Figure 1-19). Reduction of the
oxygen content can be done by flooding an area with an inert gas, such as carbon dioxide, which
displaces the oxygen; or the oxygen can be reduced by separating the fuel from the air such as by
blanketing it with foam. Of course, neither of these methods work on those rare fuels that are
self-oxidizing.
Some extinguishing agents, such as dry chemical and halogenated hydrocarbons (Halons),
interrupt the flame-producing chemical reaction and stop flaming (Figure 1-20). This method of
extinguishment is effective on gas and liquid fuels, because they must flame to burn.
Smoldering fires are not easily extinguished by this method because the moment the Halon is
shut off, air once again has access to the smoldering fuel and it continues to burn. Cooling is the
only practical way to extinguish a smoldering fire.
15
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Class A Fires
Class A fires are fires involving ordinary combustible materials such as wood, cloth, paper,
rubber, and many plastics. Water is used in a cooling or quenching effect to reduce the
temperature of the burning material below its ignition temperature. The addition of Class A
foams (sometimes referred to as wet water) may enhance water’s ability to extinguish Class A
fires, particularly those that are deep seated in bulk materials. This is because the Class A foam
agent reduces the water’s surface tension, allowing it to penetrate more easily into piles of the
material.
Class B Fires
16
FDNY Probationary Firefighters Manual
Chapter Two CHEMISTRY OF FIRE
Class C Fires
Class D Fires
17
Probationary Firefighters Manual
Chapter 3
FDNY APPARATUS
3
PART ONE
3 BOOSTER TANK.........................................................................4
6 PUMP PANEL................................................................................9
7 DECK PIPE...................................................................................13
8 HOSEBED.....................................................................................14
9 STANDPIPE HOSE.......................................................................15
11 DRAFTING CONNECTIONS......................................................16
12 ADDITIONAL HOSE....................................................................17
1.1 The engine company apparatus is a complex piece of equipment that serves both as a
vehicle and as a high capacity water pump.
1.2 There are two primary functions of an engine apparatus in the FDNY:
1.2.2 Deliver water with sufficient pressure to the fire area for firefighting operations.
1.3 In order to properly use the engine apparatus effectively, it is necessary for all members to
be knowledgeable about the critical components of the apparatus.
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
1.4 This chapter will describe the critical components of the engine apparatus as it exists in the
FDNY. This includes the components listed below, which are described in the following
sections:
• Apparatus Pump
• Booster Tank
• Inlets and Outlets
• Drain Valves
• Pump Panel
• Deck Gun
• Hose Beds
• Standpipe Hose
• Hydrant Connections
• Drafting Connections
1.5 Deleted
2. APPARATUS PUMP
2.1 Conventional engine apparatus in the FDNY are equipped with a two-stage centrifugal
pump. These apparatus’ have a total rated capacity of 2,000 GPM and a maximum pressure
rating of 600 psi.
2.1.1 Select engine companies with the two-stage 2,000 GPM pump are designated as
“High Pressure Engines” as they have been fitted with a high-pressure discharge
elbow, and issued specialized high-pressure equipment (hose, fittings, etc..). This
special equipment allows them to safely perform “High-Pressure Pumping”
operations up to 600 psi.
2.1.2 A “stage” is the portion of the centrifugal pump that consists of one impeller and
generates the force required to discharge water.
2
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
2.1.3 The FDNY also has a number of engine apparatus that have a 3rd stage, designated
as “3rd Stage Engines”, which have a total rated capacity of 2,000 GPM and have a
maximum pressure rating of 700 psi. 3rd Stage Engines have been fitted with two
special high-pressure discharge elbows, and issued high-pressure equipment. This
special equipment allows them to safely perform High-Pressure Pumping
operations up to 700 psi.
2.1.4 Deleted
2.2 Conventional Engine apparatus have the capability to operate their two stages in two
different fashions:
2.3 Engine apparatus should be maintained in “Volume Operation” unless the pumping
operation needs to overcome head pressure (such as when supplying a standpipe system in
a high-rise building). When overcoming head pressure is required, the pump should be
switched to “Pressure Operation”.
3
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
2.4 Switching the pump from Volume Operation to Pressure Operation is done using the
transfer valve, which is switched using an operating handle located at the pump panel. Prior
to using the transfer valve, the engine RPM should be returned to idle pressure.
3. BOOSTER TANK
3.1 The booster tank is a 500-gallon water tank carried by all FDNY Engine apparatus. It is
capable of quickly supplying water to a hoseline or deck pipe for a limited period of time.
3.2 The operation of the booster tank is controlled by operating handles on the pump panel.
3.2.1 One handle allows the booster tank to supply water to the pump.
3.2.2 One handle allows the booster tank to be filled from the apparatus’ water supply.
3.3 A Tank Vision Gauge is a lighted, multi-color booster tank water level indicator. There are
two on the apparatus, which are located on the pump panel and the panel on the opposite
side of the apparatus.(Figure 1)
Figure 1
4
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
4.1 The apparatus is equipped with a number of connections by which water can be either taken
into the apparatus (inlets), or discharged from the apparatus (outlets).
4.1.1 Inlets (Figure 2) are connections by which water can be supplied to the apparatus.
A. Inlets are also called “suctions”.
B. Inlets exist in a number of sizes, including 3”, 4 ½”, and 6”.
C. Inlets may be gated or non-gated. Gated inlets are controlled by an operating
handle, which may be located adjacent to the inlet, or at the pump panel.
D. Gated inlets should always be used in the fully opened position.
Figure 2
5
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
4.1.2 Outlets (Figure 3) are connections by which water can be discharged from the
apparatus.
A. Outlets are also called “discharges”.
B. Outlets come in a number of sizes, including 2 ½”, 3”, and 4 ½”. A reducer is
placed on 2 ½” outlets for hose stretches utilizing 1 ¾” hose.
C. All outlets are gated and are controlled by an operating handle located at the
pump panel. Outlets are often operated in a partially open position to regulate
pressure.
Figure 3
4.2 Inlets and outlets may be color coded to match their corresponding operating handle and
bleeder valves.
6
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
5.1 Drain and bleeder valves are located at a number of points around the bottom of the
apparatus and serve the purpose of bleeding air and draining water from the pipes that
supply and discharge water from the apparatus. These valves may be manually operated,
or some may be automatic.
5.2 There is at least one bleeder valve for each inlet, and one drain valve for each discharge.
Both drain and bleeder valves are the same design and located between a gate and the
opening associated with it.
5.2.1 Drain valves can be opened to drain water from a discharge pipe, which can
facilitate breaking down hoselines after an operation, as well as prevent freezing in
cold weather. (Figure 4)
Figure 4
5.2.2 For inlets, the bleeder valve is also used to bleed air coming from an intake hose in
order to reduce the introduction of air into the pump, which may cause a loss of
prime during pumping operations.
7
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
5.3 The apparatus pump itself is also equipped with a designated drain valve. (Figure 5)
Figure 5
8
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
6.1 The pump panel (Figure 6) is the area on the Chauffeur’s side of the apparatus that provides
controls and gauges for managing water flow and monitoring the status of the apparatus
pump. Discussed below are the key components of the pump panel and their primary
functions.
Figure 6
6.1.1 Operating handles for gated inlets (Figure 7) and outlets (Figure 8)
A. The flow of water via the various gated inlets and outlets are controlled by
operating handles. All operating handles for outlets are at the pump panel, and
the operating handles for gated inlets can either be at the pump panel, or
adjacent to the inlet.
Figure 7 Figure 8
9
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
A. At the pump panel, there is an operating handle to control the supply of water
to the booster tank (Figure 9), as well as an operating handle to control the
supply of water from the booster tank to the pump.
Figure 9
10
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
Figure 11
11
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
Figure 12
A. Adjacent to the PPG, there is a button labelled “Push to Prime”. Pushing and
holding this button will “prime” the pump, which has the effect of ejecting air
from the pump as water is supplied. This prevents air from entering the
hoselines that are being supplied.
Figure 13
12
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
7. DECK PIPE
7.1 The apparatus deckpipe (Figure 13) is permanently affixed to the engine apparatus and
supplied directly by a 3-inch pipe from the pump.
Figure 13
7.2 The deckpipe has 4 stacked tips (2 ½”, 2 ¼”, 2”, 1 ½”).
7.2.1 When the 1 ½” tip is used, it will flow roughly 660 GPM with 100 psi at the tip.
7.2.2 When the 2” tip is used, it will flow roughly 840 GPM with 50 psi at the tip.
7.2.3 The maximum rated flow of 2,000 GPM is reached when the 2 ½” tip is supplied
with 116 psi.
7.3 The deckpipe should be maintained with a single gate connected. The single gate allows
the ECC to supply the deckpipe with water prior to operating the stream.
7.4 Deleted
13
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
8. HOSEBED
8.1 Conventional Engine apparatus in the FDNY are equipped with 4 hosebeds in the rear of
the apparatus.
8.2 While the specific organization of the hosebeds may vary among companies based on their
response area and response patterns, the following guidelines must be adhered to:
8.3 The lead length of all hosebeds with either 1 ¾” hose or 2 ½” hose must be maintained
with a straight-stream nozzle attached. These hosebeds are intended for fire attack.
8.4 The 3 ½” hose bed is intended to be used as a supply line. It can be oriented with either
the male or female coupling leading away from the apparatus and may be maintained with
necessary fittings attached to the coupling.
8.5 When a hosebed contains 1 ¾” hose, the first 6 lengths of this hosebed must be 1 ¾” hose.
No more (and no fewer) than 6 lengths are permissible. This limitation is due to the high
pressures required to overcome the friction loss of more than 6 lengths of 1 ¾” hose.
8.6 The proper loading of hose in a traditional hosebed arrangement will allow the hose to play
out smoothly when stretched. When properly loaded, 4 folds of hose in the hosebed is
roughly one 50’ length of hose.
8.7 To facilitate stretching hose, the lead lengths of hose in a hosebed may be maintained in a
horseshoe arrangement (Figure 14).
8.7.2 Each horseshoe should be comprised of at least one 50’ length of hose.
8.7.3 A hose bed can have multiple horseshoes. Horseshoes can be stacked on top of each other
on the hosebed, with the lead length on top.
14
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
Figure 14
9. STANDPIPE HOSE
9.1 All Engine apparatus must carry a number of lengths of hose arranged into a “roll-up”,
intended for use when stretching from a standpipe system.
9.2 This hose may be carried on the side board of the apparatus, and is secured using straps
and buckles. They may also be carried inside apparatus compartments.
9.3.1 1 length of 2” lightweight hose, maintained as a roll-up and kept with the 2” nozzle
and 1” MST attached. This hose is colored green with a red stripe.
9.3.3 For companies staffed with 5 firefighters, 1 additional length of 2 ½” lightweight hose must
be carried, maintained as a roll-up.
15
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
9.4 Deleted
10.1 All Engine companies must carry a number of hydrant connections, as follows:
11.1 All Engine companies must carry a number of connections designated to be used for
drafting water. FDNY engine apparatus are equipped with the following 3 drafting
connections:
11.2 Deleted
16
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
Figure 15
12.1 In addition to hose maintained in roll-ups and hose carried in the hosebeds, additional hose
is required to be carried on the apparatus as follows:
12.1.1 At least 1 spare length of 1 ¾” hose, rolled or folded, and maintained with a nozzle
attached.
A. This is intended for use as an additional length in a hose stretch, as described in
Chapter 10: Engine Company Emergencies
12.1.2 Two lengths of 1 ¾” hose to be used as a “booster line”. This hose should be
maintained with a fog nozzle attached to one length (Figure 16).
A. This hose is intended to be used on outside fires, such as rubbish fires or car
fires. In an emergency, it can also be used to apply water from the exterior of
the fire building.
B. It should be maintained pre-connected to a discharge outlet. It may also be
maintained pre-connected to a gated wye attached to a discharge outlet.
C. This hose may be maintained either rolled or folded. Generally, it is stored on
the front bumper of the apparatus.
Figure 16
17
FDNY Probationary Firefighters Manual
Chapter Three APPARATUS
18
Probationary FirefightersManual
CHAPTER 3, ADDENDUM 1
July 1, 2020
1.1 The Pro-Pressure Governor (PPG) is a computer located on the pump panel of the engine
apparatus that controls the operating pressure of the apparatus pump. (Figure 1)
1.2 Its central purpose is to maintain constant pump discharge pressure at each operating outlet
throughout the operation, regardless of the opening or closing of other discharge outlets on
the apparatus.
1.3 When effectively engaged, the PPG will maintain the selected pressure setting in the LED
display regardless of the number of discharges that are opened or closed, as long as the
water supply is capable of supplying the amount of water required.
1.4 This is especially important for operations at which a single apparatus is supplying multiple
hoselines. In these situations, the PPG will adjust the engine revolutions per minute (RPMs)
whenever a hoseline is opened or closed, in order to maintain the desired pump pressure for
each hoseline.
1.5 Deleted
Figure 1
19
FDNY Probationary Firefighters Manual
Chapter Three Add. 1 PRO PRESSURE GOVERNOR
2.1.1 The PPG can be operated in two different modes, as described below:
A. PSI Mode – In the PSI (pounds per square inch) mode, the PPG will
automatically maintain the discharge pressure set in the LED display. This is
the setting used by all apparatus in the FDNY.
B. RPM Mode – In the RPM (revolutions per minute) mode, the PPG will maintain
engine RPMs set in the LED display. In this mode, it will not automatically
compensate for any changes in discharge pressure. For this reason, apparatus
in the FDNY do not normally use the RPM mode.
2.2.1 The PPG has several digital displays, each of which is described below:
A. SETTING – This display is located in the center of the PPG and displays the
pressure level at which the PPG is currently set.
C. PUMP INTAKE – This displays the pressure with which the apparatus pump
is supplied. This value will match the “Master Inlet Pressure” gauge on the
pump panel.
20
FDNY Probationary Firefighters Manual
Chapter Three Add. 1 PRO PRESSURE GOVERNOR
2.3.1 The PPG is equipped with 6 buttons, each of which is described below:
A. IDLE - The “Idle” button will bring the engine to idle. This has the effect of
deactivating the PPG.
B. INCREASE - The “Increase” button will increase the pressure setting on the
PPG. When pressed momentarily, the pressure increases by 1 psi. When the
button is held down, the pressure increases in increments of 5 psi and 10 psi.
C. DECREASE - The “Decrease” button will decrease the pressure setting on the
PPG. When pressed momentarily, the pressure decreases by 1 psi. When the
button is held down, the pressure decreases in increments of 5 psi and 10 psi.
D. PSI - The “PSI” button will change the PPG operation to the PSI mode (as
previously described). This is the standard setting for all FDNY apparatus.
E. RPM - The “RPM” button will change the PPG to the RPM mode (as
previously described). The RPM mode is only used if the PSI mode
malfunctions or to initially gain a water supply in a drafting evolution.
F. PRESET - The “Preset” button brings the pump pressure quickly to a pre-
determined setting. This setting is further described below.
2.4.1 A key feature of the PPG is the “Preset”, which is a pre-determined pressure value
that is uniquely set for each engine apparatus. The purpose of this feature is to
quickly set the PPG to a level which will most commonly effectively engage the
PPG. This value is the sum of the apparatus idle pressure and the pressure of the
water supplied to the apparatus in Volume Operation.
A. This feature is critical because the PPG will not activate unless the setting on
the PPG is at least as high as the actual pressure being generated by the
apparatus pump. If the PPG setting is lower than the actual pressure generated,
the PPG will not be effectively engaged.
B. To ensure the activation of the PPG, the “Preset” is set to the minimum pressure
generated by the apparatus, which is equivalent to the total combination of the
apparatus idle pressure and the pressure of the water supplied to the apparatus.
C. In various parts of NYC, hydrant pressures can vary significantly, ranging from
40 psi to 100 psi. Due to this variation, the preset value should be set for each
apparatus using the procedure described below.
21
FDNY Probationary Firefighters Manual
Chapter Three Add. 1 PRO PRESSURE GOVERNOR
3.1.1 Before pressure can be supplied to a hoseline, the apparatus pump must be engaged
using the following steps:
A. Place the apparatus transmission in “neutral”
B. Engage the apparatus maxi-brake
C. Move the “pump shift control” to the pump position (located in the cab)
D. Place the apparatus transmission in “drive”
3.1.2 Once the apparatus pump is engaged, water can be supplied to a hoseline using
following steps:
A. Introduce water to the apparatus
B. Press and hold the “Push to Prime” button on the pump panel
(this expels air from the pump system)
C. Press the preset button on the Pro-Pressure Governor
D. Open the desired discharge gate to charge a hoseline
3.1.3 Slowly open the discharge outlet until the desired line pressure is reached. If the
discharge gate is fully opened and more pressure is required, depress the Increase
Button until the desired pressure is reached.
3.1.4 The Pressure Governor will adjust engine speed to maintain indicated pump
pressure as the hoseline’s nozzle is opened or closed.
4.1 At a relay operation, the pumper supplying the water is called the “supply pumper” and the
pumper receiving water is called the “operating pumper”.
4.2 A concern at a relay operation is ensuring the activation of operating pumper’s PPG.
4.2.1 This can be a problem because the operating pumper is receiving water from the
supply pumper at a pressure greater than hydrant pressure. The operating pumper
is receiving the discharge pressure of the supply pumper, which is hydrant pressure,
plus the idle pressure of the supply pumper. This number will be roughly 55 psi
higher than regular hydrant pressure. Based on local hydrant pressure, this number
can range from 95 psi to 155 psi.
22
FDNY Probationary Firefighters Manual
Chapter Three Add. 1 PRO PRESSURE GOVERNOR
4.2.2 Since the operating pumper’s PPG will only effectively engage if the setting on the
PPG is higher than their actual pump pressure, the PPG will not activate at their
normal Preset value.
4.3 The ECC of the operating pumper must be aware of this difference and set their PPG to
match the “Master Pressure Gauge” of the apparatus. This will be equal to the idle pressure
of the operating pumper, plus the pressure supplied by the supply pumper (which is equal
to their apparatus idle pressure, plus hydrant pressure). Based on local hydrant pressure,
this number will range from 150 psi to 210 psi.
4.4 To minimize the difference in supply pressures, the ECC of the supply pumper should
supply water at their preset value (which is their idle pressure, plus hydrant pressure)
4.5 The operating ECC will coordinate with the supply ECC to ensure enough water is supplied
to meet pressure demands of the operating pumper.
23
FDNY Probationary Firefighters Manual
Chapter Three Add. 1 PRO PRESSURE GOVERNOR
24
PART TWO
25
26
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
Tiller Aerial
27
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
1.3 The third type of ladder apparatus currently in service is the TOWER LADDER. The
Tower Ladder (TL) was introduced to the fire service several years ago. Its full
potential is still being developed. The effectiveness of this apparatus in ladder
company operations on the exterior of buildings for access to the interior, and for
rescue purposes is without question. In addition, it also provides a superior elevated
large caliber stream capability.
Tower Ladder
2. TERMINOLOGY
2.1 Tormentors: Hydraulic supports, with direct frame attachment. When lowered and
locked each becomes a rigid member, to provide a rigid operating base bypassing the
apparatus suspension.
♦ Rear mount: (2) tormentors adjacent to turntable at rear with controls on rear of
apparatus.
♦ Tiller: (2) tormentors adjacent to turntable at center of apparatus (front of trailer
section). Controls are on pedestal.
♦ Tower Ladder: Chassis supported at (6) points. (4) jacks- one at each corner of
apparatus and (2) outriggers alongside turntable.
2.2 Aerial: 100 foot, 4 section ladder made of Corten Steel. Bed ladder is the base
section, which is fixed (does not extend or retract). Upper 3 sections are moving
(sliding) sections. Each section has a handrail, which tapers to beam at top.
2.3 Rungs: Cross members between beams which are used for climbing. Rungs are
spaced 14” apart.
2.4 Turntable (pedestal): Platform at the base of the aerial or tower ladder. On aerial
ladders this platform is used to mount and dismount the aerial. On both aerial and
tower ladders the turntable contains the pedestal controls, from which the operator
can operate the aerial or tower ladder.
28
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
26
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
30
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
31
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
♦ Operate Aerial:
1. Raise Bed Ladder.
Depress AERIAL ENABLE FOOT SWITCH at the base of the
pedestal.
Raise the ladder by pulling back slowly on the hoist lower lever.
Release HOIST/LOWER lever when sufficiently elevated.
32
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
2. Rotate Ladder.
♦ Placing Ladder.
1. Depress knob on top of Bed Ladder Control and push handle away,
directing ladder toward objective. Return handle to NEUTRAL position
when underside of beam is about 2" to 6" from objective. It is expected
that the weight of the men climbing ladder will place ladder in the
supported position.
2. Aerial Ladder Placement:
To The Roof: Extend the ladder so that the tip is at least 5 feet
above the point where the ladder comes in contact with the building.
To A Window: Placement must allow for unimpeded access and
egress at this window. Therefore, the ladder tip should be less than 6"
over the window sill. Recommended distance of the tip from the
objective is 2" to 6". In case of rescue, use the 2" positioning so that
the ladder will rest against the window sill after weight is put on it.
Alongside a fire escape: Against the building (2" out) with the tip
about one to three feet above the balcony railing. This affords easier
access to the ladder.
Note: Remember the loss in height resulting from retracting the
ladder to apply ladder locks.
33
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
♦ Coordination: Always face the aerial when climbing or descending. Eyes should
look up or forward- this will provide better balance. Avoid looking down. If
necessary to look down, look over shoulder without leaning backwards.
♦ Hands- must have one hand in contact with the aerial at all times unless secured
to aerial with leg lock or with personal harness/ life belt hook to rung. Hand
movement should be coordinated with foot movement- left hand with left foot;
right hand with right foot. On steep angles it may be necessary to grab rungs.
♦ Feet: Stand on rung with ball of foot, avoiding driving heel of boot into rung.
Each foot positioned to avoid cable.
♦ Body Position: Body should be perpendicular to ground to allow for best balance
and best support of weight carried. Climbing too close to aerial will impede
climb. Leaning back will cause too much weight to be supported by arms and you
are more likely to fall.
♦ Stop climbing at roughly the third rung from the tip and keeping the left hand on
the handrail, transfer the right hand to the rung near the left beam.
♦ Pivoting on left foot, lean to left to butt right shoulder to building with head and
body outside the window.
♦ Right leg is brought up and over the right side handrail so the climber is now
straddling the top rung and facing left.
♦ Left hand is moved to top rung, palm down. Right hand is then turned around so
that the top rung is grasped in a trapeze fashion.
♦ While maintaining grip on top rung with both hands bring left leg into room and
gradually ease weight over sill into room to test floor area. Let go of aerial only
when certain that floor area is secure.
34
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
♦ Grasp the top rung with the right hand palm up.
♦ Straddle top rung, and then shift weight and move left foot to third rung.
♦ Pushing up with left hand pivot body on ball of left foot to swing right leg out and
put right foot on third rung.
♦ Place right hand on right handrail (facing the aerial) and begin descent.
♦ Stop climbing at rung nearest top of parapet. Bring both feet to same rung.
♦ Grasp handrail on dismount side in a baseball grip and bring feet together.
♦ Maintaining grip, bring outboard foot to parapet and test stability while
supporting weight with leg still on the aerial.
♦ Move outboard hand to underside of rung then follow with the other hand.
♦ Supporting body weight with two hands, test integrity of roof with feet
♦ Grasp overhead rung, place feet on parapet and pull up. (this step not necessary if
there is no parapet or cornice)
♦ Place one foot then the other onto rung level with parapet.
35
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
♦ Never remove people via aerial ladder when they may be calmed and held safely
at that location or removed via a safer means of egress. The preferential order for
removal of people is via: INTERIOR STAIRS, HORIZONTAL EXITS, FIRE
ESCAPES, LADDERS, LIFE SAVING ROPE.
♦ Prepare for a rapid ascent as the trapped people may attempt to climb onto ladder
without assistance. Climbing the ladder while it is being extended or retracted
exposes members to severe injury and may jeopardize the rescue effort.
♦ Ascend the ladder followed by the chauffeur. Climb into window and assist
victim out feet first to the chauffeur and then search the area. Firefighter must
realize that other victims may be inside and the victim may be unable to inform
him about other occupants.
Note: The chauffer following in ascent on the aerial will keep the
chauffeur closer to the controls. (Only in an extreme emergency such as direct
exposure to flame or great heat will the movement of the ladder with the
firefighter and the victim on it be justified).
♦ To descend with an ambulatory victim, place yourself one rung below the rung
the victim is standing on. Descend in unison, i.e., right foot for right foot and left
foot for left foot. Keep the victim between you and the ladder at all times and
maintain physical contact with him. At steeper angles, have the victim grasp the
rungs. This will facilitate your control. Talk to your victim. Constantly reassure
the victim and praise his actions. Try to talk him into looking straight ahead or up
and not down, as he might freeze on you.
♦ If the victim panics, take control by pressing him against the ladder with your
body. Do not resume the descent until he is capable of continuing, if the descent is
difficult or tiring, another firefighter should `back up' the member carrying or
assisting persons down the ladder.
♦ Removal is not considered complete until he has been assisted all the way to the
ground. Do not leave him on the turntable.
♦ If required, render first aid until relieved. Assist him to an ambulance if necessary.
These actions shall not be taken if you are needed to assist in additional rescue
operations.
♦ When there are two victims to be removed, the order of removal is dependent on
variables difficult to predetermine.
36
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
In many instances, one of the people will have climbed out on the
ladder before a member has reached this position and there will be no
need to make a preferential determination as to removal.
A serious fire in the front might cut off ladder descent in a short
period of time. Both members assist the most helpless victim onto the
ladder and the chauffeur assists the victim below the point of danger
and then to the street. While the chauffeur is slowly descending, the
OVM climbs onto the ladder and assists the more ambulatory person
onto the ladder and complete descent is made. In this instance, time is
the prime consideration, in effecting a complete removal of victims
below the danger point and in preventing the possibility of your retreat
being cut off.
A serious fire in the rear, cutting off interior descent and no available
front fire escape, presents another problem. Since the fire is not
pushing out the front windows the time required to effect removal of
victims is less critical. In this case, consideration can be given to the
simple removal first and then concentrate on the difficult removal
which will require two members.
37
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
♦ Stabilizer Supports
The chassis is supported at six points while the boom is in operation, i.e., two
hydraulically operated jacks are located at the front and two at the rear of the vehicle (total
of four), and two out-rigger type jacks in the middle of the apparatus. All supports have a
direct frame attachment to bypass the apparatus suspension and provide a rigid operating
base.
When the stabilizer supports are lowered for boom operation, hydraulic "holding" valves lock
the fluid in each cylinder, thus each cylinder becomes a rigid member to support the
apparatus under all conditions of operation.
To eliminate any possibility of stabilizer support collapse brought about by loss of fluid
from a cylinder, a mechanical lock is also provided at each jack and outrigger. These locks
(pins) must be inserted manually.
All jacks and outriggers must be lowered until each reaches the end of its stroke before
raising the boom. Tower ladders are not designed to operate with outriggers and jacks
down on one side only. Exception: If apparatus is not level, lower the jacks and outrigger on
the low side first, then the jacks and outrigger on the high side until unit is level as possible.
Note: Raising the high side fully before raising the low side, or raising only one side
when on level ground, can cause damage to the suspension system.
Outriggers can easily be placed between parked cars when necessary. Jacks and outriggers
must be on firm ground and locked.
To judge that outriggers will clear all obstructions, a 6-ft. hook may be used as a gauge.
Tower ladders have indentations in the turntable to accept outriggers. This necessitates
that outriggers must be moved clear of the turntable before operating the boom AND boom
must be returned to its original position (turntable arrow markings aligned) before outriggers
are bedded.
Any member operating a tower ladder must personally verify the placement of all outriggers
and jacks prior to raising the boom from the bedded position. If a member commences to
set up a tower ladder apparatus for an operation and then decides to abort the operation,
the member must:
or
38
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
♦ Boom Assembly:
The boom assembly consists of four box sections which telescope within each other. The
first section is alloyed steel and the three telescope sections are aluminum alloy. The
extension mechanism consists of two double acting cylinders which provide power in
extension and retraction. The boom hydraulic system has hydraulic "holding" valves,
which will prevent the boom from moving in the event of a hydraulic line failure.
♦ Basket
The basket is constructed of alloy aluminum and has a floor area of approximately 15 sq.
ft. Permanently mounted on the front surface of the platform is a Stang Intelligent
Nozzle, permitting flexibility in water tower operations. The underside of the floor and
the front railing of the basket may be covered with a fire resistant shield.
Whenever a tower ladder operation is in progress, the pedestal position must be staffed.
This provides an extra pair of eyes to warn of impending danger and override basket
controls in an emergency.
• Three controls similar to those on a metal aerial ladder are provided on the
turntable. These controls are for raising and lowering, extending and
retracting, and rotating the boom assembly. Operating controls at the pedestal
allow for smoother positioning than the controls in the basket.
• Master Power Switch - Supplies electrical power for the Master Control
Valve, Master Console panel lights, engine start, deadman control and
platform (basket) controls.
• Engine Start Button - allows engine to be re-started in case of stall from the
Master Control Console.
39
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
CAUTION:
2. In the area at the base of the boom and turntable are three sets
of manually operated isolation valves, one pair for each hydraulic
circuit, e.g., 1) raise-lower, 2) extend-retract, 3) rotation. Should
one of these 3 control valves malfunction for any reason, the
isolation valves for the particular function can be closed leaving
the other systems operable.
40
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
When no other solution is possible, member may escape from the basket
by means of the fixed telescoping ladder mounted on top of the boom
sections or by life saving rope in conjunction with the Personal Harness,
which ever is most appropriate for the situation.
♦ Water System
Note: There are various model TLs in the field and companies
involved must refer to their manuals for specifics.
♦ Communications
41
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
♦ General Precautions
42
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
8) Ground stability.
43
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
Specific Details
Positioning on Hills:
44
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
♦ Rescue via basket is affected in several ways. Entering and exiting from
basket shall be through the double-acting swinging gates. Initially the basket
is elevated to a point where the middle railing of basket is level with the
window ledge, or level with the top railing of the fire escape.
♦ Positioning of basket must be such that the Stang nozzle will not interfere
with the rescue operation. This will require an angular approach that will
permit ease in entering or alighting from basket.
♦ When many trips of the basket are required to remove a great number of
occupants, safe removal need not necessitate delivery directly to the street
level. Occupants may be placed at lower levels of the fire building or any
other area of refuge.
EXAMPLES:
45
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
The air movement resulting from large caliber stream use must be
considered. This air movement effect of the stream will drive heat
and combustible gases into uninvolved areas of the building
♦ Employment of Streams
Positioning the nozzle close to and low in the window will insure:
46
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
♦ Water Delivery
47
FDNY Probationary Firefighters Manual
Chapter Three FDNY APPARATUS
5. CONCLUSION:
This section introduced the primary apparatus of ladder companies currently in service. At any
incident one of the initial objectives is to properly position the incoming ladder company
apparatus due to the aerial/tower ladder capabilities and the need for portable ladders and tools to
be in proximity of the incident. Since it’s so important to achieve this objective, it’s equally
important that the members operating are familiar with, the operation, as well as capabilities and
limitations of this apparatus.
48
Probationary Firefighters Manual
Chapter 4
SAFETY
4
TABLE OF CONTENTS
SECTION PAGE
1. OPERATIONAL GUIDELINES IN PERSONAL
PROTECTIVE CLOTHING (PPC) ..................................................... 1
In an effort to reduce the number and severity of firefighters burn injuries, especially
those to the lower extremities, the Department has outfitted all members with Personal
Protective Clothing.
2. DESCRIPTION
2.2. To effectively furnish the desired level of protection, all elements of the PPC must be
worn. In particular, the thermal liners of the Bunker Gear must be in place at all times.
2.3. Bunker Gear should be kept clean. Dirty Bunker Gear can absorb more heat, causing the
degree of protection to become questionable, and may actually cause the material to
ignite.
2.4. Bunker Gear, when properly used and maintained, will afford a limited period of
protection, to exit an area which has become, or is about to become, untenable. It is not
a "Close Proximity Entry Suit" such as that used in Airport Crash and Fire Rescues. In a
flashover situation, a Bunker equipped member must be within 5 to 10 feet of an exit in
order to survive.
2.5. FDNY Bunker Pants are provided with either of two different kinds of knee protection.
Level II Morning Pride Heat Channel Knee Pads are issued to members already assigned
to Ladders, Rescues and Squads. Members assigned to Engine companies and
Probationary Firefighters are assigned Level II Morning Pride Heat Channel Knee Pads
covered with Arashield. Level I Knee Pads ( without heat channels ) are no longer
acceptable as they do not offer the necessary levels of protection for members. When
knee pads wear out, thet shall be replaced through the Quartermaster. Bunker Pants
shall never be worn without knee pads in place.
2.6. The wearing of Bunker Pants Suspenders is an essential part of the Bunker Pants
function in protection of the lower extremities. The wearing of the suspenders is not
optional, but mandatory. When members are not wearing the suspenders during fire
operations, the Bunker Pants have a tendency to slide down especially when wet, thereby
reducing the effectiveness of the knee pads in fully protecting the knee area from burns.
1
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
2.7. The hood is part of your personal protective equipment (PPC) and its use is mandated by
the Department. It is anticipated that the use of protective hoods will have the same
positive results as bunker gear, further reducing burn injuries to our members. The
hood shall be worn whether dry, damp, or saturated with moisture.
2.8. If the protective hood is not available, the Officer On Duty shall instruct the member to
have his/her helmet ear flaps down and coat collar up and secured by the neck strap prior
to entering the fire area.
2.9. It must be understood that wearing the hood in a hostile environment somewhat reduces
your ability to note changing fire conditions in the immediate area. Therefore, you
must leave the area immediately upon feeling any pain or discomfort through the
hood, unless the area can be immediately cooled by a hose line. Remember; always
stay alert to deteriorating conditions.
3.1.2. Members are advised to use boot jacks when doffing their PRO boots. When
used properly, PRO boot jacks will extend the life of the PRO boots
significantly.
3.1.4. Protective Hood*- The Protective Hood must be donned in the following manner
to ensure a proper seal of the SCBA facepiece.
♦ Don the hood completely over your head before putting on the Bunker Coat.
♦ Don the Bunker Coat.
♦ Push back the hood from your head onto the back of your neck to store the
hood in the ready position.
♦ Before entering a smoke filled environment, the mask facepiece is to be
donned, followed by the pulling up of the hood over the head and around the
facepiece.
♦ WARNING: Failure to don the SCBA facepiece first, before the hood, will
result in an improper seal of the facepiece resulting in the loss of air from the
positive pressure facepiece.
*NOTE: The procedures for the proper donning, use, and care of the Protective Hood are
found in the training video, "Protective Hoods", issued to each firehouse. All units shall
periodically incorporate the viewing of this video into drill periods.
2
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
3.2. Responding
3.2.1 Structural Fires – Due to the possibility of members operating without full PPC
and also due to the negative perception by the public, all members except
chauffeurs shall don their PPC prior to responding. In hot weather, if the
apparatus is not equipped with a functioning air conditioning unit, coats and
protective hoods may be dispensed with while responding.
3.2.3 When responding from other than quarters, the above rules apply.
3.2.4 Members shall not drive Department apparatus while wearing rubber boots.
Driving with bunker pants and the Chauffeur boots or leather boots is optional.
3.2.5 Department Chauffeurs and Tiller operators should not insert their thumbs thought
the wristlet loops of the bunker coat prior to driving apparatus. The wristlet
material may prevent members from getting a firm grip on the steering wheel,
which could result in loss of control of the apparatus. After the apparatus is
positioned, members can easily insert their thumbs through the wristlet loops at
that time.
4.1. Chief and Company Officers shall ensure that all members wear the proper level of
protective equipment while operating at the scene of fires and emergencies. Any
member entering the fire building must have all PPC donned.
4.2. Chief Officers when operating in a command capacity outside the fire building, may
dispense with wearing the complete bunker ensemble when, in the exercise of their best
judgment, wearing the bunker gear is not necessary. The helmet must be worn at all
times. However, Chief Officers required to enter the fire building, must have all PPC
donned.
3
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
5.1 Members wearing Bunker Gear must be alert to rising heat levels and heat buildup. The
thermal protection provided by Bunker Gear can mask signs of high heat conditions,
allowing members to over-commit or delay backing out when conditions warrant. This
can greatly increase the member’s risk of incurring a serious burn injury. A bunker
equipped member exposed to moderate heat conditions for a prolonged period can
eventually be burned through the clothing.
5.2 When a unit has some members wearing protective hoods and other members operating
without hoods, additional pre-cautions must be observed, particularly by the Officer in
Charge.
5.2.2 Members wearing Bunker Gear and protective hoods retain more body heat andare
more readily subjected to heat exhaustion than members operating without hoods.
The operating limit is the maximum safe period of operation for Bunker and hood
clad members.
6. OPERATIONAL CONSIDERATIONS
6.1. The removal of pent up heat and humidity within the Bunker Garment is a high priority.
As soon as operations permit, members should start ventilating their bodies, by
removing the coat and opening the front flap of the pants. This is of particular
importance during the summer months. Because of the debilitating effect of operating
while in Bunker Gear, Chief and Company Officers must be more keenly aware of the
need for relief of units that have been engaged in firefighting.
6.1.1. Units shall be promptly relieved. Additional units should be utilized to perform
overhaul and salvage functions, where necessary.
6.1.2. Lack of oxygen contributes to heat stress; therefore a greater emphasis on mask
usage during extinguishment and overhaul is essential.
Rotation and relief of personnel during the firefighting periods are an essential
part of good fire management when companies have been engaged in operations
that are unusually demanding,
6.2. The fire environment must be continuously monitored to detect elevated heat levels.
Use of the technique known as the duckwalk is recommended when members encounter
heat conditions which are felt through the bunker pants or where operations involve
areas where water has accumulated.
4
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
6.2.1 Chief Officers and Company Officers must be aware that due to the weight and
restrictive nature of bunker gear, operations in both engines and ladders will be
performed in a less rapid fashion and will require a greater period of time to
complete.
6.3 Chief Officers must monitor the units under their command and provide appropriate
periods of rest and rehabilitation when indicated. Officers must be proactive and
consider the following factors:
6.4.3 Battalion Chiefs may authorize up to 2 hours of rest and rehabilitation and Deputy
Chiefs up to 3 hours.
Advanced cleaning of bunker coat and pants is performed by a private contractor. Upon
return of bunker gear, the member must inspect bunker gear for serviceability. If there are
any doubts on the serviceability of the gear, an evaluation shall be made at the
Quartermaster.
7.1.1 Easily removed dirt particles should be brushed off of the coat and pants at the
scene of operations. Other debris can be rinsed off with a stream of water.
7.1.2 When necessary, the bunker gear can be washed in the decontamination sink in
quarters using the following procedure:
5
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
• Only a soft bristle brush shall be used for lightly scrubbing away any dirt
or stains
7.1.3 The protective hood shall be washed in lukewarm water using a mild detergent.
Do not use soap or chlorine bleach. They are harmful to the hood’s stitching.
7.1.4 Never wring water out of the protective hood, this can stretch the material,
instead squeeze the water out. When washing the protective hood, it is necessary
to follow the guidelines stated in the training video.
7.2.1 Wet bunkers and protective hoods should be hung up to dry in a well ventilated
area out of direct sunlight. The knee pads should be removed during drying.
7.3.1 This will consist of member’s second bunker coat and bunker pants. The two sets
of bunker gear shall be worn alternately by members between advanced
cleanings. Members shall commence wearing the one set of bunker gear
continuously from tour to tour when the other set of gear is picked up for
advanced cleaning. On return from advanced cleaning, this second set of gear
shall be stored and worn only when the first set of gear is drying or being
repaired. After the first set of gear is dried or repaired, the member shall place
the second set back in storage and wear the first set of gear. Approximately six
months later, when the first set of gear is picked up for advanced cleaning, the
member shall start wearing the second set of bunker gear continuously from tour
to tour for the next six months, except when it is drying or being repaired.
Members shall continue on the schedule, alternating use of each set of bunker
gear approximately every six months, with the advanced cleaning cycle
indicating when to switch wearing the sets of gear. This also allows for each
garment piece to annually undergo an advanced inspection to identify
unserviceable gear that requires repair or replacement.
6
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
7.4 Gloves
7.4.1 Brush debris from your gloves. When necessary, hand or machine wash with a
mild detergent/soap and water. Do not use bleach. An alternative washing
method is to wear your gloves and wash them while they are on your hands. Do
not wring the water from the gloves as it may tear the moisture barrier. Allow the
gloves to dry naturally, inside and out. Provide a means to permit air to circulate
within the interior of your gloves. Do not machine dry or dry gloves on a
radiator. Soft brushing will help maintain suppleness of the gloves. When the
gloves are wet they can cause steam burns if holding hot objects. Dry gloves will
also keep members hands warm in cold weather.
8.1.1. When bunker gear has been ripped, torn, or subject to severe heat (thermal
loading) its effectiveness as personal protective equipment may be significantly
compromised. Members must routinely examine their bunker gear for rips, tears
and the signs of thermal loading: a charring, burning, or brown discoloration of
the bunker gear fabric. Whenever a member's Bunker Gear has been ripped, torn,
or displays any signs of thermal loading the garment(s) must be examined at the
Department's Quartermaster to determine whether repair or replacement is
necessary.
8.1.3. The FDNY Liaison Officer will make the final determination as to whether the
garment will be condemned and replaced or repaired.
8.1.4. Loaner gear is available for members with burned, discolored and/or damaged
bunker gear for use pending evaluation, repair and/or replacement. Loaner gear
may be obtained from SOC. Call SOC via telephone, Special Operations
Command will fax loaner gear form to company who will complete the form and
fax back to SOC. Unit must then contact their division messenger to pickup
loaner gear at SOC. Loaner must be returned to SOC by the division messenger.
7
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
8.2.1. At the start of each tour and after each use, inspect your hood for tears,
discoloration, stretching or open seams. If you find any problems notify the
officer on duty.
8.2.2. Members shall be guided by the department guidelines as stated in section 2.9,
5.2.1 and 5.2.2 of this AUC 310 if you are unable to use your protective hood due
to:
8.3.1. There are two separate procedures for delivering bunker gear to the Quartermaster
for an integrity examination. The procedure to be used depends on whether or not
the member who had been wearing the bunker gear has incurred a burn injury
which requires medical leave to be granted.
A. When the affected member does not require medical leave for a burn injury
the division messenger of member’s assigned division shall deliver his/her
bunker gear to the Quartermaster at the Fort Totten location only. If necessary
member can obtain loaner gear from SOC as per 8.1.4.
B. When the affected member does require medical leave for a burn injury the
Officer on Duty must comply with section 11.3.6 of the Regulations by
tagging the bunker gear, placing it OOS, and contacting the Safety Battalion
for instructions. The Safety Battalion will arrange for the collection of the
bunker gear for its own investigation. At the conclusion of its investigation,
the Safety Battalion will determine if the garment should be examined at the
Quartermaster for repair or replacement due to thermal loading. Safety will
deliver the garment to the Quartermaster for this evaluation. (Note: If the
assigned Safety Battalion will be retaining control of the bunker gear for an
extended period, pending completion of its investigation, they shall forward a
report to the Chief of Safety and a copy to the members unit indicating that
loaner gear shall be issued to the affected member.)
8
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
A. The Quartermaster will notify the officer on duty of the member’s assigned
unit when the repairs have been completed. The member’s assigned division
messenger shall report to SOC to return any loaner gear that has been issued
and obtains a signed receipt. The division messenger then proceeds to the
Quartermaster with signed receipt and picks up member’s repaired gear and
signs Quartermaster’s voucher.
8.4.2. If a determination is made that the bunker gear is to be condemned and replaced,
the Quartermaster will either issue new bunker gear, if the member is present, or
notify the officer on duty of the member’s assigned unit to notify the division that
the affected member’s new gear is ready to be picked-up by the member’s
assigned division messenger.
A. The member’s assigned division messenger shall report to SOCto return any
loaner gear that has been issued and obtain a signed receipt. The division
messenger then proceeds to the Quartermaster with signed receipt and picks
up member’s replacement bunker gear and signs Quartermaster voucher.
8.5.1 The following procedures shall be followed for the collection, bagging, temporary
replacement, transporting and cleaning of contaminated non-disposable personal
protective equipment and work duty uniform.
8.5.2 When personal protective equipment or work duty uniforms are contaminated
with large amounts of body fluids:
9
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
A. Disposable gloves and eye shield/face mask shall be worn by the member
bagging the contaminated items.
A. Place contaminated disposable articles that are not intended for re-use into red
biohazard bags.
8.5.5 Officers and members are reminded to review and consult with the CFR Manual
for any additional information or questions in regards to contamination by bodily
fluids and blood borne pathogens.
SOC cleans equipment and gear and issues loaner bunker gear. SOC doesn’t
issue replacement equipment.
*The Officers of the units who require loaned gear due to a Hazardous Materials
incident shall notify SOC Decon Unit and their assigned Division. The Division
messenger for those affected units will pick-up the required loaner gear from SOC
and deliver the appropriate loaner gear to the affected units. SOC will pick-up the
contaminated equipment and gear. After decontamination, the assigned Division
messenger will pick-up and return clean equipment and bunker gear.
10
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
9.2. In order to comply with the OSHA Bloodborne Pathogen Standard ( CFR 29, Sect.
1910.1030 ), while in quartes the firefighter protective ensemble shall only be kept at the
designated storage area on the clothing rack, at the designated area on or near the
apparatus for rapid donning by on-duty members or in a separate area designated for
such storage. Firefighting protective ensembles shall not be stored in personal lockers.
9.3. The Department has provided gear bags for the use of members transporting their
firefighting protective ensemble. Under OSHA Standards for Hazardous Materials and
Bllodborne Pathogens, when members are required to transport any of the elements
comprising the firefighting protective ensemble, such items must be transported in the
gear bag to prevent hazardous materials and bloodborne pathogen exposure. Gear bags
shall be utilized by all members to transport their firefighting protective ensemble.
When transporting the firefighting protective ensemble in a private vehicle, such items
shall be placed in a gear bag before being placed in the passenger compartment or the
trunk of the vehicle. Furthermore, the firefighting protective ensemble shall be kept
within the gear bag at all times when such items are stored in the living quarters of a
home.
9.4. To prevent cross contamination due to sharing of gear bags, the following provisions are
enacted:
9.4.1 Prior to placement into the gear bag, the firefighting protective ensemble shall be
placed into a plastic bag supplied by the Department.
9.4.2 The plastic bag containing the firefighting protective ensemble shall then be
securely closed before being placed into the gear bag.
9.5 Once a member has completed transporting the firefighting protective ensemble, the
plastic bag that served as a protective liner shall be disposed of in the regular trash unless
it is heavily soiled with blood or body fluids. In this event, the plastic bag would be
disposed of as per section 8.5.4 of this chapter.
11
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
9.5.1 Grossly contaminated gear bags shall not be cleaned by members. If the gear bag
becomes slightly contaminated, the member shall clean the bag following
guidelines in the CFR-D Manual, Chapter 3, Section 15.
9.6.1 Members are responsible to use the gear bag with the plastic liner anytime they
transport their firefighting protective ensemble
9.6.2 Members are responsible to return gear bags to assigned unit immediately after
completing the transportation of the bunker gear.
9.6.3 Gear bags are the property of the Department and are for official use only. Gear
bags shall not be used for any purpose other than transporting the firefighting
protective ensemble.
12
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
SECTION TWO
UNSAFE ACTS
This bulletin lists unsafe acts which can and have caused serious injuries to our members.
The purposes of this bulletin are:
1. Point out specific instances of unsafe acts for corrective action.
2. Emphasize the importance of safety.
3. Enable members to anticipate, and eliminate, actions that may cause injuries at operations.
1. GENERAL
1.1. Poor maintenance of, or failure, to use protective clothing and equipment: - Torn or
frayed clothing does not provide adequate protection and may snag and cause loss of
balance and injury. Failure to utilize protective clothing and equipment provides no
protection.
1.2. Wearing of jewelry: The safest procedure is to remove all jewelry at start of tour.
Finger rings: Gloves will not protect against crushing injuries and rings will compound
problems.
Gloves are not worn in quarters and serious injuries have occurred to members
performing necessary maintenance work on tools, apparatus and equipment. Rings can
snag on protrusions and cut into flesh.
Earrings: Ears are exposed at fires and metal will act as a heat sink. This act was
demonstrated in this department when members received face burns from exposed metal
rivets on mask facepiece in the 1960's. Subsequently this was corrected. In addition it is
possible for earrings to snag during donning of mask leading to tearing (avulsion) of the
skin.
1.5. Improper placing of tools and equipment in operations area increases hazard of tripping.
1.6. Operating directly below area where hose, tools and other equipment are being used,
raised or lowered.
13
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
1.7. Operating close to edge of roof, particularly with back to edge of roof.
1.8. Member positions himself between hoseline and edge of roof. Burst line or sudden
movement of line could cause member to fall over edge of roof.
1.9. Operating line on icy roof without being secured by a rope around the waist tied to a
substantial object.
1.10. Failure to use hose tags or other means of identifying hose lines. Injuries caused by
chauffeur starting water in line not fully positioned, or shutting down water in
operating line working in a key position.
1.13. Using axe with badly worn or mushroomed head to strike other metal tools, resulting
in flying steel chips and injuries.
1.14. When positioning pumper for drafting water, members get between pumper and edge
of pier while apparatus is moving.
1.15. Struggling with a whipping hose line, instead of shutting down the supply.
1.16. Improper lifting of tools, equipment and persons. Spine not in line with direction of lift
or pull.
1.17. Working in poorly lit areas unnecessarily; under utilization of portable lighting.
2. LADDER OPERATIONS
2.1. Life belt improperly donned with hook facing in wrong direction. Could lead to
difficulty in hooking on and increase fall hazard.
2.2. Positioning tower ladder outriggers without utilizing additional member on opposite
side from control panel.
2.4. Mounting an aerial ladder turntable with hose over shoulder. Snag could cause member
to fall to street.
2.5. Moving on or off aerial ladder at roof with hose over shoulder. Snag could cause
member to fall to street.
2.6. Ordering water started in line before line is secured or in position, when operating
from a ladder.
2.7. Straddling a hoseline while operating from a ladder. Possible injury if hose bursts.
14
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
2.8. Ascending or descending a ladder that is not butted, or secured at the top.
2.9. Eye injuries can be caused when members are looking up while pulling down ceilings
with a tool. Look down before pulling down.
3.1. Climbing raised ladder to bring rope between taped rungs without ladder being butted.
3.2. When lowering, failure to use guide line when necessary. Ladder moved into vertical
position by members working too close to edge of roof.
3.3. Failure to keep all persons away from area beneath ladder being hoisted or lowered.
4.1. Men working on top of apparatus, in dangerous positions during placement of ladder
pipe.
4.3. Chauffeur moves ladder before tillerman has completed securing ladder pipe to ladder
and has moved to a safe position. Unexpected movement of ladder could cause
tillerman to lose balance and fall to street.
4.4. Failure to observe good lifting practices when moving pipe into position on top of
ladder.
5.1. Multiversal or other large caliber stream device left unattended or unsecured during
operations.
5.2. Movement of multiversal or large caliber stream device attempted while stream is still
operating.
5.3. Hands or fingers inserted into clipper valve in attempt to stop leaking water, with lines
charged, resulting in cut fingers or hands.
5.4. Members unprepared for nozzle reaction when water is started, resulting in loss of
balance and loss of line. Officer and chauffeur must maintain communication.
5.5. Standing directly in front of capped outlets while high pressures are being developed
during operations. Defective or loose fitting caps could blow off and strike men.
5.6. Failure to maintain a clear area in the immediate vicinity of hose tests to avoid injury
to members and passersby.
15
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
5.7. Starting water prematurely. Persons not clear of the area may be struck by the heavy
caliber stream or injured by the smoke and heat pushed at them by the stream.
5.8. Excessive hose improperly stretched into operations area, increasing tripping hazard.
6.1. Fog lines advanced too rapidly, before fire is completely extinguished, exposing
members to re-flash hazard.
6.2. Equipment moved too close to fire before it is ready to be used. Wind change or flare-
up may result in loss of equipment and injury to members.
6.3. Solid stream directed into burning liquids before foam is flowing. Splash or possible
boil-over may cause burns.
6.4. Advancing fog lines without providing ventilation in advance of the line for the release
of the heat and super-heated smoke. May result in burns to the men on the line.
6.5. Failure to use extra care in advancing fog lines. Some positions of fog nozzle interfere
with vision.
7.1. Improper hauling of hose onto roof. Rope and hose walked onto roof rather than
pulled. Members may walk off roof or into roof openings when poor visibility exists
from smoke or darkness.
7.3. Rope used to secure line on roof placed at improper level and across line of travel,
causing members to walk into or trip over rope.
8.1. Improper stance by members during operations. Back not kept straight and in line so as
to properly support weight, causing back injuries.
8.2. Raised ladders coming into contact with overhead wires or other obstructions, or
moved into dangerous angles by failing to watch tip, allowing ladder to get out of
control and fall.
8.3. Failing to keep body in line with weight thrust when raising or lowering ladder.
8.4. Hands and feet placed in line of movement of extension fly ladder. May result in injury
if control is lost or halyard should break and fly section drop.
16
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
8.5. Rope trailing from extension ladder during carrying operation exposing members to
tripping hazard. Unsecured halyard may allow fly section movement if rung locks slip
or fail.
8.6. Failure to give preliminary command "Ready" or "Prepare To" so as to alert members
to the next command.
9. KNOTS
9.1. Knots tied improperly, or too loosely, or wrong knots used, allowing persons or objects
to slip out.
11.1. Failing to check clearance behind member before swinging Scott Air Pak over
shoulder.
11.2. Improper testing of masks due to not understanding the reasons for tests.
11.3. Lack of knowledge of emergency measures to be taken when mask does not function properly.
11.5. Gauges not checked for proper amount of air before use. Air may have leaked out since
roll call check or cylinder not replaced after use since last check.
12.1. Failure to check tightness of cap on unused outlet before opening hydrant.
12.2. Starting water in line before members are prepared, causing line to whip and injure members.
12.3. Failure to take proper position for receipt of orders and observation of operations.
12.4. Using excessive pressure, making nozzle difficult to operate, or causing hose to burst.
12.5. Using improper stage position (volume vs. pressure) leading to much jockeying of
controls and erratic operation of hose lines.
12.7. Moving suctions into and out of water by using apparatus, instead of hoisting or
lowering by rope during drafting operations.
17
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
12.8. Failure to prevent cars from going over hose lines may leave members in precarious
position without water momentarily.
12.9. Failure to use hose tags and subsequent possibility of shutting down wrong line,
leaving members in a precarious position without water.
12.10. Failure to set relief valves to prevent excessive pressure which results in burst hose
and/or too much nozzle pressure.
13. MISCELLANEOUS
13.1. Ladder company personnel trimming cornice, sidewalls, window frames, etc. from
bucket of tower ladder, and dropping debris to street below prior to verifying that the
area is clear of personnel.
18
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
SECTION THREE
HYDRATION & RE-HYDRATION
1. GUIDELINES FOR NUTRITION AND HYDRATION
2. Members should follow accepted guidelines for hydration and nutrition. Beverages,
foods and substances that should be avoided include the following:
• Excessive fluids
• Protein supplements
3. Five gallon water jugs carried on all apparatus shall be checked and refilled with fresh
water at each roll call.
4. Members shall consume fluids to satisfy thirst during rehabilitation and be encouraged
to continue hydrating after the incident.
5. Nausea and loss of thirst can be an early sign of dehydration and heat stress. Therefore
all members should demonstrate the ability to consume some fluids. If members cannot
demonstrate the ability to take in some fluid, they should be medically avaluated.
• Decreases strength
• Loss of coordination
20
FDNY Probationary Firefighters Manual
Chapter Four SAFETY
SECTION FOUR
1. WATERFRONT OPERATIONS WHILE WEARING BUNKER GEAR
1.1 Tests were conducted to determine the amount of buoyancy a member (Fire or
EMS) wearing bunker gear would have if the member accidentally fell into the
water. The testing included falling from heights between 1 ft. and 10 ft.
1.2 Testing was done in fresh and salt water with and without an SCBA. Each test
was started with a member wearing a full set of bunker gear, including personal
harness, PSS kit, flashlight, and hand tools.
2. OBSERVATIONS
2.1 Results of the testing have shown that members wearing Bunker Gear, with or without
an SCBA, quickly become submersed.
2.2 The higher the fall the less opportunity there may be to remain at the surface.
3. OPERATIONS
3.3 Each company’s Water Safety Kit should be brought to the point of operation.
Safety lines should be readied for use and attached to members operating in, over
and around water. At least one 20 ft straight ladder should be dedicated for the
purpose of member removal should the need arise.
4. CONCLUSION
4.1 In the event you fall into the water, do not attempt to swim - call for help, try to
remain calm and slowly tread water. Thrashing about will reduce the amount of
time you may be able to keep yourself at the surface.
21
Probationary Firefighters Manual
Chapter 5
ROPE
OBJECTIVE: • To familiarize members with the most commonly used knots and
hitches used by the FDNY
• To familiarize members with the FDNY’s complement of ropes,
life belts and harnesses and the proper use of same
• To familiarize members with the FDNY’s procedures of using the
lifesaving rope
FDNY REFERENCE: • FDNY Training Bulletins; Rope 1-8 and all data sheets
• Evolutions 23, 24, 25, 27, 28,29, 30, 31, 31A, 31B, 31C, 32
5
Rope Contents
5. Anti-Chafing Device 31
6. Search Rope 35
8. Personal Harness 44
9. Lower a Member 54
R
ope is one of the oldest tools used by the fire department. It is valuable in applications
such as performing rescues, hauling of tools, and various general uses. The ability to tie
proper knots is crucial to insure safety during rope maneuvers.
NOMENCLATURE
MEASUREMENT
Measurement of rope required to form the various knots and hitches is made by stretching the
arms out and holding the rope between the hands. The full distance measured is one arm length.
A half arm length is measured by holding the rope in the left hand at the center of the chest and
stretching the rope to the right. Note that approximately 6" is allowed to dangle from the right
hand.
1
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Knots and hitches are shown tied loosely to demonstrate the proper method. In practice, all knots
and hitches shall be made up securely.
HALF HITCH
The half hitch is used when hoisting or lowering tools and equipment. It is also used as a binder
to secure knots.
CLOVE HITCH
The clove hitch is formed by making two half hitches. It is used in the hoisting and lowering of
tools and equipment, in the hoisting of hose lines, when drafting water and various other
operations. Unless otherwise specified, a binder shall always be tied in conjunction with a clove
hitch, except where it is tied away from the working end of the rope.
When making a clove hitch for the hoisting of tools and equipment, the pull on the rope may be
from the upper or lower hitch depending on how the hitch was started or if the slip-over hitch
was used.
2
FDNY Probationary Firefighters Manual
Chapter Five ROPE
SLIP-OVER CLOVE HITCH
← →
The slip-over clove hitch is made by forming two half hitches in the hand. It may be used to
advantage by slipping the completed clove hitch over the end of the object, as in hoisting the
hook, halligan tool or extinguisher .
↑ →
←
With rope held in this loop is held in position End of rope brought up
position, press down with left hand until knot through loop with right
with fingers and up with is completed. hand, taken around in
thumb of right hand and back of rope held in left
forming loop in rope. hand.
↓ °
The bowline knot will not
slip nor tighten under
tension and is easily untied.
It is used in hoisting and
lowering ladders (20’ and
over). The bowline is useful
Continue to bring rope Take hold of rope end coming where a loop is needed that
around until end is down through loop with right will not slip.
placed down into loop hand and pull tight to complete
held with left hand. knot.
3
FDNY Probationary Firefighters Manual
Chapter Five ROPE
BECKET BEND
↑ →
The becket bend is used to join the ends of two ropes. When hoisting the portable deluge nozzle
to heights exceeding 60 feet, the becket bend is used to join the two utility ropes.
4
FDNY Probationary Firefighters Manual
Chapter Five ROPE
ROLLING HITCH
← ↑ →
↓ ° ±
Until four turns have been Bring rope end over the Slide the turns of rope
made. four turns and around close to hose butt and pull
hose with a half hitch. ends tight.
″
The rolling hitch is used to secure a hose line which has
been hoisted via the outside of a building. It is tied directly
beneath the couplings just below the edge of the roof or
window. The free end of the rope is taken back on roof and
secured to some substantial object. The rolling hitch
relieves the couplings of the weight of the hose.
5
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Measure 1 1/2 arm lengths; Form a small loop with Pull the doubled end
loop rope back on itself. left hand by turning the completely through the
Hold doubled rope in left rope forward and up over loop.
hand about 4’ from looped the doubled rope held in
end. Place loop across right hand.
doubled rope above left
hand.
5
°
Fold the large loop behind Pull the doubled rope Make up knot securely.
the small loop. down through small loop.
The bowline on a bight is a very important knot. It is commonly used to lower a fireman to
rescue persons trapped at windows which are not readily accessible to ladders. Other rescue
purposes include the lifting of persons from excavations, sewers, etc., and the lowering of
persons from places where safer escape routes are not available. The bight forms a cradle to
support the fireman and the bowline prevents the rope from tightening or slipping. The bowline
on a bight is used in conjunction with a half hitch and a slippery hitch tied about the chest.
Note: The 4' referred to under illustration 1 is approximate. Allowances must be made
according to size of the person to be lowered.
6
FDNY Probationary Firefighters Manual
Chapter Five ROPE
SLIPPERY HITCH
Rope from
above
This knot is used in conjunction with the Bowline On A Bight when hoisting or lowering a
person. It is tied around the upper chest to give stability and eliminate binding on the chest that
would be caused by an ordinary half hitch.
7
FDNY Probationary Firefighters Manual
Chapter Five ROPE
SUBSTANTIAL OBJECT KNOT OR
The Substantial Object Knot, also known as a Clove Hitch And Binder On The Taut Part Of
The Rope, is used to tie off to an anchor point during the Lowering A Member, Rescue Pick-Up
and Single Slide Evolutions. It is tied by making three half hitches over the top of the rope.
Figure 1 Figure 2
Pull a double strand of rope around Have 4 feet of rope from the point
your substantial object. Fig. 1 where the ropes cross. Fig. 2,3
Figure 3 Figure 4
Cross the working end in your right hand over the rope in your left hand forming a
letter ‘D’. Fig. 4
8
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 5 Figure 6
Reach into the ‘D’ with your right hand, grab the working end and pull it through the hole
creating a half hitch. Fig. 5 and Fig. 6
Figure 7 Figure 8
9
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 9 Figure 10
Make two more half hitches in the same manner. Fig. 8 , Fig. 9 and Fig.10
Figure 11
Tighten and set the knot. Fig. 11 A properly tied knot will have enough rope left to tie one
more half hitch. Fig 11 and Fig. 12
10
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 12 Figure 13
A finished knot. Fig. 12 A loose knot for illustration purposes only. Fig 13
11
FDNY Probationary Firefighters Manual
Chapter Five ROPE
The Figure 8 knot is tied at the end of a rope and keeps the rope from slipping out.
Put the end through the loop Dress and set the knot
12
FDNY Probationary Firefighters Manual
Chapter Five ROPE
BUTTERFLY KNOT
The Butterfly Knot is used to make a loop in the middle of a rope. It can be used as a tie-off
point or to make a three directional pull.
Figure 1 Figure 2
Figure 3
Figure 4
13
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 5
Figure 6
Figure 7
14
FDNY Probationary Firefighters Manual
Chapter Five ROPE
1. SPECIFICATIONS
• 1" nylon tubular webbing in 20' lengths
• Breaking Strength 4000 lbs
• Knotted breaking strength 3000 lbs
3. PURPOSE
3.1 To be used to assist in the removal of an unconscious member or civilian from a
hazardous environment.
3.2 Spinal immobilization may not be possible due to the need for immediate removal of the
member from an imminently dangerous situation.
3.3 To enhance simple maneuvers through the use of knots attached to an individual
firefighter's body or SCBA. This will improve leverage and allow additional individuals
to assist in the removal. In the event that a firefighter should become unconscious during
an incident, members in close proximity will be able to quickly conduct a removal.
3.4 Webbing shall only be used for dragging victims; no vertical lifts should be attempted.
4. DISTRIBUTION
4.1 Each Officer and member will be issued a length of webbing, which will become part of
the member's personal equipment.
5. REPLACEMENT
5.1 To requisition replacement lengths of webbing the Officer on Duty should forward an
RT-2 to the tool room.
15
FDNY Probationary Firefighters Manual
Chapter Five ROPE
6.2 The webbing should be inspected monthly and after each use.
ILLUSTRATION
1 2
3 4
16
FDNY Probationary Firefighters Manual
Chapter Five ROPE
KNOTS AND HITCHES USED TO HOIST AND LOWER
Rope from
above
HALF HITCH
(approx. 5” below end
of handle)
AXE
CLOVE HITCH
& BINDER
(close to head of axe)
Rope from
above
HALF HITCH
(placed under adz end)
CLOVE HITCH
& BINDER
(close to head of fork)
17
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Rope from
above
HALF HITCH
Tie a clove hitch and binder on handle. Bring working end of rope
up and tie a half hitch under hook. The hook is hoisted and lowered
with the hook end up.
Note: Lock breaker with chisel end is hoisted and lowered in same
manner, adz end up. Lock breaker with fork end is hoisted in same
manner as halligan tool.
HOOK
CLOVE HITCH
& BINDER
(approx. 6” from
end of handle)
Rope from
above
HALF HITCH
(under cap)
CLOVE HITCH
& BINDER
(approx. 3”
from bottom)
EXTINGUISHER
18
FDNY Probationary Firefighters Manual
Chapter Five ROPE
PULL-DOWN HOOK
Tie a clove hitch and binder on handle close to metal. Bring working end of rope around top of
hook and back to handle end. Tie a half hitch around handle about 12" from the end. The hook is
placed in position on the object to be pulled; a strain is kept on the rope and the men move back
to the working position.
Hooks are tied in this manner for pulling down partitions, fences, copings, etc., enabling
members to work in safe areas away from falling objects.
19
FDNY Probationary Firefighters Manual
Chapter Five ROPE
1. INTRODUCTION
1.1 Nylon rope is stronger than manila rope of the same size. A breaking strength test was
conducted on our 9/16" nylon life saving rope. The rope broke at 10, 240 pounds.
1.2 Acceptance of the rope requires that it have a minimum breaking strength of 9000
pounds. In addition, our rope must survive a drop test. This test consists of tying a 600
pound weight to the end of the rope, and dropping the weight from a platform ten feet,
seven inches high. There must be two feet of slack in the rope. The rope must survive
five such drops.
1.3 Our new life saving rope not only survived the drop test it also survived an additional
breaking strength test. The section of the rope subjected to the drop test was laboratory
tested and broke at 9800 pounds. The life saving rope has a high breaking strength
quality.
1.4 In order to retain this strength, the rope must be properly maintained.
1.5 Members should be aware that the actual length of our Life Saving Rope may be less than
the nominal length of 150 feet due to natural shrinkage after several years in the field.
Over a period of time some ropes have shrunk 8 to 10 feet. This fact should be considered
when planning to use the life saving rope.
2. MAINTENANCE
2.1 First and foremost, the life saving rope shall be used only for life saving purposes, and
always with the anti-chafing device. Use of this rope for any other purpose is strictly
prohibited.
2.2 A life saving rope subjected to the weight of two people shall be placed out of service
forthwith and replacement requested.
20
FDNY Probationary Firefighters Manual
Chapter Five ROPE
2.3 Immediately after a life saving rope has been subjected to the weight of one person the
rope shall be carefully examined for any signs of damage or abrasion before being placed
back in service. Proper journal entries shall be made by the company officer of the results
of such examination. An entry shall also be made in red on the Life Saving Rope Record
Card (RP-100). The officer, after supervising the examination of the rope, shall notify the
Division of Safety by telephone of the incident.
2.4 The life saving rope can lose from 10% to 15% of its strength when wet. This loss of
strength occurs when the rope is submerged in water at room temperature for twenty four
hours. Whenever a rope becomes wet it shall be allowed to dry naturally before being
repacked and stored on the apparatus. The rope regains its strength when it dries.
2.5 Ice particles within the strands of a rope can damage the inner fibers. Therefore, a frozen
life saving rope shall be placed out of service.
2.6 Dirt on the surface and imbedded in rope acts as an abrasive to the strands and fibers. If a
life saving rope becomes dirty, it shall be washed with mild soap and water. It should be
allowed to dry naturally before being repacked and stored on the apparatus.
2.7 The detrimental effect of rust on nylon rope cannot be overemphasized. The life saving
rope should be stored where it will not come in contact with rust. If a rust stain is found
on the life saving rope, it should be immediately removed with soap and water. A
persistent rust stain is a definite indication of fiber damage and a reduction in the strength
of the rope. It should be placed out of service and replacement requested.
2.8 Nylon rope is susceptible to damage from acids and their fumes. Formic acid,
hydrochloric acid, sulfuric acid, nitric acid and phenol are highly destructive to nylon
rope. If the rope comes in contact with acids or their fumes, it shall be placed out of
service and replacement requested.
2.9 Prolonged exposure to sunlight (ultra-violet rays) or fluorescent light is injurious to nylon
rope. Therefore, the life saving rope shall be stored where the effects of sunlight and
fluorescent light are kept to a minimum.
2.10 Nylon rope when exposed to heat over 300°F will progressively lose strength, and will
melt at 482°F. Rope that has been exposed to highly heated surfaces cannot be considered
safe and shall be placed out of service and replacement requested.
2.11 The life saving rope must be stored in the driest compartment on the apparatus and the
carrying case must be stored in the upright position. Due to heat transmission, the rope
shall never be stored on engine covers or in compartments adjacent to the engine
compartment.
21
FDNY Probationary Firefighters Manual
Chapter Five ROPE
2.12 When a rope is repeatedly twisted in one direction, a kink will develop. Kinks pulled
through a restricted space will seriously damage a rope. A kink should be removed from a
rope by rotating the rope counter to the direction of the kink. (See Fig. 1). Every effort
shall be made to prevent a rope from kinking during its use.
Figure 1
2.13 Strand hockles develop when force is used to remove a kink in rope. A hockle is very
difficult to remove. A hockle reduces the strength of a rope by 40% to 50%. Should a
hockle occur in the life saving rope, the rope should be placed out of service and
replacement requested. (Fig. 2)
Figure 2
22
FDNY Probationary Firefighters Manual
Chapter Five ROPE
2.14 All units (except Engine Companies) shall inspect and repack the Life Saving Rope every
Monday on the 9x6 tour. Engine Companies shall inspect and repack on Tuesdays.
Record the inspection on the Life Saving Rope Card (RP-100).
2.15 Inspection shall cover the entire length of the rope. Look for cut fibers, abrasion, rust,
wetness or anything that might indicate possible degradation of the rope.
2.16 This inspection should not be conducted on the apparatus floor due to the possibility of
the rope coming in contact with material that might be harmful to it. Since the apparatus
floor is concrete, it is a prime means of causing abrasion to the life saving rope. Abrasion
is one of the primary causes of a rope losing its strength.
2.17 When any doubt exists regarding the serviceability of a life saving rope it shall be placed
out of service.
3. CONCLUSION
3.1 The 9/16" nylon life saving rope is stronger than any rope available today that will satisfy
our needs. Given proper care and maintenance, it will provide us with a reliable life
saving tool.
23
FDNY Probationary Firefighters Manual
Chapter Five ROPE
The Life Saving Rope is stored in, carried in, and deployed from the Back Pack carrying
case. See next section for the description of the Back Pack carrying case.
2. INTENDED USE
2.1 To lower a firefighter or another person from a roof or upper floor to a place of safety
below.
2.2 To lower a fireman from a roof or upper floor to enable him to remove another firefighter
or person from an untenable position.
3. OPERATIONS
3.1 Number of turns required when using the Atlas Life Belt.
24
FDNY Probationary Firefighters Manual
Chapter Five ROPE
4. NOTES:
4.1 This life saving rope shall be used only for rescue operations. It shall not be used for drill
purposes.
4.1.1 If the life saving rope is subjected to the weight of two people, it shall be placed
out of service and replaced.
4.1.2 Immediately after a life saving rope has been subjected to the weight of one
person the rope shall be carefully examined for any signs of damage or abrasions
before being placed back in service. Proper journal entries shall be made by the
company officer of the results of such examination. An entry shall also be made,
in red, on the Life Saving Rope Record Card (RP-100). The officer, after
supervising the examination of the rope, shall notify the Division of Safety by
telephone of the incident. Ropes that are damaged or show signs of wear are to be
put out of service and replaced.
4.1.3 Deleted
4.1.4 Nylon rope can lose from 10% to 15% of its strength when wet. This strength loss
occurs when a rope is submerged in water at room temperature for twenty four
hours. It regains its strength when it dries.
4.1.5 Care shall be taken to avoid wetting the life saving rope. A wet rope shall be
allowed to dry naturally before being repacked in the back pack carrying case.
4.1.6 A history of every life saving rope shall be maintained on the Life Saving Rope
Record Card.
25
FDNY Probationary Firefighters Manual
Chapter Five ROPE
FIGURE 1
2. INTENDED USE
2.1 To store, carry and deploy the life saving rope, with the anti-chafing device attached.
2.2 This case provides for instantaneous use of the life saving rope in lowering and sliding
operations by eliminating the need to flake out the rope before use.
26
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.1 The entire rope is coiled CLOCKWISE. The diameter of the coil should be
approximately 4 feet. (Fig. 2).
FIGURE 2
3.2 Stand the open carrying case on the floor, to the left of the coiled rope.
3.3 Place the hook of the life saving rope in the left front corner of the back pack carrying
case. Move to the right, making a COUNTERCLOCKWISE circle just over one half the
width of the bottom of the case. (Fig. 3).
3.4 Moving to the left, make another circle slightly overlapping the first circle. (Fig. 3).
Figure 3
3.5 Continue in this manner until the entire rope is coiled in the case.
27
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.6 Remove 3 feet of rope from the carrying case and place the anti-chafing device on this
section of the life saving rope. (Fig. 4).
3.7 Grasp the hook of the life saving rope and pull 1½ arms length of rope through the anti-
chafing device. Tie a bowline on a bight on this section of the rope.
FIGURE 4
3.8 Move the anti-chafing device along the rope to the bowline-on-a-bight. (Fig. 5).
FIGURE 5
28
FDNY Probationary Firefighters Manual
Chapter Five ROPE
FIGURE 6
3.9 Fold the anti-chafing device as shown in Fig. 6, and place the bowline-on-a-bight and the
anti-chafing device in the back pack carrying case as shown in Fig. 7.
FIGURE 7
29
FDNY Probationary Firefighters Manual
Chapter Five ROPE
FIGURE 8
3.10 Carefully fold the remaining rope in front of the anti-chafing device. (Fig. 8)
FIGURE 9
3.11 While closing the flap of the carrying case, pass the hook of the life saving rope through
the window of the flap and place it in the pocket on top of the flap of the back pack
carrying case. (Fig. 9).
30
FDNY Probationary firefighters Manual
Chapter Five ROPE
___________________________________________________________________________
Anti-Chaffing Device
DESCRIPTION
4.2.2 The end of each device is flexible to permit overlapping at the roof edge. (Figure 2)
Figure 1 Figure 2
C
B
A
31
FDNY Probationary FirefighterManual
Chapter Five ROPE
4.3.1 After the life saving rope has been packed in the carrying case, remove 3 feet of rope and
pass the rope through the canvas sleeve from either end of the device. (Figure 3)
Figure 3
4.3.2 Grasp the hook of the life saving rope and pull 1½ arms length of rope through the
anti-chafing device. Tie a bowline on a bight on this section of the rope, and place the
rope and anti-chafing device in the carrying case as described in Section 3 of Rope 1 Data
Sheet 1.
4.4.1 When used in a lowering or single slide operation, the anti-chafing device is placed so that
the flexible end overlaps the roof or the parapet wall toward the street. (Figure 2)
4.5.1 Check the anti-chafing device for dryness and undue wear each time the life saving rope is
repacked.
4.5.3 Immediate replacement for the anti-chafing device is imperative since the life saving rope
cannot be used without it.
32
FDNY Probationary Firefighters Manual
Chapter Five ROPE
4.5.4 The life saving rope shall be completely repacked weekly. The rope shall be repacked
from the opposite end each time. One hook shall be marked with red tape for
identification. (Fig. 2).
Note: Do not replace the anti-chafing device until the entire rope has been packed in the
carrying case. This will allow any twists in the rope to work themselves out during the
packing procedure.
4.6.1 Each time the life saving rope is repacked, the back pack carrying case shall be checked
for cleanliness and dryness.
4.6.2 The back pack carrying case can be cleaned by sponging with mild soap and water. It is
essential that the back pack carrying case be thoroughly dry before repacking the life
saving rope.
4.6.3 Replacement back pack carrying cases shall be requested from the Technical Services
Division
5. DEPLOYMENT OF ROPE
5.1.2 The snap hook, anti-chafing device and the bowline-on-a-bight are removed from
the case through the window in the flap. Sufficient rope is pulled through the
window before securing to a substantial object.
5.2.1 Unsnap the top flap, pull the snap hook back through the window, and remove the
snap hook, anti-chafing device and bowline-on-a-bight from the case.
33
FDNY Probationary Firefighters Manual
Chapter Five ROPE
5.3.1 After the life saving rope has been packed in the back pack carrying case, remove 3 feet of
rope and pass the rope between the canvas and the webbing from either end of the
device (Fig. 4).
FIGURE 4
5.3.2 Grasp the hook of the life saving rope and pull 1½ arms length of rope through the anti-
chafing device. Tie a bowline on a bight on this section of the rope, and place the rope and
anti-chafing device in the back pack carrying case as described in the previous section.
5.4.1 When used in a lowering or single slide operation, the anti-chafing device is placed so that
the flexible end overlaps the roof or the parapet wall toward the street (Fig. 1).
5.5.1 Check the anti-chafing device for dryness and undue wear each time the life saving rope is
repacked.
5.5.2 The anti-chafing device shall be air dried when necessary.
5.5.3 Immediate replacement for the anti-chafing device is imperative since the life saving rope
cannot be used without it.
5.5.4 Replacement anti-chafing devices shall be requested from the Technical Services Division.
34
FDNY Probationary Firefighters Manual
Chapter Five ROPE
SEARCH ROPE
1. INTRODUCTION
1.1 The search rope is to be used as a supervisory tool to maintain search team integrity
under difficult circumstances. The failure to maintain search team integrity has led to
serious injuries and fatalities to firefighters during operations. The search rope is also
designed to provide members with finding a means of egress under heat and smoke
conditions when searching for life or fire. The rope can also be used to assist in search,
prevent duplication of areas searched and to locate units for assistance or relief.
1.2 Examples of when the search rope shall be deployed include, but are not limited to:
♦ Large areas such as gymnasiums, ballrooms, convention centers, etc.
♦ Complex areas such as schools, banks, office areas, commercial/industrial buildings, etc.
♦ Below grade areas e.g., subways, tunnels, basements, cellars.
♦ Areas where maze like conditions may be encountered.
Note: Search rope shall be deployed in the above locations even in light to moderate heat and smoke
conditions since conditions can deteriorate rapidly.
2. DESCRIPTION
2.1 The Search Rope is made of a 7.5 mm diameter Kernmantle design. The rope is 200 feet
long with a double-action snap hook at the working end and a single-action snap hook at
the opposite end that secures the rope to the bottom of the bag. This will help to repack
the rope in the correct direction.
2.2 The rope is packed in a yellow carrying bag marked with the company number.
2.3 Each search rope will have a company I.D. tag attached to the rope and to the bag. (Figure 1)
Figure 1 Figure 2
2.4 The adjustable carrying strap on the bag has been designed to keep the bag parallel to the
ground. It allows the rope to pay out of the bag smoothly and helps the officer and members stay
in constant contact with the rope. (Figure 2)
3.1 The search rope uses a series of plastic markers to identify both direction and distance.
3.2 The markers are a cone shaped high strength plastic material, and are approximately 1 ½”
long. Their width is tapered from 1” to ½”. The tapered cone shape is designed to provide
members with the ability to determine which direction they are proceeding (Into or Out of the
IDLH) while operating with a gloved hand. The narrow ½” end of the cone clearly identifies the
direction of egress OUT of the IDLH. (Figure 3)
35
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 3
Figure 4
5. DEPLOYMENT
5.1 When a unit deploys the search rope they must notify the Incident Commander (IC) or Sector/Group
Supervisor.
5.2 Pay out the working end of the rope through the round hole in the flap of the carrying bag.
36
FDNY Probationary Firefighters Manual
Chapter Five ROPE
5.3 Secure the double-action snap hook to a substantial non-movable object in a clear, safe
environment (floor below fire, enclosed staircase, objects on sidewalk such as lampposts,
mailboxes, street signs, etc). Remember an area that is clear at the beginning of an
operation may not be clear when you return.
5.4 The bag is designed to be worn over the shoulder but may be carried in one hand.
5.5 The officer controlling the search pays out the rope while keeping it taut, maintaining
a handhold on the rope or bag at all times.
5.6 The rope should be tied off at intervals to help keep it taut and off the floor. The rope
shall be maintained approximately one to two feet above ground. This will keep it out of
water and make the rope easier to find. When changing direction or grade, the rope shall
be tied off. This allows the member to traverse the same ground when exiting.
5.7 Voice contact (without HT use) shall be maintained with all search team members.
5.8 If more than 200 feet of rope is needed, attach the double-action snap hook of a second
search rope to the single-action snap hook of the first rope.
5.9 If a team’s search is interrupted (e.g., low air, victim removal), tie off the line and leave the
bag with the remainder of the rope. Another unit can continue the search using this rope.
5.10 If there is nothing to tie off to, take a few wraps around the bag with the rope and leave in
place.
Note: Amount of search rope deployed may not be an indication of member's location in a
building. Due to the numerous turns and obstacles that may be encountered during a
search, distance/directional markers may only indicate amount of rope deployed and not
actual distance or location in a building. Example: in a maze-like layout, members may
have deployed 100' of search rope and actually traveled only 30' from the point of
deployment.
6. OFFICER
6.1 The officer is responsible to coordinate the search.
6.2 The officer is responsible for overall search operations including but not limited to, informing
members of search objective (searching for fire or life), special hazards, control, deployment and
communications.
7. Operational Considerations
♦ Maintain the rope taut.
♦ Keep track of firefighters’ locations.
♦ Use the Thermal Imaging Camera to account for and direct members during their search.
♦ Use the Thermal Imaging Camera to monitor fire conditions.
♦ Refrain from searching in areas distant from the search rope.
8. THE SEARCH TEAM
8.1 Under most conditions, the number of members assigned to the search rope team should
be limited to three.
37
FDNY Probationary Firefighters Manual
Chapter Five ROPE
8.2 A unit (other than 1st alarm) receiving orders to search an area requiring a search rope
shall maintain unit integrity and will perform this function with all members.
♦ The officer and two firefighters will operate as the first search team.
♦ The remaining members shall remain at the tie off point to:
a. Standby as the back up team.
b. Monitor search team progress.
c. Monitor handie-talkie transmissions and when necessary relay any messages to or
from the search team with the IC or Sector/Group Supervisor.
d. Monitor fire conditions and notify the search team of any changing conditions affecting
their operation.
e. Be ready to assist the search team with recoveries or needed tools/equipment.
f. Monitor the team's on-air time.
9. RELIEF COMPANY
9.1 The relieving company should communicate directly with the initial search team regarding any
hazards that the relief team may encounter and provide information on areas already searched.
9.2 If it becomes necessary to relieve a unit at a forward point of the search, the relieving company
should enter the area to be searched with their right hand in contact with the rope (if possible).
The company being relieved should exit the IDLH with their right hand in contact with the rope
(if possible.) In this manner, companies entering and leaving the area will all be on opposite
sides of the rope and will not interfere with one another.
9.3 Members relieving a company on a search rope must communicate with each other about the areas
already searched to eliminate duplication of effort and to ensure areas that have not yet been
covered are subsequently searched.
9.4 The company being relieved must (if possible) tie off the search rope and leave the bag at the
point where the search was discontinued. The relief company should continue the search
from the point where the bag was left.
9.5 Officers shall account for all members of their unit outside the IDLH when they have been
relieved or have completed their assignment.
10.1 Members must realize that search tactics will differ greatly when using the search rope, as opposed
to searching without the rope.
10.2 When searching in maze like conditions or large open areas, there is a greater chance for members
to become disoriented, separated and lost if the search rope is not used. There usually is not a
means of egress in close proximity.
10.3 When using the search rope, a slower, more cautious and deliberate approach should be employed
with emphasis on maintaining the safety and integrity of the search team.
38
FDNY Probationary Firefighters Manual
Chapter Five ROPE
10.4 When searching off the rope, members should advise the officer of the area searched,
a description of the area searched, and results of search. This will help members visualize the
area. The officer shall relay the results of the search to the IC or Sector/Group Supervisor.
10.5 Communications is the key to a good search. It is the responsibility of the search officer to
maintain verbal contact (without HT use) with the searching members.
10.6 Companies conducting the search should utilize the fundamentals found in the Training Bulletin
Search and other FDNY bulletins.
11. RESTRICTIONS
11.1 The Search Rope is to be used ONLY for search or guide purposes, not for lifting or lowering.
11.2 Members must be aware that if the rope is tied off at different locations, the length of distance
traveled may be less than shown by the distance/directional markers.
12. TRAINING AND MAINTENANCE
12.1 Inspect the rope after each use.
12.2 Repack and inspect quarterly.
12.3 Companies shall conduct frequent drills using the rope. Various building configurations should
be utilized if possible. Company Commanders shall develop a schedule for training, inspecting
and repacking the search rope.
12.4 When the Search Rope becomes contaminated from fireground contaminants, the Search Rope
shall be decontaminated in quarters using a sponge and water. A mild detergent may be used if
necessary.
13. PACKING THE ROPE
13.1 Ensure the rope is dry before packing.
13.2 Lay the rope out on a clean dry surface, removing all kinks and coil clockwise beginning with
the end of the rope that has the double-action snap hook.
13.3 Secure the single-action snap hook at the end of the rope to the “D” ring in the bottom of the bag.
This “D” ring alerts the member when they are at the end of rope and prevents loss of contact
with the rope.
13.4 Coil the rope into the case counterclockwise. Occasionally, press the coils down with on hand to
prevent one coil from falling below the coil underneath. This keeps the rope from becoming
knotted when deployed.
13.5 Pass the double-action hook through the hole in the cover and secure the cover closed. Pass
nylon tab through the double-action hook and snap the nylon tab to the side of the bag. (Figure 5)
Figure 5
39
FDNY
Probationary Firefighters Manual
Chapter Five
ROPE
1. DESCRIPTION
1.1 F.D.N.Y. Designation Atlas Nylon Life Belt
1.2 Weight 7 pounds
1.3 Sizes A. Small, 34 – 44
B. Large, 42 – 54
C. X-Large, 46 – 58
2. COMPONANTS
(A) BUCKLE (G) BUCKLE TONGUE
(B) ENLARGED BILLET LOOP (H) HANDLE
(C) "O" RING (I) TRIPLE ACTION GATE
(D) WAIST STRAP (J) RAPPEL HOOK
(E) I.D. # (K) BODY PAD
(F) BILLET (L) GROMMETS
Figure 1
D E F
A B
C
G H J K
I L
40
FDNY Probationary Firefighters Manual
Chapter Five ROPE
2. INTENDED USE
2.1 It shall be worn by the member lowering a firefighter or another person from a roof or
upper floor to a place of safety. The bowline on a bight and the slippery hitch shall be
tied on the individual being lowered.
2.2 It shall be worn by the member lowering another firefighter for a rescue pick-up using the
knots described in 2.1 above.
2.3 It shall be worn by firefighters removing themselves from an untenable position by
means of a single slide.
2.4 It shall be worn by members during portable and aerial ladder operations as directed.
Note: The life belt shall not be used to make a rescue pick-up via a single slide.
3. OPERATION
3.1 The life belt hook has a gate and a gate lock.
3.1.1 To open the gate, pull the triple action gate downward, then rotate the gate a
quarter turn to the left. (Figure 2)
Figure 2
41
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.1.2 The gate is squeezed and held opened with the right hand while applying four
(4) turns of rope onto the hook. (Figure 3)
Figure 3
The Gate is
Squeezed
and Held
Open with
the Right
Hand
3.2 After applying four turns of rope around the hook, the gate closes automatically after its
release. (Figure 4)
Figure 4
3.3 During use, the turns of rope must play out on the solid side of the hook and not the gated
side.
42
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.4 Do not touch the hook with the bare hand after use, because considerable heat is
generated from friction.
3.5 In all life saving rope operations, four (4) turns of rope are made around the solid part of
the hook.
3.6 The life belt shall be stored with the life saving rope.
4. IDENTIFICATION:
4.1 Attached to the nylon belt is a metal tag with a three digit identification number.
4.2 Do not stamp any identification markings into the metal parts of the belt.
4.3 All units are issued a large belt. Additional sizes (small or X-large) may be obtained by
forwarding a letterhead report stating the reason to R & D.
4.4 If the belt does not fit, replace it with the proper size. Do not alter the belt.
43
FDNY Probationary Firefighters Manual
Chapter Five ROPE
1. INTRODUCTION
1.1 The personal harness will provide members with a quick and safe means for life saving
rope rescues and emergency escapes as well as a safety belt for attachment to a tower,
aerial or portable ladder.
Caution: It is extremely important that the Life Saving Rope turns be wrapped
around the rappel hook in the proper manner. Training in the use of the personal
harness is imperative. Do not slide during rope training without the use of the protective
landing mat. The harness must always be attached to the bunker pants.
Note: Members MUST attach the harness snap hook to the waistband “D” ring
EVERYTIME they don their bunker pants.
2. DESCRIPTION
2.1 The personal harness is made of nylon webbing and has a minimum breaking strength of
6,000 pounds. The harness comes in three sizes (Small, Medium, and Extra Large) and is
adjustable to fit the various size requirements of individual firefighters. Each harness has
a unique I.D. number stamped onto a metal tag permanently attached on the inside of the
left leg strap. Small harnesses have a small ‘s’ at the end of the serial number, and Extra
Large harnesses have a small ‘x’ at the end of the serial number.
Figure 1
Waistband Handle Support Strap Belly Strap Buckle Hook Support Strap
Slide
Buckle
Waistband
Snap Hook "D" Ring
Left Handle
Leg
Strap Personal Safety Triple Action Gate
System "D" Ring
Rappel Hook
44
FDNY Probationary Firefighters Manual
Chapter Five ROPE
2.2 The rappel hook has a gate with a triple action lock.
2.2.1 Members must ensure the gate is in the closed and locked position prior to performing a
slide or lowering operation. To check that the gate is locked, apply lateral pressure on the
gate with left hand.
2.2.2 The rappel hook is positioned at the center of the waistband while in the stored position.
The rappel hook and harness handle are held in the stored position by two straps: a hook
support strap and a handle support strap. The handle support strap holds the harness
handle to the waistband and the hook support strap holds the rappel hook in a position to
the left side of the harness handle. See Figure 2
Figure 2
Hook Support
Handle Support Strap
Strap
Personal Safety
System “D”
Ring
2.3 A “D” ring is incorporated to the right side of the harness handle (P.S.S. “D” ring) to
provide a connection point to the Personal Safety System. The Personal Safety System
“D” ring is permanently attached to the harness and a carabiner is used to connect the
EXO descender to the “D” ring. The carabiner is used with the “D” ring so that a
firefighter can easily detach from the system once an area of refuge has been reached.
The storage bag holding the EXO descender, rope, and anchor hook is attached on the
right side of the personal harness.
45
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.1.1 The proper position for the waistband of the harness is across the upper level of the hip as
shown in Figure 2A.
Figure 2A
3.1.3 The waist strap has two adjustable slide buckles (Figure 3):
• a belly strap slide buckle to center the rappel hook and,
• a waistband slide buckle for proper fit around the waist.
Figure 3
46
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.2 It is imperative that the harness be properly adjusted to prevent a member from inverting
when using the Personal Safety System or rappel hook. Follow the steps below to insure
that the harness is properly adjusted:
3.2.1 Lay out the harness with the waistband "D" ring to the left. Grasp the waistband "D" ring
with the left hand, palm down.
3.2.2 With right hand, palm down, grasp the waistband at the midpoint between the right leg
strap attachments. The remainder of the harness will hang free from the right hand.
3.2.3 Position the "D" ring at the member's left side. Align the vertical section of the “D” ring
with the vertical seam of the bunker pants as shown in Figure 4A.
Vertical
Section of
D Ring
Seam
47
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.2.5 The right leg strap attachment must line up over the stitched seam of the bunker
pants on the members right side as shown in Figure 5A.
Edge of
Leg Strap
Seam
3.2.6 When the waistband "D" ring and the right leg strap attachments do not align as
described above, adjustment must be made as follows:
A. Lay the harness on a flat surface with the waistband "D" ring to the left (see
Figure 6).
B. Lengthen or shorten the belly strap by feeding the upper layer of webbing
through the belly slide buckle in the desired direction to align the waistband
“D” Ring as shown in Figure 4A.
C. Recheck harness and repeat until the “D” ring and right leg strap align
properly as shown in Figures 4A and 5A.
Figure 6
Rappel
Hook
Waistband
“D” Ring
Belly Strap
48 Slide Buckle
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.3 To complete the adjustment:
B. Again, grasp the waistband "D" ring with the left hand palm down.
C. Grasp the snap hook with the right hand palm down.
3.4 The harness is now extended in front of the member and the right foot is placed over and
into both leg straps (Yellow in color), as shown in Figure 7.
Figure 7
3.5 Pull the waistband upward on the outside of the right leg. The leg straps will be pulled
up on the inside of the legs toward the crotch.
3.6 Bring the snap hook behind your back to your left side and attach the snap hook to the
waistband "D" ring.
Note: Snap hook and waistband "D" ring will be on left side of body.
3.6.1 A proper fit of the waistband requires a slight degree of effort to connect the
waistband "D" ring and snap hook.
Note: The belly strap slide buckle is used only to ensure the proper position of the
harness handle and rappel hook.
The rear waistband slide buckle is used to insure a snug fit.
3.7 When the adjustment of the waist band is necessary to ensure a snug fit, lay the harness
on a flat surface with the snap hook to the left (see Figure 8).
3.7.1 Lengthen or shorten the waistband by feeding the upper layer of webbing through
the waistband slide buckle in the desired direction.
49
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 8
Waistband
Slide
Buckle
3.8 The leg straps should remain loose for a comfortable fit while the harness is worn prior to
rappelling or lowering operations.
3.9 Prior to sliding operations, the leg straps must be made snug by reaching back and pulling
down on the webbing of each leg strap until the tension of the straps are evenly
distributed. Don't over-tighten the leg straps! If the leg straps are over-tightened, the
waistband may be pulled down from its proper position.
3.10 When operations dictate the use of the rappel hook, the rappel hook support strap and the
handle support strap shall be released and the rappel hook will deploy to the center of the
harness handle. In a situation that dictates the use of the Personal Safety System,
only the handle support strap should be released. The Personal Safety System will
slide on the “D” ring to the center of the harness handle. The rappel hook support strap
will keep the rappel hook from interfering with the operations of the Personal Safety System.
3.11.1 Hold solid part of rappel hook in right hand (Figure 9). With left hand, pull down
gate and take ¼ turn to left and push gate toward solid part of rappel hook in right
hand. (See Figures 9, 9A, 9B, 9C)
Figure 9
50
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 9A Figure 9B
Figure 9C
3.11.2 Rope is always applied by taking turns under and over the rappel hook away from
the rappel hook and away from the body.
3.11.3 To close and lock gate, release from right hand. To ensure that the gate is closed
and locked, apply lateral pressure with left hand.
4. INSPECTION
4.1 Harness shall be inspected by the member at the start of each tour, and after each use.
4.2 Inspect entire harness for cuts, abrasions, discoloration and loose or damaged stitching.
4.3 Check operation of rappel hook gate and triple action lock.
4.4 If any abnormality of harness or rappel hook exists place it out of service.
4.5 If persistent or unknown stains are discovered place the harness out of service.
51
FDNY Probationary Firefighters Manual
Chapter Five ROPE
4.7 Whenever a personal harness is subjected to an impact load it shall be placed out of
service. A member free falling three feet or more is considered a sufficient impact load
to warrant placing the personal harness out of service.
4.8 When doubt exists regarding the serviceability of a personal harness, it shall be placed
out of service.
5. MAINTENANCE
B. Avoid placing nylon webbing in contact with metal as this may cause rust stains.
5.3 Remove dirt with sponge and water. A mild detergent may be used if necessary.
5.4 Decontaminating
5.4.1 Personal harness may be spot cleaned following the procedures of CFR-D manual
Chapter 3, Section 15.
5.4.2 When a personal harness becomes grossly contaminated, it shall be placed out of
service.
52
FDNY Probationary Firefighters Manual
Chapter Five ROPE
6. ACCOUNTABILITY
6.1 Maintenance of the harness is the responsibility of the member to whom it is issued.
6.2 The Company Commander must record the ID number of the harness with the name of
the member to whom it is issued in the office record journal.
6.2.1 The member is responsible for inscribing his or her name with an indelible marker on the
inside of the harness belly strap.
6.3 The harness shall be issued to all members up to and including the rank of Battalion
Chief. Upon promotion to Deputy Chief the harness is to be returned to the Research and
Development Unit.
6.4 Upon retirement or termination of service of any member, the harness must be returned to
the Research and Development Unit.
53
FDNY Probationary Firefighters Manual
Chapter Five ROPE
1. EQUIPMENT:
1.1 One nylon life saving rope with attached anti-chafing device in a back pack carrying
case.
2. OBJECTIVE:
2.1 To lower a Firefighter or another person from a roof or upper floor to a position of safety.
2.2 To lower a Firefighter from a roof or upper floor to enable the Firefighter to remove
another person from an untenable position to one of safety.
54
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Member 2 Member 1
3.7 Maintain position of the hook adjacent
to the coiled rope by placing one foot
on the snap hook, as Member #1 pays
out additional rope to the substantial
object. (Fig. 2)
3.8 Pay out rope from the top of the coil to
the substantial object and tie a clove
hitch and binder on the taut part of the
rope. (Fig. 2 and 3)
Figure 2
Member 2 Member 1
55
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 3
Figure 4
3.11 Tie the slippery hitch in the prescribed 3.10 Step into the leg loops and hold the
manner on Member #2 and slide the knot snugly against your stomach to assist
anti-chafing device up to the completed Member #1 in tying the slippery hitch.
slippery hitch.
3.12 Walk toward the lowering point to
remove all slack in the rope between
the substantial object and yourself.
3.13 Hold the anti-chafing device in the right
hand.
56
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 6A Figure 6B
Figure 6C Figure 6D
57
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 7A Figure 7B
58
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 7C Figure 7D
59
FDNY Probationary Firefighters Manual
Chapter Five ROPE
This completes the section on the lowering operation from a building WITH A PARAPET.
60
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 9A Figure 9B
61
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 9D
62
FDNY Probationary Firefighters Manual
Chapter Five ROPE
63
FDNY Probationary Firefighters Manual
Chapter Five ROPE
NOTES:
1. The nylon life saving rope shall be used for life saving purposes only. It shall not be used
for any other purpose.
2. Communication is essential in all rope rescue operations. The Officer in Command at the
fire or emergency shall be notified when any rope rescue operation is to be undertaken.
This will enable the O.I.C. to arrange for any assistance needed at the location of the
operation, e.g.; Guide Member at roof level and/or a member in the street for safety.
3. Before a rope rescue operation begins, check that there are no obstructions in line with
the planned descent, such as signs, wire, etc.
4. Every effort shall be made to lower an individual between the line of windows. This will
provide a smoother, easier descent and reduce exposure of the rope in case fire should
show at a window.
5. Members must be alert to look for a reliable substantial object on the roof, such as
bulkhead (Fig. 11A), aerial ladder (Fig. 11B), around a chimney or cut a hole, and tie
the rope around an exposed beam. (Fig. 11C).
Note: Plumbing vent pipes, sheet metal housings for roof vents, T.V. masts, newel posts or
banisters are not reliable substantial objects.
6. To increase the safety of any lowering operation, whether a parapet is present or not, will
require that the lowering point be midway between the roof's edge and the substantial
object. This is to prevent the Lowering Member being drawn beyond the roof's edge,
after hooking up onto "O" ring. (See Sec. 3.9 and 3.20).
64
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 11C
65
FDNY Probationary Firefighters Manual
Chapter Five ROPE
7. When performing any lowering operation, the life saving rope, must be perpendicular as
possible to the roof's edge at the point where the member descends.
7.1 If the angle of the rope from the substantial object to the roof's edge is too acute,
the weight of the person being lowered will cause the rope to slide along the roof
edge. This should be avoided. (Fig. 12).
7.2 Additionally, if the angle of the rope is too acute the Lowering Member will be
pulled uncontrollably by the rope, and the line of descent will also be drastically
affected as shown in (Fig. 12). This should be avoided.
8. When members are being lowered to perform a rescue pick-up, they must:
8.1 Give the command "STOP" to halt the lowering operation while out of reach of
the victim. This is to alert the guide member and/or the lowering member that the
member being lowered is approaching the victim.
8.2 Before this operation is completed in the safest possible manner, victims tend to
jump onto their rescuers. In this situation a victim could easily fall to the ground.
8.3 The rescuer will give instructions to the victim at this point in the strongest and
most forceful language necessary in order to complete the operation successfully.
8.4 Next, give the commands "DOWN, STOP, DOWN, STOP", as necessary, until
member being lowered is shoulder to shoulder with the victim. Regardless of the
victim’s position in the window the rescuer will be in the best position to make
the pick up.
8.5 Rescuer pulls himself/herself to the victim by using the window frame. Never use
the victim to help.
9. When a Guide Member is at roof level and visibility is good, hand signals can be used to
control a lowering operation.
66
FDNY Probationary Firefighters Manual
Chapter Five ROPE
10. The fact that a member has been lowered to a window does not commit them to rope
rescue. If conditions do not demand the removal of the victim, good judgment dictates
that the member enter the area and take the necessary action to reassure, protect, and
confine the victim until the danger has passed.
10.1 If conditions demand removal, the member shall remain connected to the rope,
which would serve as lifeline. However, before continuing a lowering operation,
it is essential to remove all slack from the rope at roof level.
11. If a rope rescue is necessary, the goal is to reach a point of safety. A descent of one story
may be all that is necessary.
12. When an unconscious victim is encountered and removing the victim requires the use of
the rope, the bowline-on-a-bight and slippery hitch must be tied on the victim.
13. Members should be aware that the actual length of our life saving rope might be less than
the nominal length of 150 feet due to natural shrinkage after several years in the field.
Over a period of time some ropes have shrunk as much as 8 to 10 feet. This fact should
be considered when planning to use the life saving rope.
FIGURE 12
AVOID THIS
67
FDNY Probationary Firefighters Manual
Chapter Five ROPE
CONTENTS
PAGE NO.
1. EQUIPMENT:
1.1 One nylon life saving rope with attached anti- chafing device in a backpack carrying
case. The pre-tied bowline-on-a-bight is not necessary for this operation. However the
life saving rope must have this knot attached, therefore it must be untied at the start of
this operation.
2. OBJECTIVE:
2.2 To lower a firefighter from a roof or upper floor, in order to enable the firefighter to
remove another person from an untenable position to one of safety.
68
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.1 Both members adjust their harness leg straps for proper fit. Both members open bottom
snap of coat for access to hook, and release hook from support strap.
Member #1 (Lowering Member) Member #2 (Member to be Lowered)
69
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 1
Member 2 Member 1
70
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 2
Figure 3
71
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 4
Figure 5
72
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 6
73
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 7A Figure 7B
74
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 8
75
FDNY Probationary Firefighters Manual
Chapter Five ROPE
76
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Note: The instructions of sections3.1 through 5.1 Holding the anti-chafing device in the
3.19 apply here. left hand, walk to roof's edge and sit
with your legs over the edge, the rope
and anti- chafing device to your left.
(Fig. 10).
Note: Under smoky or unsure conditions it
may be better to crawl to the roof's
edge.
5.2 Allow enough slack in the rope to place
the anti-chafing device flat on the roof's
edge with approximately 5" of the
device draped over the edge of the roof.
(Fig. 11).
Note: Harness hook is at the end of the anti-
chafing device and must clear the edge
of the roof.
Figure 10 Figure 11
77
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 13
`
5.6 Place feet approximately 12" apart
against the wall, toes up, and give the
command "DOWN" to be lowered.
5.7 At the command "DOWN", lower
member #2. Control the rope as it
slides through your gloved right hand.
Note: If a third member is available that
member should be at the roof's edge for
control and to relay commands.
78
FDNY Probationary Firefighters Manual
Chapter Five ROPE
6. MEMBER BEING LOWERED RESCUES A VICTIM AT LOWER LEVEL
Note: Full firefighting protective clothing must be worn during this operation.
79
FDNY Probationary Firefighters Manual
Chapter Five ROPE
____________________________________________________________________________
CONTENTS
PAGE NO.
1. EQUIPMENT
1.1 One nylon life saving rope attached anti-chaffing device in the carrying case.
The pre-tied bowline-on-a-bight is not necessary for this operation. However, the rope
shall be carried with this knot attached.
2. OBJECTIVE
2.1 To enable a firefighter to remove themselves from an untenable position above grade.
NOTE: This slide may only be used as a last resort when circumstances are such
that alternative methods of removing oneself are denied.
80
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.1 Place the carrying case on the roof near the substantial object you plan to use.
3.2 Remove the snap hook from the pocket of the case. Grasp the anti-chaffing device and
pull it through the window of the case. Be sure the bowline-on-a-bight is also pulled
through.
3.3 Secure the life saving rope by taking a turn around a substantial object and tie a clove
hitch and binder on the taut part of the rope.
NOTE: Use sufficient rope between the bowline-on-a-bight and the anti-chaffing device
and make a bend in the rope to make knot.
3.4 Grasp the anti-chaffing device with one hand and pick up the carrying case with the other
hand.
3.5 Walk to the planned point of descent, sliding the anti-chaffing device along the rope and
deploy the rope by tossing the carrying case to the street.
3.6 Locate the point to grasp the rope and the hook.
3.6.1 For a Roof with a Parapet - Place the anti-chaffing device on the parapet.
Standing to the right of the rope, place the left elbow on the outer edge of the
parapet and reach down and grasp the rope with the left hand.
3.6.2 For a Roof without a Parapet - Place the anti-chaffing device on the roof near the
edge. Standing to the right of the rope, kneel down and grasp the rope at the
roof's edge with the left hand.
3.7 Turn to the left. The slider's back will now be to the point of descent.
3.8 With the right hand, lay the solid part of the life belt hook (gate to the left) on top of the
rope at the point of the left hand. Grasp the rope and hook together in the right hand.
81
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.9.1 Pull down the gate (Figure 1A) with left hand. Take a ¼ turn to the left (Figure
1B). This will unlock the gate.
Figure 1A Figure 1B
3.9.2 With left hand, push gate over to solid side of hook (Figure 1C). As gate reaches
solid part of hook, grab hook, rope, and gate together with right hand. (Figure 1D)
Figure 1C Figure 1D
NOTE: Member is now ready to proceed to take four (4) turns around the hook.
82
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.10 Using the left hand, make four (4) turns under and over the life belt hook (Figure 2A)
3.11 Release gate to locked position. Gate will lock by itself (Figure 2B).
Figure 2A Figure 2B
83
FDNY Probationary Firefighters Manual
Chapter Five ROPE
4.1 Slide the right hand back along the rope approximately six (6") inches and grasp the rope
firmly.
4.2 Pick up and slide the anti-chaffing device up to the hook with the left hand, turn to the
right and straddle the parapet with the right leg to the outside.
4.3 Position the anti-chaffing device on the parapet allowing enough slack in the rope
between the hook and the anti-chaffing device to lie flat with approximately five (5")
inches draped over the outer edge.
4.4 Place the left arm over the anti-chaffing device and rope and grasp the inner edge of the
parapet with the left hand. (Figure 3)
NOTE: To maintain the position of the anti-chaffing device, the heel of the left hand is
placed on the device.
4.5 Check the slack on the rope to assure that the hook of the life belt will clear the outer edge
of the parapet and that the anti-chaffing device is not being lifted from its proper position.
4.6 Move the gloved right hand along the rope while stretching the right arm out a full arm's
distance. (Figure 3) Grasp the rope firmly at this point.
4.7 Slide the buttocks to the outer edge of the parapet until the left knee is at the inner edge
of the parapet. With the right arm rigid press the inside of the right fist firmly against the
wall. The rope is between the fist and the wall. (Figure 3)
4.8 Using the rigid right arm for leverage, lean out over the parapet and make sure that the
rope is in the channel of the anti-chaffing device. Also, the hook of the life belt must
clear the outer edge of the parapet.
4.9 Swing the body off the parapet into a vertical position then bring the right hand, gripping
the rope, to the right buttock and maintain a firm grip on the rope.
4.10 Place feet against the wall, toes up, approximately twelve (12") inches apart.
4.11 Bring the left hand from the parapet and clear clothing, Handi-Talkie wire, etc., from the
area of the hook.
4.12 When ready to slide, grasp the hook of the life belt to the gate, with the left hand, PALM
DOWN.
84
FDNY Probationary Firefighters Manual
Chapter Five ROPE
5. SLIDING
5.1 Sliding is controlled by allowing the rope to pass through the gloved right hand.
The hand must be in position against the right buttock at all times. This position affords
absolute control of the slide.
5.2 Look down to avoid any obstructions not noted or present when the rope was deployed.
Continue slide to area of safety.
Figure 3
This completes the section on the sliding operation from a building WITH a parapet.
85
FDNY Probationary Firefighters Manual
Chapter Five ROPE
6.1 Grasp the anti-chaffing device with the left hand. Slide the right hand along the rope to
the right buttock, grasp the rope firmly and turn to the right, facing the roof's edge.
Walk to the roof's edge paying out slack through the hook.
6.2 Sit at the roof's edge, legs over edge, with the rope and anti-chaffing device to the left.
Maintain a firm grip on the rope with the right hand at the right buttock.
6.3 Position the anti-chaffing device at the roof's edge allowing enough slack in the rope,
between the hook and the anti-chaffing device, to permit the device to lie flat with
approximately five (5") inches draped over the edge.
6.4 To maintain the position of the anti-chaffing device, place the heel of the left hand on the
device. Now, slide the body forward so that only the buttocks are on the roof. (Figure 4)
Figure 4
86
FDNY Probationary Firefighters Manual
Chapter Five ROPE
7. SLIDING
7.1 Sliding is controlled by allowing the rope to pass through the gloved right hand.
The hand must be in position against the right buttock at all times. This position affords
absolute control of the slide.
7.2 Look down to avoid any obstructions not noted or present when the rope was deployed.
Continue slide to area of safety.
This completes the section on the sliding operation from a building WITHOUT a parapet.
NOTES
1. The imaginary line from the substantial object to the planned point of descent should be
as close to perpendicular as possible to the roof's edge. This will avoid an acute angle of
the rope, which will result in the rope sliding along the roof's edge when the weight is
placed on the rope.
2. The substantial object must be carefully selected. There are many objects of questionable
integrity which should never be used; e.g., soil pipe vents, TV antenna masts, etc.
Any chimney or other object chosen should be quickly examined for soundness and any
sharp edges.
2.1 When using a vertical object, such as a chimney, allow the rope to drop to the
base, close to the roof. The object should be at optimum strength at this point.
3. After making the required turns around the hook of the life belt, do not release the right
hand from the rope for any reason. Should you slip or fall from the parapet or roof while
preparing to dismount, you will still have control and will not "free fall."
4. Members should be aware that the actual length of our life saving rope may be less than
the nominal length of 150 feet due to natural shrinkage after several years in the field.
Over a period of time some ropes have shrunk as much as 8 to 10 feet. This fact should
be considered when planning to use the life saving rope.
87
FDNY Probationary Firefighters Manual
Chapter Five ROPE
88
FDNY Probationary Firefighters Manual
Chapter Five ROPE
1. EQUIPMENT:
1.1 One nylon life saving rope with attached anti-chaffing device in a back pack carrying case.
The pre-tied bowline-on-a-bight is not necessary for this operation. However, the rope shall
be carried with this knot attached.
2. OBJECTIVE:
2.1 Used by firefighters to remove themselves from an untenable position to one of safety.
NOTE: This slide may only be used as a last resort when circumstances are such that
alternative methods of removing oneself are denied. The single slide shall not be
used to make a rescue pickup.
3. PREPARATION:
3.1 Adjust harness leg straps for proper fit. Open bottom snap of coat for access to hook.
Release hook from harness hook strap.
4. OPERATION:
4.1 Place the back pack carrying case on the roof near a substantial object you plan to use.
4.2 Remove the snap hook from the pocket of the case. Grasp the anti-chaffing device and pull
it through the window of the case.
4.3 Secure the life saving rope by taking a turn around the substantial object and tie a clove
hitch and binder on the taut part of the rope.
4.4 Grasp the anti-chaffing device with one hand and pick-up the carrying case with the other
hand.
4.5 Walk to the parapet at the planned point of descent, sliding the anti-chaffing device along
the rope, and deploy the rope by tossing the carrying case to the street.
89
FDNY Probationary Firefighters Manual
Chapter Five ROPE
4.6 Place the anti-chaffing device on the parapet. Standing to the right of the rope, place the
left elbow on the outer edge of the parapet and reach down and grasp the rope with the left
hand.
4.7 Turn to the left. The slider's back will now be to the parapet.
4.8 With the right hand, lay the solid part of the harness hook ("gate" to the left) on top of the
rope at the point of the left hand. Grasp the rope and hook together in the right hand. (Fig.
1)
4.9.1 With left hand, pull down the gate (Fig. 1A).
4.9.2 With left hand, turn gate ¼ turn to the left (Fig. 1B).
4.9.3 With left hand, push gate across toward solid side of the hook (Fig. 1C). As gate
reaches end of motion, grab hook, rope and gate in right hand (Fig. 1D).
NOTE: Member is now ready to proceed to take four (4) turns of the rope around
the hook.
Figure 1 Figure 1A
Figure 1B Figure 1C
90
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 1D
4.10 Using the left hand, make four (4) turns of the rope under and over the harness hook. (Fig.
2A)
Figure 2A Figure 2B
4.12 Slide the right hand back along the rope approximately six inches (6") and grasp the rope
firmly.
4.13 Pick up and slide the anti-chaffing device up to the harness hook with the left hand, turn to
the right and straddle the parapet with the right leg to the outside.
4.14 Position the anti-chaffing device on the parapet. The device lies flat with approximately
five inches (5") draped over the outer edge. (Fig. 3)
91
FDNY Probationary Firefighters Manual
Chapter Five ROPE
NOTE: Harness hook should be at end of anti-chaffing device and clear the parapet.
5. DISMOUNTING THE PARAPET:
5.1 Place the left arm over the anti-chaffing device and rope and grasp the inner edge of the
parapet with the left hand. (Fig. 3)
NOTE: To maintain the position of the anti-chaffing device, the heel of the left hand is
placed on the device.
5.2 Check the slack in the rope to assure that the hook of the harness belt has cleared the outer
edge of the parapet and that the anti-chaffing device is not being lifted from its proper
position.
5.3 Move the gloved right hand along the rope while stretching the right arm out a full arm's
distance. (Fig. 3). Grasp the rope firmly at this point.
5.4 Slide the buttocks to the outer edge of the parapet until the left knee is at the inner edge of
the parapet. With the right arm rigid, press the inside of the right fist firmly against the
wall. The rope is between the fist and the wall (Fig. 3).
5.5 Using the rigid right arm for leverage, lean out over the parapet and make sure the rope is in
the channel of the anti-chaffing device. The hook of the harness belt must clear the outer
edge of the parapet.
5.6 Swing the body off the parapet into a vertical position then brings the right hand, gripping
the rope, to the right buttock and maintains a firm grip on the rope.
5.7 Place feet against the wall, toes up, approximately twelve inches (12") apart.
5.8 Bring the left hand from the parapet and clear clothing, Handie-Talkie wire, etc., from the
area of the hook.
5.9 When ready to slide, grasp the hook of the life belt at the gate, with the left hand, PALM
DOWN.
92
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 3
6. SLIDING:
6.1 Sliding is controlled by allowing the rope to pass through the gloved right hand. The hand
must be in position against the right buttock at all times. This position affords absolute
control of the slide.
6.2 Look down to avoid any obstructions not noted or not present when the rope was deployed.
Continue slide to area of safety.
93
FDNY Probationary Firefighters Manual
Chapter Five ROPE
94
FDNY Probationary Firefighters Manual
Chapter Five ROPE
1. EQUIPMENT:
1.1 One nylon life saving rope with attached anti-chaffing device in a back pack carrying case.
The pre-tied bowline-on-a-bight is not necessary for this operation.
2. OBJECTIVE:
2.1 Used by firefighters to remove themselves from an untenable position to one of safety.
NOTE: This slide may only be used as a last resort when circumstances are such that
alternative methods of removing oneself are denied. The single slide shall not be
used to make a rescue pickup.
3. PREPARATION:
3.1 Adjust harness leg straps for proper fit. Open bottom snap of coat for access to hook.
Release hook from harness hook strap.
4. OPERATION:
4.1 Place the back pack carrying case on the roof near a substantial object you plan to use.
4.2 Remove the snap hook from the pocket of the case. Grasp the anti-chaffing device and pull
it through the window of the case.
4.3 Secure the life saving rope by taking a turn around the substantial object and tie a clove
hitch and a binder on the taut part of the rope.
4.4 Grasp the anti-chaffing device with one hand and pick up the carrying case with the other
hand.
4.5 Walk to the roof's edge at the planned point of descent, sliding the anti-chaffing device
along the rope and deploy the rope by tossing the carrying case to the street.
(See Note #4, page 16)
95
FDNY Probationary Firefighters Manual
Chapter Five ROPE
4.6 Place the anti-chaffing device on the roof near the edge. Standing to the right of the rope,
kneel down and grasp the rope at the roof's edge with the left hand.
4.7 Maintaining hold on rope, stand and step back a safe distance. Turn to the left. Slider's
back will now be to the roof's edge.
4.8 With the right hand lay the solid part of the harness belt hook ("gate" to the left) on top of
the rope at the point of the left hand. Grasp the rope and hook together in the right hand
(Fig. 1).
4.9.1 With left hand, pull down the gate (Fig. 1A).
4.9.2 With left hand, turn gate ¼ turn to the left (Fig. 1B).
4.9.3 With left hand, push gate across toward solid side of the hook (Fig. 1C). As gate
reaches end of motion, grab hook, rope and gate in right hand (Fig. 1D).
NOTE: Member is now ready to proceed to take four (4) turns of the rope around
the hook.
Figure 1 Figure 1A
Figure 1B Figure 1C
96
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 1D
4.10 Using the left hand, make four (4) turns of the rope under and over the harness hook. (Fig.
2A).
4.12 Grasp the anti-chaffing device with the left hand. Slide anti-chaffing device up to personal
harness hook, slide the right hand along the rope to the right buttock, grasp the rope firmly
and turn to the right, facing the roof's edge. Walk to the roof's edge paying out slack
through the hook. (See Note #4, Page 16)
4.13 Sit at the roof's edge, legs over edge, with the rope and anti-chaffing device to the left.
Maintain a firm grip on the rope with the right hand at the right buttock. (Fig. 3)
4.14 Position the anti-chaffing device at the roof's edge allowing the device to lie flat with
approximately five inches (5") draped over the edge. (Fig. 3)
NOTE: The personal harness hook should be at the end of the anti-chaffing device, and
clear the roof's edge. (Fig. 3)
97
FDNY Probationary Firefighters Manual
Chapter Five ROPE
5.1 To maintain the position of the anti-chaffing device, place the heel of the left hand on the
device. Now, slide the body forward so that only the buttocks are on the roof. (Fig. 3).
Figure 3
6. SLIDING:
6.1 Sliding is controlled by allowing the rope to pass through the gloved right hand. The hand
must be in position against the right buttock at all times. This position affords absolute
control of the slide.
6.2 Look down to avoid any obstruction not noted or not present when the rope was deployed.
Continue slide to area of safety.
98
FDNY Probationary Firefighters Manual
Chapter Five ROPE
NOTES:
1. The imaginary line from the substantial object to the planned point of descent should be as
close to perpendicular as possible to the roof's edge. This will avoid an acute angle of the
rope, which will result in the rope sliding along the roof's edge when the weight is placed on
the rope.
2. The substantial object must be carefully selected. There are many objects of questionable
integrity which should never be used; e.g., soil pipe vents, TV antenna masts, etc. Any
chimney or other object chosen should be quickly examined for soundness and any sharp
edges.
2.1 When using a vertical object, such as a chimney, allow the rope to drop to the base,
close to the roof. The object should be at optimum strength at this point.
3. After making the required turns around the hook of the life belt, do not release the right
hand from the rope for any reason. Should you slip or fall from the parapet or roof while
preparing to dismount, you will still have control and will not "free fall".
5. Members should be aware that the actual length of our life saving rope may be less than the
nominal length of 150 feet due to natural shrinkage after several years in the field. Over a
period of time some ropes have shrunk as much as 8 to 10 feet. This fact should be
considered when planning to use the life saving rope.
99
FDNY Probationary Firefighters Manual
Chapter Five ROPE
100
FDNY Probationary Firefighters Manual
Chapter Five ROPE
1.1 This evolution will only be implemented under the direction of a Command Chief. Activation
will be transmitted via signal 65-2 by voice alarm, Department radio, ATSP and MDT. This
evolution will be implemented on a citywide basis when a large number of personal harnesses
and/or personal safety systems have been placed out-of-service and immediate replacement is
not available. The intention of this procedure is to provide a measure of safety to members
operating without personal harnesses and/or personal safety systems. It will remain in effect
until further orders. When the equipment has been replaced and all on-duty members have
been properly equipped, the Command Chief will rescind the implementation of this
evolution.
2. PROCEDURES
2.1 Members assigned the Roof position in the first and second ladder companies at structure
fires involving non-fireproof buildings that are 3 stories in height or greater shall bring their
Life Saving Rope to the roof of the building. Additionally, members assigned the Roof
position in the first and second Ladder companies at fireproof residential-type structures
including apartment houses, nursing homes, senior citizen housing, dormitories, etc., shall
bring the Life Saving Rope to their position on the floor above.
2.2 The 1st Roof firefighter shall carry the Life Saving Rope to their position and then perform
assigned duties on arrival at the roof level (or floor above in fireproof residential buildings).
2.3 The 2nd Roof firefighter shall carry the Life Saving Rope to their position. Immediately
after reaching their position, identify possible substantial objects for use in tying off the Life
Saving Rope and position the Life Saving Rope at that location for possible use.
This member will also position the Life Saving Rope of the first ladder company at a
substantial object, using a different one if available. This action will readily identify the
location of a designated substantial object for Life Saving Rope deployment.
After completing this initial duty, the 2nd Roof firefighter shall then perform assigned duties
at the roof level (or floor above in fireproof residential buildings), remaining alert to any
condition that might require immediate use.
NOTE: The Life Saving Rope shall not be removed from the carrying case except for
actual rescue and removal operations.
101
FDNY Probationary Firefighters Manual
Chapter Five ROPE
2.4 These two Roof firefighters shall maintain their position at the roof level (or floor above in
fireproof residential buildings) until the Incident Commander declares the operation
“Probably Will Hold,” or the Incident Commander informs the members to either evacuate
the roof or that their services on the roof are no longer required. When leaving the roof
position, Roof firefighters shall take the Life Saving Ropes with them. The Incident
Commander shall also announce on the handie-talkie that this roof level team is no longer in
place when they are removed from the roof (or floor above in fireproof residential buildings).
The Incident Commander must ensure that the duties (searches) previously performed by the
Roof firefighters are assigned to other members or units.
2.5 Both Roof firefighters shall monitor the handie-talkie for deteriorating conditions that might
require deployment of the Life Saving Rope, such as an interrupted or delayed application
of water on the fire. This may require one or both members to move to a location remote
from operating saws or other ambient noise.
2.6 The preferred method for removal of distressed members wearing a personal harness is for
them to remove themselves from danger via a single slide utilizing a Life Saving Rope that
has been deployed from above.
2.7 The preferred method for removal of distressed members not wearing a personal harness
from danger is for the two roof members to perform Evolution 25, 26 or 27 to remove the
distressed member from danger.
3. COMMUNICATIONS
3.1 Members operating inside buildings should be alert to changing conditions to alert the roof
level team of any possible need for deployment of the Life Saving Rope (remember the
inherent time delay for Life Saving Rope deployment). Be as specific as possible when
indicating the location where the rope is needed.
5. SUBSTANTIAL OBJECT
5.1 The substantial object must be carefully selected. There are many objects of questionable
integrity that should never be used; e.g., soil pipe vents, TV antenna masts, etc. Any chimney or
other object chosen should be quickly examined for soundness and any sharp edges. When using
102
FDNY Probationary Firefighters Manual
Chapter Five ROPE
a vertical object, such as a chimney or dumbwaiter bulkhead, allow the rope to drop to the base,
close to the roof. The object should be at optimum strength at this point.
103
FDNY Probationary Firefighters Manual
Chapter Five ROPE
2. OBJECTIVE:
2.1. To enable a firefighter to remove themselves from an untenable position above grade.
D. While awaiting the LSR from above, fully clear the window of all obstructions
The substantial object must be carefully selected. There are many objects of questionable
integrity that should never be used: e.g., soil pipe vents, TV antenna masts, etc. Any
chimney or other object chosen should be quickly examined for soundness and any sharp
edges. When using a vertical object, such as a chimney or a dumbwaiter bulkhead, allow the
rope to drop to the base, close to the roof. The object should be at optimum strength at this
point
104
FDNY Probationary Firefighters Manual
Chapter Five ROPE
4. ATTACH LIFE SAVING ROPE TO HARNESS DEPLOYED FROM
ABOVE WHILE CROUCHING OR KNEELING AT WINDOW
4.2 Reach out with the right hand and grasp the rope at a
point below the edge of the windowsill.
Figure 1
4.3 With your left hand holding the "gate" to the left, place
the solid part of the hook on top of the rope in the right
hand. (Figure 1)
4.4 Open the gate of the hook and hold it open with the
right hand. (Figure 2)
4.5 Using the left hand, grasp the rope coming from above Figure 2
and pull approximately 12” of slack forward through
the right hand as it is holding the rope and hook. This
is to ensure there is adequate slack to take the turns
onto the hook.
4.6 Make four (4) turns of the rope under and over the
harness hook. (Figure 3)
NOTE: The rope coming from above must be positioned at the top of the hook, and the rope going
back out the window to below must be positioned at the bottom of the hook. The rope is held
against the hook in the right hand prior to taking the 4 turns. The right hand must never lose
contact with the rope from this point on.
105
FDNY Probationary Firefighters Manual
Chapter Five ROPE
5.1 Facing the window put the right leg outside the
window and straddle the window sill.
5.2 Make sure harness hook clears the outer edge of the
windowsill, and ensure that the rope from above is
positioned on the left side of your head as you exit the
window. The rope should be between you and the
building.
5.5 Using the right arm for leverage, lean further out over
windowsill.
5.7 Feet against the wall, toes up, 12" apart. Your left
hand should be on the gate of the hook (palm down),
and the right hand should be positioned against the
right buttock for a controlled descent.
106
FDNY Probationary Firefighters Manual
Chapter Five ROPE
6.1 Lean out head first, staying low in the window, close to the sill, with the right arm rigidly
extended holding the rope.
6.2 Make sure the rope is on the left side of your head as youroll out the window. The rope
should be between you and the building.
6.3 Press the inside of the right fist firmly against the wall so that rope is between the fist and
the wall.
6.4 Roll out head first, maintaining the right arm’s rigid position.
6.5 The left hand is on the inner edge of the windowsill while exiting to provide balance and
stability.
6.6 Once you’ve rolled out of the window, your left hand should be on the gate of the hook
(palm down), and the right hand should be positioned against the right buttock for a
controlled descent.
NOTE: There will be a drop while exiting the window due to the accumulated slack in
the rope from hooking up below the windowsill.
107
FDNY Probationary Firefighters Manual
Chapter Five ROPE
PERSONAL SAFETY SYSTEM (PSS)
1. DESCRIPTION
1.1 F.D.N.Y. Designation Personal Safety System (PSS)
1.2 Components Anchor Hook, 50' Kernmantle Rope with Sewn Eye, EXO
Descender with triple action carabiner and Storage Bag.
1.3 Hook Material Dropped Forged Alloy Steel. (Figure 1)
1.4 EXO Descender Equipped with an operating handle used to control descent.
Self locking cam prevents member from an uncontrolled
descent when operating handle is released. (Figure 2)
1.5 Hook: Load Capacity 5000 pounds at tip, 10,000 pounds at saddle.
1.6 Rope: Material Technora Sheath, Technora Core
1.7 Rope: Diameter 7.5 mm (19/64”)
1.8 Rope: Length 50 Feet
1.9 Rope Tensile Strength Meets NFPA standard of 3034 pounds
1.10 System: Work Load Meets NFPA Std. - 10:1 safety factor based on 300 pounds
1.11 System: Markings Tracking number assigned by R & D.
1.12 System: Characteristics Technora Rope with the Anchor Hook attached at the Sewn
Eye. The rope passes through the EXO, over the bent flange
and through the “U” shaped rope guide. There is a Figure “8”
stopper knot tied at the end of the rope.
ANCHOR HOOK WITH SEWN EYE
Saddle
Sewn
Tip
Figure 1
108
FDNY Probationary Firefighters Manual
Chapter Five ROPE
PETZL EXO WITH LOCKING CARABINER
Carabiner
Bent Flange
Figure 2
2. INTENDED USE
2.1 Used only by members to remove THEMSELVES from an untenable position above grade
to a place of safety. The PSS is a ONE TIME use system and is only to be used as a last
resort.
2.2 After use, the PSS will be placed out of service.
PSS STORAGE BAG WITH EXO AND ANCHOR HOOK WITH SEWN EYE
Figure 3
109
FDNY Probationary Firefighters Manual
Chapter Five ROPE
STORAGE BAG WITH TEAR AWAY FLAP
DESCRIPTION
In addition to the Tear Away Flap (TAF), PSS systems equipped with the TAF
have the following new features (See Figures 4 and 5):
• The exterior of the flap is provided with orange and silver reflective 3M material.
• An Alignment Positioning Snap (APS) is provided to secure the flap to the bag.
Figure 4
110
FDNY Probationary Firefighters Manual
Chapter Five ROPE
• The top of the storage bag has a ¾” strip of Velcro and snap to attach the TAF.
• The TAF is provided with a 1” strip of Velcro and snap to secure it to the storage bag.
• The bottom of the TAF is provided with a 1” strip of Arashield to assist in grabbing
and removing the flap during deployment.
• The interior of the flap is covered with yellow Kevlar.
1” Arashield strip
• Align the ¾ inch Velcro strip at the top of the storage pouch with the 1 inch Velcro
strip at the top of the TAF (See Figure 6).
• Secure the two components together with the alignment positioning snap.
• Close the TAF over the front of the storage bag and secure the bottom with the two
Velcro tabs. To ensure a proper attachment, the TAF should be square to the edges of
the storage bag when it is closed.
Note: If the TAF cannot be securely attached to the storage bag follow the existing PSS
replacement procedures.
111
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 6
IMPLEMENTATION
The PSS with the TAF is designed to replace the original PSS bag.
• Procedures for deploying the PSS with the TAF do not change from those found
in current FDNY documents, with one exception:
o When deploying, grab the flap, rip it straight up, and pull it completely off
to expose the hook.
• Procedures for packing and inspecting the PSS with the TAF do not change
from those found in current FDNY documents, with the following addition:
o During daily and semi- annual inspections, members should ensure that
the Velcro and the APS have not been damaged and are functioning properly.
• All other procedures concerning the use, inspection, replacement, etc… of the
PSS system remain unchanged.
112
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Arashield
Right leg loop
straps
“rear”
Figure 7
113
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 7A Figure 7B
Figure 8
114
FDNY Probationary Firefighters Manual
Chapter Five ROPE
4.6 Ensure the gate has closed and locked securely by applying lateral pressure on the gate
towards the spine of the carabiner.
4.7 When the harness and the PSS are properly donned, the gate should be facing down and
away from the body. (Figure 9)
Figure 9
5. INSPECTION
5.1 The PSS shall be inspected at the following times:
5.1.1 At the start of each tour.
5.1.2 Semi-annually.
5.2 The PSS shall be properly connected to the right side of the personal harness at all times,
as illustrated in Figure 10.
Figure 10
5.3 At the start of each tour, the PSS shall be inspected for the following:
5.3.1 Bag properly connected to the harness.
5.3.2 Carabiner properly connected to the PSS “D” ring.
5.3.3 If the bag (or any component of PSS) shows signs of heat exposure (discoloration,
degradation, melting, charring, etc.) the entire system (PSS bag, rope, EXO, and
harness) should be placed out of service as specified in section 6. (Figure 11)
5.3.4 Bag properly closed and components secured inside.
115
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 11
NOTE: The sewn eye is only to be used with the issued hook. No other hardware
or device should be placed into the sewn eye.
116
FDNY Probationary Firefighters Manual
Chapter Five ROPE
117
FDNY Probationary Firefighters Manual
Chapter Five ROPE
118
FDNY Probationary Firefighters Manual
Chapter Five ROPE
PERSONAL SAFETY SYSTEM (PSS)
REPACKING PROCEDURE
Carabiner
8”
EXO
“U” Shaped
Rope Guide
Anchor Hook
Figure 1
• The PSS is laid out on a clean flat work area. (Figure 1)
• The bag should be placed on its back with bag opening facing away from member.
• Place the figure 8 stopper knot on right edge of flap closure just above rope storage
section.(Figure 2)
• Weave rope to opposite edge of flap and return to the right edge, folding the rope next
to the previous row. Continue this process making five flat rows. (Figure 2)
• Slide five folds into rope storage section of bag. Repeat this process until
approximately 18 inches of rope with hook and EXO remain.
• Be sure to maintain 8 inches of rope between eye of hook and EXO. (Figure 1)
Figure 2
119
FDNY Probationary Firefighters Manual
Chapter Five ROPE
• Secure rope in lower compartment by closing the rope separation flap and fastening
Velcro closure.
• The portion of rope coming from the rope storage area to the EXO should pass
through the small cutout in the rope separation flap and rest on the side of EXO
closest to the body if the bag were mounted on waist band of the personal harness.
• The rope shall have an eight inch loop between the “U” shaped rope guide and the
EXO. (Figure 3)
• Place EXO flat side down on top of the rope separation flap with the handle of the
EXO facing away from the body if the bag were mounted on the waist band of the
personal harness.
120
FDNY Probationary Firefighters Manual
Chapter Five ROPE
• The end of rope connected to the hook/anchor then passes over the handle of the
EXO.
• Fold the 8 inches of remaining rope behind back edge of Anchor/Hook and place
hook and rope into the hook pocket. Place the tip into its keeper. (Figure 4)
• The carabiner will extend out of the cutout on the leading edge of the storage bag
with the (gold colored) triple action lock gate facing away from the body if the bag
were mounted on the waist band of the personal harness.
• Any excess rope between storage compartment and EXO should be packed into the
lower rope compartment via the 2” cutout in the rope separation flap at this time.
8” Loop of
Rope
Rope Folded
Behind Gold Colored Triple
Anchor/Hook Action Lock Gate
Tip Stored in
Tip-Keeper
Figure 4
121
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Top
Side
Securing Tab
Bottom
Side
Securing Tab
Figure 5
122
FDNY Probationary Firefighters Manual
Chapter Five ROPE
1. EQUIPMENT
2. OBJECTIVE
This system should ONLY be used after all other means of self-rescue have been
exhausted.
When a member has decided to deploy the Personal Safety System, a Mayday
transmission for a trapped member must be transmitted.
In addition to all other required information relayed for a trapped member, include that
you are in the process of deploying the Personal Safety System.
When a point of safety is reached after using your Personal Safety System, the Incident
Commander must be notified.
Select a suitable substantial object, e.g. steam riser, radiator, two wall studs, door frame,
etc.
123
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 1
Figure 2
124
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Note: Introduce enough rope between the hook and EXO to pass the rope around the
substantial object and tie the anchor knot. Introducing more rope than what is
necessary for the EXO to clear the window sill may cause the system to be shock
loaded when exiting the window.
3.2 ANCHORING
Pass the hook around the substantial object. Allow enough slack to tie the anchor knot.
With palms facing up, place the anchor hook on top of the rope. (Figure 5)
Figure 5
125
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 6
Figure 7
Figure 8
126
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 9
Examples of alternate methods of the anchor hook used on a remote anchor with saddle and tip.
(Figures 10 through 13)
Figure 10 Figure 11
Figure 12 Figure 13
Note: When using the anchor hook as pictured in figure 12 and 13, place the anchor hook
as low as possible keeping tension. This will help prevent the anchor hook from
coming off of the anchor point.
127
FDNY Probationary Firefighters Manual
Chapter Five ROPE
3.3 LOADING THE SYSTEM
Move backwards from anchor point until rope and EXO are under tension.
Lean back sharply using body weight to pull against anchor to:
Test the substantial object,
Insure full harness handle deployment with PSS “D” ring and EXO at top of harness
handle,
Expose the EXO allowing for easy access by member.
Turn slightly to the right. Right shoulder points to the exit window.
Continue pulling rope from the storage bag, maintaining a small amount of slack between
right hand and the EXO to eliminate friction while moving towards window.
Note: Leading with your right hand will be the most effective way to exit room.
128
FDNY Probationary Firefighters Manual
Chapter Five ROPE
With EXO in left hand, maintain tension on rope between EXO and substantial object.
(Figure 15)
Exit
Anchor
Figure 15
Upon reaching the window, the EXO must be brought to a point beyond the outermost
edge of the windowsill.
Extend the device in the left hand beyond the sill, maintaining slack with the right hand
to allow the EXO to payout with less resistance. (Figure 16)
Note: It is absolutely necessary that the EXO be brought beyond the sill.
Figure 16
129
FDNY Probationary Firefighters Manual
Chapter Five ROPE
6. EXITING WINDOW
Figure 17
Figure 18
130
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 19
Figure 20
131
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Note: Pulling the operating handle too far will cause over speeding and
anuncontrolled descent. If member begins to over speed, release lever
with left hand and maintain firm grasp of rope with right hand to stop
your descent. It is essential that the right hand always stays in contact
with the rope to help prevent a rapid descent.
132
FDNY Probationary Firefighters Manual
Chapter Five ROPE
8. ANCHORING AT WINDOW
Figure 21
Figure 22
Figure 23
133
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 24
Figure 25
134
FDNY Probationary Firefighters Manual
Chapter Five ROPE
Figure 27
Speed of descent will be controlled by the operating handle and the proper positioning of
the right hand.
Note: Pulling the operating handle too far will cause over speeding and an
uncontrolled descent. If member begins to over speed, release lever with left
hand and maintain firm grasp of rope with right hand to stop your descent.
It is essential that the right hand always stays in contact with the rope to help
prevent a rapid descent.
CONTENTS: • Description of the Scott 4.5 Mask and explanations of its use and
care
• Description of the PASS alarm and explanations of the use and
care of the various versions of same.
• Addendums:
1 Toxins Reference
2 (APR) Adapter
6
Table of Contents
1. Introduction ...................................................................................................... 1
2. Limitations ........................................................................................................ 2
3. Description........................................................................................................ 3
4. Inspection.......................................................................................................... 24
7. Communication ................................................................................................ 42
12. Addendums 51
THIS PAGE WAS INTENTIONALLY LEFT BLANK
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
O
P
A
N
B
M
L
K J
C
D
E
F I
G
H
1. INTRODUCTION
1.1 FDNY currently uses the NFPA 2007 Edition, Scott 4.5 Positive Pressure, Self Contained
Breathing Apparatus (SCBA). This SCBA meets the approval of the National Fire Protection
Association (NFPA), Occupational Safety and Health Administration (OSHA) and National
Institute for Occupational Safety and Health (NIOSH). Use of the SCBA is regulated by the
U.S. Department of Labor Safety and Health Act and together with full firefighting clothing,
makes it a part of the framework of firefighters' personal protective equipment.
1.2 The NFPA 2007 SCBA Standard mandates that all SCBAs must have a visual and audible low
air alert device. All of the FDNY’s SCBAs have a Heads-Up Display (HUD), a Universal Air
Connection (UAC), and a Chemical, Biological, Radiation, Nuclear (CBRN) approval. The
regulator diaphragm is made of butyl rubber similar to a "Level A" entry suit. The CBRN
approval means that the SCBA has met the NIOSH and NFPA criteria for exposure to Liquid
Mustard and Sarin Agents. An approved SCBA CBRN regulator can be identified by its orange
background label. An approved back frame assembly can be identified by a CDC NIOSH
sticker.
1.3 Members are not fully protected from CBRN agents unless wearing the NFPA 2007
compliant SCBA in conjunction with Proper Protective Clothing (e.g., "Level A" entry
suit) and proper Haz-Mat training.
1
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
2. LIMITATIONS
2.1 PROTECTION
2.1.1 The SCBA is designed to protect against the Immediately Dangerous to Life and
Health (IDLH) atmosphere.
2.1.2 The facepiece further protects against entry of contaminants through the eyes.
2.1.3 Because the facepiece does not cover the ears, airborne contaminants can enter the
respiratory tract through a punctured or ruptured eardrum.
2.1.4 The SCBA does not protect against the absorption of toxic and hazardous substances,
or radiation through parts NOT covered by the facepiece.
2.1.5 The SCBA does not protect against heat exhaustion or exposure to flame or heat.
2.1.6 The actual working and exit time achieved from an SCBA will vary considerably
depending upon physical conditioning, type of work load, physical characteristics,
training, and a number of other factors. It is the individuals’ responsibility to know
their work and exit times of the SCBA.
2.1.7 If a member runs out of air, that member should remove the regulator from the
facepiece. The donned facepiece will provide some protection to the skin on the face.
Notify Officer and immediately leave the contaminated area. This member MUST be
accompanied to a safe area by another member using an SCBA.
2.2.1 Confined spaces include, but are not limited to, basements, sub-basements and
cellars, manholes, pits, tunnels, wells, windowless buildings, storage containers, and
other spaces that may be oxygen deficient or contain dangerous levels of airborne
contaminants.
2.2.2 All confined spaces are to be considered dangerous until proven otherwise.
2.2.3 All members entering a confined space shall operate with SCBA donned until the
space is deemed safe.
2.2.4 Members operating in a confined space must work in teams of two or more and
maintain contact with each other, in case assistance is needed.
2.2.5 When a member of a rescue team has to leave an area to service an SCBA, another
member must accompany them.
2
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
2.3.2 When the use of corrective eye lenses is required during SCBA use, the corrective
lenses must not interfere with a good seal between face and facepiece.
For example, glasses with temple bars or straps that pass between the face and the
seal of the facepiece must not be used. Each size facepiece may be equipped with a
lens frame kit. Training Bulletin; SCBA; Addendum 7, details how to procure a Scott
AV 2000 lens kit.
2.4.3 If the SCBA becomes submerged, it MUST be placed out of service and returned with
a completed service tag (RT-2) stating the problem, to the Mask Service Unit.
3. DESCRIPTION
3.1.1 The backframe is the rigid base and back plate to which the Harness Straps and
Pressure Reducer Assembly are attached. Its main purpose is to hold the air
cylinder. This is done by means of an adjustable cylinder band and a locking tab.
3.1.2 The harness assembly consists of two adjustable shoulder straps and adjustable waist
straps made of Kevlar with a quick release buckle. The shoulder straps have pockets
through which the low pressure hose and the remote gauge line pass.
The waist belt rests on the hips of the wearer and distributes most of the weight of
the SCBA to that area.
3.2.1 Cylinders are constructed of an aluminum shell and wrapped with a fiber composite
including neck and bottom, which strengthen and protect the shell.
3
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
Figure 1 Figure 2
Figure 3 Figure 4
3.2.3 The Date of Manufacture is listed on the SCOTT label by month and year.
The service life of an air cylinder is 15 years. If a manufacture date is greater than
15 years, the cylinder must be removed from service, bled down, tagged, and
returned to MSU. Figure 1
3.2.4 Hydrostatic testing is done every 5 years. If the test date shows greater than
5 years, the cylinder must be removed from service, bled down, tagged and returned
to MSU. The hydrostatic test date will also be found on the top of the cylinder. For
example, the number 102 will indicate that this cylinder was tested in January of
2002, and will need to be retested by January of 2007. Figure 2
Note: 10 minute escape cylinders used by SOC for confined space, need to be
hydrostatic tested every 3 years.
3.2.5 Cylinders that have had a Hydrostatic retest will have a round Hydro Recertified
label glued to it, with month and year of retest. Figure 3
4
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
3.2.6 The SCBA assembly has the capability of accepting 30, 45 or 60 minute cylinders.
Since all 4.5 cylinders are pressurized to 4500psi, the difference between them is
their varying cylinder sizes. The cylinder slide buckle is the only adjustment that
must be made when using a different duration cylinder. Each cylinder has a similar
hanger to lock onto the backframe. Figure 4
The service duration times for 30, 45 and 60 minute cylinders are determined by a
NIOSH Breathing Machine Test simulating an average adult moderate work rate of
40 liters per minute.
3.2.8 These are rated durations and the actual time achieved from the cylinder will vary
considerably. The End of Service Time Indicator (EOSTI) alarms (vibralert and
HUD) actuate when approximately 25% of full cylinder pressure remains in the
cylinder and valve assembly. The alarms will continue to operate until the cylinder
is nearly depleted. It is the individuals’ responsibility to know their working and exit
time of the SCBA.
The working and exit time of the SCBA will depend on factors such as:
♦ The degree of physical activity of the user
♦ The physical conditioning of the user
♦ The degree to which the user’s breathing is affected by excitement, fear or
other emotional factors
♦ The degree of training or experience which the user has with this or similar
equipment
♦ Whether or not the cylinder is fully charged at the start of the work period
♦ The atmospheric pressure; for example, if used in a pressurized tunnel or
caisson at 2 atmospheres, the duration will be one-half as long as when used
at 1 atmosphere; and at 3 atmospheres, will be one-third as long
♦ Loose or improperly fitted facepiece
♦ The condition of the SCBA
5
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
3.2.10 Spare cylinders should be placed in either storage boxes or apparatus holders.
Extra cylinders should be placed on their sides, with the valve stem and handle
protected from damage
3.2.11 Inspect all spare cylinders (depots, High-Rise Units, company and reserve apparatus)
weekly on Mondays for FULL pressure (4500psi). Stored cylinders found below
FULL should be tagged and returned to the Mask Service Unit for further inspection.
3.2.12 Compressed air is dangerous, service cylinder so that they do not fall or roll away.
Do not open the cylinder valve when the cylinder is not in the backframe or secured
in some other manner. When opening a cylinder valve of a secured cylinder, be sure
not to direct airflow at yourself or any other individual.
3.2.13 Avoid fully depleting cylinders and leaving valve open. Doing so will allow
moisture and contaminates to build up inside the cylinder.
3.2.14 Designated training cylinders are identified with a blue top and/or a polymer
protective sleeve. These cylinders are not to be used for firefighting purpose.
Note It is prohibited to perform any of the dragging methods, listed in the Unconscious
Firefighter Removal procedures, on members wearing a company or spare SCBA.
Dragging a member with an SCBA, for training purposes, has caused injury to
members and unnecessary damage to air cylinders and SCBA’s. Each Battalion is
issued a fully outfitted Unconscious Firefighter mannequin to train with.
6
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
3.3 CYLINDER EXCHANGE
A. Shut down the cylinder valve FULLY and purge all residual air from the
SCBA.
B. Uncouple the high pressure hand coupling from the cylinder.
C. Unsnap and lift cylinder toggle strap.
D. While pressing down on the cylinder locking tab, grasp the cylinder at the
rubber bumper and slide the cylinder hanger away from and free of the bottom
hook.
E. Slide cylinder over locking tab until top of cylinder clears band.
F. Slide in a FULL cylinder in opposite direction of removal.
G. As cylinder hanger clears bottom hook of wire frame, let hook slide back and
lock into hanger slot.
H. Attach high pressure hand coupling to cylinder and turn clockwise. Coupling
is to be made hand tight, never use a wrench to tighten coupling.
I. Push down on cylinder band toggle lever to firmly secure cylinder to
backframe. Toggle lever should not be hard to push down, but have some
tension. If necessary, readjust the slide buckle on the retention strap.
J. Open cylinder valve FULLY. Listen for any leaks in the entire SCBA system.
K. Shut down the cylinder valve and purge all residual air from the SCBA system,
prior to placement in apparatus mounting bracket.
7
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
A
A High Pressure Hose
B
B Relief Valve
C UAC Connection E
D Nylon O-Ring
E High Pressure Hand Coupling C
Figure 6
3.4.1 The high pressure hose and high pressure hand coupling conveys breathing air from
the cylinder to the pressure reducer assembly. Air pressure within this hose can be
as much as 4500psi.
3.4.2 NEVER use a wrench to tighten the high pressure hand coupling
Figure 7
Figure 8
8
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
3.5.1 SCOTT 4.5 SCBAs are fitted with a UAC System which permits emergency
replenishment of an approved SCBA breathing air supply cylinder on a user’s
SCBA from an approved air supply source while in use. This is not a Quick Charge
attachment and must not be used for routine recharging of the air cylinder, buddy
breathing, transferring air from another SCBA, or any unapproved use. The UAC is
for emergency use only when the SCBA user is incapacitated within the hazardous
atmosphere. The UAC manifold is equipped with a relief valve which will open if
the supply pressure of the emergency air supply exceeds the maximum pressure
rating of the complete SCBA. However, the supply pressure from the High Pressure
Coupling (A), of the emergency air supply to be connected to the UAC (B), must not
exceed 4500psi. Figure 8
3.5.2 The UAC Connection must have its protective dust cover in place. A missing cover
allows damage to the UAC or debris and contaminates to enter the connection,
allowing for a possible malfunction when used with the Fast Pak. An SCBA with a
missing UAC dust cover places the SCBA out of service.
It must be tagged with an RT-2 and forwarded to MSU.
3.6.2 A malfunction of the PRA's primary system will automatically direct breathing air
into a secondary system. When this occurs, the operating pressure will only be
reduced to 150 psi and cause the vibralert alarm to activate. The member will only
know that the vibralert alarm has activated and MUST NOTIFY THEIR OFFICER
AND IMMEDIATELY LEAVE THE CONTAMINATED AREA.
Note: If a member of a company, using an SCBA, leaves a contaminated area, this member
must be accompanied to a safe area by another member using a SCBA.
3.6.3 Failure of both the primary and secondary systems in the open position will activate a
Relief Valve in the PRA, which will rapidly discharge all pressure in excess of 185psi
into the atmosphere. When this occurs, the cylinder valve should be partially closed,
allowing only a minimal amount of air to release, permitting the member to both
breathe and conserve air. MEMBER MUST NOTIFY THEIR OFFICER AND
IMMEDIATELY LEAVE THE CONTAMINATED AREA.
Note: If a member of a company, using an SCBA, leaves a contaminated area, this member
must be accompanied to a safe area by another member using a SCBA.
9
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
3.7.2 The Low pressure hose incorporates a Quick Disconnect with HUD connection.
This connection allows for one of the options with the Fast Pak.
3.7.3 To disconnect – While pushing the plug “D” into the socket, pull the locking sleeve
“E” back toward the guard. The plug “D” will separate. Figure 10
3.7.4 To reconnect - align the HUD plug with the mating connector and push plug “D”
into socket until the locking sleeve “E” pops forward. Test for proper engagement
by tugging on the coupling. Figure 11
Figure 10 Figure 11
10
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
A
H G
F
C
D E
B
Figure 12
A Manual Shut-Off Switch E Snap Lock
B Regulator Cover F Regulator Gasket
C Purge Valve G Spray Bar
D Vibralert Alarm H Heads-Up Display
c. If the manual shut off switch fails to release for any reason.
Note - In all SCBA emergencies, the member must notify their officer and
immediately leave the contaminated area. This member MUST be
accompanied to a safe area by another member using a SCBA
12
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
A. When SCBA’s cylinder valve is turned on, the HUD will initialize and
illuminate all five lights for twenty (20) seconds. Operation of all five lights
must be verified every time SCBA use has begun and with every regular
operation inspection.
Figure 13
13
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
B. After initialization, the rectangular indicator lights will show the level of the air
supply in the cylinder as follows:
1. FULL cylinder - indicated by the two green lights glowing near the center of
the display.
2. THREE-QUARTERS cylinder - indicated by a single green light glowing.
3. ONE-HALF cylinder - indicated by the yellow light flashing slowly at once
a second.
4. ONE-QUARTER cylinder EOSTI - indicated by the red light at the far left
flashing rapidly at ten times a second. WHEN THIS WARNING LIGHT
IS FLASHING RAPIDLY, THE MEMBER MUST NOTIFY THEIR
OFFICER AND LEAVE THE CONTAMINATED AREA
IMMEDIATELY. This member MUST be accompanied to a safe area by
another member using an SCBA.
5. If a member runs out of air, that member should remove the regulator from
the facepiece. The donned facepiece will provide some protection to the skin
on the face.
Note: The HUD and vibralert work independently and may not activate at precisely
the same time.
It is the individuals’ responsibility to know their work and exit times of the
SCBA.
C. When the batteries require changing, the round low battery indicator at the far
right of the display will light for twenty (20) seconds and then begin to flash
slowly at once a second. When the low battery indicator is actuated, the batteries
still have sufficient life to operate the HUD longer than the longest duration
cylinder installed in the SCBA. However, the batteries must be changed
immediately upon termination of use of the SCBA, or before re-entry into the
hazardous atmosphere.
14
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
3.9 FACEPIECE (Figure 14)
3.9.1 The Scott AV 2000 is manufactured in three (3) sizes that are color coded. The size
and colors are :
a. Small size – Green color face seal
b. Comfort Seal - Black color face seal
c. Extra Large size - Red color face seal
d. All members are fit tested as part of the respiratory protection policy and must wear
the correct face piece size, that they were fit tested for. Members issued a personal
face piece, should wear that face piece. When a member’s facepiece is placed out-of-
service, it must be returned to MSU with an RT-2 attached. Six (6) comfort seal face
pieces are provided for all SCBA riding positions. They are etched with the company
designation and affiliated SCBA number.
Note: Divisions have been issued small and extra large facepieces to be used as
spares for units under their command. Units requiring a spare small or extra large
facepiece shall contact their Division.
3.9.2 The outer edge of the lens is fitted with a frame. The rubber seal is molded to form a
chin cup at the lower part of the facepiece, where the member's chin rests during use.
The remainder of the rubber seal continues around the upper part of the facepiece
and has the ability to conform to various facial contours. Failure to get a positive
seal will allow air to escape from around the facepiece.
3.9.3 A Kevlar head net and strap assembly is fastened to the facepiece. The net is designed
to conform to the member's scalp. Two pull straps are attached to each side of the
facepiece; pulling the straps, first the bottom and then the top snug, will ensure a
proper facepiece to face seal. A buckle-thumb release is attached to each pull strap
and facilitates the loosening of the straps prior to facepiece removal.
3.9.4 Nose cup assembly is designed to be an integral part of the facepiece and must be in
place. Inhalation valves, voicemitters, voicemitter ducts, and nosecup retainer must
all be present to ensure proper inhalation of breathing air.
These components help remove carbon dioxide from within the facepiece.
3.9.5 Split ring, attached to a head net tab "D" ring on the user’s right side, is provided to
secure the facepiece during a stand-by position and while the SCBA is stored on the
apparatus.
3.9.6 SCBAs should not be worn when conditions prevent a good face to facepiece seal.
Such conditions may include, but not limited to, growth of beards, side burns, a
skull cap that projects under a facepiece or temple pieces on glasses. Also, the
absence of one or both dentures can seriously affect the fit of the facepiece. Use of
the SCBA without a good face to facepiece seal may reduce the duration of use
and/or expose the user to the atmosphere the SCBA is intended to protect against.
15
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
3.9.7 All AV 2000 face pieces should have an installed grey nose cup. Black nose cups
have been discontinued. Facepiece with a black nose cup should be forwarded to
MSU requesting a grey nose cup.
Frame
Inhalation Valve
Nosecup Retainer
Figure 14
16
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
Pak-Alert SE 7
sensor module.
Figure 15
Signal Lights
Figure 16
3.10.1 The Scott Pak-Alert SE 7 is intended to be integrated only with the Scott
Air-Pak 4.5 Self-Contained Breathing Apparatus (SCBA). The Pak-Alert SE 7 is a
Personal Alert Safety System (PASS) intended to assist in locating a member who is
incapacitated or in need of assistance.
17
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
Note: Pak-Alert SE 7 and PASS are used interchangeably.
3.10.2 The Pak-Alert SE 7 consists of a motion sensor module mounted to the bottom of the
SCBA backframe, a pressure switch mounted between the cylinder and gauge line,
and a control console mounted on the wearers’ right shoulder strap at the pressure
gauge location. Figure 15
3.10.3 The Control Console, which is located on the right shoulder strap, contains a cylinder
air pressure gauge, a console lens, a manual alarm button (red indicator), and a reset
button (yellow indicator) located on the side of the console. Figure 16
A break in the Control Console tube will result in a slight air leak. While this leak will
not greatly reduce the member's breathing air, the member MUST NOTIFY THEIR
OFFICER AND IMMEDIATELY LEAVE THE CONTAMINATED AREA. This
member must be accompanied to a safe area by another member using an SCBA.
The vent holes on the back of the Control Console should NEVER be plugged or
sealed in any way, regardless of a suspected air leak. If a leak is suspected, member
MUST NOTIFY THEIR OFFICER AND IMMEDIATELY LEAVE THE
CONTAMINATED AREA. This member must be accompanied to a safe area by
another member using an SCBA. There are two (2) lights on the back of the Pak
Alert SE 7 called buddy lights. They flash green in normal mode and red in alarm
mode.
3.10.4 Provided proper batteries have been installed and the cylinder contains air, this PASS
device is automatically activated when the SCBA is pressurized by opening the cylinder
valve. Once activated, the Scott Pak-Alert SE 7 will remain activated until:
1. The cylinder is turned off and the residual air pressure purged from the regulator,
and
2. The reset button has been pressed twice.
3.10.5 In the automatic mode, the Scott Pak-Alert SE 7 constantly monitors motion of the
SCBA backframe. The motion sensor is located in the sensor module along with the
audible alarm. If the sensor module does not sense motion of the SCBA for 20
seconds, the Pak-Alert SE 7 will signal a pre-alarm condition. If there is still no
motion of the SCBA for the next 12 seconds, the full alarm will sound.
Note: A noticeable change in the Pak Alert SE 7 from the previous model is the audible
alarm, which now has a variable pitch, that helps eliminate audible alarm saturation.
It allows for an easier way to hone in on the audible alarm and reduces reflective
alarm sound.
18
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
3.10.6 PRE-ALARM
A. Once the SCBA is pressurized, the Pak-Alert SE 7 will automatically sound a
pre-alarm if the SCBA remains motionless for more than 20 seconds. When a
pre-alarm occurs, the green flashing light on the control console is replaced by
a red light which flashes approximately once per second and is accompanied by
an ascending/descending alarm that increases in decibels during the pre-alarm
cycle.
Note: Buckling and tightening the SCBA waist strap will decrease pre-alarm
activations.
A. If the Pak-Alert SE 7 is not moved, the Pak-Alert SE 7 will go into full alarm
12 seconds after the pre-alarm starts.
B. Full alarm is indicated by a loud, almost continuous, 3-tone alarm from the
sensor module accompanied by flashing of the red signal light on the control
console and buddy lights. The full alarm condition can only be cleared by
manually pressing the reset button twice, located on the side of the control
console.
C. After the full alarm has been silenced by pressing the reset button twice, the
Pak-Alert SE 7 will remain activated with the green light flashing once per
second. In the activated or "automatic" mode, it will again go into pre-alarm
followed by full alarm unless there is movement of the SCBA at least once
every 20 seconds for as long as the SCBA is pressurized.
19
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
B. The manual alarm causes the full alarm signal to be given. Provided working
batteries are in the Pak-Alert SE 7, the manual alarm may be activated by
pressing the manual alarm button at any time, even when the SCBA is not
pressurized. If the manual alarm button has been pressed without the SCBA
pressurized, the alarm can be silenced by pressing the reset button twice. The
Pak-Alert SE 7 is now on and in an automatic mode. To turn the unit off, press
the reset button twice again while the unit is not in the alarm mode.
A. The Pak-Alert SE 7 cannot be turned off if the cylinder valve is open and/or
pressure remains in the SCBA. Pressing the reset button when the SCBA is
pressurized will only reset an alarm condition and return the Pak-Alert SE 7 to
automatic mode. When use of the Pak-Alert SE 7 and SCBA is no longer
required, first close the cylinder and then vent the residual air from the SCBA
by opening the regulator purge valve. After waiting until the airflow stops,
close the regulator purge valve and turn-off the PASS by pressing the reset
button twice. The green flashing light will go out and a 15 second beep
sequence will be heard from the sensor module as residual air bleeds from the
system. After the air has been completely bled off the system, the unit will
sound a quick two-tone chirp indicating the Pak-Alert SE 7 is deactivated.
B. If the SCBA is turned off and de-pressurized without pressing the reset button
twice, the Pak-Alert SE 7 will continue to monitor motion in automatic mode.
This means that the Pak-Alert SE 7 may be used to monitor motion after the
SCBA is turned off and de-pressurized. Resetting the full alarm after the
SCBA has been de-pressurized will not turn off the Pak-Alert SE 7. The reset
button must be depressed twice with no alarm condition to turn off the Pak-
Alert SE 7 (the 15 second beep sequence and two tone chirp should be heard).
Note: The loud audible alarm and red flashing light can be turned on at any time by
pressing the red manual alarm button on the control console.
A. If while using the SCBA, the batteries begin to approach the end of their useful
life, the sensor module will begin to sound a chirp every two seconds and the
green light on the control module will go out. This is a low battery condition.
In this condition, the Pak-Alert SE 7 will continue to operate normally, going
into pre-alarm after 20 seconds with no motion, and full alarm after 12 more
seconds of no motion.
B. While in low battery condition, the Pak Alert SE 7 will continue to operate for
a period of time greater than the longest duration cylinder available for the
SCBA. However, the batteries must be replaced before using the SCBA again.
Failure to replace the batteries and/or continuing with multiple uses of the
SCBA after the Pak-Alert SE 7 has indicated the low battery condition,
may result in failure of the Pak-Alert SE 7 during use.
20
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
Note: Before replacing batteries, close SCBA cylinder valve, open SCBA purge
valve to vent out residual air, close SCBA purge valve and press the reset button
twice. A 15 second beep sequence occurs as the residual air bleeds off. Unit will
sound a two-tone chirp and green light will go out indicating unit is inactive. Never
remove or replace batteries with system pressurized or damage may occur to
electronic components.
A. When replacing batteries on SCBA equipped with harness and backframe,
place SCBA in a clean, non-hazardous area.
C. Remove used batteries from battery compartment by sliding them out of the
battery compartment. Figure 18
D. Install six (6) fresh new AA batteries of the same brand. Always replace all
batteries at the same time. The battery holder is marked with the style and
orientation of the batteries required. (Figure 4). Use six each of one of the
following 1.5 volt AA batteries.
Eveready Energizer Alkaline E 91 or EN 91
Duracell Alkaline PC 1500, MN 1500 or MX 1500.
Note: Do not mix battery brands. Verify correct orientation of batteries as shown by
labels inside the battery holder.
21
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
Figure 17 Figure 18
E. Before assembly of battery cover, are the type indicated above, and they have
been installed properly.
H. Do not mark, paint, etch or drill any of the Pak Alert components or housing in
any way.
3.10.13 SPECIFICATIONS
In Full Alarm (95 dBa sound and red flashing light) ---- Approximately 8 hrs
22
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
3.11.1 Cleaning, maintenance and storage of a SCBA with a Pak-Alert SE 7 shall be done
as part of the normal SCBA post use inspection and cleaning.
3.11.2 The exterior of the Pak-Alert SE 7 may be cleaned while cleaning the exterior of the
SCBA by wiping with a damp sponge and thoroughly wiping dry. The lens on the
front of the control console should be cleaned after every use to insure maximum
light intensity at all times. Do not use solvents for cleaning or attempt to paint the
exterior surfaces of the Pak-Alert SE 7.
23
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
4. INSPECTIONS
4.1.2 At the start of each tour members will be assigned an SCBA for their use.
The Company Officer will supervise the inspection of each SCBA by the assigned
member, and then make an entry in the Company Journal of this event indicating
SCBA #, names of inspecting members, and the results of inspection.
4.1.3 Place defective SCBAs out of service and replace with a battalion spare. Defects
found must be included on the SCBA Record Card (Form SD-30). When repairs to
SCBAs are required, the officer on-duty will prepare one invoice and one receipt on
Form RT-2. Defective items and RT-2 forms will be delivered by messenger to the
Mask Service Unit. Form RT-2 must include the SCBA serial number and specify
defects. Small replacement parts for SCBAs may be requested from MSU by
telephone. Delivery of such items will be accomplished through the bag.
Requesting unit will hold defective item until replacement is received, then return
defective part in receiving envelope for charge-off at MSU.
4.2.1 Remove SCBA from apparatus mounting bracket and rest wire frame on a clean, dry
surface with cylinder on top and straps spread out.
4.2.2 Check the cleanliness and condition of the entire SCBA assembly:
A. Backframe - no deformities or breaks at weld spots.
B. Harness Assembly - no cuts, rips or frayed straps. Remove the ends of the
waist straps and buckle from the belt retainers. Squeeze alligator clips on waist
belt and pull straps, so both ends overlap each other evenly. Ensure that
shoulder straps are fully extended.
4.2.3 Facepiece -
A. Disinfect and Clean.
B. Inspect head net and straps for fraying and elasticity. Check that buckle
thumb leavers are in working order.
C. Inspect internal parts:
1. Check rubber seal around lens, be sure there are no deformities, cracks or
tears.
2. Inspect for presence of a grey nose cup assembly.
24
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
3. Inspect inhalation valves in nose cup assembly, be sure they are both
present and lay flat against the nose cup.
4. Make sure voicemitter ducts are present and not deteriorated.
25
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
26
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
Caution: If cylinder threads are cracked, pressure from the opened cylinder could cause
the threads to break away, thus causing the high pressure hose coupling to be
blown off the cylinder. DO NOT touch the cylinder threads, since although not
immediately visible, a metal sliver may pierce the skin like a splinter.
Crack obscured by
high pressure
hose coupling
Figure 19
B. BATTERY TEST
When the Pak-Alert SE 7 is in the off condition (cylinder valve closed with no
flashing green light on the control console), the batteries can be checked by
pressing and holding the reset button on the console. A green light will
illuminate on the console to indicate sufficient battery power remaining;
a red light indicates that the batteries must be replaced before the SCBA is used
again.
If the low battery condition (a steady chirp every two seconds with no flashing
lights) occurs at any time during regular operational inspection, do not use the
SCBA. Change the battery in the sensor module immediately and repeat the
regular operational test or take the SCBA out of service until the batteries are
changed and the regular operational test is successfully performed.
C. In several of the inspection procedures, a full alarm will be observed.
The full alarm condition includes an audible tone that can exceed 95 decibels at
approximately 10 ft. The alarm should be reset immediately on verification
that it is functioning properly. Hearing protection should be worn if prolonged
exposure to a full alarm condition is anticipated.
28
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
D. While performing the visual inspection of the SCBA:
Visually inspect all Pak-Alert SE 7 enclosures, lenses, and wire conduits for
cracks, wear or other damage.
29
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
AFTER COMPLETION OF ALL SCBA CHECKS AND BEFORE TURNING OFF CYLINDER VALVE:
30
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
The Pak-Alert SE 7 shall remain active with green light flashing. Do not move SCBA.
Pre-alarm shall occur within 20 seconds. Move SCBA backframe slightly, pre-alarm
shall reset and green light shall start flashing again.
31
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
5.1.1 Remove the SCBA assembly from its apparatus mounting bracket, by pulling evenly
on the two shoulder straps.
5.1.2 With bunker coat fully snapped and helmet on, hold SCBA in front of legs from the
upper part of each shoulder strap with palms down. Backframe of SCBA should face
outward and cylinder towards body.
5.1.3 Look over left shoulder to ensure that either no person or object is within the SCBA
swing range.
5.1.4 In one continuous motion, swing SCBA over left shoulder, allowing arms to pass
through respective shoulder strap loops. Left hand should continue to hold onto left
shoulder strap, until SCBA rests on back.
5.1.5 While bending forward, reach back and grasp both ends of the waist belt. Lift the
entire SCBA assembly to allow the belt to rest on hips. Connect the quick release
buckle of the pre-adjusted waist straps.
5.1.6 Adjust the shoulder straps until the backframe touches the member's back. DO
NOT pull too tight since this will transfer the SCBAs weight from the hips to the
shoulders, increasing fatigue.
5.1.7 Reach back with right hand and turn cylinder valve FULLY counter-clockwise.
Listen for the momentary activation of the vibralert alarm, Pak Alert, and look for
the five lights in the HUD.
Note: The activation of the vibralert alarm is NOT an indication that the valve is fully open.
The valve handle must be turned counter clockwise until it reaches the open stop
position. If the cylinder valve is not fully opened, it will restrict air flow, possibly
causing an extremely dangerous condition, similar to SCBA shutdown.
5.1.8 At this point, the facepiece will either be donned or placed in a standby position.
Never allow the facepiece to hang free.
5.2.2 Grab hold of the upper part of the left shoulder strap with left hand.
32
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
5.2.3 Lean body forward while getting out of jump seat, allowing body motion to pull
SCBA from mounting bracket, as hand continues to hold left shoulder strap.
5.3.1 While awaiting orders prior to the anticipated entry into a contaminated area,
members are to place facepiece in the Standby Position. This position will prevent
the facepiece from dangling and possible damage.
5.3.3 During the standby position, the split ring is hooked over the open tab of the left
shoulder strap alligator clip.
5.3.4 When the standby position is used, the open side of the facepiece should be placed
against the member's chest, so that debris cannot enter.
5.4.1 The helmet, hood and SCBA facepiece function as an ensemble that is designed to
encapsulate and protect a members head, neck, face and airway from burns and falling
debris. A member is exposed to injury when one component fails or is knocked off.
Further, it can be the first link in a chain of events that prevents a member from performing
an assigned task, and endangers the lives of their fellow firefighters and the civilians they
are charged with protecting. The importance of properly donning this protective
equipment cannot be overstated.
33
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
5.5.3 With the head net on the inside, bring the facepiece up to your face.
5.5.4 Grab the helmet brim with the right hand and remove the helmet over the
facepiece and left hand.
34
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
5.5.5 The chin strap should pass over the facepiece and left hand, and rest on the left
forearm.
5.5.6 Grab the head net with the right hand and pull it over your head while placing
your chin in the chin cup. Smooth the net out over the scalp so there are no
bumps that will interfere with wearing the helmet.
35
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
5.5.7 With both hands, tighten the facepiece against the face by pulling the two
bottom straps and then the two top straps evenly straight back.
5.5.9 Pause breathing momentarily and listen for any leaking air. If any is heard, it
will be necessary to readjust the facepiece before entering a contaminated
atmosphere. If no air is heard, then a proper facepiece seal has been obtained.
5.5.10 With both hands, pull the Nomex hood over the head net and frame of the facepiece
lens.
5.5.11 Place the left hand back on the regulator with the left thumb on the purge valve
36
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
5.5.12 Grab the helmet with the right hand and place it over the hood on your head using
the left thumb to guide the chinstrap over the purge valve.
5.5.13 With the left hand, grab the free end of the chin strap and pull it tight.
5.6.3 Place thumbs behind the buckle-thumb releases located on each facepiece strap
and pull forward until the facepiece is loose.
5.6.4 With the regulator assembly in the left hand, press the manual shut-off switch to
stop air flow.
5.6.5 While holding the regulator, lift the facepiece up and pull it off of the head.
5.6.6 Place the nylon head net inside the facepiece lens. Kevlar head nets shall be
stored on the inside of the facepiece which will prevent the head net straps from
becoming tangled with the buckles.
37
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
5.7.1 While bending forward, squeeze and fully extend both shoulder strap alligator
clips.
5.7.3 With left hand grasping left shoulder strap, press button on waist belt quick
release buckle with right hand.
5.7.4 As left hand continues to grasp shoulder strap, stand straight and allow SCBA to
swing over left shoulder to front of body.
5.7.6 Shut down the cylinder valve and purge all residual air from the SCBA system.
38
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
6.1.2 Squeeze alligator clips and fully extend both shoulder straps.
6.1.3 With left hand grasp left shoulder strap as high as possible.
6.1.4 Slip right arm through right shoulder strap and unbuckle waist belt.
6.1.5 As left hand continues to grasp shoulder strap, member should turn to their left
180 degrees to face the entangled SCBA.
6.1.6 With free right hand sweep entire SCBA to locate obstruction.
6.1.7 Free SCBA from entanglement. If a cutting tool is to be used, it is best to be kept
in the right pocket of the bunker coat. This allows control of the SCBA with the
left hand.
6.1.8 Place both hands on shoulder straps and back away from the obstruction.
6.1.9 Re-don SCBA. Buckle waist belt then shoulder straps. When continuing with
firefighting operations, cancel the MAYDAY when member becomes safe.
There are times where it may be necessary to pass beneath low clearance overhead
obstructions. Generally, this may be when crawling through or operating in a confined area.
6.2.2 Squeeze and fully extend both shoulder strap alligator clips.
6.2.3 With left hand grasp left shoulder strap as high as possible.
6.2.4 Slip right arm through right shoulder strap and unbuckle waist belt.
39
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
6.2.5 As left hand continues to grasp shoulder strap, allow SCBA to swing over left
shoulder to front of body.
6.2.6 Lay SCBA assembly down on cylinder and push ahead, as body follows behind.
The left hand should always continue to grasp shoulder strap as a means of
orientation.
6.2.7 Once overhead obstruction is cleared, redon SCBA. Buckle waist belt then
shoulder straps.
6.3.2 Squeeze and fully extend the right shoulder strap alligator clip.
6.3.3 Slip the right arm through right shoulder strap and grasp waist belt without
unbuckling.
6.3.4 While right hand grasps waist belt buckle and left hand grasps cylinder at the rubber
bumper, twist the entire SCBA assembly as far left as necessary to pass obstacle.
6.3.6 After passing obstacle, return SCBA assembly to its normal position on members'
back.
6.3.7 Reach back and pass right arm through right shoulder strap.
6.4.1 Place right knee, right shoulder, and head through studs. (placing left shoulder
through first, may cause low pressure hose to get pinched on the object you are
trying to pass, cutting off air supply). (Figure 21)
6.4.2 Bring left arm over left shoulder in swimming motion. (Figure 22)
40
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
6.5.2 Conserve as much breathing air as possible by covering the damaged area with
one hand.
6.5.3 If the leak is more than can be controlled with one hand:
A. Continue to cover as much of the damaged area as possible.
B. Press the manual shut-off switch after each breath to further limit the loss of
breathing air.
C. If damaged area is too large to allow the regulator shut-off to release, then
use the purge valve in an ON and OFF motion for each breath. This action
helps to conserve the limited amount of breathing air necessary for escape.
6.5.4 Notify Officer and immediately leave the contaminated area. This member MUST be
accompanied to a safe area by another member using an SCBA.
Note: If a member runs out of air, that member should remove the regulator from the
facepiece. The donned facepiece will provide some protection to the skin on the face.
41
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
6.6.3 If it is not possible to remove the member or civilian from the contaminated
atmosphere, then one of the following options can be used to provide an air
supply while freeing the trapped individual.
A. For trapped members, utilize the nearest available FAST Pak.
B. For civilians, utilize a FAST Pak other than the one assigned to the FAST Unit.
C. Utilize a spare SCBA to provide air strictly to the trapped member or civilian.
Note: Donning a facepiece in an IDLH/smoke environment, may make it difficult to create
the negative pressure needed to release the regulator manual shut-off switch. The red purge valve
may have to be turned on, to provide/initiate an air flow.
7 COMMUNICATION
42
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
7.3.2 Units should have prearranged hand/touch signals to communicate orders for
routine movements. Touch signals will be especially useful when smoke or other
factors make visibility poor.
7.3.4 Ladder, Rescue, and Squad Companies can establish signals similar to those of
Engine Companies to communicate orders for search, ventilation, etc.
7.4.1 When one member forcibly strikes another member with four distinct blows on
the shoulder and then pulls that member in a specific direction, the second
member will recognize that the other member knows of an emergency and should
promptly follow in that direction.
8.1.1 During roll call inspection, after members have each been assigned an SCBA for
the tour, and after each use.
43
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
8.2.4 Wear goggles to protect eyes when preparing or using a hypochlorite solution.
8.4.2 Never mix disinfectant or cleaning solutions, or their respective cloths and sponges.
44
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
8.5.2 Put on goggles and rubber gloves to protect eyes and hands from hypochlorite
solution.
8.5.3 Immerse facepiece in the hypochlorite solution for five minutes, wiping lens with
cloth. Never allow facepiece to remain immersed for longer than five minutes.
8.5.4 Remove facepiece from solution and thoroughly rinse under cold running water.
8.5.5 Wash facepiece with cleansing solution and sponge, and again thoroughly rinse
under cold running water.
8.5.6 Nose cup is designed to be an integral part of the facepiece and does not need to
be disassembled for cleaning and disinfecting.
8.5.7 In the event the nose cup is removed for cleaning or inspection, make certain it is
reassembled behind the chin pocket of face seal and properly seated between the
flanges of the voicemitter ducts.
8.5.8 Shake off remaining water droplets from facepiece. The facepiece shall be dried;
drying shall not be done in direct sunlight or in high heat.
8.5.9 Clean remaining SCBA parts of dirt and debris with damp sponge.
8.5.10 Areas where SCBAs are stored should also be kept thoroughly clean of dust and dirt.
8.5.11 Place the Kevlar head net inside of the facepiece lens. In order to achieve a
proper facepiece seal when donning the SCBA, Kevlar head nets shall be stored
on the inside of the facepiece. This will prevent the head net straps from
entangling with the thumb buckles
8.6.2 Remove the breathing regulator from the facepiece by rotating the regulator 1/4 turn clockwise.
8.6.3 Remove any obvious dirt from the external surfaces of the regulator using 70% Isopropyl
Alcohol with a sponge or soft cloth.
45
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
8.6.4 Inspect the inside of the regulator assembly through the regulator opening (Figure 23).
If excessive dirt or soil is present, return the entire SCBA with a completed RT-2 to
MSU, noting reason. Do not insert any foreign objects into the opening.
8.6.5 Depress the manual shut-off, close the purge knob by turning fully clockwise and spray a
minimum of 6 full pumps of 70% Isopropyl Alcohol into the regulator opening. Make
sure to also wet the immediate area around the opening (Figure 23). Swirl to completely
cover internal components. Turn regulator opening face down and shake excess liquid
out. Allow for 10 minutes of contact time to disinfect prior to rinsing.
Note: Alcohol and water should not be directed into the spray bar ports.
Figure 23
8.6.6 Rinse regulator with drinking water using a spray bottle or softly running water.
The inside of regulator must be thoroughly rinsed after applying the 70% alcohol.
Failure to thoroughly rinse may cause a number of adverse effects. Rinsing is a key
component to the SCBA integrity after disinfecting.
8.6.7 Shake excess water out of regulator. Completely air-dry the regulator before use.
Perform regulator check by opening the purge valve and observe the air flow from the
regulator spray bar. Droplets of water indicate the regulator is not dry. If this occurs,
repeat drying procedure and regulator check.
Note: Under no circumstances should the face of the regulator be banged against a hard
surface to expedite the removal of water. It may damage the spray bar ports or crack the
exterior surface of the regulator. Shaking and opening the purge valve is the only
acceptable way to remove water.
9.1 A calendar year Preventive Maintenance Program has been implemented for each SCBA.
The intent is to flow test and ensure the operational condition of each SCBA.
46
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
9.1.1 MSU will perform a complete annual inspection, repair and flow test of each
SCBA and FAST Pak (including the UAC) on one of the following occasions:
A. Units scheduled by Fleet Services for apparatus PMP (only at Randall’s
Island). These SCBAs will remain on the apparatus and transported to
Randall’s Island. The serviced SCBAs will be returned with the Unit’s
apparatus and placed back in-service.
B. Units scheduled for training at the Fire Academy.
C. If a Unit’s SCBAs do not receive an annual inspection on one of the above
occasions, MSU will notify the unit and make other arrangements.
9.1.4 Battalion Spare SCBAs - each battalion is assigned 12 spare SCBAs. An RT-2
stating annual PMP should be attached and forward with the spares to MSU on
the following schedule;
January 1 ....................Spares 1, 2, 3
April 1 ........................Spares 4, 5, 6
July 1..........................Spares 7, 8, 9
October 1....................Spares 10, 11, 12
9.1.7 Each reserve Engine, Ladder and Rescue are assigned their own SCBAs and
facepieces. The unit responsible for the maintenance of these reserve apparatus
should forward the reserve SCBAs along with the company SCBAs.
47
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
10 IDENTIFICATION
10.3 SCBA
labels are coded with white numerals on colored backgrounds. The colored
backgrounds indicate the type of unit to which the SCBA is assigned to, as follows:
10.5 Worn or missing labels will be replaced by the Mask Service Unit.
48
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
10.6 All SCBAs are being marked in a manner similar to the handie-talkies. The
numbering system duplicates the handie-talkie number designations. For example, #1
is the Officer,
#2 is the chauffeur, etc.
10.7 Each SCBA is labeled in the center of the upper section of the back plate on the
side that rest against the member’s back. The marking is on a 3/4” wide marking
tape, and is covered with a clear 4” X 2” protective label. The markings will be
visible when the SCBA is properly mounted in the SCBA bracket on the apparatus.
For example, SCBAs in Engine 264 and Ladder 134 would be labeled as following:
11 CONCLUSION
Warning: Only those options and or accessories authorized by SCOTT and approved by
NIOSH and where required, by NFPA may be installed on this SCBA. The use
of unauthorized and or unapproved options or accessories could cause partial or
complete failure of the SCBA which may result in injury or DEATH.
11.3 If a problem arises with an SCBA, and the information required to resolve the
difficulties are not covered in this bulletin, unit shall contact the Mask Service Unit
and be guided by their instructions.
49
FDNY Probationary Firefighters Manual
Chapter Six SCOTT 4.5 POSITIVE PRESSURE SCBA
50
FDNY Probationary Firefighters Manual
Chapter Six Addendums
ADDENDUMS
51
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 1 Toxins/References
REFERENCE 1
1. Carbon monoxide is one of the most abundant of fire gases and poisons by asphyxiation.
It is colorless, odorless, and tasteless, making it impossible to detect. Since it combines
with hemoglobin (an oxygen carrying constituent of the blood) 210 times more readily
than oxygen does, carbon monoxide rapidly robs the blood of oxygen needed by the
body. At the same time, carbon monoxide prevents the blood from disposing of the waste
carbon dioxide it normally brings back to the lungs. This mode of action makes carbon
monoxide dangerous at relatively low concentrations. Exposure to 1.3% of carbon
monoxide will cause unconsciousness in two or three breaths and will cause death in a
few minutes. Exposure to small concentrations for only a few seconds inhibits one's
ability to think clearly, rapidly causes disorientation, and gives a feeling of euphoria
compounding the risk hazard.
3. Smoldering fires and fires partially extinguished by sprinkler systems produce large
quantities of carbon monoxide. Low heat from these fires affects the buoyancy of gases
of combustion making ventilation very difficult. This is particularly true with fires in
cellars and other low areas, where means of ventilation are restricted.
4. During mask operations and when encountering any emergency situations, poor
visibility, or communication problems, self-discipline must be exercised to control any
reflex action that may cause you to remove your facepiece.
5. Wear your mask, adhere to the Department's mask policy, accept and understand that
carbon monoxide is extremely deadly. This may well save a life - possibly yours.
52
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 1 Toxins/References
REFERENCE 2
1. CARBON MONOXIDE
Carbon monoxide is produced by the incomplete combustion of many common materials,
Including wood and paper. Other more modern sources are foam rubber, rubberized flooring,
vinyl wall paper, and pipes and other Installations made with polyvinyl chloride. When inhaled,
carbon monoxide crowds oxygen from the blood, and this eventually seriously affects the brain
as well as other tissues. If the process is not reversed, death follows.
2. HYDROGEN CYANIDE
Materials that give off hydrogen cyanide when they are burned include rubber and paper, and
some frequently used in carpets, namely wool, nylon, and acrilan, and in upholstery, namely
polyurethane foam. Hydrogen cyanide is a gas that is colorless but has a noticeable almond
odor. It can be absorbed through the skin as well as inhaled. It causes one to gasp in breathing,
induces muscle spasms, and speeds up the heart rate. Collapse is often sudden. A concentration
as low as 270 ppm (parts per million) is fatal.
3. ACROLEIN
At fires involving plastics, and also petroleum, there may be acrolein in the air. In homes, it can
arise from the burning of acrilan in carpeting or acrylic light diffusers. Its extreme irritation to
your nose can be felt at less than 10 ppm. It can damage your eyes.
53
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 1 Toxins/References
4. HYDROGEN CHLORIDE
Hydrogen chloride (HCL) is becoming more frequent at fires because more plastics containing
chlorine, for example in PVC, are now found in homes (and also in drug, toy, general
merchandise stores). It is produced by the burning of rubberized flooring, vinyl wall paper, and
pipes and other installations made with polyvinyl chloride. At fires, the overhaul stage is
especially dangerous, as it is for other noxious gases, because, when you remove your mask,
toxic fumes can be lingering. HCL is colorless, but has a pungent odor and is intensely irritating
not only to your eyes but also to your respiratory tract which may swell enough to suffocate you.
5. PHOSGENE
Phosgene COC12 is tasteless, and is odorless at first, but at 6 ppm it has a musty-hay smell.
Smaller amounts can cause coughing and can irritate your eyes. The moisture in your lungs
decomposes phosgene into hydrochloric acid. It may take several hours before you feel the full
effect. If the concentration reaches 25 ppm, phosgene is deadly.
6. NITROGEN OXIDES
Nitrogen dioxide, a reddish brown gas, irritates your lungs, and enough of it can cause an edema
in them that blocks breathing and so can suffocate you. It is insidious, for you can stand the
irritation in your nose and throat, even when you are breathing in a lethal dose, whose real
effects may not come for several hours.
Nitric oxide is dangerous in itself, but especially because oxygen and moisture are enough to
turn it into deadly nitrogen dioxide. These oxides of nitrogen, when inhaled, form nitrites and
nitrates, which chemically attach to your blood and lead to nausea, abdominal pains, vomiting,
and discoloration of the skin (from oxygen deficiency in the blood). They can also dilate your
arteries, vary blood pressure, and cause headaches, dizziness and delayed physical reactions.
7. FORMALDEHYDE
formaldehyde is used commercially for fumigation and as a preservative. At a fire it may be
produced by the burning of such things as wall paper and lacquered wall coverings. It collects
on carbon particles and is then inhaled. It is intensely irritating, and also has a suffocating
effect. It may inflame the bronchial tubes, from which bronchitis may develop.
8. ACETALDEHYDE
Acetaldehyde is less irritating than formaldehyde but it depresses the central nervous system
more strongly. Its fruity odor may be masked by other odors present. Exposure to this gas
usually leads to severe irritation to the eyes and the mucous membranes. Ingestion has effects
similar to alcohol intoxication.
54
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 1 Toxins/References
REFERENCE 3
Asbestos:
The danger of a firefighter breathing in particles of asbestos is wide spread, because most
buildings were put up before the danger was understood and before the use of asbestos was
controlled by federal regulations. Building permits fail to give information about whether
asbestos is present. A firefighter pulling down a ceiling or breaking open a wall is exposed
to asbestos from insulation, acoustical tile, adhesives, jointing compounds, floor tile, etc.
Chlorinated Organics:
Degreasing agents, solvents, and refrigerants contain chlorinated hydrocarbons, which are
considered to be carcinogens. Firefighters encounter them at many places. These include service
stations, auto repair shops, and auto dealers; also printing and dry cleaning establishments.
Some wood preservatives widely used in constructing wooden houses are also noxious.
55
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 1 Toxins/References
Pesticide:
Many pesticides are carcinogenic, and they are found not only on farms but also in garden shops,
hardware stores, etc.
Benzene:
There is an airborne danger at fires in places where solvents and other products containing benzene
are used or stored. These include gas stations and hardware stores. Moreover, benzene is produced
by the burning of PVC, epoxy resins, etc. Benzene is generally thought to be a cause of aplastic
anemia, which is often followed by leukemia.
56
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 1 Toxins/References
REFERENCE # 4
Most smoke related injuries are incurred by firefighters when smoke conditions are "light" and
not so excessive as to prevent entry without mask. (See attached case presentation)
Some examples of these "light" smoke conditions that members operate in are food on the stove,
oil burner and electrical fires, and fires involving household and office furnishings.
During the course of a tour it is possible that a member could operate within a few of these
"light" type smoke conditions without benefit of SCBA.
If he was asked what kind of tour he had, he probably would answer by saying "it was an easy
tour, no work, only a few small jobs." However, a member exposed to a few small jobs without
the use of SCBA, could incur an accumulative effect associated with some of the following
smoke conditions:
57
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 1 Toxins/References
Practically every structure contains materials that when involved during a fire, are capable of
producing toxic gases. These gases can be present even though smoke is barely visible. You
may not feel that you have been exposed to “smoke inhalation” by taking these few “light”
feeds during a tour. However, you definitely have "inhaled" toxic products of combustion.
The Federal Government issues a warning that smoking cigarettes may be hazardous to
your health. Our message is: “The negative effects that the accumulated light feeds
have on a firefighter’s body over the course of tours, weeks, months and years, are hazardous
to one’s health.”
58
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 2 (APR) Adaptor
Facepiece And Air Purifying Respirator (Apr) Adaptor-40 Mm & Single Mpc
Plus Cartridge Filter
1. INTRODUCTION
2.1 Each member is fit tested using their personal Scott AV-2000 facepiece during their periodic
medical using an adaptor in the APR mode.
2.2 The respirator seals against the skin of the user’s face and removes harmful contaminants from
the inhaled air by chemical reaction or mechanical filtration.
2.3 The Inhalation Valve in the 40mm adapter acts as a check valve to prevent the backflow of
exhaled air through the MPC PLUS cartridge. Exhaled air leaves the facepiece through the
exhalation valve in the 40mm adapter.
59
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 2 (APR) Adaptor
The protection offered by this respirator depends upon the quality of the facepiece fit, the
condition of the respirator and the use of the MPC PLUS cartridge. The length of time the
respirator will provide protection also depends upon the conditions of use.
This respirator is intended to be used in very limited and specific situations. No member shall
don a respirator without specific instructions from the Incident Commander. The Incident
Commander should only make this decision after consultation with the Haz-Mat Group
Supervisor and all the risks have been properly evaluated. If any uncertainty exists than the use
of SCBA should be continued until such time as the hazards can all be evaluated properly.
Anticipated uses include:
♦ Asbestos incidents, non-fire related.
♦ Confirmed or suspected biological incidents where continuous atmospheric monitoring is done.
♦ Decontamination operations of a long duration where the filter will remove the known
contaminants and atmospheric conditions are monitored and meet the above criteria.
60
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 2 (APR) Adaptor
5. SPECIAL MATTERS
5.1.1 These adaptors and cartridges should not be carried in the member’s bunker gear. They
should remain in their sealed pouches in the infection control compartment
(CFR-D Manual, Chapter 3) on the apparatus for use at incidents approved by the IC.
5.1.2 Air Purifying Respirators (APR) are not positive pressure devices and do not provide the
protection of SCBA. Proper facepiece seal must be maintained.
6. CARTRIDGE PROTECTION
The MPC PLUS air-purifying cartridge is rated as adequate protection against the
following substances:
7. DISTRIBUTION
7.2.3 Engine, Ladder, Rescue and Squad Companies will receive six adaptors and twelve cartridges
that will remain sealed in their pouches. A seventh adaptor and two cartridges will be delivered
to be used and kept for training purposes.
7.2.4 Special Field Units will receive the appropriate number of sealed pouches for the approved
riding positions and one additional set for training purposes.
8. REPLACEMENT
For replacement of filter cartridges and adaptors, forward a 23-BS-2 form to the Mask Service
Unit.
9. DONNING PROCEDURE
9.1 Examine the facepiece to be certain it is complete and in serviceable condition. Check to see
that the inhalation and exhalation valves are properly installed and operational. Check that the
nose cup is properly positioned behind the face seal chin pocket.
9.4 PERFORM NEGATIVE PRESSURE LEAK CHECK. Close off inlet side of MPC PLUS by
placing the palm of one hand over inlet located on front of MPC PLUS canister and inhale
slowly, holding breath momentarily. Leakage should not be detected and the facepiece should be
drawn slightly to the face.
9.5 Should any leakage be detected, correct problem by readjusting the facepiece.
10.1 The respirator removal must be done in a fresh air environment. Leave the contaminated area
and be certain that the respiratory protection is no longer required.
10.2 If you have been exposed to contaminants, decontamination of PPE must be accomplished prior
to removal of the respirator.
10.3 Loosen all head harness straps to their full outward position.
10.4 Remove by pulling the facepiece up and back over the head. Care must be taken to prevent
contamination of the interior portion of the facepiece during and after doffing.
62
FDNY Probationary Firefighters Manual
Chapter Six – Addendum 2 (APR) Adaptor
INSPECTION CHECKLIST
Verify that the adaptor is properly seated so that the facepiece retainer notch is aligned with the
facepiece locking clips. FAILURE TO PROPERLY MOUNT THE ADAPTOR MAY RESULT IN
NO RESPIRATORY PROTECTION. __________
When the AV-2000 APR is properly donned and adjusted, detection of any contaminant odor
or taste, or irritation of the eyes, nose or throat may be evidence of an improper seal or that the
filter cartridge is exhausted. Return to the clean area to check facepiece fit and if cartridge
replacement is necessary.
63
Probationary Firefighters Manual
Chapter 6
Part II
PART TWO
TITLE PAGE
Firefighter Removal 69
FAST Unit 89
FAST PAK 97
65
THIS PAGE WAS INTENTIONALLY LEFT BLANK
66
FDNY Probationary Firefighters Manual
Chapter Six Part II MANAGING MEMBERS IN DISTRESS
FIREFIGHTER REMOVAL
67
THIS PAGE WAS INTENTIONALLY LEFT BLANK
68
FDNY Probationary Firefighters Manual
Chapter Six, Part II FIREFIGHTER REMOVAL
FIREFIGHTER REMOVAL
1. INTRODUCTION
1.1 When a MayDay is transmitted for a firefighter that is lost, missing, trapped or in distress,
time will not be on your side. There will usually be a time lag between the trapped
firefighter recognizing that they are in danger and the transmission of a MayDay. Studies
have shown that once the firefighter realizes that they are in danger they will most likely try
to remove themselves before transmitting a MayDay.
1.2 The situations encountered where a firefighter may need assistance, can take many forms
and will involve both conscious and unconscious members. It can be as simple as finding a
disorientated member and leading them to safety or as complicated as a trapped, unconscious
member requiring extrication.
1.3 Depending on the member’s location, fire conditions and the cause of injury, various
drags or carries may be appropriate. Removal of the distressed firefighter to a tenable
atmosphere usually involves little danger from spinal injury if there was not a fall or
other injury involved. At times, fire conditions may be so severe that immediate removal of
the distressed firefighter is critical, even with a spinal injury. In all cases a member
should be positioned at the downed members head.
1.4 The removal methods outlined in this bulletin can be used for members that are either
conscious or unconscious. Once the member is out of immediate danger, immediately
begin to assess their "ABC" status (airway, breathing, circulation) and treat as necessary. At
this point the member should be secured to a backboard or stokes basket prior to moving
them any further, especially if there is any indication that a spinal injury is present.
1.5 The removal methods described are intended to be used only under difficult fireground
conditions. They require the use of minimal equipment and set up time. They are
intended for use as lifesaving steps under extreme circumstances. They are not intended for
use at removal situations, where time and equipment concerns allow the use of more suitable,
sophisticated hauling and patient handling systems.
2.1 It is important to emphasize that the operating units continue to fight the fire when a
MayDay/Urgent is transmitted for a distressed firefighter. The abandonment of Engine or
Ladder company operations to assist in a rescue where resources have been deployed to
handle the situation, places the trapped member and the rescuing firefighters in severe
danger. During this highly emotional time members must realize, that if they are not
assigned to the removal effort, they must continue with their assigned operation.
Company Officers must prevent members of their unit from leaving their area of
responsibility.
69
FDNY Probationary Firefighters Manual
Chapter Six, Part II FIREFIGHTER REMOVAL
3. OFFICER RESPONSIBILITIES
3.1 Unless there is no one else available the Company Officer should not get physically
involved in the operation. It is the responsibility of the officer to supervise the operation
and keep the members focused with the job at hand. Listed below are some additional
responsibilities of the Company Officer.
3.1.4 Call for any resources that may be necessary for the removal.
3.1.9 Call for an additional FAST Pak if the first is placed into operation.
4.1 When the member has been located, the appropriate radio transmission must be made.
Whether or not the removal involves a conscious or unconscious member, the priorities
will be:
• Fire/Environment.
• Air.
• Immediate medical care, if required and possible.
• Removal.
70
FDNY Probationary Firefighters Manual
Chapter Six, Part II FIREFIGHTER REMOVAL
5. EMERGENCY COMMUNICATIONS
5.1 If possible, the member transmitting the MAYDAY/URGENT shall begin, by pressing the
Emergency Alert Button, ensuring the message gets transmitted at maximum wattage.
Whenever the Emergency Alert Button is activated and/or a MAYDAY/URGENT transmitted,
all handie- talkie communication on that frequency are to cease, except those between the
member initiating the MAYDAY/URGENT and the IC.
5.2 The term MAYDAY or URGENT shall be repeated three times followed by the
Company designation and position of the member initiating the emergency transmission to the
IC. See Communications Manual, Chapter 9 for the proper format.
5.3 It is important to transmit a clear and concise message with the appropriate information.
An unclear message will only cause confusion and delays. When wearing the facepiece, the
microphone must be placed directly on the voicemitter.
5.4 All members must be aware that a message not acknowledged is a message not received.
The emergency transmission MUST be acknowledged by the IC.
6. FIRE/ENVIRONMENT
6.1 Consider the environment that you are operating in. The conditions in the area of the
distressed member will dictate the sequence of events. If your safety is in question, move to an
area of refuge.
• Can you operate safely in the area?
• What is the structural stability?
• Is a hoseline needed for protection?
7. AIR SUPPLY
7.1 The air supply of the member needs to be assessed whether the member is conscious or
unconscious. Removing the member from the IDLH is critical for survival. Assuring that
the distressed member has an adequate supply of air is the next priority. A member will suffer
brain damage without air in four to six minutes. In six to ten minutes a member will
move towards clinical death. Removing the member without first addressing the air
supply greatly diminishes a member’s chance of survival.
7.2 Once the member is located, a FAST Pak must be called for immediately, regardless of
whether the member has air or not. Every emergency situation is unique. The rescuer must
be trained to assess each situation and decide which re-supply method via the FAST Pak is best.
This decision can vary depending on several factors:
• Condition of the distressed member’s SCBA.
• Position of the distressed member.
• Accessibility for the various air supply methods.
71
FDNY Probationary Firefighters Manual
Chapter Six, Part II FIREFIGHTER REMOVAL
7.3 There are two ways to supply air to the distressed member:
• High Pressure.
• Low Pressure.
7.4 The high pressure air system permits emergency air replenishment of an SCBA from an air
supply source while still in use through the Universal Air Coupling (UAC). The UAC is for
emergency use only when a member is low or out of air within an IDLH. If the condition
of the distressed member’s SCBA is in doubt DO NOT provide air via the high pressure
system.
7.5 Air may be supplied to the member through the use of the low pressure system by one of the
following methods:
• FAST Pak regulator with the member’s facepiece.
• Hansen Fitting of the low pressure hose.
• FAST Pak facepiece and regulator.
7.5.1 The member assigned to monitor the air supply of the FAST Pak must protect the low
pressure hose, e.g., high heat, hot embers, sharp objects and entanglement.
7.6 If unable to determine if an unconscious member has air or not, supply the member with air.
There are three ways to determine whether the member has air:
• Turn the purge valve. If there is air, the flow will be heard.
• If the facepiece is on, break the seal between the member’s face and facepiece and
listen for air escaping.
• Look at the remote gauge of the downed member.
7.7 Use the downed member’s facepiece, unless it is damaged or missing, instead of the
facepiece with the FAST Pak. The member might require a special size facepiece, and
using their personal facepiece will provide a better seal.
7.8 Once the member is supplied with air and packaged, if required, remove them from the
IDLH as soon as possible.
• If the FAST Pak is NOT at your location, START the removal procedure.
Communicate with the member assigned the FAST Pak to determine a suitable location to
meet.
7.9 Once an unconscious member is supplied with air, turn the purge valve half way to allow a
constant flow of air.
Note: Members in distress should not remove their facepiece. If the air supply is depleted
remove the regulator and leave the facepiece on for protection. Having the facepiece on will
aid in re-establishing the air supply in the event the member becomes unconscious.
72
FDNY Probationary Firefighters Manual
Chapter Six, Part II FIREFIGHTER REMOVAL
8. IMMEDIATE MEDICAL CARE
8.1 Once clear of the IDLH environment, stop and assess the medical needs of the distressed member.
Treatment should be in accordance with CFR protocols driven by patient condition. Address
situations that are immediately life threatening such as:
• No pulse or not breathing.
• Major bleeding.
9. REMOVAL
9.1 There are a number of scenarios that can trap or disable firefighters. The method used to remove
the distressed member will be based on the conditions and the ability of the member to assist in
their own removal. Innovation and adaptation may be required to complete the rescue.
9.2 The removal of a conscious member will most often involve assisting them in exiting the area. If
the member is unable to assist in their own removal, a determination will have to be made as to
whether to wait for assistance or leave the area immediately.
9.3 There are two basic types of removals that will be encountered:
• Horizontal
• Vertical
Additional considerations for determining what method to use for the removal would be:
• Location and distance to an exit.
• If stairs or ladders are involved.
• Condition of the operating environment.
• Presence and extent of injuries.
10. IDENTIFICATION
10.1 There are a number of ways a member can be identified. Once the member is located and the
proper radio transmission has been made, the member needs to be properly identified to ensure it
is the member originally reported in distress.
73
FDNY Probationary Firefighters Manual
Chapter Six, Part II FIREFIGHTER REMOVAL
b. Positioning them on their right side (Photo 1) will provide access to the
following:
• Member’s name on back of the bunker coat.
• PRA identification number which will provide the unit and position.
This method will work as long as the SCBA is not a spare.
• Helmet frontpiece of the distressed member which may not be the unit the
member is working in.
• The engraved identification number on the side of the handie-talkie.
Photo 1
10.2 To accurately identify the distressed member by the use of the Pak-Tracker and EFAS, it is
imperative that all members ensure that both the SCBA and the handie-talkie coincide with
their assigned position.
74
FDNY Probationary Firefighters Manual
Chapter Six, Part II FIREFIGHTER REMOVAL
11. PACKAGING
11.1 Statistics will show that most often the distressed member will be found by a member or
members of an operating unit. Our main concern is the timely removal of the member
from the IDLH. If the member is unconscious or unable to assist in their own removal, the
member(s) who first found the firefighter must start the packaging process. There are a
number of methods that may be used to package a member. Listed below are the most
common methods that may be used for packaging:
• Use of the SCBA straps and personal harness.
• Nylon Tubular Webbing.
• Stokes basket/backboard.
• SKED Stretcher.
11.2 Packaging a conscious member is not always required for removal. In most situations,
packaging an unconscious member will be required for removal. The method used to
package the member will be determined by the type and the degree of difficulty involved in
the removal.
11.3 When an unconscious firefighter is found, it is more effective to take the time to package the
member prior to attempting removal. Attempting removal before packaging will delay
the removal, and may pull the member out of their SCBA harness and bunker gear.
11.4 If possible, position the member so that their back is facing toward the direction of
removal prior to starting the packaging process.
11.5 An operating member/unit that locates and starts the packaging process of the distressed
member will most likely will be fatigued and have a diminished air supply. Turning the
operation over to the dedicated FAST Unit upon their arrival will facilitate the timely removal
of the distressed member. Standardized firefighter packaging procedures will allow the rapid
transition from the operating unit to the FAST unit.
12. TRAINING
12.1 All members should be well versed in Emergency handie-talkie transmissions. Upon
discovery of a distressed member, the appropriate MayDay/Urgent message shall be
transmitted over the handie-talkie.
12.2 Many firefighter removal scenarios require extensive assistance. A FAST Unit is on the scene
of every working fire or emergency and is dedicated to assist distressed members. Members
should be familiar with the proper packaging techniques and basic removal methods. These
methods should be practiced with full PPE including gloves.
75
FDNY Probationary Firefighters Manual
Chapter Six, Part II FIREFIGHTER REMOVAL
13. CONCLUSION
13.2 Once the member is located, the appropriate MAYDAY/URGENT transmission shall be
made. We need to address the fire/environment, air supply, immediate medical care and
determine the method of removal. If packaging of the member is required, determine the best
method based on the complexity of the removal. The distressed member needs to be properly
identified to ensure it is the member originally reported in distress.
13.3 The Incident Commander/FAST Group Supervisor needs to be notified as to the location, the
condition of the member and the operating environment, and what resources will be needed.
The removal of trapped firefighters is greatly facilitated by the use of the personal
harness. All equipment issued and used by operating members must be worn properly
including the waist strap of the SCBA. This will greatly enhance your effectiveness as a
rescuer. These items will also help rescuers rescue you in the event you become the
unconscious firefighter!
13.4 The Department has pioneered the concept of the FAST Unit. These procedures are
presented with the hope that they will greatly assist a FAST Unit in the difficult task of
assisting and removing distressed members from hazardous situations. The rapid
deployment of the FAST Unit is imperative because time will not be on our side when a
firefighter needs assistance. In order to be proficient in these procedures, they must be
practiced.
76
FDNY Probationary Firefighter Manual
Chapter Six, Part II CONVERTING THE SCBA INTO A HARNESS
1.4 Lift up one of the distressed members legs and place it on your shoulder.
1.5 Take one half of the waist belt and put it behind the distressed member’s leg and bring it
up between their legs.
1.6 Take the other half of the waist belt and bring it in front of the distressed member’s leg
and reconnect the waist strap. (Photo 1)
Photo 1
1.7 Take the rappel hook from the personal harness of the distressed member and pull sharply
to release the hook from the belt.
1.9 Open the gate of the hook of the members personal harness and place the open hook
through both of the distressed members SCBA shoulder straps starting with the left strap
first and then the right strap The rescuer is moving the hook from their right to the left.
The hook is attached in this manner so as to prevent twisting of the handle of the
member’s personal harness. (Photo 2)
77
FDNY Probationary Firefighter Manual
Chapter Six, Part II CONVERTING THE SCBA INTO A HARNESS
Photo 2
1.10 Once both of the distressed member’s SCBA shoulder straps are positioned inside the
hook of their personal harness hook, release the gate of the hook.
1.11 Prior to tightening the distressed member’s SCBA straps, webbing should be placed
through the top end of the shoulder straps to make a girth hitch.
1.11.1 Place one end of the webbing through both shoulder straps. (Photo 3)
Photo 3
1.11.2 Take the other end of the webbing and place it through the center of the webbing
that was put through the shoulder straps. (Photo 4)
Photo 4
78
FDNY Probationary Firefighter Manual
Chapter Six, Part II CONVERTING THE SCBA INTO A HARNESS
1.11.3 Tighten up on the webbing by pulling on the end placed through the
center creating a girth hitch on the members SCBA shoulder straps. (Photo 5)
Photo 5
1.12 If time permits or additional securing is required, half hitches may be tied into both the
shoulder and the waist straps of the distressed member’s SCBA. When tying the half
hitches, start with the waist straps first. Pull one side of the waist straps tight to allow
enough excess in the strap to tie the half hitch. After the half hitch is completed, tighten
the other waist strap. The excess can be wrapped underneath itself to keep it from
slipping. Repeat the procedure for the shoulder straps by doing one side then the other.
Depending on the size of the member, the shoulder straps can be tied across their chest.
The benefits the knots provide will help to keep the distressed member’s SCBA as tight
as possible to the member’s back. This will help prevent the mask from getting hung up
on furniture, or when turning corners. More importantly, when carrying a member up a
flight of stairs, these knots prevent the mask harness from riding up and possibly
dislodging the member’s facepiece.
1.13 Packaging the member in this manner will allow for both a vertical or horizontal removal.
2.1 Prior to converting the member’s SCBA into a harness, move the firefighter to a sitting
position providing we do not suspect any type of spinal injury. Once in a sitting position,
rotate the member, if possible, so that their back is facing toward the direction of
removal. The benefits of moving the firefighter to a sitting position are:
• It reduces the member’s size in half, which will be beneficial in tight locations.
• It will allow full control over the distressed member. This will help prevent members
not assigned to the removal process from moving the distressed member prior to the
completion of the packaging.
• It will be easier to locate the Universal Air Connection.
• Allows easier access to the SCBA low pressure hose, facepiece and both shoulder and
waist straps.
79
FDNY Probationary Firefighter Manual
Chapter Six, Part II CONVERTING THE SCBA INTO A HARNESS
2.2 Rescuer 1 shall be positioned behind the distressed member. This firefighter places their
knee under the rubber bumper of the distressed member’s SCBA cylinder, allowing slack
in the distressed members SCBA shoulder straps. (Photo 6)
Rescuer 2
Rescuer 1
Photo 6
2.4 Rescuer 2 pulls on the yellow leg straps of the distressed member’s personal harness
creating a loop. This will allow rescuer 2 room when ready to feed the SCBA waist
buckle straps through the loops of the distressed member’s personal harness leg straps
and connect. (Photo 7)
Photo 7
80
FDNY Probationary Firefighter Manual
Chapter Six, Part II CONVERTING THE SCBA INTO A HARNESS
2.5 Rescuer 1 works their hands down the SCBA cylinder to the waist straps and depresses
the alligator clips that tighten the waist straps. (Photo 8)
Rescuer 1
Photo 8
2.6 Rescuer 2 grabs the connected SCBA waist buckle and fully extends the waist straps. (Photo 9)
Rescuer 2
Photo 9
2.7 Rescuer 2 disconnects the waist buckle and feeds the ends of the SCBA waist straps
through the loops created in the distressed member’s leg straps of their personal harness
and reconnects the waist straps. Do not tighten the waist straps at this time. (Photo 10)
Photo 10
81
FDNY Probationary Firefighter Manual
Chapter Six, Part II CONVERTING THE SCBA INTO A HARNESS
2.8 Rescuer 1 maintains the distressed member’s SCBA cylinder as high as possible creating
slack in all of the straps.
2.9 Rescuer 2 grabs the rappel hook from the personal harness of the distressed member and
pulls sharply to release the hook from the belt and opens the gate of the hook.
2.10 Rescuer 1 loosens the SCBA shoulder straps of the distressed member and brings them
both forward to allow Rescuer 2 to attach the distressed member’s personal harness hook.
2.11 Rescuer 2 places the open hook from the distressed member’s personal harness through
both of the member’s SCBA shoulder straps starting with the left strap first and then the
right strap. The rescuer is moving the hook from their right to the left. The hook is
attached in this manner so as to prevent twisting of the handle of the distressed member’s
personal harness. (Photo 11)
Rescuer 2
Rescuer 1
Photo 11
2.12 Once both of the distressed member’s SCBA shoulder straps are positioned inside the
hook of the personal harness hook, Rescuer 2 releases the gate of the hook. (Photo 12)
Photo 12
82
FDNY Probationary Firefighters Manual
Chapter Six, Part II CONVERTING THE SCBA INTO A HARNESS
2.13 Prior to tightening all of the distressed member’s SCBA straps, webbing should be placed
through the top end of the shoulder straps to make a girth hitch.
Note: Girth hitch procedures are outlined in sections 1.11.1, 1.11.2, 1.11.3 and 1.12.
2.14 Packaging the member in this manner (Photo 13) will allow for both a vertical or
horizontal removal.
(Photo 13)
83
FDNY Probationary Firefighters Manual
Chapter Six, Part II DRAG RESCUE DEVICE
1.1 The Drag Rescue Device (DRD) is designed to assist in the horizontal removal of a
non-ambulatory injured or unconscious member. The DRD has been integrated within the
bunker coat to comply with NFPA Standard 1971.
1.2 The DRD handle is located just under the collar on the back of the bunker coat and is
protected by a flap held in place by Velcro and two snaps. (Photo 1) There is a reflective
activation tab to assist in locating the DRD handle. (Photo 2)
Photo 1 Photo 2
2. OPERATION
2.1 The DRD can be deployed to assist in the horizontal removal of a non-ambulatory
injured or unconscious member. The DRD is designed for horizontal drag only. No
other application shall be attempted!
To Deploy:
• Locate and pull reflective activation tab which is connected to the DRD handle. (Photo 3)
This will deploy the DRD handle from underneath the protective flap. (Photo 4)
Photo 3 Photo 4
84
FDNY Probationary Firefighters Manual
Chapter Six, Part II DRAG RESCUE DEVICE
• Grasp and pull the DRD handle. When the DRD handle is pulled, the device is
designed to tighten around the member’s shoulders and chest, securing the member in their
bunker coat.
• The injured or unconscious member can now be securely dragged horizontally and will
not slip out of bunker coat.
NOTE: Any attempt to use the device for other than a horizontal drag could result in
the member slipping out of their bunker coat. In addition, serious injury
could occur to member’s upper torso. Members should not be dragged up stairs
utilizing the DRD.
85
FDNY Probationary Firefighters Manual
Chapter Six, Part II FF REMOVAL USING LARGE D-RING
FIREFIGHTER REMOVAL USING LARGE D-RING
1. INTRODUCTION
1.1 The distressed member packaging evolution is an efficient way to prepare a member for a
rapid removal. Packaging is accomplished by utilizing the members SCBA, personal
harness, the large D-ring of their Bunker coat, and their Drag Rescue Device (DRD).
2. PACKAGING
2.1 Place the distressed member in a sitting position and rotate them so that their back is
facing toward the direction of the removal prior to packaging.
Rescuer #1:
Rescuer #2:
Rescuer #2:
86
FDNY Probationary Firefighters Manual
Chapter Six, Part II FF REMOVAL USING LARGE D-RING
Rescuer #1:
Photo 3
Rescuer #1:
Photo 4
2.2 When the DRD handle is pulled, the device is designed to tighten around the member’s
shoulders and chest, securing the member in their bunker coat.
2.3 The distressed member can now be securely dragged horizontally and will not slip out of
the bunker coat or SCBA. This method can also be used to remove a member up or down
stairs.
87
FDNY Probationary Firefighters Manual
Chapter Six, Part II FF REMOVAL USING LARGE D-RING
3. MOVING
3.1 Once packaged, the distressed member can be securely moved in a number of ways:
B. Dragged horizontally by grasping the DRD with one hand and the distressed
members left shoulder strap with the other hand.
C. Carried horizontally, or up or down stairs with one rescuer grasping the DRD
only and a second rescuer grasping the leg-straps of the distressed member.
D. Carried horizontally, or up or down stairs with one rescuer grasping the DRD
with one hand and the distressed member’s left shoulder strap with the other,
while a second rescuer assists by grasping both leg straps of the distressed
member (Photo 5).
Photo 5
Note: It is essential that the DRD is wrapped once around the right shoulder strap
(over and under) of the distressed members SCBA before using any of these removal
methods. Failure to do so could result in the member slipping out of their bunker coat
or suffering serious injury to their upper torso.
88
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. UNIT
1. PURPOSE
The purpose of the Firefighter Assist and Search Team (FAST) is to be immediately
available to assist a member who becomes trapped, distressed or involved in other serious
life threatening situations. The FAST Unit must be ready to act immediately and
decisively when called upon.
2. NOTIFICATION
2.2 In some situations, a ladder company staffed with four firefighters may be assigned as a
FAST unit. When reporting to the ICP, the ladder company officer must inform the IC
that they are not fully staffed. The IC should take the staffing level of the FAST unit into
consideration upon deployment, and ensure adequate resources are assigned to assist if
necessary.
2.3 The FAST Unit should not be used for firefighting purposes. When an IC puts a FAST
Unit to work at an incident that has not been declared “Under Control,” immediate
notification shall be made to the dispatcher stating the reason for deploying the FAST
Unit and a request for an additional FAST Unit. Prior to the arrival of the replacement
FAST Unit, the IC shall designate a Safety Team.
3. POSITION
3.1 The FAST Unit shall report to and stage near the Incident Command Post (ICP), within
verbal contact, at a position from which they can be readily deployed. An Electronic
Fireground Accountability System (EFAS) trained member of the FAST Unit shall report
to a Battalion vehicle on scene to monitor the EFAS and the FAST Radio.
However, the IC may assign the FAST Unit to stage at a location other than the ICP,
based on the type of building units are operating, e.g. High Rise Office Building. Units
shall operate in accordance with established guidelines on FAST Unit staging at different
building types.
3.2 At large-scale, high-rise or unusual operations, additional FAST Units may be positioned
at other locations as determined by the IC.
89
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. UNIT
4. OFFICER RESPONSIBILITIES
The FAST officer is the most influential member of the FAST Unit. It is important for
the FAST officer to anticipate potential rescue situations as presented by the fire, the fire
building and the tactics implemented by operating units. In addition, the FAST officer
must:
• Constantly evaluate the progress of the operation.
• Continually monitor the location of operating units.
• Determine methods to identify, locate and remove a member in distress.
4.1 The officer of the FAST Unit shall announce their arrival on the scene over the handie-talkie
and report to the ICP, unless otherwise directed by the Incident Commander.
4.2 Upon arrival, the FAST officer shall verify that the IC is aware of the unit’s presence and
designation as FAST. If assigned by the IC to other than FAST duties, the FAST officer
shall REMIND the IC of their FAST designation.
4.3 When communicating to other units, the FAST officer and member’s radio designation
shall include the word FAST after the unit designation. Ex: “L-157-FAST to Command”
4.4 Communication between FAST Unit members does not require the use of the word FAST
after the unit designation. Ex: “Ladder 157 CAN to Ladder 157”
4.5 The FAST officer should bring an up to date copy of the response ticket to the ICP which
would include any CIDS information that is available.
4.6 The FAST officer shall get a briefing from the IC, and relay the information to the
members of the FAST Unit as to the following:
• Fire location
• Tactics implemented
• Location of operating units
4.7 The FAST officer should pre-plan possible rescue operations based on their size-up of
conditions and the location of operating units.
4.8 The IC or the FAST Group Supervisor shall coordinate a rescue plan with the FAST
officer prior to deploying the FAST Unit.
4.9 It is incumbent of the FAST officer to provide strong and decisive leadership when
dealing with a distressed member as well as providing for the safety of the FAST Unit.
90
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. UNIT
5. FAST UNIT RESPONSIBILITIES
All members of the FAST Unit should be fully prepared to operate upon arrival. The
FAST Unit must be ready for immediate deployment as directed by the IC.
5.1 The FAST Unit is responsible to know what additional equipment they are required to
bring to the ICP, in addition to their regularly assigned tools.
The following assignments must be given out at roll call:
• A member assigned the FAST Pak. Member is responsible to manage the air supply
of the distressed member, if needed.
• An EFAS trained member assigned to monitor EFAS and the FAST Radio.
If the member is EFAS trained, upon arrival, report to the Battalion vehicle being
used to monitor EFAS. This FAST Unit member shall remain in the Battalion
vehicle and monitor both EFAS and the Battalion's FAST Radio for the duration of
the incident, even if the FAST Unit is given an assignment.
If the member is not EFAS trained, upon arrival, report to a Battalion vehicle on
scene to monitor the FAST Radio Board. The member assigned the FAST Radio
shall remain in the Battalion vehicle and monitor the FAST Radio for the duration
of the incident, even if the FAST Unit is given an assignment.
Note: Whether EFAS trained or not, the FAST Unit member assigned to monitor
EFAS and/or the FAST Radio shall remain in the Battalion vehicle, even if
the FAST Unit is given an assignment, until relieved.
5.2 A survey of the fire building should be done to determine the following:
• Access for portable ladders.
• Presence of fire escapes and party wall balconies.
• Building built on a grade, setbacks and the depth of the building.
• Type and location of stairs and elevators.
• Determine if any remote or alternate access points are available.
• Obstructions that would hinder access to any side of the structure.
5.3 While staged, the FAST Unit should develop a plan of action. This plan of action should
include:
• Information gathered from the survey.
• Progress of fire operations and location of operating units.
• Expected paths of fire travel.
• Hazards posed by the type of construction, occupancy and type of incident.
5.4 Determine the availability and location of aerial, tower and portable ladders, in the event
there is a need to use and/or place into operation.
91
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. UNIT
_________________________________________________________________________________
5.5 Determine the availability of an Engine company to stretch a hoseline for protection.
6. SIZE UP
All firefighting operations should begin with a proper size-up. This is particularly important
in FAST Unit operations as well. The focus of a FAST Unit’s size-up will be slightly
different than normal since the FAST Unit will be performing a size-up for potential distress
duties, not just for fighting the fire. The 13-point size-up mentioned below must be evaluated
continually, along with anticipation of possible problems by the FAST Unit.
6.1 Construction
• As related to fire spread and collapse potential.
6.2 Occupancy
• Indicates what kind of fire spread can be anticipated and what kind of search may
have to be employed (search ropes, team search).
6.3 Area/Access
• Large areas will make for a more difficult search, unconfined fire and flashover
hazard that may not be apparent.
• What access routes are available to upper floors, cellars and roofs?
• Will there be a need for search ropes?
6.4 Life
• Consider the area where members are operating.
• Have they all been accounted for?
• What was their last known location/assignment?
6.5 Weather
• Will extremes in the weather affect the readiness of the FAST Unit and will it hamper the
rescue efforts?
92
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. UNIT
6.9 Exposures
• Can the exposures provide access to the fire area such by breaching walls?
• Do the exposures provide both access and egress from the roof?
• Is fire extending to the exposures that could endanger firefighters?
• Could the exposures become a secondary collapse hazard in the event of a collapse of the
fire building?
6.10 Apparatus/Equipment
• Is all of the required equipment at the ready?
• Are the first alarm ladder company’s apparatus in position for use?
• Is there a chauffeur at the turntable?
• Are the members of the FAST Unit familiar with the operation of the apparatus of the
first alarm units?
• Are portable ladders available?
• What other equipment may be needed and is it available.
6.11 Location
• What is the last known location of the trapped or distressed firefighter?
• Is the location of the fire known?
• Is the fire showing signs of extending to other floors, cockloft or exposures?
93
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. UNIT
6.12 Time
• How long has the fire been burning? The longer the fire is burning:
The greater the structural damage and chance of collapse.
The more fire gases are being pumped into the building.
Greater possibility of members suffering heat exhaustion.
Greater chance of auto exposure and extension to exposures.
7. OPERATIONS
When the FAST Unit is deployed for a distressed member, the fire conditions in the
immediate area of the rescue are likely to be severe. It is vital for the FAST Officer,
along with the FAST Unit to consider alternate access points to reach the trapped firefighter
7.2 When the FAST Unit operation requires the use of a ladder, avoid repositioning ladders
already in place against a fire building unless it is a life threatening situation and a
notification is made to the members operating in that area. Ladders in place may be
providing a means of egress for operating firefighters.
7.4 The FAST Unit shall remain intact and not split up when dealing with large commercial or
complex buildings.
94
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. UNIT
7.6 When the FAST Unit arrives at the location of the distressed member, the transmitting
member of the FAST Unit shall:
• Depress the Emergency Alert button (EAB) on their handie-talkie. This will identify the
member of the FAST Unit transmitting the emergency message on EFAS and the FAST
Radio. This will also ensure the message is transmitted at the maximum wattage.
• After the Emergency Alert activation, provide the IC or FAST Group Supervisor with the
information required for the emergency transmission as outlined in
Communications Manual Chapter 9. After all required information is given; the
transmitting member shall reset their handie-talkie Emergency Alert by depressing and
holding the Emergency Alert button for approximately 2 seconds.
• Assess Fire, Air, Immediate medical care, Removal (FAIR).
• Provide additional air supply as needed.
• Confirm positive identification.
• If possible, depress the EAB of the member in distress. The activation of the
distressed member’s EAB will identify them on EFAS. Notify the IC via handie-
talkie prior to EAB activation of the distressed member.
If unable to activate the distressed member’s EAB, key the mic on the distressed
member’s handie-talkie to obtain their identity on EFAS.
• The distressed member’s Emergency Alert shall remain activated until determined it is
no longer required.
• Package the member for removal.
8. TOOLS/EQUIPMENT
In addition to normally assigned ladder company tools, the FAST Unit shall report to the
ICP with the following equipment:
• FAST Pak.
• Search Rope.
• Stokes Basket with long backboard.
• 2:1 Rope
• Pak-Tracker
Note: A member other than the member monitoring EFAS will monitor the Pak-Tracker
95
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. UNIT
8.1 As part of the size-up, determine what other tools/equipment may be needed for the
various rescue possibilities such as:
• Rebar cutter.
• Life Saving Rope/Life Belt
• Saws
• Elevator keys for buildings with elevators.
• Flotation devices for operations on or near bodies of water.
9. TRAINING
Timely removal is imperative. The rescue will not only be difficult, but it will be one
that is emotionally charged. The way to overcome these obstacles is through constant
training in rescue procedures.
9.1 All units need to be proficient in proper search and radio procedures as well as the use of the
Thermal Imaging Camera, search rope, webbing and both power and hand tools.
9.2 Practicing packaging and removal techniques will greatly enhance a company’s ability to
rescue a distressed firefighter. To assist units in practicing these techniques, each Battalion has
been issued an Emergency Removal Training Kit.
96
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. PAK
F.A.S.T PAK
A I
B
C
2. DESCRIPTION
♦ Scott Air Cylinder (45 min)
♦ Low/High Pressure Assembly
♦ 5 ft. high pressure hose with Universal Air Coupling (UAC)
♦ 20 ft. low pressure hose attached to a manifold with Schrader fitting and Hansen fitting
♦ Non - CBRN Regulator and Facepiece
♦ Carrying Case
3. ADVANTAGES
♦ Lightweight, mobile, flexible air system
♦ Smaller profile / numerous air supply capabilities
♦ Ready for immediate deployment
♦ High pressure and low pressure systems can be operated simultaneously
97
FDNY
Probationary Firefighters Manual
Chapter Six, Part II
F.A.S.T. PAK
4. LIMITATIONS
4.1 The Fast Pak is not equipped with a vibra-alert or heads up display [Link] only way to
monitor the air pressure in the Fast Pak is the cylinder gauge. Therefore, it is essential that one
member of the FAST Unit is assigned to monitor the actual volume of air remaining in the
portable cylinder. This member must have audible communication with the extrication team.
Always start an operation with a full cylinder. Operational time of a SCBA resupplied by a Fast
Pak can vary depending on several factors. (eg., residual air in the distressed member's SCBA
cylinder, emotional/physical condition of distressed member.)
4.2 Every emergency situation is unique. The rescuer must be trained to assess each situation and
decide which re-supply method via the Fast Pak is best. This decision can vary depending on
several factors (e.g., position of the distressed member's body, condition of the distressed
member's SCBA). No single method is recommended for all situations.
5.1 This system permits emergency replenishment of an SCBA from an air supply source while
in use. This high pressure coupling will fit all UACs.*
5.2 The UAC is for emergency use only when a member is low or out of air within an IDLH
atmosphere.
5.3 The 5 ft. high pressure hose will administer air to a member’s SCBA via the UAC.
This will equalize air in both cylinders in approximately 60 seconds. The Fast Pak has a built
in check valve that only permits air to be delivered to a member’s SCBA.
5.4 To use the Fast Pak with a UAC system, proceed as follows:
5.4.1 Fully open the cylinder valve on the Fast Pak and remove the dust cap from the High
Pressure Coupling on the Fast Pak.
5.4.2 Identify the UAC on the member’s SCBA. Remove the dust cap from the UAC on the
member’s SCBA. (Figure 1)
Figure 1
98
FDNY
Probationary Firefighters Manual
Chapter Six, Part II
F.A.S.T. PAK
5.4.3 Verify that the cylinder valve on the member’s SCBA is fully open.
5.4.5 Air will immediately begin to flow from the Fast Pak cylinder to the member’s cylinder. The
air will stop flowing when the member’s SCBA cylinder and the Fast Pak air supply equalize.
When charging is complete, disconnect the UAC hose assembly.
5.4.6 Remove member from IDLH as soon as possible after charging is complete. If air
replenishment is needed again and time is of the essence, you can use the Fast Pak’s
remaining air. This will only result in marginally replenishing the member’s cylinder.
Both cylinders will equalize again, ½ in each cylinder.
99
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. PAK
6.4 Low pressure line may be used in one of the following four (4) modes:
1. Replace member’s regulator with Fast Pak’s regulator
a. Disconnect member’s regulator from facepiece.
b. Attach the Fast Pak regulator to the member's facepiece. Ensure that the regulator locks into
position.
c. During the initial inhalation, a click should be heard at the regulator assembly. This click indicates
the functioning and ON position of the manual shut off switch. If the member is unable to activate
the inhalation valve, turn the red purge valve downward, away from the face, to achieve a sufficient
flow. Rescuers must ensure the purge valve remains open. (This will cause a more rapid depletion of
air from the supply cylinder.)
2 Replace low pressure Hansen Fitting of member’s SCBA with the low pressure Hansen Fitting of the
Fast Pak.
a. Disconnect the Hansen fitting on the member’s low pressure hose below his regulator. Push the male
coupling in FIRST, then pull back sleeve to disengage coupling. (Figure 2)
b. Connect the low pressure hose from the member’s facepiece mounted regulator to the Hansen fitting
on the Fast Pak. Test for proper engagement. (Figure 3)
Figure 2 Figure 3
3. Replace member's facepiece with Fast Pak facepiece with regulator attached.
a. Remove member’s facepiece.
b. Place Fast Pak facepiece on member and make necessary adjustments to ensure a proper facepiece
seal.
c. During the initial inhalation, a click should be heard at the regulator assembly. Air will then flow
into the facepiece. If the member is unable to activate inhalation valve, turn the red purge valve
downward, away from the face, to achieve a sufficient airflow. Rescuers must assure the purge valve
remains open. (This will cause a more rapid depletion of air from the supply cylinder).
4. Schrader Connection
Use of the Schrader Fitting is reserved for the use of SOC units only.
Example: Supply emergency air to a Confined Space Mask carried only by SOC units.
100
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. PAK
7.1 The Fast Pak can also be used to provide an air supply to non FDNY members when:
The Fast Pak assigned to the FAST Unit shall not be deployed for this operation.
Additional Fast Paks shall be deployed if needed and victims should be removed from
an IDLH atmosphere as soon as conditions permit.
9. INSPECTION
9.1 Verify that the Fast Pak is properly cleaned and decontaminated.
9.2 Inspect the Fast Pak carrying bag for worn or damaged components.
9.3 Inspect cylinder and valve assembly for damage such as dents, gouges or discoloration of
the composite wrapping. Cylinders that show damage or exposure to high heat or flame
shall be removed from service and emptied. Attach RT-2 and return to MSU.
9.4 Turn on Fast Pak, listen for leaks throughout system.
9.5 Check the high and low pressure hose lines for cracks, cuts, abrasions or other signs of
damage.
9.6 Check all couplings for damage and cleanliness. Engage all couplings and make sure all are
working properly.
9.7 Check regulator as per Training Bulletin, Mask.
9.8 Check cylinder pressure gauge for “FULL” indication. If cylinder pressure is less than
“FULL” replace with a fully charged cylinder.
9.9 Inspect the cylinder coupling on the Fast Pak combination LOW/HIGH pressure assembly
to be certain the nipple seal is present and undamaged. If the gasket is present and
undamaged, align the coupling with the cylinder outlet.(Figure 4)
101
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. PAK
Figure 4
9.10 This equipment must be inspected at the beginning of each tour and after each use.
9.11 A Mask Record Card (Form SD-30) shall be filled out and maintained for each Fast Pak assigned to
a unit. Defects found must be included on the Mask Record Card.
10. NOTES
10.1 The designated FAST Unit shall report in at all incidents with the Fast Pak (See AUC 320)
10.2 Members using Fast Pak must be trained and be prepared to disconnect and reconnect couplings,
replace facepiece or regulator while wearing gloves. Members should be prepared to operate in zero
visibility, time being of extreme importance and in an IDLH area.
10.3 When Fast Pak use is anticipated, it should be turned on in a clean atmosphere and cylinder
pressure gauge checked for “FULL” indication.
10.4 Once a Fast Pak is put into operation, the I.C. shall ensure that a second Fast Pak is readily
available at the scene to be used as a required.
10.5 Keep all couplings dry at all times. Water on couplings may freeze during low temperatures
preventing connections.
102
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. Radio
1. FAST BOARD
1.1 The 8½” X 14” metal FAST Radio Board is equipped with leather strap and hand-holds
to act as a portable workstation. A mounted, metal clipboard container provides
compartments for waterproof FAST Radio Forms, pens, pencils and a copy of the daily
spare-radio sheet.
103
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. Radio
2.1 The FAST Radio Form is made of waterproof paper and has a printed design to facilitate
obtaining and documenting the internal radio codes. Each packet has 25 copies of the
FAST Radio Form. The Form can be filled out with either pen or pencil, but pencil is
superior, especially in wet weather. The member assigned to monitor the FAST Radio
shall record the internal radio codes of emergency transmissions in the boxes provided.
White space can be used for notes pertaining to the operation. When necessary, the
FAST Radio Form can be torn off and given to the Incident Commander.
104
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. Radio
3. PROCEDURE
3.1 One member of the FAST Unit shall report to a Battalion vehicle on scene to monitor the
FAST Radio Board. The member assigned the FAST Radio shall remain in the Battalion
vehicle and monitor the FAST Radio for the duration of the incident, even if the FAST
Unit is given an assignment. Member shall monitor for:
• Mayday/Urgent transmissions
• Members in distress
Note: If the member is EFAS trained, upon arrival, report to the Battalion vehicle being
used to monitor EFAS. This FAST Unit member will then monitor both EFAS and the
Battalion’s FAST Radio for the duration of the incident, even if the FAST Unit is
given an assignment.
3.2 When a Mayday/Urgent has been transmitted, the FAST Radio member shall record the
Radio ID number immediately on to the FAST Radio Form.
3.3 When necessary the Radio Designation Chart can be referred to for the member’s
assigned position.
105
FDNY Probationary Firefighters Manual
Chapter Six, Part II F.A.S.T. Radio
4. RADIO DESIGNATION CHART
4.1 The Radio Designation Chart will show the member’s assigned position based on the
internal radio codes.
106
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
PAK - TRACKER
1. INTRODUCTION
1.1 The Pak-Tracker Firefighter Locator System is a distress alarm system designed to help
identify and locate members in distress. The system consists of two components.
The first is a personal transmitter embedded in each SCBA. The second is a handheld
receiver (Photo 1) that is capable of receiving a signal from any SCBA in the full-alarm
mode.
The Pak-Tracker system serves a dual purpose: The first is its monitoring/identification
capability, and the second is its tracking capability. It is essential for members to
understand that the Pak-Tracker receiver is a valuable monitoring/identification tool,
serving as an early-warning device and providing a distressed member’s identity. In this
regard, the Pak-Tracker provides the Department with another valuable identification
tool, along with the Electronic Fireground Accountability System (EFAS) and the FAST
handie-talkie. In addition, the handheld receiver can also be used as a tracking device in
order to guide firefighters to the location of a distressed member.
2. SENSITIVITY DISTANCE
2.1 The maximum range from an SCBA’s transmitter to a Pak-Tracker handheld receiver is
approximately 900 feet line of sight. The range is dependent on the environmental
conditions and anything that might cause interference or reflection of the personal
transmitter signal.
3.1 The Pak-Tracker handheld receiver is not suitable for use in potentially flammable or
explosive atmospheres. Always check for the presence of a flammable or explosive
atmosphere before entering an unknown environment with the Pak-Tracker.
107
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
B D
E
F
C
Photo 1
108
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
4.1. Pak-Trackers are currently carried by all ladder, rescue and squad companies.
Pak-Trackers shall be brought to the Incident Command Post (ICP) by the FAST unit,
rescue and squad companies. A member of the FAST unit will monitor the Pak-Tracker.
The rescue and squad Pak-Tracker’s will remain at the command post as a backup should
the FAST unit be deployed.
4.1.1 Unlike EFAS, the Pak-Tracker does not possess the ability to be updated when a
spare mask is put in service. For this reason, Battalions shall print out a current
copy of the Spare Mask Assignment List at the start of each tour and keep a copy
on the FAST radio board. This can be done as follows:
• Select “SCBA Spare Mask List” from the “Applications” dropdown menu on
the FDNY Intranet homepage.
4.2 Upon arrival at the scene, the FAST unit shall report in to the ICP with their assigned
Pak-Tracker and bring it to their assigned position. A member of the FAST unit other
than the member monitoring EFAS shall monitor the Pak-Tracker. This specific Pak-
Tracker must remain in the monitoring mode near the FAST unit’s assigned
position; this allows the Pak-tracker to capture both the initial and subsequent PASS
alarm activations and ensures continuous monitoring for distress signals.
4.3 When the Pak-Tracker receives an alarm signal, the FAST member monitoring the Pak-
Tracker shall immediately notify their company officer with the identity on the LCD
display (i.e., the member’s unit and assignment). The FAST unit officer shall notify the
IC of the activation, and attempt to contact the member to determine whether the signal is
for an emergency or an inadvertent activation. If the PASS activation is for a life-
threatening emergency, or if no contact can be established, the FAST unit officer shall
immediately notify the IC with a “mayday” transmission” as per Communications
Manual, Chapter 9, and units shall operate as per Department policy in Firefighting
Procedures, Managing Incidents Involving Members in Distress.
4.4 When the IC decides to utilize the “tracking” capability of the Pak-Tracker, the Pak-
Trackers left at the command post by rescue and squad can be used immediately for their
monitoring and identification capability. The IC shall designate an available member to
monitor the Pak-Tracker until the designation of a new FAST unit.
109
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
4.5 At building collapses where members may be trapped beneath debris, a Pak-Tracker may
be used from a tower ladder bucket to help identify and locate trapped members.
Because of a signal’s tendency to pass through holes, voids, and gaps, this tactic could
allow members to determine where to begin searching when units are unsure of a trapped
member’s location. For example, a member using a Pak-Tracker from a high vantage
point in a tower ladder bucket could transmit a handie-talkie message to units on the
ground stating, “The Pak-Tracker is receiving a strong signal from Ladder 36 Can in the
two-three corner of the debris pile.” Units on the ground could then begin selected-
debris-removal operations in that area.
5.1 To turn on the Pak-Tracker receiver, press and hold both the “Enter” (right) and the
“Scroll” (left) buttons at the same time (Photo 2). The signal-strength indicator will
light, and the display will show a “power-up” message.
Photo 2
5.2 When the Pak-Tracker receives a signal from a PASS device that has been in full-alarm for
10 seconds, the receiver will emit a 2-tone audible alarm, and the LCD display will show
the SCBA’s identity (unit and member assignment) and relative signal strength (Photo 3).
Photo 3
This indicates Ladder 110 Irons SCBA. “95” represents the relative strength of the signal.
110
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
5.3 While the Pak-Tracker can receive and store up to 36 SCBA identities, the LCD display
screen is only large enough to display two lines of information. The limitations of the
screen will have the following effects:
• When two PASS Alarms are activated at the same time, both SCBA identities are
displayed on the LCD screen.
• When more than two PASS alarms are activated, downward pointing arrows are
displayed on the LCD. The left “Scroll” button can then be used to view and cycle
through all SCBA identities that have been transmitted. In order to use the scroll
feature, press and hold the “Scroll” button for three seconds. After three seconds,
the identities will begin to scroll on the LCD display. When the desired identity
appears in the top row of the LCD display, release the “Scroll” button.
5.4 After an identity appears on the LCD display, a Pak-Tracker receiver can then be locked
onto the PASS signal of an individual SCBA and used as a tracking device to find a
member in distress. It is important to understand that a Pak-Tracker receiver can only
lock onto one SCBA at a time. Once a Pak-Tracker has locked onto the signal of one
specific PASS alarm, it no longer has the ability to receive any additional PASS alarm
signals. A Pak-Tracker is also capable of being unlocked (i.e., returned to “monitoring”
mode), in order to monitor for additional transmitting signals, by pressing and holding the
“Scroll” button for three seconds.
5.5 A signal from an activated PASS alarm may be evident at a greater distance than the
audible PASS alarm. It is important to be aware of this fact, because the monitoring
member may receive a signal on the Pak-Tracker without actually hearing the distressed
member’s audible PASS alarm - the Pak-Tracker may serve as the first and only
indication of an emergency in cases when a member is incapacitated and unable to
transmit a verbal mayday.
6. OPERATIONS - IDENTIFICATION
6.1 When an SCBA’s PASS alarm is activated in the full-alarm mode for ten seconds, the
PASS alarm transmits a signal that can be received by the Pak-Tracker handheld receiver.
When this occurs, the Pak-Tracker receiver will emit a 2-tone audible alarm and display
the identity (unit and member assignment) of the SCBA.
Note: A ten-second time lag is built into the system in order to minimize inadvertent
activations.
6.2 Having a unit monitor a Pak-Tracker serves as a critical safety measure at fires and
emergencies. In this capacity, the Pak-Tracker serves as an early-warning detection
device that may indicate that an operating member is in distress. In cases when a
member is incapacitated or unable to transmit a verbal mayday (e.g., an unconscious
member), it is even possible for a Pak-Tracker activation to serve as the only indication
of an emergency.
111
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
7. OPERATIONS - TRACKING
7.1 Understanding how the transmitting signal from an SCBA PASS device behaves and how
the Pak-Tracker handheld receiver displays the strength of a signal are critical to
understanding the operation of the Pak-Tracker locator system. Successful operation of
the Pak-Tracker depends heavily on the interpretation of the relative signal strength
displayed on the Pak-Tracker, along with all other available information about the
possible location of the distressed member.
7.2 The relative signal strength displayed on the Pak-Tracker’s LCD display screen will vary
depending on:
• Distance from the SCBA to the Pak-Tracker.
• Path the SCBA signal takes to get to the Pak-Tracker.
• Materials affecting the signal between the SCBA and the Pak-Tracker.
• Orientation of the hand-held receiver.
Note: The Pak-Tracker is very sensitive in responding to small differences in signal
strength.
7.3 The user of the Pak-Tracker must interpret the readings on the display along with other
information, such as:
• Training and knowledge in systematic search and rescue techniques.
• Their sense of sight (look where you are going).
• Their sense of sound (listen for an activated PASS device).
• The assignment of the missing member.
• Knowledge of the building layout and building materials.
• Any other pertinent information available on the scene.
7.4 When the Pak-Tracker receives an activated PASS alarm signal from an SCBA, it will
sound a two-tone alarm. To lock onto a signal in order to begin tracking a distressed
member’s location, press the “Enter” button once. The LCD display will show that the
Pak-Tracker has entered the “searching” mode. If two or more SCBA PASS alarms are
transmitting, press and hold the “Scroll” button for three seconds, and continue to hold it
until the activated PASS alarm you want to track appears in the top row of the LCD
display. To lock onto a selected SCBA: release the “Scroll” button, and press the “Enter”
button once.
Note: The “Enter” button is a momentary-touch button; the “Scroll” button must be
continuously held down. This concept is similar to the door-control buttons used in
elevator operations.
112
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
7.5 To unlock from one SCBA in order to switch to another (to change which SCBA to
track), press and hold the “Scroll” button for three seconds, and continue to hold it until
the desired SCBA PASS appears in the top row of the LCD display. Release the “Scroll”
button and press the “Enter” button once to select the activated PASS alarm to track.
7.6 To begin searching, the Pak-Tracker should be held at waist height out in front of the
operating member- the top of the hand-held receiver should be pointed toward the target
(Photo 4). This is important because the hand-held receiver’s sensor captures the distress
signal from the top of the unit, and the relative signal strength will be greatly affected by
the orientation of the hand-held receiver.
Photo 4
During a search, the row of LEDs and the numerical signal strength shown on the LCD
display indicate the relative strength and approximate direction of the signal from the
SCBA. Pointing the Pak-Tracker in the direction of the strongest relative signal and
moving in that direction should lead to the activated SCBA. When the signal strength
rises above the 50-percent level, the row of LEDs will begin to light starting with red at
the bottom, yellow in the middle, and green at the top.
7.7 The Pak-Tracker receiver averages four readings per second. When there are features
such as doors, hallways, openings, or windows, take readings at each feature to determine
where the strongest signal is coming from.
7.8 Use the Pak-Tracker in a sweeping motion, very slowly in a horizontal direction first.
Sweep vertically if the signal may be coming from a higher or lower floor in the building.
7.9 Always pause 3 to 4 seconds for a reading. It is best to pause at distinct directional
points, (i.e. to the left, in front, to the right). Sweeping too quickly may average a high
reading with a low reading resulting in misleading information. Always move toward the
highest relative signal strength displayed. In general, the closer you get to the SCBA, the
higher the relative signal strength. Multiple signal paths are possible. The relative signal
strength must be interpreted with all other available information.
113
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
7.10 An SCBA signal will pass through some materials, but will not penetrate through other
materials.
The signal from the SCBA to the Pak-Tracker will usually pass through:
• Glass
• Light building materials
• Openings such as gaps, holes, stairways, windows, or elevator shafts
• Wood
7.11 When an SCBA is transmitting a signal and the Pak-Tracker responds, assess the
situation first to determine the safest method to approach the search and rescue operation.
7.12 The member operating the Pak-Tracker must be at the front of the search team to prevent
signal interference caused by other members being in the way. The transmitter signal
will be absorbed by the human body. The other members of the search team must
maintain situational awareness and provide for the safety of the member operating the
Pak-Tracker.
7.13 Follow this search-and-rescue process with the Pak-Tracker locator system:
• READ - Hold the Pak-Tracker pointed at features such as doors, windows, or halls. Look
for the highest relative signal strength as shown on the display screen.
• INTERPRET - Decide where the strongest signal appears to be coming from and how
best to get there.
• FOLLOW - Move toward the strongest signal while continuing to READ, INTERPRET,
and FOLLOW.
7.14 To locate an activated SCBA in a building from the street, point the Pak-Tracker at
windows and doors to locate the maximum relative signal on the display.
7.15 The Pak-Tracker locator system is highly dependent on the interpretation of the relative
signal strength information displayed on the Pak-Tracker, along with all other available
information about the possible location of the activated SCBA.
7.16 Continued training and practice in a variety of situations is essential in order to develop
the skills necessary to properly interpret the information provided by the Pak-Tracker
locator system.
114
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
8. INSPECTION
8.1 Inspect and test the Pak-Tracker locator system before each use and at the start of each
tour. If any malfunction of the Pak-Tracker locator system is noted during the inspection,
place the device out of service, attach an RT-2 indicating the problem and contact MSU
for replacement. Each Division has been issued a spare Pak-Tracker. The company shall
contact the Division for a spare while awaiting replacement from MSU.
Note: If this inspection is done in direct sunlight it may be necessary to shade the display
on the hand-held receiver to be sure the display lights are flashing as described.
1. Visually inspect entire Pak-Tracker body, battery compartment cover, and display
for cracks or other damage.
2. Check the optional Pak-Tracker strap handle for weakness.
3. Verify that all fasteners and mounting hardware are present and tight.
4. Check all battery contacts. The contacts must be clean and straight.
5. Verify that a fully-charged battery is properly installed. Refer to the battery
charging and battery installation sections of this manual.
6. Turn on the Pak-Tracker by pressing both the “Enter” and “Scroll” buttons
simultaneously. Verify that the unit powers up and all lights and displays operate
properly.
7. Battery Life - When the battery in the Pak-Tracker has approximately 20 percent
of its life remaining, the “Low Batt” indicator light will glow yellow. If the “Low
Batt” indicator lights at any time during the regular operational inspection, replace
the battery pack with a fully charged battery pack before proceeding with the
inspection. See the battery charging and battery installation sections in this
bulletin. After the “Low Batt” indicator light appears, the Pak-Tracker will
operate for approximately one hour. If the battery is not changed in that time, the
Pak-Tracker will shut down and will not operate until a fully charged battery is
installed.
8.2 When any damage is found, remove the unit from service.
9.1 Power for the Pak-Tracker is provided by a rechargeable Nickel-Metal Hydride (Ni-MH)
battery pack. The battery pack must be fully charged before placing the Pak-Tracker in
service. If the battery or battery charger does not operate as described in these
instructions, remove it from service and forward it to the Mask Service Unit by attaching
an RT-2 for repair or replacement.
Note: Defective batteries that are placed out of service for any reason shall be forwarded
to MSU for disposal. Do not dispose of damaged batteries as ordinary trash.
9.2 Plug the charger’s power-supply cord into the charger base. When the charger is
connected to a power source, the charging LED will flash once in RED, ORANGE and
GREEN -in that order. The charging LED indicator will then go off.
115
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
9.3 Identify the location of the three battery contacts on the square end of the Battery Pack.
Verify that they are clean and not damaged. If there is any evidence of damage, do not
use the Battery Pack. Refer to the Maintenance section of this bulletin.
9.4 The Battery pack only fits in the charger one way. Orient the battery with the ridge side
up and the triangular side of the Battery Pack down with the pull tab out.
9.5 Slide the Battery Pack into the charger until the pull tab end seats in the bracket on the
front of the charger. The light on the right will flash GREEN while the battery is
charging.
9.6 When the battery is fully charged, the light will change to solid GREEN. Battery will
require approximately 2 hours charging prior to initial use. After each use of the Pak-
Tracker, the battery should be recharged until the light turns solid GREEN.
9.7 Batteries shall be recharged on a regular basis such as once a week to maintain a full
charge ready for use.
9.8 If the light in the charger base glows YELLOW, it indicates that the charger is in
STANDBY mode.
9.9 If the light on the charger base FLASHES RED as soon as a battery is placed in the
charger, it indicates a defect in the battery. Remove the battery from service and dispose
of according to federal, state, and local regulations. Do not throw away damaged
batteries as ordinary trash.
10.1.2 Inspect the Battery Pack before installing. Verify that there is no damage to the
outer plastic cover and that the contacts are clean and not damaged. If there is
any evidence of damage, do not use the Battery Pack.
10.1.3 Remove the threaded cover from the bottom of the PAK-TRACKER handle by
turning it counterclockwise.
10.1.4 The Rechargeable Battery Pack is triangular with a ridge on one side and will fit
into the handle only one way. Hold the Battery Pack by the end with the pull tab
and slide the contact end into the handle. There is an arrow under the pull tab
indicating the top side of the battery. If properly oriented, the Battery Pack will
slide easily into the handle. If oriented wrong, the pack will not fit into the
handle. Do not force the battery into the receiver. Be careful not to press any
buttons on the Pak-Tracker while inserting the battery.
116
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
10.1.5 Thread the cover clockwise onto the end of the handle. Turn the cover until it
stops. The sides of the cover will align with the sides of the handle.
10.1.6 Test the operation of the handheld receiver according to the regular operational
inspection section of this manual.
Note: The handheld receiver will not operate if the battery is not properly installed.
If the hand held receiver does not operate, or if the battery cover does not fit as
described, verify that the battery is properly oriented.
11. CLEANING
11.1 The components of the Pak-Tracker are factory sealed to protect the electronics from dirt
and moisture. The unit should be cleaned when necessary using a cloth dampened with a
solution of mild detergent and water. Wash the hand strap in a solution of mild detergent
and water and dry thoroughly before re-attaching. DO NOT IMMERSE, SPRAY, OR
DOUSE THE PAK-TRACKER IN LIQUIDS.
11.2 After cleaning, perform a regular operational inspection of the equipment.
11.3 Inspect the charger according to the instructions provided with the chargers. If any
damage is found, remove the equipment from service and tag for repair or replacement.
11.4 Regularly verify that the batteries are fully charged so that the equipment is ready for use.
12. STORAGE
12.1 All components of the Pak-Tracker Locator System must be completely dry before storage.
12.2 Store the Pak-Tracker in its carrying case.
12.3 When storing the Pak-Tracker for an extended period of time, remove the battery pack to
prevent damage to the battery terminals.
13.1 Companies shall utilize the Pak-Tracker at multi-unit drills to verify that assigned and
spare SCBAs are correctly identified and match the Spare Mask Assignment List.
14. TRAINING
14.1 A Pak-Tracker training kit has been issued to each division. Divisions will be
responsible for scheduling training within their commands and providing accountability
for the equipment. In order to obtain the division training kit, company officers can
contact their respective divisions.
The training kit will include:
• Pak-Tracker with battery
• Battery charger
• Carrying case
• PASS simulator (a transmitting device to be used in place of a company SCBA)
117
FDNY Probationary Firefighters Manual
Chapter Six, Part II PAK-TRACKER
15. PAK-TRACKER PROGRAMMING
15.1 The Pak-Tracker system contains a programming limitation that members must be aware of
in order to ensure accurate SCBA identification in emergency situations.
15.3 When a PASS device goes into the full-alarm mode for ten seconds, a digital
identification signal is transmitted from the PASS device and can be received by the
Pak-Tracker handheld receiver. SCBAs are numbered and programmed identically to
handie-talkie radio positions.
* Each rescue and squad company is issued two company spare SCBAs, which are
numbered 7 & 8.
118
FDNY Probationary Firefighters Manual
Chapter Six, Part II SAFETY TEAM (2 IN/2 OUT)
1. POLICY
1.1 The United States Department of Labor Occupational Safety and Health Administration’s
(OSHA) revised standard regarding respiratory protection states: Where an employer
does not know or cannot reasonably estimate the concentration of contaminants in the
work environment, it is assumed that the atmosphere is Immediately Dangerous to Life
and Health (IDLH).
1.2 When a fire progresses past the incipient stage, the fire area must be considered an IDLH
atmosphere. Every member entering the IDLH atmosphere must be equipped with
personal protective equipment and a self-contained breathing apparatus. No member
shall enter, leave or operate in an IDLH atmosphere unless the member teams-up with at
least one other member and remains within visual or voice contact with that member.
Each member of the search team shall know the company identity and assigned position
of the other members of the search team. Handie-talkies or other electronic
communication devices are not acceptable to replace visual or voice contact. At least one
of the members of the team within the IDLH must have a handie-talkie and must be able
to contact a handie-talkie-equipped member of the Safety Team outside of the IDLH
atmosphere.
1.3 At least two members must team up prior to entering an IDLH (Two-In) and there must
be at least two other members outside the IDLH (Two-Out), who are designated as a
Safety Team. The members of the Safety Team shall be available to assist the interior
team(s) if the need arises. If a member leaves a contaminated area, another member
using an SCBA must accompany this member to a safe area.
1.4 If a known life hazard is discovered and immediate action could prevent the loss of life,
appropriate action (rescue activity) may be taken by an individual member. This applies
only for a known life hazard, not for standard search and rescue activity. A known life
hazard is defined as follows:
• A victim can be seen by the rescuer.
• A victim can be heard by the rescuer.
• A member has information from a credible source or a person at the scene indicating
the location of the life hazard.
If such action is taken, the Incident Commander must be immediately notified and
appropriate adjustments made.
Note: In all incidents of such individual action, the Incident Commander shall forward a
report detailing the full particulars to the Chief of Operations. A thorough review of each
of these incidents will be conducted.
119
FDNY Probationary Firefighters Manual
Chapter Six, Part II SAFETY TEAM (2 IN/2 OUT)
2. PROCEDURES
2.1 A Safety Team must be available at all times. The FAST Unit will serve as the Safety
Team. Prior to the arrival of the Fast Unit, the following guidelines should be followed
to establish the Safety Team:
2.1.1 The Safety Team shall normally be made up of the Backup and Control
firefighters of the second arriving engine. However, there will be times when
entry into an IDLH atmosphere is necessary prior to the arrival of the first two
engine companies. The following guidelines shall be followed in these instances:
♦ One 4 Firefighter Engine on Scene:
Based on the officer's size up the following options can be considered:
1) The officer and one firefighter enter the IDLH for search without line
advancement while two firefighters compose the Safety Team.
2) Take a defensive position based on conditions encountered.
2.2 The arrival of the 2nd Engine must be announced over the handie talkie.
2.3 Designated members of the Safety Team are to engage in their primary duties while
assuming the duties of the Safety Team. Once firefighters enter the IDLH, one member
of the Safety Team must account for firefighters inside the IDLH without performing
other duties.
2.4 In unusual situations, the Incident Commander may vary the make-up of the Safety
Team. An understanding of the intent of the FDNY POLICY/OSHA RESPIRATORY
STANDARDS, along with knowledge of current Department SOPs, will allow for an
efficient operation with minimal adjustments to our SOPs as currently written.
3.1 The Safety Team shall be positioned outside the IDLH atmosphere and:
♦ Monitor handie-talkie transmissions for calls for assistance from members operating
in an IDLH atmosphere, mayday, or urgent transmissions, and transmissions from
interior teams that are not being acknowledged.
♦ Be prepared to enter the IDLH atmosphere to render assistance if required.
♦ Be prepared to transmit necessary mayday or urgent handie-talkie message if an
interior team needs immediate assistance.
♦ Ensure that the Incident Commander is notified that the Safety Team is entering the
IDLH atmosphere if necessary.
3.2 The Incident Commander shall announce the FAST unit’s arrival over the handie-
talkie at the scene. On receipt of this announcement, the members performing the duties
of the Safety Team shall return to their original assignments.
4. TEAMING UP
4.1 When members are teamed up, they must contact their company officer before entering
an IDLH atmosphere and advise such officer of their status at frequent intervals,
especially when attempting tasks not normally associated with their assignments.
4.2 In unusual situations where members assigned to team up are unable to do so, the
Incident Commander shall be notified prior to entry into the IDLH atmosphere and the
Incident Commander shall make necessary adjustments in the teaming up of members.
121
FDNY Probationary Firefighters Manual
Chapter Six, Part II SAFETY TEAM (2 IN/2 OUT)
5. REFERENCE CHART
122
THIS PAGE WAS INTENTIONALLY LEFT BLANK
123
Probationary Firefighters Manual
Chapter 7
COMMUNICATIONS
7
PART ONE
SECTION TITLE PAGE
1 INTRODUCTION .....................................................................................1
2 SUPERVISION ........................................................................................1
9 HT UTILIZATION WITH
PART TWO 33
PART THREE 41
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
1. INTRODUCTION
The following procedures for handie talkie (HT) use are established to achieve greater safety,
effectiveness and efficiency at fire operations.
1.1 Company Officers have many tasks at fire operations. They must report conditions to the
INCIDENT COMMANDER, carry out orders received and control the individual members of their
units so that necessary actions are performed and the safety of members under their command is
monitored. HT communications play a vital role in all of these.
2 SUPERVISION
An Officer's span of control must allow for supervision of the actions of members under their
command in all situations.
B. They are working with a search line or hose line which is under the supervision of
an Officer.
2.2 Members are under the "Functional Supervision" of an Officer when they are HT
equipped or working with a HT equipped member and are in compliance with the
following:
A. Members assigned to tasks which are not under the "Immediate Supervision" of
their Company Officer must contact such Officer before entering a dangerous area
and advise such Officer of their status at frequent intervals, especially when
attempting tasks not normally associated with their assignment.
B. If contact cannot be made with their Company Officer, they shall contact (in this
priority) their Company Chauffeur, the INCIDENT COMMANDER or any other HT
equipped member advising such member that contact cannot be made with their
Officer. Any of the foregoing who are so contacted must advise the member’s
Officer as soon as possible.
C. Members operating alone who team up with other members shall advise their
Company Officer. If they separate, notification should again be made.
2.3 When operations are conducted in an area where the ambient noise level interferes with
HT communications, provisions must be made to ensure effective communications.
3 INTER-UNIT COMMUNICATION
The importance of communications between units and the INCIDENT COMMANDER cannot be
overemphasized. Conditions found and actions taken or contemplated must be continually
reported. However, discretion must be used. Information of a routine nature should be communicated to
Company Officer, while more serious information should go directly to the INCIDENT COMMANDER.
3.1 The Officer who arrives first at the fire area must transmit the following information to
the INCIDENT COMMANDER:
A. Location of the fire. (If a multiple dwelling, report the number of apartments on
fire floor.)
B. Fire conditions.
C. Access to fire area.
D. Whether fire is extending and how it is extending and the need for additional
lines.
E. Difficulties or delays in gaining entrance to fire area or in advancing line. Give
reasons.
F. If any occupants have been located or are reported missing.
3.2 Members operating on the roof must communicate to the INCIDENT COMMANDER the
following:
A. The configuration of the building.
B. Fire showing out windows not visible from the street and whether any exposure is
affected.
C. Color and volume of smoke coming from windows.
D. Persons trapped and their exact location.
E. Location of stairways, fire escapes and party wall balconies. Unusual information
affecting safety, for example, a fire escape on the rear of a brownstone.
F. If the building fronts on more than one street, and whether there is access for
apparatus or equipment.
G. Whether there is any difference in the height of the building from front to rear or
from side to side.
H. Evidence of unusual heat, smoke or fire in the cockloft, or if fire has burned
through roof. Need for additional saws.
I. Location of parapet and dividing walls.
J. Presence of heating ducts, ventilation ducts, air conditioning units and water tanks
on roof.
2
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
The following transmissions are to be used with discretion. The terms "MAYDAY" and
"URGENT" must only be used as is indicated herein. They are intended for use in
situations where immediate communication is necessary to protect life or prevent injury.
Whenever the Emergency Alert Button has been pressed, and/or a MAYDAY or URGENT is
transmitted, all HT communications on that frequency are to cease, except those between the
member initiating the emergency transmission and the IC. If possible, the member
transmitting the MAYDAY or URGENT shall begin, by pressing the Emergency Alert
Button, ensuring the message gets transmitted at maximum wattage and repeating
"MAYDAY" or "URGENT" three times followed by the remainder of the message. Normal
HT use may be resumed upon completion of the emergency message or signal unless the
IC orders otherwise.
NOTE:
1 Anytime a building or area is evacuated, units shall account for all members in
preparation for a Roll Call. Missing members are to be reported immediately.
2 "MAYDAY" transmissions have priority over "URGENT" transmissions.
3 To minimize misunderstanding, the terminology used below is mandatory. All
members must be completely familiar with the terminology and use it exclusively
for its intended purpose. No other wording is to be used for emergency
transmissions. The term "COLLAPSE" is to be used to indicate STRUCTURAL
FAILURE only.
3
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
4.1 MAYDAY
This transmission is an indication that a life-threatening situation has developed. If
possible, the member shall press the Emergency Alert Button ensuring that the
message gets transmitted at maximum wattage before giving their MAYDAY
message. After message is acknowledged, the member can deactivate the
Emergency Alert Tone if the “Beacon” tone is no longer required. The term
MAYDAY may be used only in the following five situations:
Note: The IC may instruct the member transmitting the emergency message to switch to
channel 16, the dedicated 5-watt emergency channel. The IC may do this to free up the
primary tactical channel and have communications continue with the member at 5
watts. When a member switches to Channel 16, their "Beacon" continues unless the
"Emergency Alert Tone" is deactivated. The IC may instruct the member to
deactivate the tones if they are hampering communications.
A. Collapse Imminent
6. The IC shall notify all units when the MAYDAY has been resolved
and that normal operations may resume.
4
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
1. A member aware of the condition shall immediately press their Emergency Alert
Button, and then contact the IC in the following format:
"MAYDAY-MAYDAY-MAYDAY, Ladder 44 OV to Command, MAYDAY."
3. The member transmitting the MAYDAY shall respond in the following format:
"Ladder 44 OV to Command, MAYDAY - COLLAPSE HAS OCCURRED" and
provide the following information:
• Location and extent of collapse
• Number and nature of injuries
• If anyone is trapped.
4. The IC shall immediately assign specific units to assist at the location of the collapse
and simultaneously ensure a roll call is conducted immediately and all members are
accounted for.
5. The IC shall notify all units when the MAYDAY has been resolved and that normal
operations may resume.
3. The member transmitting the MAYDAY shall respond in the following format:
• Location
• Resources needed
5
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
4. The IC shall assign specific units to assist with the injured member.
5. The IC shall notify all units when the MAYDAY has been resolved
and that normal operations may resume.
D Missing Member
4. The IC shall assign specific units to conduct a search for the missing
member and contact units on-scene by HT to attempt to locate the
missing member.
5. A member who locates a missing member shall immediately press
their Emergency Alert Button, and then contact the IC in the
following format:
“MAYDAY-MAYDAY-MAYDAY, Ladder 43 FAST OV to
command, MAYDAY.”
6
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
7. The IC shall notify all units when the MAYDAY has been resolved
and that normal operations may resume.
E. Lost or Trapped
7
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
Note: The term "URGENT" shall not be used for any of the above situations; these
situations are sufficiently serious to warrant "MAYDAY” transmissions.
8
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
4.2 URGENT
This transmission is used to indicate that a member has suffered a serious injury
that is not immediately life threatening, or to inform members of a serious change in
conditions. If possible, the member shall press the Emergency Alert Button
ensuring that the message gets transmitted at maximum wattage before giving their
URGENT message. After message is acknowledged, the member can deactivate the
Emergency Alert Tone if the "Beacon" tone is no longer required.
Note: The IC may instruct the member transmitting the emergency message to switch to
channel 16, the dedicated 5-watt emergency channel. The IC may do this to free up the
primary tactical channel and have communications continue with the member at 5
watts. When the member switches to Channel 16, their "Beacon" continues unless
the Emergency Alert Tone is deactivated. The IC may instruct the member to
deactivate the tones if they are hampering communications.
Examples of situations when the term URGENT may be used include the
following:
9
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
5. The IC shall announce over the HT when a positive water source has
been attained. The IC shall also inform the Borough Dispatcher that a
positive water source has been attained.
3. The IC shall then ensure a roll call is conducted immediately and all
members are accounted for.
10
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
D. Danger of Collapse
11
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
F. Loss of Water
4. The IC shall contact by HT, all of the units affected by the water
loss and units operating in positions above the water loss to ensure
they are aware of the problem. If necessary, the IC shall back units out
of exposed areas, assign specific units to assist in removal of these
units, and conduct a roll call to account for all members.
5.1 The Emergency Alert Tone Assisted Rescue can be utilized to home in on the
location of missing, lost, or trapped members e.g., a collapse situation. This procedure
takes advantage of the increased wattage of the Emergency Alert Tone and
maximum volume output regardless of the missing member’s volume setting, and
requires only one handie talkie.
5.3 All members, except the member designated to produce the emergency alert tone,
are to operate on the newly designated primary tactical channel.
5.4 Designated member should be located remote from search activity to avoid
confusion among searchers.
5.5 The Emergency Alert Tone will be created by the designated member as follows:
A. HT is placed on channel which missing, lost, or trapped member was
operating.
B. The Emergency Alert Button is pressed every few seconds to transmit the
emergency alert tone and then pausing, allowing for the possibility of response
from the missing, lost, or trapped member.
5.6 The emergency alert tone will be transmitted from the missing, lost, or trapped
member’s HT, permitting searchers to hone in.
5.8 Searchers listen for tone emanating from missing, lost, or trapped member's HT.
When tone has been detected, searchers home in on member’s location by use of
this tone.
5.9 When the definite location of member has been determined, the emergency alert
tone should be discontinued to lessen the discomfort of trapped member and to
enable communication between this member and searchers.
13
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
6.1 Elevator cars, core areas and stairs in general hamper effective HT operations.
6.2 Certain areas in a building allow good HT operations, such as outer area of the structure,
windows or unobstructed shafts. It may be necessary to move around until best location is
found.
6.3 There is a possibility that radio frequency (RF) transmissions may affect the operation of
medical equipment in hospitals.
6.4 Members shall, during non-emergency visits to hospitals, restrict the use of HT and other
RF transmissions (cellular phones, etc.) in-patient care areas of hospitals.
6.5 Except in an emergency, members shall leave the patient care area prior to transmitting
via HT.
When operations are underway at the scene of an underground subway, the IC can have the
repeater system tested to see if it is functioning. Once confirmed it’s functioning, the IC may
attempt to use the repeater system as a Command Channel. The IC may direct tha appropriate
officers/firefighters to switch to Channel 14 (Primary Subway Repeater Channel) or Channel 15
(Secondary Subway Repeater Channel).
NOTE: An effective HT relay must be established whether the station is equipped with a
repeater or not. Members of the 1st truck and the Officer of the 1st engine shall be
utilized when establishing a HT relay.
7.1 Truck Chauffeur takes a position at the bottom of subway entrance stairs. If token booth
is within 50 yards of stairs to street, contact main dispatcher through the clerk. (There is a
telephone in the booth.) Information obtained should be relayed to Company Officer and
INCIDENT COMMANDER.
7.2 OV firefighter takes a position at the foot of stairs leading to the train platform if it is
within 50 yards of chauffeur.
7.3 Roof firefighter takes a position approximately 50 yards from the stairs on platform.
14
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
7.4 Engine Officer takes a position approximately 100 yards from the roof firefighter on the
platform.
15
NOTES:
• For example, the OV may be able to • Additional H.T. equipped members may
enhance communications by moving be needed to maintain communications,
back and forth between the top and especially at locations with multiple
bottom of the platform stairs. underground levels
16
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
8.1 At the beginning of each tour a visual check of all HTs assigned to the unit must
be made. Officers shall assign individual HTs to members at Roll Call according
to the established guidelines.
8.2 Individual members shall perform necessary tests to ensure proper operation of
HT. Any malfunction discovered should be brought to the attention of the Officer
immediately. Members are responsible for compliance with procedures
established by Company Commanders to assure security of HT.
8.3 To reduce damage to the HT unit and to protect it from adverse weather
conditions, the unit must be worn under the bunker coat.
8.4 Members should monitor the HT while responding to hear any transmission of
units on scene relative to possible location of occupants, need for life saving rope,
ventilation required, and to receive instructions from the Incident Commander.
8.5 Many HTs will be in use at an all hands operation. Therefore, unnecessary chatter
shall be kept to a minimum to avoid monopolizing the HT frequency.
8.6 When more than one HT is being used in close proximity to another, a whining or
screeching noise (feedback) may result interfering with the use of HT. THIS CAN
BE OVERCOME BY KEEPING A HAND OVER THE REMOTE MIC, IF SO EQUIPPED, OF
THE UNUSED RADIOS IN THE AREA.
9.1 ALL FACEPIECES ARE EQUIPPED WITH VOICEMITTERS (AV 2000). THE PROPER
PROCEDURE FOR USE OF THE HT WITH THE VOICEMITTER IS TO:
17
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
10 RADIO DISCIPLINE
10.1 Every firefighter will be equipped with their own HT. We must all remember that
the HT is a tool of communications and should be used with discipline. The
foremost use of our HT is as a listening device.
10.2 At the scene of an expanding operation there will be numerous HTs on the scene.
Members should be listening to the radio traffic keeping them abreast of the
situation. Your message at that precise moment may not be the most important
message at the time. Before transmitting (excluding an emergency report)
member shall listen making sure the HT network is clear. Once certain no
transmissions are taking place member can than transmit their message.
10.3 Members must also be aware that a message transmitted but not responded to
should be considered not received. Member shall continue their transmission until
they receive a response.
There are many situations where emergency roll calls are necessary. Some
examples are:
11.2 The member conducting the emergency roll call will be known as the Roll Call
Officer (RCO). The RCO must be assisted by another member who is responsible
for monitoring the HT frequency that the emergency roll call is being conducted
on and recording the members by position, as they reply.
The RCO conducting the emergency roll call must monitor the HT and make sure
they are not interrupting any emergency transmissions before transmitting over
the appropriate frequency the following statement:
“Roll Call Officer to All Units, Prepare for an Emergency Roll Call”
18
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
The RCO will then pause to give officers a chance to account for members, so
they can accurately reply when called. Each officer should now account for their
members within sight or hearing without using the HT.
C. When a firefighter is answering an emergency roll call via the HT, they
will reply giving the company number they are working in, firefighting
assignment and location.
Example: RCO to Ladder 123 Roof, What is your location?
Ladder 123 Roof to RCO, I’m on the roof of the fire building.
19
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
11.5 When the roll call is completed, the RCO shall announce over the appropriate
frequency, “Roll Call Officer to all units, the Emergency Roll Call is completed.”
20
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
12.2 It shall be the responsibility of the first arriving Battalion Firefighter, after
performing their primary duties, to monitor EFAS until relieved by an EFAS
trained member of the FAST Unit.
• Upon the arrival of the FAST Unit, the EFAS trained member designated at
roll call to monitor EFAS shall report to the Battalion vehicle being used to
monitor EFAS. This FAST Unit member will then monitor both EFAS and the
Battalion’s FAST Unit HT.
Note: The member monitoring EFAS shall be identified by radio designation
“EFAS” when communicating by HT, e.g., “EFAS to Command” “Command
to EFAS”.
12.3 The EFAS program automatically starts up on the MDT when the vehicle ignition
is turned on. The EFAS window is designed to run behind the Starfire window.
The EFAS start-up is delayed 1 minute to allow Starfire to connect. Do not
attempt to select the EFAS button during this time. Members must wait until
Starfire completely “boots up” before switching to the EFAS program.
12.4 Officers arriving at an incident, after they have transmitted their 10-84 via the
MDT, must key their handie-talkie remote microphone once in order to “check
in”. Keying the handie-talkie remote microphone will have all members of the
unit recognized by EFAS.
12.5 When a member activates their Emergency Alert Button, their identity line in
EFAS will automatically be highlighted. Their company, position and name will
be listed in red in both the “RADIO STATUS” and “MAYDAYS” areas.
21
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
12.6 In addition, a hard copy automatically prints showing the company, position and
time of Mayday.
12.7 The member’s identity line will remain red in EFAS until the Emergency Alert is
resolved and the handie-talkie is reset. Once cleared, the member’s highlighted
identity line will change from red (active) back to white in the “RADIO
STATUS” area. The member’s highlighted identity line will change from red
(active) to yellow (cleared) and will remain in the “MAYDAYS” area.
12.8 The EFAS system is capable of handling multiple Emergency Alert transmissions
at the same time. All active MAYDAYS will appear in red in both the “RADIO
STATUS” and “MAYDAYS” area. Member monitoring EFAS may have to
utilize the scroll bar in the “RADIO STATUS” and “MAYDAY” area, in
order view all MAYDAYS that were transmitted.
22
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
12.9 If a member transmits a MAYDAY message on their handie-talkie, and does not activate
their Emergency Alert Button, the member monitoring EFAS shall highlight that member
by utilizing the MDT touch screen and manually assigning them a MAYDAY. Once a
MAYDAY is assigned, a hard copy will print showing the members company, position
and time MAYDAY was assigned.
12.9.1 Select the member’s name. A dialog box will appear for that member. The last
person to transmit is always the top line in the “RADIO STATUS” area.
12.9.2 Select the “ASSIGN MAYDAY” button. This will highlight the member’s
company, position and name, in red, in both the “RADIO STATUS” and
“MAYDAYS” area.
12.10 In the event a member transmits a MAYDAY for another member (e.g.,
unconscious member), the transmitting member shall:
1. Depress the Emergency Alert button (EAB) on their own handie-talkie. This
will identify the member transmitting the MAYDAY on EFAS.
2. After the Emergency Alert activation, provide the Incident Commander with
the information required for the MAYDAY transmission.
3. If possible, depress the EAB of the member in distress. The activation of the
distressed member’s EAB will identify them on EFAS. Notify the IC via
handie-talkie prior to EAB activation of the distressed member.
23
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
12.11.1 Select the member’s name. A dialog box will appear for that member.
Figure 3
1. Select “BEGIN ROLL CALL” button located at the top of the EFAS screen.
2. This will bring up the “ROLL CALL” screen. The left column will contain all
members “UNACCOUNTED FOR” at the beginning of the Roll Call.
3. When members key their remote microphone three times, their name will move
from the “UNACCOUNTED FOR” column on the EFAS screen (left side) to the
“ACCOUNTED FOR” column on the EFAS screen (right side). See Figure 4
24
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
4. If a member does not key their handie-talkie remote microphone, they will remain
on the “UNACCOUNTED FOR” EFAS column and will need to be contacted.
5. If a member is confirmed accounted for but they do not have ability to click their
handie-talkie remote microphone, you can manually account for the member.
Select the member’s name in the “UNACCOUNTED FOR” column by utilizing
the MDT touch screen. A dialog box will appear for that member, select the
“MANUALLY ACCOUNT” button. See Figure 5
Figure 4
25
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
Figure 5
6. When the Roll Call is complete, select the “END ROLL CALL” button
located at the top of the EFAS screen. A dialog box will appear, select the
“END ROLL CALL.” button. See Figure 6 below
Figure 6
12.13 “NON ESSENTIAL PERSONNEL” shall be defined as any company not assigned to
the incident but because of their proximity to the incident will show up on the EFAS
screen as a result of utilizing their handie-talkie.
12.14 EFAS defaults to Tactical Channel 1; however, it has the capability of monitoring any of
the 16 Channels. The IC shall assign an additional member to monitor EFAS for each
channel in use e.g., secondary tactical, primary command, secondary command.
A separate Battalion/EFAS equipped vehicle and EFAS trained member is required for
each channel in use.
12.15 EFAS has the capability to convert the digital data designated by the spare radios. As a
result, members who are assigned a spare radio will be identified by their Company and
Riding position.
26
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
10-4 Acknowledgment
10-6 Stand By
27
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
NOTE: The 10-31 signal shall not be utilized for any incident/emergency involving
evaluation of structural stability, any operation involving a rescue or mitigation
effort, or any type of hazardous condition.
10-32 Defective Oil Burner
28
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
10-35 Unwarranted or Unnecessary Alarm System Activation
Code 1: Alarm system testing or servicing.
Code 2 Construction activities.
Code 3: Ordinary household activities
Code 4: Unnecessary other known cause. (e.g., alarms resulting from
cigarette smoking in unauthorized areas etc.)
Unwarranted alarm (Defective condition of alarm device, low
battery, etc.)
30
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
10-80 No Code
An incident that can be controlled by the on-scene unit(s) and requires no additional
resources. The Haz-Mat Battalion (HB01) and Haz-Mat Co. 1 (HM01) can be contacted via
the dispatcher, 800 MHz radio, or cell phone for technical information if necessary. HB01
and HM01 may be requested to respond to the incident if necessary.
If people are contaminated, exposed or injured, or the incident involves other hazards,
additional resources should be special called by the IC as needed. HB01 can be
contacted for guidance as needed, or may recommend resource assignments to the
IC based on preliminary and progress reports.
The Borough dispatcher shall make the following notifications upon transmission of
Signal 10-80 Code 1:
• Deputy Chief
• FDOC
• EMS Operations
• Department of Environmental Protection (DEP)
• Department of Health (DOH) for Biological or Radiological incidents
• NYPD Operations
32
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
PART TWO
EXPOSURE IDENTIFICATION
33
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
34
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
EXPOSURE IDENTIFICATION
1. The identification of buildings and subdivisions within buildings continues to be a
problem for firefighting forces. The following outlines a system which will provide
a simple and clear concept for building identification. This system uses a more
practical approach, which will lead to improved on-scene communications
2. The system uses a series of numbers and letters to develop an identification code
which is directly related to the building or occupancy the communicator is talking
about. This system always uses as a reference point, the view as seen by a person
standing in front of and looking at the fire building.
2.1 Buildings separated by more than thirty feet from the fire building, should not be
identified as exposures unless the volume of fire or complexity of the incident
causes an exposure problem.
5. Explanation of numbers:
5.1 "0" - when used as the first digit, it indicates the FIRE BUILDING or FIRE AREA.
5.2 "0" - when used in any other position "0" refers to a subdivision of the building
which is identified by the number following the "0" or the letters following the "0".
5.3 "1" - is used to indicate the street in front of the main fire building or the
buildings opposite the front of the main fire building.
5.4 "2" - is used to indicate any building or area to the left of the main fire building.
5.5 "3" - is used to indicate any building or area to the rear of the main fire building.
5.6 "4" - is used to indicate any building or area to the right of the main fire building.
5.7 To enhance the description of a location within or around a building, and when
viewed from the Exposure 1 perspective, the building corners can be further identified
as follows:
♦ The front left corner is the “1-2” corner.
♦ The rear left corner is the “2-3” corner.
♦ The rear right corner is the “3-4” corner.
♦ The front right corner is the “1-4” corner.
35
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
6. Explanation of letters:
6.1 "A" - is used to indicate the second building or subdivision from the main fire building
or fire area.
6.5 "E" - is used to indicate the sixth, "F" is the seventh, and so on down the alphabet.
“2-3 Corner”
3 “3-4 Corner”
2 0 4
“1-2 Corner” “1-4 Corner”
1
Illustration # 1
36
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
7.1 Illustration 1, depicts a single building. The building is identified as "O", "1" is a street,
"2" is a lot "3" is a lot and "4" is a lot. This indicates that the building is isolated.
7.2 Illustration 2 depicts a taxpayer with nine (9) individual stores, or nine subdivisions. The
fire is located in the center store. The store to the immediate left of the fire store is
identified as exposure "O-2", the next store on the left (two stores from the fire store) is
"0-2A", the third store on the left would be "O-2B" and the fourth store would be "02C".
The first store on the immediate right of the fire store would be exposure "0-4", the
second store on the right would be "0-4A", the third store would be "0-4B", and the
fourth store would be "0-4C".
O O O O O O O O
2 2 2 2 2 O 4 4 4 4 4
C B A A B C
1
Illustration # 2
37
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
7.3 Illustration 3 depicts a more complex problem. It uses as a foundation the taxpayer shown
in illustration #2. The fire building is identified as "0" and all subdivisions are identified
by having their ID codes start with "0". The second character in the identification code is
a number and indicates the direction; "2" indicates the left side and "4" indicates the right
side. The third character is a letter and indicates how far away from the fire store the
subdivision is located. Exposure "1", for this illustration is a street. The first building to
the left of the fire building is exposure "2", the second is "2A". The buildings directly to
the rear of the fire building are exposure "3". The building immediately to the right of
the fire building is identified as exposure "4", the next building to the right is exposure
"4A", than "4B", "4C", etc.
Illustration #3
Note: To eliminate any confusion in identifying rear exposures, all buildings in the rear shall be
referred to as exposure "3". If operations on exposure "3" become too complex, the
Incident Commander should create a sector and assign a sector officer to manage this
area.
38
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
7.4 Illustration #4 shows how the system builds; it starts with a fire in the taxpayer, "O", that
extends to the right and then out of the taxpayer and into the windows of the top floor of
exposure "4". Exposure "4" is an "H-type" building and because of its size, we will
mentally subdivide it into sections. Each of the arms of the "H" will be identified as
WINGS. In this illustration the wing closest to the fire building is wing "A", the next arm
is wing "B" and if there is a third or fourth wing they would be identified as wing "C" and
wing "D". Wings are identified from left to right looking from the front of the building:
If necessary each wing can be further subdivided from front to rear using the terms
FRONT, CENTER, and REAR. The part of the building connecting each wing shall be
designated the throat and shall be referred to as the throat between "A" wing and "B"
wing etc.
Illustration # 4
39
FDNY Probationary Firefighters Manual
Chapter Seven COMMUNICATIONS
7.5 Illustration 5 depicts a fire that originated in the "H" building and has extended to the left
into the taxpayer. It has advanced down the row of stores to the third store and threatens
the fourth store. The "H" type building is identified as "O", the taxpayer is exposure "2"
and the first store or subdivision of the taxpayer is identified as "2-0". The "2" indicates
the first building on the left; the "O" following a number indicates that we are now
referring to a subdivision. The second store is "2-OA", the third store is "2-OB", the 4th
is "2-OC", the 5th is "2-OD", the 6th is "2-OE". The next building is a separate building,
not part of the taxpayer and is identified as exposure "2A", then "2B", etc. The buildings
opposite the fire building represent exposure "1" because either the separation is less than
30 feet or the intense fire creates an exposure problem.
Illustration # 5
40
FDNY Probationary Firefighters Manual
Chapter 7 COMMUNICATIONS
_______________________________________________________________________________________________
PART THREE
SECTION Handie-Talkie PAGE
1. INTRODUCTION ...............................................................................................................43
41
42
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
1. INTRODUCTION
After many years of use in the FDNY, the XTS3500 has reached its end of service life.
Following an exhaustive evaluation process, a new radio with many additional features
has been selected by the FDNY.
1.2.1 Voice Annunciation: Announces zone and channel when powering up and
changing channels.
1.2.2 Multi-Screen View: Top display and Main display for navigation of features.
1.2.3 Recent/Mayday Retention: Will hold the IDs of the last 15 transmissions.
1.2.4 High Visibility LED on Remote Speaker Mic (RSM): Operates on EAB
activation and manually.
43
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
Figure 1
44
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
45
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
46
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
47
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
48
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
49
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
50
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
Fig 7
Note: The additional channels, zones and frequencies are an enhancement to FDNY
communications. These additional channels afford broader communication capabilities at
the Company level, as well as provide enhanced situational awareness.
51
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
Fig 8
Fig 9
52
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
Fig 10
53
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
3. SPECIAL FEATURES
54
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
Fig 11
55
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
[Link] Audible Alerts: When EAB is depressed, Audible Alerts are emitted.
Alert Tones: Alert tones are the audio signal transmitted to other HTs
within range of the transmitting HT notifying others a member has
activated his/her EA. This signal alerts members of a Mayday or
Urgent situation. There are two types of alert tones; Impolite and
Polite. The APX8000XE transmits One (1)-Impolite and Two (2)-
Polite Alerts.
Impolite Alert - An impolite call is when the radio sends a
transmission even when the channel is busy with other radio traffic,
however it will NOT preempt any ongoing transmissions.
Note: Due to radio frequency (RF) anomalies, some radios may not
receive the emergency alert. Proximity, concrete, steel,
building construction, height, terrain and other factors can
contribute to the individual member’s radio ability to receive
the transmitting member’s EA.
Polite Alert - A polite call is when the radio sends a transmission
when the channel is not busy with other radio traffic. Thereby, increasing
the likelihood that other members will receive Emergency alert.
Approximately 8 seconds after the impolite transmission,
the Polite Alert is sent. Therefore, the Polite Alert may be
more than 8 seconds after the Impolite Alert tone if other
members are transmitting. The APX8000XE HT will
transmit 2 Polite Alerts to attempt to reach as many
members as possible.
All 3 Alerts will be transmitted, regardless if members are
transmitting or receiving messages. The Impolite Alert will
go out first, followed by 2 Polite Alerts when the channel is
clear.
Beacon Tone: Manual activation of a radio EA, will initiate an audible
Beacon transmitted from that radio. This beacon is used to locate
member that activated the EA. This audible beacon is emitted from
members HT until it is reset by member.
Reset EA: EA may be reset by depressing EAB for 2 seconds, or by
turning HT off and then back on.
56
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
Fig 12
57
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
Fig 12a
58
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
Fig 13
59
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
3.6 Backlight:
Depressing any button will illuminate both displays for approximately 20 seconds.
3.8 Batteries:
The APX 8000XE utilizes a Motorola Impres 2 lithium ion battery.
Fig 14
60
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
61
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
4.1 The following shows the Alphanumeric designation as well as the 7 digit numeric ID for
typical Units and Positions. Alphanumeric ID of HT will appear on main/top display and
will also be displayed on screen of member receiving transmissions.
5.1 If the HT becomes wet at an operation, or has been submerged in water, remove the
battery, dry HT and battery contacts before re-attaching battery to the HT.
5.2 If the remote speaker mic becomes wet, or submerged, water trapped inside the speaker
grille and microphone can be removed by shaking the unit well.
5.3 The Field Communications Unit (FCU) shall carry a limited number of additional HTs
with fully charged batteries for emergency use. HTs for emergency use shall be returned
to the FCU as soon as they are no longer required.
5.4 Members should not remove or replace any accessories associated with the radio,
including antenna and remote speaker microphone.
5.5 When HTs are sent for repair, they should be sent complete (radio, antenna, battery, and
RSM) with defect and company number recorded on RT-2. Leather goods (cases and
straps) should not be sent unless they need repair. (See addendum 4)
5.6 No items (keys, key fobs, etc.) shall be attached directly to the HT, case, antenna or RSM
as this may cause interference with radio transmissions. Items may be attached to the HT
strap; however, they must be secured in a manner that does not allow movement or
contact with the HT, case, antenna or RSM.
62
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
5.8 Functional Check, Inspection and Maintenance of the HT: including but not limited to
radio, antenna, battery, RSM and cord shall be made (see Fig. 16):
Immediately after the 0900 and 1800 hour roll calls.
After each use.
Members shall ensure that slots in radio charger are clear of dirt and debris prior to
charging batteries. Wet batteries shall be wiped dry prior to charging.
No batteries with any physical damage shall be placed in a charger. They shall be
placed out of service.
Fig 16
63
FDNY Probationary Firefighter Manual
Chapter Seven COMMUNICATIONS
6.1 Throughout the city, members will encounter areas that are RF (radio frequency)
challenged. These areas include but are not limited to hospitals, prisons, big box stores,
shopping malls, high rises, large OMD's, sewage treatment plants, power plants, tunnels
and any structure of unique construction. The use of radio relay or alternate
communications strategies shall be considered.
6.2 Members are reminded that while operating at routine alarm assignments and BI, if any
of these areas are identified as RF challenged, they should be noted in the CIDS for the
respective address.
6.4 Some buildings throughout the city have been equipped with proprietary repeaters and
amplifiers for their in-house two way communication needs. The potential exists for
these systems to interfere with FD HT communications.
6.5 As with the previous handie-talkie models, unforeseen and isolated incidents of radio
frequency peculiarities continue to be experienced which interfere with communications.
This occurs due to proximity of radios, radios out of range or poor radio discipline.
64
Probationary Firefighters Manual
Chapter 8
BUILDING CONSTRUCTION
FDNY SOURCE:
• Firefighting Procedures:
o Volume One: Books 1 – 6
o Volume Three: Book 3
• Safety Bulletins
o No. 85
OTHER REFERENCES:
1. Brannigan, F. (1992). Building Construction for the Fire Service, (3rd ed.). Quincy, MA:
National Fire Protection Association
2. Captain Murphy, D. & Firefighter Molle, H. (2000, 3rd). More on gypsum roof deck
systems, With New York Firefighters (WNYF), p. 25.
3. Dunn, V. (1988) Collapse of Burning Buildings: A Guide to Fireground Safety. Saddle
Brook, NJ: Fire Engineering Books & Videos: a Division of Penn Well Publishing
Company
4. International Fire Service Training Association (1999) Building Construction: Related to
the Fire Service (2nd ed.). Oklahoma: Fire Protection Publications, Oklahoma State
University.
5. International Fire Service Training Association (1998). Essentials of Firefighting (4th ed.).
Oklahoma: Fire Protection Publications, Oklahoma State University.
6. TenanetNet (2005). NYS Multiple Dwelling Law, Retrieved October 15, 2006, from
[Link]
8
THIS PAGE WAS INTENTIONALLY LEFT BLANK
BUILDING CONSTRUCTION
TITLE PAGE
BEAMS ....................................................................................................................1
COLLAPSE ..............................................................................................................6
BULKHEAD..............................................................................................................8
FRAMING ..............................................................................................................17
GYPSUM ..............................................................................................................24
LOADS ..............................................................................................................30
ROOFS ..............................................................................................................32
STAIRS ..............................................................................................................33
STAIRWAYS……………………………………………………………………….34
STRUCTURAL STEEL................................................................................................38
TRUSSES ..............................................................................................................43
WALLS ..............................................................................................................48
WINDOWS ..............................................................................................................49
THIS PAGE WAS INTENTIONALLY LEFT BLANK
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
BASEMENT A story partly underground but having at least one-half its height,
measured from finished floor to finished ceiling, above the curb level.
CELLAR A story having more than one-half its height from finished floor to
finished ceiling below the curb level.
BEAMS
BEAM A horizontal member used to carry loads perpendicular to its length.
FIRE -CUT A bevel cut at the end of roof beams in brick walls, leaving the beams
free to fall if burned through without causing the walls to fall.
1
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
2
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
Girder
3
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
BUILDING CODES
1938 Building Code
Class 1: Fireproof Structure
Class 2: Fire-Protected Structure
Class 3: Non-Fireproof Structure
Class 4: Wood Frame Structure
Class 5: Metal Structure
Class 6: Heavy Timber Structure
FIRE PARTITION A partition provided for the purpose of protecting life by furnishing an
area of exit, or refuge, and having a fire resistive rating of at least three
hours.
*1938 Building Code
FIREPROOF A building in which the walls, floors, structural members and
CONSTRUCTION stairway enclosures are made of incombustible materials with
fire resistive ratings as required by the Building Code,
FIRE RETARDING any material or substance that is used to hold back the spread of
fire for a rated period of time
4
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
FIRE STOPPING the closing of all concealed draft openings to form an effectual
fire barrier at floors, ceilings and roofs with brick, concrete,
gypsum, asbestos, mineral wool, rock wool, metal lath with
cement or gypsum plaster, or other approved incombustible
materials.
FIRE WALL A wall provided primarily for the purpose of resisting the
passage of fire from one structure to another or from one area of
a structure to another, and having a fire resistive rating of at least
four hours.
*1968 Building Code
5
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
COLLAPSE
A collapse is one of the most dangerous operations a firefighter will encounter. The FDNY
might be dispatched to a report of a collapse or one may happen during firefighting
operations. Injured or disoriented people may require assistance, while others may still be
trapped in the rubble.
COLLAPSE ZONE The expected ground area a falling wall will cover when it collapses.
It is at least the distance away from the wall which is equal to the
height.
Horizontal Collapse Zone – width of the structure
Vertical Collapse Zone – height of the structure
PRIMARY A structure that
STRUCTURAL supports another
structural member in
MEMBER
the same building,
such as a bearing wall,
a column, or a girder.
The collapse of a
primary structural
member will often
cause the collapse of
the structural member
it supports.
SPALLING Loss of surface material when concrete (or stone) is subjected to heat.
It is due to the expansion of moisture in the concrete. Explosive
spalling occurs violently, throwing bits of concrete projectiles
(Brannigan 331.).
Structural Weakness:
CAUSES OF • Accumulation of snow or • Excavations
COLLAPSE rain on the roof • Improper Renovations
• Overloading of floors • Weather – earthquakes,
• Backdrafts/Smoke Explosions winds etc.
• Fires • Impact load from a collision
6
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
TYPES OF COLLAPSES
7
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
WALK A structure at the uppermost portion of interior stairs that may isolate
THROUGH the front section of the roof from the rear. One must walk through the
bulkhead to reach the other section of the roof.
BULKHEAD
8
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
COAMING A raised frame around a floor or roof opening or scuttle to keep water
from running in.
COCKLOFT The space between the roof and the top floor ceiling. Fire may enter the
cockloft through recesses, voids and ducts.
COCKLOFT AREA
COMMON Open all the way from one end of a row of houses or stores to the other
COCKLOFT end.
9
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
CORBELLING Course of brick built out from the face of a wall, as steps in reverse.
*See definition of parapet for illustration
10
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
CORNICE Decorative trim at the roof line. Made of metal, wood or masonry,
which tops the front wall & projects from it (Brannigan 194.).
11
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
COPING STONE Top masonry tile or stone of a parapet wall, designed to carry off
rainwater. Sometimes called a “capstone,” it weighs between five and
fifty pounds (Dunn 18.).
COMPACTOR A device for crushing garbage and trash into a small space prior to
removal from the premises
12
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
EXPOSURES A system of designating the areas or buildings which are adjacent to the
fire building. When facing the main entrance to the fire building,
exposure #1 is in front of the building, #2 is on the left, #3 is to the rear
of the fire building and #4 is on the right.
13
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
DROP LADDER A vertical ladder normally held in the "up" position at the second floor
balcony of the fire escape by a hook. When this ladder is to be used,
the hook is released and the drop ladder is lowered or dropped to the
ground. Care must be exercised to make certain that no one is struck
by this ladder when it is lowered or dropped to the ground.
14
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
COUNTER
BALANCED
STAIRWAY
15
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
GOOSENECK A vertical ladder, the side rails of which are curved at the top. This
LADDER type of ladder is sometimes used between the top floor balcony of a
fire escape and the roof.
Yankee Gutter
WOOD (YANKEE) Found on most Brownstones. They can be dangerous, since they
GUTTER are made of wood and then tarred over many times. Usually
rotted.
16
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
FRAMING
BAYS The open area between either studs, in a wall, or beams in a floor
or a roof
LALLY COLUMN A vertical structural member consisting of a steel pipe filled with
concrete.
RAFTER Closely spaced beams supporting the roof and running parallel to
the slope of the roof.
RIDGE The horizontal line at the junction of the top edges of two
sloping roof surfaces.
RIDGE BOARD The board at the ridge to which the rafters of both slopes of the
(POLE) roof are nailed.
TAIL BEAM A beam which frames into the header instead of spanning the
entire distance between supports.
17
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
18
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
19
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
BALLOON In balloon framing construction, fire can easily extend vertically. Studs
FRAMING and corner posts are continuous from the sill to the top plate. The side
wall studs, at a point of the upper floors, are notched out and a 1 x 4 is
fitted and nailed into the studs. This is known as the ledger board. The
ledger board supports the floor joists of the upper floor.
20
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
21
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
PLATFORM Each level is completed separately. The floor beams and deck for the next
FRAMING higher level are constructed on top of the lower story.
From a fire protection standpoint, platform construction is superior to
balloon, because there are no concealed wall voids extending for more
than one floor level (Dunn).
22
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
23
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
GYPSUM PLANK Gypsum planks are normally 2 inches thick, 2 feet wide and 8 feet
ROOF DECKING long and factory-laminated of two gypsum panels. Each plank
weighs approximately 135lbs.
24
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
• However, a field unit discovered that white powdery residue will only be present on a
roof not subjected to moisture. They
further discovered that a gypsum roof
that had been penetrated by moisture will
produce a “brownish, clay-type
substance,” that will fill the shroud of the
saw during cutting operations.
o It should be stressed that this
condition exists in roofs that
already are degraded by moisture.
25
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
LIGHTWEIGHT CONSTRUCTION
LAMINATED Consist of a top and
WOOD "I" BEAMS bottom chord and web.
The chords are made of
2" x 3", 2"x 4", or two-
¾" CDX or pressed
plywood glued together.
The web is usually made
of ½" plywood.
Contractors may have
bore holes to route
electric, plumbing etc.,
compromising the strength of this beam. If not properly sealed,
fire can extend from one bay to another.
26
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
LIGHTWEIGHT • Made of 2"x3"s or 2"x4"s, which are held together with sheet
WOOD TRUSSES metal gang nails or gusset plates.
o Gang nails (gusset plates) penetrate only ¼" to ½".
• When exposed to high heat, fire, or prolonged moisture, gang
nails may pull away causing the failure of that truss. The failure
of one truss may initiate a domino effect on adjoining trusses.
• When light weight wood trusses are used as joists, fire can
spread horizontally unimpeded.
• Tests have shown truss failure rates are as low as 1 minute, 20
seconds. Failure of one truss can cause a structure to totally
collapse.
27
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
OPEN WEB
STEEL BAR
JOIST
o Solid wood
o Most common decking is corrugated steel, with the joists spaced from four to
six feet apart.
♦ Roofs with this type of roof support system must not cut.
28
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
29
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
LOADS
AXIAL LOAD is a force perpendicular to the supporting
member. An axial load is straight and true
and is evenly applied to the bearing structure.
DEAD LOAD the weight of all permanent stationary construction entering into a
structure and includes the weight of walls, floors, roofs, structural
members, etc.
LATERAL LOAD are loads that are exerted outwardly on a horizontal plane. These
forces may take place during a collapse or an explosion. Walls are
not usually designed to withstand severe lateral loads.
LIVE LOAD All loads other than dead loads. These loads are not permanent or
stationary and include the weight of merchandise, office fixtures,
furnishings and all free standing material and persons.
IMPACT LOAD Are loads delivered, in a short time, on structural members and
produce stresses on structural members that may not have been
provided for in design and may cause collapse.
30
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
RETURN The interior surface of a scuttle or skylight between the roof and
the top floor ceiling
31
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
ROOFS
BUILT UP is the roofing material applied in sealed water-proof layers on the
ROOF structural members of the roof.
RAISED A roof which is raised above the roof beams and supported by 2 x 4"s.
(INVERTED) The extent to which it is raised varies so as to provide proper drainage on
the roof. The result is a large open cockloft where fire can spread easily.
ROOF
32
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
STAIRS
TREAD: the horizontal part of a step on
which the foot is place.
NEWEL
POST: Vertical post at each landing
supporting handrails
33
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
STAIRWAYS
ACCESS A stairway, usually open, serving a number of floors of a common
STAIRS tenant. Also known as convenience stairs.
ATTACK A fire stair being used by the Fire Department to gain access to the fire
STAIRWAY area, where the door between the stairway and the fire area is being
maintained in an open position.
EVACUATION Fire tower or a fire stairs, designated by the Fire Department or a pre-
STAIRWAY existing building fire plan, that is remote from the fire area and used for
the evacuation of the building occupants. A fire tower is the preferred
evacuation stairs.
34
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
RETURN Breaks up the stair climb at the middle of the stair rise with an
STAIRS intermediate landing; here, the climber reverses direction before starting
the second half of the stair rise.
TERRAZZO A polished floor covering made of small marble chips set in several
inches of cement. A terrazzo floor is a collapse hazard: it adds weight to
floor beams, conceals the heat of a serious fire below, and, because it is
watertight, allows water to accumulate and build up to dangerous
proportions. In 1966, A fire burning in a cellar below a terrazzo floor
burned away the floor beams, although little heat and smoke penetrated
the floor itself. The floor suddenly collapsed, killing 12 firefighters
(Dunn 32).
35
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
SCISSOR Two stairs constructed side by side in the core of a building in which
STAIRS their doors alternate the point of exit to opposite sides of the core.
36
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
WING STAIRS
These stairs, one or two in a building,
are located in each wing. There is no
connection to the other wing. The
diagram represents half a building
showing each type.
ISOLATED STAIRS
Usually have individual entrance.
Floor landings are limited. No
connection to other.
37
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
STRUCTURAL STEEL
Older buildings generally only have two structural elements to support the structure,
masonry and wood. The introduction of a third element, steel, had the following advantages:
♦ And finally, the ability of steel to be connected permitted the coupling of several
building sections, e.g. the “H” type design of residential housing.
1. Steel when heated expands, and substantial elongation can occur at a fire. This
elongation can cause a wall to bulge, move, or even collapse if the steel is set within
the wall.
2. Steel when heated to higher temperatures during a fire may fail. Floor beams
supported by such failing steel will fall to the floor below.
3. Steel columns or girders, generally in an "I" beam shape, transmit fire and heat. The
"I" beam or channel rail, as it is sometimes called, when in the form of a column
located in the inner framework of a building may extend from the first floor up into
the roof space or cockloft area. The space between the enclosing wood framework
and "I" beam, when in the form of a vertical column, leads up into the cockloft and
many times spreads to this roof space.
38
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
39
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
"I" beams will absorb heat from the fire at a rate dependent on many factors, such as, the
temperature of the fire, the extent of the fire, and the mass (weight and size) of the beam. A
large, heavy "I" beam will be able to absorb more heat and its temperature will rise more
slowly than a lightweight beam.
Because of the conductivity of the steel, this temperature will diffuse into the beam
causing its expansion. An average 50 foot long steel beam, heated uniformly over its length
to 970F will extend in length approximately four inches. A longer "I" beam will expand a
proportionately greater distance, and as the temperature increases, the rate of expansion
increases. At 1000 F a 100-foot long beam will have extended in length nine-and-a-half
inches.
When these steel beams are heated from 1000 F to 1500 F, their yield strength drops
dramatically and they start to soften and fail. This temperature can be reached in five to ten
minutes at a fire and it is only a matter of time at an uncontrolled fire (thirty minutes for the
smaller beam sections), until these beams can be heated beyond their strength limitations.
There is a false impression that hot steel beams or columns cooled by hose streams
will crack or fail. Tests have shown that cooling a steel member will cause it to regain its
strength and load carrying ability, and under normal circumstances, there should be no
hesitation in cooling these members. If the beam has already sagged under the weight of
floors or roof, firefighters should not be allowed in the possible collapse zone, whether these
beams are cooled or not. The steel will contract to its original length as it is cooled and if the
beam has sagged, this shortening may pull the end of the beams off their supports or twist
the beam allowing the joists to drop.
40
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
Plenum
41
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
42
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
TRUSSES
“BEWARE OF T HE TRUSS”
• Truss roof construction is used to span large areas, free of support columns, and can be
made of wood or steel. Most roof trusses are designed just to provide the span and
support of the roof system.
• Basically, the truss is composed of two major members, chords and webs. There is a
top and bottom chord connected by shorter members called webs. The webs are placed
vertically and diagonally, forming triangular configurations with the chord members.
There are many variations but all are essentially the same; a combination of
interdependent components used to span large distances through the use of smaller
pieces fastened together.
• In any truss frame, every part of the truss is important to its stability. The failure of
any element may lead to the failure of the entire truss. Because of the wide spans and
the interdependence of trusses, one with another, the failure of a truss may have serious
consequences far from the point where the initial failure occurs.
• Truss roofs are not designed nor constructed to be used as a Fire Department working
platform. Early collapse of the roof must be anticipated in a heavy fire condition and
members should not be committed to roof operations.
• Members operating on the roof must immediately inform their officer and Incident
Commander of the type of roof system and the presence of any heavy equipment.
• Members should also be aware that light-weight wood trusses and wood I-beams are
being used as floor supports, creating the same potentially dangerous collapse
conditions within the interior of the structure.
43
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
BOWSTRING
TRUSS
44
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
45
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
VERTICAL Created by pipe recess (water & vent pipes), channel rails, electrical
VOIDS conduits, dumbwaiter shafts, etc. Can spread fire throughout the
building by convection or burning embers dropping down these voids
and starting a fire on a lower floor.
Soil pipe, water pipe and electrical line found in a rear closet.
46
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
47
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
WALLS
BEARING A wall of a building which carries any load other than its own weight.
WALL
KNEE WALL A wall used to box out a finished attic. This creates large voids and
occupants usually store combustibles behind it.
MORTAR A material composed of sand and cement (and possibly other additives)
used to build brickwork.
48
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
WINDOWS
WINDOW • The location of window security bars will vary. However, it is not
BARS uncommon to find these installations on all floors and all sides.
• The construction of these bars will vary from thin aluminum child
guards to heavy wrought iron and steel.
• Some bars may be set in mortar or brick. Others may be bolted or
screwed into the wooden frame of the window or door.
• Civilians may become
trapped with no means
of escape.
• Firefighters may
become trapped when
going above the fire
for a search.
• Window bars are
heavy and difficult to
remove.
CASEMENT A metal framed window which opens outward. This type of window is
WINDOWS usually found in high rise multiple dwellings.
49
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
ENERGY A window designed to maintain air tight insulation, and will contain
EFFICIENT more than one pane of glass with an air tight space in-between.
WINDOW
(EEW)
50
FDNY Probationary Firefighters Manual
Chapter Eight BUILDING CONSTRUCTION
51
Probationary Firefighters Manual
Chapter 9
BUILDING DESCRIPTIONS
9
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
I t is almost impossible, when arriving at a structural fire, to tell the age of the building, nor is
that so necessary. It is sufficient to know the general features of the building and this can be
accomplished at a glance if the classification of the building is known.
1
It is not intended to describe and date each law that affects the listed types of multiple dwellings; namely, Old Law
Tenement, New Law Tenement, newer non-fireproof multiple dwelling or fireproof multiple dwelling.
1
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
2
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
3
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
4
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
o 1901 to 1916
Steel “I” beams were introduced to carry floor joists which couldn’t span the
enlarged floor areas. These steel beams generally were supported by masonry
walls.
o 1916 to 1929
Unprotected steel beams are used to support some of the wood floor joists.
These steel beams are supported by vertical steel columns which run the
height of the building. Wooden floor joists (beams) run horizontally from
brick wall to a steel girder or from a steel girder to a steel girder.
• However, these dividing walls only go as high as the ceiling of the top
floor. This results in a very large undivided cockloft area. Fire can, and
often does, spread throughout this large cockloft area.
o After 1929
Changes, in NYS building law, were designed to reduce the size of the
cockloft, by requiring firewalls to be extended through to the roof.
5
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
6
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
AREA:
♦ 1901 to 1916 .............................35’ to 50’ wide & 85’ deep
♦ 1916 to 1929 .............................150’ x 200’
♦ After 1929 .................................extraordinary dimensions, though every 3,000 sq. ft., was
required to by enclosed by firewalls
APTS. PER FLOOR:
♦ 1901 to 1916
o Five to six
♦ After 1916
o “H-Type” buildings developed with the number & layout of apartments varying from
building to building.
o Some having long interior hallways, rooms of one apartment may be behind another
apartment, in “L” or “T” shaped form.
o Except for the first floor (lobby), upper floor apartment layouts are generally identical
in each vertical line.
CELLARS:
♦ Exterior entrance only
o Either by a side or rear door at that level via an exterior stair from the first floor, or
through a passageway located in the front of the building
♦ First floor (cellar ceiling) is of fireproof construction. Openings below the first floor for
pipes, conduits, ducts, dumbwaiter and elevator shafts, must be protected by fireproof doors
and assemblies and such doors must be self-closing.
♦ Some buildings may require a sprinkler in the cellar.
SECONDARY MEANS OF EGRESS:
♦ Fire escapes are more generally found in these buildings. They may be on one, two, or all
sides of the building. Some buildings may have ten or more.
ELEVATORS:
♦ Provided in some buildings, running from the cellar to the top floor with a bulkhead on the
roof.
STAIRWAYS:
♦ Some will be found near the front entrance; other will be some distance away
REAR YARDS:
♦ Entrance may be gained through passageways from the street or through interior doors
located on the first public hallway to exterior stairs.
7
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
8
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
9
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
♦ VENTILATION:
o When indiscriminate ventilation is accomplished, whether naturally, because the
windows fail, or by fire fighting forces ventilating improperly, unpredictable results
will follow, sometimes with disastrous consequences.
o Generally smoke & air will travel in a direction toward vertical shafts, stairwells and
elevators.
Care must be taken to maintain the doorway to the evacuation stair closed on
the fire floor.
o The most prominent variables that effect smoke movement are:
Height of building.
Stack Effect: the temperature differential between outside & inside
Construction and configuration of the building.
Surrounding structures and their relation to the building.
Mechanical ventilation systems.
WIND-Wind is the most serious concern to firefighting, as it alone can
override the effects of some or all of the other variables. We must strongly
consider the effects of wind , even on lower floor fires.
o When the fire apartment door has been left in the open position and the windows fail,
the public hall becomes part of the fire area.
♦ VENTILATION PROCEDURES:
o In these occupancies our ventilation is very limited. In fact it is usually not
performed until the main body of fire has been controlled.
The ladder officer in the fire apartment conducting a search and examination
should be the only one to initiate the request for additional ventilation. All
other ventilation must be strictly limited and controlled by the Incident
Commander.
In some older fireproof multiple dwellings there are windows in the stairways.
However, newer high-rise structures with scissor stairs are usually
windowless.
Stairways other than the evacuation stair may be used for venting the fire
floor. Where only two stairways are present the attack stairway will be the
primary means for vertical ventilation.
Conditions in stairways can change dramatically at a wind driven fire.
⇒ Stairways that are relatively clear at the onset of the operation may
soon become severely contaminated with smoke, especially if this
stairway is used for ventilation.
10
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
⇒ The possibility of tenants entering the stairway above the fire must
always be expected and all stairways and hallways must be monitored
on a continual basis for the presence of victims.
♦ ELEVATORS:
o Stairs shall be used when the fire is on the seventh floor or below.
o Projects may have two elevators, one serving odd and one serving even floors.
Members may wind up more than two floors below the fire due to this alternate floor
system. In other projects, the elevators serve all floors or there is a LOW/HIGH bank
system.
o Overloading of elevators must be avoided or the units responding to the fire will be
delayed arriving at the fire/emergency. A stalled elevator, is an elevator out of
service. Look for maximum load signs and consider each member and his/her
equipment to be over 200 pounds.
o After all units are in position, and two elevators are available and serviceable,
maintain one elevator on standby in the lobby and one two floors below the fire, to
transport injured members or civilians down to the lobby.
♦ FORCIBLE ENTRY:
o Fire Floor
Adjoining apartments may be forced for sufficient reasons such as high
carbon monoxide readings in the hallway or severe smoke conditions. The
ventilation effects of forcing doors other than the fire apartment on the fire
floor cannot be accurately predicted. Air movement may work against our
firefighting and search efforts. A heavy smoke condition in the hallway
indicates that the door to the fire apartment most likely has been left open.
When it is decided that a door is going to be forced to provide an area of
refuge, the door selected must be on the same side as the fire apartment door
to prevent fire from being drawn across the hall if the fire apartment windows
fail.
11
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
Dead
Man’s
Room
12
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
BROWNSTONES
BUILT .............................as private dwellings in the late 1800’s
13
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
14
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
ROOF:
♦ An iron ladder (usually in a closet) gives access from top floor to the roof through a
scuttle.
♦ Majority are flat construction with no rear parapet, with an approximate cockloft of 2 to 3
feet in height, pitched to the rear
♦ Some have a center peak, sloping towards the front & rear
♦ A third type has more floors in the rear than the
front. There may be five stories in the rear with
full windows. The roof slopes to the front where
there are small front (eyebrow) windows
making access to and removal of trapped
persons from these areas difficult. This also
creates a communication problem when making
a size up.
15
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
♦ Originally bars were often encountered on both front and rear first floor windows and
iron gates beneath the front stoop, negating access and egress. Additional bars and gates
may be found on upper floors.
♦ In some instances these buildings have been renovated by removal of the front stoop
converting the former first floor entrance to the main access for the building.
♦ In many buildings, when they were converted to Multiple Dwellings, fire escapes were
added or sprinklers were installed in the interior halls in lieu of secondary means of
egress. Sprinkler lines were further extended into individual rooms when buildings were
converted to Rooming Houses. The presence of these sprinklers may indicate the absence
of a fire escape. MOST BROWNSTONES, HOWEVER, DO NOT HAVE FIRE ESCAPES.
♦ In many instances these buildings are being utilized as "illegal" Multiple Dwellings with
single room occupancies or entire families found on all floors, without the required fire
escape or sprinklers.
♦ Rear extensions also have been added on the first floor. In some cases these extensions may
be two or three stories in height, and 10 to 20 feet in depth. They will have their own cockloft.
♦ In addition to typical problem areas associated with NFP buildings, particular points of
examination inside the Brownstone should include dumbwaiter shafts, hot air ducts and
registers running throughout the building and pockets in the walls on the second floor
(parlor floor) constructed to facilitate the operation of sliding doors (pocket doors).
♦ Some Brownstone buildings may have open stairs in the rear of the building. They usually go
from the first to second (parlor) floors. This is separate from the main staircase. Their original
use was for servants. Fire may extend via these stairs.
♦ Transom windows, which may be found over the interior doors, can fail under fire
conditions and allow heat and smoke into the hall areas. This also will allow fire to
spread more easily.
16
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
♦ Duplex Apartments: In certain areas of the city, it has become popular to convert to
duplex apartments. Each conversion will present its own unique problems. The
following is a list of construction features that may be found:
B. Partial areas of the floors may be cut out to create two story-high ceilings and
balconies.
Note: In some cases, ventilation of the roof will only provide ventilation for the
apartments on the upper floors.
17
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
1st Floor
18
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
BROWNSTONE (FRONT)
1. Stoop - May be present. Provides access to 2nd floor and better control of 1st floor fires.
Interferes with laddering of 3rd floor. Some stoops have been removed to modernize the front.
2. Iron Gate - Difficult to force: Steel exit cover from cellar often found just inside gate;
this 2nd exit required for class "B" Converted Dwellings.
3. Sunken Court - Makes laddering difficult, i.e. handling problems, falling ladders.
4. Grate Over Vent Hole - Often has wooden cover, which can be removed for ventilation.
5. Coal Chute - Metal cover often found in street or sunken court. Provides ventilation for
cellar fires.
6. Barred Windows - Bars usually recessed into brick or stone, sometimes attached to
frame with wood screws. Bars attached to wood frame are much easier to remove.
7. Cellar - Low ceiling; storage area; difficult access; ceiling is open beam construction
(unless converted to M. D.).
8. Heating Plant - Older systems coal fired, hot air. Many ducts leading to hot air registers
throughout building. Even if a newer type system present (steam or hot water) suspect presence
of ducts, for often they were left in place when newer system was installed.
9. Scuttle - (Bulkheads not found in Brownstones). Iron ladder leads from top floor to roof.
Where ladder goes through cockloft, area enclosed by "returns". A quick examination of
"cockloft" can be made by removing lightly constructed "returns".
11. Skylight over stairwell -. Often has glass panel (draft stop) at ceiling level of top floor.
For proper venting this panel must be opened or removed.
12. Brick Parapet - Carried above roof 8" or higher (as a rule).
14. Modernized Face - removal of stoop eliminates means of egress from front of building
on parlor floor. Occupants encounter difficulty exiting the building during cellar fires
19
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
BROWNSTONE
(REAR)
20
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
BROWNSTONE (REAR)
1. Some of the older Brownstones have peaked roofs. Dangerous to work on , particularly in
wet or icy weather.
3. Sliding doors are common in Brownstones. The doors recess into hollow partitions on
each side of the opening. Voids are created in the partition which allows fire to extend;
voids are larger when doors are in closed position.
4. Rear Entrance - 1st level. Only level with 2 exits (unless fire escape is present).
5. Iron Bars - Difficult to remove, unless installed with screws into wood frame. Where bars
are attached with screws to the frame, the frame is often rotted permitting rapid removal
with a prying tool.
6. Roof of Extension has cockloft which must be examined when extension area is involved
with fire.
21
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
22
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
ROWFRAMES
♦ CONSTRUCTION:
o Class 4, wood frame, as the name implies, are built in rows containing as many as twenty
or more buildings.
o When constructed, each builder may have used varying designs, i.e., with stoop similar to
brownstones but all wood; with or without cornices.
o These buildings can be either balloon frame or braced frame construction
o The salient feature common to all, regardless of variations in design, is the common
cockloft spreading over all the buildings in the row. This cockloft may vary in height
from one foot to a height tall enough for a man to stand in.
o These buildings can be considered large rectangular boxes of dry lumber, capable of
generating large amounts of heat when burning. There is danger of fire spreading in all
directions.
o Interior construction is similar to tenements and Brownstones, usually wood lathe and
plaster, wood studs; caps, and plates forming the outline for walls, door frames, etc.
o Exterior is wood or a veneer over outer wood sheathing. Fire can travel unseen in the air
space formed when vertical wood furring strips are used between a veneer and outer
sheathing.
♦ HEIGHT & AREA:
o Varying from two to five stories, are twenty to thirty feet in width, with depths ranging
from forty to sixty feet.
♦ TWO TYPES OF DESIGNS:
1. Brownstone Type:
o Generally have three front windows per floor
o One apartment going front to rear and no rear fire escape
2. Old Law Tenement Type:
o Four window front
o Two railroad apartments per floor
• The depth of the building will determine the size and number of
rooms.
o Rear fire escape
o There may be a dumbwaiter shaft present.
o The presence of light shafts is also a possibility.
23
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
24
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
25
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
o The major defects or faults in the construction are the lack of the fire stopping and the
vast quantity of combustible material used in the construction. Fire can spread in the
following manner:
A. Vertically
3. Auto exposure via front and rear windows, and via siding,
5. Via false fronts, bay windows, spaces between sheathing and building.
B. Horizontally
1. Via the common cockloft from one building to another. As the heat from the fire on
a lower floor increases in intensity, the temperature rises rapidly. Smoke and heat
will then spread laterally throughout the entire cockloft area. An extremely intense
fire will develop in short order. Identifying those buildings already involved will be
made more difficult, since we will already have heavy smoke throughout the
cockloft.
3. Thin and flimsy walls between buildings will present no stop to fire spread.
4. In those with cellars common to more than one building, fire will involve both if the
fire is of any consequence.
5. Presence of a store, and the type of business, may add to the fire. Tin ceilings make
opening up more difficult.
6. Wood cellar beams in adjoining buildings, resting on a common wall, may spread
fire where they butt.
7. Fire may also spread from the roof of the fire building to the roof of an adjoining
building by ignition of the roof covering.
26
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
A. A heavy fire in the cockloft will burn roof supports and cause the collapse
of the roof into the top floor.
B. Rear walls can pull away from the building and collapse in one section
into the yard. Personnel will have to be alert to the possibility.
E. The weight of a fire escape can cause a complete collapse of an exterior wall.
F. Brick veneer and stucco facing can collapse in sections or as a complete unit.
G. Steel plating attached on interior and exterior walls for security purposes
adds additional weight increasing collapse potential.
H. When a serious fire burns out the entire first floor, there is danger of
collapse, especially in corner buildings and buildings standing alone.
27
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
28
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
PRIVATE DWELLINGS
♦ BUILT: ...........................................Originally for one or two families
29
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
♦ Dwellings built on sloped terrain can cause communication and operational problems.
SPECIFIC DESCRIPTIONS
♦ Straight Line Colonial
O Typically 2½ to 3 story and 20'x40'
O Balloon frame construction is commonly
found.
O The side door generally gives access to the
kitchen and to the cellar stairway.
O The utilities are found in the cellar.
O The 1st floor has a front porch area, a living
room with an open stairway to the 2nd floor,
a dining room, and a kitchen in the rear.
O The kitchen contains the stairway leading to the side door and cellar.
O The 2nd floor has 2 or 3 bedrooms, a bathroom, and
access to the attic.
This access space can be as large as a
normal stairway or as small as a hatch in a
closet.
O Due to the limited ventilation of the attic/3rd floor,
conditions in this area will be extremely punishing.
o The roof of the front porch allows for easy access to
upper floor bedrooms.
30
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
♦ Queen Anne
o 2½ to 3½ stories in height
o 25’ to 30’ wide & 30’ to 50’ deep
o Construction is wood frame with
exteriors of wood siding, asphalt
shingles, brick veneer, or stucco.
o The roofs have many peaks,
dormers, overhanging eaves and
possibly a cupola.
o (A cupola/turret is a tower-like
room with a round or dome
shaped roof).
o Multiple variations in size and
number of dormers and gables
create a maze of peaks and
valleys at roof level.
o Balloon construction is most
common and early attempts at built-in fire stopping are negated by poor workmanship,
open holes for house service lines, etc.
o A narrow rear or side stair connects the 1st, 2nd, and 3rd floors, or a stair may lead directly
to the 3rd floor from the 1st floor.
o Vertical arteries supplied by old hot air ducts, dumbwaiter shafts, boxed in space around
fireplaces and the usual pipe recesses, contribute to undetected and fast upward fire
travel.
o They may have a fire escape or a sprinklered stairway.
31
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
o The fire escape will be attached to a combustible wall and its use shall be carefully
considered if that wall is exposed to, or involved in fire.
1. Under the porch area may be a ventilation point. Cellar windows rarely exist here. When
they do, they may be inaccessible. Windows may exist in the rear, however.
2. Open area permits ventilation and easy access to the first floor.
3. Enclosed porch inhibits access and ventilation.
4. Roof overhang(eaves) can permit fire to extend into the attic if fire has vented out a
window. Three levels of eaves are shown.
5. &6 Sharply pitched roof with many peaks and gables is difficult to walk on.
7. Rear and side extensions may present many other means of entry and escape. An outside
cellar entrance usually exists at the rear or side.
32
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
33
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
With attached homes it is not always This photo shows the rear of the attached
apparent from the front what conditions homes shown in the photo to the left.
may be in the rear. Another concern is Note the difference in height in the rear.
proper identification of the fire floor.
o In most cases, it is readily apparent from street level that these structures have flat roofs.
However, in some areas of the city, flat roof structures have a decorative peak in the
front. The absence of a window in this peak may be an indication of a flat roof. Once it is
confirmed that the structure has a flat roof, all members must be informed. These
structures may have a skylight and/or scuttle.
34
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
♦ SPECIAL CONSIDERATIONS
The following are common in private dwellings and create special fire safety and fire fighting
problems:
o Cellar areas used as living quarters with no secondary means of egress.
o Lack of a secondary means of egress from upper floors. Interior stairs are often narrow
and sometimes winding. Landings are small; thus restricting movement of the operating
forces and making an interior attack more difficult. CONTROL AND MANAGEMENT
OF THE INTERIOR STAIRS IS CRITICAL TO A SUCCESSFUL OPERATION.
o In some dwellings the stairs to the attic or third floor are found behind a small door
resembling a closet door. In other homes, access to the attic is via a pull down type stairs
with a rope attached for ease of use. Access may also be found in a bedroom closet with
no ladder provided.
o When it is obvious that the dwelling has two or more families (separate entrances,
multiple mailboxes, etc.) bedrooms can be found on all floors.
o Attached and built-in garages may have a door that opens directly into the house which
can be avenues for fire extension. Storage of automobiles, flammable liquids, propane,
lawn or pool chemicals may be found. Some attached garages may also be converted to
living spaces.
o Alterations and repairs using sub-standard materials and faulty workmanship.
o Fires involving the electrical service may energize the aluminum siding. A ground is
completed when an aluminum ladder is placed against, or a firefighter makes contact
with, the siding.
o Use extreme caution when operating with aluminum ladders in proximity to overhead
electrical service. Power lines may burn through when exposed to heavy fire conditions
causing live wires to fall to the ground. If these wires fall on a chain link fence, the entire
fence may become energized.
o Thoroughly examine areas under windows (especially when found in the open position),
and porch roofs, as victims may have jumped prior to the arrival of units. These victims
may be easily overlooked if trees and bushes surround the house.
o Central air conditioning systems may spread smoke and toxic gases throughout the
building. Dual heat and air-conditioning units will be in operation throughout the year.
35
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
T he term "Taxpayer" is not defined or recognized in the building code. The term
originally referred to the practice of real estate investors who, while holding land for
speculation, resorted to minimal investment in construction to produce income to offset
the cost of taxes. These structures were usually of cheap and flimsy construction with little or no
fire retarding features.
Supermarkets and one story shopping centers of more recent construction do not fit the above
description but contain many of the inherent hazards associated with taxpayers. For the purpose
of this manual, they shall be considered "taxpayers."
A taxpayer building is commonly taken to mean a business structure one or two stories in height.
Their areas vary from 20' x 50' to areas of whole city blocks, the most common size being
approximately 100' x 100'.
They can be built on one or more lots with adjoining structures of greater heights on three sides.
These buildings are usually single structures commonly sheltering from one to as many as 15
different businesses with weak non-fire resistive partitions and no fire stops in the cocklofts.
36
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
37
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
♦ An indication that a fire may have been "cooking" for some time prior to receipt of an alarm
by this department, is an alarm received in the early morning hours, after the occupancy has
been closed since the night before or longer. This calls for a more careful assessment of a
plan of action before the commitment of forces since the factors of collapse or backdraft
must be considered.
CANOPIES OR MARQUEES
♦ These extensions are generally supported by cables, steel tie rods or steel beams, which go
through the wall and are attached inside the building, probably to combustible members in
the cockloft. A fire in the cockloft can weaken these attachments or supports, causing sudden
collapse of the canopy or marquee and a long section of the parapet wall, without any
warning. Six firefighters lost their lives in the collapse of such a marquee and parapet wall at
a furniture store fire in 1956.
o Marquees are hollow boxes which can fill up with run-off water at a fire operation
due to use of heavy streams. A 12' x 24' marquee, 4' deep, when filled would contain
approximately 35 tons of water. In effect, a hanging swimming pool. Marquees are
required by the building code to have drainage facilities. Many have been found to
have roof type gutters and down spouts blocked with debris, rubbish and rubber balls.
ACCESS TO CELLAR AREAS
♦ Outside sidewalk trap doors in front of the stores give access to wooden, iron or masonry
stairs, straight iron ladders and chutes or conveyors for stock delivery.
o The chutes, when not in use, may be folded against the wall alongside the cellar
stairs. After units have been committed to cellar operations down such stairs, these
chutes can fall, covering the stairs. This will make it difficult to evacuate the cellar in
an emergency.
♦ Outside cellar stairs are usually found in the rear of taxpayers. When there are several stores
in the building, these stairs may lead to a passageway along the rear cellar wall from which
access can be gained to the various storage areas.
♦ Outside sidewalk or interior elevators.
♦ Interior stairs, trapdoors or chutes and conveyors.
♦ Windows to cellars and basement in taxpayers are usually below grade in depressed areas
that are covered with gratings.
♦ In the older type taxpayers, the flooring of the first floor may not be extended under the
raised front window display area. By removing the paneling under these windows an opening
for ventilation and water application can be gained.
38
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
CELLAR AREAS
♦ Cellar areas are often divided into a maze of storage spaces. The layout often does not
necessarily conform to the store layout. One occupancy may use a large section of the cellar
with openings through partitions, while other occupancies may use smaller areas or none at
all.
♦ Cellar ceilings are required to be fire retarded but the plaster covering may be deficient.
Partition walls between cellars are usually of combustible or flimsy construction and joist
channels at cellar ceilings are often not fire-stopped allowing fire, combustible gas and
smoke extension from cellar to cellar.
CELLAR CONTENTS
♦ May include flammable, fast burning ♦ Heating furnace rooms and oil
or poisonous materials, and/or storage tanks.
pressurized containers.
♦ Electrical supply entrance points
♦ Large amounts of stock piled to the with panel boxes and large amounts
ceiling with very little aisle space. of wiring.
♦ Refrigeration machinery and piping. ♦ Gas supply with gas meters and
piping.
♦ Walk-in refrigerated areas.
COCKLOFTS
♦ Usually is a common area extending over all the stores in the structure.
♦ Can vary in height from four inches to more than six feet.
COLUMNS
♦ Can be made from wood, cast iron, lally columns (steel or cast iron) or masonry piers
which support the beams.
o Cast iron columns are unpredictable and fail, on the average, in about thirty
(30) minutes in fire endurance tests. Some columns fail sooner than cast iron
columns. The failure of a column is generally more serious than the failure of
a girder or beam. The failure of a column in the cellar can cause the
subsequent collapse of the floors and roof. Coating or spraying the columns
with fire proofing material on new type construction is often a haphazard
process, because of shoddy workmanship and on-the-job alterations made
after application.
39
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
COLLAPSE
♦ The following may be causes of collapse during fire operations in taxpayers:
o Backdrafts blowing out walls or floor.
o Weakened and burned out structural members.
o Heating of unprotected structural members.
o Accumulation of a large volume of water on a floor or in a ceiling.
o Presence of water absorbent materials such as rags, paper, clothing, which
increase floor loads when wet and which may push out walls by expansion
from the absorbed water.
o Impact load: An object such as a gas heater falling from the ceiling, or a
firefighter jumping onto a roof or floor which has been weakened by fire may
be enough to cause collapse. An impact load has a much greater effect than
the same weight carried as a static (stationary) load.
o Vibration or movement in or near a weakened building.
o Water, ice or snow loads on the roof.
40
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
Some of the warning signs that will signal a potential structural collapse:
o Heavy body of fire which has been burning out of control for 20 minutes or more,
particularly in a large open floor area.
o Unsupported walls.
o Sagging or bulging walls. One cubic foot of brickwork weighs about 100 pounds.
Multiply this by the expected area of wall collapse and we are dealing with a vast
total weight.
o Cracking or groaning noises which may indicate strain being placed on structural
members.
o Presence of heavy equipment or signs on the roof. These are examples of static
loads. They pose especially dangerous collapse potential when their supporting
structural members are subject to heavy fire conditions.
o Heavy floor loading. Floor loads vary with the occupancies. Display cases loaded
with merchandise or the presence of heavy stock or equipment such as ice boxes,
freezers, and counter must be taken into account.
o Spongy or soft feeling, as you walk on the roof. The inverted or raised roof is
inherently spongy. A realistic appraisal must be made.
41
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
CONSTRUCTION
♦ Instability of the structure may not be obvious during fire operations because
structural elements are covered by finishing material or obscured by smoke
conditions.
NEW TYPE CONSTRUCTION
♦ The new type of construction (supermarkets, etc.) is much better than the traditional
or older type from a fire protection view point.
o Many of the newer type taxpayers are built on a concrete slab foundation, which
removes a major problem of cellar and basement fires. The partition walls are
usually better constructed due to the use of the steel and aluminum stud system
which employs gypsum blocks and sheathing as a bearing or nonbearing wall
system.
o The roof system will remain a major fire fighting factor because, for the most
part, the roofs are constructed of "Bar Joists," light weight steel or flat wood
trusses.
EXIT FACILITIES
♦ In both the older and newer taxpayer, exit facilities are poor.
o In the smaller type store establishments there is usually only one means of
entrance and exit; the main store opening.
o In the larger type occupancy (supermarkets, etc.), there are two means of egress.
The customers, however, are aware of the main entrance only, since the secondary
exit is usually remote or obscure. The entrance may consist of only two doors to
as many as six doors. Some of the newer types are automatic in operation,
opening inward and outward for the customers use.
o Depending on access, use and location, there may be a second means of egress in
the rear of the store from a storage, utility or delivery area. This exit is not readily
available or accessible for public use.
o In supermarket and discount type store occupancies the obstruction of exit
accessibility can be anticipated due to the presence of checkout counters, stock
displays and shopping carts.
42
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
FIRE EXTENSION
♦ Horizontal Spread:
o Via common cockloft. o Butted joists.
o Through flimsy partitions. o Common ceiling.
o Between the beams in ceilings. o "I" beams.
o Via hanging ceilings. o Party walls.
o Via ducts-air conditioning,
heating, vent ducts
♦ Vertical Spread.
o Via ducts. o Convection -mushrooming at
upper levels.
o Via pipe recesses.
o Shafts- light and ventilation
o Through ceilings.
shafts from interior bathrooms
o Via concealed spaces between and offices.
furred plaster and brick walls.
o Stock conveyor belts and chutes
o Via open stairs or trap-doors. from cellars.
o Via voids.
FLOORS
♦ The most common type floors are tongue and groove boards or plywood, supported
by wood floor joists.
♦ Heavy terrazzo or concrete placed over a wood joist floor can possibly create an
exceptionally hazardous condition. A fire in the cellar may weaken floor supports
with little evidence of heat conditions on the first floor. These floors are difficult to
ventilate to allow early advance of cellar lines or use of cellar pipes and distributors.
Sudden failure due to weight on the floor is possible.
♦ Paneling under display windows at street fronts can sometimes be removed to offer
easy ventilation and stream operation points for cellar fires. The flooring under the
raised display platform is sometimes omitted behind these panels.
o In newer type taxpayer slab construction, concrete floors are prevalent on
ground level with no basements or cellars in the buildings.
43
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
HAZARDOUS MATERIALS
♦ By looking at the occupancy signs, or through knowledge gained during building
inspection, units should be aware of the presence of hazardous materials. This will
alert them to the precautions that must be taken before starting operations.
♦ Some occupancies containing hazardous materials are:
o Drug Stores. The presence of combustible, explosive, and flammable
materials, which if mixed with each other, or if water is applied, or if
exposed to the heat of a fire, may unleash poisonous or corrosive fumes or
create an explosion or an explosive atmosphere.
o Paint Stores. They present the problems of various combustibles or
flammables such as paints, lacquers, varnishes, etc., in containers of
various sizes.
o Supermarkets. They have many different aerosol sprays, refrigerants,
compressed cylinders, lye in containers and other corrosives and caustics.
o Bakeries. They have large ovens. The potential for extensive gas leaks
from broken or burned away piping presents the potential for a highly
combustible atmosphere and a gas explosion.
o Swimming Pool Supply Stores. They have large stocks of oxidizing agents
which in the presence of fire and limited water supply pose the possibility
of rapid fire involvement and the release of gases such as chlorine.
o Smoke Shops are prevalent in many areas of the city. Various drug
paraphernalia are commonly stored and sold out of these shops. Among
the substances stored and sold are: ether in pint bottles, small butane
cylinders (packed in cases) and in some cases acetone in small bottles.
Most of the stores have roll down security doors, but can be identified by
advertising signs denoting them as Smoke Shops.
♦ It is recommended that any units encountering a fire in these occupancies stretch 2 ½"
line and proceed with extreme caution. Consideration should be given to knocking
down the fire from sidewalk area before entry is attempted.
44
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
LIFE HAZARDS
♦ Life hazard in two story taxpayers can be a serious problem on the second floor.
Occupancies such as restaurants, private clubs, dance halls, etc., open to large
numbers of people unfamiliar with the means of egress. Security measures may also
be a factor effecting means of egress.
MEZZANINE AREA
♦ Found in some taxpayers. Their location, area and use will differ. In most cases used
for storage of goods, but it can contain offices (predominant in supermarkets and
factories) and also sales areas to which the public will have access.
♦ Since these areas have probably been added to the premises after the original
construction date, the load bearing components can be of light construction.
o These supports may be loaded beyond their safe load bearing capabilities.
♦ The height of the ceilings in the mezzanine and the area below will be below average.
♦ In the majority of the mezzanines this area will not be enclosed.
45
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
ROOFS
♦ Roofs built in step fashion with one store roof slightly higher than another sometimes
give the false impression of fire division walls. The side walls of such protrusions are
made of wood sheathing and are easily detected by striking them with a tool to
differentiate them from a masonry wall. They can be opened for inspection or stream
operation.
♦ Trusses:
Truss construction is used where large areas, free of roof support columns, are
desired. As spans and loads increase, structural components must increase in size
to absorb and transmit to bearing surfaces the stresses of tension and
compression. The truss was developed to allow greater spans while minimizing
the increase in the size of the spanning members. Basically, the truss is composed
of two major members -the top one is called the TOP CHORD and the lower one
called the BOTTOM CHORD. Shorter members, called WEBS, connect the top
and bottom chords. The WEBS are placed vertically and diagonally, forming
triangular configurations with the CHORD members. There are many variations
but all are essentially the same; a combination of interdependent components used
to span large distances through the use of smaller pieces fastened together.
Trusses can be either wood or steel. The open web joist or steel bar
Joist prevalent in modern taxpayer construction is a light weight parallel
chord truss. The type of truss and the material used varies with the needs of the
particular application.
♦ Skylights:
o On some roofs the skylights, scuttles & other openings have additional
security materials, such as, heavy metal grates, steel plates & electrically
charged grids.
o If any of these appurtenances are removed & the area covered over, the
supports for these coverings may be of very light weight (sometimes wooden
2 x 4’s covered with thin sheets of plywood). In a fire situation these supports
will fail much more rapidly than the regular beams.
o In some cases heavy steel plates are being used to cover these openings
♦ Ventilators or exhaust ducts are sometimes found on the roof
♦ Large display signs on rods or front walls can present a collapse hazard.
SUSPENDED CEILINGS
♦ As many as two or three dropped ceilings may be found in a particular store.
46
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
47
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
SECURITY DOORS
♦ Typical of these installations are the familiar metal overhead rolling doors which
cover the entire store or building front.
♦ It is common to find six case hardened padlocks securing one of these doors. The
locks defy our conventional methods for forcing them open, and they must be cut
with a power saw or a torch.
♦ The weight that is added to the front walls, especially when these doors are in the
open position, can cause the lintel over the store front to fail and the wall and door
assembly may fall during a fire.
♦ Store fronts covered by overhead doors have presented the following problems:
A. Delayed discovery of the fire causing:
■ Greater severity of fire upon arrival with possible extension.
■ Possible early collapse in parts of the structure.
■ Possibility of a smoke explosion (backdraft) when entry is made,
causing a collapse with resulting injuries to members and fire
involvement of the entire structure.
B. Delay in operations due to the following:
♦ Doors in the rear will be equipped with many strong security devices, such as the
same type overhead doors as are found in the front. Conventional doors will have two
or three strong door locks, plus strong metal bars across the inside of the door with
strong anchor supports, which are securely attached to the walls, and the doors.
48
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
♦ Problems with overhead type doors that depend on spring tension to counter balance
their weight will be encountered in structures as well as trucks. At fires in
warehouses, garages etc., heat can cause springs to loose tension. If these doors start
down without the counterbalance of fully tensioned springs they will come down with
tremendous force.
o When dealing with overhead type doors that may have been affected by fire
the following is suggested:
1. Avoid standing in door path.
2. Secure door from rolling by clamping vise grip pliers in track under roller
or place a ladder as a stop.
3. Check the integrity of overhead track as soon as conditions permit.
4. Attempting to force large overhead doors that have lost spring tension will
require lifting dead weight and normally may be futile. If door can be
opened electrically it should be serviced immediately.
♦ Treat every open overhead door for what it is - a heavy overhead hazard like air
conditioners, machinery trucks, etc
TRUSSES
♦ The open web joist or steel bar joist are prevalent in modern taxpayer construction.
WALLS
♦ Exterior bearing walls are constructed of brick, stone, concrete block and mortar.
o In some cases brick walls are only two courses wide in taxpayers. Differential
thermal expansion may cause a wall to bulge, expanding "I" beams can easily
upset masonry or stone walls which inherently have little lateral strength. A
close watch should be kept on such walls.
o Stone or block may spall due to heat or subsequent stream application.
♦ The stability of masonry walls is very much dependent on the integrity of the roof.
o The roof acts as a monolithic brace which ties the walls together. In effect the
roof is holding up the walls by providing lateral support.
� A collapse or disintegration of the roof removes this support and may
impart a lateral load, either pushing out, or pulling in, on the wall as
stresses are formed.
♦ A parapet wall is a continuation of an exterior wall, fire wall or party wall above the
roof line. The parapet section of the exterior walls may extend around the entire
perimeter of a building roof area.
o A particularly hazardous condition is the possible collapse of the front parapet
wall (e.g., any parapet wall facing a street; a corner building facing one, two
or three streets). This parapet wall is often unsupported laterally for a long
distance, receiving its support only at the ends where they tie into crosswalls.
49
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
o The weight of the parapet wall is supported by steel “I” beams or angle shapes
which span the openings for the display windows and entrance doors. Rust
formation and normal expansion and contraction of these steel lintels and frost
action in the parapet, weaken the mortar joints. "I" beams which support the
roof joists often butt against the front parapet. An uncontrolled fire in a
remote portion of the taxpayer or in the cockloft may be heating these "I"
beams causing their expansion and steadily pushing the parapet outward.
♦ Operations within the stores or operations at the front of the store such as forcible
entry, cellar pipe or hand lines, may have to be discontinued because of the condition
of the parapet wall.
o A long section of this wall often remains intact as the wall topples onto the
sidewalk. Members have been killed or injured by such wall collapses.
♦ Interior partition walls between stores are usually of wood stud construction, with
plaster or sheetrock covering, and are usually firestopped at the floor and the ceiling
by wood sills and plates. The plaster or sheetrock provides longitudinal rigidity for
these partition walls between the front and rear walls and roof. Removal of large
sections of plaster will weaken this bracing.
50
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
51
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
52
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
♦ CLASSIFICATION:
Buildings shall be classified as Class “E” when they are primarily occupied
for transacting business, e.g. office spaces, showrooms, banks, civic
administration, etc.
53
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
54
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
COMPARTMENTATION
The subdividing of floor areas by fire resistive separations into smaller spaces or
compartments, such as numerous enclosed offices as compared to open space cubicles
CORE CONSTRUCTION
A building in which the elevators, stairway and building support systems are grouped
together in one area of the building. This area could be in the center of the building as in
a center core building or on one of the sides of the building as in a side core building.
In buildings of this design, the second hose line may be used to prevent fire from
wrapping around the core, endangering the operation of the first line.
2
This is not a complete list of what is required of a class “E” system.
55
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
CURTAIN WALL
A non-bearing wall, built between piers or columns for the
enclosure of the structure, but not supported at each story.
“Q” DECKING
56
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
VACANTS
57
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
GENERAL DESCRIPTION
♦ For the purpose of this manual, a vacant building is a structure which is considered to
be completely unoccupied, where the owner has abandoned all efforts to maintain
the building. These buildings are typically open, unguarded, lack operating utilities
and are not maintained in a safe condition.
♦ Vacant buildings have all the construction defects and potential for fire spread that
they possessed when occupied. In addition, hazards above the normal have developed
as a result of deterioration caused by misuse, vandalism and previous fires.
♦ In vacant buildings, the life hazard is typically limited to firefighters. A slower, more
cautious operation should be initiated. Devote more time than usual must be devoted
to the size-up of the situation.
♦ The personal injury hazard to firefighters is of paramount importance. Items to be
considered are entrapment by rapid fire spread, falls, falling objects and partial and
complete structural collapse.
♦ A vacant building does not necessarily mean there is no civilian life hazard. Children,
derelicts, trespassers, workmen, squatters, etc., may be present.
♦ What may appear to be a vacant building could be occupied by one or more families.
In many cases this occupancy may not be evident from the front of the building
because the apartments in the rear of the building are the ones that are occupied.
♦ Indications of tenants in an apparent vacant building:
o Lights in windows of some apartments.
o Curtains, window shades, plants, window gates.
o Open doors or windows, or signs of forced entry in sealed building.
o Electric extension wires strung from utility pole, or through backyard
of adjoining building into windows of an apparently vacant building.
♦ Vacant building fires do not "just happen." They are caused by one or more
individuals who have no regard for the safety of the firefighter. Indeed, vacant
buildings have been "Booby Trapped" deliberately to injure or kill the unwary.
♦ More time than usual must be devoted to physical size-up of the building.
♦ The IC may implement an interior attack after a risk assessment has been
performed based on the following factors:
If interior operations are implemented, the operating force and interior operational
time shall be kept to a minimum with the maximum amount of supervision.
58
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
At large or advanced fires, the primary attack strategy should consist of a defensive exterior attack
and should focus on the protection of exposures. The IC may vary from this guideline in critical
situations involving life hazard.
59
FDNY Probationary Firefighters Manual
Chapter Nine BUILDING DESCRIPTIONS
60
F.D.N.Y.
PROBATIONARY FIREFIGHTERS MANUAL
VOLUME II
DANIEL A. NIGRO
Fire Commissioner
Updated: 03/12/2021
PROBATIONARY FIREFIGHTERS MANUAL
TABLE OF CONTENTS – VOLUME TWO
CHAPTER SUBJECT
10. HYDRANTS
11. ENGINE COMPANY TOOLS & APPLIANCES
12. ENGINE COMPANY OPERATIONS
13. STANDPIPE & SPRINKLER OPERATIONS
14. LADDER COMPANY TOOLS
15. PORTABLE LADDERS
16. LADDER COMPANY OPERATIONS
17. EMERGENCIES
18. ELEVATOR EMERGENCIES
19. NON-STRUCTURAL FIRES
20. FOAM
21. PORTABLE FIRE EXTINGUISHERS
22. HOUSEWATCH
23. DECONTAMINATION
24. EMERGENCY OPERATIONS
25. BISP WORKBOOK
26. AUC 323
Probationary Firefighters Manual
Chapter 10
HYDRANTS
10
HYDRANTS
HYDRANTS
Hydrants are the primary source of water for firefighting operations. There are several types of
hydrants available in NYC, which may be equipped with a variety of features, as described
below.
1. TYPES OF HYDRANTS
1.2 Smith Low Pressure Hydrant - The Smith hydrant has a black barrel with a
silver bonnet. There are two outlets, one 2 1/2 inch and one 4 1/2 inch. This
hydrant is equipped with two valves, a main and a drain which are both activated
by the operating nut on top of the hydrant. The number on the barrel of the
hydrant indicates the size of the main supplying the hydrant. A white line under
the number on the barrel indicates this hydrant is on a dead end main and is only
supplied from one direction. Dead end mains are generally smaller in diameter
and provide less water than mains fed from two directions (see Fig. 1-1).
1.3 Dresser Low Pressure Hydrant - The Dresser hydrant differs from the Smith in
appearance but its operation is the same. The barrel is painted black and the
bonnet silver and it is provided with two outlets, one 2 1/2 inch and one 4 1/2
inch. This hydrant also has two valves (main and drain) which are activated by
the operating nut.
1
FDNY Probationary Firefighters Manual
Chapter Ten HYDRANTS
FIG. 2 FIG. 3
FIG. 4 FIG. 5
2
FDNY Probationary Firefighters Manual
Chapter Ten HYDRANTS
3. Hydrant features
3.1 Hydrant Markings - Some hydrants may be marked with a white number on the barrel,
which indicates the size of the main supplying the hydrant (in inches). A white line under
the number on the barrel indicates the hydrant is on a dead end main and is only supplied
from one direction, which may limit water flow.
3.2 Breakaway Feature - Some hydrants have a “breakaway” feature, which was designed as
a safety feature to minimize damage to the hydrant system if a hydrant is struck by a
vehicle. These hydrants will have a “collar” fitted on the lower portion of the barrel which,
when broken, will cause the water supply to the hydrant to be shut down. It is sometimes
possible to find this collar buried beneath concrete surrounding a hydrant.
3.3 Curb Valve - Hydrants are equipped with a curb valve, which provides a means to shut the
water supply to a hydrant from the water main. These valves are generally located in the
street, near the hydrant and require a special curb valve key to shut down. The curb valve
key is turned clockwise to shut the valve.
3.4 Hydra-Shield – This is a threaded hydrant cap with three indentations on its surface.
Except for the three tapered indentations, the cap has a smooth rounded surface which
prevents removal using conventional tools. The hydrant wrench matches the indentations
on both the 2 1/2 inch and 4 1/2 inch caps. (see Figure 6)
3.5 Custodian Hydrant Guard – This is a free spinning cap which completely covers the
hydrant operating nut to prevent it from being turned on by unauthorized users. The
Custodian hydrant wrench, which is equipped with an internal magnet, is needed to open
the hydrant. (see Figure 7)
3.6 Hydrant Drain - After the hydrant is shut, the residual water in the barrel will drain out
into the ground by way of a small hole in the bottom of the barrel. This hole is the hydrant
drain and, if blocked, it may not completely drain.
3.7 Hydrant Discs - If a hydrant is found to be unserviceable, it should have a white disc
attached to one of the outlets. A frozen hydrant should have a yellow disc attached. Blue
discs are reserved for use on partially OOS auxiliary fire protection systems (standpipe and
sprinkler systems). The company number and individual disc number shall be marked in
black on one side of each disc.
3.8 Hydrant Caps – All hydrants should be equipped with caps on both the 2 ½” and 4 ½”
outlets. This minimizes damage to the hydrant and limits possible obstructions inside the
barrel.
3
FDNY Probationary Firefighters Manual
Chapter Ten HYDRANTS
Fig. 6 Fig. 7
Figure 8
4
FDNY Probationary Firefighters Manual
Chapter Ten HYDRANTS
4.4 Wall Hydrants – Hydrants that are embedded in the wall of a building (Figure 9).
They closely resemble a Fire Department Connection (FDC), but should be
labeled as a hydrant. They are operated by turning an operating nut (often located
above the outlets).
Figure 9
5
Probationary Firefighters Manual
Chapter 11
OBJECTIVE: • To familiarize members with the uses of the tools and appliances
associated with Engine Companies.
FDNY REFERENCE: • FDNY Firefighting Procedures, Vol. 2, Book 1 – Engine Co. Ops.
Ch 3
• TB Tools 7, DS 2,9,12,17; TB Tools 11, DS 1,2,3; TB Tools 17
11
PART ONE
1 OVERVIEW.......... …………………………………………1
2 HOSE.................................. ………………………………...2
1.1 This chapter will describe the various equipment used by engine companies in the FDNY.
The aim of the chapter is to describe key physical attributes of each piece of equipment, as
well as its pertinent operating capabilities and capacity.
1.1.2 For information on the maintenance and routine inspections of hydrants, refer to
Chapter 3, Addendum 2: Hydrant Maintenance.
1.1.3 For information on the maintenance and annual testing of hose, refer to Chapter 11,
Addendum 2: Hose Maintenance.
1.1.4 For information on the equipment that exists as part of the water supply
infrastructure in NYC that is used by engine companies, specifically, this includes
hydrants, sprinkler systems, and standpipe systems, refer to Chapter 11,
Addendum 3: Water Supply Infrastructure Equipment
1
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
2. HOSE
2.1 Hose is the primary tool for the application and transfer of water in the FDNY. A variety
of different size and types of hose are used by units in the department. This section will
describe key characteristics of each type of hose used in the FDNY.
Figure 1
2.2.1 1 ¾” hose is the primary attack hose for firefighting operations in the FDNY. Its
smaller size and reduced weight provide the benefits of increased speed and
mobility while operating.
2.2.2 1 ¾” hose is carried on the hosebeds of all engine and squad companies for rapid
deployment at a fire or emergency operation.
2
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 2
2.3.1 2 ½” hose is the most versatile type of hose in the FDNY. It can be used as an attack
line at a fire or emergency. Additionally, it can be used as a supply line in a number
of situations.
2.3.2 2 ½” hose is carried on the hosebeds of all engine and squad companies for rapid
deployment at a fire or emergency operation.
2.3.3 When used as an attack line, 2 ½” hose provides increased water flow, but is heavier
and more difficult to maneuver than the 1 ¾” line.
3
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 3
2.4.3 It is only used as the lead (nozzle) length on the attack line when using a standpipe
system in residential buildings.
4
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 4
5
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 5
6
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
3.1 NOZZLES
3.1.1 A nozzle is a hose line appliance that is used to direct the flow of water,
increase the velocity of flow, or disperse water in various patterns. Nozzles are
identified by the type of water pattern created and size of the tip used.
3.3 A shut-off is the portion of the nozzle that contains a handle which controls the opening
and closing of the nozzle. Shut-offs may sometimes be equipped with a “pistol grip”
handle.
3.4 A tip is an attachable component that shapes the stream of water as it leaves the nozzle.
3.4.1 Tips can either be solid stream or fog stream and exist in a variety of different sizes.
3.4.2 Tips are also classified as Main Stream Tip (MST) or Outer Stream Tip (OST).
A. MST’s attach directly to the shut-off and have a threaded outlet orifice. In the
FDNY, nozzles to be used for fire attack are equipped with MST’s.
B. OST’s are smaller and can attach to the threaded outlet orifice of the MST. The
only OST used in the FDNY is the ½” tip. The OST should only be attached to
the MST for overhaul operations, if deemed necessary.
3.5 There are three basic metrics used to describe the performance of a nozzle:
3.5.1 Nozzle pressure - In order to create the desired stream, nozzles must be supplied
with sufficient pressure “at the tip”. This pressure is called nozzle pressure. It is
generally measured in psi (pounds per square inch).
3.5.2 Nozzle reaction - This is a metric that measures the reaction force of water flowing
through an open nozzle. It is a mathematically derived metric that is based on the
size of the tip and the supplied nozzle pressure. Nozzle reaction provides a standard
measure of how strong the force of the nozzle “feels”, which allows for comparison
between nozzles of different sizes. It is generally measured in pounds.
3.5.3 Flowrate – This is a measurement of how much water is discharged by the nozzle.
It is generally measured in gallons per minute.
7
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
3.6.2. 1 ¾” Nozzle
Figure 6
8
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
3.6.3 2 ½” Nozzle
Figure 7
9
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
3.6.4. 2” Nozzle
Figure 8
10
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
3.7.1. Fog nozzles can produce either a straight stream or a fog pattern (Figures 9, 10, 11
& 12). The straight stream is hollow. The fog pattern is adjusted by rotating the
outer barrel and the reach of the stream depends on the width of the pattern: when
the fog pattern is wider, the reach of the pattern will become shorter.
3.7.2. Removable fog tips may have a fixed fog pattern without the option of a straight
stream. These can be attached directly to a shut-off.
3.7.3. Fog patterns are effective for maximizing hydraulic ventilation, dispersing gas
vapors, and extinguishing fire near electrical equipment. However, fog patterns can
have limited stream reach and can entrain (draw in) air as they operate.
3.7.4. Fog nozzles used in the FDNY are classified in the following two ways:
A. Variable flow fog nozzles provide a different flowrate depending on the fog
pattern selected. All fog nozzles in the FDNY are variable flow.
B. Variable pressure (also called non-automatic) fog nozzles will allow their
nozzle pressure to change as the fog pattern is adjusted. All fog nozzles in the
FDNY are variable pressure.
11
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 9
12
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 10
13
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 11
14
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 12
15
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 13
A. The High-Rise Nozzle (Figure 13) is designed to be used from the floor below
the fire when standard interior handline attack methods are not possible, such
as conditions caused by wind-driven fires.
Figure 14
A. The cockloft nozzle (Figure 14) is primarily designed for use at cockloft fires,
but may also be used in other situations such as in a vertical application to
extinguish fire on the outside of a building from a window on the floor below.
When the cockloft nozzle is being used to extinguish fire in a cockloft, the
nozzle may be placed above the ceiling on the top floor of a building or inverted
and lowered into the cockloft area from the roof of the building.
16
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
3.7.11 The Combination Nozzle is a two-piece system that allows for the use of either a
High-Rise Nozzle attachment or a Cockloft Nozzle attachment to a single base pipe
section.
A. It is comprised of 3 different components, as follows:
1. Base Pipe – a 48” long aluminum alloy pipe with a 1 ½” diameter. It is
equipped with a permanently attached 2 ½” shutoff and has a 1 ½” quick
connect for attaching one of the two different nozzles (Figure 15). Attached to
the aluminum pipe is a support rod with a quick connect at the top and a T-
handle at the bottom. The Base pipe should be stored with the 1 ½” x 2 ½”
increaser attached to the 2 ½” shut off.
Figure 15
B. High Rise Nozzle (HRN) Tip - a 44” long aluminum pipe with a 68 degree, 2-
foot bend to provide the proper angle for the water stream (Figure 16). It has a
1 1/8” tip attached to its outlet and a 1 ½” quick connect at the bottom. The
HRN tip has a support rod attached with a quick connect.
Figure 16 Figure 17
C. Cockloft Nozzle Tip - a 32” long aluminum pipe divided at the tip into two
ninety-degree bends to provide the proper angle for the water stream (Figure
17). Each bend terminates with a 15/16” MST and a ½” OST. The two ½"
OSTs are NOT to be removed; these tips increase the reach of the stream in
excess of 60 feet. They also facilitate the generation of steam that enables a
more rapid extinguishment of fire in the confined spaces of a cockloft. The
Cockloft Nozzle tip has a support rod attached with a quick connect.
D. The Combination Nozzle has been issued to a number of companies in the field.
It is carried in a kit mounted above the portable ladder rack on the apparatus.
17
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Note: The original one piece HRN has not been removed from Companies
equipped with the Combination Nozzle. These Companies carry both so
that non-trained members can use the one piece HRN. Engine Companies
not trained in the use of the Combination Nozzle System should continue to
use the conventional High Rise Nozzle or Cockloft Nozzle as required.
3.8 FITTINGS
3.9 A fitting is a hose connection which allows dissimilar couplings to become coupled.
Specifically, fittings allow for different size couplings to be connected and for couplings
of the same sex to be connected.
3.10.1 Reducers – allow for larger male couplings to connect to smaller female couplings.
The male threaded orifice on a reducer is smaller than the female threaded orifice.
These are typically used for water to flow from a larger hose to a smaller
hose.(Figure 16A)
3.10.2 Increasers – allow for smaller male couplings to connect to larger female couplings.
The male threaded orifice on an increaser is larger than the female threaded orifice.
These are typically used for water to flow from a smaller hose to a larger hose
(Figure 16B).
Figure 17
3.10.4 Double females – allow for two male couplings of the same size to be connected
(Figure 18)
Figure 18
3.11 Fittings are available in all necessary sizes in each of the four categories above.
3.12 There also exists a fitting specially designed as a hydrant connection, which is a double
female with different sized couplings. One side has 4 ½” threads (for hydrant connection)
and the other side has 3” threads (for connection to a 3 ½” hose)
19
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 19
3.13 By using the proper fittings, any hose in the FDNY can be connected to any other hose. Be
aware that multiple fittings may have to be used to make coupling possible.
3.14 ADAPTERS
3.15 An adapter is a fitting that allows connection between a coupling with FDNY threads and
National Standard threads or between FDNY threads and National Pipe threads.
3.16.1 Adapter with a male FDNY coupling and female National Standard
(or National Pipe) coupling
3.16.2 Adapter with a female FDNY coupling and male National Standard
(or National Pipe) coupling
3.16.3 Double male adapter, with a male FDNY coupling and male National Standard
(or National Pipe) coupling
3.16.4 Double female adapter, with a female FDNY coupling and female National
Standard (or National Pipe) coupling
20
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
3.17 National Pipe threads (NPT) adapter can be differentiated by the length of the threaded
coupling; National Pipe threads (Figure 20) are longer (deeper) than FDNY or National
Standard (NST) threads (Figure 21).
Figure 20 Figure 21
4.1.1 The Digital In-Line Pressure/Flow metering device (Digital In-line Gauge) is used
to monitor the pressure and flow being delivered from the standpipe outlet. It does
not regulate water flow; it simply monitors the pressure and flow of the water
supplied (Figure 22)
Figure 22
21
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
4.1.2 The Digital In-line Gauge has 2 ½” couplings and has a built-in 45-degree elbow.
4.1.3 To turn the gauge on, press and hold the green ON/OFF button. The digital display
will show “- - - -” under PRESSURE and "r3.00" above FLOW. When the button
is released, the digital display will show “0” PRESSURE and “0” FLOW. The
gauge is now ready to be used. (Figure 23)
Figure 23
4.1.4 The red digital display shows the pressure at the gauge in psi.
A. High Pressure Warning: red display flashes “HI-P” when pressure exceeds 200
psi.
4.1.5 The blue digital display shows water flow at the gauge in GPM.
A. High Flow Warning: blue display flashes “HI-F” when flow exceeds 250 GPM.
B. Low Flow Warning: blue display flashes “LO-F” when flow is less than 80
GPM.
4.1.6 If there is no water flow for 15 minutes, the display goes into “sleep” mode and
will not display any readings. Resumed water flow automatically re-activates the
display. If there is no water flow for 30 minutes, the display will power off
automatically. To resume operations, the gauge has to be re-started manually.
22
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
4.1.7 The Digital In-line Gauge is powered by a 9-volt rechargeable lithium ion battery
A. Only the supplied batteries (HIGHTECH RLI-9600 9V 600) may be used.
B. A fully charged battery will supply approximately 5 hours of continuous
operation.
C. After 3½ hours of usage, the digital display will slowly flash “LO batt”.
D. When 10 minutes of battery life remains, “LO batt” will flash rapidly.
Immediately replace the battery if this occurs.
E. To test the battery, press the “Battery” button. A battery in serviceable condition
will display as “Batt Good”.
F. Units are issued 4 batteries. One is used in the gauge, one is carried in the clear
battery pouch of the carrying case, and 2 are placed in the charging unit at
quarters.
G. Batteries on the charger should be rotated weekly and switched with the
batteries in the gauge and the carrying case.
H. The battery charger indicators are as follows:
1. Indicator is steady red color = the battery is charging
2. Indicator is slowly blinking red color = defective battery must be replaced
3. Indicator is steady green
Figure 24
23
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
4.2.1 The analog in-line pressure gauge is used to monitor the pressure being delivered
from the standpipe outlet.
A. Like the digital in-line gauge, it does not regulate water flow; it simply monitors
the pressure of the water supplied.
B. Unlike the digital in-line gauge, the analog gauge does not measure water flow
4.2.2 It has 2 ½” couplings and an analog dial to measure the supply pressure.
5.1 All Engine and Squad companies carry a foam eductor and nozzle capable of producing
finished firefighting foam.
5.2 The eductor and nozzle are carried together in a black pelican case. The foam nozzle can
be identified by white markings on the tip, handle, and pistol grip.
5.3 When supplied with 200 psi, it has a flow of 125 GPM.
5.4 Refer to Chapter 20, Foam for a full discussion of foam operations.
24
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 25
6.2 The multiversal has three stacked tips (2”, 1 ½”, 1 ¼”).
6.2.1 When the 1 ¼” tip is used, it will flow roughly 465 GPM with 100 psi at the tip
6.2.2 When the 1 ½” tip is used, it will flow roughly 560 GPM with 70 psi at the tip.
When supplied with 100 psi at the 1 ½” tip, it will flow roughly 660 GPM.
6.2.3 When the 2” tip is used, it will flow roughly 840 GPM with 50 psi at the tip
6.3 The multiversal has two 3” inlets. The maximum pressure to be supplied to the appliance
base is 200 psi.
25
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 26
7.1 The hose roller (Figure 26) is used to facilitate the hoisting of a hoseline over a windowsill
or parapet by eliminating the friction of the dry line being pulled over a window sill or roof
parapet during an exterior hose stretch.
7.2 When properly used, the hose roller should be placed over the windowsill or roof parapet
and secured to a substantial object using the attached rope.
Figure 27
26
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
7.4 The Bresnan Distributor (Figure 27) is an appliance carried by engine companies that
attaches to a hoseline to distribute water in a 360-degree pattern. It is designed to be used
remotely in a fire area that cannot be accessed by a hoseline. Generally, it is used for fires
below grade, such as cellar fires.
7.5 It is comprised of 9 angled ports for water delivery. When in operation, the angled force of
the water will cause the Bresnan distributor to spin, which maximizes the distribution of
water.
7.6 When supplied at 50 psi nozzle pressure, it will deliver 250 GPM of water.
7.7 The Bresnan distributor is supplied with a 2 ½” hose. A shut-off should be placed one
length from the distributor, allowing flow to the distributor to be controlled.
7.8 To properly use the Bresnan distributor, it should be lowered into the fire area via an
opening and the shut-off should be opened to begin water flow. The distributor is lowered
until it hits the floor, then raised several feet to position for optimal distribution.
8.1 SINGLE GATE: The primary function of a single gate (also called “one-way gate”) is to
enable firefighters to control the flow of water at a point other than the water source
itself. By using a single gate, flow can be augmented, or even halted, without having to
shut down the water source itself. (Figure 28)
Figure 28
8.2 Commonly, single gates are used on the 2 ½” outlet of a hydrant, but they are also often
used to control flow from standpipe outlets, deck guns, or multiversals.
27
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
8.3 Single gates exist in a number of different sizes for use on hydrants, standpipe outlets, or
other appliances (such as a deck pipe or multiversal).
8.4 To use a single gate, it must be attached before the water source is turned on. Once attached,
the water source is opened and the flow can be controlled at the single gate.
8.5 GATED WYE: The primary function of a gated wye is to allow a single source of
water to supply two separate hoselines. A gated wye has one inlet and two outlets. Each
outlet is equipped with a gate that allows for the control of water flow.(Figure 29 a & b)
Figure 29 a Figure 29 b
8.6 Commonly, gated wyes can be found attached to an outlet on fire apparatus, most often on
the front pumper. Gated wyes can also be attached to a hydrant, or attached to a hoseline
to facilitate the stretching and operation of multiple hoselines.
8.7 Gated wyes exist in all available sizes, from 4 ½” to 1 ½”. The most common size has one
2½” inlet and two 1 ½” outlets and is often found on the front outlet of the apparatus.
8.8 To use a gated wye, it must be attached before the water source is turned on. Once
attached, water flow can be controlled by the quarter-turn ball valve at each outlet. Units
should be aware that when two hoselines are operating from a gated wye and one of
those hoselines is shut down, backpressure may impact the other operating hoseline.
28
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 30
8.10 Siamese connections are not typically carried on engine apparatus in the FDNY, but they
are carried by aerial ladder apparatus for use with their ladder pipe.
8.11 The Siamese used in the FDNY has two 3” inlets and one 3” outlet. It is used in conjunction
with a single gate to supply the 3 ½” hose used when an aerial ladder pipe is placed in
operation.
29
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
9.1 The primary function of a spanner wrench (Figure 30) is to tighten and loosen
hose couplings.
Figure 30
9.2 Every firefighter is issued a spanner wrench and is required to carry it with them at a fire
operation.
9.4 A spanner wrench is used by gripping the lugs to tighten or loosen the coupling. While a
single spanner can be used, it is most effective to use two spanners together, facing opposite
each other and pulled in opposite directions.
30
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
9.6 The primary function of a hose strap is to secure a hoseline that has been stretched
a distance vertically, with the purpose of preventing the hose from falling back down
the vertical space through which it was stretched.
9.7 Hose straps are commonly used when performing a well-hole stretch, fire escape stretch,
or a rope stretch.
9.8 Every firefighter is issued a hose strap and is required to carry it with them at a fire
operation. Two basic types of hose strap exist:
9.8.1 Rope hose strap with hook - One end has a metal hook and the opposite end has a
loop in the rope (Figure 31A)
9.8.2 Nylon hose strap with carabiner - One end has a carabiner and the opposite end
has a loop in the nylon strap. There are a number of small metal loops on the strap,
which are not normally used when securing a hose (Figure 31B)
9.9 When used properly, the looped end of the hose strap secures the hose by using a girth
hitch. This uses the weight of the hose to tighten the grip of the hose strap. The carabiner
(or hook) end of the hose strap is used to attach to an anchor point. The hose strap is
attached to the anchor point by passing over the anchor point and is attached back to the
strap itself.
9.10 The ideal location on the hose to secure the hose strap is just below a coupling. This
minimizes the likelihood of the hose slipping through the girth hitch, while also relieving
pressure on the coupling.
31
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
10.1 There are two basic types of hydrant wrenches available, both of which are carried by all
engine and squad companies:
10.1.1 Custodian Hydrant Wrench - equipped with a magnetic cup (Figure 32A) that
allows the operation of hydrants equipped with a Custodian lock. It can also operate
Hydra-Shield equipped hydrant caps and can operate the standard 5-sided hydrant
operating nut. Hydrant is turned clockwise to open.
10.1.2 Standard Hydrant Wrench – Used to open the standard 5-sided hydrant operating
nut (Figure 32B). Hydrant is turned clockwise to open.
10.2 Curb Valve Keys (Figure 33) Carried by all engine and squad companies and is used to operate
the curb valve that controls water flow from the water main to a hydrant.
Figure 33
10.3 The wrench is placed over the operating nut and turned counter-clockwise to close.
32
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
11.1 Carried by all engine and squad companies. If the outlet threads of a hydrant are damaged
or missing, a hydrant plug can be used to close the 2 ½” outlet before using the hydrant.
11.2 The hydrant plug (Figure 34A) consists of a T-bolt, (which has a threaded rod) and a handle
with an attached rubber washer. The T-bolt may be equipped with a rope in case it falls
into the barrel of the hydrant during operation.
11.3 To use the hydrant plug, maneuver the T-bolt through the 4 ½” outlet into the hydrant barrel
(as pictured). Place the threaded rod out through the 2 ½” outlet, centering it in the middle
of the opening. Hold the T-Bolt firmly against the inside of the hydrant barrel with one
hand and turn the handle onto the threaded end of the T-Bolt with the other hand until
handle is tight to the barrel. The washer must be on the outside of the hydrant Figure 34B).
33
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 35
12.1 There are 3 different drafting connections on the apparatus (Figure 35):
12.2 Each of these connections is equipped with 6” couplings. The connection with a strainer
has a strainer on one end and a female coupling on the other. The other two connections
have one male and one female coupling.
12.3 When used for drafting, the connection with the strainer is lowered into the water and the
smooth connection is used to connect to the ungated inlet on the apparatus. The
3rd connection is to be used between them if more length is needed. Please refer to
Chapter 12: Engine Company Chauffeur for more information on drafting.
34
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 36
13.1 The “soft suction” is a black, semi-rigid hose used exclusively as a hydrant connection.
13.2 It is 10 feet long, has a 3 ½” diameter, and is equipped with two 4 ½” female couplings for
direct connection to a hydrant.
10-FOOT SEMI-RIGID 4 ½”
HYDRANT CONNECTION
Figure 37
Figure 37
13.4 It is 10 feet long, has a 4 ½” diameter, and is equipped with two 4 ½” female couplings for
direct connection to a hydrant. It is similar to the older 3 ½” soft suction connection, but is
more rigid and has a larger diameter.
35
FDNY Probationary Firefighter Manual
Chapter 11 ENGINE COMPANY EQUIPMENT
Figure 38
13.5 The 35-foot soft connection is a yellow, synthetic hose that is used exclusively as a hydrant
connection.
13.6 It is 35 feet long, has a 5” diameter, and is equipped with two 4 ½” female couplings for
direct connection to a hydrant.
36
Probationary Firefighters Manual
CHAPTER 11, ADDENDUM 1
EQUIPMENT INSPECTIONS
1.1 The following table lists each piece of engine company equipment, along with the
following information:
1.1.1 The inspection requirement for the equipment
Equipment Inspection
Hydrants Spring and Fall
Annual test, Spring and Fall
Hose
repacking
Annual test (in August),
Nozzles
Each tour
Digital In-line Gauge Each tour
Hose Strap Each tour
Hydrant Wrench Each tour
Spanner Wrench Each tour
10-foot Semi-rigid 4 ½” Connection Each tour
10-foot Soft 3 ½” Suction Each tour
35-foot Soft Hydrant Connection Each tour
Analog In-line Gauge Weekly
Adapters Weekly
Blitzfire Weekly
Bresnan Distributor Weekly
Cockloft Nozzle Weekly
Combination Nozzle Weekly
Curb Valve Wrench Weekly
Drafting Connections Weekly
Fittings Weekly
Foam Eductor and Nozzle Weekly
Gated Wye Weekly
High Rise Nozzle Weekly
Hose Roller Weekly
Hydrant Plug Weekly
New Yorker Multiversal Weekly
Single Gate Weekly
37
THIS PAGE INTENTIONALLY LEFT BLANK
Probationary Firefighters Manual
CHAPTER 11, ADDENDUM 2
HOSE MAINTENANCE
1. HOSE MAINTENANCE
1.1 This bulletin will outline the basic requirements of hose maintenance for all engine
companies in the FDNY. This includes the following:
2.1 Engine companies are required to maintain the amount of hose listed below. This amount
includes hose kept on the apparatus and hose maintained in quarters. Minimum
requirements are as follows:
2.1.1 20 lengths of 1 ¾” hose
2.1.2 1 length of 2” lightweight hose
2.1.3 3 lengths of 2 ½” lightweight hose
(Engines normally staffed with 5 FF’s should carry 4 lengths)
2.1.4 30 lengths of 2 ½” hose
2.1.5 10 lengths of 3 ½” hose
2.2 Additionally, hose is required to be carried on the apparatus in the following fashion:
2.2.1 1 length of 2” lightweight hose shall be arranged in a roll-up and maintained with
a 2” nozzle attached.
2.2.2 3 lengths of 2 ½” lightweight hose shall be arranged in a roll-up. One of these
lengths shall be maintained with a 2 ½” nozzle attached.
2.2.3 For companies staffed with 5 firefighters, 1 additional length of 2 ½” lightweight
hose must be carried, maintained as a roll-up.
2.3.4 At least 4 lengths of 1 ¾” hose shall be carried, either rolled or arranged in a roll-up.
One of these lengths shall be maintained with a 1 ¾” nozzle attached (to be used to
replace a burst length or to add to a short stretch).
39
FDNY Probationary Firefighters manual
Chapter 11 Add 2 HOSE MAINTENANCE
3. HOSE PACKING
3.1 When carried on the apparatus or stored in quarters, hose can be maintained in several
different arrangements, as described in the following sections.
3.1.2 No more than six lengths of 1 3/4 inch hose shall be used as lead lengths in any
hose stretch. Greater friction loss in 1 3/4 inch hose precludes the use of
more lengths without the danger of exceeding the maximum permissible
working pressure of 250 psi.
3.1.3 When loading hose, fold it neatly, compactly and uniformly. Loading hose
correctly allows the hose to play out properly and at the same time indicates to the
public and to the Department, the state of supervision and spirit of the company.
3.2.1 Hose is carried in the hosebeds of all engine apparatus in a traditional hosebed
arrangement. This is created as follows:
A. Load hose from left to right in the hosebed compartment
B. Begin on the left side with the coupling extended beyond the hosebed
C. Lay the hose straight back to the left rear of the compartment
D. Fold hose at the rear and bring back forward, veering slightly to the right
E. When at the front of the compartment, the hose should lie alongside the
coupling.
F. Fold the hose at the front and repeat the movement until the layer is complete
G. When a layer is finished, fold the hose at the right rear of the compartment and
bring forward diagonally to the front left to begin the next layer.
Figure 1
40
FDNY Probationary Firefighters manual
Chapter 11 Add 2 HOSE MAINTENANCE
Figure 2
3.3.1 The lead lengths of hose in a hosebed can be maintained in a horseshoe arrangement
to facilitate the hose stretch (Figure 2). This arrangement is created as follows:
A. Each horseshoe is comprised of exactly 1 length of hose
B. Place the hose on its edge on top of the hosebed
C. Fold the hose back and forth in the shape of a horseshoe
D. Completed horseshoes should be roughly 4 feet long
3.3.2 The horseshoe arrangement makes the hose easier to carry and ensures exactly 1
length of hose is carried.
3.3.3 The midpoint of the horseshoe can be located by grabbing the middle ring of the
horseshoe (Figure 3).
Figure 3
41
FDNY Probationary Firefighters manual
Chapter 11 Add 2 HOSE MAINTENANCE
3.4 Roll-ups
Figure 4
3.4.1 In order to facilitate the efficient deployment of hose when stretching from a
standpipe outlet, dedicated lengths of hose should be folded in a specific
arrangement, referred to as a “roll-up” (Figure 4).
Figure 5
42
FDNY Probationary Firefighters manual
Chapter 11 Add 2 HOSE MAINTENANCE
B. For the lead length, attach the nozzle and fold hose in half so that the nozzle tip
is even with the female coupling (Figure 5).
C. Bring the midpoint fold to the couplings (Figures 6A with nozzle and 6B).
Figure 6A Figure 6B
D. Bring the next fold up to the couplings over the midpoint fold (Figure 7
Figure 7
E. Lift the couplings (and the two folds of hose on top of them) and fold them over
on top of the remaining fold of hose.
43
FDNY Probationary Firefighters manual
Chapter 11 Add 2 HOSE MAINTENANCE
F. The folded hose should now be arranged with the couplings on top of the hose.
Facing couplings (while standing away from the hose, as pictured), the male
coupling is now on the right (Figure 8).
Figure 8
G. Secure completed folds with a strap connector on top
Figure 9
3.4.3 The roll-up makes the hose easy to carry, allows lengths to be easily connected to
each other, and facilitates a smooth deployment when stretched.
3.4.4 The midpoint of the hose can be identified by grabbing the hose fold located
directly beneath the couplings (Figure 10). This point is called the “A-fold” and is
painted red on all lightweight hose. Using this A-fold, the hose should be deployed
as discussed in Chapter 8: Standpipe Operations.
44
FDNY Probationary Firefighters manual
Chapter 11 Add 2 HOSE MAINTENANCE
Figure 10
3.5.1 Spare serviceable hose may be maintained in a rolled length when carried on the
apparatus or stored in quarters. This arrangement is created as follows:
A. Lay the hose out and fold the hose back on itself
B. Lay the male coupling on top, roughly 3 feet from the female coupling
C. Beginning at the folded end, roll the doubled hose towards the couplings
D. Rolled hose may be secured with a short piece of rope
Figure 11
45
FDNY Probationary Firefighters manual
Chapter 11 Add 2 HOSE MAINTENANCE
3.5.2 When hose is being placed out-of-service, it is arranged in a single roll (Figure 12).
The male coupling should be placed on the inside when single rolled. An over-
hand knot is to be tied 3' from the female coupling.
Figure 12
4.1 Hose should be removed and repacked in the spring and fall of each year, in accordance
with schedules issued by Division Commanders. Spare hose shall be used to replace hose
on the apparatus, when available.
4.2 Any hose 10 years old or older should be placed out-of-service. The first two digits of the
serial number stamped on the female coupling will indicate the year of manufacture.
4.3.1 Any hose of doubtful strength should be placed out-of-service. This may be due to
cuts, abrasions, wear, or burns to the hose jacket.
4.3.2 Couplings should not be cracked or out-of-round and there should be no burred
threads
4.3.3 All female couplings should have a rubber washer. Washers that are dried out or
cracked shall be replaced.
46
FDNY Probationary Firefighters manual
Chapter 11 Add 2 HOSE MAINTENANCE
6. HOSE OUT-OF-SERVICE
6.1 To place hose out of service, complete form RT-3 and attach it to the OOS hose.
6.2 Replacement hose is requisitioned from Fire Tools and Equipment (718) 391-9405.
47
THIS PAGE INTENTIONALLY LEFT BLANK
Probationary Firefighters Manual
CHAPTER 11, ADDENDUM 3
1.1 This section will discuss critical equipment that is regularly used by Engine
Companies, but is not carried on the engine apparatus. This equipment exists as part
of the water supply infrastructure of New York City and plays a vital role in Engine
Company Operations.
1.2 This section will provide a brief discussion of the physical specifications and key
equipment as it exists in the field. It is not intended to provide a comprehensive
description of the capabilities of the systems discussed, but rather a general
overview of key components.
2. SPRINKLER SYSTEMS
2.1 Sprinkler systems are found in a wide range of buildings and occupancies in NYC.
2.1.2 Wet pipe - Wet pipe sprinkler systems contain water in the riser and piping at all
times. When a sprinkler head activates, water is immediately discharged.
2.1.3 Dry pipe - Dry pipe systems are installed where there is a danger of freezing and
Contain air (or sometimes nitrogen) in the riser and piping. When a sprinkler head
activates, the air is exhausted through the open head, allowing water to be admitted
to the riser and piping.
49
FDNY Probationary Firefighters Manual
Chapter 11 Add 3 WATER SUPPLY INFRASTRUCTURE
3.1.4 Deluge - Deluge systems are often found in aircraft hangars or where large
quantities of flammable liquids are used in industrial processes. A "deluge" valve
opens upon an electrical signal received from a detector. In a deluge system, all
sprinkler heads (or nozzles) are open and will flow water simultaneously.
3.1.5 Pre-action - Pre-action systems are most often found in computer rooms or where
other sensitive electronic equipment is used. A pre-action type of sprinkler system
consists of fusible sprinkler heads, dry piping, and a valve which is opened upon
an electrical signal from a detector.
3.1.7 Non-automatic sprinkler systems depend solely upon the fire department to supply
water for firefighting. They are commonly found in cellars and sub-cellars of older
commercial buildings. These systems may contain fusible sprinkler heads, open
sprinkler heads, or even perforated pipes.
3.2 While many sprinkler systems will have a fire department connection (FDC) for FDNY
units to supply water, it is common to find a sprinkler system with no FDC. These systems
cannot be augmented by FDNY units.
3.3 Automatic sprinkler systems are identified by FDC or caps that are painted green. Non-
automatic sprinkler systems will have FDC or caps that are aluminum colored. Sprinkler
systems that are part of a combination system will have FDC or caps painted yellow.
3.4 While the flowrate provided by sprinkler heads will vary, a standard sprinkler head can be
expected to provide a flowrate of 13 – 18 GPM.
50
FDNY Probationary Firefighters Manual
Chapter 11 Add 3 WATER SUPPLY INFRASTRUCTURE
4. STANDPIPE SYSTEMS
4.1 A standpipe system is a system of piping installed in a building or other structure that serves
to transfer water to hose connections located throughout the structure for firefighting
purposes.
4.2 In NYC, the requirements for the presence of a standpipe system are described in the NYC
Building Code and are based on several criteria, primarily the height and area of the
structure.
4.3.1 According to national standards, standpipes are formally classified into 3 distinct
classes as follows:
A. Class I - Designed to be used by the fire department only. Equipped with 2 ½”
outlets only.
B. Class II - Designed to be used by trained, non-fire department personnel.
Equipped with 1 ½” outlets only.
C. Class III - Designed to be used by both the fire department and by trained, non-
fire department personnel. Equipped with both 2 ½” and 1 ½” outlets.
4.3.2 In NYC, nearly all standpipe systems are Class I systems. In several older
occupancies (such as theaters), Class III systems may still exist. Class II systems
are not compliant with NYC building code and should not exist in NYC.
4.4.1 Standpipe systems can be categorized as either “wet” or “dry”. Wet systems contain
water in the piping at all times. Dry systems do not contain water in the system
under normal conditions.
4.4.2 Standpipe systems can also be considered either “automatic” or “manual”. The
description of each type will depend on whether the system is wet or dry, as follows:
A. Automatic wet systems - capable of providing water under pressure at the
standpipe outlets, possibly with the assistance of a fire pump or a gravity tank.
B. Manual wet systems - connected to a small water supply that will maintain
water in the system, but is not capable of providing necessary operating pressure
to the system.
C. Automatic dry systems - usually supplied by a public water main, but are
maintained with pressurized air in the standpipe piping. When a decrease in air
pressure is detected in the system, water will automatically be supplied to the
system.
51
FDNY Probationary Firefighters Manual
Chapter 11 Add 3 WATER SUPPLY INFRASTRUCTURE
4.4.3 Air Pressurized Systems – a specific type of manual dry systems that are
maintained pressurized by a dedicated air compressor. These systems are required
in buildings under construction that are taller than 75 feet. When there is a change
in air pressure that exceeds a pre-determined threshold, an alarm will sound on site.
4.4.4 Combination systems - systems that supply both the standpipe system and an
automatic sprinkler system. The FDC or caps for combination systems are painted
yellow.
4.4.5 Multi-zone systems - standpipe systems that are vertically subdivided into zones to
limit the maximum operating pressure in the system. Each zone may have its own
FDC, or the entire system may be supplied from a single FDC.
4.4.6 Express Piping Systems - Some taller high-rise buildings may have separate “Low
Zone” and “High Zone” standpipe systems (Figure 5). These separate risers are not
interconnected and may have separate FDC. The FDC shall be identified with
signage stating either “Low Zone “or “High Zone” and indicate the floors they
serve. The High Zone riser is also known as “Express Piping”.
Figure 5
52
FDNY Probationary Firefighters Manual
Chapter 11 Add 3 WATER SUPPLY INFRASTRUCTURE
4.5.1 Standpipe systems include a variety of different components. The most significant
of these are described below. This list is not exhaustive and additional components
may exist.
Figure 6
53
FDNY Probationary Firefighters Manual
Chapter 11 Add 3 WATER SUPPLY INFRASTRUCTURE
4.5.3 Section valves - can be used to shut down water supply to a section of the standpipe
system (Figure 7). These are OS&Y type valves (Outside Stem & Yoke) and can
be located at various points in the system. Often, they can be located in a cabinet
below the standpipe outlet. If the valve is open, the stem will be visible outside the
attached wheel. If closed, the stem is not visible. These valves may also be called
a Riser Control Valve or an Isolation Valve.
Figure 7
4.5.4 Post Indicator Valves - exist in Interconnected Building Systems and are used to
isolate a building from the rest of the system. They are painted red and are generally
located outside and in close proximity to the building (Figure 8). If the valve is
open, the word “OPEN” should be visible on the face of the valve. If closed, the
word “CLOSED” should be visible.
Figure 8
54
FDNY Probationary Firefighters Manual
Chapter 11 Add 3 WATER SUPPLY INFRASTRUCTURE
4.5.5 Gravity Tank - a large container that uses the force of gravity to supply water
pressure to a standpipe system. To work properly, the gravity tank needs to be
located a distance above the highest outlet, so they are commonly located above
roof level. For standpipe systems in an interconnected building complex, a single
gravity tank may supply the system for the entire complex (Figure 9 and Figure 10).
In larger high-rise buildings with low-zone and high-zone systems (such as mega-
high-rises), it is possible for additional gravity tanks to be found inside the building.
Figure 9 Figure 10
4.5.6 Roof Manifold - the top of the standpipe riser, where the piping extends to the roof
level (Figure 11). It is terminated with three outlet connections, which are used
when testing water flow in the standpipe. It may be used by fire companies to
supply a hoseline at the roof level.
Figure 11
55
FDNY Probationary Firefighters Manual
Chapter 11 Add 3 WATER SUPPLY INFRASTRUCTURE
4.5.7 Pressure Reducing Device (PRD) - a device installed at the standpipe outlet for the
purpose of reducing the water pressure (Figure 12 and Figure 13) flowing from the
outlet. PRD’s are removable and are adjustable.
Figure 12 Figure 13
4.5.8 Pressure Reducing Valve (PRV) - a valve (Figure 14) that is permanently attached to a
standpipe outlet for the purpose of reducing the water pressure flowing from the outlet.
PRV’s are not removable and cannot be adjusted.
Figure 14
56
Probationary Firefighters Manual
CHAPTER 11, ADDENDUM 4
1. INTRODUCTION
1.1 This bulletin will describe the operation of the FRC Digital In-Line Pressure/Flow metering
device that has been designed specifically for standpipe operations. The Digital In-Line
Gauge does not regulate water flow, but provides members with the ability to monitor the
pressure and flow being delivered from the standpipe outlet to the nozzle team.
57
FDNY Probationary Firefighters School
Chapter 11 Addendum 4 DIGITAL IN-LINE GAUGE
2. DESCRIPTION
58
FDNY Probationary Firefighters School
Chapter 11 Addendum 4 DIGITAL IN-LINE GAUGE
3. OPERATION
59
FDNY Probationary Firefighters School
Chapter 11, Addendum 4 DIGITAL IN-LINE GAUGE
4. SPECIAL FEATURES
4.1 A safety alerting system is incorporated in the Digital In-line Gauge. The visual alerts
are set at the following levels and will give the Control Firefighter an early indication of a
condition that may require attention. The pressure and flow alerts are not a direct
indication of an unsafe condition. HT communication with the officer may be needed to
clarify the situation.
• The red digital readout will alternately flash a high pressure alert -“HI-P” when
pressure exceeds 200 psi.
• The blue digital readout will alternately flash high flow alert “HI-F” when water flow
exceeds 250 gpm.
• The blue digital readout will alternately flash a low flow alert “LO-F” when water
flow is less than 80 gpm.
4.2 In order to extend battery life, a “sleep” mode for conserving battery power has been
programmed into the Digital In-line Gauge.
• After the unit is turned on the display will remain on as long as water is flowing.
• If there has been no water flow for 15 minutes, the digital display will go into a
“sleep” mode and not display any readings. The resumption of water flow during this
“sleep” mode will re-activate the digital display automatically.
• If there has been no water flow after 30 minutes, the digital display will power off
automatically. If operations are then resumed, the Digital In-line Gauge will need to
be re-started by firmly pressing and holding the green ON/OFF button for 4 to 5
seconds.
5. BATTERIES
5.1 The Digital In-line Gauge is powered by a special 9v rechargeable lithium ion battery.
The specific batteries supplied are HIGHTECH RLI-9600 9V 600 mAh specifically used
in the design and operation of the Digital In-Line Gauge. No other 9V battery may be
used in this equipment.
60
FDNY Probationary Firefighters School
Chapter 11, Addendum 4 DIGITAL IN-LINE GAUGE
5.3 A fully charged battery will supply approximately 5 hours of continuous operation. After
3.5 hours of usage, the digital readout will slowly flash “LO batt”. This is an indication
that approximately 90 minutes of battery life remains. If a slowly flashing
“LO batt” is displayed, the battery shall be swapped at the conclusion of the operation.
When 10 minutes of battery life remains, the digital readout will flash “LO batt” rapidly.
If a rapidly flashing “LO batt” is displayed the battery shall be swapped with the
replacement in the carry case as soon as possible. This can be done when water is flowing.
5.4 The Digital In-line Gauge has a battery test feature that when pressed will indicate battery
condition. Condition of the battery installed in the gauge is to be checked each tour using
this Battery Test Function. A battery in serviceable condition will display as “Batt
Good”. (Photo 5)
5.5 Batteries are easily changed by unscrewing the knurled battery cup, pulling out the
existing battery and inserting a fully charged battery. Ensure that the battery terminals
are properly aligned and do not force the connection. Inspect the condition of the “O”
ring on the battery cup. Reconnect the battery cup snugly; be careful not to over tighten.
(Photo 6)
5.6 Batteries should be rotated and recharged weekly and after use. Remove the batteries
from the Digital In-Line Gauge and the carry case (clear pouch). Rotate them with
batteries from the charging unit (two in, two out). Field units may put identification
numbers or letters on batteries in order to track and evenly rotate them (for example A +
AA and B + BB). Recharging batteries in this manner will ensure properly charged
batteries are in service at all times. Company Commanders shall establish schedules that
will facilitate this battery rotation.
5.7 The battery charger is to be connected to a 120v AC outlet. If the battery charger
indicator is a steady red color, the inserted battery is charging. A steady green color
indicates a fully charged battery. A slowly blinking red color indicates a defective
battery that must be replaced.
61
FDNY Probationary Firefighters School
Chapter 11, Addendum 4 DIGITAL IN-LINE GAUGE
6. STORAGE
6.1 The Digital In-line Gauge is issued with a specially designed carry case that helps protect
it from damage. (Photos 7 & 8) Fittings and adapters should be placed in the bottom of
the bag under the moveable flap, with the In-Line Gauge placed on top.
The contents of the bag should be arranged so that the tools needed first are easier to
obtain. Adjustable dividers can separate the various items into different compartments.
This will provide a level of protection to the gauge and to threaded fittings.
7.1 The Digital In-Line Gauge should be inspected for damage and operability each tour.
7.2 The Digital In-Line Gauge does not require specialized maintenance. It should, however,
be carefully handled and kept clean. As with all standpipe equipment, it should not be
stowed away wet after use.
7.3 If the Digital In-Line Gauge needs to be placed out of service, or replacement batteries
are required, complete form RT-2 and notify the Fire Tools and Equipment Unit at
718-391-9405.
62
PART TWO
LARGE CALIBER STREAMS
(LCS)
Title
Section Page
1 OVERVIEW.......... …………………………………….……65
3 LCS OPERATIONS........................................……………....65
5 APPARATUS DECKPIPE.......…………………...................69
6 TOWER LADDER..................................................................70
63
THIS PAGE INTENTIONALLY LEFT BLANK
64
Probationary Firefighters Manual
1.1 A Large Caliber Stream (LCS) is a fire stream that delivers 350gpm of water flow or more.
They can be ground based (New Yorker multiversal), engine apparatus based (deckpipe),
or applied thru an elevated position (tower ladder or aerial ladder pipe).
1.2 The versatility and increased flow rates of LCS can dramatically impact operations. At fast-
moving fires, early use of LCS can limit fire growth and spread.
1.3 Only the Incident Commander may order the use of LCS, which may be the first arriving
officer. This includes the first arriving engine using its apparatus deckpipe.
2. SUPPLYING LCS
2.1 Whenever possible, an engine company supplying LCS should be dedicated to that task
and not engaged in supplying handlines.
2.2 LCS should be supplied with the largest available hoselines. Most commonly, this will be
3 ½” hose.
2.3 Engine companies supplying a LCS may require additional augmentation, especially when
in-line pumping is used. This can be accomplished through the use of a 2 ½” single gate
attached to a hydrant for the purpose of possible self-augmentation.
3. LCS OPERATIONS
3.1 If LCS use is ordered after units are operating within a building, all operating forces must
be notified and time permitted for their safe withdrawal to unexposed positions.
Confirmation of their safe withdrawal will be verified by way of a Roll Call and all officers
should be prepared to account for the members of their company.
3.2 As an additional safety measure, the LCS should be quickly swept through the building
without stopping at any window or other opening to serve as a warning to any members
left in the area of operation.
3.3 LCS use requires strict adherence to operating procedures to avoid serious injury or
unnecessary property damage. LCS can cause structural stress when driven into building
components and may dislodge building materials, turning them into dangerous projectiles.
Additionally, water accumulation can add significant weight to a building and can
precipitate structural collapse.
65
FDNY Probationary Firefighters Manual
Chapter 11 Part 2 LARGE CALIBER STREAMS
3.4 LCS can entrain large amounts of air into a structure with stream application. The effect of
air movement resulting from LCS use must be considered by the IC and operating members
as conditions may deteriorate in remote areas of the building.
Figure 1
4.1 The New Yorker Multiversal (Figure 1) is carried by all engine companies and has a two-
piece design:
4.1.1 The top section contains the tips, stream shaper, lock, and wheel.
4.1.2 The base section contains the folding legs, attachment points, pins, and supply
connections.
4.2 The multiversal is equipped with three stacked tips (1 ¼”, 1 ½” and 2”).
4.2.1 When the 1 ¼” tip is used, it will flow roughly 465 GPM with 100 psi at the tip
4.2.2 When the 1 ½” tip is used, it will flow roughly 560 GPM with 70 psi at the tip.
When supplied with 100 psi at the tip, it will flow roughly 660 GPM.
4.2.3 When the 2” tip is used, it will flow roughly 840 GPM with 50 psi at the tip
4.3.1 Extend the three leg supports and the place the base section on the ground. The
front leg (with safety chain attached) points in the direction of operation.
66
FDNY Probationary Firefighters Manual
Chapter 11 Part 2 LARGE CALIBER STREAMS
4.3.2 Attach the top section to the base section by placing the top section on top and
inserting the two locking plungers fully, one on either side of the appliance.
4.4.1 Due to the significant back pressures caused by the nozzle reaction, the multiversal
must be secured to ensure a safe operation.
4.4.2 The primary means of securing the multiversal is the proper placement of the supply
hose. All hose supplying the multiversal should be brought straight back from the
appliance for 15 feet. This configuration of hose will effectively absorb the nozzle
reaction and prevent lateral movement of the multiversal.
Figure 2
67
FDNY Probationary Firefighters Manual
Chapter 11 Part 2 LARGE CALIBER STREAMS
Figure 3
4.4.4 If there is no substantial object readily available in the area, the supply hose itself
can be used as a substantial object. This is done by looping the supply hose in front
of the multiversal and tying the rope to it. The supply hose should be laid straight
back for 15 feet before it is looped in front of the multiversal.
4.4.5 Additionally, the safety chain can be secured to a substantial object, if one is close
enough. The safety chain alone should never be relied on to secure this appliance.
4.5.2 The multiversal should be supplied with two supply lines whenever possible,
though it can be operated when supplied with only one line.
4.5.3 The multiversal should be supplied with the largest size hose available. Generally,
this is 3 ½” hose, though it is possible to supply it with 2 ½” hose.
4.5.4 The maximum allowable pressure supplied to the appliance base is 200 psi.
68
FDNY Probationary Firefighters Manual
Chapter 11 Part 2 LARGE CALIBER STREAMS
4.6.1 Do not move the multiversal or the 15 feet of supply hose while it is in operation.
4.6.3 The vertical range of the nozzle is from 15 degrees below the horizontal to 90
degrees above the horizontal. The elevation is adjusted by the operating wheel.
4.6.4 There is a safety stop at 35 degrees above the horizontal. To operate below 35
degrees, release the safety stop by pulling up the release pin.
5. APPARATUS DECKPIPE
Figure 4
5.1 The apparatus deckpipe is permanently affixed to engine apparatus and supplied directly
by a 3-inch pipe from the pump (Figure 4).
5.2 The deckpipe has 4 stacked tips (2 ½”, 2 ¼”, 2”, 1 ½”).
5.2.1 When the 1 ½” tip is used, it will flow roughly 660 GPM with 100 psi at the tip.
5.2.2 When the 2” tip is used, it will flow roughly 840 GPM with 50 psi at the tip.
5.2.3 The maximum flow of 2,000 GPM is reached when the 2 ½” tip is supplied with
116 psi.
69
FDNY Probationary Firefighters Manual
Chapter 11 Part 2 LARGE CALIBER STREAMS
5.3 The deckpipe should be maintained with a single gate connected. The single gate allows
the ECC to supply the deckpipe with water prior to operating the stream.
5.4.1 In situations where fast water on a rapidly expanding fire is required, the IC may
consider using the engine deckpipe for a quick knock-down. This may be the first
arriving officer.
5.4.2 Prolonged usage of the deckpipe LCS may necessitate augmentation, especially
when in-line pumping. An engine company using a LCS should attach 2 ½ gate to
the hydrant for possible self-augmentation
6. TOWER LADDERS
Figure 12
6.1 All tower ladder apparatus in the FDNY are equipped with a basket-based monitor capable
of delivering a large caliber stream when supplied by an engine company (Figure 12).
70
FDNY Probationary Firefighters Manual
Chapter 11 Part 2 LARGE CALIBER STREAMS
6.2 The tower ladder monitor has 2 stacked tips (2”, 1 ½”). A fog tip may also be attached to
the monitor.
6.2.1 When the 1 ½” tip is used, it will flow roughly 660 GPM with 100 psi at the tip
6.2.2 When the 2” tip is used, it will flow roughly 840 GPM with 50 psi at the tip
6.2.3 The maximum solid stream flow of roughly 1,200 GPM is reached when the 2” tip
is supplied with 100 psi.
6.2.4 When the Akron Turbomaster fog tip is used, the flow can be up to 1,250 GPM.
6.3.1 Generally, only one source at the base of the tower ladder should be used.
A. A Satellite Water Unit is the best source of supply if available
B. When supplied with 3 ½” hose, ensure the male end is stretched to the gated
inlet
C. 200 – 250 psi is the recommended pressure at the gated inlet
71
FDNY Probationary Firefighters Manual
Chapter 11 Part 2 LARGE CALIBER STREAMS
Figure 13
7.1 The Blitzfire Oscillating Monitor is a compact portable monitor that is carried only by the
following specialized engine companies:
7.2 The inlet and the outlet of the Blitzfire are both equipped with 2 ½” threads. There is one
2 ½” supply inlet which should be supplied with only one 2 ½” hoseline.
7.4 The Blitzfire comes supplied with its own Max-Force Dual Pressure fog tip. This is the
only tip that may be used on the Blitzfire for exterior water stream application.
7.5 The fog tip can flow approximately 500 GPM at its maximum pressure of 175 psi.
7.5.1 The fog pattern ranges from straight stream to a 120-degree fog pattern
7.5.2 The fog tip may be switched from a standard mode of 100 psi to a low pressure
mode of 55 psi
7.5.3 The fog tip may also be used to apply finished firefighting foam
7.6 The Akron 500 GPM foam nozzle may also be used with the Blitzfire to apply foam.
72
FDNY Probationary Firefighters Manual
Chapter 11 Part 2 LARGE CALIBER STREAMS
7.7.3 It also has an oscillation feature providing an automatic horizontal sweep of either
20, 30, or 40 degrees.
7.8 The Blitzfire has a flow control handle that can be used to control water flow and act as a
safety shut-off feature. The handle is closed when pushed fully forward and open when
pulled back. The flow control handle also has 6 flow positions, allowing the water flow
(gpm) to be regulated at different positions.
7.9 The flow control handle also has a safety shut-off valve. The safety shut-off valve will
automatically shut off the monitor’s water flow if the monitor starts to move sideways.
Once the safety shut-off is tripped, the flow control handle will automatically move to the
fully closed position. To resume operations, push the handle fully forward to ensure the
safety shut-off valve has been reset.
7.10 If the monitor is positioned on a sloped surface, the safety mechanism may activate
preventing the flow control handle from remaining open. This can happen because it
appears the monitoring is moving. If this occurs, the flow control handle will have to be
manually held open by a firefighter. In these situations, it is dangerous to attempt to utilize
utility rope, webbing or any other device to hold the flow control handle open.
7.11 When in operation, the Blitzfire should only be secured using the tie down strap. The loop
end of the strap will be secured to an anchor point and the hook will be snapped into the
hole at the front of the Blitzfire. This is the safest method to secure the monitor because if
the monitor slides, its travel is limited by the length of the strap
73
Probationary Firefighters Manual
Chapter 12
12
PART ONE
ENGINE OPERATION
OPERATIONS
STANDPIPE OPERATIONS...............................................................................93
1.1 The primary function of the engine company officer is to facilitate fire extinguishment by
overseeing the placement of a hoseline to the fire area and directly supervising its
operation to extinguish the fire.
1.2 In the fulfillment of this primary function, the engine officer is responsible to make a
number of critical decisions and take decisive action. While the decisions to be made
will differ depending on the specific operation, the following is an outline of the actions
the engine officer should expect to make at a fire operation. They are listed here and will
be further discussed in the sections to follow.
2.1 As soon as the Engine Officer has determined a hoseline is needed, they should contact
the nozzle firefighter via the handie-talkie and order a hoseline to be stretched. With this
transmission, the Engine Officer should include the following information:
2.1.3 The route and method by which the line should be stretched (if not obvious).
1
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
2.2 If possible, this information should be communicated by handie talkie, even if the nozzle
firefighter is within voice contact. This ensures all units on the fireground are aware a
line is being stretched and where it will be located.
2.3 If the need for a hoseline is evident before the exact location of the fire is confirmed, the
engine officer may elect to call for a line to be initially stretched to the front of the fire
building. This can save time, as the line will be readily available to be advanced to the
fire area as soon as it is located.
2.4 Before the engine officer can direct the hoseline to the fire area, they must know where
the fire area is. While a line may be called for before the exact location of the fire is
discovered, the officer must identify the location as soon as possible, so as to ensure the
hoseline is stretched to the correct location.
2.5 As searching for the fire location is a primary function of the ladder company, the engine
officer will work in close coordination with the ladder company and will often rely on
information from them to effectively lead the hoseline to the fire.
2.6 If the apparatus will be performing a back stretch and will proceed to a position at a
hydrant more distant from the fire building, the Engine Officer can consider calling for a
2nd hoseline to be placed in the street as the first line is being stretched.
3. LINE PLACEMENT
3.1 The engine officer must determine the proper placement of their hoseline. The location to
which the line is stretched must be clearly communicated to their nozzle firefighter, as
well as the engine company that will be assisting them in stretching the line.
3.2.1 Generally, the purpose of the first hoseline is to extinguish the main body of fire.
This line should be placed to attack the main body of fire while also protecting the
primary egress of the building. This position will allow the hoseline to extinguish
the fire while enabling civilians and firefighters to safely use the primary egress.
3.2.2 One exception to this may be a situation in which fire is actively endangering
civilians that are evacuating the building via windows or fire escapes and the
immediate application of water from the exterior is needed to protect them. In this
case, the first line may be operated from the street to partially extinguish or
knockdown fire and protect the fleeing civilians (this is further discussed in a later
section).
2
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
3.3.1 The placement of the 2nd hoseline will depend on the purpose of the line.
Generally, the 2nd hoseline will be stretched for one of the following purposes:
A. Back-up the 1st hoseline
B. Address extending fire
C. Attack the main body of fire from an alternate access point
D. Protect a life hazard from fire
3.3.2 Back-up the 1st hoseline – At most fires, the primary purpose for the 2nd hoseline
will be to back up the 1st line.
A. This line will protect the 1st line in case of a burst length or other water loss.
B. This line can also be used simultaneously with the 1st line if warranted by
advanced fire conditions.
C. When the 2nd hoseline is stretched to back up the 1st line, it should be stretched
to the same location as the 1st line and use the same path to get there.
D. If the 2nd hoseline is not needed to back up the 1st line, it can be advanced to
address possible fire extension. Most commonly, this will be on the floor
above the fire.
3.3.3 Address extending fire - The 2nd hoseline may be stretched to address extending
fire when it is not needed to back up the 1st line, or when the need to address
extending fire demands the immediate placement of a hoseline.
A. When stretched to address extending fire, the 2nd hoseline will be stretched to
a different location than the 1st line.
B. If the 2nd hoseline is stretched to address vertical fire extension, the likely
location will be the floor above the fire. This occurs often at multiple dwelling
fires (tenements, brownstones, row frames, etc.) when heavy fire has extended
above the fire floor due to internal voids or auto exposure. If this line is to be
stretched above the fire, the officer must confirm the existence of a safe area
to flake and charge the line.
C. If the 2nd hoseline is stretched to address horizontal fire extension, it may be
stretched to a different building than the 1st line. This occurs often in
structures (private dwellings, row frames, etc.) in which horizontal fire
extension is an immediate concern due to heavy fire extending laterally via
windows, combustible exteriors, or shafts.
3
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
3.3.4 Attack from alternate access point - The 2nd hoseline may be stretched to attack
the main body of fire from a different access point if the fire can be more readily
accessed from a different location than the position of the 1st line, or if the 1st line
is having difficulty advancing to the seat of the fire.
A. If a second access point is identified as providing a more effective attack on
the fire, the 2nd hoseline can be stretched to this point. This may be common at
a cellar fire (private dwellings, tenements, places of worship, etc.), where
multiple access points to the fire area might exist.
B. If the 1st hoseline has difficulty gaining access to the fire area due to heavy fire
conditions, obstructions, or other delays, an alternative access point may allow
the 2nd hoseline to reach the fire. This may be the case at an advanced cellar
fire, when fire conditions prevent the advancement of the hoseline down the
interior stairs. It may also be the case when a fire escape or balcony provides
access to the fire area, or if stretching the 2nd line by way of a ladder is
possible.
C. If the fire is on the building exterior in the rear (deck or patio fire, etc.), the
fire might be more effectively attacked with a 2nd hoseline stretched to an
access point in the rear of the building.
D. When stretched to attack the main body of fire from a different access point,
the operation of the 2nd hoseline must be closely coordinated with the
operation of the 1st line.
3.3.5 Protect life hazard from fire - This may be done if a person is at a window, fire
escape, or other exposed position and the immediate application of water from the
exterior is needed to protect them while the 1st hoseline is being put into
operation.
A. If the 1st hoseline is already committed to extinguish the fire, an immediate
life threat to a person seriously exposed at a window or other location may
require the 2nd hoseline to be operated as an exterior hoseline from the street
level.
B. In this situation, the 2nd hoseline should be operated so as not to drive heat,
smoke, or fire into the building. This is accomplished by operating the
hoseline into the window at a steep angle, directing the stream at the ceiling.
The stream should be kept stationary; it should not be moved in the circular
motion that is used to advance an interior hoseline. This circular motion can
create an air current into the fire area and negatively affect conditions opposite
the stream.
4
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
3.4.2 Cellar fires – If a hoseline is operating in a cellar or similar area below grade, an
additional charged hoseline must be positioned at the top of the cellar stairs.
A. This position may be covered by the 2nd hoseline, but if the 2nd hoseline is
stretched elsewhere, an additional hoseline must be stretched to this location.
B. This hoseline is critically important because it is protecting potentially the
only egress for the members operating in the cellar. In this case, all members
operating in the cellar may need to pass through the floor above the fire to get
to safety.
3.4.3 Additional exposure protection – If fire is extending to more than one location,
additional lines will be required at each location of extension.
A. These additional locations may be located in different buildings, as in the case
of fire extension horizontally into exposures 2 and 4, in one or both directions
(private dwellings, row frames, old law tenements, etc.)
B. These additional locations may also be in the original fire building, as in the
case of fire extension horizontally within larger buildings via voids or the
cockloft (new law tenements, H-types, or taxpayers etc.). In this case, the
engine officer should be sure that no more than two hoselines are stretched in
a stairway. If there are no additional stairways available, an alternative hose
stretch may be required (rope stretch, fire escape stretch, etc.).
3.5 Typically, the 2nd arriving engine company will team up with the 1st arriving engine to
operate the 1st hoseline. However, there are situations in which the 2nd arriving engine
company may stretch and operate a 2nd hoseline. This should only be done when all of the
following conditions exist:
3.5.1 The 1st arriving engine company must have secured a positive water source. The
2nd arriving engine officer can communicate with the 1st arriving chauffeur to
confirm this.
3.5.2 The 1st arriving engine company does not require the help of the 2nd arriving
engine to get the 1st line in operation. The 2nd arriving engine officer must
communicate with the 1st arriving engine officer to confirm this.
3.5.3 The hose stretches are sufficiently short, so the 1st arriving company will not
require immediate assistance in operating the line once it is charged.
3.5.4 There is an immediate need for a 2nd hoseline to address fire extension or a life
hazard.
5
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
Note: The Incident Commander (Chief Officer or Acting Chief Officer) may
order the second engine in any situation to immediately stretch a second
line for any purpose including the need for a backup line or exposure
protection.
3.5.5 Generally, this situation will only occur in 1 or 2 story structures where the length
of the stretch is manageable. The decision by the second engine officer to
immediately stretch a 2nd line, even in these buildings, must be weighed against
the need to assist the 1st arriving engine in quickly getting the 1st hoseline in
operation. Getting the first line into operation is the primary tactical concern.
3.6 Typically, the 3rd arriving engine company will team up with the 4th arriving engine to
stretch and operate the 2nd hoseline at an operation. However, if the 2nd arriving engine
has already begun stretching a 2nd hoseline (as described above), the 3rd arriving engine
should team up with the 1st arriving engine and assist in the operation of the 1st hoseline.
3.6.1 There may be situations in which the 3rd arriving engine may need to assist the 1st
and 2nd arriving companies in getting the 1st hoseline in operation. This may be
the case if there is an excessively long or difficult stretch, or if there was a
problem with the stretch. The 3rd arriving engine officer should make sure their
assistance is not required with the 1st line before ordering a 2nd line stretched.
3.6.3 The 3rd arriving engine should only stretch a 3rd hoseline when ordered by the
Incident Commander.
4.1 Determining the size of the hoseline to be stretched is a critical decision to be made by
the engine officer.
4.1.1 When making this decision, the advantages of the speed and mobility of the
smaller 1 ¾” hoseline need to be weighed against the limitations of the flowrate
provided.
4.1.2 Similarly, the advantages of the increased flowrate of the larger 2 ½” hoseline
need to be weighed against the limitations of the heavier weight and decreased
maneuverability of the hoseline.
6
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
4.2 The engine officer should determine the size of the hoseline stretched based on the
conditions faced and the specific purpose of their hoseline.
4.2.1 All hoselines stretched at an operation do not need to be the same size; if the
initial hoseline stretched is a 2 ½” line, subsequent hoselines are not required to
also be 2 ½” hose. If the engine officer determines the use of a smaller hoseline
would be appropriate, subsequent hoselines may be 1 ¾” hose.
4.3 To aid the engine officer in making this decision, the following sections discuss the
capabilities of both the 1 ¾” and 2 ½” hoselines, as well as their applicability to various
situations. These guidelines are intended to assist the engine officer in making a difficult
and important decision.
4.4.1 The 180 GPM flowrate provided by the 1 ¾” hoseline is sufficient to extinguish
the majority of fires encountered.
4.4.2 When the 1 ¾” hoseline is supplied with 50 psi at the 15/16” tip, the nozzle
reaction is 68 lbs. This is the force felt by the nozzle firefighter.
4.4.3 The increased speed and mobility of the 1 ¾” hoseline enables the nozzle
firefighter to more effectively operate the hoseline and direct the water stream as
needed.
4.5 There exist situations where the flowrate provided by the 1 ¾” hoseline may not be
sufficient and the larger flowrate provided by the 2 ½” hoseline is needed.
4.5.1 When supplied with a nozzle pressure of 40 psi, the 2 ½” hoseline will provide a
flowrate of 235 GPM and a nozzle reaction of 78 lbs. This is the force felt by the
nozzle firefighter.
4.5.2 If this flowrate proves inadequate, the engine officer can request an additional 10
psi be supplied to the 2 ½” hoseline. This will provide a nozzle pressure of 50 psi
and a Flowrate of 265 GPM. The nozzle reaction will be 98 lbs, which is nearly
50% greater than the nozzle reaction of the 1 ¾” hoseline.
4.6 While the elevated flowrates of the 2 ½” hoseline provide increased extinguishment
power, the resultant nozzle reactions reduce the maneuverability of the hoseline. The
advance of the line will be slower and it may be more difficult for the nozzle firefighter to
maneuver the stream as needed.
7
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
4.7 There are five situations in which the use of the 1 ¾” hoseline would not be appropriate
and a larger hoseline should be used:
4.8.2 Unknown size or extent of the fire area – If the size of the fire area cannot be
determined by the engine officer, a 2 ½” hoseline should be used. This situation
could be encountered in larger, non-typical buildings, where the size or extent of
the fire area cannot be readily determined at the outset of the operation.
4.8.3 Advanced fire conditions – If the fire conditions on arrival are advanced to such a
degree that the officer feels the flow provided by the 1 ¾” line would not be
sufficient, the 2 ½” hose may be used. The reduced maneuverability of the 2 ½”
line should be considered in this case, especially if the fire is above the first floor
or the fire is in a smaller, compartmented building like a Brownstone or Row
Frame.
4.8.4 Large, uncompartmented fire area – If the fire area is large and is
uncompartmented, a 2 ½” hoseline should be used. While the officer should use
their discretion in assessing the size of the fire area, a general guideline is that a
fire area over 50 feet wide can be considered “large”. The area should also be
“uncompartmented”, which means that it largely consists of open areas and floor
space. An uncompartmented fire area may also have high ceilings, or directly
access a potential roof vent. This may include large industrial or commercial
occupancies, such as warehouses, places of worship, large stores, or one-story
taxpayers. In such cases, the large, uncompartmented area will allow the reach of
the stream to be unimpeded and hit the seat of fire from a distance.
8
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
4.8.5 Standpipe operations – When a hoseline is stretched from a standpipe system, the
1 ¾” hose must not be used due to its high friction loss. In order to achieve a
reliable and effective firefighting stream, larger hose with less friction loss must
be used from a standpipe system. For residential occupancies, the lead length of
the stretch from the standpipe outlet should be 2” lightweight hose, as the relative
speed and mobility is more appropriate for the compartmented conditions
encountered in these occupancies. In all other situations (commercial, subways,
etc.), all lengths stretched should be 2 ½” lightweight hose.
4.9 Considering the above guidelines, further clarification may be required for specific
situations, as follows:
9
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
5.1 When ordering a hoseline stretched, the engine officer is responsible for determining the
path by which the hoseline is stretched. If the path is not obvious, it will need to be
clearly communicated to the nozzle firefighter when the line is called for.
5.2 When stretching the first hoseline, the hoseline should be stretched in such a way to
protect the primary egress of the building while accessing the fire area. Generally, this
will require the path of the hoseline to be via the stairway.
10
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
5.2.1 In rare situations, unique building characteristics may necessitate the first hoseline
to be stretched via an alternative method (such as a rope stretch). In these cases,
the path of attack should protect the primary egress as best as possible. These
situations should be noted in CIDS.
5.3 If multiple stairways are available, the engine officer should choose the stairway that will
provide the most efficient stretch and attack possible. Most commonly, this will be the
stairway that provides the shortest path to the fire area.
5.3.1 Consideration should be given to using the stairway that provides the shortest
stretch on the fire floor. This is particularly relevant when scissor stairs are used.
5.3.2 If a more remote stairway would provide an easier stretch, consideration should be
given to using that stairway instead. This is relevant if the closer stairway provides
a difficult stretch (such as a wrap-around stretch), or if a more distant stairway
provides a much easier stretch (such as a well-hole stretch).
5.4 The engine officer determines when a well-hole stretch is to be executed. The presence of
a well-hole and the intention to use it should be clearly communicated to the nozzle
firefighter. This information is also critical to the control firefighter for estimating the
stretch.
5.4.2 The engine officer will need to determine the location at which the hoseline will
be taken out of the well hole and secured with a hose strap. The following
locations should be considered:
A. On the floor below – Hose can be secured on the floor below the fire if
conditions or limited space on the fire floor prevent it from being secured on
the fire floor. This will provide a safe area to flake out hose. From this
location, the hose will be stretched via the stairway to the fire floor, providing
an element of protection to the primary egress.
B. On the half landing – If there is a half-landing present in the stairway (which
is common when a well-hole is present), the hose may be secured at this point.
This will provide a safe area to stage the hose, but may provide limited space
to flake the hose out.
11
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
5.5.1 If the 2nd hoseline is stretched to the same location as the 1st line, it should be
stretched using the same path as the 1st hoseline and access the fire floor using the
same attack stairway. A second dry hoseline should not be stretched into a
building until the first hoseline has been charged with water. This is because this
practice may cause confusion at operations as to which line is being referred to.
Additionally, it may cause the two lines to get tangled with each other.
5.5.2 If the second hoseline is stretched to a different location (to address extending
fire, to attack the main body of fire from an alternate access point, or to protect
life), it will be stretched via the most effective path for that destination, as
determined by the engine officer.
5.6.1 At a fire operation, only 2 hoselines should be stretched on a stairway. If a 3rd line
is to be stretched, it will need to be stretched by an alternative means.
5.6.2 If additional lines are to be stretched in the fire building, the engine officer should
consider other options available, which may include using a different stairway, or
possibly an exterior stretch.
5.6.3 For exterior stretches (such as a rope stretch, fire escape stretch, or stretch via
aerial or portable ladder), the engine officer will have to determine the location at
which the line will be brought into the building.
A. In most situations, the line will be brought in the building on the floor below
the fire. This ensures the hoseline is flaked out in a safe area below the fire.
The hoseline will then be advanced to the point of operation via the interior
stairs.
B. Depending on the situation and building characteristics, it may be possible to
bring the line in the building on the floor on which it will be operated. This
should only be done if the hose can be flaked out and charged in a safe area
before being advanced to the point of operation.
C. In the case of a fire escape stretch or a stretch via a ladder, it may be possible
to charge the hoseline outside the building and advance it directly into the
building on the fire floor while charged. This operation must be closely
coordinated with all other units operating on the fire floor.
12
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
5.7.1 Depending on the situation, the engine officer may have several options available
for stretching hoseline. In the event that multiple methods are available, the
following is the priority order of methods for stretching hoselines:
A. Interior stairs
B. Rope
C. Fire escape
D. Portable ladder
E. Aerial ladder
6.1 As the hoseline is being stretched, the engine officer must determine the point at which
the hoseline will be flaked out and charged. This point should be in a safe area, as close to
the fire area as possible.
6.2 In some occupancies and building types there are no public hallways to flake out and
charge the hoseline before entering the fire area, thus the hoseline will be charged outside
the fire building. In these cases, the hoseline should be flaked out and charged as close to
the building entrance as possible. This includes hoselines stretched at private dwelling
fires, place of worship fires, and taxpayer fires (among others), where hoselines are flaked
out and charged outside the fire building.
6.3 If the hoseline is to be stretched dry into the building, it should be flaked out and charged
in a safe area as close to the fire area as possible. This includes fires in all types of
multiple dwellings, as well as fires in lofts, and other large commercial or industrial
spaces.
6.4 If the door to the fire apartment (or fire area) is controlled and conditions in the public
hallway are tenable, the hose should be flaked out and charged at the apartment door.
6.5 If the door is not controlled and conditions in the public hallway are not tenable, the
hoseline may have to be flaked out and charged before entering the hallway. If the
stairway is a safe area, the hoseline may be flaked out and charged in the stairway. If the
stairway is not a safe area, or there is no space to flake out the hose, it may be necessary
to charge the hoseline in a safe area on the floor below the fire.
13
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
7.1 The application of exterior water into an occupied structure is a valuable tactic under the
right set of circumstances
7.2 In the FDNY, the first hoseline is normally stretched at fires to the interior of the structure
to protect the primary egress route, and to confine and extinguish the fire. The NFPA
compliant staffing of FDNY Engine Companies greatly contributes to the FDNY’s ability
to quickly and efficiently stretch and operate handlines to protect life and property with
little delay.
7.3 On occasion, when heavy fire is venting out a front window or door on arrival, the first
hoseline may be used to momentarily extinguish venting fire. This is tactic of opportunity
which does not unnecessarily delay interior operations.
7.4 There are situations where the standard approach of interior attack may not lead to a
quick extinguishment of the fire enabling the fire to grow larger. In these situations, the
proper application of water from an exterior stream may facilitate the rapid advance of
interior attack hoselines by partially extinguishing the fire.
7.5 Exterior stream application may significantly improve interior conditions that may have
otherwise been untenable. It may also provide a limited amount of additional time for the
interior attack team to overcome obstacles and facilitate advance for final extinguishment.
7.6 The single best way to always improve conditions at any fire is to apply water on the fire.
In structures that are not built with fireproof construction, the failure to rapidly apply
water on the fire allows a contents fire to extend to the structure. This creates a greater
fire problem because the structure is weakening, fire is extending, and heat and smoke
conditions are becoming worse.
14
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
7.9 The acronym to allow for easy mental recall of the manual technique of applying water
correctly from an exterior handline to the interior of a building is “S.S.S.S”
7.9.1 Solid (bore) stream – fully open, do not partially open, do not use a fog tip
(occlusion)
7.9.2 Steep Angle – will assist with breaking up and cooling the hot gases at the upper
levels
of the room as it strikes the ceiling
7.9.4 Sprinkler –a solid stream held steady and positioned at a steep angle will create a
“sprinkler effect” to cool the hot gases and knock back the fire
7.10 Engine company officers should develop a physical communication system with the
nozzle firefighter for use when voice communications cannot be heard. The following
system of touch signals can be used in conjunction with verbal commands to relay orders:
7.10.1 open or close the nozzle – one or two slaps on the back or shoulder
7.10.2 direction of stream – tug on the arm or nozzle, either left or right
7.10.4 stop line advance – pull back on shoulder, bunker coat, or SCBA
7.10.5 emergency withdrawal – 4 slaps on the shoulder and pull in direction of retreat
7.11 After final extinguishment, the engine officer may order a fog or broken stream directed
out a window in the fire area to assist in removal of heat and smoke conditions. A broken
stream can be produced for venting purposes by removing the MST and partially shutting
down the control handle.
15
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY OFFICER
16
Probationary Firefighters Manual
1.1 The primary responsibilities of the Engine Company Chauffeur (ECC) involve three
general areas:
1.1.1 The safe delivery of the members and apparatus to the scene of a fire or emergency
1.1.3 Delivering and maintaining a water supply to the firefighting force throughout the
operation
1.2 To effectively fulfill these responsibilities, the ECC must be thoroughly familiar with the
engine apparatus, all the tools and equipment carried on board, and the layout of the hose
beds.
1.3 The ECC must also be familiar with the various methods of establishing a positive water
source, as well as the procedures and requirements for properly supplying water to a
firefighting operation.
2. RESPONDING TO A FIRE
2.1 Upon receiving a call for report of a fire, the ECC is to determine the best route to the
reported site of the fire. Consideration should be given to the response patterns of other
incoming units. If other units are already 10-84, this may require coordination with the
officer, as well as with the other units on scene.
2.2 When entering the block of the reported fire, the ECC should immediately check the
building addresses, so as not to pass the building by too great a distance. Once on the block,
the ECC should coordinate with the officer to locate hydrants to be used.
2.3 The first due engine company should strive to enter the block ahead of the first ladder
company and from the same direction. This will allow for optimal apparatus positioning.
17
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
2.4.2 The engine apparatus should be positioned as close to the fire building as possible
to reduce the time, effort and number of lengths needed for the stretch. However,
consideration must be given to ladder company response and the engine apparatus
should be positioned so that it will not interfere with ladder company positioning.
2.4.3 The engine apparatus can be positioned to hook up to a hydrant either past the fire
building, or before reaching the fire building. A hydrant in the immediate vicinity
of the fire building may also be used if it will not interfere with ladder company
positioning.
2.5.1 The ECC should position the apparatus to hook up to a hydrant past the fire building
whenever possible. This allows for an efficient hose stretch, while providing engine
company members with a view of the entire frontage of the fire building before
they stretch their line.
2.5.2 When the hydrant is in close proximity to the fire building, the ECC may elect to
initially position the apparatus directly at the hydrant itself. An initial position at
the hydrant will facilitate hooking up to the hydrant, but may result in a longer hose
stretch from the apparatus to the fire building.
2.5.3 When the ECC plans to use a hydrant more distant from the fire building, they may
elect to initially position the apparatus in the immediate vicinity of the fire building,
so as to facilitate the stretch of the attack line. In this case, the hose stretch will
begin at this initial position and the ECC will reposition the apparatus to the hydrant
while the stretch is in progress. This evolution is called a “backstretch” (Figure 1).
2.5.4 When executing a backstretch, the ECC will initially position the apparatus in the
vicinity of the fire building, but so as not to impede ladder company positioning. In
most cases, this will be a proper distance past the front entrance and is normally
based on the type of ladder apparatus responding directly from behind. At most
structural fires, the location of the ladder apparatus turntable normally dictates how
far past the front entrance of the building the engine backstep should initially be
placed on arrival. For longer stretches in larger buildings (such as H-types), an
initial position just opposite the front entrance may significantly facilitate a more
efficient stretch.
18
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
Figure 1
2.5.5 After firefighters remove sufficient hose to reach and cover the fire area, the ECC
proceeds with the rig to the hydrant to be used, playing out hose as the rig moves.
If deemed advantageous, a 2nd hoseline may also be removed before the engine
repositions to the hydrant.
2.5.6 When positioned for a backstretch, the ECC should be mindful of any company
approaching from the opposite direction that might prevent the engine from
reaching their desired hydrant and should be prepared to contact them via Handie
Talkie to coordinate their response, if necessary. Similarly, if engine company
positioning prevents access for a ladder company responding from the opposite
direction, the ECC should inform them either via Handie Talkie, or through the
dispatcher.
2.5.7 Another benefit of positioning for a backstretch is that the apparatus will be
positioned in close proximity to the fire building at the outset. This initial
positioning allows for the use of the deck gun, when needed. This is important when
the immediate application of exterior water could facilitate life-saving operations
due to extreme fire conditions.
19
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
2.6.1 When the ECC elects to use a hydrant located before the fire building, a more
challenging stretch will result, as members will be forced to stretch the line around
the apparatus. This forces the hoseline to make an extra turn and commonly requires
a member to remain at the backstep until sufficient hose has been stretched to reach
and cover the fire area.
2.6.2 When the hydrant is in reasonable proximity to the fire building, the hose stretch
may be initiated from a position directly at the hydrant. This also may be required
if ladder apparatus positioning prevents the engine from moving closer to the fire
building.
2.6.3 When there is room to reposition the apparatus closer to the fire building without
blocking out ladder apparatus, in-line pumping may be used to facilitate a shorter
and more rapid hose stretch. This is executed by stretching 3 ½” hose to the hydrant
to be used. This can either be hand stretched back to the hydrant, or stretched using
the apparatus.
Figure 2
2.6.4 When the apparatus is used to stretch the 3 ½” hose, the Control firefighter will first
“key” the hydrant with the 3 ½” hose, wrapping it around the hydrant to anchor it
in place. The apparatus will then proceed to a more advantageous position closer to
the fire building. The 3 ½” hose will play out as the apparatus is repositioned. If
time permits, the Control firefighter should connect a 2 ½” gate to the hydrant’s 2
½” outlet for possible augmentation.
20
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
2.6.5 When the apparatus is repositioned, in-line pumping can result in shorter hose
stretches to the fire area, but longer stretches from the apparatus to the hydrant.
This also necessitates the use of the smaller 3 ½” hose as a hydrant connection,
which may limit water supply.
2.7.1 The term “in-line pumping” refers to any situation in which 3 ½” hose is used to
connect to a hydrant (Figure 2). In these situations, the apparatus will be more
distant from the hydrant and will be pumping “in-line” between the hydrant and the
fire building.
2.7.2 In-line pumping is not exclusive to a situation with a hydrant before the fire
building and can be used regardless of the position of the hydrant or apparatus. In-
line pumping can be used if the hydrant and apparatus are positioned past the fire
building as well.
2.7.3 It is important to specifically identify “in-line pumping” because the smaller size
of the 3 ½” supply hose may limit the available water supply. Whenever in-line
pumping is used, the ECC should be mindful of the possible need to augment their
water supply. If intake pressure drops below 15 psi, the ECC must have their water
supply augmented.
3.1 Hydrants are the primary source of water in the FDNY. Before connecting to a hydrant, it
must be visually inspected for obvious defects, properly flushed, and tested to ensure
sufficient water supply.
3.1.1 Flushing a hydrant allows for any debris inside the barrel to be removed. The
hydrant should be opened slowly to allow water to flow from the outlets without
having the outlets completely filled with water. This will permit debris trapped
inside the barrel to flow out with the water. If large debris is noted inside the barrel,
all efforts must be made to remove it.
3.1.2 After the hydrant is properly flushed out, it must be flow tested for proper pressure.
This is done by opening the hydrant until sufficient water flow under pressure is
observed, indicating there is appropriate water volume available for supply. Once
sufficient flow is noted, the hydrant is shut down. The hydrant is now ready for
connection
21
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
3.2.1 10-foot soft suction – This 3 ½” soft suction has 4 ½” couplings, so it can be
connected directly to a hydrant. It can be bent, but will straighten when charged
with water and is very difficult to kink. At 10 feet long, it is the shortest hydrant
connection and requires accurate positioning close to the hydrant.
3.3.3 35-foot soft connection – This 5” synthetic hose is yellow and has 4 ½” couplings
for direct connection to a hydrant. It is 35 feet long, so it allows for some distance
from the hydrant and provides the ability to maneuver around obstructions. It
provides the largest flow of any hydrant connection, but has the potential to kink,
so it needs to be properly flaked out.
3.3 Hydrants are operated using a hydrant wrench. It is placed over the five-sided operating
nut on the top of the hydrant and turned clockwise to open. If the hydrant is equipped with
a Custodian Lock, the magnetic cup feature of the Custodian hydrant wrench is placed over
the Custodian lock and turned clockwise to open.
3.4 White hydrant discs are used to identify inoperable hydrants. If the ECC encounters a
hydrant with a white disc, it should be considered unserviceable. Yellow hydrant discs are
used to identify frozen hydrants. If a hydrant is discovered to be inoperable or frozen, the
ECC should use the proper disc to identify it.
22
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
3.5 If increased water supply is anticipated, the ECC may consider attaching a 2 ½” single gate
to the 2 ½” outlet of the hydrant before the hydrant is initially opened for water supply.
This will make it possible to later self-augment if the need for elevated water flow arises.
If needed, a second supply hose can be connected to this single gate, which can be opened
to further supply the engine apparatus. This maximizes the water supply from a single
hydrant.
3.5.1 Self-augmentation by way of a 2 ½” single gate can also be used to bypass the
initial supply line in the event an obstruction in the supply line interrupts water flow
to the apparatus. In this case, a second supply line from the 2 ½” single gate can
ensure continued water supply.
3.6.1 In the event an ECC cannot hook up to a positive water source, the ECC should
transmit a signal 10-70 via handie talkie. The EAB should be used and the
signal transmitted as per Communications Chapter 7: Company Unit
Communications. This will alert all on-scene units that the 1st due engine does not
have a positive water supply and they require assistance in obtaining one.
3.6.2 It’s important to also transmit the 10-70 on the department radio, which informs
incoming units of the situation and allows dispatch to assign a water resource unit.
The second arriving engine will be the water resource unit when a 10-70 is
transmitted by the first arriving engine.
3.6.3 Once the 10-70 is transmitted, the ECC should coordinate with assisting units,
including the water resource unit, and make clear what assistance is needed.
3.7.2 When receiving water via a relay, the engine apparatus delivering the water is called
the “supply pumper” and the engine apparatus receiving water is called the
“operating pumper”. The supply pumper and operating pumper should both remain
in the “Volume” position. However, at standpipe operations where head pressure
needs to be overcome, the supply pumper remains in volume while the operating
pumper switches to the pressure position.
Note: Head pressure is the static pressure (the pressure when water is not flowing)
caused by the weight of water solely due to its height above the measuring
point.
23
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
3.7.3 The ECC of the operating pumper opens the inlet gate and should verify incoming
water with the ECC of the supply pumper. The ECC of the operating pumper must
also open the air bleeder valves to the inlet being used, so as to prevent air from the
supply hose from entering the pump.
3.7.4 The ECC of the operating pumper then sets the reading on the Pro Pressure
Governor (PPG) to match the idle pressure on the pump pressure gauge. The
operating ECC will coordinate with the supply ECC to ensure enough water is
supplied to meet pressure demands of the operating pumper.
3.8 Drafting
3.8.1 Engine companies can also use a standing body of water as a positive water source.
This can be used when there are no hydrants available, or in situations where more
water is required than can be supplied by the hydrant system.
3.8.2 FDNY apparatus carry 3 connections intended exclusively for use in the drafting
evolution. Each of the connections is 10 feet long and one is a smooth connection,
while the other 2 are ridged connections.
A. The 10-foot smooth connection is hooked up to the 6” ungated inlet on the rig
B. The ridged connection equipped with a strainer is lowered into the water
C. The 2nd ridged connection is connected between the other two connections.
3.8.7 The connection equipped with the strainer is secured in the water with a rope. The
rope is tied to the connection just above the strainer using a clove hitch and binder
and lowered until the strainer is at least 2 feet under the water’s surface. The other
end of the rope is secured to a substantial object, using the substantial object knot.
3.8.8 A limiting factor on the apparatus’ ability to draft water is the vertical distance
water needs to travel from the water’s surface to the apparatus. In practice, a pumper
can draft water a maximum distance of roughly 22 feet, though lifting water
vertically beyond 10 feet reduces the Gallons Per Minute (GPM) capability of the
pumper.
4. SUPPLYING WATER
4.1 The ECC is responsible for supplying water to firefighting forces via hoselines and
maintaining the provision of sufficient operating pressure throughout the operation. This
occurs in a number of different ways:
24
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
4.2.1 In order to properly supply a hoseline, the ECC must know the number of lengths
stretched, the size of the hose stretched, and the elevation to which the line is being
stretched. Generally, this information is confirmed by communicating directly with
the control firefighter.
4.2.2 Supplying water to a hoseline is the responsibility of the ECC, however, all
members should be capable of placing the apparatus in pump and supplying a
hoseline, in case of an emergency. To accomplish this, the following steps should
be taken:
4.2.3 Before pressure can be supplied to a hoseline, the apparatus pump must be engaged
using the following steps: (see Figure below)
A. Place the apparatus transmission in “neutral”
B. Engage the apparatus maxi-brake
C. Move the “pump shift control” to the pump position (located in the cab)
D. Place the apparatus transmission in “drive”
25
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
4.2.4 Once the apparatus pump is engaged, water can be supplied to a hoseline using the
following steps:
A. Press the “Push to Prime” button (Figure 3) on the pump panel
(this expels air from the pump system)
Figure 3
Figure 4
26
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
Figure 5
4.2.5 The maxi-brake on the apparatus must be set for the apparatus pump to be engaged.
The pump will not engage if the maxi-break is not set.
4.2.6 The ECC ensures proper pressure is supplied to the handline by calculating the
pressure needed to overcome the friction loss in each length of hose and the
pressure loss due to the elevation of the hoseline, while still providing the correct
nozzle pressure “at the tip”. This practice is known as “street hydraulics”.
4.2.7 The following are the rules of thumb that govern the quick calculations involved in
street hydraulics:
A. add 20 psi friction loss per length of 1 ¾” hose
B. add 5 psi friction loss per length of 2 ½” hose
C. add 5 psi per floor of elevation (one floor is roughly 10 feet)
D. subtract 5 psi per floor of elevation loss below grade (one floor is roughly 10 feet)
E. 1 ¾” hoseline nozzle (15/16” tip) requires 50 psi at the tip
F. 2 ½” hoseline nozzle (1 1/8” tip) requires 40 psi at the tip
G. Fog nozzle requires 100 psi at the tip
27
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
4.2.9 The ECC should inform the engine officer via handie talkie when water is being
supplied. In this transmission, the ECC should also inform the officer whether they
are being supplied by a hydrant or if they are only supplied by the booster tank. (for
example: “255 Chauffeur to 255, Here comes your water…you’re on hydrant
water”).
4.2.10 In a situation where there is delay in hooking up to a hydrant and the officer calls
for the hoseline to be charged, it may be necessary for the ECC to supply the line
with the booster tank. This may also occur if the officer calls for quick water in an
attempt to immediately protect life. When the officer calls for water, the ECC must
supply water as soon as possible. Supplying water to a hoseline from the booster
tank should not be delayed by the ECC continuing to hook up to a hydrant after the
officer has called for booster water.
4.2.11 Whenever a line is supplied with the booster tank, the ECC must communicate to
the Engine Officer that they are on booster water. The Engine Officer should also
be notified when the water level in the booster tank is half empty. Once they are
hooked up to a hydrant, the “tank to pump” valve is closed, and there is sufficient
intake static pressure (pressure when water is not flowing) and residual pressure
(pressure remaining after a line is charged), the ECC must notify the officer that
they are now on hydrant water.
4.3.1 When a hoseline is to be operated from a standpipe outlet, the ECC must hook up
to the standpipe system and augment the system. This supply line should be the first
line stretched from the apparatus.
4.3.2 Exception: Most modern and some older high-rise buildings may have unique
standpipe system considerations that first alarm units have become aware of. The
reliability, or unreliability of such systems may be knowledge that local units are
cognizant of. These buildings may require Pre-Incident Guidelines, Familiarization
Drills and identification in CIDS with specific instructions regarding standpipe
supply tactics for such buildings. Division Commanders are authorized to approve
CIDS and Pre-Incident Guidelines for those buildings that have unique standpipe
systems requiring adjustments to the standard FDNY policy.
4.3.3 When supplying water to a standpipe system, the ECC should use 3 ½” hose (or 3”
hose if high-pressure pumping) to supply the appropriate Fire Department
Connection (FDC, formerly known as Siamese connections). The standpipe FDC
is entirely painted red or may just have red caps (Figure 6A). If part of a
combination system (Figure 6B), the FDC is entirely painted yellow or may just
have yellow caps.
28
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
Figure 6A Figure 6B
4.3.4 ECC’s can encounter a wide range of difficulties when connecting hose to a FDC.
This can include defective or damaged threads, frozen female swivels or swivel that
will not turn, caps that cannot be removed, broken clapper valves, or outlets stuffed
with debris. In these situations, there are various possible solutions to this problem:
A. Tapping the swivel(s) on the FDC with a tool (spanner) may loosen paint, dirt,
etc…and allow the swivel to operate
B. Twist the supply hose 4-5 turns to the left, insert the male end, then twist the
male end to the right (clockwise) into one of the female swivels of the FDC
C. Insert a 3” x 3” x 3” Siamese into one of the female swivels of the FDC, this
provides a female coupling for the male coupling of the 3 ½” supply hose to
attach to.
D. Using a 3” double male fitting and a 3” double female fitting. The double male
fitting is attached to the malfunctioning female coupling of the FDC (the fitting
will be turned, not the broken swivel). The double female fitting is then coupled
to the double male, which provides a female coupling for the male coupling of
the 3 ½” supply hose to attach to.
4.3.5 If the FDC is found to be inoperable, or if the position of the FDC in relation to the
hydrant makes connection to the FDC impractical, the standpipe system can be
supplied by way of the first-floor standpipe outlet as an alternative.
4.3.6 The ECC must provide for sufficient pressure available at the standpipe outlet, but
should also strive to minimize the amount of excess pressure supplied to the system.
When the standpipe system is charged with excessive pressure, it can become more
difficult for the control firefighter to set the proper pressure in the handline at the
standpipe outlet.
29
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
4.3.7 With this in mind, the ECC should generally supply the standpipe system with a
pressure of 100 psi, plus an additional 5 psi per floor of elevation. This is measured
to the floor on which the hoseline will be operating.
A. Example—If fire is on the 26th floor of a HRFPMD, the ECC should supply 225
psi to the standpipe system (100 psi-baseline + 125 psi for 25 floors of
elevation)
4.3.8 The guideline of supplying standpipe systems with 100 psi, plus an additional 5 psi
per floor of elevation should be used as the primary guide at most operations in
buildings that are known to be older, traditional construction.
Note: Chapter 8, Addendum 2 provides two standpipe supply charts:
4.3.9 It is important to note that these supply charts are approximations and adjustments
must be considered as the height of the fire floor increases. This is particularly
pertinent in modern high-rise construction located mostly in the Borough of
Manhattan, but now starting to be seen in the outer boroughs.
4.3.10 It is critical that units with unique high-rise construction familiarize themselves
with the standpipe systems provided, and develop appropriate Pre-Incident
Guidelines, Familiarization Drills and CIDS messages so that appropriate standpipe
supply decisions can be made at operations.
4.3.11 For a full discussion of ECC operations at a standpipe operation, please see Standpipe
page 93
4.4.1 Upon being ordered to supply a sprinkler system, the ECC should supply the system
with a 3 ½” hoseline to the FDC. Not all sprinkler systems have a FDC, so only
those with an available connection need to be supplied.
4.4.2 Automatic sprinkler system FDC’s are painted green (Figure 7), or are equipped
with green caps. If part of a combination system, either the FDC or the caps are
painted yellow. If the FDC is aluminum or has aluminum caps, it indicates a non-
automatic sprinkler, or a system of perforated pipe.
30
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
Figure 7
4.4.3 The ECC should supply the sprinkler system with 150 psi, but should be prepared
to increase pressure upon any indication that the system requires more water. This
can be based on reports of system performance from operating members.
4.4.4 While the flowrate provided by sprinkler heads will vary, a standard sprinkler head
can be expected to provide a flowrate of 13 – 18 GPM.
4.4.5 When the building is equipped with both a standpipe and a sprinkler system, the
first supply line stretched should be to supply the standpipe FDC. Once the
standpipe FDC is supplied, a second line should be stretched to supply the sprinkler
FDC.
4.4.6 When the first due engine is supplying both the standpipe and sprinkler systems,
both systems should be augmented by later arriving units. If a sprinkler/standpipe
combination system is being used, it should similarly be augmented by later
arriving units. The water demanded by this system will be much higher, as it
supplies both the standpipe and the sprinkler systems.
4.5.1 LCS are streams that deliver at least 350 GPM of water. Streams of this size are
delivered through several different appliances, including tower ladder monitors,
aerial ladder pipes, engine apparatus deck pipes, Blitzfire Oscillating Monitors, and
the New Yorker Multiversals.
4.5.2 ECC’s should supply LCS with 3 ½” hose. When their use is anticipated, or if the
LCS apparatus is not yet in position, the ECC may stretch 3 ½” hose to the location.
4.5.3 During LCS operations, all valves and gates should be opened slowly to avoid a
“water hammer”. This sudden force that results when a water supply is quickly shut
down can result in damage to pump, appliances, and hose.
31
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
4.6.1 When performing a relay operation, the pumper that is hooked up to a water source
and supplying water to the operating pumper is called the “supply pumper”.
4.6.2 The ECC of the supply pumper supplies the operating pumper using 3 ½” hose and
should maintain the supply pumper in the “volume” setting. This will ensure the
operating pumper can properly receive the relay and supply the required water flow.
4.6.3 The supply ECC should set their Pro Pressure Governor to idle pressure and inform
the operating ECC of the pressure that is being sent (this should be roughly 55 psi
plus hydrant pressure).
4.6.4 The operating ECC will tell the supply ECC if more pressure is required. The
supply ECC should increase the relay pressure in increments of 10 psi until
sufficient pressure is achieved, or until the incoming pressure on the supply pumper
drops to 15 psi.
5. TROUBLESHOOTING
5.1 A critical component of the ECC’s job is the ability to quickly recognize and address
problems that could jeopardize the supply of water to firefighting units. The following
section will highlight common issues ECC’s can expect to encounter at an operation.
5.2 Once the ECC has properly charged a hoseline, they must continually monitor the status of
the line. This includes monitoring of intake pressure, as well as the pressure and flow of
each line supplied. The ECC must be able to identify a problem from the pump panel that
could compromise the maintenance of water in the hoseline. Some indications of loss of
pressure can include:
5.2.2 Flow on flowmeter decreases, rig RPM decreases = possible kink in the hoseline
5.2.3 Flow on flowmeter increases, rig RPM increases = possible burst length
5.3 The ECC needs to ensure the rig is receiving enough water to meet the demands of the
hoselines it is supplying. The rig will “run away from water” if it attempts to pump out
more water than it is taking in. To prevent this from happening, the ECC should not allow
the intake pressure to drop below 15 psi. Once 15 psi intake pressure is reached, the
apparatus should be augmented with an additional water supply.
32
FDNY Probationary Firefighters Manual
Chapter 12 ENGINE COMPANY CHAUFFEUR
5.4 One option for augmentation is to “self-augment”, which is accomplished when an engine
hooks up to both the 4 ½” and 2 ½” outlets of a single hydrant. To do this, a 2 ½” single
gate needs to be attached to the 2 ½” hydrant outlet before the hydrant is opened. Then,
when augmentation is needed, a 3 ½” hose (with an increaser) can be used to further supply
the rig using the single gate on the hydrant.
5.5 Often times, a hydrant can be especially difficult to open with a standard custodian wrench.
To overcome this, a “breaker bar” can be used to generate additional torque when using
the wrench. A breaker bar is a section of pipe that fits over the handle of the wrench and
acts as an extension of the handle, creating more force when opening a hydrant.
5.6 For further discussion on troubleshooting in emergency situations, refer to Chapter 13:
Engine Company Emergencies.
33
THIS PAGE WAS INTENTIONALLY LEFT BLANK
34
Probationary Firefighters Manual
THE BACKSTEP
1. OVERVIEW
1.1 “The Backstep” is a term used to describe the team of firefighters in an engine company
whose primary purpose is to stretch and operate hoselines to extinguish fire.
1.1.1 The Backstep is comprised of the following 4 firefighters and does not include the
Engine Company Chauffeur (ECC):
A. Nozzle firefighter
B. Back-up firefighter
C. Door firefighter
D. Control firefighter
1.2 The duties of each of these positions is described in the sections below. Additionally, all
firefighters should be able to perform the following basic operations (which are fully
discussed in Chapter 3: The Engine Company Chauffeur):
1.3 All firefighters should be familiar with buildings within their districts which pose extreme
difficulties when stretching hoselines (interconnected buildings, wrap-around stretches,
etc.).
1.4 All firefighters must be proficient in executing all types of hose stretches and must be
familiar with the proper usage of all related tools and equipment.
1.5 All firefighters must be proficient in forcible entry and must be familiar with the proper
usage of the halligan, axe, and all related forcible entry equipment.
1.6 All firefighters must conduct many individual size-ups during any incident, each of which
may have a direct impact on the success or failure of the operation. This includes reading
the response ticket for all relevant information, including CIDS, as well as a thorough size-
up of the fire building itself.
1.7 The following sections will describe the general responsibilities and techniques relevant
for the positions of the Backstep. The techniques specific to the various types of hose
stretches will be discussed in Stretching Hoselines p.59.
35
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
2.1 The firefighter assigned the nozzle occupies one of the most challenging and dangerous
positions on the fireground. The duties associated with the nozzle position routinely take
this firefighter in close proximity to the fire and require a determined and experienced
member.
2.2 This position is assigned by the officer at the start of each tour, but can be flexible
throughout the tour, allowing a less experienced firefighter to move up to the nozzle
position at a minor fire to gain valuable “on the job” experience.
2.3 In addition to their standard size-up, the nozzle firefighter should pay particular attention
to the various factors that influence the hoseline stretch and operation. This includes the
location of the fire apartment within the building, the type of stretch to be executed, the
type of stairway present, and the size of public hallways and stairway landings.
2.4.1 The Nozzle firefighter stretches the first length of hose with the nozzle attached via
the route and to the location determined by the officer (Figure 1). If the hosebed is
maintained using a horseshoe arrangement, the nozzle firefighter takes their length
by carrying the first horseshoe. If horseshoes are not used, the nozzle firefighter
takes their first length by grabbing the top 3 folds of the hosebed.
Figure 1
36
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
2.4.2 The hose should be stretched to a safe location in proximity to the fire area. If the
line is to be charged inside the building, such an area could be a stairway landing,
hallway, or adjoining area. From this point, it is the nozzle firefighter’s
responsibility to flake out the lead length of hose.
2.5.1 The nozzle firefighter is responsible for flaking out the lead length of the hose
stretch. A determining factor in the technique used to flake out the lead length will
be whether the hose is to be charged inside the structure (as in multiple dwellings,
etc.), or outside the structure (as in private dwellings, taxpayers, etc.).
2.5.2 In either scenario, the nozzle firefighter should carry the entire lead length intact to
the entrance to the fire area and flake out the hose from that location. This should
be in a safe area, but as close to the fire area as possible.
A. If the line is being charged inside the building, this point may be the door to the
fire apartment.
B. If the line is charged outside the building, this point will be the entrance to the
building.
2.5.3 When stretching hose carried in a horseshoe, an effective technique is to use the
midpoint of the length to efficiently flake the hose out. This is accomplished by
laying the horseshoe down at the point of deployment and pulling the hose from the
middle “ring” of the horseshoe (which is approximately the midpoint of the length).
The midpoint can then be walked or tossed away from the point of deployment for
a smooth flake out (Figure 2).
Figure 2
37
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
2.5.4 When properly flaked out, the nozzle and first coupling should be side by side at
the entrance to the fire area, ensuring an entire 50-foot length of hose is available
for the interior of the fire area.
A. This “U-shaped” orientation will facilitate a smooth advance into the fire
building by allowing the lead length to pivot at the first coupling. This allows
the lead length to advance without having to pull the weight of the entire line.
In effect, the nozzle team only has to advance the weight of one length of hose,
rather than the weight of the entire stretch.
2.5.5 When flaking out hose outside the structure (private dwellings, taxpayers, etc.),
consider the following:
A. The availability of space to flake the hose is not usually a problem when flaking
out outside the structure.
B. If possible, hose should be flaked out in line with the entrance to be used. This
is especially important when stretching 2 ½” hose, which is heavier and more
difficult to maneuver.
C. Avoid areas where the hoseline could be damaged by falling glass, heat, or fire.
2.5.6 When flaking out hose inside the structure (multiple dwellings, etc.), consider the
following:
A. The availability of space to flake out hose is a central concern when flaking out
inside a structure.
B. The condition of the public hall is also a critical concern. If conditions in the
hall allow, the nozzle length should be carried to the door to the fire area and
flaked out from there. If the public hall is untenable, the lead length will need
to be flaked out elsewhere (Figure 3).
C. If conditions allow, hose should be flaked out in the hallway on the fire floor.
If necessary, other apartments on the fire floor, on the same side of the public
hallway as the fire apartment, can be used for additional space.
D. If more space is needed, hose can be flaked up the interior stairway to the half
landing or the floor above, which allows gravity to assist with the advance of
the hose line into the fire apartment. Hose can also be flaked down the interior
stairway to the half landing or to the floor below the fire. When flaking out on
the floor above the fire, be mindful to allow space for the possibility that an
additional hoseline may be stretched to that area. When flaking hose out above
the fire floor, the nozzle firefighter should ensure the door to the fire area is
being controlled.
E. When hallways and landings are extremely small, hose can be flaked out on the
floor below the fire and advanced to the fire area.
38
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
Figure 3
F. The hose needed to reach the fire area should be supplied by the length carried
by the back-up firefighter. This ensures the nozzle firefighter’s length is
reserved for the fire area itself. Additional hose from the back-up firefighter’s
length will be used to make sure there is enough extra hose available and flaked
out to facilitate a smooth advance into the fire area.
G. While most apartments require one length of hose, it is possible for larger
apartments or duplexes to require additional hose for the fire area. With this in
mind, the nozzle firefighter should estimate the amount of line needed to cover
the entire fire area and communicate this need to the back-up firefighter, who
may have to adjust the location of their drop point to accommodate the
additional hose required for the fire area.
H. When the public hall on the fire floor is untenable, the lead length will have to
be flaked out in a safe area elsewhere. This may be on the floor below, or
possibly inside the stairway (if the stairway is enclosed). Ideally, the lead length
should be flaked out in the same manner at the point of deployment, with the
nozzle and first coupling next to each other as close the fire area as practical.
2.5.7 When flaking out the lead length, the hose should be laid out as neatly as possible
to reduce the chances of kinking or snagging the line once the line is charged.
39
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
2.6.1 After flaking out the line in preparation for its advance, the nozzle firefighter should
keep a knee on the nozzle to protect it from being kicked or moved while they don
their SCBA facepiece.
2.6.2 Once their protective equipment is donned and the line is flaked out, the nozzle
firefighter should signal the engine officer that they are ready for water. The
decision to charge the line is ultimately made by the engine officer.
2.6.3 When the engine officer calls for water the nozzle firefighter must prepare for a
“long bleed” of the hose line. This allows for the release of air trapped in the hose,
confirms serviceability of the nozzle, and allows the operating pressure to be
accurately set.
A. To bleed the line, the nozzle is fully opened after water reaches nozzle, allowing
water to flow. While waiting for the line to be charged, the nozzle can either be
kept closed or cracked slightly open, allowing air to escape.
B. When bleeding the line, it should be directed towards the fire area, if possible.
In buildings with elevators, an attempt should be made to direct the bleed away
from elevator shafts. This can help keep elevators serviceable for firefighting
operations.
C. The long bleed is especially important at standpipe operations, as it allows the
control firefighter to accurately set the operating pressure at the standpipe outlet
while water is flowing.
D. The long bleed is also particularly important when a 2 ½” hoseline is stretched
from the apparatus. At these operations, the lower friction loss of the 2 ½” hose
will require lower discharge pressures and the operating pressure may be below
the preset on the Pro Pressure Governor. In such cases, the ECC will need to
manually set the operating pressure at the discharge gate while water is flowing.
Without a long bleed, the ECC may not have the opportunity to set the pressure
properly.
2.6.4 The nozzle firefighter must be at a position at the door to the fire area crouched low
and out of the doorway opening itself, regardless of conditions. A sudden ceiling
collapse, rapid self-venting or a fire driven by wind could create a blowtorch effect
at the entrance door and seriously injure any firefighter in its path.
A. This position also allows unobstructed access and egress for the ladder company
operating in the fire apartment prior to the line being charged. After entry is
made into the fire area, the advancement technique may be adjusted based on
conditions encountered.
2.6.5 The nozzle firefighter should never enter the fire area without a charged hoseline.
To do so could allow the fire to rapidly extend and overtake the nozzle team causing
burns to them and any firefighters operating behind or above them.
40
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
2.7.1 There are a number of decisions the nozzle firefighter is empowered to make while
operating a hoseline. They are as follows:
A. Direction of the stream
B. Rate of advancement
C. Sweeping the floor with the stream
D. Calling for more line
E. Partially closing the nozzle to reduce nozzle reaction and regain control
F. Opening the nozzle in an emergency
G. Communicating the need to be relieved on the nozzle
2.7.2 The nozzle firefighter must understand that the decision to open or close the nozzle
is made by the engine officer. Based on the conditions encountered, the officer
may decide to have the nozzle opened on smoke and high heat, or they may decide
to advance the line until the nozzle can be opened on visible fire.
2.7.3 Opening the nozzle on smoke is a preventive measure taken so that hidden fire can
be extinguished while reducing the chance of flashover. If there is a smoke
condition with high heat, the nozzle should be opened on the smoke and operated
as necessary to cool the area and advance toward the fire. This is done only at the
direction of the engine officer.
2.7.4 Advancing a hoseline under a smoke layer without opening the nozzle is not
unusual at fires. In the absence of high heat and turbulence in the smoke, conditions
may be such that advancing the charged line in the smoke condition without
opening the nozzle would be more effective. The line can be advanced with the
nozzle closed until the fire can be hit directly with the stream.
2.7.5 Once fire is visible, the nozzle should be opened and the fire extinguished, as
ordered by the engine officer. Never pass fire; extinguish it and continue to advance
the line. This includes fire visible in the upper levels of a smoke condition, which
should be extinguished to prevent a pre-flashover condition from reaching
flashover.
41
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
Figure 4
B. The nozzle firefighter should keep the nozzle out ahead of their body at a
distance such that they can comfortably operate the nozzle handle with their
arm extended (Figure 5). This distance allows them to manage the movements
of the nozzle, giving them the ability to achieve complete coverage of the fire
area from ceiling to floor.
Figure 5
42
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
C. When using the 1 ¾” hose, most movements of the nozzle are made by the
nozzle firefighter simply turning the nozzle itself. The bend in the hoseline will
occur in the distance of line between the nozzle itself and the nozzle firefighter’s
body.
D. Using the pistol grip while operating the hoseline is not recommended, as it will
limit the nozzle firefighter’s effective maneuverability.
Figure 6
43
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
2.7.8 In the FDNY, there are two basic nozzle advancement techniques used: “Flow and
Move” and “Stop and Flow”. Both of these techniques are effective with both the
1 ¾” hose and the 2 ½” hose.
2.7.9 “Flow and move” is a technique that involves opening the nozzle and advancing
the line with the nozzle open and water flowing until extinguishment is reached.
This is the standard technique taught in the FDNY Fire Academy and is effective
in nearly all fire situations.
A. This technique makes for a rapid advance on the fire while providing a reduced
temperature environment in which to travel. Additionally, temperature rebound
does not occur, as the line will not be shut down and the fire will not have a
chance to regain strength.
B. This technique provides for increased nozzle team safety by enabling the nozzle
team to direct a flowing nozzle as the need arises, as in the situation of the
discovery of an additional room of fire. It also allows the nozzle team to pace
their rate of advancement to meet conditions encountered; once an area is cool
enough to enter, the line can be quickly advanced.
C. By flowing water as the nozzle team advances down the hallway towards the
fire area, the reach of the stream is being used to facilitate extinguishment.
Additionally, surface cooling and gas contraction will be maximized, both of
which contribute to effective extinguishment.
2.7.10 “Stop and Flow” is a technique that involves opening the nozzle and operating
from a stationary position while extinguishing fire. The nozzle is then partially
closed as the line is advanced further without water flowing. Upon reaching the
next point of operation, the advance is stopped and the nozzle is re-opened for
extinguishment.
A. This is the primary technique to be used when advancing a 2 ½” hoseline.
B. This technique is useful in situations where obstructions or other physical
obstacles create a difficult path of advancement for the line, such as heavy
clutter conditions. It is also useful when faced with fire in multiple, separate
locations.
C. “Stop and Flow” has the effect of cooling an area so the nozzle can be further
advanced to a position from which the main body of fire can be extinguished.
D. “Stop and Flow” should not be used when faced with heavy fire conditions or
high heat. It requires sufficient knockdown of the fire to allow for the
advancement of the line before the fire can regain strength.
44
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
2.7.11 The nozzle firefighter must constantly be aware of the need to sweep the floor ahead
of the advancing nozzle team. This is true when using either nozzle advancement
technique.
A. This should be a quick and deliberate side to side motion to achieve good
coverage of the floor area ahead of the nozzle team.
B. Sweeping the floor will clear the path of debris, burning embers, and hot water.
It also allows the nozzle firefighter to detect a change in the impact noise of the
stream, which could indicate an obstacle or the lack of a solid floor ahead of the
nozzle team.
C. The nozzle firefighter should sweep the floor (Figure 7) each time the nozzle
team makes another forward push, and not just a single sweep when entering
the fire area.
Figure 7
45
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
2.7.12 While operating, the nozzle firefighter can use the stream impact noise as a guide
to which direction to advance or direct the hoseline.
A. The lack of impact noise, while operating the nozzle above the floor level, could
indicate an opening such as a doorway or a window. Conversely, an increase in
impact noise could indicate an obstruction and the need for the nozzle to be
operated in a different direction. The nozzle firefighter should have the ability
to ‘see what they hear’ when deciding on direction of the stream.
2.7.13 When advancing the hoseline, the nozzle firefighter should normally operate from
a “knee-up” position, with one knee up in front of them and one knee down.
A. This position provides a stable platform that allows the nozzle firefighter to
keep the hose line in tight and close to their body as they operate. This is
especially important in cluttered areas where unsure footing could cause the
nozzle firefighter to lose balance.
B. This position also naturally forces the nozzle to be directed upward toward the
ceiling, which causes the line behind them to be directed downward toward the
floor. This can assist the nozzle firefighter in handling the nozzle reaction.
2.7.14 When using this “knee-up” position, the hoseline can be advanced using two
methods:
A. Step forward - The nozzle firefighter can use the forward leg, which has the
knee up, to step forward while lifting and dragging the other knee
B. Alternating knees - The nozzle firefighter can roll one knee forward and down,
while raising the other knee, thereby alternating knees which have contact with
the hot floor surface
2.7.15 As an alternative to the knee-up position, the nozzle firefighter can also operate
with their front leg outstretched, while their other knee is down.
A. This method gives the nozzle firefighter a lower profile, which can provide more
control of nozzle and direction of the stream. It also allows them to check the
integrity of the floor surface ahead of the advancing hose line
B. However, the outstretched leg method can make it more difficult to continually
advance the line, especially in clutter conditions.
2.7.16 While it is possible to operate the hoseline with both knees off the ground in a
“duckwalk” technique, this can be difficult to execute while wearing bunker pants.
The duckwalk was primarily used before the development of bunker pants, which
provide the knees with a degree of protection that makes it possible for them to stay
in contact with the floor.
46
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
2.7.18 If fire appears behind the nozzle team as it is advancing the hoseline, it must be
immediately addressed. Fire behind the nozzle is a serious threat, as it blocks the
egress of the nozzle team and any other members operating ahead of the nozzle.
A. This problem can be complicated if the nozzle team is operating in a narrow
area that would prevent the nozzle firefighter from simply turning around to
extinguish the fire behind them.
B. In this case, the nozzle firefighter should bend the hoseline back on itself and
pass the line to the back-up firefighter, who is better positioned to extinguish
the fire behind them. The nozzle firefighter will act as their back-up while they
operate the hoseline.
C. When passing the nozzle back, the nozzle firefighter should be sure to turn
towards the hoseline to avoid getting tangled in the line. The nozzle will pass
overhead as it is bent back and should be maintained open, if possible.
D. Once the fire behind the nozzle team is extinguished, the back-up firefighter
will similarly bend the line back in the original direction and pass the nozzle
back to the nozzle firefighter to continue advancing the line.
E. It should be noted that the nozzle firefighter is not “giving up the line” in this
case; they are simply working together with the other half of their nozzle team
to temporarily address an immediately dangerous situation.
47
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
3.1 The back-up firefighter works together with the nozzle firefighter to form the “nozzle
team” and is responsible for providing the nozzle firefighter with physical and moral
support as the hoseline is advanced.
3.2 In addition to their standard size-up, the back-up firefighter should pay particular attention
to the various factors that influence their ability to properly execute the stretch and flake
out the hoseline. This includes sizing up the specific route of the stretch, as well as the size
and location of public hallways and stairway landings.
3.3.1 The member assigned the back-up position is the second firefighter on the hoseline.
This firefighter is responsible for removing the second length of hose from the
hosebed and then proceeds, in unison with the nozzle firefighter, to the fire area. If
the hosebed is maintained with the 2nd length in a horseshoe, the back-up firefighter
carries the second horseshoe. If there is no horseshoe, the back-up firefighter takes
their length by grabbing the next 3 folds of the hosebed.
3.3.2 The back-up firefighter will drop and flake out their length of hose in coordination
with the nozzle firefighter. The proper deployment of the length of hose contained
in the back-up firefighter’s horseshoe is essential, as it is the hose the nozzle
firefighter will need to reach the fire area with their full length intact.
3.3.3 Once their length is properly deployed and flaked out, the back-up firefighter
should also help flake out hose from the nozzle firefighter’s length.
3.4.1 Before the hoseline is charged the back-up firefighter should ensure the hoseline
near the fire area is properly flaked out and that the nozzle firefighter has enough
hose available to make an advance on the fire.
3.4.2 When the line is charged, the back-up firefighter should make a quick check for
kinks and take a position behind the nozzle firefighter providing physical as well
as moral support as the fire attack is commenced.
48
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
3.5.2 The back-up firefighter should avoid pushing the nozzle firefighter forward as they
operate the line. Instead, they should work to absorb the backwards thrust of the
nozzle reaction and advance at the pace set by the nozzle firefighter.
3.5.3 In order to achieve this, the back-up should be on the same side of the hose as the
nozzle firefighter and as close as physically possible behind them (Figure 8).
Figure 8
3.5.4 In a situation in which the line is flowing but not advancing, the back-up firefighter
can pin the line to the floor and achieve the same desired results (Figure9).
Figure 9
49
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
3.6 The back-up firefighter should be positioned so they can look forward as they advance.
This allows the back-up firefighter to see what the nozzle firefighter sees and enables them
to anticipate the nozzle firefighter’s movements.
3.7 The back-up firefighter should maintain a firm grip of the advancing hoseline at all times.
If this member was to lose control of the line, the reaction of the opened nozzle could pull
it through the grasp of the nozzle firefighter and leave the nozzle team unprotected from
the fire.
3.8 When the nozzle firefighter wants to change the direction or elevation of the stream, the
back-up member should maneuver the section of hose behind the nozzle firefighter in the
opposite direction. This is especially true when operating a 2 ½” handline, in which the
back-up firefighter can hinder the operation if they do not coordinate their movements with
the nozzle firefighter.
3.9 During the initial hoseline advance, the back-up firefighter should maintain the hoseline
below the level of the operating nozzle and keep the line as straight as possible. Any change
in direction could lead to a severe kink between the back-up firefighter and the nozzle.
3.10 In the event the advance of the hoseline is stalled due to insufficient available hose, the
back-up firefighter may need to momentarily leave the nozzle firefighter to retrieve the
hose necessary to continue the fire attack. This must be coordinated with the officer and
nozzle firefighter.
4.1 The door firefighter is responsible for supplying the nozzle team with sufficient hose to
make the fire attack and ensures the proper flaking out of the hoseline.
4.2 In addition to their standard size-up, the door firefighter should pay special attention to the
particular route of the stretch and the size and location of areas to flake out excess hose.
4.3.1 The member assigned the door position is the third firefighter on the hoseline. This
firefighter is responsible for removing the third length of hose from the hosebed
and carrying it to an appropriate drop point in the hose stretch. If the hosebed is
maintained with the 3rd length in a horseshoe, the door firefighter carries the third
horseshoe. If there is no horseshoe, the door firefighter takes their length by
grabbing the next 3 folds of the hosebed.
4.3.2 After dropping their hose, the door firefighter assists with flaking out the hoseline in
preparation for it being charged. The door firefighter is also responsible to check the
stretch for kinks while proceeding to the entrance of the fire area.
50
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
4.4.1 The door firefighter should also identify any potential pinch points the hoseline will
encounter. Any potential pinch point should be dealt with by placing extra hose in
the area of the pinch point itself, prior to advancing to the entrance of the fire area.
Such pinch points can include a stairway newel post, a doorway, or any abrupt turn.
4.5.1 After the nozzle team enters the fire area with the charged line, the door firefighter
takes a position at the entrance of the fire area and slowly feeds line into the
advancing nozzle team. The door firefighter must not push the hoseline to the
nozzle team, but instead provide enough slack in the line so that they can advance
easily.
4.5.2 The door firefighter should maintain a bow in the section of hoseline between the
door and the nozzle team. This tactic will allow the door firefighter to monitor the
advance of the nozzle team by observing the straightening of the hoseline. As the
hose straightens the member restores the bow in the line (Figure 10).
4.5.3 When maintaining bow in the line, avoid placing the hose high up against a wall
where it will be subjected to high heat levels and possible burn through.
Additionally, a firefighter attempting to exit the area by following the hoseline may
lose contact with the hoseline if the bow is maintained high against the wall.
Figure 10
4.5.4 In large rooms or open areas, it may be possible to maintain a horizontal bow in the
line, rather than a vertical bow. This will look like a large loop in the line, laid
horizontally on the floor. As the line is advanced, the door firefighter can feed hose
to the nozzle team the same way as with a vertical bow (Figure 11).
51
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
Figure 11
4.5.5 In larger apartments or private homes the door firefighter may be forced to move
into the fire area to keep line of sight with the nozzle team. Maintaining visual
contact with the nozzle team is necessary to ensure they are supplied with enough
line as they advance.
4.5.6 If either member of the nozzle team requires relief or is injured, the door firefighter
can quickly move into position and the attack on the fire can continue. The door
firefighter should consider leaving their flashlight on which would serve as a guide
for members exiting the fire area.
4.5.7 An important task of the door position is to monitor and observe heat, smoke and
fire conditions at the entrance doorway. Undetected or extending fire could
suddenly erupt or appear between the entrance and the nozzle team. The door
firefighter is in a prime location to detect this situation and warn the nozzle team.
This position at the entrance to the fire area also gives the door firefighter the ability
to monitor and warn the firefighters going above the fire in the case of a sudden
change in conditions or water loss.
52
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
5.1 The member assigned the control position is the last firefighter on the hoseline. The control
firefighter’s primary function is to ensure the correct amount of hose is stretched to enable
the nozzle team to advance to the seat of the fire.
5.2 The success of an engine company hoseline operation relies greatly upon the actions of the
control firefighter. Where possible, only experienced and knowledgeable firefighters
should be assigned the control position. This will assure a more accurate hose estimate
and removal from the apparatus.
5.3 In addition to their standard size-up, the control firefighter should pay special attention to
the route of the stretch and the various factors that influence the number of lengths of hose
required to reach the fire area. This includes sizing up the location of the fire apartment,
type of stairway present, and any possible obstacles in the stretch.
5.4.1 The control firefighter is responsible for the accurate estimation of the amount of
hose to be stretched. Their objective is to ensure enough hose is stretched to reach
the seat of the fire, while minimizing the number of excess lengths used. Excessive
hose increases both friction loss and the potential for kinks, which can cause a
considerable reduction in both flow and stream quality at the nozzle.
5.4.2 The control firefighter must pay close attention to the particular route of the stretch
in order to accurately estimate the amount of hose to be used. This includes
consideration of the following:
A. Distance from apparatus to building entrance
B. Distance from building entrance to foot of stairs
C. Type of stairs to be used
D. Number of floors to ascend or descend
E. Distance to fire area from stairs or building entrance
F. Size of fire area
53
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
5.4.3 When estimating the amount of hose to be used, the distance involved in each of
the building features listed above needs to be accounted for. The following are
guidelines to be considered:
A. At least 1 full length of hose is needed to cover the fire area. Larger apartments
or fire areas may require 1 ½ lengths.
B. Roughly 1 length is needed to travel up (or down) 1 floor.
C. For a wrap-around stretch, roughly 1 ½ lengths are needed to travel 1 floor
D. For a well hole or rope stretch, 1 length of hose stretched vertically can travel
roughly 5 floors.
E. Generally, return type stairs may require more hose than straight run stairs.
5.5.1 To effectively control the hose stretch, the control firefighter must remain last in
the stretch. This is true even when they are assisted by another unit in the stretch.
When the 2nd engine arrives to assist the stretch, the 1st control firefighter should
not delegate or transfer the control position to the 2nd control firefighter. Instead,
they should maintain a position at the hose bed and complete the hose estimate and
removal.
5.5.2 The control firefighter’s position at the hosebed is especially critical when
performing a backstretch, as the ECC may be waiting for the necessary hose to be
removed prior to proceeding to a hydrant.
A. If the control firefighter was to abandon this position, it may delay the ECC in
securing a water source. It may also give the ECC the false impression that
sufficient hose has already been stretched, which could lead to the apparatus
being prematurely repositioned to a hydrant. If this occurs before enough hose
is removed, a short stretch could result.
B. To avoid the above mistakes, direct face to face communication between the
control firefighter and ECC regarding the number of lengths removed should
take place prior to moving onto the hydrant.
5.5.3 The control firefighter shall remove hose from the hosebed in a manner that allows
for later arriving firefighters to easily pick up their length of hose in the street.
A. After the nozzle, back-up, and door firefighter take their lengths from the
hosebed, the control firefighter shall remove additional required lengths of hose
individually and place them on the ground in the direction of the stretch. Later
arriving firefighters can more readily stretch these lengths, as needed.
B. The control firefighter should avoid simply pulling hose off the hosebed and
piling it on the ground. This complicates the stretch and delays the positioning
of the line.
54
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
5.5.4 After sufficient hose is removed from the hose bed, the line must be broken and
connected to a pump discharge outlet. The control firefighter must inform the ECC
of the size of hose, total number of lengths stretched, and which floor the hose is
stretched to.
A. If a backstretch is performed, once sufficient hose has been stretched, the
control firefighter will signal the ECC to proceed to the hydrant to be used. At
this point, the line will be broken and connected to a discharge outlet.
B. When a second hoseline is dropped at the same time as the first hoseline, the
control firefighter must be sure to correctly identify to the ECC which hoseline
each unit is operating.
5.5.5 If the hydrant used is in close proximity to the fire building, the control firefighter
may assist the ECC with hydrant connection after controlling the hose stretch. This
should only occur after the hose stretch has been completed.
A. If in-line pumping is used, the control firefighter may similarly assist the ECC
with connections as necessary after the stretch is completed.
5.6.1 After sufficient hose has been stretched and the ECC does not require their
assistance, the control firefighter should assist in flaking out hose between the
apparatus and the building entrance door, in addition to feeding slack toward
firefighters ahead on the line. In doing this, they should remain mindful of the
following:
A. Minimize the number of turns made by the hoseline outside the building.
B. Hose should not be stretched or flaked out in the middle of the street.
C. If apparatus positioning or the presence of cars makes stretching in the street
difficult, bring the hoseline onto the sidewalk close to the apparatus and stretch
by way of the sidewalk.
D. If the hoseline needs to cross the street, cross over as close to the fire building
as possible, while remaining mindful of ladder company positioning.
E. Leave room for the hoseline to move around any obstructions or pinch points,
such as parked cars, trees, fences, or doorways. Be especially mindful of car
tires, which can easily snag the hoseline.
5.6.2 Once the line is charged, the control firefighter will eliminate kinks in the hoseline
as they move along the line toward the fire area. This may require repositioning of
hose in halls and stairways and straightening any bends that are restricting the water
flow.
55
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
5.7.1 Once the line is charged and the stretch is checked for kinks the control firefighter
should take a position at the entrance to the fire area, this allows the door firefighter
to move into the fire area allowing them to better supply the nozzle team with line.
5.7.2When an engine is staffed with four firefighters the control firefighter will also assume
the responsibilities of the door firefighter.
5.8.1 The responsibilities of the control firefighter differ significantly when the hoseline
is stretched from a standpipe outlet. In this case, the control firefighter is
responsible for supplying the proper pressure to the hoseline from the outlet.
5.8.2 The control firefighter’s responsibilities at a standpipe operation are fully discussed
in Standpipe Operations page 93.
6.1 Generally, the backstep of the 2nd arriving engine will assist the 1st arriving engine in
stretching and operating the 1st hoseline. Members should maintain their assigned order as
they assist in the stretch, with the nozzle firefighter closest to the 1st arriving company,
followed by the back-up, door, and control firefighters
6.2 `If the 2nd engine arrives on scene before the 1st engine begins the stretch, they should join
the 1st arriving engine at the back of the apparatus and assist in the stretch. If necessary,
members of the 2nd arriving engine should carry a full length each by grabbing 3 folds of
hose from the hosebed. This may be needed for a long stretch.
6.3 If the 2nd engine arrives after the 1st engine has begun stretching, the 2nd arriving members
should begin assisting with the stretch only after they have confirmed the position of the
1st arriving engine and the progress of the stretch. This may require the 2nd arriving
members to enter the building and follow the line to determine the progress made by the
stretching members.
6.4 When backing up a hoseline in operation, the members of the 2nd arriving engine should
ensure the smooth advance of the hoseline. This will require the members be positioned in
proximity to the 1st arriving company, while remaining adequately spaced out on the
hoseline.
6.5 However, members of the 2nd arriving engine should also strive to conserve air and remain
outside of an IDLH atmosphere as much as possible, as they may be assigned to relieve the
1st arriving engine on the nozzle at a prolonged operation. Their position should consider
both the need to advance the charged line and the need to conserve air for possible relief.
56
FDNY Probationary Firefighters Manual
Chapter 12 THE BACKSTEP
7.1 For later arriving engine companies at a fire operation, the hoseline operations of the
members of the backstep will be determined by whether the company is stretching and
operating their own hoseline, or whether they are the company backing the hoseline up.
7.2 Engine companies that are stretching and operating their own hoselines should operate
similar to the 1st arriving engine company, as described above.
7.3. Generally, this will include the 3rd arriving engine, who is usually responsible for stretching
and operating the 2nd hoseline at a fire operation.
7.4. Any company stretching their own hoseline must determine the destination of their
hoseline and the location of the apparatus from which they will stretch the hoseline.
Depending on the location and availability of engine apparatus, this may not necessarily
be the same apparatus from which the 1st hoseline was stretched.
7.5 Engine companies that are backing up additional hoselines should operate similar to the
2nd arriving engine company, as described above. They must confirm the identity of the
unit who is stretching the hoseline they will be backing up.
57
THIS PAGE WAS INTENTIONALLY LEFT BLANK
58
Probationary Firefighter Manual
STRETCHING HOSELINES
1. STRETCHING HOSELINES
1.1 In the FDNY, the primary method of fire extinguishment is by way of a hoseline hand-
stretched from the engine apparatus. The method used to stretch the hoseline depends on a
variety of factors, including the fire situation encountered, building construction, and
stairway type.
1.2 When stretching hoselines from an apparatus, the FDNY stretches either 1 ¾” hose or 2
½” hose to extinguish fires. The decision of which line to stretch is made by the engine
officer and is further discussed in The Engine Company Officer page 1. All of the hose
stretching techniques discussed in this chapter are effective for stretching either size
hoseline.
1.3 The placement of the hoseline and the path of travel are also determined by the Engine
Officer and are also discussed in The Engine Company Officer page 1. However, the 1st
and 2nd hoselines are generally stretched to the fire area by way of the building’s primary
means of egress.
1.4 The interior placement of the first hoseline by way of the primary means of egress provides
protection for evacuating occupants and firefighters alike, while allowing direct fire
extinguishment. However, in some situations (cellar fire in a private dwelling, fire in a
place of worship, etc.), hoselines are stretched by way of the entrance which provides the
quickest access to the fire.
1.5 Depending on the occupancy and conditions encountered, the first hoseline may either be
flaked out and charged outside the fire building, or it may be stretched into the fire building
and flaked out in a safe area in proximity to the fire area before it is charged.
1.5.1 Generally, the hoseline is charged outside the fire building for fires in buildings that
do not contain public hallways or stairs which are separated from the occupancy
areas. This includes private dwellings, places of worship, taxpayers, and similar
occupancies. This tactic may also be necessary if units are met with fire at the main
building entrance of any occupancy type.
1.5.2 For fires in buildings that contain public hallways or stairs which are separated from
the occupancy areas, like multiple dwellings, lofts, and similar occupancies,
primary hoselines will be stretched dry inside the fire building and will be flaked
out and charged in a safe area as close to the fire area as practical.
1.6 When stretching hoselines inside the fire building, the most critical factor in determining
the manner in which the first and second hoselines are stretched is the type of interior stairs
to be used. The concerns that are of the greatest consequence for stretching hoselines are
the following (which will be further described in the sections below):
59
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
1.6.4 Does the layout of the stairway complicate the stretch, or can it make it easier?
(Is there a well hole? Does it wrap around an elevator shaft?)
2. TYPES OF STAIRWAYS
2.1 Each of the concerns listed above should be determined when a stairway is to be used to
stretch a line. This is accomplished by categorizing the stairway based on the following
questions:
2.3.1 Open stairways are directly exposed to the public hallway and generally extend
from the ground floor to the roof. They do not have doors separating them from
the public hallway and cannot be isolated to provide a safe area on the fire floor.
2.3.2 It is common to have a roof vent at the top of an open stairway (skylight, bulkhead,
scuttle, etc.), which can be used to relieve the early upper level smoke travel that is
common in an open stairway.
2.3.3 The floors above the fire will become quickly filled with smoke, which can
complicate stretching and operating additional hoselines on upper floors.
60
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
Figure 1
2.4.1 Enclosed stairways are separated from the public hallway on each floor by a door
(Figure 3). If conditions in the public hallway are untenable, this stairway door can
be controlled to provide a safe area from which to operate on the fire floor.
2.4.2 This stairway provides a barrier to smoke travel and allows safe passage for egress
on all floors (in stairways other than the attack stair).
2.4.3 Smoke conditions on floors above the fire can be less severe in the case of an
enclosed stairway, as each floor will be isolated from the path of smoke travel.
Figure 2
61
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
Figure 3
2.5.1 Straight run stairways are stairs that run in a single direction from floor to floor
(Figure 4). As a result, the entrance to the stair at the bottom of the stairway will
not be directly beneath the exit from the stairway on the floor above.
Figure 4
62
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
2.5.2 Typically, these stairs are stacked over each other in most buildings. Sometimes,
the straight run stairs are oriented so the stairway is a continuously straight run for
a number of floors. While climbing a continuous straight run staircase, the access
point on each floor will be increasingly further away from the original stairway
entrance. This type of stairway can be found in loft buildings and other large
occupancies (such as theaters).
2.6.1 The defining characteristic of a return stairway is that the stairway’s access point is
located at the same place on each floor. When using this stairway, you will “return”
to the same spot when you enter each floor.
2.6.2 Return stairs generally exist in one of three possible orientations: straight run
stacked stairs, half-landing return stairs, or wrap-around stairs.
2.6.3 Straight run stacked stairs involve a straight run stairway connecting each floor.
However, the stairway is not continuous; to continue up the stairway, you will have
to walk down a hallway on each floor to return to the bottom of the next flight. The
result is a series of straight run stairs oriented in the same direction and stacked on
top of each other.
2.6.4 Straight run stacked stairs can be found in a variety of occupancies, but are common
in brownstones, old law tenements, and some styles of private dwellings.
Figure 5
63
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
2.6.5 Half-landing return stairs have a platform (half-landing) between floors, which
allows the stairway to change direction and return to the same access point location
on each floor (Figure 5). In effect, there are two sets of stairs between each floor:
one going from the floor to a half-landing, and another going from the half-landing
to the next floor (facing the opposite direction).
Figure 6
2.6.6 Half landing return stairs (Figure 6) can be found in a variety of occupancies, but
are commonly found in new law tenements, larger apartment houses, and high-rise
multiple dwellings (including Class 2 buildings).
2.6.7 It is possible for a half landing return stair to have more than one platform (half-
landing) between floors. If there is more than one change-of-direction platform, the
result will be a “wrap-around” staircase that wraps around between floors as it
returns to the same access point on each floor.
2.6.8 These “wrap-around” stairs can exist in larger buildings of various occupancies,
including new law tenements and larger apartment houses. The stairway may wrap
around an elevator shaft, or it may have a large well-hole.
64
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
2.6.9 Wrap-around staircases (Figure 7) can have one or more half-landings between
floors. In either case, it will also be necessary to walk around the remaining turns
on each floor to access the next flight of stairs. In essence, these wrap-around stairs
combine the elements of straight run stacked stairs and half-landing return stairs.
When wrapped around an elevator shaft (or other obstruction), wrap-around stairs
present a challenging stretch.
Figure 7
2.7.1 Scissor stairs are a series of continuous stairs (Figure 8) that change direction at
each floor. A flight of stairs will run in one direction up to the next floor where a
landing is found, allowing the stairway to change direction. The direction of the
stairway changes at the landing and the next flight of stairs will be oriented in the
opposite direction. These stairs are continuous in the sense that you don’t have to
leave the stairway to continue to the next floor.
2.7.2 The result is that the stairway access point in the public hallways will not be the
same on each floor. Rather, the location of the access point will alternate from floor
to floor. However, the access point on alternating floors will be in the same location
(if you climb two flights up, the stairway exit will be in the same location). This
can be a source of confusion at a fire operation.
65
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
Figure 8
2.7.3 Typically, scissor stairs exist in pairs; there will be two stairways that mirror each
other as they continue from floor to floor. The staircases will crisscross as they go
between floors and their access points will be at opposite (Figure 9) and alternating
locations on each floor.
Figure 9
66
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
2.7.4 Scissor stairs must be properly labelled. Mislabeled scissor stairs can cause great
confusion at an operation. Each stairway should have the same letter designation
throughout its span; it does not alternate as you climb from floor to floor. Instead,
the orientation of the lettered staircases in relation to each other on each floor will
alternate. The Incident Commander must be notified immediately when members
find stairs mislabeled at an operation so that all units can be made aware of this
matter.
2.7.5 Scissor stairs are most commonly found in high-rise multiple dwellings, high-rise
commercial buildings, and other large occupancies. They can also be encountered
in various styles of newly constructed low-rise multiple dwellings.
2.8.1 Transverse stairs are stairways that provide access to all apartments on a floor. By
using a transverse stairway, access is possible to all apartments.
2.8.2 Transverse stairs are a key concern in buildings with multiple stairways, such as
new law tenements or larger apartment houses. Typically connected by a
“transverse hallway”, these stairs are often located at the ends of the hall. The
hallway allows members to transverse to all apartments and all stairways.
2.9.1 Wing stairs are stairways that provide access to only the apartments found in a
specific section (or “wing”) of a building. By using wing stairs, there will be
apartments in the building that cannot be accessed.
2.9.2 Wing stairs can access a “wing hallway”, which only provides access to apartments
in that specific section (wing) of the building. While smaller than transverse
hallways, these wing hallways are often large enough to accommodate flaking out
hose.
2.9.3 Wing stairs are often found in new law tenements and larger apartment houses and
are a key concern when stretching hose. Care must be taken to ensure the correct
stairway is used to access the fire apartment.
2.10.1 Isolated stairs are stairways that access only a small number of apartments and are
isolated from other areas of the building. By using isolated stairs, there will only be
access to the apartments immediately accessed by the stairs.
67
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
2.10.2 There is typically no hallway associated with isolated stairs. Rather, these stairs
open onto a landing on each floor, from which the apartments are accessed. This
landing area can be small and may present difficulty in flaking out hose.
2.10.3 Isolated stairs can be found in a number of building types, including new law
tenements, apartment houses, and other newly constructed multiple dwellings.
When faced with isolated stairs, care must be taken to ensure the correct stairway
is used to access the fire apartment.
2.11.1 While a “well hole stairway” is not a specific type of stairway in a strict sense, the
presence of a well hole is a critical concern when stretching hose. A well hole
stretch can save time, energy, and minimize the amount of hose needed.
2.11.2 A well hole is the empty area in the center of the stairway that serves as a vertical
void spanning the length of the stairs. If the space is large enough, this area can be
used to aid in the hose stretch.
2.11.3 Well holes can exist in all three types of return stairways (straight run stacked stairs,
half-landing return stairs, or wrap-around stairs) and may also exist in some scissor
stairways.
3. TYPES OF STRETCHES
3.1 Typically, at fires above the first floor, the first hoseline at a fire operation is stretched by
way of the main building entrance and the interior stairs. This is done to protect the primary
means of egress.
3.2 However, there may exist specific building characteristics or situational considerations
may necessitate a variation from stretching via the primary means of egress and an
alternative method may be appropriate (such as a rope stretch or fire escape stretch).
Buildings where these alternative methods may need to be employed should be identified
in CIDS.
3.3 The following sections describe various techniques to stretch hoselines using different
types of interior stairways and various techniques of exterior stretches.
4.1 In a traditional stairway stretch, the hoseline is stretched by carrying the hose up the interior
stairway and to the fire area (Figure 10). As the hose is stretched, each member carries
their length (in folds or a horseshoe) and the hose plays out on the stairway behind them.
68
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
Figure 10
4.2 In this type of stretch, two critical concerns are managing the turns on the staircase and
determining the proper drop point for the length of hose carried by each member.
4.3 To properly manage the turns on the stairway, the hose should be carried in the outside arm
of the stretching members. This will help the members make wide turns with the hose as
they climb the stairs. This is important because, if stairway turns are taken too tight, the
hose can get caught on the turns as the members climb. If this happens, the back-up
firefighter or other members may have to go back to loosen the hose around the caught
turn.
4.4 The nozzle firefighter will carry their length (folds or horseshoe) intact to the point of
deployment, which will be as close to the fire area as possible. They should keep their
length intact to be used in the fire area itself. If the hallway is tenable and if there is enough
room, the hose should be flaked out in the hall.
4.5 If there is not enough room in the hallway on the fire floor, the length can be flaked up to
the half-landing (if present) or all the way up to the next landing. Hoselines can also be laid
out in adjoining apartments (on the same side as the fire apartment) on the fire floor if
additional space is needed. Alternatively, the hose can be flaked out on the floor below the
fire and advanced up to the fire floor.
4.6 If the public hallway on the fire floor is untenable the hoseline may need to be flaked out
and charged on the floor below the fire.
69
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
4.7 The back-up firefighter carries their length (in folds or a horseshoe) and must determine
the proper drop point at which to deploy their length. This should be coordinated with the
nozzle firefighter. The proper deployment of the length of hose contained in the back-up
firefighter’s folds or horseshoe is essential, as it is the hose the nozzle firefighter will need
to reach the fire area with their full length intact.
4.7.1 The location of the back-up firefighter’s drop point will depend on the distance of
the fire area from the stairway. If the hallways are long, this may be on the fire
floor. If the hallways are small, or if the fire area is close to the stairway, the back-
up firefighter may need to drop their length on the floor below the fire.
4.8 Similarly, the hose carried by the next firefighter in the stretch should be deployed at the
proper drop point. This will depend on the type of stairway present, as some stairways can
require more hose than others. Generally, the next length of hose should be dropped on a
floor below the fire.
5.1 The presence of a well hole in the stairway makes it possible to execute a well hole stretch
as an alternative to a traditional stairway stretch. This type of stretch will use significantly
less hose, will take less time, and will be less physically demanding, while still protecting
the primary egress of the building.
5.2 In order for the well hole to be used, it must be large enough to accommodate the hose. An
effective test for size is a closed hand 9Figure 11); if you can fit your gloved fist inside a
well hole, it should be large enough to execute a well hole stretch.
Figure 11
70
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
5.3 The presence of a well hole does not require the execution of a well hole stretch. The
decision to use the well hole is made by the engine officer and should be clearly
communicated to the members executing the stretch.
5.4 Before the decision is made to use the well hole, be sure the path of the well itself is clear.
This is accomplished by looking up from the bottom of the well. Obstructions in the well
hole (such as metal bars) can complicate the stretch. Also, be sure the well continues above
the first floor, as variations in layout may impact the well hole. Conversely, be mindful that
variations in layout may create a well hole that begins on the 2nd floor. If desired, the well
hole stretch can begin from that point.
5.5 The engine officer should also determine the point at which the hose will be pulled out of
the well and flaked out for fire attack. This point should be in a safe area as close to the
fire apartment as practical. Most commonly, this will be on the floor below the fire (or half
landing) and stretched to the fire apartment by way of the stairs. In larger buildings, it may
be possible to pull the hose out of the well hole and secure it on the fire floor, if the stairs
are sufficiently remote from the fire apartment to allow for members to flake out the
required lengths and secure the hose.
5.6 Before the hose is secured, the engine officer must confirm that enough hose is available
on the fire floor to reach the fire area.
5.7.1 The nozzle firefighter will carry their entire length intact to the fire apartment,
where it will be flaked out for fire attack. Only the “tail” of the hose that leads from
the nozzle length towards the back-up firefighter should be placed inside the well.
There is no need to carry the folds or horseshoe in the well hole itself.
Figure 12
71
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
5.7.2 This is best accomplished by carrying the length in their outside arm as they walk
up the stairs. This allows the nozzle firefighter to use their inside hand to guide the
“tail” of the hose into the well and avoid obstructions (such as newel posts).
5.7.3 By using this technique, the entire lead length can be carried up to the fire floor
intact, regardless of the size of the well. The “tail” hose of the nozzle firefighter’s
length can easily fit in a narrow well. This ensures an entire lead length of hose is
readily available to cover the fire apartment and eliminates the need for the nozzle
firefighter to hoist an entire length of hose up the well.
5.7.4 Before the nozzle firefighter can begin climbing the stairs, there needs to be a length
of hose available at the bottom of the well. This is the hose that will be hanging in
the well hole. This hose will be provided by the back-up firefighter, who will drop
their length at the base of the well. As the nozzle firefighter begins to climb the
stairs, the back-up firefighter should ensure the smooth advance of hose up the well
hole.
5.7.5 Upon arrival at the fire floor, the nozzle firefighter will set their length aside
(keeping it intact), step on the hose to prevent it from falling down the well, and
pull up any additional hose needed on the fire floor, being mindful that their entire
lead length should be reserved for advance into the fire apartment. If there is enough
room in the hallway, line can be more easily pulled up by simply walking with the
hose away from the well hole.
5.7.6 Once enough hose is on the fire floor, the hose hanging in the well hole needs to be
properly secured using a hose strap. A girth hitch is placed around the hose, and the
hook/carabiner is used to secure it to the stairway railing. Allow the weight of the
hose to hang freely on the hose strap to ensure it is properly secured. Ideally, the
hose strap should be placed just below a hose coupling, but this exact placement is
not necessary.
72
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
5.7.7 Once the hose is secure, the nozzle firefighter should pick up their length, carry it
intact to the fire apartment, flake it out, and prepare to advance, as described in
The Backstep page 35.
5.7.8 As the stretch is being executed, the back-up firefighter should ensure the smooth
deployment of hose up the well hole and make their way up to the fire floor as soon
as practical. Once there, assist the nozzle firefighter in pulling up the necessary
hose, securing the hose strap, and flaking out the hose before preparing to advance
as in The Backstep page 35.
5.8 Well hole technique 2: Nozzle and back-up firefighters both carry their lengths
5.8.1 When conditions allow, a more efficient alternative to the above evolution would
allow both the nozzle and back-up firefighters to carry their lengths up the stairs
(Figure 14). This technique should be considered when the floors are larger and
more hose is required on the fire floor.
Figure 14
5.8.2 To do this, the control (or door) firefighter would supply the length of hose at the
bottom of the well hole and guide the hose up the well. This is the 3rd length in the
stretch and the control (or door) firefighter would stretch it to the base of the well
hole behind the nozzle and back-up firefighters.
73
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
5.8.3 With the 3rd length on the floor at the bottom of the well, both the nozzle and back-
up firefighters will carry their lengths up the stairs (in their outside arms) and the
“tail” of the back-up firefighter’s hose would be placed inside the well, as described
above. The “tail” of the nozzle length will hang between the nozzle and back-up
firefighters on the stairway as they climb. Working together, the nozzle and back-
up firefighters would then carry two entire lengths up to the fire floor, being careful
not to entangle the hose hanging between them.
5.8.4 Upon reaching the fire floor, two lengths will already be present, so it is likely that
no additional lengths will need to be pulled up. The hose can be secured using the
hose strap and the line stretched to the fire apartment as described above.
5.9.1 When there is an obstruction in the well hole, the line will need to be passed around
the obstruction at every turn. Such an obstruction may be a pole or other
construction feature. If there is a hoseline already stretched in the well hole, it will
also be an obstruction. For this reason, a second hoseline stretched in a well hole
should be executed as described below.
Figure 15 Figure 16
5.9.2 Even if it is possible to pass an entire length around an obstruction, it is not easily
accomplished and greatly complicates the stretch. To avoid this, the nozzle
firefighter should drop their length at the base of the well hole and carry only the
nozzle itself up the well, passing it around the hanging hose (or other obstruction)
as necessary.
5.9.3 Upon arrival on the fire floor, all hose required for operation will need to be hoisted
up and properly secured. This is likely at least 2 lengths, as at least one length will
be needed to reach the fire area and another entire length will be needed to cover
the fire area itself.
74
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
6. ROPE STRETCH
6.1 If the stairway is not to be used to stretch the hoseline, an alternative method is to use a
rope to hoist the hoseline into position. This can commonly occur when two lines have
already been stretched on a single stairway, or when a hoseline is stretched to a roof.
6.2 The decision to execute a rope stretch is made by the engine officer and should be clearly
communicated to the members executing the stretch.
6.3 In some cases, the first hoseline may be stretched using a rope stretch. This may be
appropriate when a rope stretch would greatly facilitate line placement due to unique
building characteristics or other similar circumstances. In this case, the engine officer
should be aware that the primary egress to the building will not be fully protected.
Buildings where these alternative stretches may need to be employed should be identified
in CIDS.
6.4 To execute a rope stretch, the engine officer carries the rope to the drop location to which
the hose will be hoisted. This will be a window (or similar opening), balcony, or roof
parapet. The officer must ensure windows are sufficiently opened, which may involve
removing child gates or other obstructions.
6.5 The rope is carried in a bag or a similar container. Commonly, a modified bleach bottle
may be used (this evolution is sometimes called a “bottle stretch”).
6.6 The hoseline will be stretched to a point directly below the drop location and the nozzle
and back-up firefighters will arrange their lengths neatly on the ground (Figure 17). The
back-up should be careful not to place their hose on top of the nozzle firefighter’s hose.
Figure 17
75
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
6.7 If the hose is going to be stretched from outside the building, the nozzle and back-up
firefighters will drop their lengths on the ground outside the building, directly underneath
the drop point.
6.8 A rope stretch may also be executed from inside the building. This can be beneficial in
cases of long and difficult stretches (such as a wrap-around stretch) and would require a
window available on the ground floor, in addition to another window available directly
above this window to serve as the drop point.
6.8.1 If the hose is going to be stretched from inside the building, the nozzle and back-
up firefighters will carry their lengths inside the building and neatly drop them next
to the window to be used on the ground floor.
6.8.2 The rope will be lowered to this window from the drop point above and the nozzle
firefighter will pull the rope into the window on the ground floor and secure their
length of hose (as described below).
6.8.3 The rope will then be lifted out of the window on the ground floor and hoisted up
to the deployment point above. On the ground floor, the hose should pass through
the upper pane of the window, while the hose should pass through the lower pane
on the upper floor.
6.9 The engine officer will send the rope to the members below. This can be accomplished two
different ways:
6.9.1 Toss the rope - The officer can hold the working end of the rope and toss the rope
container itself to the members below. This may be necessary if the rope needs to
be thrown a distance away from the building, but it introduces the possibility of the
rope becoming caught in an obstruction, or not reaching the ground if it does not
play out of the container properly. It also requires the members in the street to make
a more complex knot to secure the hose.
6.9.2 Lower the rope - The officer can lower the working end of the rope to the members
below, keeping the container upstairs with him. This ensures a smooth play-out of
the rope as it is lowered and allows the members below to use a carabiner or clip
on the working end of the rope to secure the hose.
6.10 Once the rope reaches the ground, the nozzle firefighter secures it to the hose. If the
working end of the rope is lowered, this can be done using a carabiner or clip, if present. If
there is no carabiner or clip, a clove hitch or slipknot can be tied to secure the hose. If the
working end is not lowered, the hose will need to be secured in the middle of the rope. To
do this, either a slip-over clove hitch or a slipknot can be used (Figure 18 and Figure 19).
76
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
Figure 18 Figure 19
6.11 When the hose is secured, the rope is hoisted up. The engine officer may start this process,
but either the nozzle or back-up firefighter should make their way to the drop point as soon
as possible to hoist the hose up. Enough hose will need to be hoisted to reach and cover the
fire area.
6.12 When available, a hose roller can be used to help hoist the hose. This will remove the
friction of pulling the hose over the window or roof edge. The hose roller is placed over
the window sill (or roof edge) and serves as a channel through which hose is pulled,
allowing it to roll smoothly over the edge. When the hose roller is used, the attached rope
should be properly secured with a substantial object knot.
6.13 One member should stay at ground level to ensure enough hose is available below the drop
point to allow for a smooth and complete stretch (Figure 20).
77
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
Figure 20
6.14 Once sufficient hose has been hoisted into the window (or onto the roof), the hose must be
properly secured. This should be done directly below a hose coupling. Generally, a hose
strap secured to a substantial object inside the building will effectively secure the hose.
6.15 At higher elevations, the increased weight of the hose may make it necessary to use a
rolling hitch to secure the hose. The rolling hitch is used when the weight of the line
hanging vertically is heavy enough to cause the hose to kink when a hose strap is used. The
width of the rolling hitch (wrapped 4 times around the hose) prevents such kinking. When
used, the rolling hitch must be properly tied directly below a hose coupling and properly
placed in a vertical position outside the window. It is anchored with a substantial object
knot inside the building.
6.16 Once the line is secured, the nozzle and back-up firefighters will stretch and flake out their
hose for fire attack, as described in The Backstep page 35.
78
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
7. WRAP-AROUND STRETCH
7.1 When stretching up a wrap-around stairway, the technique used needs to be modified
somewhat from the traditional stairway stretch. Due to the additional turns in the stairway
and limited visibility, these stretches are more time consuming, demand greater
coordination, and require additional hose.
7.2 These stairways require 4 turns to be made for each floor, which is twice as many as typical
return stairways. In addition to being obstacles themselves, the added turns demand more
hose per floor. Instead of a single length per floor, a more accurate estimate would be 1 ½
lengths per floor for a wrap-around stretch.
7.3 Commonly, wrap-around stairways are located around an elevator shaft. This further
complicates the stretch by hampering communication between members on the line. The
solid walls of the elevator shaft eliminate visibility between members on different floors
and make verbal communication difficult.
7.4 The keys to this stretch are adopting a methodical pace and keeping the lead lengths intact
for deployment on the fire floor. The numerous turns on the staircase will invariably catch
on the hose and stop forward progress. When this happens, stretching members may need
to put down their length (without deploying it) and go back down the stairs to help move
the line forward. This is especially true for the back-up firefighter, but it may be necessary
for the nozzle firefighter as well.
7.5 After the line has been advanced on the floors below, the back-up (and possibly the nozzle)
firefighter should return to their folds, pick them back up, and continue the stretch without
prematurely deploying their lengths.
7.6 To minimize the incidence of the hoseline being caught on the wrap-around turns, both the
nozzle and back-up firefighters should carry their lengths in their outside arms and make
their turns around the elevator shaft as wide as possible. This will allow the stretch to
progress as far as possible before the hose becomes caught up on the turns of the staircase.
7.7 A technique that is effective in maintaining the methodical pace necessary to minimize
hose being caught up is to use visual contact between members to execute the stretch one
turn at a time. This is accomplished as follows:
79
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
7.7.1 The nozzle firefighter climbs the stairs to the first turn, at which point they turn
back to make visual contact with the back-up firefighter (Figure 21).
Figure 21
7.7.2 Once they make visual contact, the nozzle firefighter proceeds to the next turn and
waits there until they can make visual contact with the back-up firefighter again
(Figure 22).
Figure 22
80
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
7.7.3 The back-up firefighter does the same (Figure 23); they await visual contact from
the next member in the stretch below them (this may be the door firefighter, control
firefighter, or the 2nd due nozzle firefighter).
Figure 23
7.7.4 If there is no one there, they may have to go back and lighten up on the line
themselves (if necessary). If another member is in the stretch, the back-up only
moves forward when they have visual contact with them.
7.8 By using this technique, the pace of advancement is driven by the back of the hoseline,
which ensures methodical, but steady progress as hose becomes available and prevents the
nozzle and back-up firefighters from prematurely deploying their lengths.
7.9 Once the fire floor is reached, the nozzle and back-up firefighters will flake out their line
and prepare for fire attack as described in The Backstep page 35.
8.1 When stretching a hoseline up a fire escape, the hose is not stretched up the fire escape in
the same manner as a stairway; rather the line is stretched vertically, brought in over the
side, and secured with a hose strap.
8.2 To execute this stretch, members can use a six-foot hook to pass the hoseline up the exterior
of the fire escape. As an alternative, a rope stretch may be executed, as described in the
previous section.
81
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
8.3 Initially, the hose is stretched to an area near the fire escape drop ladder. Once the hose is
available below the fire escape, one member will climb to the second floor of the fire escape
and wait for the line to be passed to them.
8.4 Using an inverted six-foot hook to hold the shut-off handle of the nozzle (Figure 24), the
line will be passed up to the member on the fire escape. As this is happening, another
member will climb to the 3rd floor of the fire escape. Once there, the hook will be used to
pass the line up to them (Figure 25). This procedure will continue until the floor below the
fire is reached.
Figure 24 Figure 25
8.5 On the floor below the fire, the member receiving the hoseline will pull up sufficient hose
to reach and cover the fire area. The hose will then be secured with a hose strap to the fire
escape railing. This one hose strap will effectively secure the hose; additional hose straps
are not necessary.
8.6 If the hoseline is to be stretched directly to the fire floor by way of the fire escape, the
necessary hose needs to be flaked out on the fire escape balcony on the floor below. This
would occur if the line was to be charged outside the building (on the fire escape) and the
fire attack made via the window.
82
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
8.7 If the hoseline is to be stretched to the fire floor by way of the interior stairs from the floor
below the fire, then the line will be brought in the window on the floor below and stretched
to the fire area via the stairs.
9.1 Using an aerial ladder is an additional option for stretching hose to a roof, upper floor
window, or other elevated position. The hoseline may be stretched to the desired location
via the aerial ladder or the hoseline may be operated from the aerial ladder itself.
9.2 Stretching a handline up an aerial ladder requires that the aerial not move during the stretch
or throughout the operation of the hoseline.
9.3 The engine officer should proceed to the elevated location via the aerial ladder.
9.4 The hoseline is stretched to the area near the turntable of the aerial apparatus and is placed
neatly on the ground. The back-up firefighter should be sure not to place their hose on top
of the nozzle firefighter’s hose. Enough hose to complete the stretch should be brought to
this point.
9.5 The nozzle firefighter will leave their length on the ground and carry the nozzle with them
as they climb the aerial with the hose playing out behind them. The hose is carried under
the left arm (Figure 26) and the nozzle is draped upward across the front of their torso and
back over their right shoulder (Figure 27). This technique will allow the hose to advance
smoothly and prevents the nozzle from being caught in the rungs as the nozzle firefighter
keeps both hands on the rails of the ladder.
Figure 26 Figure 27
83
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
9.6 Once the nozzle firefighter has reached the destination, they should momentarily pass the
nozzle to the engine officer, allowing them to safely dismount the aerial. Once off the aerial
ladder, the nozzle firefighter pulls sufficient hose onto the roof (or into the building).
9.7 As the nozzle firefighter climbs the aerial, the back-up firefighter climbs the ladder behind
them, advancing hose as they climb. The hose should be maintained on the left side of the
aerial ladder.
9.8 Initially, the control firefighter should guide hose onto the aerial from the position on the
ground. When there is a member available to guide hose (possibly the 2nd due nozzle
firefighter), the control firefighter should climb the aerial and advance hose behind the
back-up firefighter.
9.9 Once the nozzle firefighter has dismounted the aerial and begins to pull hose into the
building or onto the roof, the members on the aerial will advance hose from a stationary
position on the ladder, keeping the hose on the left side of the ladder. Before doing this,
members on the aerial must clip the hook of their personal harness to the rungs of the aerial
ladder
9.10 When sufficient hose has been stretched, a hose strap is used to secure the hoseline to a
rung of the aerial ladder at the window or roof level. Once secured, all members on the
aerial will complete the ascent up the ladder and proceed to the point of operation.
9.11 The engine officer will wait until all of the firefighters are off the aerial before calling for
water in the line. The line should be charged gradually.
9.12 When firefighters are going to operate the hoseline from a position on the aerial ladder, all
members must have the hooks of their personal harness clipped to the rungs of the ladder.
A hose strap must be used to secure the line in the vicinity of the nozzle firefighter.
10.1 A portable ladder is an additional option for stretching hose to a roof, upper floor window,
or other elevated position.
10.2 Hose may also be advanced up portable ladders to access difficult-to-reach places to
extinguish fire (such as attic fires or mezzanine areas fires).
10.3 When using a portable ladder, the hoseline may be either stretched dry and charged once
in position, or it may be advanced up the ladder while charged.
10.4 When the line is to be stretched dry up the portable ladder, the technique will be similar to
the aerial ladder evolution. The engine officer should proceed to the location to which the
hoseline will be stretched. This may be by way of the portable ladder, or other route, if
more practical.
84
FDNY Probationary Firefighters Manual
Chapter 12 STRETCHING HOSELINES
10.5 Enough hose to complete the stretch should be stretched to the base of the portable ladder.
The nozzle firefighter will climb the ladder with the hose under the left arm and the nozzle
is draped upward across the front of their torso and back over their right shoulder. This
technique will allow the hose to advance smoothly and prevents the nozzle from being
caught in the rungs as the nozzle firefighter keeps both hands on the rails of the ladder. The
hose is maintained on the left side of the ladder to facilitate a smooth advance.
10.6 Once the nozzle firefighter has reached the destination, they should momentarily pass the
nozzle to the engine officer, allowing them to safely dismount the portable ladder. Once
off the ladder, the nozzle firefighter pulls sufficient hose onto the roof (or into the building).
When sufficient hose is stretched, the hose is secured to a substantial object using a hose
strap.
10.7 The back-up firefighter will feed hoseline to the nozzle firefighter from a position on the
ground at the base of the ladder. Once sufficient hose has been advanced, the back-up will
climb the ladder and assist the nozzle firefighter in flaking out the line.
10.8 When a charged hoseline is advanced up a portable ladder, the nozzle firefighter should
carry the hose in their left hand and the hose should be maintained on the left side of the
ladder.
10.9 When the nozzle firefighter is to operate the hoseline from a position on the portable ladder,
they should clip the hook of their personal harness to a rung of the ladder and the base of
the ladder must be secured.
85
THIS PAGE WAS INTENTIONALLTY LEFT BLANK
86
Probationary Firefighters Manual
CHAPTER 12, ADDENDUM 1
COCKLOFT NOZZLE
Figure 1
1. DESCRIPTION
1.1 The cockloft nozzle is a 6' 3" aluminum pipe with two ½" OSTs. Attached to the body is a
¾ " aluminum handle allowing members control during operation.
1.2 The cockloft nozzle has a 1 ½” female coupling at one end which connects directly to any
controlling nozzle shut-off. After removing the MST from the shut-off, members then
connect the 1 ½" female coupling of the cockloft nozzle to the shut-off.
1.3 The other end has two ½” OST’s. The configuration of these two ½” OST’s eliminates
backpressure. These two OST’s should not be removed when the nozzle is being used to
extinguish fire in a horizontal area like a cockloft. The design of the OST’s enables the
stream to reach in excess of 60 feet. (Figure 1)
87
FDNY Probationary Firefighters Manual
Chapter 12 Add 1 COCKLOFT NOZZLE
Figure 2
2. INTRODUCTION
2.1 The cockloft nozzle (Figure 2) is a versatile tool that has proven extremely effective in
applying water into a narrow, confined area (such as a cockloft). It is primarily designed
for use at cockloft fires but may be used in other situations. It is carried by all Divisions
and Squad companies, as well as select engines that carry a combination nozzle. Any
Engine company can be tasked with placing it into operation.
2.2 When the cockloft nozzle is being used to extinguish fire in a cockloft, the nozzle may be
placed above the ceiling on the top floor of a building or inverted and lowered into the
cockloft area from the roof of the building.
2.3 The cockloft nozzle may also be used to extinguish fire vertically inside of a building (in a
vertical shaft) or vertically on the outside of a building (for an EFIS fire) by placing the
nozzle so that the OST’s are in a vertical position. When used in a vertical application to
extinguish fire above, the ½” OST facing downward may be removed and capped with a
shut-off, if deemed necessary. This is the only time the ½” OST may be removed.
2.4 The design of the cockloft nozzle greatly minimizes the introduction of air into the confined
area of the cockloft, often maintaining the fire in a ventilation limited state.
3.1 To place the cockloft nozzle into operation, a hoseline is needed at the point of operation.
This may be an existing handline already in place that is converted to a cockloft nozzle
operation, or an additional handline that is stretched and dedicated to operate the nozzle.
3.2 Members should be mindful that only two hoselines may be stretched up an interior
stairway, so an alternative means of stretching may be necessary.
3.3 An 1 ¾” or 2 ½” hoseline can be utilized to supply the cockloft nozzle. It should be supplied
with a nozzle pressure of 50 psi and is capable of delivering 100 GPM.
88
FDNY Probationary Firefighters Manual
Chapter 12 Add 1 COCKLOFT NOZZLE
3.4 The cockloft nozzle should be inserted into the cockloft between the joists (Figure 3 and
Figure 4). Operating members shall alternate the direction of the stream by rotating the
nozzle 90 degrees and returning the nozzle to its original position to provide maximum
coverage. Do not rotate the cockloft nozzle in a continuous counter-clockwise direction;
this action may cause the nozzle to become unscrewed from the shut-off.
Figure 3 Figure 4
3.5 The cockloft nozzle may be placed into operation for fires in the cockloft areas of
taxpayers, row frames, and NFP multiple dwellings like H-types. When deemed necessary,
a separate, conventional protection line should be stretched, charged, and in the area of
operation before the cockloft nozzle is used on a separate handline.
3.6 This is especially important when members are operating the cockloft nozzle in an area
where ceilings may blow down or fire extension may trap members. These events have
greater potential at top floor operations in H-type or similar buildings, even when members
are operating in another wing.
3.7 There are times when the cockloft nozzle may be needed in an exposure, like a Row Frame
building, as a precaution or to prevent extension, and the conditions are such that a
protection line is not initially necessary during its operation.
3.8 Only the IC (or Sector Chief), should determine when to place the cockloft nozzle into
operation, and when to shut it down. The IC and / or Sector Supervisors must use judgment
based on existing conditions to determine when it is safe to operate without a protection
line, bearing in mind that conditions may change.
3.9 The operation of the cockloft nozzle should be supervised by a Chief Officer.
89
FDNY Probationary Firefighters Manual
Chapter 12 Add 1 COCKLOFT NOZZLE
3.10 The cockloft nozzle is generally placed into operation on the top floor of a building for use
in the cockloft area above the ceiling. It may also be lowered into the cockloft from the
roof of the building, when the roof is deemed safe to operate on. The Incident Commander
and / or Sector Supervisors must determine which is the best location (top floor or the roof)
to operate from.
3.11 Operating from the roof is a particularly useful tactic when there are high ceilings or
difficult ceilings to pull, which often occurs at taxpayer fires. Operating from the roof may
sometimes provide the opportunity for a quicker stretch and safer operation at residential
building fires, depending on the existing conditions.
3.12 Ideally, when operating from the roof, members should begin nozzle operation from an
inspection hole where fire is not venting and move toward the area of origin as conditions
permit.
3.13 If members are operating without a separate, additional protection line, they should operate
as follows
3.13.1 A hoseline with a conventional nozzle should be stretched and charged in case it is
needed while members are opening up the ceiling area where the cockloft nozzle
will operate.
3.13.2 In non-fireproof multiple dwellings, the area immediately inside the apartment door
offers an extra degree of protection provided by the public hallway. This option
should be employed when fire conditions dictate.
3.13.3 Members should then open up an area in the ceiling into which the cockloft nozzle
will be placed for operation. The hole should initially be limited in size, but large
enough for the cockloft nozzle to fit into. Additional holes may need to be made to
use the nozzle at different locations.
3.13.4 If fire shows while opening up the ceiling, the fire should be knocked down by the
hose line with the conventional nozzle. The MST should then be removed from the
hose line and the female coupling of the cockloft nozzle connected directly to the
shut-off of the charged line.
3.13.5 The cockloft nozzle should then be placed into the opening, the shut-off handle
opened, and the nozzle operated to extinguish fire in the cockloft.
3.13.6 The nozzle should be maintained upright and alternately rotated 90 degrees and
then back to its original position, allowing water to be distributed in all directions
in the cockloft.
3.14 The use of the cockloft nozzle does NOT eliminate the need of pulling ceilings for final
extinguishment and washdown.
90
FDNY Probationary Firefighters Manual
Chapter 12 Add 1 COCKLOFT NOZZLE
3.15 Firewalls, division walls, nogging and other impediments may require the repositioning of
the cockloft nozzle into several different areas to obtain final extinguishment.
91
THIS PAGE WAS INTENTINALLY LEFT BLANK
92
Probationary Firefighters Manual
STANDPIPE OPERATIONS
1. OVERVIEW OF STANDPIPE SYSTEMS
1.1 In New York City, standpipes can be found in a wide range of buildings containing various
occupancies. Standpipe systems can be found in the following locations:
1.2 All required standpipes in NYC are compatible with FDNY equipment and can be used to
provide FDNY hoselines with adequate water supply. Fire companies will use standard
FDNY hose and other equipment when using any standpipe system.
1.3 Existing 1 ½” diameter occupant-use hose should not be used, except in rare cases where
life is in immediate peril and a FDNY hoseline is unavailable. This situation would most
likely occur when a ladder company or rescue company is operating without an engine
company.
2.1 A more complete discussion of the types of standpipe systems that exist in NYC and their
various features and components can be found in Chapter 3: Engine Company Equipment.
This section will focus on several key practical characteristics of standpipe systems.
2.2 The primary practical concern for a standpipe system is the presence of water.
2.2.1 A wet system is maintained with water in the system at all times. A dry system is
maintained without any water under normal circumstances. Both wet and dry
systems are supplied and used by the same procedure.
93
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
2.3.1 While many standpipe systems are equipped with a fire pump, it is common to find
a building with a standpipe system, but no fire pump.
2.3.2 Fire pumps are designed to supply the standpipe system with sufficient pressure to
operate as needed. Some fire pumps are manually operated, some operate
automatically. Units must be aware of the buildings in their response area and what
types of fire pump systems exist. Firefighting Procedures High Rise Office
Buildings provides detailed information regarding fire pump operations.
2.4 The location of floor outlets within the system impacts firefighting operations.
2.4.1 Regardless of the type of standpipe system encountered, floor outlets can be found
in a variety of locations within the area protected and there are important
operational considerations unique to each location that could provide advantages or
disadvantages in the execution of the stretch.
2.4.2 Floor outlets inside a stairway (Figure 1) provide direct access to that stairway, but
can create a more complex stretch in the event a different stairway is selected for
the fire attack.
2.4.3 Floor outlets in a public hallway (Figure 2) can provide more space in the proximity
of the outlet to hook up and arrange the lengths of hose, though the floor outlet will
not provide direct access to a stairway. However, floor outlets in the hallway can
provide easier access to alternative stairways, which would simplify the stretch if a
different stairway was used for attack.
Figure1 Figure 2
2.4.4 Standpipe outlets in open areas can present a challenging situation, especially when
located in non-residential occupancies, such as subway stations and parking
garages. In these cases, the outlet may be located remote from the attack stairs.
94
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
3.1 Standpipe systems are supplied with 3 ½" hose. The only exception to this is when 3” high
pressure hose is used to supply a standpipe system as part of the High-Pressure Pumping
evolution.
3.2 Standpipe systems may be supplied through Fire Department Connections (FDC) and/or
floor outlets. While the FDC is the primary consideration, the standpipe system can be
supplied by way of a floor outlet as an alternative. This should be considered in the
following situations:
3.2.2 FDC is located remote from the hydrant to be used to supply the system and the
floor outlets are more readily accessed from the apparatus
3.2.3 It is necessary to augment the system and there is no available FDC (all FDC are
already being supplied)
3.3 When a building is equipped with both a standpipe system and automatic sprinklers, the
first supply line should supply the standpipe system. If the first arriving engine is supplying
both the standpipe and sprinkler systems, later arriving engine companies should stretch
additional lines to augment both systems.
3.4 When the building being supplied is part of an interconnected building system, one
building will have a gravity tank on the roof which supplies water to that building and the
other interconnected buildings. These interconnected buildings have a Post Indicator Valve
which is normally open to allow water supply into that building. The ECC should be aware
of the possibility of a Post Indicator Valve (PIV) being closed to one of the other
interconnected buildings. If the PIV is found closed, the ECC should notify the Engine
Officer. A closed PIV in one of the interconnected building means that this structure is now
isolated from the water supply coming from the building with the gravity tank. The
standpipe in that interconnected building will have no access to a water source until the
ECC supplies the building system. Until supplied by the ECC, the only water available will
be the residual water in the standpipe riser itself. This water can quickly run out, which
could place operating units in danger if the Engine Officer is unaware of the PIV closure.
3.5 Due to the possibility of a Post Indicator Valve (PIV) being closed, it is preferred that
ECC’s supply the FDC on the fire building when it will not result in any delay of water
supply to the standpipe system.
3.6 When the building is equipped with an air pressurized standpipe, the pressurized air must
be bled from the system before the system can be supplied with water. These systems are
maintained dry and are used in buildings that are being demolished and in buildings
under construction upon reaching a height of 75 feet. See Addendum 3, page 125 for a
complete description on the operations at buildings with Air-Pressurized Standpipe
Systems.
95
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
3.7.1 To supply the standpipe system via the FDC, the male end of a 3 ½” hoseline should
be stretched to the FDC and connected. Depending on the orientation of the 3 ½”
hose on the apparatus, a double male fitting may be needed.
3.7.2 FDC are color coded for ease of identification (Figure 3). Either the caps or the
entire FDC may be painted. The color of the connections are as follows:
A. Red = standpipe system
B. Yellow = combination system (sprinkler/standpipe)
C. Green = automatic sprinkler system
D. Aluminum = non-automatic sprinkler system or perforated pipe
Figure 3
3.7.3 When any part of the system is out of service (OOS), the FDC will have a colored
disc attached to indicate the serviceability of the system. The color coding is as
follows:
A. White disc = system fully OOS
B. Blue disc = system partially OOS
3.7.4 Whenever possible, a second apparatus should hook up to an available FDC and be
prepared to augment water supply, if needed.
96
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
3.8.1 If a standpipe system is to be supplied via a floor outlet, proper fittings must be
employed to attach the 3 ½" supply hose to the 2 ½" outlet threads.
3.8.3 When supplying water to a floor outlet, it is important to keep the outlet valve
closed until water is supplied to the outlet via the supply hose. If the outlet is opened
prematurely, the water supply on the fire floor may be severely impacted.
3.8.4 To facilitate this operation, the company commander may consider carrying a
designated “ECC standpipe kit” on the apparatus. Such a kit should include:
A. Necessary fittings (i.e. double female, 3 ½” to 2 ½” reducer)
B. Pipe wrench
C. Spanners
D. Chocks
E. Adapter
97
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
4.1 It is the responsibility of the Engine Officer to select the floor outlet to be used. This
decision should be based on the consideration of a number of criteria, including:
4.2 The selected floor outlet should be located on a floor below the fire. This will ensure the
outlet is in a protected, smoke free-area. Primary consideration should be given to using an
outlet on the floor immediately below the fire. This will minimize the length of the stretch
and facilitate verbal communication between the fire floor and the floor outlet.
4.3 The selected floor outlet can be located on any floor below the fire. Generally, the outlet
on the floor below the fire will be used, but it may be necessary to use a more distant floor
due to an unserviceable outlet on the floor below the fire in a building with a single
standpipe riser. A more distant outlet may also be used if it will facilitate an easier stretch
due to unique building characteristics (e.g. unusual stairway layout, duplex apartments,
etc.)
98
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
4.4 In rare cases, using the floor outlet on the same floor as the fire may be permissible due to
unusual building characteristics. This would require approval from the Division
Commander. A CIDS entry is mandated in these situations. An example of this is where
the stretch of the handline from the floor outlet to the fire apartment entrance is via an
exterior, open air balcony, and stretching from the fire floor allows the fire apartment to be
reached with 3 lengths of hose.
4.5 Selecting a floor outlet on the same level of the fire may also be necessary in non-residential
structures with standpipe systems, such as parking garages, subway stations, or large
industrial occupancies. This would require approval from the Division Commander. A
CIDS entry is mandated in these situations.
4.6 Once selected, the engine officer should clearly communicate the floor outlet to be used to
the members of their company. This can be visually communicated, or may be
communicated verbally, either by handie-talkie transmission or face-to-face.
4.7 If the control firefighter finds a problem with the selected floor outlet and needs to move
to a different outlet, the engine officer should be immediately informed. The engine officer
should also ensure the 2nd due engine is aware of the new outlet, so they can assist with the
stretch. If scissor stairs are used, it may be easier to move to an outlet two floors away, as
this would likely be shorter than having to stretch from the opposite staircase if the
immediate floor below is used.
4.8 If a floor outlet has a Pressure Reducing Device (PRD) attached, it should be removed, if
possible. If it cannot be removed, the outlet can still be used to supply the hoseline, so long
as sufficient pressure can be achieved. The Engine Officer should be notified that the outlet
being used has a PRD attached.
4.9 If a floor outlet has a Pressure Reducing Valve (PRV) attached, it will not be removable.
As long as sufficient pressure can be achieved, the outlet can still be used to supply the
hoseline. The purpose of a PRV is to supply the appropriate pressure to the floor on which
it is located under the operation of the building fire pump, so sufficient pressure at the
outlet can be expected. The Engine Officer should be notified that the outlet being used has
a PRV attached.
99
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
5.1 The 1st due control firefighter is responsible for supplying water to the first hoseline from
the selected floor outlet. They shall remain at the floor outlet throughout the operation and
communicate with the Engine Officer to ensure that adequate pressure is supplied to the
nozzle.
5.2 Upon arriving at the selected outlet, the control firefighter should open the outlet and flush
it thoroughly. This is to confirm a water supply is available and to clear the outlet of any
possible obstructions to water flow. After confirming the availability of water, the control
firefighter should connect the in-line pressure gauge and the hoseline to be supplied. The
in-line pressure gauge is used to ensure the correct pressure is supplied to the hoseline.
5.3 For the most common standpipe hose stretches, the control firefighter should supply
hoselines supplied from an outlet on the floor below the fire as follows:
5.4 These standard pressures are calculated based on the guidelines of “street hydraulics” and
are explained as follows:
5.4.1 A residential 3 length stretch from the floor below the fire has 2 lengths of 2 ½”
lightweight hose (5 psi each = 10 psi total), 1 length of 2” lightweight hose (10 psi),
1 floor of elevation (5 psi) and 55 psi at the 1” tip of the nozzle. This adds up to the
target outlet pressure of 80 psi and provides 220 GPM.
5.4.2 The 1” tip of the nozzle is supplied with 55 psi, which is above the minimum
recommended nozzle pressure of 50 psi. This additional pressure is added to
minimize the likelihood of kinking in the hose.
5.4.3 A commercial 3 length stretch from the floor below the fire has 3 lengths of
lightweight 2 ½” hose (5 psi each = 15 psi total), 1 floor of elevation (5 psi) and 50
psi at the 1 1/8” tip of the nozzle. This adds up to the target outlet pressure of 70
psi and provides 265 GPM.
5.4.4 Since the 2 ½” lead length will be stretched primarily for commercial occupancies,
which may involve a large, open floor space with a potential for a heavy fire load,
the 2 ½” nozzle should be supplied with 50 psi at the tip. This is to enable the full
reach of the stream to be used and to achieve the maximum available flow from the
standpipe system.
100
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
5.4.5 If additional lengths of hose are required for a standpipe stretch, the control
firefighter should supply an additional 5 psi for every length of 2 ½” hose added.
5.4.6 If the hoseline will be stretched from further than 1 floor away, the control
firefighter should supply an additional 5 psi for every additional floor of elevation
needed.
5.5 Pressures at the outlet should be set while water is flowing at the nozzle. When the nozzle
is shut, the gauge will read the static pressure (the pressure when water is not flowing) in
the hoseline, which will be higher than the actual operating pressure. In order to properly
set the operating pressure, the nozzle firefighter must use a “long bleed” and bleed the line
for long enough to allow the control firefighter to adjust the pressure accordingly. The long
bleed is essential to ensure the proper pressure is set.
5.6 Operating pressure is adjusted by use of the operating wheel at the floor outlet and by
observing the in-line pressure gauge. If there is no valve wheel attached to the standpipe
outlet, a substitute tool can be used. Such options include a pipe wrench, vise grips, or a
removable operating wheel carried in the standpipe kit.
5.7 The Control firefighter should be aware that a properly supplied hoseline may exceed the
Hi-Flow alarm of the digital pressure gauge (which alarms when flow exceeds 250 GPM).
This activation does not necessary indicate a problem with water supply. If doubt exists as
to the accuracy of the supply pressure reading, the Control Firefighter can communicate
directly with the Engine Officer to confirm that sufficient pressure is supplied to the
hoseline.
101
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
6. STANDPIPE KIT
6.1 The control firefighter carries the standpipe kit. This ensures the control firefighter is in
possession of all the equipment necessary to secure a water source at the standpipe outlet.
6.2 The standpipe kit is required to include the following equipment (Figure 4):
6.2.4 Chocks
6.2.6 1 ½” to 2 ½” increaser
6.2.7 Adapters (National Standard thread and/or National Pipe thread to FDNY thread)
Figure 4
6.3 The following equipment may be included in the standpipe kit as deemed beneficial by the
Company Commander, but are not required, as some are not provided by the FDNY:
102
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
6.3.4 Wire brush (to be used to remove paint or debris from outlet threads)
6.3.5 Fog tip (to be used to vent the fire area during overhaul)
7.1 The presence of a standpipe system does not mandate engine companies to use the
standpipe to supply their hoselines. The Engine Officer may elect to stretch their hoseline
from the apparatus as an alternative to using the standpipe system. When making this
decision, the Engine Officer should consider a number of factors, including:
7.2 The 1st due Engine Officer must ensure the 2nd arriving engine company is aware of their
decision to stretch from the apparatus, as they will need to assist the 1st arriving company
with the stretch and will not require their standpipe equipment.
7.3 Additional hoselines may be similarly stretched from the apparatus, as determined by the
Engine Officer of the unit stretching the hoseline and are not required to be stretched in the
same fashion as the first line. For example, if the first line uses the standpipe, the second
line may be stretched from the apparatus, as determined by the Engine Officer of the
company stretching the line.
103
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
7.4.1 All hoselines should be stretched from the attack stairway and all access to the fire
floor should be made by way of the attack stairway. This is in an attempt to keep
all other stairways free of smoke. All stairways, other than the attack stairway, can
be considered evacuation stairways.
7.4.2 The attack stairway does not need to be the stairway closest to the floor outlet. The
stairway selected should allow for the most efficient stretch possible, with the goal
of minimizing the length of the stretch, while allowing for an efficient advance on
the fire floor. The selection should be made by the Engine Officer, in consideration
of the following criteria:
A. Proximity of the stairway to the fire area on the fire floor
B. Proximity of the stairway to the floor outlet on the floor from which the hoseline
is being supplied
C. Type of stairway used
D. Conditions on the fire floor
7.4.3 The Engine Officer is responsible for selecting the attack stairway. Once selected,
the IC must be informed of the identity of the attack stairway and operations should
be coordinated with the ladder companies operating on the fire floor.
7.4.4 The Engine Officer should be sure of the location of the fire before committing to
an attack stairway. This is especially important in situations involving a large area
and multiple stairway options, such as in commercial high-rise buildings or open
areas, such as parking garages. In these situations, a stretch of at least 4 lengths
should be anticipated, which may require hose from the 2nd due engine company.
7.4.5 The type of stairway used should be a key consideration when selecting the attack
stairway. Certain characteristics of various stairway types may allow for a more
efficient stretch, as follows:
A. If available, an enclosed stairway should be used. Open stairways are more
readily contaminated and should be avoided, if possible. However, if the
building only has one enclosed stairway, the priority will be for the enclosed
stairs to be used as an evacuation stairway and an open stairway would need to
be used for the attack.
B. Return-type stairs offer several advantages as an attack stairway. The stairway
door will be at the same location on each floor, which makes it possible to
visualize the path of line advancement on the fire floor by using the layout of
the floor below the fire. Also, return-type stairs often have half-landings, which
can provide an ideal location to flake out the hoseline. This can be helpful when
the public hallway is contaminated and the hoseline needs to be charged inside
the stairway.
104
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
C. Scissor stairs are effective as an attack stairway, but may introduce an element
of complication, as their orientation will vary from floor to floor. It is important
to remain aware that the orientation of the attack stairway door on the fire floor
will be on the “opposite side” of the scissor stairs on the floor below the fire.
D. When using scissor stairs, consider using the stairway that provides the best
access to the fire area on the fire floor, even if it is further from the standpipe
outlet on the floor below the fire. This would require stretching from the floor
outlet to the selected attack stairway on the floor below the fire.
E. If the floor outlet is located inside a scissor stairway, stretching to the opposite
stairway on the floor below the fire will involve additional turns and potential
pinch points, as the line will have to be stretched out of the stairway, down the
hall, and back into the opposite stairway. As a result, the hoseline will go
through at least three stairway doors when using the opposite stairway, instead
of just one.
F. In this situation, another method to stretch the line via the opposite stairway is
to hook up to the floor outlet 2 floors below the fire. By doing this, the outlet
will be located inside the desired attack stairway and the hose need not be
stretched around on the floor below. Instead, the hose will remain inside the
stairway and be stretched straight up two floors. While the outlet is a floor
further away, the total amount of hose used may actually be less and the
additional turns and pinch points will be eliminated.
Figure 5
105
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
7.5.1 In a standpipe stretch, the engine officer needs to estimate the length from the
standpipe outlet to the fire area in order to determine if a standard 3-length stretch
will be long enough to reach the fire area.
7.5.2 When estimating the length of the stretch, the officer must remember that the nozzle
firefighter’s length is designated to be used inside the fire apartment itself and
should not be included in the estimation. Consequently, the distance between the
standpipe outlet and the fire area must be covered using only two lengths. This
means that if the fire area is more than 100 feet away from the standpipe outlet, a
4th length will need to be added to the stretch.
7.5.3 The officer must be sure to estimate using the actual path the hoseline will travel.
This includes ensuring the right attack stair is considered. Also, the officer must be
sure to consider the vertical distance travelled, especially if a floor outlet is used on
a more distant floor.
7.5.4 If the officer finds that a 4th length will be needed, they must notify the control
firefighter and second engine that an extra length of hose will be needed for the
stretch.
7.6.1 The 1st due engine and the 2nd due engine will work together to stretch the first
hoseline from the selected standpipe outlet to the fire area by way of the designated
attack stairway.
7.6.2 When using the standpipe system in a commercial occupancy, all hoselines
stretched from the outlet will be 2 ½”. In a residential occupancy, hoselines
stretched from the outlet may have a lead length of 2” hose. 1 ¾” hose must not be
stretched from a standpipe outlet. The larger diameter hose is required for the
purpose of minimizing friction loss in the hose and maximizing water flow from
the standpipe system.
7.6.3 In residential occupancies, the lead length will typically be 2” hose. However, a
lead length of 2 ½” hose should be considered instead in situations in which
adequate pressure may not be immediately available from the standpipe outlet.
Such situations may include an outlet with a PRV or a building in which the ECC
will be delayed in supplying the FDC due to difficulties accessing the FDC or
securing a hydrant. In these situations, the larger diameter of the 2 ½” hose will
allow for better performance at lower supply pressures.
106
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
7.6.4 Each firefighter will bring one length of lightweight hose, folded into a roll-up. The
nozzle firefighter will have a nozzle attached to their length. The roll-up is oriented
such that the midpoint of the length is located directly beneath the hose couplings.
This will ensure the hose is easily deployed. The midpoint is indicated with a red
marking.
7.6.5 For most residential occupancies, lightweight hose will be used as follows:
A. The nozzle firefighter will bring one length of 2” lightweight hose with a nozzle
that has a 1” tip attached. This hose has a friction loss of 10 psi per length. The
midpoint of this length is indicated with red paint. This point is called the A-
fold.
B. This nozzle should be supplied with 55 psi nozzle pressure, which will provide
a flowrate of 220 GPM and a nozzle reaction of 85 lbs.
C. The Back-up and Control firefighters will each bring one length of 2 ½”
lightweight hose, each of which will have a friction loss of 5 psi per length.
7.6.6 For commercial occupancies (and some residential occupancies), lightweight hose
will be used as follows:
A. The nozzle firefighter will bring one length of 2 ½” lightweight hose with a
nozzle that has a 1 1/8” tip attached. The midpoint of this length is indicated
with red paint.
B. This nozzle should be supplied with 50 psi nozzle pressure, which will provide
a flowrate of 265 GPM and a nozzle reaction of 98 lbs.
C. The Back-up and Control firefighters will each bring one length of 2 ½”
lightweight hose. All 2 ½” hose has a friction loss of 5 psi per length
7.6.7 If the door to the fire area can be controlled, the 1st hoseline should be stretched to
the door to the fire area, flaked out, and charged at that location. If the door to the
fire area cannot be controlled and the public hall has become part of the fire area,
the hoseline should be stretched to the stairway door, flaked out, and charged inside
the stairway and public hallway on the floor below.
7.6.8 Flaking out and charging hose in the stairwell below the floor outlet would require
the weight of the charged hose to be pulled back up the stairs in a stairwell.
Additionally, the turns in the staircase create a greater opportunity for a kink to
occur. In these situations, these stairway areas may also become very congested.
7.6.9 When charging a hoseline in the stairwell at the stairway door, the public hallway
on the floor below the fire near the floor outlet provides an area where the hose may
be more easily flaked out, and more easily advanced under these conditions.
107
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
7.6.10 All three roll-ups should be connected to each other (Figure 6) in close proximity
to the standpipe outlet (in the stairway, or public hallway) and the control
firefighter’s length should be connected to the outlet. This will provide visual
confirmation that the line is intact and connected to the outlet. The roll-ups should
be arranged with the nozzle length closest to the direction of the stretch.
Figure 6
7.6.11 The nozzle firefighter should keep their length intact in a roll-up as they carry it to
the point of operation. This will ensure the entire lead length of hose is available to
be used inside fire apartment and will aid in flaking out the hose.
7.6.12 To facilitate the efficient stretching and flaking out of the hoseline, consider
“splitting” the backup firefighter’s roll-up, as follows:
A. The backup firefighter’s roll-up can be split into a “male” section and “female”
section. The nozzle firefighter can then carry the male section of the backup
roll-up in addition to their own roll-up (Figure 7). The nozzle firefighter would
then be carrying roughly 75 feet of hose.
108
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
Figure 7
B. As the nozzle firefighter approaches the fire area, they can drop the portion of
the roll-up at an appropriate drop point (Figure 8 and Figure 9), while keeping
the lead length intact in a roll-up, to be used in the fire area itself.
Figure 8 Figure 9
109
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
C. The female section of the backup roll-up can be carried and flaked out by the
backup firefighter, who is responsible for ensuring both the backup and control
roll-ups are properly stretched and flaked out. The female section of the backup
hose back can be similarly carried as necessary.
D. If practical, the control roll-up can be similarly separated (Figure 10). The
female section of the roll-up would connect to the outlet, while the male end
could be carried by the backup firefighter to a drop point and flaked out.
Figure 10
E. This technique allows the nozzle and backup firefighter to both carry sections
of hose without being too close to each other, as their roll-ups will be coupled
together and it would be impossible to carry both roll-ups intact while coupled.
7.6.13 The nozzle firefighter should carry their entire roll-up to the point of operation and
flake out the line from that point. It is preferred that seat-belt buckles be removed
from the roll-ups before leaving the protection of the stairway.
A. The first fold of hose beneath the couplings is the midpoint of the length and
can be used to flake out the line. This midpoint will be indicated with red paint.
(Figure 11 and Figure 12) To flake out, grab the midpoint fold and walk or toss
it away from the point of operation. This creates a large “U”, leaving the nozzle
and first hose coupling at the point of operation.
110
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
Figure 11 Figure 12
B. Depending on the length and complexity of the stretch, the back-up firefighter
may be quickly available to help the nozzle firefighter flake their hose out
(Figure 13 and Figure 14). In this case, the back-up firefighter can grab the
midpoint of the nozzle length and flake it out by walking it away from the point
of operation, allowing the nozzle firefighter to prepare for the attack.
Figure 13 Figure 14
111
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
C. This “U” shaped configuration makes for a smooth advance into the fire area
(Figure 15), as the nozzle team will only be pulling the weight of the first length
as it pivots at the first coupling, instead of the weight of the entire charged
hoseline.
Figure 15
7.6.14 If the hallway is part of the fire area, the line will need to be charged at the stairway
door and the hose flaked out inside the stairway and the hallway on the floor below.
A. Standing inside the midpoint fold and walking it up the stairs (Figure 16) can
effectively flake out the line. If possible, flake the line out up the stairs, so line
advancement will be aided by gravity once the line is charged. The presence of
a half-landing will be helpful and the line should be flaked out on the half-
landing platform.
112
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
Figure 16
Figure 17 Figure 18
113
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
C. When the line is charged at the stairway door, the nozzle side of the hoseline
should be oriented on the outside wall of the stairway on the fire floor (Figure
18). This will reduce kinking and ease the advance of the charged hoseline.
Figure 19
D. If more room is needed to flake out hose inside the stairway (Figure 19), it is
preferred to use the hallway on the floor below rather than flaking hose down
the stairs below the floor outlet.
7.6.15 As the nozzle firefighter is carrying their roll-up to the fire floor, the backup
firefighter will flake out the 2nd and 3rd lengths of hose, allowing the nozzle
firefighter to bring their entire length to the point of operation. When compatible
with the building layout, the backup firefighter may carry a portion of their hose to
a drop point closer to the fire area and flake their line out in a similar fashion to the
nozzle firefighter. All doors should be chocked.
7.6.16 Once the hoseline is in position, the Engine Officer will communicate with the
control firefighter to charge the line. The control firefighter will supply water and
maintain adequate pressure in the line from the floor outlet.
114
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
7.6.17 As the line is being charged, the nozzle firefighter must “bleed the line” until the
operating pressure is set.
A. This allows air in the hoseline to escape and allows the control firefighter to set
the proper operating pressure.
B. Allow the water entering the hoseline to reach the nozzle. The nozzle must be
opened fully and carefully to ensure an accurate reading at the floor outlet while
maintaining control of the line.
C. A “long bleed” may be necessary to allow the Control firefighter to set the
proper operating pressure with water flowing. Keep the nozzle open until the
Control firefighter has set the correct pressure.
D. If possible, avoid bleeding the line in the direction of the elevators and attempt
to use the stairway or compactor chute. This will help prevent flooding in the
elevator shafts in an attempt to keep all elevator cars in operation for firefighter
use.
7.6.18 As the line is being charged, the backup firefighter should consider taking a
temporary position at the stairway door on the fire floor. From this position, they
can make sure the line does not become trapped beneath the stairway door as it is
charged. As soon as the line is charged, the backup firefighter makes their way to
the nozzle, removing any kinks or obstructions they encounter in the hoseline. By
the time the nozzle firefighter finishes “bleeding” the nozzle, the backup firefighter
should be in position behind them and ready to advance.
7.6.19 The Engine Officer must ensure sufficient pressure is available in the hoseline
before committing to the fire area. Once the hoseline is properly charged and in
position, the fire attack can begin.
7.6.20 The 2nd engine company will assist with stretching and operating the first hoseline.
The 2nd Engine Officer should consider the type and length of stretch when
deploying members to properly assist the first engine company.
A. Since the 1st engine’s Control firefighter will remain positioned at the standpipe
outlet, members of the 2nd engine will need to be properly positioned to assist
the 1st engine’s nozzle team with their advance into the fire area.
B. The second engine officer must exercise proper judgment when deploying
members to assist. The factors that must be considered include the status of
water supply, the length of the stretch from the fire floor stairway door to the
fire occupancy door, size of the fire occupancy, are there any turns in the
hallway between the fire floor stairway door and the fire occupancy door, and
is the first engine a four or five firefighter unit.
C. The second control firefighter should be positioned at the stairway door on the
fire floor to ensure the hoseline does not become kinked or otherwise impeded.
This also keeps them in the vicinity of the first control firefighter should water
supply issues occur.
115
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
D. The second engine officer should then deploy other members in the public
hallway as necessary to assist with line advance.
E. When there is a turn in the hallway, such as in a T-shaped hallway, another
member should be positioned at that turn to ensure the hoseline does not become
kinked or otherwise impeded.
F. The second engine officer should ensure the position at the fire occupancy door
is covered to insure a proper advance into the fire area.
G. If the stretch from the fire floor stairway door to the fire occupancy door is long,
members may need to be spaced along that path to ensure the line is properly
advanced. This may also require the assistance of a third engine company.
H. If the 1st hoseline is charged inside the attack stairway, members of the 2nd
engine will be needed to assist with the more arduous task of advancing the
charged hoseline up the stairs and then down the hallway to the fire area.
7.7.1 Floor outlet selection can be a challenge when multiple lines are stretched at an
operation. Depending on the number of standpipe risers in the building, it may be
necessary to stretch additional lines from several floors below the fire. This will
result in longer stretches, requiring the assistance of additional engine companies
and their hose.
7.7.2 If the first line is stretched from an outlet on the floor below the fire, the second
line may have to be stretched from 2 floors below the fire when using the same
standpipe riser. If this second line is being stretched as a back-up line on the fire
floor, this stretch will be at least 4 lengths long. If the second line is being stretched
to the floor above the fire, the stretch will be even longer.
7.7.3 In the extreme case of a third line being stretched to the floor above the fire, and if
the floor outlet is located in an enclosed stairway, consideration may be given to
hooking up the 3rd line to the outlet on the original fire floor. This outlet will be
protected by charged hoselines and the door to the stairway will be controlled,
providing the control firefighter of the 3rd line with a protected environment to hook
up to the standpipe. Approval by the IC or Fire Sector Supervisor is needed to hook
up to an additional line to an outlet on the original fire floor.
7.7.4 The proper operating pressure for additional hoselines should be calculated using
“street hydraulics”. The Engine Officer should communicate with the Control
firefighter to ensure the hoseline is supplied with sufficient pressure.
116
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
8.1 While the line is operating, the control firefighter must remain at the standpipe outlet to
ensure proper pressure is maintained in the line throughout the operation. It is important to
recognize the difference between the higher static pressure that will exist when the nozzle
is closed and the pressure reading when the nozzle is flowing water, which is the true
pressure reading in the hoseline.
8.2 If there is inadequate pressure in the line, the Engine officer should communicate with the
control firefighter to rectify the problem.
8.3 After the proper operating pressure has been established, if the pressure reading at the outlet
is adequate, or even too high, and there is inadequate pressure at the nozzle, this is an
indication of kinking in the line. Kinks should be removed manually, not by supplying
more pressure.
8.4 After the fire is extinguished, ventilation of the fire area can be difficult. To facilitate
ventilation, consideration can be given to using a fog tip on the hoseline. A small,
removable tip may be carried in the standpipe kit and can replace the existing tip. The fog
tip can be used to move smoke and heat out an open window in the fire area. This can also
be accomplished by removing the MST from the nozzle and partially opening the shut-off
handle. This should only be considered in the overhaul phase of the operation, well after
the fire has been fully extinguished.
9.1 The 5th due engine on a 10-77 assignment is responsible to bring the High-Rise Nozzle
(HRN) to the Incident Command Post (ICP) and when ordered, put the High-Rise Nozzle
into operation. If they are not equipped with a HRN, they will obtain it from another unit
on scene. If necessary, they should contact the dispatcher to determine which responding
unit(s) are equipped with a HRN. See Addendum 2, p.119 for a complete description on
the use of the High Rise Nozzle.
Figure 20
117
FDNY Probationary Firefighters Manual
Chapter 12 STANDPIPE OPERATIONS
10.1 The NFPA provides national standards regarding the installation and maintenance of
standpipe systems. NFPA 14 outlines standards for the installation of standpipe systems
and NFPA 25 outlines standards for the maintenance of standpipe systems.
10.2 The New York City Building Code describes the legal standpipe requirements in NYC.
Standpipe systems are described in the chapter dedicated to Fire Protection Systems.
10.3 The New York City Fire Code describes maintenance requirements for standpipe systems
in NYC. Standpipe systems are discussed in the chapter dedicated to Fire Protection
Systems.
NOTE: To simplify computing pump discharge pressure when supplying a standpipe system, a
street hydraulics chart has been formulated. These calculations are based on nozzle
pressure, friction loss of three lengths of 2 ½" hose, head loss, system friction loss, and
friction loss of two lengths of 3 ½" hose supplying the fire department connection.
Recommended Pump Discharge Pressures for Standpipe Operations
Recommended
Variations in building and standpipe system layout, length of supply lines, etc. will
impact pressure loss throughout the system. All members, particularly ECC’s, should
monitor the handie-talkie for indications that the pressure to the standpipe system needs
to be increased.
118
Probationary Firefighters Manual ,
ADDENDUM 2
2. INTRODUCTION
2.1 Experience has shown that members have become caught in wind-driven fires often with
minimal or no warning. Members must remain alert and knowledgeable of the conditions
which may cause a wind-driven fire, some examples include: a wind condition blowing
toward a fire apartment window, an open window, an open fire apartment door with a high
heat and smoke condition on the fire floor. If the equipment and resources are available
and wind conditions exist, the high-rise nozzle should be placed in position as a precaution
even if the need is not immediately evident. Depending upon the fire conditions
encountered, if the decision is made to place the High Rise Nozzle in position, additional
resources may need to be called to the incident.
2.2 Dispatch policy dictates that every 10-77 will have at least one HRN equipped engine
company assigned. It is the responsibility of the 5th due engine to bring the HRN to the
Incident Command Post. If the 5th engine is not equipped with a HRN, they will obtain it
from another unit on the scene. If necessary, the officer should contact the dispatcher for
the identity of the assigned engine company equipped with a HRN. Upon arrival the officer
will have the unit bring the HRN, roll-ups and a standpipe kit to the ICP.
3.1 The HRN may be used as an alternate attack strategy at high rise multiple dwelling fires in
the following situations:
3.3.1 IC has determined that a direct interior attack with a handline is not possible, such
as conditions caused by wind-impacted fires.
3.3.2 The fire apartment is inaccessible to traditional exterior streams (TL, handlines,
etc..)
3.3.3 Any situation where the IC determines the HRN will be beneficial.
119
FDNY Probationary Firefighters Manual
Chapter 12 Add 2 HIGH RISE NOZZLE
4. DESCRIPTION
4.1 The High Rise Nozzle is an eight-foot long aluminum pipe with a 68 degree two-foot bend
to provide the proper angle for the water stream. It is attached to a standard 2 1/2” FDNY
shut-off that is permanently attached to the nozzle. There is a T-shaped handle that allows
members operating the nozzle to control the direction of the stream and maintain control
of the nozzle. (Figure 1)
Figure 1
4.2 A 1 1/8” MST is attached to the outlet of the HRN. The tip is removable and should be
checked weekly during MUD and before use. (Figure 2)
Figure 2
4.3 The HRN may be supplied by a 2” or 2 1/2” hoseline. The HRN requires a pressure of 50
psi at the tip with water flowing to produce a flow rate of 225 GPM. A stretch of longer
than 3 lengths should be anticipated and thus the floor outlet pressure will need to be
adjusted accordingly. A properly positioned high rise nozzle in operation is shown in
Figure 3.
120
FDNY Probationary Firefighters Manual
Chapter 12 ADD 2 HIGH RISE NOZZLE
Figure 3
5. PROCEDURE
5.1 The High Rise Nozzle (HRN) will only be placed into operation at the direction of the IC,
who must be a Chief Officer.
5.2 The IC must consider the following when placing the HRN into operation:
5.2.3 Intensity and stage of the fire: Wind driven fire creating supercharged fire
conditions in the fire apartment and/or the public hallway.
121
FDNY Probationary Firefighters Manual
Chapter 12 ADD 2 HIGH RISE NOZZLE
5.3 The IC shall announce over all radio frequencies that the HRN will be placed into
operation, and ensure members are safely positioned before the stream is operated. By
design, the high rise nozzle provides effective water application based on the principles of
exterior water application (discussed further in Chapter 4). Namely the acronym S.S.S.S.
of solid bore stream, steep angle, steady stream without circular motion and a steep angle
providing a sprinkler effect.
5.4 The IC should ensure a spotter, equipped with a handie-talkie and a pair of binoculars, is
in place to clearly observe the operation from the exterior. This member must monitor the
conditions in the fire apartment before, during and after HRN deployment. The spotter will
provide direction and progress reports to the IC and members operating.
5.5 The officer supervising HRN use will initiate and maintain HT contact with the spotter to
ensure the nozzle is being operated effectively and the stream is knocking down the fire.
5.6 The IC should be aware that putting the HRN into operation will generally require
additional units to assist the 5th Engine. These units should bring roll-ups, standpipe kits,
and / or forcible entry tools to assist with deployment of the nozzle and forcible entry.
5.7 Units will need to gain access to the apartment below the fire apartment and determine
which window the HRN will be operated from. Depending on the situation, the hose line
supplying the HRN may have to be stretched from an outlet two or three floors below the
fire floor. Officers must size up the number of roll-ups required to reach the area of
deployment, if assistance is needed with forcible entry and inform the IC of the conditions,
the actions being taken and any needs that they have.
5.8 Once the proper window is chosen and opened, impediments such as window bars, child
gates, will have to be removed. In most cases it is not necessary to remove the window to
operate the nozzle. Some windows are easily removed via clips on the top of the sash.
5.9 The supply line must be attached to the HRN before the nozzle is slid out on the window
sill for use. Firefighters operating the HRN will use the T-handle to properly position the
nozzle for optimum stream placement. The T-handle will allow the firefighters to move the
nozzle along the window sill and maintain control.
5.11 The key to the rapid extinguishment of a wind-driven fire is putting water directly on the seat
of the fire. If multiple rooms are involved, it will be necessary to reposition the nozzle to
ensure complete knockdown of the fire. If this is the situation, start with the window that the
wind is blowing into and extinguish the fire in this room first. Then move to the other
windows downwind of the original fire room and complete knockdown of the fire.
5.12 If a wind-driven fire has control of several rooms, it will be necessary to move the HRN
from a window in one room to another window in a separate room to achieve knock down
of the fire. If this is the situation, company officers must anticipate and make sure the next
window(s) that will be used for operation of the nozzle is cleared of window gates, bars
etc., this will speed up the repositioning.
122
FDNY Probationary Firefighters Manual
Chapter 12 ADD 2 HIGH RISE NOZZLE
5.13 A shut-off shall be placed in line one length back from the nozzle. When repositioning of
the HRN is required, the supply line should be shut down at the shut-off located one length
back and the nozzle opened to bleed the line. This will make it easier to move the nozzle
and supply line while repositioning. Once in position, the officer supervising nozzle
operations will order water started. This officer will then notify the IC that the nozzle is in
position and ready to operate. The nozzle will not be operated until the IC has given
approval.
6.1 If repairs to the High Rise Nozzle are required, the company officer shall contact the
Technical Services Division via phone and request a replacement. The out of service HRN
shall be tagged with an RT-2 documenting the nature of the defect.
123
THIS PAGE WAS INTENTIONALLLY LEFT BLANK
124
Probationary Firefighters Manual
ADDENDUM 3
1.1 An air pressurized manual dry standpipe system is required at buildings under construction
upon reaching a height greater than 75 feet or buildings undergoing demolition with an
existing standpipe (2014 NYC Building Code and Local Law 64 of 2009). The entire
standpipe system including the riser, cross connections, and Fire Department Connections
(FDC) are pressurized by a dedicated air compressor. This air pressurized standpipe
system is designed to alert workers on site when the standpipe has been compromised.
1.2 When the air pressure drops below a predetermined (supervisory) pressure due to an open
valve or broken pipe in the system or pressure rises above 25 psi an audible alarm will
sound only at the site. The supervisory pressure will vary for each site but will always be
below a maximum of 25 psi. The alarm will continue until the opening in the system is
closed allowing the compressor to slowly bring air pressure back into the supervisory range
or excessive pressure is reduced below 25 psi.
1.3 When an alarm sounds, work at the site must cease, and construction personnel are to notify
the FDNY. Concrete pouring operations in progress shall be permitted until an orderly
termination of such operation can take place. No construction or demolition work shall
resume except repairs needed to restore air pressure to the standpipe.
Note: Any portion of the standpipe compromised above a closed section valve will
not cause activation of the alarm due to air pressure being maintained
constant in the lower portions of the standpipe.
2. OPERATION
2.1 To use an air pressurized standpipe system at a fire operation the air pressure must be released
from the system prior to uncapping the FDC and supplying it with water. Attempting to
remove the FDC caps prior to expelling the air from the system may cause the cap to become
a projectile causing serious injury. After the air pressure is discharged, units can supply the
system with water as they would at a standard dry standpipe operation.
2.2 A 2 ½” manual air release / drain valve (usually a standard standpipe outlet) is required to
be installed immediately adjacent to the FDC. (See Figures 1) Remove the manual air
release valve cap and open the valve fully. Air will be heard escaping from the manual air
release valve. The ECC shall not remove the FDC cap(s) until air pressure has been
expelled from the system. Air will be heard escaping from the open manual air release.
The number of air release valves is required to be such that air pressure shall be released
in no more than 3 minutes. When encountering systems with more than one manual air
release valve, all manual air release valves should be opened. (See Figure 3)
125
FDNY Probationary Firefighters Manual
Chapter 12 Add 3 AIR PRESSURIZED STANDPIPE
Figure 1
2.3 Once air pressure is expelled, FDC cap(s) may now safely be removed. Connect the supply
line, close the manual air release valve, and supply the standpipe with water.
2.4 It is not necessary to deactivate the air compressor as it will shut off when the standpipe is
supplied with water.
2.5 The location of the FDC is required to be marked by a sign and lit by a red light at night.
Signs are also required indicating that the standpipe is pressurized with air as well as the
location of the manual air release valve. (See Figures 1, 2 & 3)
2.6 If air is noticed escaping under pressure from a FDC cap while being loosened, and no sign
is present, member should stop cap removal immediately and notify the IC that the
standpipe is pressurized with air. Steps shall be taken to bleed the air from a manual air
release valve and/or standpipe outlet inside the building prior to removing the FDC cap(s).
Figure 2
126
FDNY Probationary Firefighters Manual
Chapter 12 Add 3 AIR PRESSURIZED STANDPIPE
2.7 Screw in type FDC caps are required in order to provide the air tight seal necessary for an
air pressurized standpipe system. Breakaway caps or other non-screw in type caps on the
FDC are indicative of a standpipe that is not pressurized with air.
Figure 3
2.8 The control firefighter, after reaching the floor outlet where the hoseline connection will be
made, should remove the cap, open the standpipe outlet control valve, and wait for water to
reach this point. This will expedite air removal from the system. Once water is present at
the outlet, close it, and make necessary connections. The standpipe system will now function
as a standard manual wet standpipe.
2.9 An occupied building with a wet standpipe system will have a check valve installed inside
the exterior building wall providing freeze protection for the piping and FDC connection.
During the construction or demolition phase with the standpipe pressurized with air, this
check valve will be bypassed allowing air pressure to reach the FDC connection. At a fire
operation, once the system has been drained of air and charged with water, water will flow
past the bypassed check valve(s) out to all FDC connections. If FDC clapper valves are
defective or tampered with in the second FDC, its caps may be under pressure.
2.10 The manual air release valve does not need to be opened when augmenting the standpipe
with a second pumper. However, when loosening the FDC cap(s) at this second FDC, if
water begins spraying out under pressure consider the clapper valves inside this FDC
defective. Immediately stop cap removal, and use another option for augmenting the
system e.g. supply the drain valve next to the FDC, use another FDC, or supply the first
floor or another floor outlet. The manual air release valve can be supplied in the same
manner as you would supply the first floor standpipe outlet.
127
THIS PAGE WAS INTENTIONALLY LEFT BLANK
128
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 1 HOSELINE PLACEMENT GUIDE
ADDENDUM 4
BROWNSTONES 135
TAXPAYERS 139
129
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
130
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
First Line - The first line should be stretched to the cellar entrance door
which is located inside the building, under the interior stairway on the first floor. This
line should remain at this position to provide protection for people coming down the
stairway, and to extinguish fire which may be extending upwards from the cellar via
partitions, dumbwaiter shafts and other voids. This line should not be advanced down
the cellar stairs if there is an outside entrance to the cellar at the front or rear of the
building, unless of course, the fire is minor.
Second Line - The second hose line stretched should be advanced into the cellar
by way of the front or rear entrance to the cellar.
Store Fires
First Line - The first line should be stretched to the store. Store fires in OLTs
may involve a large amount of combustible material. A 2 ½" line should be stretched for
large volume fires.
Second Line - The second line is stretched to the entrance hallway. When assured
that the second line is not needed on the first floor it may be advanced to the floor above
the fire.
Stairway Fires
First Line - The first hose line should be stretched up the stairway, operated to
extinguish fire, shut down and advanced further up the stairway. When possible, the
line should be operated up the well hole to cool off the hall and stairs above. This
procedure should be repeated until line is advanced
to the top floor.
Second Line - A second hose line may be necessary if it appears that fire might
have extended into the adjoining building.
For fires in rooms in the vicinity of a shaft, after the fire in the room has been
controlled, the line should be operated up the shaft to extinguish fire and cool the shaft.
131
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
This section includes all Class "A" non-fireproof multiple dwellings built after 1901.
Emphasis will be on the larger buildings, historically referred to as "H type" since they are our
greatest problem. Although there are variations in the shapes of these buildings, such as "U",
"O", "V", Double "E" and the newer, larger rectangular buildings, the problems and solutions are
similar. A "worker" in an apartment of an "H type" building is of much greater potential than a
similar fire in an apartment of a smaller building. An apartment in an "H type" building is
usually larger, irregularly shaped and has long private halls.
It is of vital importance that, before a line is committed in an "H" type building, the exact
location of the fire be determined. Care must be taken to avoid using a wrong stairway. Many
times just stretching a line to a fire apartment will prove difficult. It may require many lengths
(five or more) just to reach the building entrance. There may be large courtyards, often with
obstacles such as trees, benches, fences, shrubbery, etc. Every effort must be made to get the first
line in operation before additional lines are stretched. All available engine companies should be
used to stretch the first line.
Store Fires
First Line - The first line is stretched to the store and extinguishes fire.
Second Line- The second line should be used to back up the first line. When it is
obvious that the first line can control the store fire, the second line should be advanced to
the floor above the fire. If two lines are needed in the store, the third line shall be
stretched to the floor above.
Cellar Fires
First Line - The first line is stretched by way of the usually numerous exterior
approaches to seat of fire and extinguish.
132
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
Fires in these buildings can be extensive, extremely hot, and depending on wind
conditions and building air flow patterns, very difficult to extinguish. These fires require a
coordinated effort from the designated attack stairway with 2½" hose. All extinguishment efforts
shall proceed initially from the one attack stairway. If a
second stairwell is required for attack and extinguishment, it should not be the stairwell
designated as the evacuation stair.
When the fire apartment door is left open; it will allow smoke and/or fire to vent out into
the public hallway. If a window in the fire apartment fails, and wind is blowing into the fire
apartment, an extreme condition may be created on that floor. This may negate the standard
attack strategy; which is a direct frontal attack with a hose line from a stairwell, down the public
hall and through the apartment door. Prior to advancing to the reported fire floor, members must
gather information from the floor below, or two floors below if scissor stairs are present.
Determine the location, letter designation and number of stairways serving the fire floor.
Prior to the designation of the attack stairway, all members must access the fire floor
from the same stairway. If the door to the fire apartment has been left open and size-up indicates
that wind may impact fire conditions, the air flow paths must be controlled on the fire floor.
Uncoordinated opening of apartment and
stairway doors may cause fire conditions to dramatically increase with little or no warning.
The 1st and 2nd engines to arrive shall team up to place the 1st 2½" hose line into
operation on the fire floor. Initial hose lines stretched from a standpipe shall be from an outlet on
a floor below the fire. Communicate with the ladder company officer to select the attack
stairway. The attack stairway need not be the stairway with a standpipe outlet. The hoseline can
be connected and stretched on the floor below and then up another stairway that is closer to the
fire apartment to facilitate advance.
If the apartment door has been left open, the public hallway is now considered an extension of
the fire area, (fire apartment and public hallway);
• The hose line should be charged before exiting the attack stairway.
• In most cases, the hose line shall not enter the public hallway until the ladder company
locates the fire apartment and provides direction for the advancing engine company.
• Engine companies shall not enter the IDLH without a charged hose line.
133
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
The 3rd engine company to arrive is responsible to start the stretch of a 2nd hose line when
required. They will be assisted by the 4th engine company. If a 2nd hose line is not required, the IC
shall be notified. The second hose line is usually stretched from two floors below the fire. The
second line will be stretched via the attack stairway and this will be the factor in determining
which standpipe outlet to use. Additional lengths of hose will probably be needed from the 2nd or
4th engine companies. The additional lengths should be added between the last length of the 2nd
hose line and the standpipe outlet. The third engine officer will determine when this hoseline
shall be charged. This line should be charged at the stairway door to the fire floor depending on
hallway conditions and size of the fire area. When the 2nd line is charged the pressure on the first
line may drop; therefore, the control firefighter and officer of the first line should be notified.
134
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
BROWNSTONES
Fires discussed are to be considered of such magnitude as to require the use of one or two
hand lines for extinguishment. All interior hand lines stretched will be considered 1 ¾". Reason
for use: Speed, mobility, and close quarters
CELLAR FIRES
First Line - First hose line stretched through the front door on the first floor, then
down to the cellar via the interior cellar stairs to extinguish the fire.
Second Line - Second hose line stretched through the front door on the first floor
to back up the first hose line. If the first line was used to secure first floor, second
line will be stretched to cellar via interior cellar stair to extinguish the fire..
.
First Floor Fires
First Line - First hose line stretched through the front door on the first floor to
extinguish the fire.
Second Line - if not needed to back up the first hose line, shall be stretched
through the front door on the second (parlor) floor to maintain the integrity of the
interior stairs.
First Line - Advanced into the fire building through the front door.
Third Line – Will be stretched as ordered by the Incident Commander and may be:
1. Advanced into the fire building.
2. If fire is reported in an exposure, stretch to that exposure.
3. If there is no fire in that exposure, stretch through an exposure to the rear yard
of the fire building.
135
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
ROW FRAMES
These buildings, as the name implies, are built in rows containing as many as
twenty or more buildings. The room arrangement will vary with design of building. One
type is similar to the Brownstone layout of rooms. They generally have three front
windows per floor with one apartment going front to rear and no rear fire escape. Another
type is the railroad flat with two apartments per floor. They generally have four windows
across the front, with a rear fire escape.
CELLAR FIRE
First line - First line through the front door via the interior stairs to extinguish the
fire. When this line cannot be advanced down to the cellar due to the intensity of
the fire, it shall be used to protect the public hall, interior stairs, and the first floor,
allowing the occupants to leave the building, and the ladder company to perform
VEIS. The first line can be advanced to the top floor to cover any extension to that
area or the cockloft after the cellar fire has been controlled by the second line.
Intervening floors shall be checked for fire on the way to the top floor. A member
must be stationed on the landing to warn of any fire that may break out below
them.
Second line - Second hose line shall back up the first hose line. If the first hose
line has advanced into the cellar, and a backup line is not
needed, the second hose line shall extinguish any fire on the first floor then
proceed to the top floor as above. If the first hose line is used to cover the first
floor public hall, and a backup line is not needed, the second hose line will be
stretched into the cellar via the outside cellar entrance to extinguish the fire.
Second Line - The second hose line, if not needed to back up the first hose line,
should be stretched to the floor above the fire.
First line - The first line should be stretched to the location of the fire via the
interior stairs. This line will need to have sufficient length to cover the entire
building.
Second line - The line should be stretched to the top floor or to the floor above.
When a fire is reported in the exposure, the second line may be more effective
being stretched to the exposure, with the third or fourth line stretched to back up
line #l. This line will need to have sufficient length to cover the entire building.
136
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
ROW FRAMES
BUILDING FULLY INVOLVED AND FIRE IN THE EXOSURES.– HOLDING
OPERATION
First line - The first line is stretched into the fire building through the front door.
When a building is fully involved with fire showing in exposure(s) the first
arriving engine company should stretch one 3 ½" supply line for a tower ladder,
and a hand line for entering the building. Prior to the use of the TL stream, multi-
versal nozzle on the pumper, or heavy caliber stream, consideration must be given
to the life hazard and the need for advancement of an interior line.
Second line - The second line, if not needed to back up the first line, is stretched
to the top floor of the most severe exposure. This line will be needed to protect
the cockloft, and interior shafts. While proceeding to top floor check intermediate
floors for fire.
Second line - If not needed to back up the first hose line, shall be
stretched to the fire building or to the opposite exposure
Second line - If not needed to back up the first hoseline, stretched to the
opposite exposure or through an exposure to the rear yard.
NOTE: Whenever possible, a separate engine shall be dedicated to the sole task of
supplying water to a Tower Ladder in order to ensure proper water delivery.
137
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
VACANT BUILDINGS
Since the strategy of vacant building firefighting is based on timely and safe
control of the situation, the initial tactics of implementation are chiefly engine company
operations. In this regard, supply to, and placement of, apparatus is of critical importance.
Because of the conditions in a vacant building conducive to rapid fire build-up, quick
water on the fire is a prime requisite to affect reasonable control. For attainment of this
objective, deployment of the first engine company to arrive is most important.
Protection of life is the most important consideration in size-up. This means
placing the first stream between the fire and persons endangered.
A. When a vacant building is heavily involved on arrival, place hose streams
between the involved building and the most severe LIFE EXPOSURE.
Assume an unoccupied factory severely exposed by a fully involved vacant
building, and the same fire communicating to an occupied dwelling. The
first stream would be placed in position to protect the people in the
multiple dwelling, even though the factory is the most severely exposed of
the two. The factory is the Most Severely Exposed Building, but, because of
life hazard, the multiple dwelling is the Most Severe Life Exposure and the
exposure which must be protected first.
B. When no life is endangered in the exposures, position the first stream to
protect the greatest amount of property. Assume a fire exposing a stack of waste
lumber, and communicating at the same time but not quite as severely to
an oil storage yard. In this case, the stream should protect the oil storage yard.
Even though it is not the most severely exposed to fire, it is the Exposure to be
Given Greatest Consideration.
C. When possible, take a position which not only protects the exposure, but
also enables the stream to be used on the main body of fire. In cases where it is
impossible to so confine the fire, alternate the stream from fire to exposure.
This procedure controls the effects and reduces the cause of spread of fire.
When using an exterior hoseline from a purely defensive position, (i.e., when a
unit does not expect to advance a hoseline within the structure), members should
stretch a 2 1/2" hoseline.
TAXPAYERS
A fire in a taxpayer is usually a fast-spreading and difficult fire to control and
extinguish. It calls for many hand lines stretched quickly to the proper locations to prevent a
large loss. When heavy or medium fire conditions are encountered the initial lines should be 2-
1/2 inch. These lines can later be used to supply distributors, cellar pipes and heavy stream
appliances. If the striking power and the water capability of 2-1/2 inch hose lines are not
required, after the initial attack, they can be reduced to 1-3/4 inch lines for subsequent
operations.
CELLAR FIRES
1. To control the first floor if the first engine company has advanced into
the cellar via the interior cellar entrance.
3. Stretch into the cellar via the interior stairs or the outside entrance if
the first unit's line has to control the first floor.
Store Fires
First Engine Company - Stretch the first line into the involved store to
protect life and extinguish the fire. In a building protected by a sprinkler
system, when staffing and conditions permit, a second line shall be
stretched to feed this system.
139
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
TAXPAYERS
STORE AND COCKLOFT FIRES
Cockloft Fires
First Engine Company - When fire has control of the cockloft and the
need for exposure protection is critical, position the engine to utilize the deckpipe.
In-line pumping will give good positioning and allow room for placement of a
tower ladder. Stretch a hand line into the most seriously exposed
occupancy/building, depending on life hazard and the location and severity of the
fire
Second Engine Company –When fire has control of the cockloft, and the
need for exposure protection is critical, assist first engine with initial line. When
staffing and conditions permit, stretch a line into another seriously exposed
building/occupancy and operate into the cockloft to confine and extinguish the
fire. It may be advisable to skip stores in order to confine a cockloft fire.
140
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
The many variables and complexities built into high-rise office buildings
may be compounded by both the fire location and the fire load within the tenant
space on the floor. The many variables and complexities built into high-rise office
buildings may be compounded by both the fire location and the fire load within
the tenant space on the floor.
Remain at the ICP until the first ladder company has verified the fire
location. Proceed to the upper floor via the elevator staffed by the member of the
first ladder company. With the assistance of the second arriving engine company,
stretch a hose line from the standpipe outlet on the floor below the fire in the
designated stairway.
Provide the communications link between the lobby and the fire area
pending the establishment of a Fire Sector/Branch. This is accomplished by taking
the Post Radio and report with his/her company to their normal location in the
vicinity of the standpipe outlet from which the first hand line is being stretched.
Assist the first arriving engine company in stretching sufficient hose to reach the
fire. Leave the fire area when the hose line has been stretched and is operating so
as not to deplete their air supply.
141
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
PRIVATE DWELLINGS
Private dwelling fires challenge the expertise of firefighting forces and require a
coordinated team operation. Seventy percent of all fire deaths occur in private dwellings.
Due to the size of these structures, crowding of stairs may become a major problem.
Stairs must be kept clear. The number firefighters inside the fire building should be kept
to a minimum to safely carry out operations.
Fires discussed will be based on the need for one or two hand lines. Due to the
combustible nature of both interior and exterior building materials, fire can spread
rapidly. The unprotected, open interior stairwell to the upper floors acts as a natural flue
for fire spread. Small rooms and narrow stairs are commonly found in these dwellings.
Due to the need for speed and mobility, a 1¾" hoseline is recommended.
CELLAR FIRES
First Hose line - Proper placement of the first hoseline requires a coordinated
size-up and communication by the first Engine and Ladder Officer. After size-up, the first
hoseline should be stretched to the entrance door that provides the quickest access to the
cellar in order to extinguish the fire. In detached and semi-attached PD’s, the secondary
entrance found on the side or rear of the dwelling is usually the option that provides the
quickest access to the cellar. Some PD’s have secondary entrances to the cellar in the
front of the dwelling which lead directly into the cellar and provide quick access. When
using a secondary entrance, members should size-up the layout of the entrance, the stairs
and the cellar, and then flake the hoseline out for the most efficient advance of the line.
This is particularly important when stretching hose via a narrow alley, driveway or rear
yard. In some situations, various factors including the following would preclude the
descent of the first hoseline down the interior cellar stairs:
In the cases above, hoseline advancement via a secondary entrance or water applied
through a cellar window will be available options.
In situations where the first line is advanced through the main entrance and the first
hoseline does not advance into the cellar, then the first hoseline will maintain its
position on the first floor (if safety allows) to:
142
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
PRIVATE DWELLINGS
CELLAR FIRES
Second Hose Line - Initially positioned and charged outside the fire building as a
back-up for the first hose line. When not needed to back-up the first hose line, it
can be used to extinguish any fire that may extend to the floors above or
positioned as per the Incident Commander. Enough hose line shall be considered
in the stretch for possible advancement into the cellar through an exterior
entrance. Depending on where the first hoseline was stretched and the progress of
thishoseline, the IC should consider the following options for placement of
the second hoseline:
Second Hose Line - Initially positioned and charged outside the fire building as a
back-up for the first hose ine. When not needed to back up the first hose line, it
can be used to extinguish any fire discovered in the cellar, on other floors, or in
exposures.
143
FDNY Probationary Firefighters Manual
Chapter Twelve, Addendum 4 HOSELINE PLACEMENT GUIDE
PRIVATE DWELLINGS
BUILDING FULLY INVOLVED
EXPOSURE PROTECTION
• Fire "lapping" out of a window, or burning on the exterior of a building, presents a
serious exposure problem.
• Openings in the underside of eaves (i.e. vent openings) or deteriorated siding may
allow for fire extension to the attic of an exposure or the original fire building.
• Units operating a hose line to extinguish fire on the exterior of a building should
sweep the stream across the face of the building, starting at the top, so the water
cascades down the exterior.
• Consider stretching a 2½” hose line if increased volume or reach of the stream is a
consideration.
144
PART TWO
ENGINE EVOLUTIONS
SECTION TITLE PAGE
1 ESTIMATING A HOSE STRETCH .................................................147
5 BACKSTRETCH...............................................................................154
145
146
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
1.2 This rule assumes that the engine has stopped at the fire building and the required
lengths are removed prior to repositioning the apparatus at a hydrant.
1.3 For large multiple dwellings (H-types and their variations), hose estimations must
consider the distance from the backstep of the engine to the entrance door. In
some cases several lengths of hose might be required to reach the entrance door.
The distance from the entrance door to the base of the stairway must also be
considered. This is in addition to the required one length per floor plus one for
the fire floor. Some buildings may require two lengths for the fire floor.
1.4 If the engine apparatus is positioned at a hydrant before reaching the fire building
or has to pass the fire building, the additional distance must be taken into account
in estimating the number of lengths required to reach the seat of the fire. The
building frontage can be used to estimate the required number of additional
lengths. Ex: row of OLT's, engine is two buildings past fire building, OLT 20-25'
wide, at least 2 lengths will be needed to reach the entrance to the fire building.
1.5 Use the apparatus for as much of the stretching as possible. Hose stretched at
fires should be laid as close to the side of the street as possible and on the same
side as the hydrant or pumper. If it is necessary for hoselines to cross the street,
the lines should cross in front of the fire building. This allows as much room as
possible for the maneuvering of apparatus.
147
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
2. WELL-HOLE STRETCH
2.1 The use of a well-hole for stretching the hoseline allows for more rapid
positioning of the line and reduces the number of lengths required. The rule of
thumb is that a 5 story stretch up a well-hole requires about one length of
hose (see Fig. 2-1A & 2-1B).
2.2 The engine officer should communicate to the members stretching, the presence
of a well-hole, as soon as possible. The officer should look up the well to see if it
goes up the entire stairway. In certain stair configurations, a well exists between
the 1st and 2nd floor, but the rest of the stairway does not have sufficient space to
accept a charged hoseline.
A. The nozzle firefighter has two options depending on the size and
configuration of the well-hole.
• Narrow well-hole - nozzle firefighter drops his/her folds at the base
of stairway, securely grasps the nozzle and proceeds up stairway
pulling hose up through well-hole.
• Wide well-hole - nozzle firefighter carries nozzle and lead length in
well.
Fig. 2-1A
148
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
F. The door firefighter lightens up on the line and proceeds up the stairway
pulling line up the well-hole.
G. The control firefighter will remain at the base of the stairway until notified
by the officer that sufficient hose has been stretched. Any remaining hose
on the first floor should be flaked out and checked for kinks, once the line
is charged.
2.4 When a second hoseline is stretched up a well-hole, caution must be exercised to
ensure the first and second lines do not become entangled. To prevent
entanglement, the nozzle firefighter should carry only the nozzle and change
hands at each newel post (turn) as the line is stretched up the well-hole. A utility
rope can also be used if the well-hole is large enough to accommodate its use.
Fig. 2-1B
TOTAL =
3 LENGTHS
149
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
The fire escape stretch can be utilized to stretch a hoseline (or an additional line) via the
outside of the building. The line can be stretched to the balcony of the floor below the
fire and in through a window and up to the fire floor via the interior stairs. Another
option, when there is no access via the interior (i.e. a vacant with damaged interior stairs)
is to stretch up to the balcony of the floor below the fire and then gain access to the fire
area via the balcony through a window on the fire floor.
NOTE: The following is the procedure to follow when utilizing the fire escape to
access the fire floor from the fire escape.
3.1 Sufficient hose should be stretched and arranged below the fire escape balcony.
3.2 The hose can be hoisted with a utility rope or a 6 foot hook.
♦ If the rope is used:
the nozzle firefighter should proceed directly to the balcony of the floor
below the fire and pull up the nozzle once the Control firefighter secures it
to the rope.
♦ If a 6 foot hook is used:
members ascend the fire escape and position themselves on successive
balconies, with the nozzle firefighter proceeding to the upper balcony. At
ground level, the control firefighter inverts the hook and places the handle
of the controlling nozzle onto the hook. The handle is passed from the
member below to the member on the balcony above. The member on the
lowest balcony (door Firefighter) remains at this position to lighten up on
the hose until sufficient hose is hoisted. Nozzle and back-up firefighters
continually pass the hook up and move up until the nozzle reaches the
balcony of the floor below the fire.
In both cases the control firefighter will remain at ground level and assist
in hoisting and securing the line. Once sufficient line has been hoisted and
the line has been charged, the control firefighter can ascend the fire escape
and join the nozzle team (see Fig. 3-1).
3.3 Once the nozzle reaches the balcony of the floor below the fire, the nozzleman
must secure the nozzle and notify other members to move up one landing
(exception: Control firefighter remains at ground level). At this point the
nozzleman pulls up sufficient hose to make entry on the fire floor above. This
additional hose can be flaked over the fire escape railing. Once this hose is in
place the nozzleman can position himself roughly half way up the steps to the fire
floor landing to await water.
3.4 The back-up man, upon reaching the balcony below the fire will pull additional
hose to operate through the fire area above. When sufficient hose is pulled onto
this balcony the back-up man will secure the line with a hose strap and then join
the nozzleman.
150
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
3.5 The doorman, will initially lighten up on the hoseline as it’s being hoisted. Once
the backup man is done hoisting hose the doorman (if necessary) will secure the
hose to the fire escape railing and then proceed up to flake out hose from the fire
escape into a window on the floor below the fire.
3.6 The line must be secured with hose straps on alternate floors, beginning with the
floor below the fire.
Fig. 3.1
3.7 NOTES:
♦ The line is secured with hose straps beginning with the floor below the fire
and continuing with alternate floors down.
♦ Hose straps are used as follows: hook end of strap is passed around hose and
through loop of rope. It’s then pulled taught, brought over and under fire
escape railing, and then hooked on strap.
♦ Prior to charging the line members must position themselves between the dry
line and the building- not the dry line and the fire escape railing.
♦ Fire below the 4th floor, the line is stretched up the well of the fire escape.
151
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
4.1 Engine companies should carry 75 feet of 3/8 inch nylon rope to be used for a
quick, efficient stretch to upper floors or roofs (see Fig. 4-1). This rope can be
used to haul the line:
• To roofs of low buildings, i.e., taxpayers, three story frames, brownstones.
• In vacant buildings when interior stairs are missing or damaged and would
present a hazard in supporting an interior stretch.
• In buildings with the staircase winding around an elevator shaft.
• At fires requiring three lines, when the interior stairs already have two
lines on them.
• When CIDS or previous knowledge indicates its use.
• In non-standpipe project buildings.
Fig. 4-1
4.2 Example: Utility Rope Stretch Via Stair Shaft Window In Buildings With Stairs
That Wrap Around An Elevator.
♦ In order to reduce the number of lengths required and speed up the stretch,
the line can be hoisted via stair shaft window with the utility rope. If the fire
is below the third floor, the line is stretched up the stairs.
152
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
♦ The officer's initial size-up will determine if this type of stretch would be
beneficial in reducing the number of lengths required. Knowledge of the
building, the location of the fire, and availability of stair shaft windows will
assist in making this determination.
♦ Before the utility rope is deployed, look out the window and check for
obstacles or obstructions such as air conditioners, clotheslines, overhangs or
setbacks which might interfere with the rope.
♦ Remove the child guard if present, raise the lower sash and ensure that it stays
open.
♦ At the lower floor window, lower the top sash, grab rope and tie to nozzle.
♦ Members must be aware that tools will be required to remove child guards.
Some windows will be secured closed and others may have stops which limit
the raising of the sash only a few inches.
♦ Hinged windows which open outward can prove difficult and similar windows
on intermediate floors may have to be closed to prevent the line from getting
hung up.
♦ If difficulty is encountered in raising a window, remove glass from sash.
153
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
5. BACK STRETCH:
A backstretch is a stretch of an attack line in which the pumper reaches the fire before the
hydrant. The necessary amount of hose to reach the fire is removed and the pumper can
be used to fill out the stretch. As the pumper proceeds to a hydrant the additional
necessary hose peels off the rear of the hosebed.
5.1. Steps:
♦ Pumper proceeds to hydrant playing out hose on way. One member (control
firefighter) rides rear step, standing clear of moving hose. Upon reaching
hydrant, connect pumper; break hose line and attach to pumper. Officer gives
command, "Start Water." Control firefighter after controlling stretch, proceeds to
fire, moving hose close to curb, removing kinks etc.(See Fig 5-2)
Fig 5-1
Fig 5-2
154
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
♦ To Remove hose from apparatus one member mounts rear step of apparatus,
places arm through first 3 folds of hose, gives a strong pull, steps down and walks
backward, dragging hose. Firefighter lays hose on ground about 15 feet from
apparatus and slightly to side in direction of stretch. A second firefighter lays the
next three folds directly to rear of apparatus. A third member lays the next three
folds slightly to side away from direction of stretch. There are now three full
lengths laid out neatly in street. Additional hose may be removed similarly.
♦ Advancing line to fire -- (Three members used). Attach nozzle to line. Each
firefighter carries three folds of hose. They walk toward point of operation with
loop of hose between each member. As they advance, hose is played out in a
continuous line beginning with last firefighter.
♦ When fire and hydrant are adjacent, apparatus need not be used in stretching lines.
♦ If, on rolling in to fire, the officer anticipates use of multiple lines, two lines shall
be laid simultaneously by apparatus performing stretch.
6. INLINE PUMPING:
Inline pumping is a stretch of the supply line in which the hydrant is located before the
fire (in relation to the direction of the pumper’s response). In this evolution the supply
line can be stretched from the hydrant to the pumper’s operating point (in this situation
the hose would peel off the hosebed as the pumper proceeded to the operating point).
Another option would be to hand stretch the supply line from the operating point back to
the hydrant.
6.1 Steps:
♦ Pumper stops so that the rear step is opposite the hydrant. The Hydrant FF
equipped with a hydrant wrench and a 2½” gate, tests the hydrant. A bolt cutter
should be taken if necessary.
♦ After the hydrant is deemed serviceable, the Hose FF keys the hydrant by
pulling sufficient 3½” hose from the hose bed prepared for In-Line Pumping
(ILP) and takes a turn around the hydrant. (See Figure 1) The Hose FF then
mounts the pumper's backstep, and prepares to use the signal buzzer. (See
Note 10)
155
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
2’
Figure 2
Figure 1 Hydrant FF Maintaining Keyed Hose
Hydrant Keyed With 3½ " Hose
Figure 3
• Hydrant FF connecting 3½” hose to 4½”
outlet of hydrant Figure 4
• 2½” gate connected to 2½” outlet of Hydrant FF waiting for notification
hydrant to start hydrant water.
6.2 At a slow rate of speed, playing out 3½” hose, the pumper proceeds to the vicinity
of the fire building, so as not to impede the positioning of a ladder [Link]
Hose FF rides the rear step and monitors the playing out of the supply hose.
6.3 Pumper stops at the operating position where the members remove enough hose to
reach the fire. The ECC:
1) “Drops” booster tank water into pumps
2) Engages the pump
156
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
3) Breaks the 3½” inch supply line and connects it to the 3” gated inlet on
the pump panel side.
4) Notifies the Hydrant FF to start water.
Note: The ECC should leave the gated inlet closed while opening the drain to the gated
inlet, thus allowing air in the 3½” supply line to exhaust. When good water flow is
observed flowing through the drain, the ECC should close the drain.
The ECC should then slowly open the 3” inlet gate fully, then prime the pumps and begin
fire line operations as per standard operating procedures.
Supplying booster water upon Officer's orders shall be given priority over hooking up the
in-line supply line.
6.4 After receiving notification from the ECC to start water, the Hydrant FF opens the
hydrant fully and then proceeds to the pumper for the purpose of controlling the
stretch. The Hydrant FF, after controlling the stretch, ensures tools are placed on
the apparatus and then proceeds to the fire, moving hose close to the curb,
removing kinks, etc.
Note: Depending on staffing, the initial handline stretch will be controlled by either the
Door FF (5 FF Engine) or the ECC (4 FF Engine), until relieved by the Control FF
(Hydrant Firefighter).
6.5 When the Engine Officer calls for water, the ECC supplies available water,
notifying the officer as to type. If booster water is used, the ECC must notify the
Engine Officer when hydrant water is started.
6.6 ECC notifies the Incident Commander and incoming Engine Companies when the
necessity exists for the ILP pumper to be augmented. (See Note 5)
NOTES:
1. Hydrant shall be tested and flushed before the supply line is committed.
2. Hydrant selected for ILP must be on a 6” or larger main. During Water Alert, ILP shall
not be used unless absolutely necessary.
3. Pumper shall use 3½” inch hose as the initial supply line from the hydrant to the pumper.
4. Not more than 6 lengths of hose shall be used in the initial supply line.
5. When intake pressure drops below 15 psi, the pump operator shall have his intake supply
augmented.
6. Necessary fittings to connect to a hydrant shall be preconnected to the 3½” supply hose
on the pumper.
7. In order to prevent injuries or damage to hose or equipment, the supply line shall not be
preconnected to an inlet of the pumper.
157
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
8. Consideration should be given to the pumper mounted deck pipe nozzle in ILP
positioning when the need for exposure protection or quick knock down is evident.
9. Pumpers should not be positioned where they will prevent effective utilization of aerial
and tower ladders.
10. Pumper may proceed to the operating position, stopping only to drop the Hydrant FF off
for testing the hydrant. Generally, a maximum of 3 lengths of 3½” supply line may be
hand stretched back to this hydrant if necessary.
11. Time permitting, a 2½” gate should be attached to the hydrants 2½” outlet for possible
augmentation if necessary. This is particularly effective when the hydrant being used for
ILP is nearby (3 lengths or less).
12. The ECC of the ILP should have water supply augmented when the intake pressure drops
below 15 psi. The method selected requires judgment based on fire conditions, location
and location of apparatus.
13. The following signals shall be sent from back step buzzer:
One buzzer tone -----------Emergency stop.
Two buzzer tones ----------Hose FF is in position, pumper to proceed.
Three buzzer tones --------Area to rear of pumper is clear for backing up operations and
under proper supervision.
14. ILP is another option in stretching firefighting lines. It may be used in lieu of the back
stretch when conditions indicate that ILP may be advantageous.
ILP may be utilized as a supply option when signal 10 – 70 is transmitted.
15. The capacity of a hydrant is a major factor in “In-line pumping” operations. The capacity of
a hydrant is based on many variables (size of main, location within the system etc.). It is
important for units to know the capabilities and limitations of hydrants in their response area.
158
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
7. RELAYING WATER
A relay operation is one in which one pumper supplies water to another. Relay
operations can complicate pumping operations because they require
coordination between two or more pumpers (potentially accruing higher pressures) and
two or more pump operators (necessitating more communication). In addition there is an
increased possibility of introducing air into an operating pumper and losing prime.
However, if a water relay is warranted, the following procedure shall be implemented.
Figure 1 Figure 2
Supply Pumper Operating Pumper
7.1. Steps:
♦ The Officer or ECC of the operating pumper (normally 1st due pumper), upon
finding no viable water source transmits signal 10-70 via Department radio and
HT and decides on optimum position of the pumper, factoring such things as
easiest hose stretch, ladder company accessibility, fire conditions, collapse
potential, etc.
♦ The next arriving pumper, designated as the Water Resource Unit, upon
hearing signal 10-70 must find a viable water source.
♦ The supply pumper connects to a hydrant utilizing either the 10’ or 35’ hydrant
connection. The necessary lengths of 3½” hose are stretched from a 3” outlet
of the Supply Pumper to the Operating Pumper’s 3” gated inlet on the pump
panel side of the pumper.
Figure 3 Figure 4
3½” Hose From Supply 3½” hose Into Operating
♦ Pumper's 3 ”Gated Inlet
Pumper's 3” Outlet (Pump Panel Side)
159
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
Both the Supply Pumper and the Operating Pumper must remain in the Volume
Position. An exception to this is standpipe operations, where head pressure needs
to be overcome. In this case, the operating pumper will operate with its pump in
the Pressure configuration. (Supply pumper will still be in volume).
Figure 5
Transfer Valve in the Volume
♦ When ready to send water, the Supply Pumper ECC communicates this to the
Operating Pumper ECC. Upon confirmation that the Operating Pumper is
ready the Supply Pumper ECC should fully open the 3” discharge valve to
supply idle pressure. Idle pressure is hydrant pressure plus pressure imparted
by the pump at idle (typically 100-125 psi).
♦ If the Supply Pumper’s Intake pressure gauge drops below 15 psi, the Supply
Pumper ECC should contact the Operating Pumper ECC and the Incident
Commander to inform them that the hydrants supply limit has been reached.
NOTES
1) Time permitting, a 2½” gate should be attached to the 2 ½” hydrant outlet for
possible augmentation if necessary.
160
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
4) On some hydrants with high pressures (e.g., parts of Staten Island) the Intake
pressure reading on the Operating Pumper may reach or exceed 150 psi, even if
the Supply Pumper is in the Volume position. If the Operating Pumper ECC
notes the intake pressure is greater than 150 psi or the automatic intake relief
valve discharges (this should happen when the inlet pressure reaches 150-175
psi), he/she should communicate with the Supply Pumper ECC to insure he/she
is in the Volume position.
6) Officers ordering ECCs to “drop” booster tank water should be aware that in
addition to the possibility of running out of water, it also increases the
possibility that the pump may loose prime, necessitating the ECC to shut down
lines and re-prime the pumps.
8.1 ECC- Connect pumper to hydrant and charge pump. Stretch 3½" hose line from
pumper and connect to Siamese to supply standpipe siamese. Start water.
Augment supply to siamese with second hose line from pumper.
8.2 Control firefighter will proceed to the floor below the fire with a folded length of
2½” hose and the standpipe kit. The Nozzle, Back-up and Door Firefighters (if a
five (5) fighter company) will proceed as follows:
161
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
♦ Leave straps connected on folded lengths and proceed as follows: (Photo 8-1)
Remove protective covering from male butts.
Nozzle firefighter connects hose butts between lead length and second
length.
Backup firefighter connects hose butts between second and third
lengths.
Door firefighter (if present):
a) Connects hose butts between 3rd and 4th lengths (if needed).
b) Assists Control firefighter in hooking up to standpipe.
c) Assists Nozzle and Backup firefighters.
Photo 1
♦ Disengage straps from the folded lengths. The Nozzle firefighter may opt to
take his length up to the fire floor before removing the strap.
♦ Nozzle and Backup firefighters advance the hoseline up the stairway to the fire
floor. Hose plays out in the same manner as if it was stretched from the bed of
the apparatus. Door firefighter (if present) monitors hose as it plays out to
prevent kinks and snags. Control firefighter operates standpipe.
♦ The control firefighter of the 1st to arrive engine company will complete the
connection to the standpipe outlet, charge the line when ordered, provide
proper water pressure, and remain at the standpipe outlet throughout the
operation to provide orderly and accurate communications and continuity.
162
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
NOTES:
a. All hoselines stretched from standpipe shall be 2½" hose with controlling nozzle and
1⅛" Main Stream Tip. All hoselines stretched from standpipes shall be connected to
outlets on floors below the fire floor. Variations from stretching initial hoselines from
standpipe outlets on a floor below the fire due to building configurations shall be
approved by division commanders and placed in the CIDS program.
b. If a pressure reducing/restricting device (PRD) is found on the standpipe outlet, it
should be removed. If the PRD cannot be removed, and there is no other outlet
available without a PRD, than it is permissible to use an outlet with a PRD.
c. Always connect in-line pressure gauge to standpipe outlet to ensure correct nozzle
pressure. Pressure gauge can be carried attached to the Control firefighter's length in
the same manner as is the nozzle.
d. Controlling nozzle must always be carried attached to the folded lead length.
e. Observe the color of siamese or outlet caps and indicating signs or plates before
connecting hose lines. Color markings for the systems are:
♦ Standpipe……………………………………Red
♦ Automatic Sprinkler………………………..Green
♦ Non-Automatic Sprinkler…………………..Aluminum
♦ Combination Standpipe/Sprinkler………….Yellow
To supply the standpipe if the Siamese is inoperable (but the system is otherwise
serviceable) or if the Siamese is supplied but further augmentation is required, this can
be done by connecting and supplying water to the first floor outlet. To make this
connection a 3”x 2 ½” reducer and a 2 ½” double female is required. Another option to
make this connection would be to use a 3” double female and a 2 ½”x3” increaser.
f. Before water is started, member controlling supply must personally check connection of
hose to proper siamese.
g. If building is equipped with both standpipe and sprinkler systems and standpipe is to be
used, the engine company first to arrive must connect first line to standpipe siamese and
second line to sprinkler siamese.
h. Another pumper must augment the supply to combination standpipe and sprinkler
systems.
i. Certain pumpers in the FDNY are capable of delivering water at high-pressure, this may
be needed in high-rise buildings. During high-pressure pumping, members must not
utilize stairways as staging or rest areas. Utilize minimum amount of personnel in
stairways served by standpipes, during high-pressure operations.
j. Exposed male hose butts on folded lengths must always be protected.
k. Photo 2 demonstrates how to carry folded lengths so as to protect the firefighter and
others from the exposed hose butts. Note that the folded length is placed with the butts
toward the body, minimizing the chance of the butts flopping around (especially in tight
quarters like elevators).
163
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
Photo 2
l. The folded lengths shall be placed on the floor with the butts facing up. For narrow
landings, folded lengths can be stacked on stairs, adjacent to each other. (Photo 3)
Photo 3
164
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
Stretching a line up an aerial is another option available to place a hoseline from the
exterior when the situation calls for such. The procedure is as follows:
9.2 Place turntable of aerial ladder directly below objective. Raise ladder and place it
in position with tip of ladder level with sill..
9.3 Stretch hose from pumper and use controlling nozzle. Arrange hose in folds
below turntable.
9.4 Officer climbs ladder, enters window, surveys conditions, and orders line
advanced. Nozzle, backup, and doorman use life belts. The nozzleman climbs to
turntable; nozzle is passed up to him. Placing hose under left arm and nozzle over
right shoulder, nozzleman climbs the aerial. Backup and doorman follow
nozzleman, lightening up on line. Nozzleman snaps life belt on top rung of aerial
and passes nozzle and hose in over sill to officer who holds the line. Nozzleman
then climbs in the window. Backup continues up, positions at top of the aerial,
and snaps life belt on top rung. Doorman positions at middle of the aerial and
snaps life belt hook on rung. The Control firefighter positions on turntable to feed
hose up ladder.
9.5 When the backup and doorman are locked in to aerial, the nozzleman, assisted by
those locked in to aerial pulls sufficient hose in for operations.
9.6 When sufficient hose is raised both the backup and doorman secure the hose with
hose strap to the aerial, unsnap their life belt, and move up to join nozzleman for
operations.
9.7 When hose is flaked out and everyone is in position the officer gives the
command to start water.
NOTES:
1) Hose is placed on left side of ladder as men climb.
2) All members operating on ladders shall wear personal harness or life belts.
165
FDNY Probationary Firefighters Manual
Chapter Twelve (Part 2) ENGINE COMPANY OPERATIONS
166
Probationary Firefighters Manual
Chapter 13
CONTENTS:
13
ENGINE COMPANY
EMERGENCIES
1.1 Engine companies can encounter a number of unique emergency situations on the
fireground. Each presents a serious safety hazard and need to be decisively addressed to
avoid catastrophic consequences.
1.2 Engine emergencies can be classified into three broad categories, based on the underlying
threat presented by each specific situation:
1.3 The following sections will describe a number of emergency situations that engine
companies may encounter at a fire operation. These sections will also discuss the proper
reaction by engine company personnel, as well as potential solutions to the problems faced.
2.1 The inability of the 1st due engine company to secure a positive water source is a serious
situation that affects everyone on the fireground.
2.2 Anytime an engine company is unable to secure a positive water source, a signal 10-70
should be transmitted. This should be given by an URGENT handie-talkie transmission in
accordance with Communications Manual: Company Unit Communications. The signal
10-70 should also be transmitted over the department radio, which will alert incoming units
of the situation. The 2nd due engine officer will be designated the “Water Resource Officer”
and will be responsible for ensuring a water source is secured.
2.3.1 If the 1st due engine finds their hydrant to be inoperative (or frozen), the ECC should
immediately notify their officer that their primary hydrant is inoperative and
attempt to find a nearby operable hydrant that can supply water. If there are no
nearby hydrants, and the second due engine is not on scene, the 1st ECC should
transmit a 10-70, as described above.
2.3.2 If there is another hydrant in the immediate area, the ECC should test it for
operability. If the second nearby hydrant is inoperative or frozen, and the second
due engine is not on scene, the 1st ECC should transmit a 10-70, as described above.
1
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
2.3.3 If there is no alternative hydrant in the immediate area and the 2nd due engine is on
scene, the 1st ECC should contact the 2nd ECC to see if they have a working hydrant.
2.3.4 If the 2nd due company has a working hydrant, the 1st ECC must determine if they
can hook up to that hydrant directly, either by repositioning their rig, or by
stretching 3 ½” hose. If either option is available, the 10-70 signal is not required.
2.3.5 If the 1st ECC determines that they cannot directly hook up to the working hydrant,
they will need to be supplied via a relay operation. If this is required, the 1st ECC
should transmit a 10-70, as described above.
2.3.6 If the 2nd due engine does not have a working hydrant, both ECC’s must continue
searching for a working hydrant until a water source is obtained. In this situation, a
10-70 should be transmitted as described above.
2.4.1 If the standpipe system fails to provide a water source on the upper floors of a high-
rise building, engine company members will not be able to stretch and operate a
hoseline from the standpipe outlet, creating an emergency situation for operating
units.
2.4.2 This will likely be discovered by the control firefighter at the standpipe outlet. If
they are unable to use the standpipe system to supply the hoseline, they should
transmit a signal 10-70 via an URGENT handie talkie transmission as described
above and inform the Incident Commander and engine officer of the situation.
2
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
2.4.4 If the standpipe system proves to be fully inoperative, engine companies must seek
out an alternative method of supplying water to the fire floor. By the time the failure
of the standpipe system is discovered, the 1st arriving engine will likely be
positioned at the floor outlet on the floor below the fire, equipped with their
standard complement of equipment, which includes 3 lengths of hose and a
standpipe kit. Using this equipment, this emergency can be solved by performing
either a “reverse stairway stretch” or an “exterior hose drop”.
2.4.5 A “reverse stairway stretch” involves members carrying 2 ½” roll-ups into the
building and stretching down the stairway to the apparatus. Rather than beginning
the stretch on the street level, the stretch begins on the floor below the fire and
additional lengths are added as it continues down the designated stairway. This
method will use gravity to facilitate a long and difficult stretch.
3
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
2.4.6 An “exterior hose drop” is similar to a rope stretch, but instead of using a rope to
hoist hose up to a window, members will lower connected lengths of hose down
from a window to the street below. While completing a rope stretch from a window
on an upper floor might be possible, the extreme weight of the hose will make
hoisting the required number of lengths prohibitively difficult.
2.4.7 In both scenarios, the key point is that 2 ½” roll-ups are carried to the fire area and
stretched down to the apparatus.
2.5.1 The execution of a reverse stairway stretch must be approved by the IC and
communicated to all units.
2.5.2 The engine officer will communicate with the Incident Commander and the ECC
to identify the stairway to be used for the stretch. On the ground, the ECC (assisted
by additional engine companies) will begin stretching 2 ½” hose up the designated
stairway.
2.5.3 Beginning on the floor below the fire, members will connect their lengths of 2 ½”
hose (roll-ups) and begin stretching down the designated stairway. As additional
engine companies arrive, they will add their roll-ups to the stretch as it descends
the stairway. Members should ensure the female end of the hose is being stretched
downwards towards the street.
2.5.4 Depending on the length of the stretch, additional engine companies may be
directed to report to a lower floor (equipped with their roll-ups) to meet the stretch
as it descends the stairway. This operation will require significant coordination and
clear communication to ensure sufficient hose is brought to the correct locations.
2.5.5 The stretch will continue down the designated stairway until it meets the hoseline
being stretched up the stairway. At this point, the hoselines will be coupled and the
stretch will be complete.
2.5.6 Once the stretch is complete, the engine officer in command of the nozzle team
must be notified. Only the officer in command of the nozzle team can call for the
hoseline to be charged.
2.5.7 The ECC should supply the line with pressures consistent with the street hydraulics
calculations for a 2 ½” hoseline. The ECC must remain aware of any indication of
insufficient pressure in the hoseline and be prepared to supply additional pressure
if necessary.
4
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
Figure 1
2.6.1 The execution of an exterior hose drop must be approved by the IC and
communicated to all units.
2.6.2 The engine officer will communicate with the Incident Commander and the ECC
to coordinate the location from which the hoseline will be lowered. On the ground,
the ECC will stretch a 2 ½” line to the point at which the lowered line will reach
the ground.
2.6.3 hose and begin to lower it out the window. If there is a rope available, it can be tied
as a safety precaution to the lead coupling being lowered, so as to allow the
members waiting on the ground below to guide the hose as it’s being lowered. Once
the lead coupling reaches the ground, the ECC will couple it to the supply line
stretched to that location.
2.6.4 After the hose has been lowered, members of the first due engine company must
properly secure the hose. This is the most critical point of the evolution. If the hose
is not properly secured, the weight of the charged hoseline will cause such severe
kinking in the line such that sufficient water will not reach the fire floor. Once
charged, the line will be too heavy to move and adjustments to eliminate the kinks
will not be possible.
5
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
2.6.5 To properly secure the hoseline with the equipment available, a rolling hitch must
be tied and secured directly below the first hose coupling that will be located
outside the window (Figure 2). The knot must be tied and secured before the line is
charged. If a different knot, such as a standard clove hitch, is used, the line will
likely kink around the rope and severely limit water flow. The wide surface area of
the rolling hitch (4 turns around the rope) will minimize this kinking effect. If the
knot is tied away from the coupling, it will likely also kink severely; it requires the
stability of the coupling to prevent kinking.
2.6.6 Once the rolling hitch is tied at the coupling, the knot must be lowered outside the
window so the hose is oriented vertically (Figure 3). If the knot is kept inside the
window when it is secured, the weight of the water will severely kink the line as it
comes over the window sill. (photos show hose lowered from a roof, but the
evolution is the same from a window)
Figure 2 Figure 3
2.6.7 After the knot is lowered into place, the rope must be secured inside the window
using a substantial object knot. The location of the substantial object knot will
depend on the length of the rope being used. Any available rope may be used for
this purpose.
6
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
2.6.8 When the rolling hitch is in position, the substantial object knot has been secured,
and the nozzle is attached, the line is ready to be charged (Figure 4). When the
officer calls for water, the ECC should charge the line slowly to minimize
movement in the hose as the water fills the line.
2.6.9 Once the line is charged, there will likely be a significant kink at the window sill.
This can be eliminated by lifting the line to create a bow, effectively “loading” the
line onto the rolling hitch (Figure 5), which is supporting the hose at the first
coupling located outside the window.
Figure 4 Figure 5
2.6.10 The ECC should supply the line with pressures consistent with the street hydraulics
calculations for a standard 2 ½” line stretched. This calculation should include the
lengths to be stretched inside the building from the floor below the fire to reach the
fire area.
3.1 When an engine company loses water in their hoseline while operating, the Engine Officer
should transmit an URGENT message via handie-talkie, as outlined in Communications
Chapter 9. This will alert the entire fireground of the emergency. In addition to this
transmission, the Engine Officer must initiate action to remedy the situation.
3.2 It is important for the engine officer to coordinate with the ECC to identify the problem
and correct it as soon as possible. Once the problem is accurately identified, there may be
corrective action that can be taken that would not require the water supply to the hoseline
to be shut down. Shutting the water supply to the hoseline should be avoided, if possible.
7
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
3.3.1 When a burst length is severe enough to critically reduce the extinguishment
capabilities of the hoseline, it should be treated as a loss of water in the hoseline
and it must be addressed. An URGENT handie talkie transmission must be made
and the hoseline should be withdrawn to a safe location. The Incident Commander
must ensure that all members that may be endangered on the fire floor or floors
above are notified, and when necessary repositioned.
3.3.2 It is important to note that a leak in the hoseline does not necessarily constitute a
burst length. If adequate water flow is still present at the nozzle, it is not a “water
loss” emergency, even if water is leaking from the hoseline. If a significant leak is
found in the hoseline, the engine officer should be notified, but the determination
of a water loss should be made by the engine officer in charge of the hoseline.
3.3.3 The indications of a burst length include water loss at the nozzle, pressure loss in
the lead length, an elevated water flow reading at the pump panel flowmeter (or
standpipe outlet flowmeter) and the apparatus pump RPM increasing automatically.
This indicates that water is leaving the pumper, but not reaching the nozzle. This
diagnosis from the pump panel must be followed up with the confirmation of the
location of the burst length itself.
3.3.4 This problem can be solved by locating and replacing the burst length. To do this,
water to the hoseline will need to be shut down at the pumper (or standpipe outlet)
and a replacement length of the same size hose will be brought to the location of
the burst length. Once water is shut, the burst length is disconnected and replaced
with the new length. Only the engine officer can order the hoseline shut down.
3.3.5 In certain situations, if enough hose is available and it is determined that the
hoseline can safely operate with one less length, the burst length can simply be
removed and the couplings reattached from existing hose lengths.
3.3.6 Once the replacement length of hose is connected, the engine officer in command
of the hoseline must be notified. The engine officer will then call for the line to be
recharged.
3.4.1 If there is a water loss at the nozzle, but no pressure loss in the lead length of hose,
there may be an obstruction at the nozzle itself. In this case, the pump panel will
indicate normal pressure, but no water flow.
3.4.2 To check for an obstruction at the nozzle, the shut-off handle to the nozzle should
be closed and the MST is removed, allowing any obstruction to be removed. Water
may not need to be shut down at the pumper.
8
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
3.4.3 Once the obstruction is removed, reattach the MST and open the nozzle to continue
operations.
3.4.4 If the clog is suspected to be related to ice or slush in the hoseline, a possible
solution may be to rapidly open and close the nozzle repeatedly. This may help
break up the ice or slush in the line.
3.5 Kinks
3.5.1 Kinks are a common problem on the fireground, but they can escalate to an
emergency situation if the kinking is severe enough to critically reduce the
extinguishment capabilities of the hoseline. This would be the case if water flow is
reduced at the nozzle to the degree that the engine officer determines that the
hoseline cannot continue to advance.
3.5.2 If kinks are severe enough to critically reduce the extinguishment capabilities of
the hoseline, they should be treated as a loss of water in the hoseline and they must
be addressed. An URGENT handie talkie transmission must be made. When
deemed necessary, the hoseline may be withdrawn to a safe location. The Incident
Commander must ensure that all members that may be endangered on the fire floor
or floors above are notified, and when necessary repositioned.
3.5.3 In the case of kinking, the pump panel would indicate normal pressure, but there
will be a reduced water flow reading at the pump panel flowmeter (or standpipe
outlet flowmeter). There will also be a decrease in the engine RPM.
3.5.4 The problem can be solved by dispatching members to survey the path of the
hoseline and manually remove any kinks in the line. Kinking should not be
corrected by increasing the pressure in the hoseline.
3.5.5 Once the kinks are removed, full water flow should return to the nozzle. The engine
officer should communicate the return of water to the line.
3.6.1 If a hoseline becomes charged while it is under a door (or similar narrow opening),
water flow and pressure at the nozzle may be completely lost. Additionally, the
hoseline may not be able to advance as it is physically stuck in place under the door.
This is a more serious situation than kinking and is not as easily resolved.
3.6.2 In this situation, the pressure reading at the pump panel will be normal, but there
will be a reduced water flow reading at the pump panel flowmeter (or standpipe
outlet flowmeter).
9
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
3.6.3 Upon the discovery of the charged hose under a door, the engine officer must be
notified and steps must be taken to remove the hose from the pinch point. The
engine officer should transmit an URGENT handie-talkie message and withdraw
the nozzle team to an area of safety.
3.6.4 If a charged hoseline is found under a door and critically reducing the
extinguishment capabilities of the hoseline, this situation should be treated as a loss
of water in the hoseline and must be addressed. An URGENT handie talkie
transmission must be made and the nozzle team should be withdrawn to a safe
location. The Incident Commander must ensure that all members that may be
endangered on the fire floor or floors above are notified, and when necessary
repositioned.
3.6.5 The member that discovered the pinch point must work to remove the hose from
the obstruction. This will likely require a halligan, hydra ram, or other hand tools.
In the case of a hose stuck under a door, the quickest solution may be to remove the
door from the hinge (if the door removal will not adversely impact fire conditions).
3.6.6 If the charged hose cannot be removed from the obstruction, it may become
necessary to momentarily shut the water supply to the hoseline to allow members
to free the hose. Once the water supply is shut, the ECC will need to relieve the
pressure in the line by opening the appropriate drain valve on the apparatus. This
order must be given by the engine officer and would have to be closely coordinated
between the engine officer, ECC, and member removing the hose from the pinch
point. Once removed, the engine officer will order the line recharged as soon as
possible.
3.6.7 If this scenario occurs when a line is stretched from a standpipe outlet, there will
not be an option to relieve the pressure in the hoseline by opening a drain valve on
the apparatus. This is a more serious situation, as there will be no way to relieve the
pressure in the line once it is charged from the standpipe outlet. The obstruction
will need to be removed.
3.7.1 A serious emergency situation would be the failure of the apparatus pump while
supplying a hoseline. This could cause the immediate loss of water in all hoselines
supplied by that apparatus.
3.7.2 If the issue is first noticed at the nozzle, the engine officer would experience a loss
of water and pressure in the line. An URGENT handie-talkie message should be
given indicating the problem.
10
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
3.7.3 If the problem is first noticed by the ECC, they should transmit an URGENT
handie-talkie message for a water loss. Since the problem is with the apparatus and
not the water source, a signal 10-70 should not be transmitted. When a 10-70 is
transmitted, resources are focused on securing a water source for the 1st due
apparatus. In this case, the apparatus itself is not operational, so an URGENT
transmission for water loss is more effective.
3.7.4 Following this transmission, the engine officer should withdraw the nozzle team to
an area of safety and members in the street should provide whatever assistance
necessary to solve the problem. The Incident Commander must ensure that all
members that may be endangered on the fire floor or floors above are notified, and
when necessary repositioned.
3.7.5 If the problem with the apparatus cannot be quickly solved, water supply can be
restored to the hoseline by stretching 2 ½” hose from a nearby apparatus (that is
connected to a hydrant) to the 1st due pumper. The hoseline is then disconnected
from the 1st due apparatus outlet and connected to the new 2 ½” line. The hoseline
can now be supplied by the new pumper.
3.7.6 An alternative solution may be to supply water from a 2nd apparatus to the apparatus
with the failed pump. The pumping operation can then be controlled from the 2nd
pumper, with the original apparatus essentially functioning as a large manifold. In
this scenario, the pressure supply to the original apparatus will be limited to 150
psi, as the relief valve will dispel any additional pressure.
3.8.1 If the PPG of the apparatus fails to operate properly, the ECC may not be able to
supply sufficient pressure to operating hoselines.
3.8.2 As a solution, the ECC may be able to boost available pressure by switching the
apparatus to Pressure Mode by using the apparatus transfer valve. An additional
solution may be to receive a relay from another pumper.
4.1 At a fire operation, there are a number of reasons that a hoseline would not be able to access
the fire area. While such a situation may not require an URGENT transmission, it should
be treated as an emergency and all available resources should be used to facilitate the
advance of the hoseline to the fire area.
4.2 If the hoseline is unable to reach the fire area, the engine officer must clearly communicate
the situation to the IC and ensure all members operating in exposed positions (such as the
floor above) are aware that extinguishment will be delayed. Depending on the situation,
corrective action may be taken.
11
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
4.3.1 If there is not enough hose in the hoseline to reach the fire area, it is called a “short
stretch”. This problem can be prevented by ensuring an accurate estimation of the
amount of hose needed in the stretch to reach the fire area.
4.3.2 The problem of a short stretch can be fixed by adding a length of hose to the stretch.
A length of 1 ¾” hose should be maintained in readiness on all engine apparatus
for this purpose. If 2 ½” hose is needed, a length maintained as a roll-up can be
used.
4.3.3 If the short stretch is recognized after the line is operating inside the fire area, the
line will need to be withdrawn to a safe area in order to add the additional hose.
This may occur when the hoseline cannot reach the fire room itself. In this case, the
IC must be informed when the line is repositioned to a safe area.
4.3.4 The engine officer must decide where to add the additional length to the stretch.
There are two options: the length can either be added to the front of the stretch at
the nozzle, or it can be inserted at any point in the stretch itself.
4.3.5 When adding an extra length in the stretch behind the nozzle, the water supply to
the hoseline will need to be shut. To minimize the amount of time without water,
the extra length should be flaked and ready to be coupled at the desired location
before the engine officer orders the water supply shut to the line. Once the new
length is connected, the officer will order the line recharged.
4.3.6 To avoid shutting the water supply to the hoseline, the length can be added to the
front of the stretch at the nozzle. To do this, the added length (with an additional
nozzle attached) will be brought to the nozzle. With the hoseline remaining
charged, the nozzle is closed and the MST is removed. The added hose is coupled
directly to the shut-off of the nozzle. If the added length is 1 ¾” hose, no additional
fittings are required and it is connected directly to the existing shut-off. If the added
length is 2 ½” hose, an increaser will be needed to make this connection. The added
length will now become the new lead length.
4.3.7 Once the new lead length is flaked out, the original shut-off will be opened and the
lead length will be charged. The shut off must be maintained in an open position,
which can be achieved by securing it with a hose strap. The hose strap is looped
around the hose several feet behind the original shut-off and the clip of the hose
strap is attached to the handle of the shut-off to maintain it in an open position. A
member must also be positioned at the shut-off to ensure the shut-off remains open
and the water supply is not interrupted.
4.3.8 If conditions prevent the new length from being added to the front of the stretch, it
should be added as close to the front of the stretch as possible. This will minimize
the hose that will need to be advanced after the addition of the extra length.
12
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
4.3.9 If six lengths of 1 ¾” hose have already been stretched, it is permissible to add one
extra length of 1 ¾” hose to the stretch in the emergency situation of a short stretch.
4.3.10 If the hoseline is stretched from a standpipe, it may have a lead length of 2” hose.
In this case, the procedure is the same and the 1” MST can be removed to allow the
connection of an additional length. The additional length can be either 2” hose or 2
½” hose, so an increaser will be needed to make the connection. In this emergency
situation, it is permissible to add a 2nd length of 2” hose (with 1” tip) to remedy a
short stretch. It is also permissible to add a length of 2 ½” hose (with 1 1/8” tip) to
a lead length of 2” hose.
4.4.1 When a hose strap is used in a well hole stretch, rope stretch, or fire escape stretch,
it is supporting the weight of the charged hose that is hanging vertically. If the hose
strap fails (either the strap breaks or the securing knot is ineffective), this hanging
hose will begin to fall away from the fire floor.
4.4.2 Such a failure will have the effect of halting the forward progress of the hoseline
and may even pull the operating hoseline out of the fire area. If this happens, the
engine officer must be made aware of the situation and coordinate the restoration
of the hoseline to the proper position.
4.4.3 The problem can be solved through a coordinated effort of members lifting the hose
back to the fire area and properly securing it with another hose strap.
4.5.1 In a situation in which the 1st hoseline cannot gain access to the fire area, the engine
officer must clearly communicate the problem and work to find a solution.
4.5.2 A common obstruction to a fire area can be the door to the fire area itself. If the
door opens inward into the fire area, it can often block access for the hoseline when
the door is chocked in the open position (Figure 6). This is especially difficult if the
open door blocks the entire hallway behind it, as is common in a variety of multiple
dwellings. In these situations, the presence of a hallway behind the door can be
difficult to detect and units may have difficulty finding the fire.
13
FDNY Probationary Firefighters Manual
Chapter 13 ENGINE COMPANY EMERGENCIES
Figure 6
4.5.3 To resolve this, the engine needs to advance a sufficient amount of the charged lead
length into the apartment and stage it in an area opposite the door. Once in position,
the door needs to be closed (at least partially) to allow the engine to advance the
hoseline and access the fire. Once water is on the fire, consideration can be given
to removing the door from its hinges, if it will not negatively impact fire conditions.
This will allow for unimpeded egress from the fire area.
4.5.4 In the case of a more significant obstruction that cannot be removed and hoseline
access will be impossible or severely delayed, the engine officer must notify the IC
and consideration should be given to finding alternative access with a 2nd hoseline.
The 1st hoseline should remain in position to protect operating members and the
building egress, but the operation of the two hoselines must be closely coordinated.
14
Probationary Firefighters Manual
Chapter 14
14
TOOL PAGE
HOOKS 1
AXES…………………………………………………..…………………...…..5
HALLIGAN ………………………………………………………………..……7
POWER SAW 11
CHAIN SAW 31
HURST TOOL 43
T
HOOKS
he duties of a Ladder Company include, but are not limited to, forcible entry, search &
rescue, ventilation, overhauling and laddering. The following is a list of tools carried by
ladder companies to accomplish these duties:
♦ Come in various sizes: 6, 10, 12, 15 or 20 feet. The six foot hook is the most commonly used.
Hooks are used mostly for pulling ceilings and opening walls. They are also used to pull up
sections of roof after an opening has been cut.
♦ There are two different types of hooks:
1. Wooden with a pike end
♦ When carrying hooks, care must be taken to avoid injuring people in front or behind. Hook
should be carried with the hook end straight up, to the rear and close to the body.
1
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
♦ USES:
o Opening Up Concealed Spaces:
• Pulling ceilings:
The ceiling is penetrated with one firm stroke with the hook end parallel to the
lath. This breaks only one lath on the upstroke instead of two or three. The hook
is then turned to form a right angle to the lath and the ceiling is pulled with short,
sharp strokes close to the beam. This method is fast and conserves energy. The
firefighter should not stand directly below the ceiling being pulled. They should
keep the work in front of them. In close quarters firefighters shall keep their
heads down to prevent injury. Eye shields shall be used.
NOTE: WHEN PULLING SHEET ROCK CEILINGS, BE AWARE THEY MAY FALL IN
LARGE HEAVY SECTIONS.
• Opening Walls:
To make a hole high in a sidewall or partition of lath
and plaster:
• This requires a sharp blow with the hook. After
penetration with the hook, the tool is used to pull
down or pry out if leverage is possible.
2
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
• Use the handle of the hook, or the point to make small probing holes to check
for extension or to allow water to flow out as opposed to pulling.
3
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
NOTE: Member lowering a drop ladder should, when possible, stand under the fire escape. This way if the guide
rails are missing or defective, the ladder will fall away from the member.
o Venting Windows:
4
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
AXES
♦ The FDNY uses two types of axes, a flat head and a pike head:
♦ The flat head axe is usually carried by the Forcible Entry Firefighter, married together with
the halligan tool.
♦ The pike head axe might be used the Ladder Company Chauffeur (LCC).
♦ Besides using as a striking tool against the halligan, axes can be used to cut floors or roofs.
o Cutting a floor:
• Cut floor at a 60 degree angle and on a bias as shown.
This is easier than cutting across the grain.
5
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
6
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
HALLIGAN TOOL
♦ One of the most versatile tools of the FDNY arsenal.
♦ Usually carried by the Forcible Entry Firefighter, married together with a flat head axe, or the
Roof & Outside Vent Firefighters.
7
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
RABBIT TOOL
♦ A hydraulically operated forcible entry tool
consisting of a hand pump, high pressure
hose & jaws.
♦ Designed for doors that open inward.
♦ Exerts over 4 tons of force
♦ Weighs 25 lbs.
♦ Has also been successful on sliding
elevator doors.
♦ Not to be use as an auto extrication tool.
♦ The hand pump is designed to be operated
horizontally, but may be used vertically if the
hose is facing down.
HYDRA RAM
8
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
K-TOOL
♦ Used to pull out a lock cylinder on door. It is used
with an axe and halligan. The K-tool is forced
behind the ring & face of the cylinder until the
wedging blades take bite into the cylinder. Light
blows with an axe help this forcing. When the
cylinder is removed, use a key tool in the hole to
move the locking bolt to the open position.
BOLT CUTTERS
♦ Used for cutting bolts, locks, metal
cables, etc.
♦ Should not be used on case hardened
locks.
PORTABLE LIGHTS
♦ Used to provide illumination to facilitate
operations.
♦ There are various types of lights that can be
operated from fixed locations, i.e. on top of
apparatuses & tower ladder buckets and/or by placing
portable lights where needed.
9
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
SHOVELS
Used for overhauling, clearing floors of
plaster, sheetrock, etc.
WIRE CUTTER
A tool with insulated handles and used for
cutting electrical wires. Rubber insulated
gloves must be worn when using wire cutters.
MAUL
The maul (sledge hammer) has many different
uses, e.g. with a halligan for force entry, breaking
concrete covers over gas curb valves, breaching
cinder block walls, etc.
DUCK BILL
Its long, sharp pointed pick may be used for
forcing padlocks.
TORCH
An oxygen and MAPP gas cutting torch.
Used to cut steel & iron
10
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
♦ DESCRIPTION:
o High speed, two cycle engine Control
o Gasoline/oil mixture: 2.6 fluid ounces of oil to one gallon of gasoline Handle
o 20 to 30 minutes operating time
o Special suction wick; allow saw to operate regardless of position, such as upside down,
sideways, etc.
o Three different types of blades:
1. CARBIDE TIP:
Will cut through gravel & tar covered roofs, wood flooring, light sheet metal and
similar material (pictured above). The Carbide blade shall not be used on metal
security doors, auto bodies, metal window bars & case hardened locks, etc.
Dislodged carbide tips can become airborne & cause injuries
Blades are placed out of service when
a. Eight (8) or more tips are broken or missing from the 24-tooth blade.
b. Three (3) or more tips are broken or missing from the 12-tooth blade.
c. Blade is cracked
d. Center hole wears out of round
Will cut various types of steel, including auto bodies, metal security doors, metal
window bars, etc.
Figure 1
11
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
The 12" blade is a diamond brazed saw blade for use on the forcible entry saw. This blade
replaces both types of abrasive disks mentioned above. The blade can cut wood, however it's
not recommended. If the blade is glazed over and cuts ineffectively, run the blade through
an abrasive material such as concrete. This removes build up and exposes more diamonds on
the blade's edge. (Figure 2)
Figure 2
Choke
Decompression
Button
12
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
Place the left foot in the control guard & the right foot back for balance.
o Lift the starter cord a couple of inches. (This is to prevent damage to the recoil
mechanism).
o Pull the starter cord, until you here the motor kick.
Disengage the choke and pull the starter cord again.
Once the saw starts disengage the trigger lock, by squeezing & releasing the throttle
trigger.
NOTE: With the problem of large boots not fitting into the handle, members have the option
of placing their right foot onto the lip of the right side of the handle. If this method is
employed the carrying handle should be held down with the right hand. An
additional option is to insert a tool or a substantial object such as a thick piece of
wood or steel through the handle and step on the same prior to starting the saw.
Regardless of which method is used, the saw handle must be held by hand prior to
starting the saw.
13
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
14
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
• After dropping hand tools on roof the Firefighter shifts body to the right side of the aerial
ladder and lets the saw hang over the outside of the right rail
• The firefighter maintains grip of aerial ladder with the right hand and places the left arm
through the right rail of the aerial ladder and grasps the portable power saw handle in an “arm
lock”.
15
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
• Once the left “arm Lock” has secured the firefighter and the saw the firefighter uses their
hand to release the double action carabineer from the rear of the throttle grip handle of
the saw.
• The firefighter returns their right hand to the portable power saw handle and grasps the
saw sling with the left hand where it is attached to the saw on the blade guard and slowly lowers
the saw to the roof by slowly passing the saw harness through both hands.
16
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
• While using this procedure the firefighter safely maintains contact with the aerial ladder
at all times.
17
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
Note: The Sling Must Be Removed From The Saw Before Starting The Saw.
18
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
o CIRCLE OF DANGER
During cutting operations, everyone in the vicinity of a saw in operation shall
observe, "as near as possible and practical, a 20 foot radius Circle of Danger."
This circle shall be measured in all directions FROM THE POINT WHERE THE
BLADE OF THE SAW IS IN OPERATION.
Only the Officer, the Operator and the member designated as the guide may enter this
circle. All persons directly to the rear of the operating saw blade must be warned
away, as the saw may throw debris 20' feet or more.
The Operator shall not bring a "live saw" (i.e. a saw with engine running) into a
position that puts other members within the Circle of Danger.
19
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
If conditions permit, scrape gravel and debris from the path to be cut, in order to
reduce the danger of injury from flying chips and loose materials.
To prevent accidents caused by moving belts, gears, blades, etc., it is imperative that
Operator and Guide have their clothing completely buttoned up and close fitting.
"GUNNING" the saw while the Operator is either "standing by" or moving to a new
point of operation SHALL NOT BE PERMITTED. Gunning engages the centrifugal
clutch and causes the blade to spin, thus increasing the possibility of injury.
The saw cut should be only as deep as necessary. Deep cuts may weaken supporting
beams and lead to collapse. The experienced Operator will know when a beam is
being cut by the sound and feel of the saw.
Side pressure or twisting of the blade when operating should be avoided. The saw
should never be forced. If too much pressure is applied to the blade, the hazard of
blade breakage (carbide tipped) or blade shattering (aluminum oxide or silicon
carbide discs) is increased.
Always place saw down when changing operators
Avoid using saws from portable ladders
Hold with two hands
The saw shall always be shut down when unattended
20
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
♦ CUTTING OPERATIONS
o CARBIDE TIP BLADES:
Lean forward, squeeze the throttle and bring the blade up to full RPMs before
contacting the surface with the blade. Let the blade lower itself into the material.
Then move backwards, guided by your guide man. Maintain the saw at full RPMs
while cutting.
A slight back and forth motion of the saw will widen the cut & help prevent the
blade from binding.
♦ MAINTENANCE PROCEDURES
o Saw should be checked at the beginning of each tour.
o Weekly, and after every cutting operation, the belt should be adjusted.
o Other maintenance, as needed, include:
Changing the spark plugs
Change the blade
Refueling the tank
Change & adjust the belt
Cleaning the exterior of the saw
Changing the air filter
21
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
COMPONENTS:
♦ AIR CYLINDER
o Steel SCBA cylinder, painted green as not to be confused with breathing air cylinders
♦ BAGS
22
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
♦ PRESSURE REGULATOR
o Piston-type high pressure o Pressure Regulator Knob (sets low
pressure)
o Connected to air cylinder, by
the High Pressure Air Inlet o Knurled Knob Controlling Air
Supply (clockwise to close)
o Two gauges: High (cylinder) &
Low (working) pressures o Air Supply Nipple Connection (used
to supply air to the CVSR and to
o Low pressure gauge – set to 135psi
bleed off air from the regulator)
23
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
ASSEMBLY
♦ SET THE PRESSURE REGULATOR:
24
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
NOTE: When the high pressure gauge falls below 200psi, change the air cylinder.
NOTE: Always open the high pressure air source slowly. Failure to do so may
damage the regulator diaphragm. Make sure all valves are in the closed
position before you turn on your air source. This will reduce the risk of any
uncontrolled lift.
25
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
♦ CONNECTING A BAG
26
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
o Place the bag under the load with the air inlet nipple pointing out. Place the bag as
close to the load as possible to maximize the contact area between the bag and the
load.
NOTE: Always have the bag connected prior to placing it under or between a load
to minimize the operator's exposure to the load area and to eliminate the
possibility of the operator placing the bag with the air inlet under the load.
27
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
o When the gauge reading reaches the vicinity of the red mark, the safety relief will
open (at 118psi) and start venting.
o At this time, close the control lever to conserve the air supply.
o If the desired lift is reached before the bags reaches maximum pressure, simply
close the control lever.
NOTE: Stabilize and shore a load before placing bags into position. Build
shoring in stages as load is being lifted. Always exercise care to avoid
injury in the event of a drop or load shift
o To deflate the bag with the control valve safety relief, close the control levers.
Then, slowly turn the knurled knob on the top of the safety relief counter-
clockwise. The lowering speed must be adjusted by the operator.
NOTE: The bags are designed to inflate and deflate slowly to prevent the load
from being thrown off-center.
28
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
♦ OPERATIONAL GUIDELINES
o Personnel should wear protective clothing.
o Only trained members should be allowed to operate the system.
o Before raising an object, determine the desired height or load movement and
obtain blocks or shoring before the bags are inflated.
o When using an air bag, inflate at a slow rate and maximize the surface contact
area of the bag. This may require either blocking up the bag before inflating or
using two bags, one on top of the other.
If necessary to block up a bag, 3/4" plywood, 3 layers thick, glued and nailed
or screwed together is recommended. Plywood will not split or crack under
loads as it has elasticity.
o The bags should only be inflated half to three quarters of their rated height
capacity. The "pillowing effect" should be avoided. This can cause the load to
shift with possible dangerous results.
o During inflation, stand to one side and clear all personnel from the vicinity. Do
not stand in front of the opening where the bag has been placed, there is a
possibility of the bag being pushed out by the load shifting.
o Never work under a load unless it is blocked or shored. As the load is being
moved or lifted, always block or shore the load. Remember that although a bag
does not need a smooth surface, blocks and shoring do.
29
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
o Avoid inflating bags against sharp objects or on a surface heated to over 220 F. If
necessary, insert a flexible insulated pad (heavy canvas, leather, rubber) or 3/4"
plywood between the hot or sharp surface and the bag, in order to protect the bag.
o Two bags may be used safely from one control valve safety relief device.
Remember that, when stacking, you cannot add together the tonnage of the
two bags to get the total lifting weight. The tonnage of the smaller bag is the
maximum that can be lifted.
The lifting capability is reduced by 50% to obtain maximum lifting height.
Example: a 30 ton bag with a maximum lifting height of 10 inches will lift 30
tons 1 inch, but will lift 15 tons to a height of 10 inches.
Do not operate bags, hoses, valves or regulators that are damaged or
improperly assembled.
It is recommended that the bags be stored in a horizontal position to reduce
stress.
It is important to center the bags on top of each other when stacking them.
Blocking or shoring should be centered as much as possible. Do not place
wood between the bags.
To insure proper inflation of the correct bag (when two bags are stacked)
always refer to the bag by the color of the supply hose; e.g. when you want the
bottom bag inflated, say "raise the yellow bag" when the yellow supply hose
is connected to the bottom bag. This is extremely important when the operator
of the control valve and safety relief cannot see the bags or cannot distinguish
which line is connected to what bag.
Have one firefighter on the far side of the lift to observe any shift or reaction.
The firefighter should be equipped with a handie-talkie.
30
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
CHAIN SAW
1. INTRODUCTION
1.1 Chain saws can save time and energy. They are also extremely dangerous. The safety
and operational procedures of this training bulletin are to be enforced.
2. POLICY
2.1 Except for pier fire operations, the chain saw is not to be used for the ventilation or
overhauling of structural fires.
2.2 The chain saw may be utilized at emergencies or non-structural fires only if the safety
and operational procedures outlined in this bulletin are followed.
2.3 Members are to adhere to AUC 301 "Tree Emergency Operations" while operating at
such incidents.
2.4 While operating the chain saw, the operator and control person shall wear the following
NFPA compliant and FDNY approved protective equipment: Long sleeve work duty
shirt or bunker coat, helmet, eye protection, ear protection, saw protected gloves, bunker
boots, and saw protected chaps.
Bumper
Spikes
Figure 1
31
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
3. GENERAL RULES
Refer to manufacturer’s manual for starting and stopping instructions specific to the
model saw.
3.1.1 Hold saw down on a clear level surface with the bar and chain clear of any
obstructions.
3.1.2 Keep body to the left of the chain. Never straddle the saw or lean across chain.
3.1.3 Hold the front handlebar on top behind the hand guard with left hand.
Figure 2
3.2 Always hold the saw firmly with both hands while the engine is running. Keep your left
hand on the front handlebar and your right hand on the rear handle so that your entire
body is to the left of the cutting line. (Figure 2) Never use a cross-handed grip or any
stance which would place your body and arm across the chain line.
3.3 Proper grip is to be used at all times, fingers encircling the handle with the thumb
wrapped around the opposite side from the fingers. (Figure 3)
32
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
Figure 3
Figure 4A
Figure 4B
33
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
3.6 Properly position yourself for cutting. Hold saw near log and throttle up to full speed
just before allowing chain to touch wood.
3.7 Maintain steady footing while gripping the saw firmly with both hands. When
operating on slopes, the chain saw operator must always stand on the uphill side of
the tree/log when cutting.
3.8 Start cuts with "bumper spike" against the wood and keep it there. Let the chain saw
do the cutting. While firmly holding the saw, use the bumper spike for leverage as
you slowly rock the saw in upward motions. (Figure 1)
3.9 Do not force the chain saw. If you have to force the saw, stop until you find out what
is prohibiting you from cutting. Exert moderate feed pressure to help the chain cut
the wood.
3.10 While cutting downward you will experience a pulling reaction. When the saw
breaks through the wood the pull will cease. Operator must be ready to stop pushing
down on the saw and hold the saw nose up. (Figure 4C)
3.10.1 Pull-in:
A. Pull-in occurs when the chain on the bottom of the bar is
suddenly stopped. The chain on the bottom of the bar stops when it is
pinched, caught or encounters a foreign object in the wood. The
reaction of the chain pulls the saw forward and may cause the operator to
lose control.
B. Pull-in frequently occurs when the bumper spike of the saw is not
held securely against the tree or limb and when the chain is not rotating at
full speed before it contacts the wood.
Warning: Use extreme caution when cutting small size brush and
saplings which may easily catch the chain and pull you off
balance.
C. To avoid pull-in:
1. Always start a cut with the chain rotating at full speed and
the bumper spike in contact with the wood.
2. Pull-in may also be prevented by using wedges to open the kerf.
Note: The kerf refers to the space left behind the cutting blade as it cuts.
34
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
Figure 4C
Figure 4D
While cutting downward you will experience a pulling reaction. During upward cutting a
pushing reaction will be felt.
3.11 When cutting on the underside of a log or limb with the top of the saw blade, the saw will
naturally be pushed out of the cut towards the operator. To compensate for this force, keep
your left arm stiff and maintain constant pressure against log with the saw. (Figure 4D).
3.11.1 Pushback:
A. Pushback occurs when the chain on the top of the bar is suddenly stopped
when it is pinched, caught or encounters a foreign object in the wood. The
reaction of the chain drives the saw straight back toward the operator and
may cause a loss of saw control. Pushback frequently occurs when the top
of the bar is used for cutting.
B. To avoid Pushback:
3. Do not twist the saw when withdrawing the bar from an underbuck
cut because the chain can pinch.
35
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
3.12 Beware of "hidden" pressure points; cut slowly to avoid binding saw in these instances.
Watch the kerf space for any decrease in size; this will warn you prior to binding.
3.13 Do not hit the ground with the blade of the saw, even momentary touching will dull the
chain to some degree.
3.14 When finished using the saw, slowly loosen both, the fuel cap and the oil cap to relieve
the pressure. After refilling, tighten both caps.
4. SAW OPERATION
4.1 Size-up the job before starting and take your time, do not rush.
4.1.1 Check area for power lines, vehicles, trapped victims or possible tree shifting.
4.1.3 Where is the tree/log lying? Is it on a slope? Is it hung up in other trees? Does
the tree need to be secured before cutting?
4.1.5 Do you have adequate tools and enough staffing to complete the job?
4.1.6 Size-up should continue throughout the job as you plan out each move. Always
keep evaluating the scene.
4.2 After receiving instructions, control person and saw operator are to don protective
equipment including eye and hearing protection prior to starting the cutting operation.
4.4 A circle of danger of a radius of at least 10' will be established before the commencement of
cutting. The saw operator and control person will be the only personnel in this area
during cutting. Officer is to monitor conditions and relay orders received from the officer in
command. If possible, the officer is positioned as to permit visual contact with the
control person.
36
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
4.5 The noise level of a chain saw, in conjunction with the hearing protection being worn,
makes voice communication very difficult. Hand signals must be established between
operator, control member and officer.
4.6 The control member should be positioned as to permit easy visual contact with the
operator maintaining a safe distance from the saw. The control member must maintain a
sufficient distance from the member using the saw, to prevent any possible contact with the
saw. The possibility of kickback or movement of the operator must be taken into
consideration. The control member must not remove cutting debris while the operator is
cutting. Anytime the control member approaches the immediate cutting area, the
operator must first apply the chain brake and signal the control member to approach.
When possible, the control member is to maintain a visual contact with the officer.
4.7 Members outside the circle of danger are to be deployed as required. Duties may
include: monitoring incident for changing condition, relief, assist in refueling, pedestrian
and crowd control.
4.8 One of the primary reasons for the establishment of a circle of danger is to reduce the
exposure of members to high noise levels. Long or continuous exposure to noise levels
associated with chain saw operations may cause permanent hearing impairment. Hearing
protection devices must be worn during operational and training sessions by members within
circle of danger.
4.9 Debris from cutting operation should not be removed from work area until saw operator
indicates it is safe to do so. Always clear immediate work area before continuing
operations, eliminating tripping hazards.
4.11 Officer is to rotate personnel to reduce individual exposure to high noise levels and
prevent operator fatigue.
5. OPERATIONAL PRECAUTIONS
5.1 Prior to cutting, examine the area. Note branches or other objects which may spring back to
their normal position when freed. Precautionary measures must be taken to avoid
injury or damage.
5.2 Do not attempt cutting an object which has fallen against a structure and is now
supported by it.
5.3 If a branch, tree section or other object is hanging, leaning or otherwise damaged, members are
to prevent access to the danger area by unauthorized persons. If practical, the object
should be stabilized by lashing or shoring. Cutting it down is not to be attempted.
5.4 Be aware of the consequences of the cut. Cut may cause shifting, rolling or dropping of
object.
37
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
5.5 Prior to cutting operations, members are to survey area for electrical wires in contact with
tree. TREES ARE GOOD CONDUCTORS OF ELECTRICITY.
5.6 Kickback potential of the chain saw is very dangerous. Never make plunge cuts with the
tip of the blade. Never use the tip of the saw blade for cutting. This practice can cause a
violent, uncontrollable kickback. (See figure 5).
Figure 5
5.7 Pinching top of guide bar in a cut could cause recoil of the saw. Saw engine could be
propelled either to or away from the operator. (Figure 6)
5.8 Sand, dirt, cement and metal objects can be found in trees and can dull a sharp chain in
seconds. Check trees for such hazards prior to cutting. A dull chain saw is an extremely
dangerous tool, as it causes the operator to exert excessive force to compensate for slow
cutting.
5.10 Trees knocked over may have their trunks fractured or split. Be cautious when cutting as
they can "jump" when partially cut due to undetectable tension.
Figure 6
38
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
6. SAFETY REQUIREMENTS
6.3 While operating the chain saw, the operator and control person shall wear the following
NFPA compliant and FDNY approved protective equipment: Long sleeve work duty shirt
or bunker coat, helmet, eye protection, ear protection, saw protected gloves, bunker
boots, and saw protected chaps.
6.3.1 Chaps must be worn over either long pants or bunker pants. Chaps shall not be
worn over shorts.
6.3.2 Bunker coat and/or long sleeve shirt shall be worn to protect against flying debris,
insect bites, poison ivy, etc.
Warning: Bunker coat, bunker pants, and firefighting gloves are NOT saw
protected and will NOT prevent the chain saw blade from inflicting severe injury.
6.4 The kickback potential is very real. Members are not to tamper with or remove
manufacturer safety devices.
6.5 Saw is not to be used in situations where the vision of the operator is limited.
6.6 Never attempt cutting a tree which is in contact with live electrical wires. TREES DO
CONDUCT ELECTRICITY.
6.7 Always hold running saw with both hands. Never overreach or operate saw above your
shoulders.
6.9 Rotate saw operators, never permit a fatigued member to operate the saw.
6.10 When transporting, refueling or performing maintenance, the saw must be in the "OFF" position.
6.11 Keep chain of saw away from all parts of body while motor is running.
6.13 Never cut while wearing loose clothing such as torn or hanging bunker coat stripes.
6.14 Use saw protected gloves when operating saw and handling chain.
6.16 Always hold saw with two hands properly positioned when engine is running.
39
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
6.17 Be sure chain stops when throttle is released. If the chain continues to spin at idle place saw
out of service.
6.18 Once cut is started do not slow down and then accelerate, saw may pull you off balance.
6.21 Whenever opening up the fuel tank, always loosen the cap slowly and wait for the tank
pressure to be equalized before removing cap. This will prevent the spurting of fuel.
6.22 Do not rev the saw until you are ready to make the cut.
6.23 Do not walk through unstable areas cluttered with brush, logs, vines or heavy underbrush with
a running chain saw. Carry the saw with the guide bar to the rear when climbing uphill
and to the front when going downhill. Keep the safety brake engaged when traversing uphill,
downhill or on uneven surfaces.
6.24 When the operator is not actively cutting, the safety brake must always be applied.
6.25 Beware of unnatural forces and pressure being exerted on limbs and trunks, especially
when operating with ice storm damage.
6.26 The term “Feathering” refers to increasing and decreasing pressure on the throttle trigger.
This technique should be applied just prior to finishing each cut, this will help the
Operator maintain control of the saw as the chain breaks clean.
6.27 When operating a chain saw, secure or remove your handie-talkie as to avoid the
potential for the radio to swing into the cutting space or become tangled on debris.
40
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
7. MAINTENANCE
7.1 General
7.1.1 Saws are to be examined and tested weekly. Schedule is to be established by the
Company Commander.
• Two persons at all times. A two member team consisting of the saw operator
and control person is required whenever chain saw operations are being
conducted.
41
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
7.2.1 Bar oil levels are to be checked prior to cutting operations and replenished as
required during cutting. The chain saw should never be operated without chain and
blade being oiled. It is unsafe and can cause damage to saw.
If saw is not oiling the bar, first check reservoir for oil and, if necessary, remove the
bar and clean debris from oiling grooves and ports in bar.
7.2.2 Only 2 cycle engine oil, received from Technical Services Division, specifically for
the chain saws is to be mixed with gasoline when making the fuel mixture.
Manufacturer’s directions are to be followed when making mixture.
7.2.3 Bar and fuel oil are to be requisitioned from Technical Services Division using
form 23-BS-2.
7.2.4 Fuel and bar oil levels are to be examined and replenished at the weekly
inspection of the saw.
7.3 Filters
7.3.1 Air filter shall be examined and cleaned after each cutting operation. If replacement is
required, saw will be forwarded to the Technical Services Division.
Clean air filter after each use. Place choke to on position before cleaning. Do not
remove filter until first brushing off sawdust. Remove filter and blow out carburetor
housing and filter being careful not to get any sawdust into carburetor barrel. Replace
filter and cover. Then tighten filter cover housing nut.
7.4 Chain
7.4.1 Chains requiring re-sharpening are to be forwarded with RT-2 to the Technical
Services Division.
7.4.3 To replace the chain or bar assembly on all chain saws, the chain brake has to be
in the off position before removal of side cover. Check that the chain brake is in the
off position by moving the front hand guard towards the front handle. Failure to do
so will prevent you from reinstalling cover and the saw will have to be sent out for
repairs.
42
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
♦ INTRODUCTION
o The Hurst Tool System is a high powered, self-contained, hydraulic spreading and
pulling device carried by all ladder companies, rescue companies and squad companies.
The system consists of a power unit, cutters, spreaders, rams, a hand pump and low
pressure hoses that may be used for vehicle rescue, structural collapse, urban search
and rescue, and industrial rescue. Refer to the specific Operating Instruction Manual for
each tool’s general and technical specifications.
♦ STORAGE
o When storing the Hurst Tool System provide adequate space to prevent damage to
hoses, hose connectors and all components.
o Inspect all mounting brackets and holders in apparatus compartment for damage.
o When storing the Honda Mini Mate Power Unit on the apparatus, the fuel valve lever
MUST be in the OFF POSITION.
43
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
1. TOOL SPECIFICATIONS
2. FEATURES / BENEFITS
2.2 Two tool simultaneous use with no loss of individual tool power.
2.4 Reservoir sight glass for ease in monitoring Hurst fluid level.
3. OPERATION
3.1 To start unit, place pressure / dump valve in the dump (horizontal) position.
3.6 Pull the starter cord. Once the engine starts, gradually move the choke lever to the open
position.
3.7 After connecting tools, place pressure / dump valve in the pressure (vertical) position.
3.8 To shut down unit, place pressure / dump valve in the dump position.
45
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
1. TOOL SPECIFICATIONS
2. FEATURES / BENEFITS
2.1 Star control valve permits tool actuation from almost any gripping position.
2.2 Dead man design control valve reverts back to the neutral position if the user’s hand is
released from the control.
2.3 Hose exit directs the hydraulic hose out of the tool handle and away from the work area.
46
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
1. TOOL SPECIFICATIONS
2. FEATURES / BENEFITS
2.1 Can be used to crush, spread, pull, lift, pinch and pry objects.
2.3 Dead man control valve reverts back to the neutral position if the user’s hand slips
from the control.
47
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
♦ DESCRIPTION
o Material Hot-Stop 1500 L. The Blanket and Ropes have been tested
to 2000 degrees F. The KO Curtain survived 50 mph winds
and 60 minutes of fire exposure.
o Dimensions 8’ x 6’
o Clips Four stainless steel clips at ends of each rope. Clips are
connected to form loops at top and bottom of curtain.
♦ USE
o To cover a fire vented window(s) where the wind is blowing the fire back into the fire
occupancy. With the door to the fire occupancy open, this condition makes it
impossible to advance toward the fire occupancy via the public hallway.
o Once the curtain is in place, the negative effects of the wind on the fire will diminish.
Curtain shall never be deployed in the horizontal position. It is designed and shall
be deployed only in the vertical position.
♦ MAINTENANCE
o The KO Curtain shall be inspected weekly during MUD and after each use. The
inspection will include removing the curtain from the carrying sleeve and unfurling it.
Inspect the deployment ropes, the 5 aluminum bars embedded in the curtain and all
stitching.
If there is any doubt as to the serviceability of the KO Curtain, the officer on duty will
notify Research and Development and be guided by their instructions.
48
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
o If the KO Curtain has been subject to direct flame impingement, it shall be placed OOS
and forwarded to Research and Development for evaluation. A letterhead report to the
Chief of Operations detailing the specifics of the operation shall be included with the
OOS KO Curtain.
♦ REPACKING PROCEDURE
1. Place the curtain on a flat surface with reflective stripes up and ropes unclipped.
2. Ropes are loosely coiled and placed as shown and clipped together. (Figure 1)
3. Curtain is rolled from bottom to top, bottom ropes encapsulated within the roll.
(Figure 2)
4. Top ropes are placed 5-10” from the top edge of curtain, and roll is completed.
5. Curtain is placed into carrying case.
Figure 1
Figure 2
49
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
♦ DEPLOYMENT
Figure 3
50
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
• USE
o To cover a window when the wind is blowing fire back into the fire occupancy. An
open door with wind driven fire indications will make it impractical to advance a
handline down the hallway to the fire occupancy. A 2 ½” handline will not provide
sufficient cooling of the hallway to protect exposed members. Once the Fire Window
Blanket is in place, the negative effects of the wind will be diminished, allowing
members to advance a handline toward the fire area as directed by the Incident
Commander. Testing conducted by the FDNY and NIST (National Institute of
Technology) showed an immediate 50% decrease in temperatures and significant flame
reduction when the Fire Window Blanket is deployed, but there will be an increase in
the smoke condition produced by the fire
o The Fire Window Blanket may be used as pre-deployment option to cover a window
prior to it failing in order to prevent a wind-driven fire.
o Under no circumstances is the Fire Window Blanket to be deployed for drill purposes.
Each Division has been issued Training Fire Window Blankets for drill. Repeated use
of the Fire Window Blanket for drill can cause unnecessary damage.
• MAINTENANCE
o Fire Window Blanket shall be inspected weekly. If the inspection reveals holes, tears or
damage to the straps, the blanket shall be placed out of service. The officer on duty shall
notify R&D. The R&D Unit will conduct an inspection to determine the serviceability
of the Fire Window Blanket.
51
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
Lay blanket on a clean flat surface. (Photo 1) The words “Top” and “Bottom” are
stenciled on the blanket and straps for easy identification
Photo 1
Fold each strap (top and bottom) over itself approximately 18 inches in length. (Photo 2)
Photo 2
52
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
Place tape to secure the top strap, create a handle with tape for easy removal. Only tape top
straps. Never use tape on bottom straps. (Photo 3)
Photo 3
• Place bottom straps along the bottom edge of blanket. Fold the blanket onto itself with the
side edges placed 2” from the center line, leaving a 4” space. The bottom straps must stay
inside of the folded blanket. (Photo 4A, B)
2"
2"
Center line
Photo 4A Photo 4B
53
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
Fold the side edges of the blanket onto itself, again, towards the center line. Leave
approximately a 4” along the center line. (Photo 5A, B)
4"
Photo 5A Photo 5B
Begin to roll the blanket from the bottom towards the top. Do not tuck top straps into the
rolled blanket. (Photo 6)
Photo 6
When completely rolled to the top of the blanket, fold blanket in half. Place the bag over the
blanket, turn bag upright pushing the blanket into the bag, then tuck top straps in the bag.
Securely close the bag. (Photos 7A, B, C)
♦ INTRODUCTION
o This bulletin is intended to explain the basic theory and application of thermal
imaging cameras (TIC). Training Bulletin Tools 27, Data Sheets, will cover the
features of the individual TICs in service in the FDNY.
o The thermal imaging camera is a valuable tool that can be used for many
operations. TICs may be especially helpful in the low visibility environment of
structural firefighting. TICs provide a pictorial representation of temperature differences
that are unaffected by smoke. Basic understandings of thermal imaging, fully
understanding the functions of the TIC in use, combined with disciplined
tactical applications are essential in utilizing this tool to its fullest potential.
o TICs provide a new perspective of the fire ground that can be beneficial. When the
images presented are properly interpreted, operators may utilize the information to assist
in making decisions especially in the instances of firefighting, firefighter accountability
and directing interior operations. The company officer, being empowered to direct, may
be best suited to carry and operate the TIC.
o The following companies are equipped with TICs and shall carry and operate them at
structural fires and applicable emergencies;
• Battalion Vehicles
• Ladder Companies
• Rescue Companies
• Squad Companies
• Haz-Mat Company 1
55
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
o The TIC is a tool and shall be used as an adjunct to, not a replacement for the
established firefighting procedures and practices already in use.
♦ OPERATING THEORY
o TICs detect infrared (IR) energy and electronically process it and display it into a
viewable image.
o Vision in Smoke
• Visible light is blocked by the solid carbon particles in smoke.
• IR wave length is unaffected by smoke.
Example - During interior firefighting operations, vision may be greatly
reduced, however heat penetrates through the smoke within the structure.
o Some TICs in service also associate colors such as RED or ORANGE with specific
temperature ranges. Operators MUST be thoroughly familiar with the specific TIC
they are using as functions vary from camera to camera. Refer to TB Tools 27,
Data Sheets for specific camera function.
o LOW Contrast - May occur in cooler areas where images may be difficult to
view due to the lack of heat present, and all objects being close in temperature.
The overall area being viewed may have little or no contrast and appear
darker.
56
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
o HIGH Contrast - The more heat present, both generated and subsequently
absorbed by objects, the clearer and sharper the image will appear. This is true
until the area being viewed reaches the point of thermal saturation. This occurs
when everything in the viewing area is heated to temperatures beyond the
capabilities of the TIC being used. The overall area being viewed will loose all
contrast and appear whiter and featureless.
o Convected Heat: When using a TIC, convected heat movement may appear as
WHITE swirling waves or smoke. Because heat rises, most often it will appear
when viewing the ceiling area. However it may also appear from the floor area
when entering or operating above the fire. When searching for fire location or
extension, operators should make every attempt to detect the presence of convected
heat along with its direction and velocity earlier rather than later. This movement
may give the operator an indication of the location of the fire.
o When operating a TIC, it must be understood that the ability to thermally image is
dependant on the amount of energy being absorbed by objects or generated by fire
or a heat source. The object or heat source in question may be concealed by
thickness or layering of materials preventing them from being viewed with the TIC.
Example -When searching for fire, walls or multiple layers and thickness of
materials such as drop ceilings and insulation, may conceal fire. When searching
for life, it must be understood that furniture or layers of blankets, sheets and clothes
may conceal a person.
57
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
♦ TACTICAL APPLICATIONS
Thermal imaging cameras shall be carried and used at all structural fire
operations by all units equipped with this tool.
In order to allow the operator to function safely by having both hands available to
perform search, rescue and firefighting functions, operators of thermal imaging cameras
shall utilize the carrying strap and ensure that it properly interfaces with their Personal
Protective Equipment. Proper application of the TIC may be invaluable in most
situations including but not limited to:
o Initial Size-Up
• Occupants at open windows who are obscured by smoke
• Fire location
• Fire extension
o Structural Fires
• Residential - Private and Multiple Dwellings
• Commercial - Stores, Warehouses, Schools, Theaters, etc.
• Hi Rise - Residential and Commercial
• Vacant - All types
Operators of TICs should remember to stay low and slowly scan the area.
Operators should begin at the ceiling and use a side-to-side scanning motion,
slowly working their way to the floor area. This will compensate for the narrow
field of view of the TIC.
Objectives:
C) Structural Considerations
• Construction features and hazards
58
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
• Avenues of extension
o Roof Operations
• Firefighter accountability while operating
• Ventilation – Location
• Extension
• Navigation & Safety
o Overhaul Operations
• Location
• Extension
o Emergencies
• Electrical
Overheated:
a) Motors
b) Circuits
c) Ballast
• Exterior Search Operations
a) Person in water (surface)
b) Person in woods
c) Victim thrown from vehicle
59
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
o HAZ-MAT
• Spilled liquids
• Some vapor clouds
• Liquid levels in containers
♦ LIMITATIONS
o Thermal imaging does not see through clear glass or plastic. These act as a
mirror to IR.
o Shinny surfaces will reflect IR creating a mirror effect. The actual source of the
image may be opposite the reflected surface. Example - Glass, waxed floors,
tiled walls, some painted or polished surfaces or water on the floor.
o Focal point of a TIC is approximately 3 feet from the camera lens. Operators
viewing objects within 3 feet are too close. As a result objects within 3 feet
may be blurry, out of focus or featureless. To help prevent this, operators
should scan an area before entering or advancing.
o Depth perception in TICs is rarely represented in a 1:1 ratio and may vary from
camera to camera. Specific camera familiarization is essential.
o Steam and condensation or fogging on the SCBA facepiece, display screen and
camera lens may distort the clarity of the image that is displayed and cause it to
be featureless. If there is fogging or condensation build up on the SCBA
facepiece, it probably exists on the camera lens and display also. Wiping
all 3 places, SCBA facepiece, the display screen and camera lens, will greatly
improve the clarity of the image. This may have to be done repeatedly
before image clarity is improved.
60
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
o Functional Check shall include the following in accordance with the associated
TB Tools 27 Data Sheet:
• Turn the camera ON
• Check for proper warm up and electronic self-test.
• Verify that the camera is functioning properly by placing the TIC close
to your face and viewing your outstretched hand or another firefighter.
• Verify POWER/BATTERY LEVEL
• Verify proper function of all buttons and switches.
• Verify that all LEDs and ICONS are properly displayed and functioning.
o Maintenance
61
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
o Repair/Replacement
• The TIC does not meet the inspection as described or does not operate
properly.
• Battery chargers or other components are defective.
• Battery operational/charging time is not consistent with TB TOOLS 27
62
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
Figure 1
2. OPERATIONAL USE
2.1 The Drager PAC 6500 CO Meter is always to remain on. The on/off function has been disabled.
There are two buttons on the meter; units are only required to use the green (OK) button to silence
the alarm.
2.2 Fire Officers and Firefighters assigned riding positions that have a CO meter are required to wear the
meter whenever they are out of quarters (emergency and non-emergency operations). The CO meter
shall be affixed to the handie-talkie strap above the remote mic.
2.3 Alarm threshold 1, (A1) is activated at 35 ppm. Alarm threshold 1, (A1) can be acknowledged and
silenced by pressing the OK button.
2.4 When the concentration of CO in the atmosphere is 35 PPM or greater, the meter will signal the
following alarm:
When the CO concentration falls below 35 PPM, the alarm will automatically turn off.
63
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
Press to
acknowledge
and silence
alarm
Figure 2 Figure 3
2.5 Alarm threshold 2 (A2) is activated at 100 PPM. Alarm threshold 2 (A2) cannot be
acknowledged or be silenced.
2.6 When the concentration of CO in the atmosphere is 100 PPM or greater the meter will signal the
following alarm:
• a fast modulating tone (every ½ second)
• with fast flashing red lights (every ½ second)
• a fast vibration (every ½ second)
The display will alternate between A2 and the measured amount of CO in ppm.
See Figures 4 and 5.
When the CO concentration falls below 100 PPM, the meter will go into Alarm threshold 1,
(A1), and the alarm can be silenced, see Section 2.3.
2.7 The Drager CO Meter will retain the highest reading the meter has been subjected to. Due to the
CO Meter remaining constantly on, this peak reading is not to be relied on or used during any
operation or incident.
Figure 4 Figure 5
64
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
NOTE:
CO meters will display readings up
to 2000 PPM (Figure 6). When
readings exceed 2000 PPM, the CO
meter will display “rrr” (Figure 7),
indicating concentration too high to
measure.
Figure 6 Figure 7
3. MAINTENANCE
3.2 Calibration will only be done by Haz Mat Operations Meter Room every 6 months on a
scheduled basis. An error message (notification) will appear on the screen 2 days prior to
the required 180 day calibration cycle.
3.3 Field units are not to perform any maintenance on, or open the device (opening the device
will void the manufacturer’s warranty). The CO meter will always remain on.
3.4 Battery life is dependent on use, alarm activations and temperatures. The lithium ion
battery has a maximum life of two years under ideal conditions (on 24/7 but no alarm
activations). There are two low battery alarms.
• Pre-Alarm - A battery “pre-alarm” activates when there is 5% battery life left. The
battery icon will flash, and a visual and audio warning is given similar to the A1
alarm without the vibration. The battery pre-alarm can be acknowledged
and silenced by pressing the green OK button. However, there is limited battery life
left, between 1 day and two weeks. The Officer on duty must contact the Meter
Room at Haz-Mat Operations for a replacement.
• Main Alarm - A battery main alarm will display a rapid visual, audio and
vibration alarm. This alarm cannot be acknowledged, and the meter will
countdown from 10 to zero and shut down. The meter will be unusable and must
be placed OOS. The Officer on duty must contact the Meter Room at Haz Mat
Operations for a replacement.
3.5 When marking meter with company ID, do not etch or use marker (sticker/tape is
acceptable).
65
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
4. Radio Signal 10-38
Radio Signal 10-38 shall be transmitted for any type of Carbon Monoxide Response.
66
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
1. INTRODUCTION
1.1 The Radalert™ 50 radiological monitor has been issued to all Engine and
Ladder companies, Rescues, Squads, HMC1, Haz Tac, Battalion and Division Chiefs
throughout the city to protect FDNY members from the hazards of a radiological
release.
2. OPERATIONAL PROCEDURES
2.1 When units leave quarters, they shall turn on their Radalert™ 50 monitor for the
purpose of constant monitoring for radiation hazards. The following procedures shall
be adhered to:
2. Turn on monitor using OFF/ON/AUDIO switch. The switch should be in the AUDIO
position for proper operation.
3. Ensure mode switch is in the mR/Hr position.
4. On the top of the monitor next to the alpha window, depress the alert Set button once.
The LCD display should read current alarm level for the alert mode. This reading
should be 1.000 mR/Hr. This alarm level should only be altered under the supervision
of an officer from the hazardous materials group.
5. Depress the Set button again and the monitor will be in the alert mode. Also, you will
see a radiation-warning icon appear on the LCD when the unit is in alert mode.
2.2 After the unit has been turned on for one minute, the hourglass icon will disappear,
and the unit is now ready for use. The continuous screen readings will reflect normal
background radiation. Background radiation will vary, maintaining normal levels
between .02 and .05 millirems per hour (mR/Hr).
2.3 When moving toward the suspected area of contamination, move slowly to allow
the monitor to detect any abnormal amounts of radiological activity.
NOTE: The unit takes a full minute for a change to be indicated on the LCD
display, therefore progress slowly. As a safety factor, if the rate at any time goes
over 1 mR/Hr, the monitor will immediately sound the alert tone.
67
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
2.5 All reports (positive and negative) should be communicated to the Incident
Commander or Haz-Mat Group Supervisor. Any area that causes the Radalert™ 50
to alarm requires confirmation by a second unit. Perform the Initial Event Status
Assessment and determine if the situation is a Radiological Incident or a
Radiological Emergency
2.6 The Radalert™ 50 alarms at 1.000mR/Hr, indicating an area that has radiation
above normal background. A circular pattern should then be used around the
object or area to determine the size of the isolation zone as scene size-up continues.
The Fire Department of New York uses 1 mR/Hr as an action level. The Hotline
(defining the Hot Zone) should be established at a rate of 2 mR/Hr, and
marked with the red “hazardous materials” barrier tape supplied by Tech Services.
Access to this area is restricted to first responders conducting life saving operations
and protection of life and major property. In those incidents with obvious or known
viable victims, the officer in charge must carefully weigh the risk (level of radiation
in the area and the time members would be in the zone to complete the rescue)
versus the benefit (saving a known viable victim), before committing personnel.
3.1 Using the Radalert™ 50, all units will monitor the area in front of quarters for 5
minutes at each of the times on the designated day and determine the background rate
for each. This information will be recorded on the RAD-3 report, titled "Radiation
Background Monitoring Chart." Any unusual or elevated background readings
(>.05mR/Hr but <.9mR/Hr) shall require the officer on duty to
forward a copy of RAD-2, titled “Elevated Background Radiation Readings
Above 0.05mR/Hr to Haz-Mat Operations.
3.2 A copy of this data chart must be forwarded to their respective Battalions
for consolidation and forwarding to the Division. The Division shall collate their
Battalion reports, highlighting any elevated readings, and forward a report to their
Borough for forwarding to the Bureau of Fire Operations.
NOTE:
Normal background readings for some areas may be several times higher than others.
68
FDNY Probationary Firefighters Manual
Chapter Fourteen LADDER COMPANY TOOLS
4. MAINTENANCE
4.1 Maintenance of the Radalert™ 50 requires that the 9-volt alkaline battery be
changed every 3 months. The 9-volt alkaline battery shall be changed on Jan. 1,
April 1, July 1, and Oct. 1 of each year.
4.3 Companies shall use the firehouse expense fund to purchase replacement 9-volt
alkaline batteries.
69
Probationary Firefighters Manual
Chapter 15
PORTABLE LADDERS
15
PART ONE
SECTI ON T I TLE PAGE
Glossary ........................................................................................ i
10.3.2 Ventilation............................................................. 18
12 Safety ............................................................................................ 21
GLOSSARY
Beam The solid or trussed main structural side member of a ladder,
supporting the rungs.
Bed ladder/Bed The lower section of an extension ladder into which the upper section
section retracts.
Butt plates / Cleats / The steel spikes mounted on the butts to provide a more secure base
Spikes / Spurs / for the ladder on hard surfaces such as concrete. They also serve as a
Shoes protection against excessive wear on the ends of ladders.
Combination ladder A versatile ladder that can serve as a straight ladder or be converted to
an "A" type ladder: i.e., Metal Duo-Safety "A" Ladder and Little Giant
Ladders.
Extension ladder A ladder with two sections that can be nested for ease of handling and
extended to provide the needed height.
Folding ladder A ladder designed for use in inaccessible areas where ordinary ladders
will not fit: the rungs fold completely into the beams when fully
closed.
Guides/channels Light wood strips or metal channels which guide the fly ladder while it
is being raised.
Gusset plate A flat metal plate used in truss constructed ladders, which connects the
rails of the beams and supports the rungs.
Ladder locks A locking mechanism that secures an extension ladder in the desired
extended position by engaging the beams of the fly ladder to the rungs
of the bed ladder. Also called dogs or pawls.
i
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
Latching device A device used on combination ladders to lock the ladder in position.
Consists of hinges/pins.
Rails The two lengthwise members of a trussed ladder beam, which are
connected by the gusset plates.
Rungs The cross members between the beams of the ladder, used as footrests
in climbing.
Safety shoe A swivel type butt plate consisting of rubber tread and a spike. It may
be used with either the rubber or the spiked end on the ground.
Solid beam ladder A ladder with beams of solid construction (see trussed ladder).
Stops A limiting device on extension ladders to prevent fly ladder from over-
extending out of the bed ladder.
Telescoping Ladder A compact, lightweight ladder with multiple segmented beams that nest or
"telescope" inside of each other.
Tip or top The upper end of a ladder.
Trussed ladder A ladder with beams of open construction consisting of rails and
gusset plates.
ii 1/19/2121
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
1. Deleted.
20' 55 lbs.
20'(Hook) 60 lbs.
12'(Hook) 35 lbs.
Note: All weights, and the closed lengths of the extension ladders, are approximate, due
to variation between manufacturers. Refer to Figure 1 for the various parts of a metal
extension ladder.
1 1/19/2121
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
2
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
3.1 Aluminum ladders are divided into two basic types of construction, viz: solid beam and
truss.
3.1.1 Solid Beam Aluminum Construction - This type of ladder has a solid side rail
construction with aluminum rungs connecting with the side rails at fourteen inch
intervals. The connection is generally either by a welded joint between rung and
side rails, or by an expansion plug pinching the rung tightly to the side rails and
internal backup plates. (Figure 2 A)
3.1.2 Aluminum Truss Construction - In the aluminum truss design, the top and
bottom rails are connected to rung assemblies or rung blocks by rivets. The rungs
are either welded or expansion plugged to the rung plate assemblies, which are
supported by the top and bottom rails. (Figure 2B)
A. This construction allows greater side beam heights for greater carrying
capacities without requiring massive solid beams that add to the overall
weight of the ladder.
3.2 The base of the portable aluminum ladder is provided with either steel spikes or swiveling
rubber safety shoes and aluminum spikes. For ladders equipped with the swiveling
device, the rubber pads should be utilized when the ladder is to be raised and used on
hard surfaces. (Figure 2A, 2B)
Solid Beam Construction with Swivel Truss Construction with Steel Spikes
Safety Shoes and Aluminum Spikes
3
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
4.1 Aluminum ladders are generally lighter in weight and stronger than comparable wood
ladders.
4.2 They are made of a high tensile, heat treated aluminum alloy and can sustain daily wear
and tear very well. The aluminum will not weaken with age. It has a long life
expectancy.
4.3 Aluminum ladders in general are tough. They will dent but will not chip or crack when
subjected to severe impact nor will they fail suddenly because of overloads. They will
bend but not break, as wood does.
4.4 No protective finish is required on aluminum ladders, as they will not dry out and
weather with age or sunlight exposure. A slow oxidizing of the surface occurs but it can
be polished off.
5.1 Aluminum ladders readily conduct electricity. Refer to Sections 12.1.16 and 12.2.3A.
5.3 If an aluminum ladder has been subjected to excessive heat exposure at a fire, even for
a brief period, it may have lost its heat treatment. This may affect its load carrying
capacity, even though the metal shows no signs of any change. A discoloration may
indicate a loss of structural strength. In either of the above cases, the Fire Tools and
Equipment Unit shall be notified.
6.1 The numerical length of a ladder shall be marked on the side of the rails within 12
inches of the end of the ladder.
6.1.1 Straight ladders - The ladder length shall be marked on each end of each rail.
6.1.2 Extension ladders - The ladder length shall be marked at the butt end only of
each rail of the bed ladder.
6.1.3 Ladder length markings shall be visible when ladders are stored on the
apparatus.
6.2 The unit designation shall be marked within 18 inches of each butt end as outlined in
Sections 6.1.1 and 6.1.2 for numerical ladder length markings.
4
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
Figure 3
7.1 Avoiding Obstructions to the Removal of Portable Ladders from Ladder Company
Apparatus.
7.1.1 20 foot straight and/or 35 foot extension ladders are carried in the internal slide-in
racks on many ladder company apparatus. If another apparatus arriving at a fire or
emergency is positioned closer than 20 feet to the rear of the ladder apparatus, the
20 foot straight or the 35 foot extension ladder cannot be removed from these
racks due to insufficient clearance.
7.2 The advantage of an extension ladder is that its height can be adjusted for safe and
accurate positioning. Choosing the precise ladder length is not as critical when using an
extension ladder as it is when using a straight ladder which has a fixed length.
7.3 Ladder Climbing Angle - Climbing angle for a ground ladder is approximately 65-75
degrees.
7.3.1 The 65-75 degree angle allows the ladder to provide its maximum strength and
best service.
7.3.2 An angle steeper than 75 degrees increases the chances of the climber falling off
and sustaining injuries.
7.3.3 Ladders angled less than 65 degrees require a reduction in maximum loading.
(See Section 8.4)
5
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
7.4 A simple formula used to obtain a 75 degree angle is to place the base of the ladder at a
distance from the vertical plane equal to 1/4 the total working length of the ladder. The
working length is the distance from the base of the ladder to the top of its support. (Fig.
4, 5)
Figure 4
Figure 5
6
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
7.5 Ladder Placement - Proper placement of the tip of the portable ladder provides for easier
and safer mounting and dismounting of the ladder and it allows the user to maintain his
balance by providing a handhold.
7.6.1 In order to prevent slippage of the butt, or movement of the top, of a raised portable
ladder, it is important that it be butted by a member. In any case for fire, emergency
or rescue work, a butt man shall be used to stabilize the ladder and prevent slipping.
A. The butt firefighter places his left foot in the center of the bottom rung of
the ladder and maintains a downward pressure. The members right foot is
positioned behind him at a comfortable distance to maintain balance and
provide resistance against ladder movement.
B. The butt firefighter places both hands are placed against and grasp the
ladder beams to aid in steadying the ladder.
C. If a member is working off one side of the ladder, the butt firefighter moves
his/her foot from the center of the bottom rung of the ladder to the side
opposite the one from which the member is working, and places his/her foot
next to the beam. This will prevent the bottom of the beam from shifting
due to the relocated weight of the member working on the ladder.
7.6.2 The butt firefighter must be aware of the force that causes the outward slippage of
the butt of the ladder. This force is in direct proportion to the climbing member's
weight, increases as he ascends the ladder, and is maximum at the top of the ladder.
Because of this, extra care must be exercised when a member receives a victim at
the top of the ladder.
7.6.3 The aluminum portable ladder, if it is to be left unattended, should be secured at the
tip by the first member that climbs the ladder. This is to prevent the ladder from
being dislodged from its position by the wind or by the impact of water from a hose
line or a large caliber stream.
7
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
8.1 When the portable ladder has been raised and placed in position, one member butts the ladder
as outlined in Section 7.6.1. The assigned member climbs the ladder in the following manner:
8.1.1 Climb on the balls of the feet near the arch, left and right of the center line up and down
the ladder.
8.1.2 The underside of the beams are grasped with the hands.
8.1.5 If a tool is carried, it should be balanced in the carrying hand, which holds onto the side
of the beam. The free hand continues to grasp the underside of the beam.
Do not carry the tool close to the body or inside the ladder over the rungs because of the
danger to the butt firefighter below should the tool be accidentally dropped
8.1.6 During freezing weather when ice forms on the ladder due to water spray, to ensure safe
ascending and descending:
A. Position the rung of the ladder under the arch of the boot, next to the heel.
B. Position the feet on the rungs directly next to the beams with each step, to avoid
slipping.
C. The hands remain on the underside of the beams. Should a member slip while climbing,
they should immediately pull themselves into the ladder and regain their footing.
8.1.7 Whenever a member operates on a ladder of any kind, they must have enough hand
control to ensure his/her safety. This is an absolute necessity when on vertical ladders,
such as fire escape drop ladders and gooseneck ladders to the roof. Greater physical
effort is needed when using a completely vertical ladder, because a missed step or a slip
of the hand will result in a vertical drop and a serious injury. A similar mishap on a
ladder which is angled into an objective could result in the member falling toward the
ladder other than straight down.
8.2 Duties that require the member to work from the ladder necessitate the use of a leg lock or the
life belt for safety.
A. The leg performing the locking maneuver is opposite the working side. For example, if
the member wants to lean to the right and vent a window, he will lock their left leg on
the ladder.
8
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
Figure 6
• The snap hook of the personal harness hooks directly to the ladder rung.
8.3.1 The mechanical ladder lock assemblies on the extension ladders are positive action
automatic spring loaded locks. If in good condition, they will work and lock in either
the fly out or the fly in position. The advantage of the fly out position is that the fly
ladder tends to tighten its hold on the bed ladder, when it is extended at the proper
climbing angle. For this reason and for standardization, the FDNY has adopted the fly
up position for the placement of extension ladders (See Part Two).
A. The first member ascending the ladder should always check the ladder lock
assemblies to ensure that they are completely engaged on the rung.
8.4.1 The maximum load capacity imposed on a ladder includes the weight of the victims,
members and their equipment, and any other weight such as a hose line. The ladder must
be positioned correctly as outlined in Section 7.4.
9
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
B. Roof, straight and extension ladders (26' or less) - up to 500 pounds load.
8.5.1 Due to the nature of the construction of telescoping ladders, the must NOT be:
Photo 1
9.1 Portable ladders may be used in many ways and with different tools to perform a variety
of functions at fires and emergencies. The most innovative uses of ladders have resulted
from quick responses to unusual situations.
10 1/19/2021
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
9.2.1 Used to Bridge a Fence - At times it's necessary to gain access to a particular area
surrounded by a high fence with no immediately available entry way. If the
situation does not require cutting the fence, entrance may be gained by using two
short portable ladders, e.g., a 16' extension ladder and a 12' hook ladder, and a short
length of rope or hose strap. (Figure 7)
A. One short ladder is placed against the fence at the proper climbing angle and
butted by a member.
B. One member ascends the ladder to the point where the top of the fence is at
about waist level.
C. The butt end of the second ladder is passed to the member on the first
ladder. He/she then places one beam on top of the fence. The second ladder
is slid out a sufficient distance, pivoted downward from the fence top, and
lowered to the ground.
E. The adjacent beams of the two ladders are tied together securely where they
intersect, to prevent ladder movement during use.
Figure 7
11
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
9.2.3 Deleted
9.2.4 Used to support opened overhead doors and in other instances where it is
necessary to supply support.
10.2 Buildings Requiring the Use of Portable Ladders - In the following examples it will be
assumed that a fire of moderate to severe intensity exists somewhere within the building.
When the fire is in the cellar, 1st floor, and/or 2nd floor, raise the portable
ladders adjacent to and above the fire area even if the aerial ladder will be
required on the upper floors. A severe fire may render the interior stairs
untenable and portable ladders will be required, even if the need is not
obvious from the street.
12
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
1. Fire escapes often become overcrowded when there is a fire anywhere within the
building. Under these conditions, a portable ladder should be raised to the first
balcony at a point opposite the drop ladder. If more relief for the fire escape is
required, another portable ladder should be raised to the second balcony.
2. If panic conditions reign on the fire escape, attempt to keep the ladders out of
reach of the people while raising and positioning them . If a panic stricken victim
interferes with the ladder raising procedure, members may lose control of the
ladder and it may fall and cause injury .
b. If time and conditions permit, lash the ladders to the fire escape for safety.
3. When the overcrowding conditions have been alleviated use the portable ladders
for other duties if necessary.
Figure 8
8A 8B 8C
13
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
Figure 9
C. Tenements and multiple dwellings with fire escapes on the rear of the building.
1. Overcrowding on the fire escape in the rear may be relieved by members assisting
occupants to the roof via the gooseneck ladder. (Figure 10)
2. In the event of a fire in a building constructed with "party wall balcony fire
escapes" where the fire has spread to the adjoining building, thereby eliminating it
as a second means of egress, occupants maybe trapped on the fire escapes.(Figure
11)
a. Portable ladders must, if possible, be taken through the 1st floor public
hall, apartments or store to the rear yard to effect rescue.
b. Because of its portability the 12' hook ladder may be used to gain access to
the various balcony levels by the roof firefighter or OVM for search and
rescue procedures. The ladder may be brought to the rear yard as in a)
above, or brought to the roof via the Aerial, Tower Ladder or utility rope
and lowered to the top balcony.
14
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
A. Brownstone buildings are usually either 4 story (3 stories above a basement and a
cellar) or 3 story (2 stories above basement and cellar)-the basement level is
counted as a story. Most brownstones are similar in their construction. However,
their type of occupancy varies. Although originally designed as 1 or 2 family
private dwellings, they often are used as public or commercial buildings, multiple
dwellings (3 or more families), and as Class ‘B’ rooming houses.
B A serious life hazard is present in brownstone buildings due to the absence of fire
escapes on many of the buildings, the number of occupants (often transients)
resulting from single room occupancy, and the building's combustible
construction. Ventilation, isolation, entry and search (VEIS) on the fire floor and
above the fire may require the use of portable ladders. All horizontal ventilation
tactics whether Ventilation for Extinguishment or Ventilation for Search, require
communication with, and coordination by, the Ladder Company Officer operating
inside the fire area to be vented.
Figure 10
15
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
Figure 11
1. Placing a portable ladder at the window of the small room over the front entrance
door will be difficult because of the long, high stoop, which may interfere with
firefighting operations. Consider placing the ladder at the adjoining window to
gain entrance to this small room. (Figure 12)
a. There generally are 2 doors to the small room, one from the large
adjoining bedroom and one in the hallway.
b. If there is no door in the small room from the large bedroom, and hallway
fire conditions prevent normal entry into the small room, access may be
gained by breaking through the lath and plaster partition between the two
rooms.
3. Some brownstones have small elevated or depressed courts in the front of the
building adjacent to the stoop. They generally have a small wall of iron railing
around them. These present additional obstacles to overcome when maneuvering
and placing portable ladders.
16
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
Figure 12
1. The rear of the brownstone presents a severe life hazard if there is no fire escape.
Portable ladders transported to the rear of the building and properly positioned are safer
than a life saving rope rescue. They require less Staffing and effort.
a. Due to operations in the fire building, to barred windows at the basement level,
and to floor layout, movement of portable ladders to the rear may be difficult and
time consuming.
b. In most cases, taking the ladder through the second floor (parlor floor) of an
adjoining brownstone, passing it out the rear window to another member in the
yard below, is faster than using the fire building.
In a row frame, transporting a ladder through the interior of the building to the
rear is generally less complicated because there are front and rear doors or
window entries at ground level.
Note: In a Brownstone, it is important to take the ladder through with the butt facing
rear of building. In a row frame, transporting a ladder through the interior of the
building to the rear is generally less complicated because there are front and rear
doors or window entries at ground level.
c. Fences constructed between the properties in the rear yard may be an obstacle for
rapid ladder placement.
17
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
2. Most often, all floors in the rear of a brownstone can be reached with portable extension
ladders. It is recommended that extension ladders be used in lieu of straight ladders
because:
a. They are easier to transport because of the shorter nested length.
b. The ladder height can be adjusted.
c. One ladder may serve several floors.
d. Generally, floor and ladder working length are:
1) 4th floor - 35' extension ladder.
2) 3rd floor - 24' or 35' extension ladder.
3) 2nd floor - 24' extension ladder, or 14' "A" Frame ladder.
A. Forcible Entry - Straight ladders have been successfully used to force entry into
stores and other occupancies having wood frame inward opening doors. This
method will provide a margin of safety where conventional methods of forcible
entry would place members in a hazardous position, e.g., when, working in return
show window area of plate glass panels, heat or flame prevents close approach, or
where the possibility of back draft exists.
2. Place the butt of the ladder on the Lexan window in the corner adjacent to
the window frame.
3. Three or four members apply a gradual leaning pressure against the window
until it is forced inward.
18
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
2. The tip of the ladder, if possible, should be level with, or higher than the
top of the window.
1. The member using a portable ladder to ventilate a window must wear full
firefighting clothing, eye shield down, and boots pulled up. This will help
prevent injury if he is struck by failing glass.
2. The ladder should be positioned so that it will break the desired window
glass area when dropped against the window.
3. When the ladder strikes the glass, there should be no contact between the
member and the ladder. The reason for this is that there is a great
probability that the window glass will slide down the ladder beams. By the
member maintaining a ‘no contact’ position, he reduces the chances of
personal injury. Care should also be taken to ensure that no other personnel
are in the ‘danger area’.
4. As soon as the glass sections have fallen or are clear of the ladder, the
member must stabilize the ladder to prevent its falling to the ground.
10.3.2 Hook ladders, in addition to their use as conventional straight ladders, may be
used on sloping roofs, to gain access to piers or bulkheads, or any other
application where a hanging ladder may be required. To prevent slipping on
peaked roofs, set hooks into roof by pulling down on ladder.
10.3.3 Portable ladders may be placed over weakened, damaged or burnt-out stairs in
order to safely gain access to upper stories of a building. The preferred ladder for
this is the 24’ extension ladder rather than a straight ladder. The shorter nested
length allows easier maneuverability and positioning, while the adjustable length
should ensure proper coverage of the entire stair span. The butts shall be
supported by the floor at the base of the stairs, while both the upper beams at the
tip of the ladder should rest at the upper floor landing for proper support.
19
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
10.3.4 Portable ladders may be used to gain access to a higher or lower roof level from
an adjoining roof
10.3.5 When portable ladders are placed over holes in a floor or roof or over a shaft
opening, they aid in preventing members from falling into these unprotected
openings. Other objects placed on top of the ladder will identify the hazard and
can provide additional coverage over the opening.
10.3.6 Portable ladders used in bridging operations can span courts, alleys, shafts and
similar openings between floors and roofs. Extension ladders must be used only in
the nested position when bridging.
10.3.7 Short ladders are used to support a bent cellar pipe during its operation, from
exterior cellar stair or below grade openings. The ladders can also be placed
across trench cuts, holes in a floor, or other openings to facilitate distributor use in
cocklofts, cellars or wherever they are required.
10.3.8 In order to prevent electrically operated overhead doors from closing when power
in the fire building is shut down or affected by fire, a short ladder may be used to
chock the door in the open position.
10.3.9 All Unit Circular 200 states that, during winter months when snow conditions
prevent or restrict approach of the apparatus close to the fire area, in transporting
heavy equipment and rolled or folded hose, the ladder as a sleigh should be
considered. The ladder should be covered lengthwise with a tarpaulin, wide
boards or other materials to help support the hose or other equipment and prevent
it failing through the ladder, dragging in the snow, or being lost.
10.3.10 When a ladder has been positioned and used by a member to gain entry to a fire
building, there is the possibility that he/she will also need it as a means of retreat.
He/she expects the ladder to be there. Therefore, do not move or reposition a
ladder used in this manner except if it is necessary to use the ladder for rescue.
Members should be notified that the ladder was repositioned and should be
returned to the original location or replaced as soon as possible.
11.1 In order to perform an emergency search, portable ladders may be used as a brace where
there is partial collapse of a floor area. The ladders may be used singly or in groups
depending upon the extent of the collapse and the amount of stress to which the
ladders will be subject. To ensure that the searching members' lives are not
jeopardized, the collapse condition must not be underestimated. Therefore extreme
care and judgment must be exercised.
20
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
11.3.1 If it is necessary for a member to proceed out on the ladder to attempt rescue, he
shall be secured with a life safety rope as a safety precaution.
11.4 Elevator emergencies may at times necessitate the use of a portable ladder.
11.4.1 The ladder may be used to remove occupants from a stalled elevator car stuck
between the floors of a building. The occupants are first relocated to the roof of the
car via a ladder and then to a landing or a breached wall by a portable ladder.
The10' Folding and 12' Telescoping Ladders as particularly well suited for this application
11.4.2 Victims sometimes fall through a shaft opening and into an elevator pit or onto the top
of an elevator car. Portable ladders may be required to gain access to such
victims.
12. SAFETY
12.1 General:
12.1.1 Extension ladders in general are not made to be taken apart and used as
single section ladders. The upper sections normally are not furnished with any
type of safety foot. Therefore they are prone to slip when used as a single ladder.
12.1.2 Extension ladders and Telescoping should never be used upside down, that is,
with the round ends down, since this will cause the ladder to slip on the
ground. Also, the lock assemblies will not be able to function correctly.
12.1.3 When an extension ladder is raised, the halyard shall be tied off to the
lower section of the ladder as a safety measure and prevent the ladder
locks from accidentally unlocking by a pull on the rope.
12.1.4 Telescoping ladders have no heat resistance and must not be used fr laddering in
firefighting operations or any other situation where the ladder could be exposed to
heat.
12.1.5 Make sure the ladder is set on a firm foundation. Before climbing, take care to
see that it does not wobble.
21 1/19/2021
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
12.1.6 Ladders should never be placed against window panes, window sashes, or loose boxes,
barrels, or other surfaces that may break or collapse.
12.1.7 Always face the ladder when ascending or descending.
12.1.7 Do not climb higher than the third rung from the top on either straight or
extension ladders.
12.1.9 Resist the temptation to overreach. It is better to get down and move the ladder.
12.1.10 When using a ladder for access to high places, it shall be securely lashed or
otherwise fastened at the top to prevent slippage.
12.1.11 Never maintain a defective ladder in service. When a defect in a ladder is found
during an in-quarters inspection or damaged at a fire, remove the ladder from
service and notify the Technical Services Division for their recommendation as to
collection, repair or replacement.
12.1.12 Hooks of roof ladders in general are used to secure the ladder over the peak of a
house or to hang it from a wall edge or window opening. Be sure the bolts are
secure on the roof hooks and that the hooks have not been accidentally bent open.
12.1.13 Many pumper extension ladders, when in position in the ladder holding brackets
on the side of the apparatus, protrude enough to create a potentially hazardous
condition. Care should be exercised when mounting the back step of the pumper.
12.1.14 Electrical Hazards:
A. Both metal and, under certain conditions, wooden portable ladders can
conduct electricity. The fact that a metal ladder will conduct electricity is
obvious. However, wet wooden ladders or the metal component parts such
as tie rods, wire cables, ladder lock assemblies and the like, when in
contact with electrical wires or equipment can do likewise.
22
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
12.2.1 After a portable extension ladder has been raised and placed into a position against
a building, do not lower the ladder by pulling the butt end further away from the
building.
A. Doing it will reduce the load capacity as the angle becomes more shallow.
B. There is a great possibility that it will unlock the lock assemblies in the
upper section.
C. Always lower the fly ladder below the desired level and re-raise it in order
to ensure a safe 65 - 75 degree climbing angle and also the proper locking
action of the lock assemblies.
12.2.2 When ventilating the upper windows of a building with a portable ladder, watch for
glass shards sliding down the beam. (Section 10.3.2.B)
12.2.3 When placing a metal portable ladder against a building constructed with an
aluminum siding exterior, the member should release the ladder before contact is
made with the building.
A There have been occasions when the aluminum siding was energized due
to a faulty electrical service connection or a faulty ground, or due to the
service being damaged by fire conditions. If a member places an aluminum
ladder on such a building, they could make themselves part of an electrical
circuit and receive an electric shock.
12.2.4 Position metal ladders away from electrical service wires entering buildings from
utility poles. Injury to a member can be caused by the member brushing against
wires having an outer insulation covering that is in a deteriorated condition.
23
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
13.1 Aluminum ladders require considerably less maintenance than wood ladders and with a
few simple precautions should provide long service.
13.2.2 Aluminum ladders shall be maintained free of dirt and grime. They shall be
washed when necessary with warm soapy water and rinsed thoroughly.
13.2.3 Nicks or burrs that are found on the ladder shall be removed with a fine file in
order to prevent injury to member's hand during ladder handling.
13.2.4 A visual inspection of portable ladders shall be made weekly, and also after use,
to determine their condition and serviceability. Examples of ladder defects are as
follows:
A. Cracked welds.
B. Loose rungs.
B. Grease is normally used only for internally guided aluminum truss ladders.
The grease shall be cleaned from the guiding grooves, and they shall be
recoated each year, or when the grease has dried out and is no longer
an effective aid to sliding.
24
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS
C. On all ladders, plain candle wax or paraffin shall be applied every three
months to all contacting surfaces of multiple section ladders to ensure
smooth operation. Apply the candle wax or paraffin where there is contact
between rungs, guides or side rails.
1. Any wax that is thinner than candle wax or paraffin either spreads too
thinly or rubs off almost immediately. The net result is no lubrication and
the sections do not slide easily.
2. If, after the application of candle wax or paraffin, the ladder sections do
not move smoothly, or if they bind during use, check the ladder for
damage and/or alignment problems.
13.3.2 Pulleys:
A. Pulleys are found on all extension ladders. These pulleys usually have a
ball-bearing center that requires 1 to 2 drops of oil once a year.
13.3.3 Halyards:
A. The halyards on the 24’ extension ladder are generally made of manila
rope. The halyards on the 35’ extension ladder are made of a poly blend.
When either rope becomes frayed or twisted from usage, it should be
replaced.
13.3.4 Mechanical Lock Assemblies:
A. The mechanical lock assemblies are spring loaded devices. These springs
have, at times, broken or rusted off thereby placing the ladder out of
service. The assemblies shall be given careful scrutiny during inspections
and kept clean and well oiled.
13.4 Hook Ladders:
13.4.1 The hooks of the hook ladders are spring loaded and are covered assemblies to
ensure operation even under freezing conditions. These assemblies, like
the mechanical lock assemblies in Section 13.3.4A, must be carefully inspected,
kept clean and well oiled to ensure proper functioning.
13.5.1 If the ladder becomes very wet during use, it should be wiped down and allowed
to dry before being stored. Do not is candle wax, paraffin or grease to lubricate
a telescoping ladder. If lubrication is required, use a silicone-based furniture
polish (such as Pledge) on the beams of the ladder. Never use WD-40 or similar
oil-based lubricants. These may clog mechanisms inside the ladder.
25 1/19/2021
THIS PAGE WAS INTENTIONALLY LEFT BLANK
26
PART TWO
SECTI ON T I TLE PAGE
1 Transport Ladder ....................................................................... 29
6 Secure Ladder.............................................................................. 36
27
28
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
EQUIPMENT:
♦ 1 Portable ladder
OBJECTIVE:
Procedures will apply to all portable ladders except 35 ft. metal Duo-Safety extension
ladders for which separate instructions have been included.
29
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
Figure 1
1.1 Two firefighters, positioned one at each end of the ladder, with fly out, grasp upper beam.
1.5 Gives command "Ready, Transport" and Transports ladder towards operation
moves toward operation point. point.
1.6 When destination has been reached, Halts and awaits next command.
gives command "Ready, Halt." Halts.
30
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
ALTERNATE METHOD: Hand carry for short distances - Figure 2
Two firefighters, one near butt, the other near tip. Members, on command carry
ladder by the upper rail farthest from body (as with a suitcase). (See Note D).
Carry ladder to objective.
Figure 2
31
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
2.1 Ladder is positioned on beam parallel to building, fly facing away from building, butt
directly below objective.
2.2 Takes position with back to building, Takes position one-third the distance
foot (nearer tip) is placed on lower from the tip, on the street side of the
ladder shoe, hand(near tip) grasps ladder facing the tip.
underside of upper beam at
approximately the 3rd rung, palm up.
Other hand grasps upper beam shoe,
palm down, other leg is extended for
leverage.
2.3 Give command "Prepare to Raise". Does partial knee bend, grasps
upper beam on rail closest to building.
2.4 Gives command "Raise" and, as ladder is Lifts ladder from the ground. Pivots
being raised, pushes down with hand on in under lower beam to a position
shoe and pulls up with hand nearer tip: facing the butt firefighter. Raises
stretches extended leg away from the ladder to a vertical position using a
butt until ladder reaches vertical hand under motion along lower
position. beam.
2.5 At this point the firefighter is in a position Takes position on street side of ladder
opposite rungs on building side of ladder. opposite butt firefighter
Figure 3
32
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
Figure 4
3.1 Snubs left beam with left toe, unties Takes boxer's stance, left foot forward
knot, extends fly ladder to desired dead center between beams. Both hands
height. Locks fly. (note C) (note B) grasp beams on inner rail about shoulder
high. Steadies ladder as it is extended.
(Note A)
Figure 5 Figure 5A
33
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
4. COMMAND: "Place Ladder Against Building" - Figure 6
4.1 Grasps both beams on inner rails about Places left foot on center of bottom
shoulder high, steps backward lowering rung, grasps rung at shoulder level with
ladder into building. Looks forward, not both hands, palm down, looks up and
upward. guides ladder into building.
4.2 Secures halyard by making clove hitch Adjusts angle of ladder if necessary.
and binder on taut part of rope above the
3rd rung.
Figure 6
34
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
5.1 Ladder is returned to vertical position in reverse order of the way it was placed against
the building.
5.2 Each firefighter moves to his right, facing beams, grasps beam in front of them
about head high with lefthand, grasps 3rd rung from butt with right hand, palm up.
5.3 The firefighter facing direction of travel gives command "Ready, Lift". Both lift
ladder a few inches off ground.
5.4 The firefighter facing direction of travel gives command "Prepare to carry".
Both men set themselves to carry ladder.
5.5 Member facing direction of travel gives command "Carry". Both firefighters carry
ladder to objective. The firefighter facing direction of travel looks alternately
at tip and direction of travel to avoid obstructions.
5.6 When ladder reaches objective, the firefighter facing direction of travel gives
command "Ready, halt". Both members halt. Place ladder on ground.
Figure 7
35
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
6.2 If they are facing beams when secure command is given, rest ladder on ground if
necessary, each grasps beam in front of them at eye level one hand on each rail and
exert a downward pressure, pivots to the left, and assumes secure position as in
step 6.1.
Figure 8
36
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
7.1 Ladder is returned to vertical position in reverse order of placing ladder against the
building.
7.2 Lower fly ladder where necessary in reverse order of extending procedure. Secure
halyard.
Gives command "Prepare To Step Out," Raising firefighter keeps moving but is
7.6 alert to next command "Step out".
when raising firefighter approaches
1/3 distance from the tip.
7.7 Gives command "Step Out" when raising On command of butt firefighter to
firefighter reaches 1/3 distance from the step out from under beam, turns to
tip. street side of ladder, facing tip, grasps
upper beam on inner rail and lowers
ladder to ground.
Figure 9
37
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
8.1 Ladder is positioned on beam parallel to building, fly facing away from building, butt
directly below objective.
8.2 Takes position with back to building. Take position on the street side of
Foot (near tip) is placed on lower shoe. the ladder, about 1/3 the distance
Hand (nearer tip) grasps underside of from the tip, facing the tip. Taller
upper beam near 3rd rung, palm up. PERSON nearer tip.
Other hand grasps upper beam shoe
palm down. Other leg is extended for
leverage.
8.3 Gives command "Prepare to Raise". Both do partial knee bend, grasp
upper beam on inner rail (near
building) with hand near building.
8.4 Gives command "Raise". As ladder is Both lift ladder from the ground,
being raised, pushes down with hand on then pivot in under lower beam to
shoe and pulls up with hand on beam, position facing the butt firefighter.
extends leg for leverage until ladder (Figure No. 10). They raise ladder to
reaches the vertical position. a vertical position using a hand under
hand motion along lower beam. As
ladder nears vertical position raising
man nearer butt steps out and
proceeds to far side of the ladder and
faces the beam.
38
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
Figure 10
Figure 11
39
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
9.1 Snubs left beam with left toe, unties Both men stand facing beams grasp
knot, extends fly to desired height, locks beams on rails of bed ladder with left
fly. (Note C). See Figure 5 for correct hand about head high and right hand
position of hands on halyard when waist high. Feet are about two feet
extending fly. (Note B). apart. (Note A). Both steady
ladder as it is extended. Look up.
Figure 12
40
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
10.1 Takes position on building side of ladder Take position on street side of
facing raising firefighter. Gives ladder, facing butt firefighter.
command "Prepare to place
ladder against building".
10.2 Grasps beam about shoulder high, gives Both men place foot near partner on
command "Place ladder". Steps bottom rung and grasp rung shoulder
backward while looking forward, high, palms down. They guide
lowering ladder into building. ladder into building as butt
firefighter steps back. Look toward tip
to avoid obstructions.
10.3 Does not look up as ladder angle is being
adjusted. Secure halyard as in two Adjust ladder if necessary.
firefighter raise.
Figure 13
41
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
11.2 Grasps rungs just above head with hand Each faces outside of beam nearer him.
on side opposite of travel, palm down. Grasps beam about head high with left
Other hand grasps 2nd rung from hand, grasps 2nd rung from bottom with
bottom, palm up. right hand, palm up. (see foot note)*
11.3 Gives command "Ready, Lift". Looks Both men lift ladder slightly off ground
alternately from tip to direction of travel and carry it to objective. Eyes are kept
to avoid obstructions and help maintain looking at tip to avoid obstructions and
ladder in straight position. to maintain ladder in level position.
11.4 Gives command "Ready, Halt". Ladder Both firefighters halt and place
is placed on ground. ladder on ground.
*NOTE:Taller firefighter may grasp 3rd rung from bottom if this position is more comfortable.
However, both must grasp same rung.
Figure 14
42
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
12. COMMAND: "Secure Ladder" Figure 15
Given by Butt Firefighter when ladder is in vertical position between commands or
by man having difficulty if Ladder starts to get out of control.
43
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
13. COMMAND: "Lower Ladder to Street" - Figures 16 and 17
13.1 Ladder is returned to vertical position in the reverse manner it was placed against
building.
13.2 Lower fly ladder where necessary in the reverse manner of the extending procedure.
Secure halyard.
BUTT FIREFIGHTER RAISING FIREFIGHTER
13.3 With back to building, places foot closer Taller firefighter takes position facing
to the direction of lowering on lower beam on lowering side of the ladder.
ladder shoe. Other leg is extended for Shorter firefighter stands next to them on
leverage. street side.
13.4 Both hands grasp beam opposite raising Taller firefighter grasps beam about head high
men. One hand on shoe in pushing with both hands. Shorter firefighter stands by.
position. The other hand higher on the
beam in pulling position.
13.5 Gives command "Prepare to Lower". Taller firefighter prepares to lower.
13.6 Gives command "Lower". As ladder is Taller firefighter pulls ladder so that it leans in
lowered, pushes with hand on shoe and their direction, lowers ladder in a hand over hand
pulls with hand on beam. Extends leg motion along the lower beam. As ladder is
for leverage until ladder reaches ground. lowered, shorter firefighter steps in under same
beam as taller one and assists them in lowering
ladder.
Figure 16
44
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
13.8 When raising men reach one third On command of butt man, both men
distance from the tip, gives command step out from under the beam, turn to
"Step Out." street side of ladder facing tip. Grasp
upper beam on inner rail and lower
ladder to ground.
Figure 17
NOTES:
A. Raising firefighter keeps their hands clear of the moving fly ladder by grasping the
side rails of ladder beams furthest from them (toward building). The left toe must be
dead center to avoid descending fly.
B. When extending or lowering fly ladder, hands grasp halyard at right angles to
direction of pull to prevent rope from slipping through hand. (See Figure No. 5).
D. This method prevents lower beam from bumping into leg as ladder is carried.
45
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
14. COMMAND: "Raise Ladder from Position Flat on Ground, fly up,
perpendicular to building with both shoes against the
building".
Figures 18 and 19
This method is used when methods previously described are impracticable.
One FF: All ladders except 35' Duo-Safety Metal Extension Ladder (Figure 18).
14.1 Firefighter(s) stand(s) at tip of ladder facing building, grasp top rung of ladder.
14.3 Move(s) toward building, raising ladder with a hand under hand motion on the
beams, (one firefighter on each beam on Duo-Safety) until ladder is in vertical
position against the building, fly in.
Figure 18
46
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
Figure 19
15.1 With tip against building, one firefighter snubs toe against left beam.
15.3 Roll ladder to turn fly away from building. (This must be done even if ladder is not
extended).
15.4 Move ladder by rolling it along building where necessary. Readjust angle if required.
Rope must be re-tied before ladder is rolled.
47
FDNY Probationary Firefighters Manual
Chapter Fifteen PORTABLE LADDERS – STUDY GUIDE 1
R AISING T HE L ADDER
PALM DOWN
UPPER SHOE
RAISING FIRE-FIGHTER
1/3 FROM THE TIP
FOOT TOWARDS TIP ON STREET SIDE
LOWER SHOE OF LADDER FACING TIP
REAR LEG IS EXTENDED
FOR LEVERAGE
RAISING FIRE-FIGHTER
LIFTS LADDER & IS NOW
FACING BUTT F.F.
RAISES LADDER USING HAND
UNDER MOTION
BUTT FIRE-FIGHTER
RAISE!!!
E XTENDING T HE F LY L ADDER
RAISING F.F.
STEADIES LADDER
BUTT FIRE-FIGHTER
BOXER STANCE
EXTENDS FLY
LEFT FOOT FORWARD,
SNUBS LEFT BEAM WITH LEFT TOE
CENTER OF BEAMS
CRIMP THE HALYARD AT RIGHT
ON THE GROUND
ANGLES TO PREVENT SLIPPAGE
HANDS GRASP BEAMS,
HAND OVER HAND MOTION
SHOULDER HIGH,
& CLEAR OF THE FLY
49
Probationary Firefighters Manual
Chapter 16
OBJECTIVE:
• To provide a general explanation of ladder
company fireground operations.
CONTENTS:
Part One:
• Ladder company positions, duties & tool assignments of
the first arriving companies at various buildings
Part Two:
• Ventilation
• Forcible Entry
• Search
16
PART ONE
LADDER COMPANY POSITIONS
TITLE PAGE
GENERAL AREAS OF RESPONSIBILITY .....................................................................1
SIZE UP ...................................................................................................................4
TAXPAYERS ............................................................................................................23
T his chapter describes initial assignments and tools used by Ladder Companies operating at
fires. Ladder Company assignments are given to each member at roll call. Each member
shall personally check his/her firefighting gear and equipment including mask, PASS
alarm, flashlight, personal rope and assigned tools. A copy of the riding positions shall be posted
on the blackboard. Members shall inform their officer of the results of their apparatus, tool and
equipment inspections.
Ladder companies institute a two-team offense to cover their assigned area of responsibility. The
charts that follow break down the tools, positions and duties for each member of the first and
second arriving ladder companies at a fire in a non-fireproof multiple dwelling. The ladder
company members’ tools, positions and duties vary depending on the type of building. The types
of buildings the FDNY has specific procedures for are: taxpayer buildings, row frame buildings,
brownstones, private dwellings, vacant buildings, high rise office buildings and fireproof
multiple dwellings. Non-fireproof multiple dwellings represent the bulk of the FDNYs’
responses.
1
FDNY Probationary Firefighters Manual
Chapter Sixteen LADDER COMPANY OPERATIONS
Basic Gear
Bunker Gear- 19.5 lbs. (Coat, pants, boots, gloves, and hood)
Helmet-3.5 lbs.
SCBA (self-contained breathing apparatus)-27.5 lbs. (45 min. cylinder)
PSS (personal safety system)-6 ¾ lbs. (includes harness)
Radio-1 ¼ lbs. (includes battery & harness)
Light- 3 lbs.
Pocket Tools-1 to 3 lbs. (knife, wrench, screw driver, chock, etc...)
*Total Weight- 62 ½ -65 ½ lbs.
*(hose strap 1 lb.)
Inside Team 1st due
Officer Complement of basic gear- 65 ½ to 68 ½ lbs.
Officers Tool- 3 to 5 lbs.
C.O. Detector-1/2 lb.
Thermal Imaging Camera -3lbs
*Total Weight-66-71 lbs.
Can Complement of basic gear- 62 ½ to 65 ½ lbs.
6ft Hook-5 lbs.
Extinguisher-30 lbs.
*Total Weight-97 ½- 100 ½ lbs.
Irons Complement of basic gear- 65 ½ to 68 ½ lbs.
Axe-7 lbs. or Maul 10 lbs.
Halligan-9 lbs.
Hydra Ram-12 lbs.
K-tool-3 lbs
*Total Weight-90 ½-93 ½ lbs.
Outside Team 1st due
Chauffeur Complement of basic gear- 62 ½ to 65 ½ lbs.
Tools-what he/she deems necessary to complete their assignment
*Total Weight-depending on tools chosen
Outside Vent (OV)* Complement of basic gear- 62 ½ to 65 ½ lbs.
Halligan-9 lbs.
Halligan Hook-6 ½ lbs.
*Total Weight-78-81 lbs.
Roof Complement of basic gear- 62 ½ to 65 ½ lbs.
Halligan-9 lbs.
Halligan Hook-6 ½ lbs.
Life Saving Rope-17 ¼ lbs. (includes atlas life belt)
*Total Weight-95 ¼- 98 ¼ lbs.
*Top floor fires in some occupancies the OV will go to the roof with the saw (25 lbs.) & halligan
(9 lbs.), also in other situations the OV may choose to take the maul (10 lbs.) in place of the
halligan hook (6 ½ lbs.).
2
FDNY Probationary Firefighters Manual
Chapter Sixteen LADDER COMPANY OPERATIONS
• The Thermal Imaging Camera has become a very common tool in initial operations, which
can be utilized by any member, (2.8 lbs.) also the Rad. 50 (1 lb.) is used more frequently.
• There are times when an Engine company may be utilized as a Truck company, or an Engine
member may be detailed to a Truck for the tour, so it is important that all members are aware
of the weight imposed upon them when assigned certain positions with the associated tools
that accompany that position. Engine Company members performing their normal duties
should be aware of the weight placed upon them also. Aside from the weight of the basic
gear & pocket tools which will include a hose strap
(1 lb., 63 ½ to 66 ½ lbs., total weight of basic gear), members will be under an additional
weight strain as in standpipe operations where they will carry a 2 ½ roll up (35 lbs., 37 lbs.
with a nozzle attached & a standpipe kit (control bag) 25 to 35 lbs.).
• A length of 1 ¾ hose weighs 22 lbs., once charged the weight increases to approximately 52
lbs., as stated above a length of 2 ½ hose weighs 35 lbs. once charged the weight increases to
approximately 135 lbs. . . . Factor in several lengths (of either size hose) and the friction of
stretching (dragging) along the ground, floor, or around obstacles you will note that this can
be an arduous task.
• The weight of the basic gear may vary depending on the height & weight (size) of the
member wearing the PPE (personal protective equipment). Weight of tools and equipment
may vary depending on the manufacturer of such.
• Refer to the Proby Manual Volume 2 Chapter 12 (engine company operations) for Engine
company member’s positions and equipment assignment with the associated weight.
3
FDNY Probationary Firefighters Manual
Chapter Sixteen LADDER COMPANY OPERATIONS
SIZE UP
Size up is an ongoing evaluation of the problems confronted within a fire situation. Size up
starts with the receipt of the alarm and continues until the fire is under control. This process may
be carried out many times and by many different individuals during a fire.
1. Time
Governs the life hazard. Night fires mean poor visibility; buildings locked effecting delay in
access. A tenement fire is more serious at night than in daytime.
2. Life
The most serious factor at any fire. What is the location of the life hazard in relation to the
fire. Life hazard to firefighters must also be considered.
3. Area
Building or occupancy area. Large areas to be searched requiring search lines. Large areas
generate fires of great intensity, heavy volumes of smoke and severe heat.
4. Height
Building height will govern the use of the Aerial and/or Tower Ladder and portable ladders.
5. Construction
Non fireproof contains vertical voids that allows for extension. Alterations may have
introduced larger voids, both vertical and horizontal. Wooden "I" beams, lightweight truss,
Energy Efficient Windows and membrane roofs can effect the safety of operations within the
structure. The presence of front or rear fire escapes or party balconies, will also have an
effect on fireground operations.
6. Occupancy
This determines the severity of the life hazard and the intensity of the fire. For example: A
commercial occupancy with an increased fire load on the first floor with apartments above.
7. Location & Extent of Fire
A fire in the cellar, shaft, or apartment on the top floor
will determine access and areas to be searched.
4
FDNY Probationary Firefighters Manual
Chapter Sixteen LADDER COMPANY OPERATIONS
8. Water Supply
Hydrant availability, and the placement and readiness of hoselines
9. Street Conditions
Effect apparatus access and the placement of Aerial/Tower ladders to the fire building.
10. Auxiliary Appliances
Standpipe/sprinkler systems, and the location of outlets, O S & Y, and/or check valves.
11. Weather
Snow and freezing conditions, wind velocity and
direction are major factors in safety and fire operations.
12. Apparatus & Equipment
Be aware of the units on the scene. The arrival of those units
assigned on the alarm, Engines and Ladders, 1st due, 2nd due, etc.
13. Exposures
May be adjoining buildings or areas within the fire building itself (auto exposure). E.g., floor
to floor via windows, and across shafts or adjoining apartments.
5
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
INSIDE TEAM
♦ POSITION:
o Door to the fire area reached via the interior stairs of
the fire building
♦ DUTIES:
o Forcible Entry
Maintain Control of Fire Apartment Door
o Locate the Fire
Try to contain it by shutting a door or using the portable extinguisher
Provide & maintain an unobstructed path through which the hose line can
advance
o Search & Removal of victims
Ventilate as ordered by the Ladder Company Officer.
Verify that all areas of the fire apartment have been covered
o CAN
6 ft Hook
Pressurized water extinguisher
o IRONS
Axe & Halligan or Maul & Halligan
Rabbit Tool (Hydra Ram)
OUTSIDE TEAM
OUTSIDE VENT (OV):
6
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
♦ TOOL ASSIGNMENT:
6 ft. Hook & Halligan
♦ VARIATIONS:
6tore Fire – ventilate the rear of the store from exterior after receiving permission
from Ladder Co. Officer.
Top Floor Fire – to the roof with saw & Halligan, then, if possible, exterior of fire
area to prepare for VEIS.
If company is a Tower Ladder & there is no front fire escape, operates as basket
firefighter for ventilation
Roof
2. Aerial Ladder - The aerial ladder is used when the building is isolated or
the roof cannot be reached, or accessed from the adjoining building, due to
a difference in height or obstructions caused by security barriers, fences
etc. Roof access from the aerial can be dangerous. The cornice slopes
towards the roof and in some instances there is a high front parapet wall.
Use caution stepping off the aerial, especially when visibility is poor.
3. Rear Fire Escape - This access to roof is least desirable. It is only used
when other means are not available and when the fire floor can be safely
passed at this location. It is obviously dangerous to try to pass the fire
floor when the fire is exposing the fire escape or is on the verge of venting
itself in this direction. Rear fire escapes extend to the roof (Figures 3D
and 3E) unless of the party wall balcony type (Figure 3F). Front
fire escapes do not extend to the roof (Figures 3C and 3E).
7
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
NOTE: The interior stairs are NEVER used for the following reasons:
Rear View
of Building
8
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
2. The Roof Firefighter shall then perform initial vertical ventilation unless
ordered to delay or withhold this action by the Ladder Company Officer
operating inside the fire area.
Note: Initial vertical ventilation is the venting of bulkheads, scuttles or skylights
over stairwells and hallways. When skylights are vented, members must
recognize that this action is non-reversible.
If the Ladder Officer does not want initial vertical ventilation
performed; the Roof Firefighter will not perform vertical
ventilation.
However, in an attempt to reach potential victims who may be
trapped inside the bulkhead as soon as possible, the Roof
Firefighter will perform the following actions, which are not
considered vertical ventilation. They will force open the bulkhead
door, if conditions are tenable, the member should reach in and
probe the immediate area of the bulkhead for potential victims and
then immediately close and control the door until the Ladder
Officer orders vertical ventilation.
If the bulkhead door cannot be closed and controlled for any
reason (e.g. victim removal, damaged door), immediately notify
the Ladder Officer.
If the Ladder Officer does want initial vertical ventilation
performed, the Roof Firefighter will force open the bulkhead door,
if conditions are tenable, the member should reach in and probe the
immediate area of the bulkhead for potential victims, then continue
to ventilate the bulkhead and take additional vertical ventilation
tactics, as needed.
NOTE: Never attempt to climb onto or off a bulkhead or similar type structure
at a spot near or next to an open shaft or near a building wall that faces
on a shaft, areaway, courtyard or street.
3. When necessary, team up with the OV to VEIS the fire floor and, if not
needed for search on that floor, proceed to VEIS the floors above the fire.
4. When necessary, team up with second Roof Firefighter to VEIS all floors
above the fire.
9
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
5. At top floor fires, ventilate top floor windows from roof level. Prior to
conducting any horizontal ventilation tactics from the exterior, the Roof
Firefighter shall request permission from the Ladder Company Officer in
order to coordinate ventilation tactics with interior operations.
Communication with the Ladder Company Officer must be maintained in
order to coordinate the horizontal ventilation as the hoseline is applying
water to extinguish the fire. The Roof Firefighter is also responsible for
utilization of the saw to vent the cockloft and top floor when necessary
after completing initial duties.
7. Reports back to their Company Officer (generally located on the fire floor)
when assignment is completed or when relieved by second Ladder
Company and apprise them of all pertinent information.
NOTE: One of the greatest hazards is the possibility of fire cutting off the roof
Firefighter’s escape route. Conditions on the roof often change
without warning, cutting off the initial access point. The Roof
Firefighter must plan alternative routes, then continually monitor the
fire and its effect on the alternatives for as long as they are on the roof
10
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
Figure 3G
Exposure #4A
Perimeter search
Exposure #3 of building Exposure #1
REAR FRONT
If building has a bulkhead, open the bulkhead door. These doors are
almost always self closing. To keep the door open, either remove
the upper hinge or block the door open (Figures 3H and 3I).
Figure 3H Figure 3I
11
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
Figure 3J
Heavy smoke and high heat issuing from the bulkhead doorway or
scuttle would obviously require further ventilation such as removal
of the skylight. The absence of these indications does not
necessarily mean that skylight ventilation is not required. Opening
a bulkhead door or scuttle cover will not always give a true
indication of interior fire conditions; the door to the fire apartment
may not be open, either because it has not been forced or because
it is being held in a closed position. Evaluate other factors (heavy
smoke or fire showing from several windows, etc.) in determining
the amount of ventilation that will be required when the door to the
fire apartment is opened.
Remove skylight over stair bulkhead (Figures 3K and 3L) or on
roof level. (Figure 3M) If fire and smoke conditions are obviously
heavy, immediate venting of the skylight prior to the removal of
the scuttle cover to relieve the interior would be justified.
12
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
Figure 3K Figure 3L
Skylight
Sloping Bulkhead
with Skylight
Figure 3M
Work with the wind at your back, when possible. When protective
wire screens cover skylights, insert the tool beneath screen to
remove glass.
NOTE: Skylights at roof level may have been removed and openings covered
with roofing materials. It may be necessary to cut a hole over the
stairs to vent stairway. The Incident Commander should be informed
that a saw is needed to accomplish this.
13
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
Figure 3N Figure 3O
Dumbwaiter Bulkhead
Figure 3P
Open returns to check
for fire extension in the
cockloft.
Patch where
Scuttle skylight used to be.
Skylight Shaft
14
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
Figure 3Q
INSIDE TEAM
♦ POSITION:
o Door to the apartment directly above the fire, reached via
the interior stairs of the fire building
o Top floor fire – adjacent apartments
♦ DUTIES:
o Prior to Proceeding Above, Size Up Conditions of the Fire Floor
Severity & location of fire
Line placement & availability of water
Control of fire apartment door
Consideration of an area of refuge before going above
o Forcible Entry
When operating above the fire, members should force one or more doors on
each floor to provide an area of refuge
o Search & Removal of Victims
Ventilate as required in order to conduct this search, keeping in mind that the
fire can be drawn to the area vented.
Verify that all floors above the fire have been covered.
The adjacent apartments to the one directly above may be more severely
exposed due to the construction of Old Law Tenements.
o Check for Extension of Fire
Feel baseboards, walls, etc.
Call for a line, if needed.
♦ TOOL ASSIGNMENTS:
o Tools remain the same, as the first (1st) to arrive ladder, except for
top floor fires CAN firefighter should take two 6 ft. Hooks in lieu
of the pressurized water extinguisher
16
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
OUTSIDE TEAM
O U T S I D E V E N T (OV):
♦ P O S I T I O N , D U T I E S & T O OL A S S I GN M E N T :
o Same as first (1 s t ) to arrive OV, except position
is the floor(s) above and does not take a saw to
the roof.
*NOTE: At top floor fires the 2 n d due OV assumes the duties of the 1 s t due OV.
ROOF:
♦ POSITION:
o Roof of Fire Building
o Contact the 1 s t to arrive ROOF to determine:
1. Method of access to the roof, an alternative
route may be needed
2. If an y problems have been encountered
3. Need for assistance
*Interior stairs are NEVER used.
DUTIES:
1. Assist and confirm all duties of the 1st to arrive roof firefighter have been
completed. Must team up with another member for efficiency and safety.
Whenever possible, the first and second roof firefighters should team up to
safely complete roof duties.
NOTE: Never attempt to climb onto or off a bulkhead or similar type
structure at a spot near or next to an open shaft or near a building wall that
faces on a shaft, areaway, courtyard or street.
2. When necessary, team up with the 1st Roof firefighter or 2nd OV (or
another available member) to search and ventilate all floors above the
fire. Remove victims. Pay particular attention to top floor apartments, including the
public hall.
• T O OL A S S I G N M E N T :
o 6 ft. Halligan Hook
o Halligan
o For top floor fires, the saw & the Halligan Hook are taken.
17
FDNY Probationary Firefighters Manual
Chapter Sixteen NON-FIREPROOF MULTIPLE DWELLING
CH A U F F E U R :
TOOLS: H.T.
Flashlight
The chauffeur shall select the tools he/she deems necessary to complete
their assignment.
POSITION:
The front of the fire building, if not needed here, then go above the fire if
teamed with the 2nd OV (or another available member).
DUTIES:
1. If possible, position apparatus to cover fire building.
2. Be alert to the possibility that the first to arrive ladder company may be
blocked out. In this instance, if this position is not covered, the Incident
Commander must be notified.
3. Assist laddering with 1st to arrive ladder company, if required.
4. Ventilate and search if teamed up with the 2nd OV (or another available
member).
5. Be ready to use an aerial or portable ladder to remove members or
civilians in distress.
18
FDNY Probationary Firefighters Manual
Chapter Sixteen BROWNSTONE & ROWFRAME FIRES
Ventilation
All horizontal and initial vertical ventilation tactics must be controlled, communicated
and coordinated by the Ladder Company Officer inside the fire area to be vented. Initial
vertical ventilation tactics include the venting of bulkheads, skylights and scuttles over
stairways and hallways. Before ordering any horizontal ventilation the officer must
evaluate the impact the ventilation tactic will have on interior conditions.
ROOF:
o ACCESS TO THE ROOF: (Order of Preference)
1. Aerial Ladder or Tower Ladder Basket
2. 2nd Arriving Aerial Ladder (if available)
3. Access Via Adjoining Buildings*
* Brownstones usually do not have fire escapes.
OUTSIDE VENT:
o DUTIES:
o If the basket is used for roof access the saw and life-saving rope will be
brought to the roof. The OV will wait for completion of roof size up before
repositioning the basket to the fire floor for ventilation.
CHAUFFEUR :
o DUTIES:
o Prior to venting the top floor, the chauffeur shall communicate and coordinate
with the Ladder Company Officer inside the fire area to be vented
o Once assured that laddering is not needed, or after VEIS has been
completed, the chauffeur will report to their officer with whatever tools
necessary, keeping in mind that maximum utilization of 6’ hooks is expected
at top floor fires.
19
FDNY Probationary Firefighters Manual
Chapter Sixteen BROWNSTONE & ROWFRAME FIRES
INSIDE TEAM:
o T OP F LOOR F IRE :
o BROWNSTONE:
1. Check floors below to ensure fire did not start on
lower floor.
2. Unit should remain on the floor below until needed.
They shall not block the stairs or hallway leading to
upper floors.
o ROWFRAME (Brownstone Type):
1. Initially, the top floor of the most severely
threatened exposure
OUTSIDE TEAM:
NOTES: All members of the outside team should be aware when an LSR rescue
may be underway. The outside team shall be prepared to assist the 1st
arriving ladder as needed.
OUTSIDE VENT:
♦ POSITION:
Assist the chauffeur in front of the building when aerial or portable ladders are
needed for rescue or removal.
♦ DUTIES:
1. Check rear for trapped occupants and to assure ventilation has been
completed. This is especially important when the first to arrive ladder is a
TL, as the 1st to arrive OV will be operating in the bucket in front of the
building.
2. When not needed for ladder operations, report in to their officer above the fire.
20
FDNY Probationary Firefighters Manual
Chapter Sixteen BROWNSTONE & ROWFRAME FIRES
♦ VARIATIONS
o Top floor fire - after checking the rear, report to the roof to assist in
ventilation and opening up of the roof, or go into an exposure as directed by
their officer.
ROOF:
♦ POSITION:
Roof of the fire building to ensure the roof has been opened and to assist the
first arriving ladder in ventilation and opening up.
o For a top floor fire - proceed to the roof with the saw and Halligan hook.
o For fire below the top floor - be alert to 1st arriving Roof FF’s request for a
saw because of the inability to ventilate the interior stairs due to no roof level
skylight (tarred over skylights), dumbwaiters and penthouse structures.
♦ DUTIES:
2. When the 2nd arriving aerial can be raised to the fire building or an exposure,
the member assigned to the roof, should attempt access this way.
3. When there is no apparent need for their presence on the roof, reports to officer,
via HT, for further duties.
CHAUFFEUR:
♦ TOOLS: HT
Flashlight
The chauffeur shall select the tools that he/she deems necessary to
complete assignment.
♦ POSITION:
Reports to the turntable area of the 1st ladder Company to assist, or if necessary, team
up with the chauffeur of the 1st ladder for top floor VEIS.
21
FDNY Probationary Firefighters Manual
Chapter Sixteen BROWNSTONE & ROWFRAME FIRES
♦ DUTIES:
1. Position apparatus and place in Power Take Off (PTO) for use by the roof
firefighter.
2. When no longer needed at the aerial or for other laddering operations on the
front of the building, goes to work where their company officer directs.
22
FDNY Probationary Firefighters Manual
Chapter Sixteen TAXPAYER STORE FIRES
TAXPAYERS
♦ POSITION:
o The store occupancy involved with fire
♦ DUTIES:
o Forcible Entry
o Locate the Fire
Provide & maintain an unobstructed path through
which the hose line can advance.
Open ceilings, ducts and partitions
Cellar fires might require the cutting of floors for
ventilation & operation of cellar pipes, distributors,
bent tips or high expansion FOAM
o Search & Removal of victims
Ventilate as required in order to conduct this search.
o Shut Down Utilities
♦ TOOL ASSIGNMENTS:
o CAN
6 ft Hook
Pressurized water extinguisher
o IRONS
Axe & halligan or Maul & halligan
Rabbit Tool (Hydra Ram)
Security doors may dictate specialized equipment i.e.
Forcible Entry Saw (aluminum oxide blade), duckbill,
maul, etc.
23
FDNY Probationary Firefighters Manual
Chapter Sixteen TAXPAYER STORE FIRES
OUTSIDE TEAM
O U T S I D E V E N T (OV):
♦ POSITION:
o Roof of Fire Building, via a portable ladder.
• DUTIES:
o Vertical Ventilation (scuttles, skylights, etc.)
o Communicate conditions found, e.g. location or extension of fire
or heav y equipment on roof
• T O OL A S S I G N M E N T :
o 6 ft. hook and saw
o For fires in the cellar, the halligan & 6' halligan hook are taken
C H A U F FE U R :
24
FDNY Probationary Firefighters Manual
Chapter Sixteen TAXPAYER STORE FIRES
INSIDE TEAM
♦ POSITION:
o Adjacent stores
♦ DUTIES:
o Check for fire extension
♦ TOOL ASSIGNMENTS:
OUTSIDE TEAM
O U T S I D E V E N T (OV):
♦ POSITION, DUTIES
o Assist the 1 s t to arrive OV
o If not needed, proceed to the roof or otherwise directed
♦ T O OL A S S I G N M E N T :
o Same as first (1 s t ) to arrive OV
ROOF:
♦ POSITION:
o Roof of fire building, via a second portable ladder
• DUTIES:
o Assist & confirm all duties of the 1 s t to arrive ROOF
• T O OL A S S I G N M E N T :
o Saw & either an ax or a halligan
C H A U F FE U R :
• P O S I T I O N , D U T I E S & T O OL A S S I GN M E N T :
o Same as the first (1 s t ) to arrive ladder chauffeur
25
FDNY Probationary Firefighters Manual
Chapter Sixteen PRIVATE DWELLING FIRES
♦ DUTIES:
o Forcible Entry
After gaining entry through the main entrance door, the door shall be
controlled in a closed position by a member of the interior team
If the engine company requires assistance in order to advance the line through
the cellar, one member of the interior team shall be sent to provide assistance.
o Locate the Fire
Locate and confine the fire.
Attempt an examination of the cellar for fire
o Search & Removal of victims
When the search of the room has been completed, the door shall be kept
closed until the main body of fire has been extinguished
- Ventilate as required in order to conduct this search, keeping in mind that the
fire can be drawn to the area vented.
- At cellar fires, if the 2nd arriving ladder company is not at the scene, conduct a
rapid search of the first floor.
♦ TOOL ASSIGNMENTS:
o CAN
6 ft hook
Pressurized water extinguisher
o IRONS: Axe & halligan
26
FDNY Probationary Firefighters Manual
Chapter Sixteen PRIVATE DWELLING FIRES
♦ Conduct a quick survey around the perimeter of the dwelling for occupants in need of
immediate rescue. Communicate and coordinate any rescue attempt with the Ladder
Company Officer.
♦ Vent for extinguishment after the Engine Company is applying water to extinguish the fire.
T O OL A S S I G N M E N T :
o 6 ft. halligan hook and/or halligan for each member
o Portable ladder
C H A U F FE U R :
• POSITION & DUTIES:
o At the turntable. May use the aerial for necessary ventilation if not needed by the
Roof/OV team. Venting the attic window may greatly assist interior operations.
o Ventilation of the upper floors as directed by the Ladder Company Officer
operating in the fire area to be vented.
o Vent for extinguishment after the Engine Company is applying water to
extinguish the fire.
Note: Some buildings have exterior stairs to second floor (with no interior stairs) and
fire escapes to attic.
FLAT ROOF
ROOF:
♦ POSITION & DUTIES:
o Roof of the fire building for vertical ventilation
o Survey sides & rear
o Vent attic window as directed by the Ladder Company Officer
♦ T O OL A S S I G N M E N T :
o 6 ft. halligan hook , halligan & LSR
O U T S I D E V E N T (OV):
♦ POSITION & DUTIES:
o Assist the chauffeur with any laddering needed
o Vent the fire area when ordered
o VEIS area most likely occupied, when teamed up
C H A U F FE U R :
• POSITION & DUTIES:
o Operating ladder apparatus in front of the building
o Place and/or assist ROOF on the roof
o VEIS when teamed up with another member
27
FDNY Probationary Firefighters Manual
Chapter Sixteen PRIVATE DWELLING FIRES
♦ DUTIES:
o Prior to Proceeding Above, Size Up Conditions of the Fire Floor
Severity & location of fire
Line placement & availability of water
Control of fire apartment door
Consideration of an area of refuge before going above
o Search & Removal of Victims
When the search of the room has been completed, the door shall be kept
closed until the main body of fire has been extinguished
Ventilate as required in order to conduct this search, keeping in mind that the
fire can be drawn to the area vented.
Verify that all floors above the fire have been covered.
o Check for Extension of Fire
At top floor fires, check floors below to ensure fire did not start on, or drop
down to lower floors.
Check exposures
Be available to relieve the first to arrive ladder company
♦ TOOL ASSIGNMENTS:
28
FDNY Probationary Firefighters Manual
Chapter Sixteen PRIVATE DWELLING FIRES
C H A U F FE U R :
FLAT ROOF
ROOF:
♦ TOOLS:
Note: If the exposed building is an IDLH area, the chauffeur must team up
with another member before entering.
29
FDNY Probationary Firefighters Manual
Chapter Sixteen FIREPROOF MULTIPLE DWELLING FIRES
INSIDE TEAM
♦ POSITION:
o Fire Apartment
♦ DUTIES:
o Take Elevator to at least two floors below (Less than 7 stories take the stairs)
use precautions normally taken with elevators
Examine this floor and try to determine fire apartment location, stairway, etc.
This slight delay will enhance your operation on the fire floor should you
encounter a heavy smoke condition.
If it is determined the smoke and/or heat condition in the public hallway is
due to a wind impacted fire, members shall remain in the stairwell and follow
procedures outlined in Wind Impacted Fires.
o Forcible Entry
If conditions allow, enter the apartment to search.
Must be prepared to exit quickly and control door under all circumstances.
Do not chock the door open until a charged hose line is moving into the
apartment.
o Locate the Fire
Provide & maintain an unobstructed path through which the hose line can
advance
o Search & Removal of victims
Can be extremely hazardous based on the height of the building, weather and
wind conditions, the location of the apartment and the stack effect.
The officer may decide that the fire can best be extinguished without
additional exterior ventilation. See Wind Impacted Fires
♦ TOOL ASSIGNMENTS:
o OFFICER
Search Rope , carbon monoxide (CO) monitor & TIC
o CAN
6ft. hook & Pressurized water extinguisher
o IRONS
Axe & Halligan or Maul & Halligan
Rabbit Tool (Hydra Ram)
30
FDNY Probationary Firefighters Manual
Chapter Sixteen FIREPROOF MULTIPLE DWELLING FIRES
OUTSIDE TEAM
OUTSIDE VENT (OV):
♦ POSITION:
Apartment directl y above the fire via attack stairway
• DUTIES:
o Make sure the attack stairway door is maintained closed on the
floor above
o Gain entry into apt. above
o Check for occupants showing at windows on the fire floor.
o Notify officer of condition found, apartment layout, fire location
on the fire floor
o Determine what windows serve the fire room and report on wind
conditions. Size up this location for curtain deplo yment.
o Preplan tie off points in the event of a life saving rope rescue.
• T O OL A S S I G N M E N T :
o KO Curtain, Halligan and Hydra-Ram
CHAUFFEUR:
31
FDNY Probationary Firefighters Manual
Chapter Sixteen FIREPROOF MULTIPLE DWELLING FIRES
INSIDE TEAM
♦ POSITION:
o Hallway on the fire floor
♦ DUTIES:
o Take Elevator to at least two floors below
o Confirm the attack & evacuation stairways
o Search hallway
Severe heat & smoke conditions or high carbon monoxide readings are
two possible indications of the need to force adjacent apartments.
o Search attack stairway for five floors above the fire, after searching hallway
o Assist 1st. ladder if curtain (WCD) is being deployed .
♦ TOOL ASSIGNMENTS:
OUTSIDE TEAM
O U T S I D E V E N T (OV):
♦ POSITION, DUTIES:
o Contact 1 s t OV/chauffeur via Handie-Talkie
o If outside operations are in progress, team up with 2 n d
chauffeur and assist.
o If no outside operations are indicated, and building has
fireman service elevators, take control of a different
elevator than the 1 s t OV.
o If no fireman service elevators, proceed to the fire floor,
and assist the inside team.
♦ T OOL A S S I G N M E N T :
o SAME AS THE FIRST TO ARRIVE OV
ROOF:
32
FDNY Probationary Firefighters Manual
Chapter Sixteen FIREPROOF MULTIPLE DWELLING FIRES
C H A U F FE U R :
• P O S I T I O N & T O OL A S S I GN M E N T :
o The chauffeur shall select the tools he/she deems necessary
to complete the assignment.
• DUTIES:
o Assist & confirm all duties of the 1st to arrive chauffeur.
o If outside operations are in progress, team up with 2nd OV and assist with the same.
ENTIRE COMPANY
♦ POSITION & DUTIES:
o Report into the lobby & be directed by the Incident Commander
If roof operations were not initiated by the 1 s t & 2 n d to arrive
ladder companies due to outside operations, then the Incident
Commander shall assign this responsibility to the 3 r d to arrive
ladder compan y.
33
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
1. INTRODUCTION
1.1 A wind impacted fire may be one of the most dangerous operations members of the
FDNY will encounter. The term “wind impacted” fire shall be used to describe a fire in
which the wind has the potential to, or is already causing, a dramatic, sudden and
unexpected increase in fire, heat and smoke conditions. Experienced, respected members
of this Department who have survived wind impacted fires have all described the
following:
• Within seconds, fire, heat and smoke conditions changed without warning “from
routine to life threatening.”
• An operating 2½” hoseline had little or no effect on the incredible heat being
produced.
• Directly attacking these fires with one or two - 2½” hoselines proved ineffective
and ultimately led to members incurring serious injuries.
Members of this Department and many civilians have lost their lives or suffered serious
injuries when wind has impacted fire conditions causing the conditions to dramatically
increase without any warning indications.
1.3 The FDNY and the National Institute of Standards and Technology (NIST) fire research
group, conducted extensive research to determine the causes and effects of wind
impacted fires in FPMDs. Live burns recreating wind impacted fires were conducted in
vacant apartments on Governor’s Island. Based on data gathered from these burns, and
from interviews conducted with officers and firefighters who have operated as the first to
arrive units at wind impacted fires, alternate firefighting strategies and tactics were
developed, tested and evaluated for effectiveness. This testing has resulted in a revision
to firefighting tactics and procedures. In addition, new tools and equipment have been
developed for the purpose of extinguishing wind impacted fires.
34
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
2.1 The key to successfully operating at wind impacted fires in FPMDs depends on
recognizing the wind impacted fire conditions that may change a seemingly routine fire
into a blowtorching fire. Blowtorching is the appropriate description of what will occur
when fire conditions are impacted by wind conditions.
When wind impacted fire conditions exist in a FPMD, the IC shall notify the
Borough dispatcher so this information can be relayed to all responding units. Once the
contributing factors are identified, steps can be taken to minimize the hazards to
operating members.
2.2 The following five conditions must be present for a wind impacted fire to occur:
1. Wind.
2. Fire in an apartment.
3. Failed or opened window in the fire room.
4. Fire apartment door leading to the public hall left open or not fully closed.
5. An area of low pressure such as an opened stairwell door, or an opened apartment door
on the opposite side of the public hallway from the fire apartment.
This characteristic of air movement is known as the Flow Path.
Note # 1: The term Flow Path describes the movement of fire, heat and smoke from an area of
high pressure (the fire area) to an area of low pressure (all areas other than the fire area).
Note # 2: The impact of the wind will be affected by the size of the window opening, the fuel
load and the stage of the fire when the window failed.
2.2.1 When these five conditions are present, a wind impacted fire condition may occur. The
combination of wind feeding the fire and the natural airflow that results from the
construction characteristics of all buildings, especially FPMD’s, may cause fire to
blowtorch from the fire area. In FPMD’s, the flow path for these conditions will be
towards the public hallway if the fire apartment door is open. The fire is drawn to an area
of low air pressure such as an open door on the opposite side of the public hallway or
open stairway door. Eliminating this flow path, by keeping these doors closed, is key to
preventing a fire in a FPMD from becoming wind impacted. The one factor that cannot
be controlled is an occupant in another apartment opening their apartment door,
especially on the opposite side of the fire apartment.
Members must be aware and understand that the recognition of any of these factors is the
critical first step in evaluating the potential for a wind impacted fire.
The IC and company officer must be notified immediately when any of these conditions
are observed. The communication of this critical information to the IC and company
officers operating inside the building must be acknowledged.
35
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
3. SIZE-UP
3.1 Size-up begins by observing the wind and weather conditions before the tour starts and
knowing forecasted weather changes that will involve wind conditions. This information
must be discussed at each roll call. Members must maintain constant situational
awareness and accurately size-up conditions when responding to any reported fire in a
FPMD. In addition to normal size-up of life, fire and exposures, particular attention must
be paid to the following:
• The direction and speed at the street level is not a reliable indicator of wind
conditions above the street level.
• Wind behavior is not consistent or predictable. Wind impacted fires have occurred on
upper and lower floors. Building height, size, shape and location of adjoining or
adjacent buildings add to the unpredictability of the effects of wind on fire conditions.
• It does not take high winds to dramatically increase fire conditions inside the
building. When the wind subsides or shifts, pressure will equalize allowing the fire
and smoke to vent out the window. This condition has also been described as fire
and/or smoke pulsing in and out of a failed or opened window. Members operating in
the fire area must be aware that when the fire and smoke pulse outward from the
window, the condition in the interior will temporarily subside, giving a false sense
that the interior conditions improved. When the wind gusts back into the window the
interior conditions will dramatically deteriorate.
3.2.2 Fire or smoke visible inside the fire apartment that is not venting out of an open or failed
window is a potentially dangerous, life threatening condition. This is the classic
ventilation profile of a wind impacted fire.
• This indicates the wind is pressurizing the fire area, keeping the fire, heat and smoke
from venting out of the window.
• The firefighter performing the outside survey may be the first member to observe this
wind impacted fire condition.
• Their observations and size-up are critical to fire operations. These conditions must
be immediately transmitted to the company officer and IC. The IC must immediately
relay this information to all members on the scene.
Note: The IC must communicate with the officers on the fire floor to determine the interior
conditions. The IC must determine if an alternate strategy for extinguishing the fire should be
implemented. If so, the IC must communicate this to all officers and receive acknowledgement
of the change to the regular SOP’s for FPMD’s.
36
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
3.3.1 Prior to advancing to the reported fire floor, member must gather information by
surveying the floor below or two floors below if scissor stairs are present.
• Determine the location, the number of and letter designation of stairways serving
the fire floor. This information is critical if confronted with heavy smoke conditions
when arriving on the fire floor or if conditions unexpectedly deteriorate due to fire
conditions.
• All members must access the fire floor from the same stairway until the attack
stairway has been determined.
• The flow path of any fire will be towards the stairwell, the control of the stairwell
door is critical. This door should be maintained closed as much as possible.
3.3.2 When conducting the survey of the floor(s) below, determine the layout, shape and size
of the public hallway, especially if there are dead-end hallways. Heightened awareness is
required when operating in any hallway that is unusually long, odd shaped, or has dead-
ends.
3.3.3 Take note of the location and presence of any fire/smoke stop doors in the public
hallway.
3.3.4 Take note of the apartment designations in sandwich type apartments; take note of the
apartment layout designation.
3.3.5 The roof firefighter in the apartment above the fire may be able to provide the following
information:
4.1 The utilization of alternate strategies to combat wind impacted fires will provide the
following benefits:
• Ability to enter the public hallway to close the door to the fire apartment, thereby
gaining control of the public hallway and decreasing the flow of smoke and heat from
the fire apartment into other areas of the building.
• Rapid deployment of units to search apartment(s), public hallway(s), and stairways.
• Rapid knock down of the fire to quickly improve conditions on the fire floor.
• Reduction of serious injuries to members and civilians.
37
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
4.2.1 Live fire testing and fireground deployments have shown that the deployment of
WCDs (KO Curtains and Fire Blankets) will have the following effects:
Note: Refer to TB Tools 2, 3 and Evolutions 33, 33A, and 34 for additional information on this
equipment.
4.2.2 In FPMDs, water applied to the main body of fire from a high rise nozzle (HRN),
exterior stream, or flanking strategy can provide an offensive tactic designed to rapidly
knock down the fire. An exterior stream may be a hoseline operated from street level, a
setback, an outside terrace, another wing of the building or advanced up an aerial ladder.
A tower ladder stream or ladder pipe may also be effective. Any exterior stream must be
directed at the ceiling of the main fire area.
38
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
Note: Tests done by the Department concluded that the deployment of the HRN to
combat a wind impacted fire greatly improves conditions in the public hallway and inside
the apartment when the apartment door has been left open. If members are trapped and a
wind impacted fire is preventing their removal, the use of a
HRN or an exterior stream may protect members and allow for their safe removal.
(Refer to TB Tools 7 Data Sheet 17, High Rise Nozzle)
4.2.3 WCDs and HRNs may be difficult or impossible to deploy in windows of buildings with
the following construction features:
• Balconies that extend beyond the building face and are in front of a vented fire window.
• Luxury high-rise multiple dwellings having non-operating windows, limited opening type
windows or window walls. In these instances, glass removal will be a time- consuming
operation requiring specialized equipment. In addition, falling glass will present a hazard.
• Any type of façade or ledge that extends beyond the face of the building may prevent
WCDs from being effectively deployed if they are above or below the fire window.
Note: Members must be aware of the obstacles that buildings in their area present. Drills shall be
conducted to determine which alternate strategies may be used based on the building
characteristics.
4.2.4 A Flanking strategy is the application of water from inside the fire building to control the
main body of fire via a non-frontal attack. A small opening is made in the adjoining wall
to the fire room as close to the exterior wall as possible, so as not to create a flow path.
The hoseline is operated into the opening to extinguish the fire. Initially, the hole in the
wall should be only large enough for the main stream tip of the nozzle to be placed into
the opening allowing the stream to be directed at the ceiling of the fire room.
A. Flanking attack when the door to the fire apartment has been left open:
• This option is available based on the location of the fire apartment, the location of a
stairway closer to the selected apartment, and the interior hallway conditions.
• Enter an adjoining apartment to apply the hose stream to the fire room or fire
apartment via a breached wall adjacent to the fire area, if this adjoining area can be
accessed and occupied safely.
• Once access is obtained to the adjoining apartment, the door to that apartment must
remain closed and the hoseline stretched to this adjoining apartment from the
apartment below via an exterior window or balcony using a utility rope.
39
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
• Enter an adjoining apartment to apply the hose stream to the fire room or fire
apartment via a breached wall adjacent to the fire area, if this adjoining area can be
accessed and occupied safely.
• Once access is obtained to the adjoining apartment the hoseline will be stretched via
the fire floor public hallway into the adjoining apartment to operate into the fire
apartment.
40
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
5. OPERATIONS
5.1 If it is determined that the smoke and heat condition in the hallway is due to a wind
impacted fire with the fire apartment door left open, operate as follows:
a. The Ladder Officer shall ensure members exit the public hallway immediately, and notify
the IC and Engine officer of conditions. Units on scene shall be notified that a wind
impacted fire condition exists.
b. The IC shall implement the appropriate alternate strategy to gain control of the fire area
to allow the forcible entry team to reach and close the fire apartment door. Control of the
fire apartment door is critical.
c. A hoseline shall be stretched and charged in the attack stairwell. This charged
hoseline will remain in the stairwell so as not to create a flow path drawing the heat and
smoke into the stairwell.
d. The door to the stairwell must remain closed until the alternate strategy has been
implemented, and the IC receives confirmation of the following:
• A KO Curtain or Window Blanket has been deployed over the target window(s) and
is secured in place.
And/or
• The stream of a High Rise Nozzle, Exterior Stream, or Flanking Strategy has
controlled the fire.
Note: In most circumstances, the KO Curtain would normally be the first tactic used due to its
availability and time it takes to deploy.
e. Once confirmation is received that the alternative strategy has been successfully
implemented, the following actions may be taken:
• Approval to enter the public hallway must be given by the IC, Operations Section
Chief or Fire Sector Supervisor.
• Only the Ladder Officer and one member of the forcible entry team shall enter the
public hallway to locate and gain control of the fire apartment door. The Ladder
Officer shall utilize the TIC to assist in locating the fire apartment.
• The other member of the interior team will remain at the attack stairwell door on the
hallway side of the door to ensure the stairwell door remains closed limiting the flow
path and to act as a beacon in case members need to evacuate the hallway. The
Engine officer shall be responsible for control and coordination on the stairwell side
of the door.
• Once the Ladder Officer gains control of the fire apartment door, have the Engine
Company advance the charged hoseline to the fire apartment door. The Ladder
company member who remained at the stairwell door shall also advance to the fire
apartment door.
41
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
• The Ladder Company Officer shall evaluate and communicate to the IC and/or
Fire Sector Supervisor of the conditions found. The IC and/or Fire Sector
Supervisor shall determine if additional alternate strategies are required or whether to
enter the fire apartment.
• Once the decision has been made by the IC and/or Fire Sector Supervisor to enter the fire
apartment, the Engine Company must enter the apartment first followed by the Ladder
Company. This is for the protection of operating members due to the extreme conditions
and the need to cool the fire apartment immediately.
Opening the handline and using the reach and penetration of the stream ahead of the
advancing firefighters will cool the fire gases and will help extinguish the fire ahead of
the line.
• Prior to entering the fire apartment, to assist the engine company in locating and
extinguishing the main body of fire, the Engine Officer shall contact the roof firefighter,
or other member operating in the apartment above the fire apartment, and request the
following information:
2. Location of the main body of fire (e.g., kitchen, bedroom, living room)
3. Most direct route to the fire area (e.g., When you enter the apartment, go in
straight 6 feet and make a right down the hallway, the fire room will be the
second door on the left approximately 12 feet down.
• Once the hoseline advances towards the interior fire area as directed by the
Engine Officer, the fire apartment door shall be chocked open.
5.2 When the door to the fire apartment is found closed on arrival, window failure has
occurred, and reports are received from members operating on the floor above and the
exterior that the wind is impacting the fire, operate as follows:
• A KO Curtain or Window Blanket has been deployed over the target window(s) and is
secured in place.
And/or
• The stream of a High Rise Nozzle, Exterior Stream, or Flanking Strategy has controlled
the fire.
Note: In most circumstances, the KO Curtain would normally be the first tactic use due to its
availability and time it takes to deploy.
42
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
e. The Ladder Company Officer shall evaluate and communicate to the IC and/or
Fire Sector Supervisor of the conditions found. The IC and/or Fire Sector
Supervisor shall determine if additional alternate strategies are required or
whether to enter the fire apartment.
f. Once the decision has been made by the IC and/or Fire Sector Supervisor to enter
the fire apartment, the Engine Company must enter the apartment first followed
by the Ladder Company. This is for the protection of operating members due to
the extreme conditions and the need to cool the fire apartment immediately.
Opening the handline and using the reach and penetration of the stream ahead of
the advancing firefighters will cool the fire gases and will help extinguish the fire
ahead of the line.
g. Prior to entering the fire apartment, to assist the engine company in locating and
extinguishing the main body of fire, the Engine Officer shall contact the roof
firefighter, or other member operating in the apartment above the fire apartment, and
request the following information:
h. Once the hoseline advances towards the interior fire area as directed by the
Engine Officer, the fire apartment door shall be chocked open.
5.3 When the door to the fire apartment is found closed on arrival, window failure has not
occurred but size-up indicates there is a wind condition; Officers must still evaluate the
potential for the wind to adversely affect fire conditions. Prior to entry into the fire
apartment, the following actions shall be implemented:
a) The hoseline can be advanced to that location and charged.
b) Wind Control Device in position above the fire apartment ready for immediate
deployment. As a precautionary tactic, the IC may decide to deploy a Wind
Control Device over an intact window of the fire room/area.
Note: Where you are unable to determine the target window from the exterior, the
TIC may be of assistance. The IC shall assign a member with a TIC to scan the
windows of the fire apartment from street level. Scanning of the fire apartment
windows with the TIC can assist in identifying the target window for deploying of
the WCD. The TIC does not see through clear glass or plastic, but a heated
window or window frame may be detected from below.
d) Prior to opening the door of the fire apartment, the Ladder Officer shall get a
report on exterior conditions from members operating outside the building and the
Roof firefighter operating on the floor above.
43
FDNY Probationary Firefighters Manual
Chapter Sixteen WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS
e) The Ladder Officer and one member of the forcible entry team shall enter the fire
apartment to perform a search for the interior fire area location while the other
member stays at the fire apartment door inside the apartment making sure the
door remains controlled in the closed position, thereby limiting the flow path.
f) The door to the fire apartment must remain controlled in the closed position until
the Ladder Officer requests the charged hoseline be advanced into the fire
apartment or requires other assistance. Generally, the charged hoseline should not
be advanced into the fire apartment until the main fire area/room has been located
and if possible confined by closing a door. Keeping the fire apartment door
controlled in the closed position until the fire room/area is confined will
significantly reduce the flowpath. Taking steps to reduce the flowpath is a key
tactic for member’s safety when wind has the potential to adversely affect fire
conditions.
g) Once the hoseline advances towards the interior fire area as directed by the
Ladder Officer, the door shall be chocked open.
Note: The goal of the tactics outlined in this situation is to provide a margin of safety to
members if window failure should occur. The immediate deployment of these resources
will enable members to rapidly exit the fire apartment and control the fire apartment
door.
5.4.1 When faced with a known life hazard in either the public hallway or the fire
apartment, the following actions shall be taken:
a. Notify the IC and all units of the location of the known life hazard.
c. If the open fire apartment door is found in close proximity to the known life
hazard in a public hallway, attempt to close the door. Control of the fire
apartment door is critical. Notify the IC if the fire apartment door has been
controlled.
d. Members operating in the stairwell shall keep the landing clear to allow for
victim removal and/or emergency egress.
44
FDNY Probationary Firefighters Manual
Chapter Sixteen KO CURTAIN DEPLOYMENT
KO CURTAIN DEPLOYMENT
1. PURPOSE
1.1 When deployed properly, the KO Curtain will prevent wind from blowing into a fire
apartment and creating a wind driven fire condition. An open fire apartment door, with
wind driven fire indications, will make it impractical to advance a handline down the
hallway to reach the fire occupancy. A 2 ½” handline will not provide sufficient cooling
of the hallway to protect exposed members. Once the KO Curtain is in place covering
the window(s) to the fire apartment, the negative effects of the wind will diminish,
allowing members to advance a handline toward the fire area, as directed by the Incident
Commander. Testing conducted by the FDNY and NIST (National Institute of
Technology) showed an immediate 50% decrease in temperatures and significant flame
reduction when the KO Curtain is deployed. However, there will be an increase in the
smoke condition produced by the fire.
1.2 The KO Curtain shall be deployed for the following conditions:
1.2.1 A window in the fire apartment has failed and size-up indicates wind is blowing
the fire into the apartment continuously or intermittently.
1.2.2 Size-up indicates that deployment of the KO Curtain prior to window failure will
prevent a wind driven fire from developing.
Receiving Firefighter: Member responsible for securing bottom ropes of the KO Curtain.
45
FDNY Probationary Firefighters Manual
Chapter Sixteen KO CURTAIN DEPLOYMENT
3. SIZE-UP
46
FDNY Probationary Firefighters Manual
Chapter Sixteen KO CURTAIN DEPLOYMENT
• Do not remove or break the deployment window unless absolutely
necessary. An intact window will provide protection from auto-
exposure, which may occur due to shifting or gusty winds, allowing fire
to intermittently vent from the fire apartment. Once the KO Curtain is
deployed, members can expect that fire will vent from the target
window and auto expose the deployment window via the space between
the KO Curtain and the building wall.
5.2 The Deployment firefighter must have their facepiece on and full PPE donned
when deploying the KO Curtain. This will protect the Deployment firefighter from
unexpected auto-exposure which will subject them to fire, smoke and superheated gases.
5.3 The Deployment Firefighter, located above the fire, chooses the Deployment
Window which must be directly above the Target Window. If the fire is on the
top floor, the Deployment firefighter will be on the roof. Some situations will
require deployment from two floors above the fire apartment (e.g., duplex
apartments).
5.4 Remove the KO Curtain from the case, place on the floor below the Deployment
Window. The KO Curtain shall NEVER be deployed in the horizontal position. The
KO Curtain is designed and shall be deployed ONLY in the vertical position.
47
FDNY Probationary Firefighters Manual
Chapter Sixteen KO CURTAIN DEPLOYMENT
5.5 Open the Deployment Window without removing/breaking the glass, and remove
any child guards or window gates. Do not remove the glass unless absolutely
necessary. This window will need to be closed if auto-exposure becomes a problem.
5.6 Communicate with the Receiving Firefighter assigned to the floor below at the
Receiving Window, and determine if he/she is in position and ready to assist with
deployment.
5.7 Estimate how much rope will span from the Deployment Window sill to the top of
the Target Window. When the receiving and deploying firefighters are in position and
ready, notify the 2nd arriving ladder company officer that the KO Curtain is position
and ready to be deployed.
5.8 When deploying the KO Curtain, the firefighter shall grasp the ropes, place and hold
the KO Curtain outside the open window. Press the hand holding the ropes under the
sill and lock the ropes with hand against the wall. Allow the KO Curtain to drop (do
not throw) and cover the Target Window. Receiving member will gather KO
Curtain ropes at Receiving Window.
5.9 Deployment firefighter and Receiving firefighter must communicate and make sure
the Target Window is completely covered by the KO Curtain. If in position, the
spotter may be able to assist with this step.
5.10 When assured that the Target window is completely covered, the Deploying and
Receiving firefighters will maintain control of their respective ropes. The ropes shall
not be tied off. The deployment window shall be closed to prevent auto-exposure.
5.11 The IC and the ladder company officer on the fire floor will be notified when the
KO Curtain is in position fully covering the target window.
5.12 If the KO Curtain will be subject to direct flame exposure for an extended period of
time, the IC should consider deploying a second KO Curtain or Fire Window
Blanket to cover the first one.
5.13 Both the Deploying firefighter and the Receiving firefighter will remain in position
until otherwise ordered by the Incident Commander.
5.14 Once the fire has been extinguished, it may be necessary to remove the KO Curtain
to assist in ventilation of the fire apartment. The removal of the KO Curtain
must be approved by the Incident Commander. The request for removal of the KO
Curtain will be made by the Ladder Company Officer inside the fire apartment, after
first consulting with the Engine Company Officer in charge of the hoseline inside
the apartment. The Ladder Company Officer shall use the Thermal Imaging
Camera to confirm all fire has been extinguished. The Engine Officer shall ensure
that the nozzle team is aware of KO Curtain removal, and is prepared to
extinguish any increase in fire conditions resulting from removing the KO Curtain.
48
FDNY Probationary Firefighters Manual
Chapter Sixteen FIRE WINDOW BLANKET
1. DEPLOYMENT
1.1 The blanket is kept in a vinyl carrying bag, along with an instruction sheet for its use.
1.2 The blanket is large enough to cover at least two windows if necessary. The bottom of
the blanket is weighted to facilitate positioning.
1.3 Both the Rescue floor above team and the Squad floor above team must bring their
Window Blankets to the floor above. If the blanket is to be deployed, they must assist
in the deployment.
1.4 Any unit or units may be used to deploy the blanket. The assigned unit or IC shall
designate a spotter to observe the deployment of the blanket from the exterior. The
spotter should monitor the deployment and effect on the fire situation and report any
change in conditions to the IC. The spotter should be equipped with a handi-talkie, and
binoculars obtained from the battalion vehicle. The officer of the blanket deploying
unit will assign members to the floor below to secure the Fire Window Blanket. These
members must be in place prior to deploying the blanket. If additional resources are
necessary, the officer must notify the IC.
1.5 Due to the length of the top supporting straps, the blanket can be lowered from two
floors above, if the IC deems this necessary.
Just before the blanket is put in place, the IC must make a handi-talkie announcement
to all units. All units must be instructed to report any adverse conditions caused by the
blanket being put in place.
1.6 Incident Commanders shall be aware that if progress is not being made in the initial
fire room, fire may extend and additional Window Blankets or KO Curtains may be
needed in anticipation of further window failure.
49
FDNY Probationary Firefighters Manual
Chapter Sixteen HIGH RISE OFFICE FIRES
Search and Evacuation Group or A position established above the Fire Sector/Branch
Branch to control and coordinate all search and evacuation
operations in that area.
Fire Sector or Branch Defined as the fire floor and the floor above.
Incident Command Post Established in the lobby which will enable the
Incident Commander to exert central control over the
operations.
50
FDNY Probationary Firefighters Manual
Chapter Sixteen HIGH RISE OFFICE FIRES
51
FDNY Probationary Firefighters Manual
Chapter Sixteen LADDER COMPANY OPERATIONS
52
FDNY Probationary Firefighters Manual
Chapter Sixteen LADDER COMPANY OPERATIONS
PART TWO
TITLE PAGE
VENTILATION ....................................................................................... 55
VENTILATION TECHNIQUES...........................................................................77
FORCIBLE ENTRY.................................................................................. 85
SEARCH ................................................................................................ 95
53
FDNY Probationary Firefighters Manual
Chapter Sixteen LADDER COMPANY OPERATIONS
54
FDNY Probationary Firefighters Manual
Chapter Sixteen LADDER COMPANY OPERATIONS
VENTILATION
55
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
56
Probationary Firefighters Manual
______________________________________
FDNY
Chapter Sixteen VENTILATION
VENTILATION
Glossary i
1. Introduction 57
5. Ventilation Communications 63
6. Ventilation Tactics 65
7. Horizontal Ventilation 65
9. Vertical Ventilation 68
16. Conclusion 75
GLOSSARY
Auto-Exposure The extension of fire via the exterior of a building from a fire originating in
the same building.
Backdraft Occurs when a fire burns in a closed compartment with a limited amount of
ventilation. The products of combustion (smoke) will fill the compartment
and create an atmosphere with insufficient oxygen to support flaming
combustion. Suddenly, when a ventilation opening introduces fresh air into
the hot environment, a mixing of gases will occur. An ignition source inside
the compartment will initiate combustion and propagation (burning) of the
gases, resulting in a turbulent explosion (deflagration) causing an increase of
pressure, forcing the expanding gases out of available ventilation openings.
These expanding gasses on the exterior may ignite and burn. Generally,
backdrafts will occur in proximity to the main body of fire and require a
sudden change in ventilation. Backdrafts can cause significant structural
damage and potential collapse. See Smoke Explosion.
Decay Stage The stage of fire development within a structure characterized by either a
decrease in the fuel load (fuel-limited) or available oxygen (ventilation-
limited) to support combustion, resulting in lower temperatures and lower
pressure in the fire area.
Door Control The process of ensuring the entrance door providing access to the fire area is
controlled and closed as much as possible until water is applied to the main
body of fire. Steps must be taken to prevent the door from locking behind the
entering members. By controlling the door, we are controlling the flow path
of fire conditions from the high pressure of the fire area towards the low
pressure area on the other side of the door. Door control limits fire
development by controlling the flow path of fresh air at the lower level of the
open door towards the seat of the fire, and limits the movement of smoke and
heat to unaffected areas of the structure.
Fire Growth The potential size or intensity of a fire based on the available fuel load, room
Potential size and oxygen.
i
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
Flow Path The movement of heat and smoke from the higher pressure within the fire
area towards the lower pressure areas accessible via doors, window openings
and roof structures. As the heated, expanding fire gases are moving towards
the low pressure areas, the thermal updraft of the fire is pulling in additional
oxygen from the low pressure areas. This can be a bidirectional or
unidirectional flow dependent on the location of the main body of fire in
relation to the ventilation opening and the neutral plane. Based on varying
building designs and available ventilation openings (doors, windows, etc.),
there may be multiple flow paths within a structure. Any operations
conducted in the flow path will place members at significant risk due to the
increased flow of fire, convective heat and smoke toward their position.
ii
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
Bidirectional A flow path where hot gasses from the fire area (higher pressure) flow
Flow Path towards a ventilation point (lower pressure) AND an entrainment of fresh air
in the opposite direction back to the seat of the fire.
Example of a single room compartment fire - As the fire grows and uses the
available oxygen, the neutral plane drops lower in the open doorway.
The doorway is a bidirectional flow path. The hot gasses and smoke exhaust
out above the neutral plane and fresh air is pulled into the fire compartment
below the neutral plane.
iii
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
Unidirectional A flow path where hot gasses from the fire area (higher pressure) flow
Flow Path towards a ventilation point OR an air entrainment back towards the seat of the
fire. All gas movement is in one direction.
Example of a multi-level compartment fire: As the fire grows and uses the
available oxygen, the neutral plane will be higher in this compartment due to
the ventilation point above. Here we see fresh air pulling in through the
doorway in one direction and hot gases exhausting out of the ventilation point
on the floor above in one direction.
iv
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
Flow Path The tactic of controlling ventilation points prior to water application will have
Control the following benefits:
Limit additional oxygen into the space, thereby limiting fire
development, heat release rate and smoke production.
Control the movement of heat and smoke conditions out of the fire area
to the exterior and other areas within the building.
Fuel Limited Fires in which the heat release rate and fire growth are controlled by the
Fire characteristics of the fuel because there is adequate oxygen
available for combustion.
Fully The stage of fire development which has reached its peak heat release rate
Developed within a compartment. This usually occurs after flashover, resulting in floor
Stage to ceiling burning within the compartment, creating heat conditions untenable
for civilians and members.
Growth Stage The stage of fire development when the heat release rate from an incipient
fire has increased to the point where heat transferred from the fire and the
combustion products are pyrolyzing adjacent fuel sources. The fire begins to
spread across the ceiling of the fire compartment (rollover).
Heat Release The rate at which energy is generated by the burning of a fuel and oxygen
Rate mixture. As the heat release rate increases, the heat, smoke production and
pressure within the area will increase and spread along available flow paths
towards low pressure areas (open doors, windows and roof openings).
Horizontal The opening or removal of windows or doors on any floor of a fire building
Ventilation which will become flow paths for fire conditions.
Incipient Stage The early stage of fire development where the fire’s progression is limited to
a fuel source and the thermal hazard is localized to the area of the
burning material.
Modern Fires that involve hydrocarbon and synthetic-based contents such as foam
Content Fire rubber, nylon, rayon and polypropylene. Modern fires have a high heat
release rate. Modern fires rapidly react to ventilation and the in-flow of
additional oxygen.
v
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
Neutral Plane The boundary layer in a structure fire where below it, air will be drawn into
the structure, and above it, combustion gasses will be exhausted. The neutral
plane can be an indicator of the stage the fire is in, and will drop down
towards the floor as the fire grows in intensity.
Flashover imminent
Pyrolysis The transformation of materials into their basic compound when subjected to
heat. Contents will continue to off-gas (pyrolize) and add to the flammable
fuel load within the compartment as long as the material is subjected to
elevated temperatures.
Rollover Occurs in the growth stage when sufficient fuel, heat and oxygen are available
to allow flame spread in the upper, hot gas layer inside the compartment.
When observed at the ceiling level, rollover shall be taken as an indicator that
fire conditions are rapidly deteriorating and flashover may be imminent.
vi
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
Smoke The combination of airborne solid particulates, liquid particulates and gases
emitted when a material undergoes pyrolysis or combustion. Smoke is a
heated fuel source and a toxic mixture that contains numerous poisonous
gases and carcinogens such as carbon monoxide, hydrogen cyanide and
phosgene.
Smoke Occurs when a fire burns in a closed compartment with a minimum amount of
Explosion ventilation. The flammable products of combustion form a mixture with
sufficient oxygen and are ignited either internally or externally which can
result in a turbulent explosion (deflagration) of greater or lesser degree.
These expanding gasses may ignite and burn on the exterior. Generally, they
occur remote from the fire area and may not necessarily be a high heat
condition. They tend to initiate in a void space between floors or in a remote
portion of the cockloft. Typically, a light smoke condition may be present in
the compartment below the void space prior to the smoke explosion.
No additional ventilation is needed to occur for a smoke explosion to occur.
See Back Draft.
Situational The on-going activity of assessing what is going on around you during the
Awareness complex and dynamic environment of a fire incident. Operations will be
more effective and safer by continually observing your surroundings,
communicating conditions to other members and monitoring handie-talkie
transmissions.
Tenability An assessment on whether units can operate within the fire area based on the
conditions encountered and the impact of these conditions to potential victims
and members.
Ventilation The controlled and coordinated removal of heat and smoke from a structure,
replacing the escaping gases with fresh air. This exchange is generally
bidirectional with heat and smoke exhausting at the top and air flowing in
towards the fire at the bottom. The fire will pull the additional air flow into
the building towards the fire which can intensify the fire conditions.
This exchange can occur by opening doors, windows or roof structures.
Controlled, communicated and coordinated ventilation will facilitate
quicker extinguishment and limit smoke and fire spread.
vii
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
Ventilation The appearance of the fire building’s ventilation points showing the flow
Profile paths of heat and smoke out of the structure as well as any air movement into
the structure. This is an evaluation of fire behavior.
VEIS VEIS (Vent, Entry, Isolate, Search) is the approved tactic when entering a
structure through an opening (door or window) to search an area for the
location of the fire or to locate possible victims. The priority upon entering
the area via a window is to close the door to the room or area in order to
isolate that area being searched from the fire area. When entering a fire area
via a doorway entrance, the door needs to be controlled until the fire area is
further isolated or a charged hoseline is advancing on the fire. By isolating
the area, we are controlling the flow path of the fire, heat and smoke towards
the ventilation point as well as controlling the air flow from the ventilation
point towards the fire area.
Ventilation for The controlled and coordinated ventilation tactic which should coincide with
Extinguishment the Engine Company extinguishment of the fire.
Ventilation for The controlled and coordinated ventilation tactic performed to facilitate the
Search movement of a firefighter into an area to conduct a search for victims.
Ventilation- A fire in which the heat release rate and fire growth are regulated by the
Limited Fire available oxygen within the fire compartment.
Vertical The vertical venting of structures involving the opening of bulkhead doors,
Ventilation skylights, scuttles and roof cutting operations. These are methods of
releasing smoke and heat from inside the fire building and will generally
create unidirectional flow paths.
viii
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
1. INTRODUCTION
1.1 Originally issued on June 1, 2013, this document has evolved to include advances in
research and our understanding of fire dynamics. Each fire incident to which the
Department responds requires various tactics to bring the incident under control. These
tactics include search, suppression and ventilation procedures. These tactics are reliant
upon each other in order to achieve a successful outcome.
1.2 When ventilation and suppression tactics are controlled and communicated between
interior and exterior members, and coordinated by the Ladder Company Officer inside
the fire area, we dramatically increase the survivability of trapped civilians. In addition,
this can increase the safety of our members and improve the effectiveness of overall
operations.
2.1 Successful ventilation tactics begin with the understanding of basic fire dynamics as well
as how a ventilation tactic will impact the fire’s behavior.
2.2 Controlled, communicated and coordinated ventilation is necessary to remove heat and
smoke to facilitate hoseline advancement. The exchange of air is bidirectional when
there is a single vent opening on the same level as the fire. Heat and smoke will exhaust
at the top and air will flow in towards the fire at the bottom. The fire will pull the
additional air flow into the building towards the fire which will intensify fire conditions.
This is known as a bidirectional flow path.
2.3 When there are multiple ventilation openings these openings can act as an inlet, outlet or
bidirectional vent. In this instance, air will flow in towards the fire from one vent
opening known as the inlet while heat, smoke and fire vent or exhaust from another vent
opening known as the outlet, thus forming a unidirectional flow path. Recognition of a
unidirectional or bidirectional ventilation opening is important in determining the flow
path and can be useful in determining the inlet, outlet, number of ventilation openings
and the most advantageous attack position for the hoseline.
2.4 Some important fire dynamic concepts to understand regarding fire development are:
2.4.1 Modern content fires are largely comprised of hydrocarbons and synthetics which
rapidly consume the available oxygen in the fire area as they burn.
2.4.2 Modern content fires quickly become ventilation-limited fires due to their higher
fuel load. An additional contributing factor is the energy efficient construction of
buildings, which limits the amount of available oxygen within the fire area as well
as retaining the heat of the fire.
2.4.3 Modern content fires enter an early decay stage, producing heavy smoke and
varying and decreasing heat conditions, due to the limited available oxygen to
support flaming combustion. The fire will remain in the decay stage as long as it
remains ventilation limited.
57
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
2.4.4 The necessary oxygen to support fire growth can be supplied by improper ventilation
tactics or if the windows fail. If indications of an early decay stage exist upon arrival,
uncontrolled and/or uncoordinated ventilation can have negative outcomes for both
civilians and operating members.
2.4.5 The Traditional Fire Behavior Curve follows the below stages. (Figure 1)
Incipient
Growth
Fully developed
Decay
2.4.6 The Modern Fire Behavior Curve diagram differs from the Traditional Fire
Behavior Curve as follows: (Figure 2)
Incipient
A Rapid Growth stage that consumes the available oxygen very quickly.
Due to this rapid consumption, the fire will enter into an earlier oxygen-
limited Decay stage when compared to traditional fires, and will remain in the
Decay stage if no additional oxygen is introduced to the fire area. When units
encounter this earlier Decay stage, they should make every effort to control
the ventilation of windows and maintain control of the doors to the fire area.
If additional oxygen is admitted to the heated atmosphere through ventilation
openings, the following can occur:
o The fire regains its energy, increases its heat release rate and enters into a
Rapid Second Growth stage, generating more heat and increased smoke
production.
o It ends in a Second Decay stage as the fuel load is depleted or the fire is
extinguished.
58
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
2.4.7 The Coordinated Attack Fire Behavior Curve- differs from the Modern Fire
Behavior Curves as follows: (Figure 3)
The fire will behave in the same way up until the Early Decay stage.
If there is no additional oxygen admitted to the heated atmosphere, the fire will stay in an
Elongated Decay stage. An Elongated Decay stage where the fire is kept ventilation-limited
is the stage where firefighters can effectively operate and extinguish the fire by denying the
fire additional oxygen, thereby limiting fire growth and smoke production. This Elongated
Decay stage is maintained by firefighters by coordinating ventilation with the application of
water on the fire.
By controlling, communicating and coordinating the fire attack, ventilation will occur,
increasing the fire growth momentarily, which will be followed by suppression and
extinguishment.
59
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
(Figure 1)
(Figure 2)
60
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
(Figure 3)
61
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
The use of the Thermal Imaging Camera (TIC) is critical due to heavy smoke
conditions and the heat release rate of modern (synthetic) fires. Units equipped with
TIC’s must carry and use them at all structural fires. However, as with any electronic
device, it can malfunction. Units must maintain situational awareness in the fire area;
it is critical to safety and survival.
Hydraulic forcible entry tools allow quicker access to the fire area resulting in an
increase in the time gap between the Ladder Company gaining access to the fire area
and the extinguishment of the fire. Prior to the use of hydraulic forcible entry tools, it
was common for a hoseline to be in position at the door while the Ladder Company
was still forcing entry into the occupancy. Until a charged hoseline is available to
advance on the fire, it is critical to control the flow path of fire conditions by
maintaining control of the entrance doorway to the fire area and coordinate horizontal
and vertical ventilation.
The above factors make it critical to control, communicate and coordinate our
ventilation tactics with interior operations. Proper communication will increase the
situational awareness of all operating members, thereby allowing them to anticipate
changing conditions.
4.1 On each response, officers and firefighters must conduct an initial size-up which includes
the type of building, occupancy and conditions on arrival as well as the known life
hazard. Part of this initial size-up should also include a ventilation profile of the fire
conditions. This ventilation profile should note:
The location where smoke or fire is venting from the building.
Evaluation of the volume, pressure and velocity of the smoke venting from the
building. It is equally important to evaluate the air being pulled into the building
which is an indicator of a ventilation-limited fire condition.
When fire or smoke is not venting out of open windows.
Fire and smoke should be venting outwards and upwards. If the smoke and fire are
venting downward, horizontally or pulsing from an opening in the building, this
indicates the fire conditions may be wind impacted. Any unusual ventilation profile
must be immediately communicated to the Ladder Company Officer inside the fire
area to be vented and the IC. Indications of a wind impacted fire require the
consideration and implementation of alternate strategies.
Any change to the fire conditions as the incident progresses, or as the result of
ventilation tactics performed by members, must be communicated to the Ladder
Company Officer inside the fire area to be vented and the IC.
Example: When heavy smoke venting from an opening transitions to visible fire.
The following critical fire indicators observed during size-up may greatly impact
safety and operations:
62
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
o While in the Decay stage, the fire may no longer have enough pressure to push
smoke from the fire area or building. The assumption that the absence of smoke
pushing from a building is a positive sign, is not accurate. Modern content fires
require the control of ventilation tactics to prevent a ventilation-induced
flashover.
o Heavy flames out of a window are usually an indicator of high heat and smoke
conditions within a structure, including areas remote from the main body of fire.
On arrival, a vented fire should not be considered a favorable condition; we must
still control, communicate and coordinate all ventilation tactics.
o The more that venting flames fill an open window, the more members can
anticipate severe interior conditions. Modern content fires generate a greater
volume of heat and smoke that may overwhelm the ventilation point(s).
The excess heat energy and smoke not being vented rapidly pre-heat the interior,
causing fire conditions to move toward any other opened ventilation point.
5. VENTILATION COMMUNICATIONS
On Arrival Size-up: “E-234 to Brooklyn, Box 1628, 10-75, we have fire out
2 windows on the 3rd floor of a 5-story non-fireproof
multiple dwelling. Numerous people on the fire escape.”
The above transmission provides information about the
incident to responding units. The information about
numerous people on the fire escape could indicate that the
fire apartment door is open, creating a high heat and smoke
condition within the hallway. The occupants from other
than the fire apartment who are using the fire escape may
have left the windows opened as they exited from their
apartment. This potentially creates a flow path if their
apartment door is also open.
Exterior Size-up: “L-19 OV to L-19, we have fire on the 13th floor, visible
fire in the apartment, no fire or smoke venting out the open
windows.”
This transmission may indicate that we have a wind
impacted fire and these conditions could have a severe
effect on interior operations if the apartment door is not
controlled. This may also indicate the need for the
deployment of a wind control device (in a fireproof
structure) and the need for an alternate attack strategy to get
water on the fire.
63
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
Fire Floor Operations “E-58 to L-26, the line is charged and ready to advance”
This transmission:
Indicates the Engine Company has a charged
hoseline at the entrance door, ready to advance.
The Ladder Company Officer should direct the
Engine Company to the fire area.
Note: If the fire could not be isolated or located, and
based on the smoke and heat levels within the fire
area, the interior team may need to exit the fire area.
Members should then advance behind the charged
hoseline.
Initial Roof Operations “L-102 Roof to L-102, we have heavy smoke pushing out
3rd floor windows in exposure 3-4 corner.”
This transmission indicates:
The Roof FF has conducted an initial size up of the
roof and ventilation points, s monitoring handie-
talkie transmissions and is about to perform initial
vertical ventilation.
64
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
6.1 At structural fires, ventilation tactics are used to ventilate the building both horizontally
and vertically. When these tactics are properly controlled, communicated and
coordinated, the following can be expected:
An increase in the survivability of trapped civilians and an increase in the safety of
our members as they search for the fire and/or victims by controlling flow paths.
Facilitation of an effective operation by controlling fire development, and limiting the
spread of fire, heat and smoke conditions within the fire area and throughout the
entire structure.
Note: All members are reminded that conducting ventilation remote from the immediate
fire area can have a negative impact on civilians and members caught in the flow path.
Uncoordinated ventilation can intensify fire conditions and has the potential to create a
ventilation-induced flashover. This also applies to situations where fire is already
venting out of window(s) remote from your location. Where door control was lost on the
fire floor, members have been severely and fatally injured.
7.1 All horizontal ventilation tactics, whether Ventilation for Extinguishment or Ventilation
for Search, require communication with, and coordination by, the Ladder Company
Officer operating inside the fire area to be vented.
7.2 Horizontal ventilation tactics include controlling the door and window openings until a
charged hoseline is advancing within the fire area and extinguishing the fire.
The benefits of controlling the flowpath and properly performing horizontal ventilation
are:
Reducing temperatures in the fire area, limiting fire extension and auto exposure.
Limiting the in-flow of additional oxygen, reducing the potential for a ventilation-
induced flashover.
Improving conditions within hallways and stairwells by limiting the movement of
heat and smoke from the immediate fire area.
Maintaining tenability within the fire area, increasing the time available to locate the
fire and search for victims.
Limiting fire growth, permitting a rapid advance of the attack hoseline within the
immediate fire area, allowing for quicker extinguishment.
Reducing the danger of heat and flame passing over or around the attack hoseline.
65
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
8.1 Interior Operations: All interior and exterior horizontal ventilation tactics must be
controlled, communicated and coordinated by the Ladder Company Officer inside the fire
area to be vented. Before ordering any horizontal ventilation, this Officer must evaluate
the impact that this tactic will have on interior conditions.
8.1.1 The Ladder Company Officer inside the fire area shall:
Ensure door control at the fire area entrance and evaluate the ventilation
profile at the entry point. Pay particular attention to the air being pulled into
the fire area.
Communicate with the Engine Company Officer regarding the status of the
hoseline and control of the fire.
Communicate the location of the fire, fire conditions or difficulty finding the
fire to the Engine Company Officer and the IC.
Remain aware of all potential ventilation points within the structure or fire
area. Ventilation points that are behind your operating position may place you
in a flow path; control and limit flow paths until there is a charged hoseline
advancing within the fire area to extinguish the fire.
Continually assess the volume of smoke and heat conditions in the fire area
utilizing the TIC to enhance the initial size-up.
66
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
If the officer encounters a high heat and heavy smoke condition without a
charged hoseline, he/she should consider the following:
8.2 Exterior Operations: All horizontal ventilation tactics performed from the exterior must
be controlled, communicated and coordinated by the Ladder Company Officer operating
inside the fire area to be vented.
Notify the Ladder Company Officer when they are in position to ventilate as
directed; this can either be Ventilation for Search or Ventilation for
Extinguishment.
67
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
Evaluate the ventilation profile, paying particular attention to the air being
pulled in.
Determine if fire has extended to this area and request a hoseline if needed.
If the Ladder Company Officer determines the fire has not communicated to
the floor above, limited ventilation is justifiable if it facilitates search
operations, with the understanding of potentially pulling fire to that location.
The change in the fire dynamics of modern content fires require that ALL ventilation be
controlled, communicated and coordinated with operations on the fire floor. Modern
content fires generate greater volumes of smoke until the fire is extinguished, or kept vent
limited. This continuous smoke generation of modern fires may quickly overwhelm
available exhaust ventilation points and will not provide the intended or expected
removal of smoke and heat conditions from the interior. If the door to the fire area is
open, or not controlled, before a charged hoseline is available to extinguish the fire, and
roof ventilation is not controlled or coordinated with interior operations, the immediate
vertical air flow created may draw fire conditions into the hallway and up the interior
stairs, continuously filling the stairway with heat and smoke. This may place members
and civilians on the fire floor and floors above in an untenable environment. In order to
minimize the likelihood of this occurring, it is critical that the initial vertical ventilation
be coordinated with door control of the fire area.
9.1 The benefits of coordinating vertical ventilation with door control of the fire area include
the following:
The vertical flow path can begin to remove the heat, smoke and fire gases from the
public hall and stairwell pending the arrival of the charged hoseline.
It will relieve the upper portions of the building of heat, smoke and fire gases,
permitting a thorough examination of the hallways for potential victims.
Additionally, it will reduce the potential of smoke migrating into uninvolved areas of
the building.. Members will still require full PPE, use of the SCBA and TIC to
effectively conduct these searches.
68
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
10.1 Interior Operations: Initial vertical ventilation tactics must be controlled, communicated
and coordinated by the Ladder Company Officer operating inside the fire area to be vented.
10.1.1 The Ladder Company Officer inside the fire area shall:
Establish door control of the fire area and perform a ventilation profile at the
entry point, paying particular attention to the air being pulled in.
10.2. Exterior Operations: Initial vertical ventilation tactics can be conducted upon reaching the
roof. The Ladder Company Officer operating inside the fire area will advise the
Roof Firefighter when vertical ventilation is to be withheld or delayed.
Note: Initial vertical ventilation is the venting of bulkheads, scuttles or skylights over
stairwells and hallways. When skylights are vented, members must recognize that this
action is non-reversible.
• Conduct a visual survey of the exterior of the building. Look for any life
hazard and reassess the ventilation profile of the fire conditions.
• Communicate findings to the Ladder Company Officer (i.e. life hazard and
ventilation profile.)
• Initial Vertical ventilation shall be performed unless the Roof
Firefighter is ordered to delay or withhold this action.
69
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
11.1 Ventilation for Extinguishment is the controlled and coordinated ventilation tactic which
facilitates the Engine Company’s extinguishment of the fire. This tactic must coincide
with the application of water on the seat of the fire.
11.2 This ventilation tactic requires venting the window(s) of the immediate fire area while the
Engine Company is extinguishing the fire. The member on the exterior may be in
position prior to hoseline placement and must coordinate their actions to prevent
premature ventilation. Premature ventilation allows the fire to grow and spread through
the fire area, endangering occupants and members. Once in position on the exterior,
perform a size-up, communicate the ventilation profile and await permission to vent from
the Ladder Company Officer.
11.3 To properly coordinate Ventilation for Extinguishment between the interior and exterior
operating forces, all members must monitor handie-talkie transmissions to ensure proper
communications prior to performing ventilation.
11.4 The member on the exterior waiting to perform the horizontal Ventilation for
Extinguishment of the immediate fire area shall listen for the following transmissions
from the Engine Company Officer:
• The notification from the Engine Officer to the Engine Chauffeur to start water.
“E-162 to E-162 chauffeur, start water.”
• The notification from the Engine Officer to the IC that water is being applied to the
main body of fire. “E-310 to Command, we have water on the main body of fire.
The transmissions above are indications to the exterior member to prepare to conduct
Ventilation for Extinguishment. Before venting the window(s), the member must
communicate and coordinate with the Ladder Company Officer inside the fire area to be
vented. “L-3 OV to L-3, ready to vent.” “L-3 to L-3 OV 10-4, vent the windows.”
Note: This horizontal Ventilation for Extinguishment tactic only applies to the
window(s) in the immediate fire area (fire compartment) and only for the member
venting the immediate fire area. Any additional horizontal ventilation tactics must be
communicated with and coordinated by the Ladder Company Officer operating in that
area prior to performing such ventilation. This communication and coordination with
interior operations will reduce the likelihood of any negative impact on interior fire
conditions.
70
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
12.1 Ventilation for Search is a horizontal ventilation tactic performed to facilitate the
movement of a member into an area in order to conduct a search for a known life hazard;
this has the inherent risk of pulling fire towards the ventilation/entry point. This action
needs to be communicated to the Ladder Company Officer operating inside the fire area
to be vented as the ventilation may also negatively impact the members operating in the
interior.
12.2 When entering an IDLH, all members must comply with the provisions of Firefighting
Procedures, Volume 4, Book 1, Chapter 1, Safety Team, Section 1.2 which states:
When a fire progresses past the incipient stage, the fire area is considered an IDLH
atmosphere. Every member entering the IDLH atmosphere must be equipped with
personal protective equipment and a self-contained breathing apparatus. No member
shall enter, leave or operate in an IDLH atmosphere unless the member teams-up with
at least one other member and remains within visual or voice contact with that member.
Each member of the search team shall know the company identity and assigned position
of the other members of the search team. Handie-talkies or other electronic communication
devices are not acceptable to replace visual or voice contact. At least one of the members
must be able to contact a handie-talkie equipped member of the safety team outside of the
IDLH atmosphere.
12.3 The only exception to this Federally Mandated Standard for the teaming of members is
when a known life hazard is found and immediate action could prevent the loss of life.
This does not apply to standard search and rescue procedures.
12.4 Members of the Department must continuously perform a risk assessment when operating
at incidents. It is acceptable to take significant risk for a known life hazard and adjust
our standard operating procedures accordingly. In the absence of a known life hazard,
standard search and operational procedures will be utilized to locate any possible victims.
What may appear to be a routine fire operation at first can quickly transition into a major
incident with little or no warning. Unapproved and uncoordinated ventilation tactics
have been a factor at numerous incidents resulting in serious and fatal injuries to
members as they searched for the location of the fire and possible victims.
71
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
12.5 Members conducting Ventilation for Search must consider the following:
When ventilating windows or doors for access to the interior we are creating new
flow paths for fire, heat and smoke conditions.
The ventilation opening will increase the in-flow of air into the building providing
additional oxygen for the fire, while at the same time drawing the fire, heat and smoke
towards this ventilation flow point and the member performing the ventilation tactic.
Operating into and through a flow path places members at extreme personal risk.
There has been a substantial increase in serious or fatal injuries to members due to
members being caught in the flow path of fire conditions.
12.6 The member(s) performing Ventilation for Search shall comply with the following:
The Ladder Company Officer shall be notified when a search team enters from the
exterior to conduct a search for a known life hazard or when they are entering to
conduct standard search procedures.
The Ladder Company Officer shall acknowledge the report and take appropriate
action to assist and support any rescue operation. If the Ladder Company Officer and
interior team have quicker access to the location of a victim or to the area requiring a
search, the Ladder Company Officer may decide to disapprove the entry to search in
order to limit any negative impact caused by the additional ventilation.
Members venting for search should be cognizant of the location of the main body of
fire and the position of hoselines. Officers must notify these members searching
away from hoselines when the hoselines begin to advance toward their position.
Prior to venting the window for access, the member must determine if the ventilation
profile indicates that the area may be tenable for search and does not pose a high risk
to the member.
Members should also consider other factors, such as wind conditions, potential for
auto-exposure and if there is a life hazard above their position.
Once a decision has been made to enter, the member entering should choose the tactic
most appropriate. This may initially entail opening the window to judge the
ventilation profile; this would maintain the ability to reclose the window if conditions
dictate. Prior to entry, member may clear out the window for unobstructed access and
entry. Members must be cognizant that the flow path may change in either case.
Upon completion of clearing the window, and before entering, the member should
reassess the smoke and heat conditions to determine if the area is tenable.
If conditions now prevent access, immediately notify the Ladder Company Officer of
this situation.
If conditions are tenable, the member should reach in and probe the immediate area
for potential victims.
72
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
After venting and entering, the priority action for the member is to isolate the area by
closing a door before conducting the search (VEIS). By isolating the area, the
conditions in the room should improve as the closed door will stop the flow of fire
conditions and the window will provide an exhaust vent allowing a safer and more
effective search.
Search the room and locate any victim. The Company Officer and IC shall take
necessary action to support the rescue effort.
Note: If a victim is found prior to isolating the room, the member shall isolate the
room and proceed with the rescue effort.
Note: Once the IC receives credible information that the fire structure or fire area is
unoccupied; the IC shall announce that fact via the handie-talkie.
12.7 Ventilation tactics, whether Ventilation for Extinguishment or Ventilation for Search,
must be coordinated with interior operations and communicated to, and controlled by, the
Ladder Company Officer to ensure the safest and most effective operation possible.
The tactics for horizontal ventilation are different than vertical ventilation and always
require permission from the Ladder Company Officer operating inside the fire area to
be vented. Hearing transmissions from the Engine Company Officer, such as
ordering the Chauffeur to start water or a transmission to the Incident Commander
providing an update on the fire attack, does not alleviate the requirement to obtain
permission to vent, but rather, should be a sign to the exterior member to prepare to
conduct Ventilation for Extinguishment.
73
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
The following section covers ventilation tactics for High Rise Fireproof Multiple
Dwellings. This includes fireproof apartment buildings 75 feet or more in height,
including New York City housings projects.
In these occupancies, the ability to conduct ventilation is limited. In fact, horizontal
ventilation for smoke removal is usually performed after the main body of fire has been
controlled. This methodology is used for a number of reasons, including eliminating the
possibility of wind being introduced to the fire area, which may then cause the spread of
fire and smoke throughout the building. Wind impacted fires in these buildings have
overwhelmed operating hoselines injuring and trapping members in the flow path.
More importantly, indiscriminate ventilation can create conditions that place firefighters
and civilians in serious danger by hampering search efforts. It can also create dangerous
conditions directly below the vented windows due to falling glass shards that can injure
civilians and hamper operating units.
Smoke and hot fire gases increase the air pressure inside the fire compartment. This
higher air pressure will always travel toward areas of lower air pressure, creating a flow
path for smoke and fire to travel. These lower air pressure areas are the public hallways,
vertical shafts, stairwells and elevators. Lower air pressure areas also include other open
apartment doors and open windows, especially on the opposite side of the public hallway
from the fire apartment.
74
FDNY Probationary Firefighters Manual
Chapter Sixteen VENTILATION
The Fire Sector Supervisor, usually a Battalion Chief, can coordinate roof ventilation
through the Incident Commander after communicating with the Engine and Ladder
Company Officer in the fire area.
The firefighter(s) assigned to roof operations, during the ascent to the roof level, must
monitor floors for any smoke accumulation that poses a threat to civilians. The
location and severity of observed conditions must be communicated to the Incident
Commander. Additionally, this member must remain at the roof level to ensure that
bulkhead doors remain closed until the Incident Commander orders them vented.
Firefighters on the roof will be in position to assist the Ventilation Support Group
with stairwell pressurization and/or sequential ventilation (floor by floor ventilation;
conducted later in the operation).
When a firefighter operating on the roof discovers a condition that prevents the
control of the bulkhead, such as a broken bulkhead window, or a missing or damaged
bulkhead door, the Incident Commander and units operating must be notified.
In New York City, low rise fireproof multiple dwellings are generally older buildings
and may be found in proximity to high rise fireproof multiple dwellings.
These building are less than 75 feet in height. Since their construction is fireproof,
apartment fires will present fire problems similar to those in taller fireproof buildings.
Because of the lower building height of these fireproof buildings and the heavy
smoke conditions that usually occur in the attack stairway after the attack has begun,
emphasis will generally be placed on venting the attack stair bulkhead after approval
of the Incident Commander, earlier in the operation. This is done to relieve
conditions in the attack stairway and/or public hallways. Sometimes these stairwells
are unenclosed and result in a quicker smoke buildup on the upper floors.
Although roof ventilation is emphasized and conducted earlier in low rise fireproof
multiple dwellings, permission must still be granted by the Incident Commander
before providing vertical ventilation via the attack stair bulkhead. However, similar
to high rise fireproof multiple dwellings, the first Ladder Company Officer will
initiate and control ventilation of the fire apartment.
16. CONCLUSION
Today’s fireground has been scientifically proven to be vastly different from the fires of
years past. The characteristics of modern furnishings, in combination with the energy
efficient construction being utilized today, presents new ventilation and suppression
challenges to the Department. The continuous training, education and evaluation of our
tactics and procedures will allow us to meet these challenges in the most professional
effective manner possible, creating a safer, more efficient operational environment.
75
THIS PAGE WAS INTENTIONALLY LEFT BLANK
76
FDNY Probationary Firefighters Manual
Chapter Sixteen Ventilation Techniques
VENTILATION TECHNIQUES
NOTE: Energy efficient windows maintain their integrity longer than ordinary single pane
windows in a fire environment and may not give any of these indications.
Figure V-1
NOTE: Horizontal ventilation tactics must be controlled, communicated and coordinated
with the interior operations. Ventilate as directed by the Ladder Company Officer.
Figure V-3
77
FDNY Probationary Firefighters Manual
Chapter Sixteen Ventilation Techniques
♦ ROOF VENTILATION
To loosen bulkhead door from the upper hinge, or to remove the door entirely;
♦ To loosen the door from the upper hinge, open the door slightly and put the fork end
of the tool between the door and the door jamb (Figure V-6). Close the door on the
tool loosening hinge screws, or,
♦ Open the door slightly and put the adz end of the tool between the door and the door
jamb. Apply pressure with the tool as shown in figure V-7.
♦ To remove the door entirely, free both hinges and free the self-closing device.
In the foregoing, operate from the roof side of the door and use the door as a shield
against heat from the interior
78
FDNY Probationary Firefighters Manual
Chapter Sixteen Ventilation Techniques
Difficult bulkhead doors that are fastened on the inside:
♦ Even if these doors are tight against the door jamb there will usually be enough
space between the bottom of the door and the sill to get a purchase.
♦ The bottom of the door is pulled outward.
♦ Alternately using the Halligan tool and the hook, the firefighter works upwards until
the adz or fork end of the Halligan is near the fastening.
♦ Prying out will break or dislodge the fastening.
♦ In this operation the hook is not used for prying, but merely to hold the advantage
obtained, enabling the Halligan tool to be shifted to a new position.
Use Adz or
Fork End of
Halligan
o SCUTTLE COVER:
79
FDNY Probationary Firefighters Manual
Chapter Sixteen Ventilation Techniques
o SKYLIGHTS:
Heavy smoke and high heat issuing from the bulkhead doorway or scuttle would
obviously require further ventilation such as removal of the skylight.
The absence of these indications does not
necessarily mean that skylight ventilation is not
required. Opening a bulkhead door or scuttle
cover will not always give a true indication of
interior fire conditions; the door to the fire
apartment may not be open, either because it has
not been forced or because it is being held in a
closed position. Evaluate other factors (heavy
smoke or fire showing from several windows,
etc.) in determining the amount of ventilation that
will be required when the door to the fire
apartment is opened. Figure V-9
Remove skylight over stair bulkhead (Figures V-9, V-10) or on roof level (Figure V-11).
If fire and smoke conditions are obviously heavy, immediate venting of the skylight prior
to the removal of the scuttle cover to relieve the interior would be justified.
80
FDNY Probationary Firefighters Manual
Chapter Sixteen Ventilation Techniques
After venting a skylight, to ensure an unobstructed outlet for smoke, gases and heat,
probe with hook to detect possible presence of a glazed sash, draft stop or other
covering and remove it.
After removing roof level skylight or scuttle cover returns can be opened into the cockloft
to gain knowledge of conditions or to ventilate.
The following are two suggested methods to assist climbing onto a high bulkhead, to vent
a skylight, when alone:
81
FDNY Probationary Firefighters Manual
Chapter Sixteen Ventilation Techniques
2) Using the removed bulkhead door in conjunction with the Halligan (V-13).
HALLIGAN
Figure V-13
Figure V-14
82
FDNY Probationary Firefighters Manual
Chapter Sixteen Ventilation Techniques
o CUTTING THE ROOF (TOP FLOOR FIRE):
83
FDNY Probationary Firefighters Manual
Chapter Sixteen Ventilation Techniques
SEQUENCE
The size and location of the opening will depend on fire conditions. A suggested method to make
an expandable opening "COFFIN CUT" is as follows:
# 7 = 3’
NOTE: When a fire is burning in a top floor apartment, it is not efficient to wait until the fire is
"knocked down" before examining the cockloft. An early inspection can be made by going to a
room adjacent to the fire (in the same or adjoining apartment) and opening an observation hole in
that ceiling. If fire can be seen burning in the cockloft, the observation hole should not be
expanded until a charged hoseline has been positioned.
It is a good practice while waiting for the charged hoseline to ventilate all windows in the
apartment, because once the ceiling is opened the floor will quickly become filled with smoke.
This is also the time to make sure that a roof ventilation hole is being cut directly above the fire.
84
FDNY Probationary Firefighters Manual
Chapter Sixteen FORCIBLE ENTRY
Forcible Entry
85
FDNY Probationary Firefighters Manual
Chapter Sixteen FORCIBLE ENTRY
86
FDNY Probationary Firefighters Manual
Chapter Sixteen FORCIBLE ENTRY
w hen forcible entry is required, start immediately. A door should be forced in such
a manner as to preserve its integrity. If upon arrival an open apartment door is
found allowing fire and smoke to extend to the public hall, close the door but
ensure the door does not lock.
NOTES:
When forcing doors with two locks use the
above procedures placing the tool between
the two locks
87
FDNY Probationary Firefighters Manual
Chapter Sixteen FORCIBLE ENTRY
C. Taking action at the hinge side of the door is another method of forcing entry.
With the back of an axe, or maul, strike the solid part of the door adjacent to the
upper hinge location. If the door shows signs of being effectively forced in this
manner continue striking until the upper hinge is freed and then use the same
method on the lower hinge.
D. If this fails drive the fork end of the halligan tool in with the axe below the upper
hinge forcing the screws from the hinge. Repeat the same process above the lower
hinge. Judgment will be required since the hinges will not be visible.
E. By using a Halligan tool (Figure 4A) another and frequently easier method is to
drive the hook of the Halligan tool into the door jamb behind the lip and near the
hinge (Fig. 4B). The hook is driven deep into the jamb and then the Halligan tool
is moved towards the door tearing the hinge and screws from either the door or
the frame. Repeat this process near the lower hinge.
Note: The upper hinge is always attacked first so that the smoke and heat will rise while you
complete the forcible entry at the bottom
3.1 The method used to force outward opening doors is determined by the position of the
door in the frame.
A. Flush fitting doors. These doors may be forced using either the adz or fork end of
the Halligan.
1) When using the fork end of the Halligan, place the concave side of the
fork toward the door, tool canted slightly for initial penetration. As the
tool is driven in between the jamb and door, it is brought to the
perpendicular to avoid penetrating the jamb When the tool has spread the
door as far as possible, force the adz end away from the door.
88
FDNY Probationary Firefighters Manual
Chapter Sixteen FORCIBLE ENTRY
2) Place the adz of the Halligan 6" above or below the lock and drive it into
the space between the door and jamb being careful not to penetrate the
door stop portion of the jamb. Pry downward and out with the fork end of
the tool.
B. Recessed doors or doors with a wall adjacent to the lock side of the door.
Place the adz of the Halligan 6" above or below the lock and drive it into the
space between the door and jamb being careful not to penetrate the door stop
portion of the jamb. Pry downward and out with the fork end of the tool.
4. PADLOCKS
4.1 Padlocks are portable or detachable locking devices having sliding and pivoting shackles
that pass through a staple and are then made fast.
A. Attack points:
♦ Staple.
♦ Point of attachment.
♦ Shackle.
B. Tools.
1) Halligan.
2) Duck bill.
3) Bolt cutter.
4) Saw - aluminum oxide blade.
5) Cutting torch.
6) Bam-bam tool.
C. Operation.
1) Attack the point of least resistance.
2) Hook of Halligan or the duck bill can be driven through staple or shackle.
3) Bolt cutter to cut staple or shackle.
4) Case hardened locks require use of saw (aluminum oxide blade) or cutting
torch. It is also possible to pull the cylinder on some of these locks with a
bam-bam tool.
89
FDNY Probationary Firefighters Manual
Chapter Sixteen FORCIBLE ENTRY
5.1 A portable or detachable locking device that fits over a staple and locks by use of a
movable steel pin located in the body of the lock.
A. Attack points.
♦ Point of attachment.
♦ Body of lock.
B. Tools.
1) Saw (aluminum oxide blade).
2) Cutting torch.
C. Operation.
1) Use either of the above tools to cut staple or other point of attachment to
wall, etc.
2) Cut through the lock about 2/3rds of the distance up from the keyway,
cutting it in two pieces. Then remove the pin from the security gate.
CUT HERE
2/3rds
Figure FE-5 1
90
FDNY Probationary Firefighters Manual
Chapter Sixteen FORCIBLE ENTRY
6.1. Bar
A piece of wood or steel held in place by brackets which
traverses both sides of the door frame. BAR
Reference #5, Figure 2.
SLIDING BOLT
6.3. Forcible entry may be made using the axe and Halligan. The bar brackets or bolt may be
driven off the door frame by driving the fork end of the Halligan directly at the bar or
bolt.
7. WINDOWS
7.1 By placing the fork end of the Halligan under the window at
the center of the window sill and applying downward pressure
on the Halligan a single window and/or window lock can be
forced.
A. Some windows found at the ground floor level or fire escape will have window
gates behind the glass.
♦ These gates are always on the room side of the
window and will first require opening or
removing the window.
♦ Attack the window gate at the hinge side
(opposite the locking device), using either the
fork or adz end of the halligan.
♦ After taking the top & bottom hinge, slide the
gate towards the locking device thus clearing
about 2/3rds of the window.
♦ If severely exposed to heat or smoke at this
side of the gate, removal may be accomplished
at the lock side.
91
FDNY Probationary Firefighters Manual
Chapter Sixteen FORCIBLE ENTRY
8. MULTI-LOCK DOORS
8.1 The lock is not necessarily centered in the door but
easily recognizable by the large plate covering the
lock. Four bars, one in each direction, enter the door
jam when the lock is engaged.
To force the door, cut a triangle in the lower
quadrant of the door on the doorknob side. This will
enable you to unlock conventional locks as well.
Make the cut large enough to get your arm through
and back out, but small enough so that you don't cut
the bar.
9. SECURITY GATES
92
FDNY Probationary Firefighters Manual
Chapter Sixteen FORCIBLE ENTRY
Child guard gates come in a variety of weights and sizes. There usually are three to four
horizontal bars, which interlock and slide to the prescribed opening. The device is secured
across the lower sash of the window to prevent children from falling out.
Typically, they are secured on the outside of the sash to the window frame. They also can be
mounted to the inside of the window.
93
FDNY Probationary Firefighters Manual
Chapter Sixteen FORCIBLE ENTRY
If the gate is larger than the window it was designed for, the
vertical frames will be too close to the side of the window frame,
preventing placement of the prying tool.
94
SEARCH
95
THIS PAGE WAS INTENTIONALLY LEFT BLANK
96
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
SEARCH
TABLE OF CONTENTS
Glossary
1. Introduction
2. Fire Environment
3. Definition of Search
4. Size-Up
5. Types of Search
6. Primary Search
7. Secondary Search
8. Communications
9. Search Tactics
10. Searching Above the Fire
11. Use of Thermal Imaging Camera
12. Search Tips
13. Rescue of Victims
14. Conclusion
97
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
98
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
GLOSSARY
Flow Path The movement of heat and smoke from the higher pressure within the fire
area towards the lower pressure areas accessible via doors, window openings
and roof structures. As the heated fire gases are moving towards the low
pressure areas, the energy of the fire is pulling in additional oxygen from the
low pressure areas. Based on varying building design and the available
ventilation openings (doors, windows, etc.), there may be several flow paths
within a structure. Any operations conducted in the flow path will place
members at significant risk due to the increased flow of fire, heat and smoke
toward their position.
Heat The rate at which energy is generated by the burning of a fuel and oxygen
Release Rate mixture. As the heat release rate increases, the heat, smoke production and
(HRR) pressure within the area will increase and spread along available flow paths
toward low pressure areas (open doors, windows and roof openings).
VEIS VEIS (Vent, Entry, Isolate, Search) is the approved tactic when entering a
structure through an opening (door or window) to search an area for the
location of the fire or to locate possible victims. The priority upon entering
the area via a window is to close the door to that room or area in order to
isolate that area being searched from the fire area. When entering a fire area
via a doorway entrance, the door needs to be controlled until the fire area is
further isolated or a charged hoseline is advancing on the fire. By isolating
the area, we are controlling the flow path of the fire, heat and smoke towards
the ventilation point as well as controlling the air flow from the ventilation
point towards the fire area.
Ventilation The controlled and coordinated removal of heat and smoke from a structure,
replacing the escaping gases with fresh air. This exchange is bi-directional with
heat and smoke exhausting at the top and air flowing in towards the fire at the
bottom. The fire will pull the additional air flow into the building towards the
fire which can intensify the fire conditions. This exchange can occur by
opening doors, windows or roof structures. Coordinated and controlled
ventilation will facilitate quicker extinguishment and limit fire spread.
Ventilation A fire in which the heat release rate and fire growth are regulated by the
Limited Fire available oxygen within the space.
Ventilation The appearance of the fire building’s ventilation points showing the flow
Profile paths of heat and smoke out of the structure as well as any air movement into
the structure.
Ventilation for The controlled and coordinated ventilation tactic which should coincide with
Extinguishment the Engine Company extinguishment of the fire.
Ventilation for The controlled and coordinated ventilation tactic performed to facilitate the
Search movement of a firefighter into an area to conduct a search for victims.
99
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
1. INTRODUCTION
1.1 Saving lives is the primary mission of the FDNY. The best lifesaving tactic we have is a
systematic search plan, coupled with rapid water on the fire. Search and rescue are the most
important tasks the firefighter performs during a fire.
“When a fire progresses past the incipient stage, the fire area must be considered an
IDLH atmosphere. Every member entering the IDLH must be using all personal protective
equipment and a self-contained breathing apparatus. No member shall enter an IDLH
atmosphere unless the member teams up with at least one other member and remains within
visual or voice contact with that member.”
“Two members must team up prior to entering an IDLH (Two-In) and there must be at least
two other members outside the IDLH (Two-Out) who are designated as a Safety Team. The
members of the Safety Team shall be available to assist the interior team(s) if the need arises.
If a member leaves a contaminated area, another member using an SCBA must
accompany this member to a safe area.”
“If a known life hazard is found and immediate action could prevent the loss of life,
appropriate action (rescue activity) may be taken by an individual member. This applies only
for a known life hazard, not for standard search and rescue activity. If such action is taken,
the Incident Commander must be immediately notified and appropriate adjustments
made.”
1.2 This training bulletin will make members aware of the various actions involved in a
systematic search and the techniques that will help make conducting a search thorough and
relatively safe for members.
1.3 There are many different types of structures within the City of New York and in some of
these structures the areas of search responsibility differ. However, the information and
techniques presented in this bulletin are applicable to any type of structure or occupancy.
1.4 A coordinated, concentrated team effort is required of all units conducting searches to
ensure a proper, prompt search and removal of all endangered occupants. Refer to the
Firefighting Procedure Manuals for specific areas of responsibility.
1.5 The strategies of search never change in that the FDNY always strives to conduct an
immediate primary search, followed by a painstakingly complete secondary search. The
tactics used in performing the searches evolve with the changes in construction and fire
dynamics. This bulletin will describe the concept of search and offer techniques that can be
applied to the vast variety of situations and occupancies found in NYC.
100
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
2. FIRE ENVIRONMENT
2.1 Conducting a search in the modern fire environment has added many challenges to the fire
service. The increased use and amount of synthetic contents found in all buildings is one
challenge presented. Synthetic materials have a higher heat release rate (HHR) giving
off heat more quickly than ordinary combustibles, leading to a more rapid and sudden change
in the fire environment. Fires today develop faster, producing thick black smoke, which
greatly reduces the searcher’s visibility. This is why Thermal Imaging Cameras (TIC) have
taken on a greater importance when conducting searches.
2.2 Fires involving modern synthetic contents coupled with new building construction
methods that contain the heat and smoke within the fire area, may quickly become a
ventilation limited fire that will react rapidly once a door is left open or other parts of the
occupancy are ventilated allowing air flow into the fire area. These openings will
provide enough air flow that may rapidly expand the fire condition and extension,
causing conditions to become untenable in as little as 1 1/2 minutes after entry (ventilation) is
made into the fire apartment or area. It is critical for Company Officers to control all
ventilation tactics, including doors to and within the occupancy. The tactic of venting as we
search can have severe consequences with modern synthetic contents.
2.3 Today’s fire conditions lower the survival threshold of civilians as well as decreasing the
amount of time needed to safely perform a search without an operating hoseline in place.
Bunker gear, while providing better protection, is totally encapsulating allowing
members to search deeper into an IDLH. For safety reasons, members need to be constantly
aware of the search environment including the status, location and operation of all hoselines.
3. DEFINITION OF SEARCH
3.1 A search is an orderly and systematic examination of a building or area for the purpose of
locating persons, or locating fire and extension of fire.
Note: This bulletin will deal primarily with search for persons, in order to save lives.
4. SIZE-UP
4.1 Size-up starts with the receipt of the alarm. The teleprinter or MDT dispatch message
shall be checked for Critical Information Dispatch System (CIDS). The information provided
by CIDS will enhance operational efficiency by alerting units to dangerous, hazardous or
unusual conditions which are not necessarily apparent from the front of the building.
101
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
4.2 Upon arrival, take the time to orient yourself on the fireground. The need to take
adequate time to perform a size-up to determine the occupancy type and the expected life
hazard, before attempting a search, cannot be over emphasized. All affected areas within the
fire building should be searched within the limits of safety.
4.3 Searching members must understand that the degree of aggressiveness incorporated into a
search for life must be dependant upon several factors, some of which are:
• What is the structural stability of the building?
• What is the ventilation profile of the fire conditions, (the location and movement of any
smoke and fire into and out of a structure)?
• Are there reports of a life hazard?
• What is the stage of the fire development and what will be the effects of any
ventilation?
• What is the tenability of fire conditions within the occupancy?
• What is the status of the water supply and the position of charged hoselines?
• What are the rewards and benefits to the searchers in relation to the risk and
consequences of their actions?
Members engaged in searches must continually assess these factors by monitoring
handie-talkie transmissions and through personal observation.
4.4 Consider how the heat, smoke and fire will extend within the building. Occupant egress
from the building (interior stairs, fire escapes, etc.) can be quickly impacted by the fire
conditions, negating their use and endangering occupants.
4.5 Members must include the buildings configuration as part of their size-up. The benefits
gained by observing construction features of the fire building (types of construction, window
layout, presence of window bars, access and egress points from the building, is the building
built on a grade, etc.) may give members an idea of the floor layout inside a residential
building. This may help members determine how many apartments are on each floor and
the floor plan of the apartment (ex. Railroad flats). Prior to reaching the fire floor,
knowledge can be gained from conducting a survey of the floor below to determine the
interior hallway layout, apartment numbering system, floor plan of the apartment, and closest
means of access to a fire apartment. Information from this survey shall be communicated
between the Officers and the Incident Commander (IC).
4.6 It is critically important to take into consideration the effects of the wind direction and
velocity on fire conditions, especially when windows are open or failed. Direct or
gusting wind may suddenly increase the fire conditions and fire growth within the structure.
As part of their size-up, members of the outside team must report wind
conditions and its affect on the fire and smoke conditions to their Officer and the IC. Alternate
strategies and tactics shall be considered when the ventilation profile and interior
conditions indicate the potential for a wind impacted fire.
102
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
4.7 Take into account the time of day and consider the following:
• It can be assumed there will be a large number of sleeping occupants in a multiple
dwelling at night.
• Commercial buildings may have watchmen or cleaning personnel working after
normal business hours.
• Commercial loft buildings may have been converted into residential buildings.
• Office buildings often have cleaning and maintenance people present day and night.
Computer personnel are often present 24 hours a day.
• It cannot be assumed no one is present inside taxpayers that have roll down security
doors with padlocks in place. Many times people are padlocked in to provide
security at night.
4.8 Information about the location of the occupants and reports of any missing occupants
must be obtained early in an operation. It is critical to ascertain if all occupants have
evacuated or if any occupants are reported trapped or missing. Obtain information on who
is missing and their last reported location including the access to their location. Ask occupants
if they had anyone visiting and staying with the family. Verify if a report of a trapped victim
is a person or a pet.
4.9 Be aware of smoke spread that can be affected by air conditioning systems and vent
shafts in kitchens and bathrooms.
4.10 In retail establishments all areas must be searched for occupants with particular attention
given to the rear and main selling area. Be aware there may be accommodations in the
store for employees to rest or sleep.
4.11 It is important for an engine company to realize that a properly positioned hoseline will
contain the fire, possibly saving civilian lives and protecting firefighters who are
searching both the fire floor and the floors above.
Note: Only in extreme cases should an engine company become involved in search and
rescue without simultaneously stretching and positioning a hoseline.
5. TYPES OF SEARCH
5.1 Upon arrival at the fire building, members must perform search activities with two
objectives:
• The location of any life hazard
• The location of the fire
103
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
6. PRIMARY SEARCH
6.1 A primary search is the immediate search for life. This search is rapid but thorough and
systematic. The primary search will be influenced by the fire, heat and smoke conditions
in a room or area, and may be prior to the application of water. It should be done
quickly, with due regard for your personal safety.
6.2 Usually the 1st arriving ladder company is responsible for the primary search on the fire
floor or fire area, and the 2nd arriving ladder company is responsible for the primary
search on the floors above.
6.4 The search for life in the areas adjacent to or above the fire area/floor, should start
immediately upon entering the area, followed by searching for the extension of fire. Any
extension should be immediately reported to the IC.
6.5 Depending on the type of structure, the second arriving ladder company may be assigned
to assist the first arriving ladder company with the primary search on the fire floor.
In these situations, the IC shall assign additional units to the floor(s) above.
6.6 When both of the assigned ladder companies arrive at almost the same time but out of
response sequence, their responsibility for search shall be guided by their response
assignment. This avoids confusion and ensures that the fire area and the floors above are
covered. If units operate out of the assigned response sequence then the IC must be
notified.
6.7 The IC shall have a primary search of elevators conducted early in an operation.
104
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
7. SECONDARY SEARCH
7.1 The secondary search is a thorough and painstakingly complete search for life of all areas
that required a primary search. In addition, the secondary search must also include the
entire outside perimeter of the building and all shafts, basements, cellars, elevators, roofs,
etc. Its purpose is to ensure that no possible victims are overlooked. Time is not as
important as accuracy.
7.2 A secondary search shall be completed before any extensive overhauling of the fire area
is attempted.
7.3 A secondary search must be performed by a different company than the company which
performed the primary search.
.
8. COMMUNICATIONS
8.1 Communication between all members and the need to monitor communications when
conducting a search is imperative to improve the safety and efficiency of operations.
Effective communications include the following:
• To ensure the safety of the interior team, the outside team must report exterior
conditions, including the effect wind is having on the smoke and fire. The exterior
size-up must be relayed to their Officer, the IC or Sector Supervisor (if implemented).
• Officers shall communicate with the members of the outside team to determine their
location and areas they are searching, and require them to maintain contact with the
interior search team to ensure the outside members’ safety and team integrity.
• Members conducting searches will maintain situational awareness by monitoring
handie-talkie transmissions, especially the status of the water supply and position of
operating hoselines.
105
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
9. SEARCH TACTICS
9.1 The Ladder Company Officer must supervise searches by controlling both the interior
and exterior search teams. This Company Officer is responsible for maintaining the
search team integrity. The failure to maintain search team integrity may lead to serious
injuries and fatalities during operations. The interior team search is controlled by
immediate supervision via verbal communication and the use of the Thermal Imaging
Camera (TIC). The exterior team is supervised through functional supervision by
tracking the member’s progress via handie-talkie reports.
9.2 All search teams must have a plan in order to complete an effective search. A plan will
enable members to achieve the main objectives of searching for life hazards and the
location of fire. Members shall always remain cognizant of their surroundings by making
a mental note of point of entry and any secondary means of egress that are passed during
their search.
Members can orientate themselves within the occupancy by:
• Knowing the exposure from which the member entered the building;
• Conducting a survey of the floor below;
• Knowing what floor the member is on, the number of the apartment the member is
searching in, and the room the member is searching;
• Noting landmarks (radiators, large furniture, etc.) within the search areas;
• Making a mental note of the floor plan as members move through the search area.
Maintaining situational awareness will enable members to perform a thorough and
systematic search, allowing them to maintain contact with other members searching and
provide details of their exact location in case the need for assistance should arise.
106
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
9.4 Prior to forcing an entrance door to a fire occupancy, the Ladder Company Officer shall
determine:
• Is there a report of a life hazard?
• Are interior conditions tenable to sustain life or to conduct a search for life?
• Are all members in proper PPE?
• What is the location and status of the charged hoseline?
• Who is the member to remain at the door if the interior search is to be conducted
without an operating hoseline in place?
• What will be your area of refuge, if needed?
9.5 Gaining access to the fire area, or area to be searched, will usually be through the main
door that the occupants use. If there are indications of fire on the other side of the door,
do not stand in front of the door when opening it. Stay to one side, keep low and then
open the door. If fire is wrapping around the door jamb as the door is being forced open,
a hoseline must be charged and in place at the door before the door is opened. This may
also indicate that a window has failed and that wind is forcing the fire toward the
occupancy entry door. The Company Officer shall contact the exterior team for their
size-up if it has not been communicated. Evaluate the interior and exterior size-up and
determine if an alternate means of attack and access to the fire area is necessary.
9.6 The area in the vicinity of, and behind, the entrance door must be checked as soon as
entry is made. People may have tried to reach a means of egress and may be unconscious
near or behind the door.
9.7 If a door opens easily at first and then is stopped by something, reach around the door to
determine if the obstruction is an unconscious person.
9.8 Upon entering the occupancy, do not let a door lock behind you. Set the lock or put a
large sure search door marker over the latch and around both knobs (See Training
Bulletin Tools 19). Upon entering any IDLH area, all searches shall be conducted with
members at the floor level.
9.9 When unable to enter due to severe fire conditions, probe the area in the vicinity of the
door with a hand or tool before closing the door. Maintain control of the door. Once the
engine company has a charged hoseline and is ready to advance, move in behind the
nozzle team to start the search for life.
9.10 Door Control: The opening or forcible entry of the entrance door to the fire area is not
just a point of access or egress. But equally important, it is a ventilation point creating a
flow path for fire, heat and smoke. This ventilation point allows both the heat and smoke
to flow from the fire area and also provides a fresh in-flow of air at the floor level from
the exterior to the interior of the fire area.
107
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
The contemporary contents of today’s occupancies burn quickly and become ventilation
limited. These fire conditions lack sufficient oxygen to further expand the fire. The
inward flow of air from the door opening may be enough to cause a rapid expansion of
fire conditions and limit the time for an effective search. It is critical to the safety of the
occupants and the members conducting searches, that we control the entrance doors until
a charged hoseline is in position to operate.
9.10.1 A determination must be made as to whether the door will remain open or closed
while the search is being conducted. The determining factor is whether or not the
engine company has a charged hoseline and is ready to advance into the fire
area/occupancy.
a. If the engine has a charged hoseline, the door to the fire area will be left open.
A member of the ladder company shall chock open the door to facilitate the
advance of the hoseline.
b. If the engine does not have a charged hoseline at the door to the fire area, the
door should be closed after the search team enters. Before entering, the
Ladder Company Officer shall communicate the identity of the fire apartment
to the IC and Engine Officer. A firefighter of the interior team must be
positioned at the door inside the fire area to maintain control of the door until
a charged hoseline is ready to advance through that door. The Ladder
Company Officer and the other member of the interior team will search the
fire area. The interior team shall leave the hydraulic forcible entry tool
outside the doorway to indicate the apartment they are searching. The Ladder
Company Firefighter at the door will:
1. Maintain control of the apartment door to control the flow paths of heat
and smoke.
2. Make sure the door doesn’t lock behind the interior team by setting the
lock or using a large sure search door marker.
3. Monitor conditions in the immediate entrance area that may affect the
safety of the interior search team.
4. Monitor handie-talkie transmissions to maintain situational awareness,
especially reports of water problems, and wind conditions and its effect
on other ventilation points, to ensure the safety of the members searching
the fire area.
5. Act as a beacon to guide the searching members back to the door, if
necessary.
6. If members are forced to evacuate, account for the interior team and close
the door after all members have exited the apartment.
Note: The door should be closed after the search team enters to prevent the creation of a
flow path from the fire area towards the door and eventually into the public
hallway and stairwell. A wind condition created by a failed or open window may
increase the negative effects of flow paths within the fire area.
108
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
The Ladder Company Officer must notify the Engine Officer and the IC of the
decision to close the door.
Once the engine company reaches the apartment door with a charged hoseline, the
Engine Officer must notify the Ladder Company Officer of their readiness to
enter the apartment and that the apartment door will be opened. The door should
not be opened until the Ladder Company Officer acknowledges and approves.
9.10.2 Attempt to locate and confine the fire to the area of origin until the hoseline is in
position to reduce the number of people endangered. Once the fire area has been
determined, it should be confined by:
• Closing an open door to the fire apartment, to gain control of the public
hallway and stairs.
• Closing the door to a fire room to prevent a flow path for the fire toward the
apartment door when the hoseline enters the apartment.
Note: The water extinguisher may enable members to get close enough to close an
apartment or room door, thereby confining the fire.
109
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
9.12 When unable to enter through the window due to severe conditions, probe the floor area
immediately inside the window with your hand or with a tool.
9.13 When a known life hazard exists and entry through a door or window to the area to be
searched is not possible because of fire, it may be advisable to seek another or alternate
means of entry. An example of alternate means of access is breaching a wall to enter the
fire area or room from an adjoining apartment.
9.14 The public hallway and the entire staircase up to the bulkhead door must be examined for
those civilians who unsuccessfully attempted to use the interior stairs to escape from the
fire or smoke.
10.1 Gaining access to the floor above in many types of structure can be extremely difficult
and can place members in a dangerous position. Initially, this may not always be
attainable, but an attempt should be made while always keeping safety in mind.
Company Officers must evaluate the risk of going above a fire without a protective
hoseline and determine the benefits and consequences. A thorough size-up of the
conditions on the fire floor shall be performed before going above the fire. When
deciding whether to go above, consider the following:
• What is the location of the fire?
• Do they have control of the door to the fire area?
• Do they have a charged hoseline on the fire floor?
• Is the hoseline advancing into the fire area?
• Are there water problems?
• Is there a need for protection with a hoseline above the fire floor?
Note: When assigning an Engine Company to stretch a hoseline to the floor above the
fire, the IC shall give that Engine Company’s identity to the units operating on
that floor.
10.2 Prior to proceeding above the fire, notification must be made to officers on the fire floor.
Acknowledgement of this message must be received before proceeding above. This is
necessary to ensure that the officers of units operating on the fire floor will know who
must be notified of any situation necessitating their withdrawal from the floor above.
10.3 Once determined that access to the floor above can be safely attained, get up and off the
stairs immediately.
110
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
10.5 Upon reaching the floor above, the officer must consider forcing a door to an apartment
other than the one directly over the fire, to provide an area of refuge in the event the
conditions deteriorate. If an area of refuge is to be made, ensure that the door is closed
and unlocked, so as not to create an additional flow path for smoke, heat and fire.
10.6 When conducting a primary search above the fire, it is vital that members continually
assess their location in relation to both your primary and secondary means of egress in
the event that conditions deteriorate requiring an evacuation. Situational awareness is
crucial to the safety of all members, especially those operating above the fire. The
progress of the hoselines on the fire floor below must always be monitored and used as the
indicator governing how far the searching members will continue to advance on the floor
above the fire.
11.1 The Thermal Imaging Camera (TIC) is a valuable tool that can be used for many
operations. TICs may be especially helpful in the low visibility environment of today’s
structural firefighting. TICs provide a pictorial representation of temperature differences
that are unaffected by smoke. Basic knowledge of thermal imaging, understanding the
functions and use combined with disciplined tactical applications are essential in utilizing
the TIC to its fullest potential.
11.2 TICs provide a new perspective of the fireground that can be very beneficial to the safety
and efficiency of operations. When the images presented are properly interpreted,
operators may utilize the information to assist in making decisions regarding firefighting
tactics, firefighter accountability, victim searches and directing interior operations. The
company officer responsible for directing searches is best suited to carry and operate the
TIC.
11.3 The TIC is only a tool and shall be used as an adjunct to, not a replacement of, the
established firefighting search procedures and practices already in use.
11.4 TICs must be carried by Ladder Company Officers and used at all structural responses.
At all times, the TIC shall be used in conjunction with a systematic search plan allowing
Ladder Company Officers the ability to maintain a supervisory role of members involved
in the search.
111
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
11.5 When confronted with smoke conditions negating visibility, a TIC can give the Ladder
Company Officer the capability to visualize the convection and radiant heat waves being
generated by the fire and can visually provide an early warning of a rapidly expanding fire.
11.6 All members shall refer to Training Bulletin Tools 27, Operation of the Thermal Imaging
Camera, for more information on the use and limitations of the TIC.
12.1 Always be alert for sounds of a trapped victim (e.g., coughing, moaning, or crying).
12.2 Sweep beds and couches from front to back. If a person is found on a bed, give an extra
sweep as there may be more than one person on the bed.
12.3 Check the areas between the bed and the wall, and between 2 beds pushed together.
12.5 Look under beds and behind furniture for trapped victims.
• Try to avoid moving furniture, as it may hide a victim or block a doorway to an
adjoining room by doing so.
• To find out whether there is a victim under a bed, probe with an arm, tool, or insert a
leg under it and sweep gently back and forth.
12.6 Be sure not to pass the upper levels of double and triple-bunk beds, which are well above
the floor. The extremely low level of the mattress on the lower part of the bunk bed will
alert you to search higher.
12.7 Narrow tapered legs (with wheels) will probably indicate a crib.
12.8 Thoroughly search all piles of clothes, draperies, or bed linens. The removal and
dropping of window draperies may have covered a victim.
12.9 Check all dresser drawers, toy chests, refrigerators, and closets for victims. Children
often seek refuge in such places.
112
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
13. RESCUE OF VICTIMS
13.2 Attempt to remove a victim via the safest route available. The preferential order of
removal is:
• Interior Stairs
• Horizontal Exits
• Fire Escape
• Ladders
• Life Saving Rope
13.3 Most fire victims found during primary searches are usually found in these areas:
• Within the area of fire origin.
• In a path leading from the area of fire origin towards an exit.
• In the apartment or occupancy directly above the fire in non-fireproof multiple
dwellings.
• On the top floor of non-fireproof multiple dwellings.
• In hallways and stairways in fireproof multiple dwellings.
13.4 Members must communicate that they have located a victim by transmitting signal 10-45,
the location of the victim and if assistance is needed. Always remove a victim via the
safest route available.
13.5 Ambulatory victims are those that can assist themselves in their own removal. They may
hesitate or want to return for valuables, pets, etc. Members must be firm, authoritative
and direct these victims to a place of safety before returning to complete the search.
Ambulatory victims should be removed or directed from IDLH areas. The IC should be
notified of any ambulatory victims that are evacuated from the IDLH area.
13.6 Non-ambulatory victims cannot assist in their own removal. They may be aged,
infirmed, obese, small children or unconscious. Members may require assistance and
should use their handie talkie or notify nearby members for assistance. Whenever any
member removes a non-ambulatory victim, the victim must be removed to a non-IDLH
area. When required, the rescuer shall provide medical treatment until the arrival of a
CFR Engine or EMS. Keep the IC aware of the location of any victim.
13.7 A search is not complete just because a victim is found and removed. There may be
other victims within the occupancy and all rooms must be searched. The IC needs to
ensure that all areas are properly searched.
113
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
14. CONCLUSION
14.1 This bulletin is not to be considered all-encompassing or meant to cover every possible
situation. However, the material included has been learned from many years of
experience and should prove valuable to members.
14.2 It is of the utmost importance that all members are familiar with the types of buildings
within their response area. Knowledge of building layouts and occupancies can be a
firefighter’s greatest asset when conducting searches.
114
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
FIGURE 1
Key Points for Searching
115
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
Figure 2
SEARCHING HINTS
Typical Tenement Floor Plan
Fire
Escape
A locked bathroom door is
usually an indication that Where there are two doors
Entry through a to an apartment the one in
breached partition is someone is inside
front is often blocked.
often prescribed when
entry at the door is Every door in the apartment hall will
thwarted by heat and have to be opened so a search can be
smoke made. Be sure to check closets as
well.
Escape Routes
Proper operation at an intense fire in an Old Law Tenement generally requires that a part of the
operating forces be in severely exposed positions if we are to properly perform our search and or
rescue mission. The fire condition also requires the ladder chauffeur to remain in front of the building
with his/her apparatus anticipating the location of other members and be prepared to position the aerial
ladder to provide egress for them when necessary. This, in addition to the member’s other previously
assigned duties. If early extinguishment is not accomplished, these members will have to withdraw by
means of interior stairs, fire escapes or ladders. When these means of escape are cut off an emergency
means will have to be considered, such as breaching a wall or partition to an uninvolved area or to a
safe means of egress.
116
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
In Old Law Tenements, the infrequently used procedure, of going from front to rear
apartments or vice versa through the common partition may also be used as an escape route.
To accomplish this:
1. Use the halligan, hook or axe. This is the order of preference but all can do the job.
• It is easier to push the opposite side of the wall off the studs
3. The tool is placed in a bay with the bottom anchored against the opposite side of the
partition. The firefighter then pulls the tool towards themselves using short strokes to
snap the lath off on their side. Best results are obtained when the opposite side is kept
intact until near side is completely removed.
4. With the sole of his/her boot, the member can kick the lath off the far side of the bay
5. The member then uses the Swim Move or the Reduced Profile Maneuver and quickly
moves through the opening.
117
FDNY Probationary Firefighters Manual
Chapter Sixteen SEARCH
118
FDNY Probationary Firefighters Manual
Chapter Sixteen OVERHAULING
OVERHAULING
119
FDNY Probationary Firefighters Manual
Chapter Sixteen OVERHAULING
120
FDNY Probationary Firefighters Manual
Chapter Sixteen OVERHAULING
OVERHAULING
The term overhauling shall include any opening up of walls, ceilings, partitions,
voids, etc. while checking for extension or to extinguish fire during the pre-control as
well as during the post control phase of operations. Proper overhauling will expedite
final extinguishment and minimize damage to the structure and its contents.
PRECONTROL - Search for fire and extension which takes place up to the point where
the fire is under control. Pre-control overhauling begins as soon as possible after the
fire has been knocked down.
POSTCONTROL - The continued operation that takes place after the fire is under
control to ensure that there is complete fire extinguishment.
1. After the fire has been knocked down it is the responsibility of the first ladder
company to arrive to determine if the fire is extending and where it is extending.
This information should be transmitted to the Incident Commander and the ladder
company on the floor above.
2. The ceiling should be opened first by starting at a point where the fire was most
intense and working towards a clean area of ceiling space. The ceiling light
fixture area should be pulled and examined.
4. Fire that is found in ceiling bays or adjacent to steel beams that cross over
partitions separating other uninvolved rooms or apartments must be inspected by
pulling ceilings.
5. Boxed out protrusions: These boxed out voids can contain pipe risers, electric
conduit, chimney flues, steel columns or sealed dumbwaiter shafts which run
from the ceiling to the cockloft.
6. Steel Columns: Steel columns and beams can be found in N.L.T. or O.L.T. Boxed
out areas around a steel column create a natural void. If a boxed out protrusion
on a wall contains a steel column and was involved in fire, then the entire length
of this void will have to be examined. Particularly its highest point, the cockloft,
will have to be inspected. Also, burning embers can easily drop down this void
and start a fire on the lower floors.
121
FDNY Probationary Firefighters Manual
Chapter Sixteen OVERHAULING
8. Walls: Wall switches, receptacles and fuse boxes (circuit breakers) are locations
for fire to enter and travel. Especially when burning furniture is against the wall.
9. Floors: The flooring in the fire area must be checked. If the flooring is charred,
the ceiling below should be examined for fire extension.
Beams in Old Law Tenements generally run parallel to front and rear walls.
Lath is attached at right angles to the beams and runs front to rear. Each piece of
lath usually covers two or more bays. The ceiling is penetrated with one firm
stroke with the hook end parallel to the lath. This breaks only one lath on
the upstroke instead of two or three. The hook is then turned to form a
right angle to the lath and the ceiling is pulled with short, sharp strokes close
to the beam. This method is fast and conserves energy. The firefighter should
not stand directly below the ceiling being pulled. They should keep the work
in front of them. In close quarters firefighters shall keep their heads down to
prevent injury. Eye shields shall be used.
NOTE: When pulling sheet rock ceilings, be aware they may fall in large heavy sections.
Figure 1
Figure 2
122
FDNY Probationary Firefighters Manual
Chapter Sixteen OVERHAULING
B. To make a hole high in a sidewall or partition of lath and plaster
(Figure 2). This requires a sharp blow with the hook. After penetration
with the hook, the tool is used to pull down or pry out if leverage is
possible.
Figure 3 Figure 4
C. To make a hole low in a side wall or partition (Figure 3). The hook
is held like a javelin before penetrating the wall. After an opening has
been made, the hook is then pushed down behind the lath and the
lath is removed by pulling the handle. This should open the wall to
the floor or baseboard. When prying with the hook, excessive strain
which may break the wooden handle must be avoided.
D. Use the handle of the hook, or the point to make small probing holes
to check for extension or to allow water to flow out as opposed to
pulling (Figure 4).
123
FDNY Probationary Firefighters Manual
Chapter Sixteen OVERHAULING
TRIMMING A WINDOW OR DOOR
The trim around windows and doors is put on last during the construction
stage and should be the first pieces removed if examination is required at these
points. Removal of the trim is generally sufficient to allow an adequate
examination and application of water.
Depending on the tool being used, the most efficient and safest way to remove
the trim is to start at the top or bottom corner or joint and work along prying
the molding out from the wall.
OPERATIONAL NOTES
124
Probationary Firefighters Manual
Chapter 17
EMERGENCIES
17
THIS PAGE WAS INTENTIONALLY LEFT BLANK
EMERGENCIES
Section Title Page
1 WATER CONDITIONS ....................................................... 1
M ost of us, before we became firefighters thought that the Fire Department responded only
to fires. In reality we are present at every type of emergency situation that occurs in New
York City. These responses account for 21% or our turnouts- and in recent years 38% of
the work we do is of an emergency nature. The percent of people saved at emergencies from injury,
death, discomfort and even fire is probably higher than those aided at fires.
The Fire Department does not advertise but the public relies on us to solve any problems they feel
are dangerous to themselves, their families or property. Firefighters react to this with the
knowledge that often at inconvenient times, in inclement weather and without any thanks we are
professionals capable of remedying any solution. To enhance this ability we continue to study
those problems we may encounter.
1. WATER CONDITIONS
1.1 GENERAL OPERATIONS
♦ Determine the source of the leak and locate the corresponding water shut off
valve. Locate water shut-off: Possible shut-off’ locations include:
on the wall near the ceiling of the apartment directly below.
on riser line of apartments in basements.
Still no shut off; then locate where main enters building. Usually near
front building wall. (Often in a corner.)
♦ Pipe is coldest pipe in building and may also have condensation on outside
♦ Listen for sound of running water.
♦ Feel vibration.
♦ Armored ground cable may be attached to main from electric meter.
♦ Once valve is located, shut off clockwise.
♦ If water has leaked into an electrical fixture, turn off power at the fuse box or
circuit breaker.
1.2 WATER CONDITIONS: WATER LEAKS
♦ Leaking Sinks.
Possible actions:
Locate handle under sink.
Turn clockwise.
2
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Possible actions:
If shut off handle is accessible turn clockwise.
If inaccessible and tubing used then simply crimp until flow stops.
(Use pliers, tap with axe, etc.).
For non malleable metal use tapered piece of wood (shaved chock,
pencil, chair leg, golf tee, etc.
♦ House Main.
Frequently broken by scavengers collecting mungo for resale.
Action must be taken to stop water flow.
Malleable pipe (copper, lead): Strike with maul or flat head of axe until
sufficiently closed to stop water flow.
3
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Not Malleable: Insert rounded end of stick, chock, pencil, chairleg, etc.
to be used as a plug.
NOTE: It is sometimes helpful to use cloth on end of wood to aid in
sealing.
4
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
1.3 WATER CONDITIONS: FLOODED BASEMENTS
♦ Occupied building.
May cause problems with oil burner in building or in an adjoining
building. Children may be playing in area and could possibly be
drowned.
Actions to be taken:
o If location of drain is known then clear surrounding area of debris
and if possible channel flow towards drain. Look near shower or
basement sink for drain if location of drain is unknown.
o Remove the toilet bowl. This action will provide drainage. A
screen or wire basket will keep out debris.
♦ Vacant building.
Same actions as occupied building
Break into cast iron waste pipe at most convenient location with Halligan
and axe to permit water to escape. This location can be at ceiling level
depending on water depth.
CAUTION
Avoid areas of basements where electrical power may be on.
5
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
1.4 WATER CONDITION: Flooded Roofs
♦ Actions to be taken:
DO NOT CLEAR ANY BLOCKAGE WITH HANDS!!! Member's arm
can be drawn into drain. Deaths have resulted. Actual suction pressure
can be quite high.
Clear blockage with 6' hook or applicable tool from drain or scupper.
Using hose.
o Stretch entire length under water and allow to fill.
o Kink one end.
o Drape edge over parapet extending below roof level.
o Release kink.
6
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Alternate possibility: remove a brick at a low point on a parapet wall which will serve as a
scupper.
Each sq. ft. over 12" deep weighs 62 pounds. Use as few members as practical on the roof.
7
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
8
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
2. STEAM CONDITIONS
2.1 Radiator
Safety Valve blown off
Action:
♦ Shut down flow at the valve handle by turning clockwise
♦ Replace safety valve or plug with a wooden plug wrapped in cloth, tapping it in
until secure.
This is usually due to numerous operations of on and off flow. Generally it will be
nearby and undamaged.
Action:
♦ Make certain flow handle is in open position (this is important).
♦ Replace fitting to open piping by turning nut on in clockwise direction.
♦ After restoration of flow valve it may be turned off or on as necessary. The use
of a compound or sealant on threads may be beneficial in obtaining a seal.
Crayon, string, cotton thread or wax may be used.
NOTES:
1. Wear gloves.
2. Place towel over main valve to divert steam flow while resetting
valve.
3. It may be necessary to shut steam off at boiler.
9
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
3. ELECTRICAL EMERGENCIES
3.1 OVERHEAD ELECTRICAL SERVICE EMERGENCIES
When live electrical wires fall, they constitute a hazard to the public as well as
responding firefighters. It is essential for the Officer of the responding unit to make
a careful assessment of the risk to both civilians and members.
All Fire Department units are to treat downed wires as live wires until an on scene
utility company representative confirms that the wires have been de-energized.
There is currently no safe way for FDNY personnel to move energized power lines,
even if it presents a condition imminently dangerous to life.
Members shall not take any actions relating to removing electrical wires from
people and/or vehicles until wires are de-energized by the utility company.
Do not attempt to remove occupants from vehicles in contact with wires until wires
are de-energized by the utility company.
Do not attempt to move wires with any hook or rope.
3.2 WIRES DOWN IN THE STREET
3.2.1 Immediately upon confirming that live electrical wires are down and are
creating a situation that places life in danger:
[Link] The first arriving unit must contact the Fire Department Dispatcher
via Department radio indicating that life is in danger. Specify the
location (address, pole number) of the downed wires, and request
forthwith power removal and priority response by utility company.
[Link] Request response of Battalion Chief if not already assigned.
[Link] Responding Battalion Chief shall also contact the Utility Company
Electrical Operations Center directly by cell phone indicating that
life is in danger and request priority response. These telephone
numbers are found on the Con Edison notification cards distributed
to all Chiefs Officers.
3.2.2 In situations involving live electrical wires, which are down but do
not present an imminent life hazard, the Department can only guard against
the hazards of fallen wires by isolating the area, notifying the utility
company, and standing by until a utility company crew responds. It is the
utility company that will correct the problem.
10
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
The following are additional guidelines for the safety of all members:
♦ ACTIONS TO BE TAKEN:
Place a priority call to the Fire Department dispatcher for power removal.
Be sure to request that ALL electrical equipment at the station be deactivated
and request the immediate on site response of a utility company representative.
All electrical equipment at the station/substation is to be considered energized
until verification of power removal is made by the on site utility company
personnel.
11
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Unless human life is in jeopardy, do not enter substation until arrival of
power company representative.
Do not under any circumstances bring metal ladders or metal tools inside
of gate of generating station.
Do not enter fenced off areas without power company representative.
No ladders, metal or wood, should be supported by metal
superstructures.
NOTE: The metal overhead piping in a substation or rectified station
are "bus bars" and carry high voltage and/or amperage. These
may arc up to 18 feet.
3.4 OVERHEATED BALLAST:
♦ Flourescents:
How to identify.
Smoke emanating from fixture.
Smell
Flickering light.
Partial or complete darkening of bulb.
Presence of heat.
♦ Actions to be taken:
Shut off power.
Remove bulb.
Remove cover panel.
Disconnect wires to ballast (black box) and remove same.
Isolate black and white power wires and cover exposed ends with caps or
tape. Keep apart.
Check for any fire or smoldering in ceiling.
Overheated fluorescent ballasts may leak PCB-contaminated oil. SCBA
must be used while performing the above operations.
12
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Confirm the nature of the “gas” leak: is it natural gas, propane, or gasoline?
♦ Extinguish all sources of ignition.
♦ Ventilate the area if necessary. Be aware that if the gas/air mixture in the room is
too rich to burn, it will pass through its’ flammable/explosive range as you
ventilate.
♦ If the gas leak is at an appliance, the gas feed to the appliance should be shut off. If
that is not possible or the leak is elsewhere, then the gas supply to the
apartment or building must be shut down.
Most natural gas shutoffs are of the ¼ turn variety and can easily be shut off using the
fork end of a Halligan tool (Figure 1) ,vice grips or pliers to turn the wing cock valve
¼ turn counter-clockwise. Exercise caution when using the Halligan tool to shut the
valve as too much force could result in a new gas leak at the valve location.
Open Closed
Figure 1 Figure 2
13
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
If the appliance valve is defective or the leak is on the supply side of the appliance
valve, check for the presence of an Interior Gas Riser Valve in the basement/cellar near
the ceiling. This is a ¼ turn valve similar to the appliance valve and will disrupt less
service than closing a Master Meter Valve would.
Each occupancy may have its own meter and natural gas supply can be controlled using
the ¼ turn valve at this meter. This will shut the gas supply to the affected occupancy.
A Master Meter Valve may control the flow of natural gas to just a few appliances (i.e. in
a private dwelling), or to many appliances (i.e., in an apartment house). When possible,
avoid shutting the Master Meter Valve if it supplies many occupancies/appliances. A
Master Meter may have a second Master Meter adjacent to it. This second meter is used in
the event of a malfunction in the primary Master Meter in use.
Building Service Valve: This valve is found just inside of the building where the natural
gas service enters and will usually be a ¼ turn valve. When the meter or meters are
located outside, the valve will be before the meter(s).
Exterior Gas Riser Valve: Exterior Gas Riser Valves are ¼ turn valves located on the
natural gas riser outside of the building, before any exterior meters. All external meter
installations will have a riser valve installed prior to the meter. Each meter also has its
own shut-off valve (meter valve).
Although the FDNY is authorized to shut curb valves/service valves, it should only be
done as a last resort and in consultation with the Utility Company. Many valves are old
and require skill to shut to avoid breaking the valve.
The curb valve/service valve is usually found on the sidewalk side of the curb and shuts
the natural gas supply to the entire building. It is generally recessed in from the curb, but
may be in the street. It is usually covered with a 4” X 4” square or round, brittle concrete
or steel cover which may be sitting on top of a plastic or wooden plate. To shut the
valve, remove or break the cover and plate. (See Figure 3 and Figure 4)
14
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Figure 3
To operate the valve break the concrete covers remove the pieces and the wooden shelf, and use the
gas key which has been supplied to the various units.
Figure 4
IMPORTANT: When Fire Department personnel shut off a utility, or find a utility shut, they are
not to turn the utility back on! The utility company must be notified to restore service.
15
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
♦ If stove off then locate butterfly on piping or tubing at rear. Turn until butterfly
is perpendicular to flow of gas pipe (¼ turn.)
Occupant needs utility company check stove and restore gas.
NOTE: A liquid detergent brushed on area of suspected leak will bubble if
gas is leaking.
♦ Causes:
Usually occurs as the result of the occupant removing the plug in the old
gas supply line when installing a new fixture.
It can also occur because repairmen only used wax as a plug when gas
line use was discontinued, and this wax either melts or deteriorates over
a long period of time causing a leak.
♦ Possible actions:
Make certain area is ventilated.
If he has removed cap then replace same. If he has sawed into pipe then
shut off at service to apartment which may be in the apartment or in
basement.
NOTE: Service entrance is where gas, electric and water enter
building.
Occupant requires Brooklyn Union Gas or Con Ed to restore gas. Under
no circumstances should units restore service as there may be open pilots
or burners on elsewhere.
WARNING:
Gas piping is of small diameter and there is a possibility of it being
energized through faulty electrical connections. i.e., Someone may be
inadvertently using pipe as a ground.
16
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
• Locate gas shutoff at either boiler or at service entrance. Turn perpendicular
to piping (1/4 turn)
• Occupant needs Brooklyn Union Gas or Con Ed to restore gas
Often on arrival you have a heavy odor or visible smoke on scene which is usually caused
by delayed ignition.
Actions to be taken:
NOTES:
1. Be alert to other locations for switch especially if there is a
commercial occupancy on street floor.
2. It is helpful to turn on lights if possible.
♦ Fuse box.
Remove fuse.
Pull knife switch.
Switch off circuit breaker.
NOTE: Box is usually marked "oil burner." Power line can also be traced
from oil burner or switch.
Ignition component at boiler: Remove cover from component and place
non-conductor between contact points. (Small piece of wood, plastic,
rubber, cardboard, etc.
5.2 Fuel shut off:
♦ At tank (all tanks have shut off).
♦ At oil burner (with 275 gallon tanks).
♦ On preheat or #6 oil, turn gas off to preheater (1/4 turn) and also the electric.
17
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
♦ On boilers with larger than 275 gallon tanks there may be a shut off on the feed
line near the filter.
Caution: There is a very real danger of the flexible, thin wall gas line tubing to
the preheater melting or being disconnected. The gas/air mixture ignited by the
heat of the oil burner can result in an explosion in which members have been
injured.
6. VEHICULAR ACCIDENTS:
Actions to be taken.
6.1 Rope off and clear area.
6.2 Chock vehicle.
6.3 Keep apparatus out of immediate area.
6.4. Stretch and charge a line into position to protect a trapped victim.
6.5. If gasoline is leaking then battery should be disconnected, ground cable first. At
times, hoods, batteries and trunks are destroyed for no viable reason. Try to locate
key.
♦ Hydrogen is evolved when electric storage batteries are being charged. When a
firefighter attempts to disconnect a battery with a large metal tool he can
accidentally short the two terminals. The resulting sparks can ignite the
hydrogen in the battery causing it to blow apart.
♦ Shorting terminals is not the only way to produce a spark. Connecting or
disconnecting terminals can also create sparks. Turning off all current drawing
devices in the vehicle before disconnecting the battery will eliminate sparking.
It would also be safer to disconnect the grounded terminal first and to use a tool
small enough to avoid accidental contact across the battery terminals.
Note: Some cars have two batteries (Diesels) and some have battery in trunk.
6.6 Prevent movement of vehicle if victim is trapped.
6.7 Do not forcefully pull victim free as it may aggravate the injury. An examination for
bleeding and fractures should be made.
6.8 Prevent smoking at scene if gasoline is leaking or oxygen being used.
6.9 Request police for traffic and crowd control and EMS if services are required.
6.10 Special units can be called for their use of emergency equipment (Saws, Hurst Type
Tool, etc.).
18
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Catalytic converters can reach 2000° F, well above the ignition temperature of
leaves, grass, etc.. This must be considered when working near overturned vehicles
or using air bags. These high temperatures can cause severe burns and/or damage
air bags.
Note: If vehicle is to be towed, use a chain. A cable will store kinetic energy
and if cable snaps serious injuries can occur. If a link snaps there is no
violent whipping action.
19
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
7. SUBWAY EMERGENCIES:
This Department on many occasions will be called upon to operate in the track areas of
numerous subway and railroad systems that serve all areas of the City. Fires and
emergencies will occur on the elevated portions, in open cuts, in tunnels or stations. There
are general hazard prevalent in all systems, and some hazards peculiar to the particular
system.
Fire Department personnel will never be permitted to operate on track areas unless assured
that the power is off. This rule may be ignored only if life is in imminent peril and direct
and immediate action is required to save life. In the latter instance every possible precaution
should be taken to minimize the risk.
Types of Incidents:
♦ Fire in Station
♦ Fire on Track
♦ Fire in Car
♦ Emergencies – Medical
♦ Fire Related (Smoke-Panic)
Unit Operations
♦ Engine Companies shall not connect to a hydrant until the fire is located.
♦ Many operations will require more than one engine company due to long
stretches. All efforts will be concentrated on stretching and placing in operation
the initial line before back up lines are ordered.
♦ Whenever possible, small railroad tie involving ties of an elevated railroad shall
be handled by handlines operated from the street below.
♦ Most fires in a station are of a minor nature, e.g. rubbish fire in trash receptacle,
papers on railroad ties, or overheated ballast at station lights. These fires will
usually be controlled by a can.
♦ When a fire is located under the platform, members will not be permitted in
track area unless:
Power is removed.
Confirmation of power removal by F.D. Dispatcher.
Members are posted at each end of platform to act as safety people.
An alternate area of refuge is assured in case of train movement.
20
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Truck Chauffeur Bottom of subway entrance stairs. If the token clerk booth is within 50
yards of stairs to street, contact train dispatcher through the clerk. (There
is a telephone in the token clerk’s booth. Try to obtain additional
information for the Company Officer and Incident Commander). The
LCC should relay the token booth phone number to the Truck Officer in
case it is necessary to call the booth from a blue light telephone.
Outside Vent FF The foot of the stairs leading to the platform if it is within 50 yards of
the Chauffeur.
Roof FF Approximately 50 yards from the stairs on the platform for relay.
Engine Officer Approximately 100 yards (line of sight) from Roof FF on the platform.
Truck Officer To location of the fire.
Additional HT equipped members every 100 yards, if necessary.
♦ New York City Transit Authority has installed colored light globes in the post
lights at street entrances. The colored globes indicate entrance availability.
♦ There are two globe colors being used in these entrances:
GREEN Post Light: The stairway is open 24 hours a day. There will either
be a token booth clerk on duty or the station will have high entry/exit
turnstiles (HEET see photo 1& 1a) with an adjacent gate secured with an
FDNY 1620 lock.
RED Post Light: Token booth clerk may NOT be on duty and the stairway
may be closed some time during a 24 hour day.
If given a choice, the first point of access to a subway should be through an
entrance with a green globe, if possible.
A new replacement globe installed is a spilt type-the top half color denotes
the type of access and the bottom half is clear for better lighting of the
subway entrance.
21
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Photo 1 Photo 1a
All companies are issued Subway Emergency Keys. There are three different key
shapes and a pry bar on this tool. All the Subway lines (IND, BMT, IRT)
emergency exits can be opened with this one key. The pry bar end is used to lift the
emergency exit door, and to scrape out debris between the door and the door buck.
However, some emergency exit locks are now appearing with other than the
standard shapes. If this is the case, a pair of vise-grips or pliers will have to be used
to open the emergency door.
22
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
7.4.1 Officers shall insure that members use extreme caution, whenever operating in the
track area. There are many potential dangers located throughout the subway system,
that pose many tripping, slipping, and falling hazards, such as grates in the track
roadbed, grease, oil, water, steeldust, protruding items, and varied debris. Strict
enforcement of this item and those that follow will be the responsibility of all
Supervising Officers.
7.4.2 Contact with the third rail or the third rail cover must be avoided even when
power is confirmed to be off. Unexpected restoration of power must be anticipated.
Members crossing the third rail must not step on the third rail cover, but rather, over
it.
7.4.3 Always operate as if power is on and avoid contact or proximity to the third rail and
the third rail contact shoes. Even with power off there are elements within the
undercarriage electrical system that possess enough voltage to cause a shock.
Contact with any undercarriage electrical components must be avoided.
7.4.4 Whenever members are committed to a track area, firefighters shall be assigned in
pairs to act as warning guards. The Officer in Charge shall assure that they are
posted at the perimeter of an operation. Their primary function will be to warn all
operating members of unexpected train traffic.
7.4.5 A member directed to halt traffic shall use a light. The light is to be held chest high
and moved in a wide horizontal motion of at least four feet. Train Operators are
accustomed to seeing trackwalkers (inspectors) carrying lights. If this horizontal
motion is not used, the firefighter might be mistaken for a walker and the train will
not stop. Members must use extreme caution; stopping a moving train with a
light is not assured. They shall ensure themselves a position of safety and warn
any endangered members to stand clear.
7.4.6 All officers shall maintain strict control of the actions of all members of
their command. Limit the amount of personnel committed to the track area to the
minimum needed to accomplish the goal. Rarely does an entire unit need to be on
the tracks.
7.4.7 A pre-selected area of safety shall be a constant thought of all members for use
in an emergency situation.
23
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
The possibility of no clearance between a moving train and the sidewall is very
pronounced in some tunnel and railroad cut areas. The pre-selected area of safety,
minimum staffing and alert observers are essential in this instance. All items of
clothing must be fastened securely to prevent the possibility of loose clothing being
caught on a moving train.
Never assume power is off when railroad personnel are seen working on a 3rd rail.
They are trained and equipped to operate while tracks are "live".
Note: It is the constant awareness, preparedness, and paying attention to basics that have kept
firefighters alive.
24
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
The Power Removal Box may not necessarily be located under the blue light, but it
will be in proximity to it or across the tracks from it. This will require us to cross live
third rails and be subject to moving trains. The correct way to cross a third rail is walk
over it and not step on the third rail cover; it may fail from a person's weight if
stepped on. In those cases where the power removal box is across the tracks, consider
sending a member in another direction that does not require crossing the tracks.
Remember that the only reason for operating on track areas without the assurance that
power off is when life is in imminent peril and direct and immediate action is required
to save life. While awaiting the arrival of a hand line, there should be a dry chemical
extinguisher available to us at the blue light, but this may be missing due to vandals.
Whenever NYC Transit personnel determine that a Power Removal Box or the
Telephone is out of service, they will be covered with a bag to identify them as being out
of service. This bag will be white, with red lettering, and it will state “Out Of Service.
If a member encounters an out of service Power Removal Box, the member should use
the associated Telephone to contact the Rail Control Center (RCC) to request the removal
of power. The member must identify him/herself, state the reason that the power must be
removed, and remain on the phone until they receive confirmation that power has
been removed. All members are reminded that the use of a Power Removal Box to
remove power should only be used as a last resort, when there is an imminent life
hazard. The power limits associated with the activation of a Power Removal Box can be
very extensive and may result in many trains and passengers being needlessly stranded,
requiring assistance, evacuation, and thereby compounding the incident.
The activation of a Power Removal Box, or the use of the associated
telephone, does not alleviate the Officer in Command of the responsibility of
requesting and confirming the removal of power via Department Radio, with the
Borough Communications Office.
C. If the Truck Officer did not obtain the token booth telephone number prior to
proceeding to the location of the fire or emergency, the Officer can use any
blue light telephone to contact the Desk Superintendent. He shall request the
Desk Superintendent to relay the blue light telephone number to the FDNY
Borough Dispatcher, who shall relay the number to the Chief Officer at the
scene. The Chief Officer can then have the token booth telephone used to
call the blue light telephone to establish contact with the Truck Officer. To
use a token booth telephone, which is a conventional telephone, request the
token booth clerk to pass the telephone through the pass through
window. The Chief Officer can call the blue light telephone with his
cellular telephone from the street, but the token booth phone is the preferred
method. The blue light telephone does not ring, there is a buzzer mounted
on the wall above the telephone that will intermittently activate.
26
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
27
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
The Emergency Evacuation Device (EED) was designed by the New York City Transit
Authority’s Office of System Safety. EEDs are provided for FDNY use and are located
throughout the Transit Authority’s subway system.
7.6.1 DESCRIPTION
A. The EED is a yellow, 7-foot long device with steps on the front (Figure 1) and a
flat surface on the backside (Figure 2). A non-skid surface is applied to both sides. Each
unit weighs approximately 42 pounds.
B. These devices are constructed of fiberglass reinforced plastic and are electrically
non- conductive for use within the confines of the subway environment.
C. When positioned against the side or end doors of a subway car the EED will reach
the roadbed at approximately a 70° angle (safe for ascent / descent) and the steps will
provide a horizontal stepping surface (Figure 3). A notch cut in the beams on one
end of the ladder helps to anchor the EED in position against the car and or platform.
7.6.2 LOCATION
A. At underground and grade level stations, the EED is located at the first Blue
Light location south of the southbound platform (typically within 50 feet of the platform
end).
B. At elevated stations, the EED will be located in the area of the full time token booth.
C. An EED is located at the base of the emergency exit, at both ends of each under
river tunnel.
D. Keys to remove EEDs from their mounting brackets are available at every token booth.
E. In Staten Island, EEDs are located near Tower B, at the Saint George Rail Terminal
and near the crew quarters at the Tottenville Train Yard.
7.6.3 ACCESS
Metal mounting brackets are provided at each location and are secured with a corrosion
resistant padlock. If a key can not be obtained, the locks can be forced using
conventional forcible entry methods.
28
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
7.6.4 OPERATIONS
The Emergency Evacuation Device can be used in the following three ways.
A. When passengers are being evacuated to the roadbed, the EED is positioned
with the cut out against the edge of the car floor with the step side up. The
ladder provides a safe angle for most ambulatory passengers to descend, however
personnel must be assigned to both the top and the bottom of the ladder, to
provide assistance and stability to the passengers.(Figure 3).
B. The EED can also be used as an evacuation stair to access the platform level
from the roadbed.
C. When a rescue train is used, the EED can be positioned step side down, to
form a bridge between two adjacent cars. The flat surface provides a stable
platform to walk passengers from one car to another. Personnel must be stationed
in each car to provide assistance and stability to the passengers.
Figure 1 Figure 2
Figure 3
29
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Photo 1
When rail carts are transported to an incident, the following procedures shall be followed:
30
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Note: Proper usage of the yellow ratchet straps is essential to getting the rail cart to
location safely. Straps must be initially positioned to allow for free use of
ratcheting mechanism. This will enable member to properly tighten the
straps securing the unit to the apparatus.
Upper strap to
grab handles.
Lower strap to
lower tow loops.
Photo 2
Release Lever
Photo 3 Photo 4
Hook upper strap with carabiners on grab handles. Hook lower strap with carabiners
on lower tow loops (Photo 3).
To tighten yellow straps, pull release lever on ratchet handle and tighten ratchet. To
lock ratchet, pull release lever and bring ratchet handle to nested position (Photo 4).
Any engine company may be special called to transport a rail cart from the
quarters where it is stored to the scene of an incident. Laminated instruction cards
outlining rail cart transportation and use are attached to the rail cart hand truck.
Place each half of rail cart on track with the wheels on the rail cart positioned close to
the operator, with the operators facing each other (Photo 5).
31
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Insert handles into sockets on each half of rail cart sections, then secure with hitch
pin clips (Photo 6).
Photo 5 Photo 6
Using handles for leverage, have each member place one foot onto rail cart and raise front to
an approximate 450 angle, so that each connection point joins to one another (Photo 7). Raise
one section slightly higher than the other until pin seats into slot (Photos 7-8).
Photo 7 Photo 8
Slowly lower halves until they join together and lie flat onto tracks and the rail cart is in
position for use (Photo 9-10).
32
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Photo 9 Photo 10
33
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
One wheel is provided with a wheel lock (slide bolt). A red square is painted on the
surface corner of the rail cart to denote the location of the wheel lock (Photo 11). Once
assembled, the member can use the wheel lock to secure rail cart from rolling.
Note sliding
bolt and wheel
receptacle.
Photo 11
Two rail carts can be connected together using the connector plate (Photo 12-13).
Photo 12 Photo 13
Tools, equipment or non-ambulatory victims may be secured to the rail cart using
supplied elastic cargo net, red cam buckle straps, or utility rope utilizing clips positioned
around the rail carts edge (Photos 14 – 17).
34
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Photo 14 Photo 15
Photo 16 Photo 17
7.7.3 DEPLOYMENT
Upon arrival at the incident, the officer shall report to the Command Post and inform the
IC of the availability of the rail cart. Members shall remove the rail cart from the
apparatus and prepare for ground transport. When ordered to deploy the rail cart, the
officer shall determine the best access point and order the members to transport the rail
cart to the scene using the hand truck. Every effort should be made to keep the rail cart
packaged together. When necessary, individual components from the hand truck can be
separated, and then carried to the designated area.
35
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Deployment of rail carts needs to be part of a carefully developed plan. For example, setting
up a rail cart prematurely on tracks being used for the evacuation of ambulatory civilians
may hinder operations. Likewise, rail carts cannot be moved both ways on the same tracks
simultaneously. The operational plan needs to consider how many rail carts and what
equipment needs to be transported to the incident scene. When all rail carts have been
moved to the scene, they can then be used in reverse order to remove non-ambulatory
victims.
Avoid allowing equipment to extend beyond the sides of the cart to prevent contact with
tunnel walls or the third rail. Likewise, stretchers and stokes baskets should extend over
the front and rear of the cart, instead of the sides.
When there is a heavy load or when used on a steep grade, the cart should be pushed by or
pulled by two (2) or more members. Utility ropes and/or straps may be used to increase
control.
A connector plate is supplied to join two carts together. Joining carts together with
connector plate might be useful at large incidents.
Rail cart sections are color coded for mounting back onto hand truck. Hand truck has a
specially designed “step plate” to accommodate the cart sections.
Place rail cart sections on hand truck as per color coding (Photo 18):
B. Place second cart section onto the hand truck with diamond plated in and
the painted side-beam facing up. Correct placement will have all color coding
matched up – orange on cart section to orange on hand truck and cart
section(orange and green) to cart section(orange and green).
C. To ensure proper nesting of two cart sections onto the hand truck, the wheel
of the inner section (green marking) must be lifted while the outer section is seated.
D. Secure to hand truck with red cam buckle straps (Photo 19).
36
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Photo 18 Photo 19
E. Place handles between hand truck and cart sections (Photo 20).
F. Tie handles to cart, using slack from red retraining straps (Photo 21).
Photo 20 Photo 21
7.7.5 TRAINING
Company Commanders shall ensure that all members are familiar with the storage and
operation of rail carts.
Two rail carts will be available at the Bureau of Training, for use at the subway training
module.
Additional instructions on how to assemble the rail cart can be found on laminated
instructional guides attached to rail carts.
37
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
7.7.6 SAFETY
Operating on rail tracks is inherently dangerous. Use of rail carts, while necessary, has
the potential to increase this danger.
The wheel lock must be engaged when the cart is left unattended. This is especially
important when a cart is operated on a grade, is loaded with patients, or carrying
equipment.
38
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
7.8.1 INTRODUCTION
[Link] Sound powered telephones (SPT) provide a hard wired means of voice communication
without the need for a power source. Sound powered telephones contain electro-
mechanical transducers that convert voice directly into electrical energy. This signal is
sent down a two-wire line and converted back into voice at the other end. Sound
powered telephones are a more sophisticated mechanical version of two tin cans
connected by a string and are capable of transmitting clear voice communications over
distances up to five miles.
[Link] FDNY sound powered telephone equipment is used primarily in New York City Transit
(NYCT) stations and under-river tunnels, in conjunction with hard-wired systems
installed there.
[Link] Sound powered telephones can be used as a stand-alone system in tunnels, high-rise
buildings, or anywhere that such use is deemed beneficial by the Incident Commander.
Sound powered telephones are not effected by temperature or humidity, surrounding
concrete or steel structures, and do not present the user with a shock hazard.
[Link] Sound powered telephones have been issued to the following units:
• All Battalions
• High-Rise Units 1 and 2 (E-3, E-39)
• Field Communications Unit
7.8.2. EQUIPMENT
[Link] Sound powered telephone equipment consists of a waterproof SPT box (Photo 1) and
wire reels. The waterproof SPT box contains:
• 2 - Headsets
• 2 - 1620 keys attached to headsets. 1620 keys are used to gain access to SPT
connectors in the NYCT System.
• 2 - Amplifiers
• “Y” Connector
39
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
• 2 - Jumper cords
• T-handle subway key
• Screwdriver (to change amplifier battery)
• 4 - Glow sticks
• Laminated instruction sheet
Photo 1
[Link] Headsets - A headset consists of a microphone and two ear cups, connected by a strap
that is worn around the back of the user’s head. This allows for a helmet to be worn
when operating with sound powered telephones (Photo 2). A headset has a male
connector. Headsets have less interference and background noise then handsets, and
allow for hands-free use which enables the user to perform tasks (e.g., record messages,
hold a flashlight). A 1620 key is attached to each headset to gain access to SPT jacks in
the NYCT System.
Photo 2 Photo 3
[Link] Handsets - A handset resembles and functions like a standard telephone handset.
A handset has a male connector (Photo 3).
40
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
[Link] Wire Reel - A SPT wire reel consists of a 400 foot-long wire wound around the reel
inside a plastic case, with a 3 foot-long fixed wire coming out of the side of the reel.
Both ends of the wire reel have female connectors. The headset is connected to the fixed
wire. Wire reels shall be stored with the end of the long wire looped around the handle,
to prevent it from becoming entangled inside the case (Photo 4).
Photo 4 Photo 5
[Link] Components are assembled using male and female connectors. A male connector has a
protruding plastic edge which shields two pins, and a locking collar (Photo 5). Female
connectors have a 2 pin receptacle and exterior threads (Photo 6). Care must be taken to
line up and attach connectors properly. Once a connection is made, the locking collar on
the male connector must be threaded onto the female connector and tightened.
Photo 6 Photo 7
41
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Photo 8 Photo 9
[Link] Amplifiers - increase the volume of verbal transmissions, but are not required to be used.
Each amplifier has 2 cords; an 8” long cord with a female connector that attaches to the
headset, and a 42” long cord has a male connector that attaches to the SPT system (Photo 10).
A. There are 2 controls on the amplifier; a talk level knob that controls the
volume and shall be placed at the highest setting when in use, and a PTA (Push to
Amplify) button. The PTA button must be pressed and held whenever the user
wants to transmit a message. Once the message is completed, the PTA button
must be released, or the reply will not be heard.
Photo 10
42
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
[Link] Once the start and end points of communications are determined, one or more wire reels
are deployed. The wire from the bottom of the reel is pulled out a few feet and secured at
the starting point. This wire plays out as a member carries the reel towards the end point of
communications. If the wire does not play out easily, pull wire from the reel while
walking. If the distance requires more than one reel to be used, jumper cords are used to
connect the short wire of one reel to the long wire of the next reel.
[Link] Once wire is stretched to the end point, listening devices and amplifiers are connected to
each end.
[Link] Specific members shall be dedicated to maintain the SPT communications link. Each
shall be paired with another member who monitors HT communications.
[Link] Unlike conventional telephones, sound powered phones do not emit a ringing or buzzing
sound when communications are initiated. A member monitoring a sound powered
phone must constantly listen to the headset/handset in case another member is
transmitting a message.
[Link] When transmitting messages, speak loudly and clearly, keeping the mouthpiece close to
your face. As with HT transmissions, use the term “K” to indicate the end of your
transmission.
[Link] A member using a headset in a standby position (awaiting a transmission) should cover
the mouthpiece with his or her hand. This will reduce the background noise which might be
transmitted through the wire.
B. There is usually no connection from one SPT system to another (e.g., from
an under river tunnel system to a nearby station).
C. Headsets are preferred for use throughout the NYCT system, due to the high
noise levels that may be encountered.
43
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
D. All SPT connectors within the NYCT are located in locked metal boxes that
are adjacent to standpipe Siamese or outlets. Boxes containing SPT jacks require
a 1620 key to open.
A. Street Level - At the street level of a subway station, SPT connectors are
found near the standpipe Siamese, with a sign that reads Street to
Station Communications (Photo 11). Depending on the size of the station,
there may be more than one Siamese. The standpipe Siamese with the SPT
connectors are not always found closest to the subway entrances. They may
be located a few hundred feet away from the station, in either direction of train
travel. These connections may also be found in the middle of larger roadways,
such as Queens Blvd., Houston Street and the Grand Concourse.
Photo 11
44
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Photo 12 Photo 13
B. SPT connector are typically located at the street level Siamese connections
closest to the emergency exits on both sides of the under river tubes. In the under
river tubes, SPT connectors are found at standpipe outlets; approximately 200
feet apart. The Transit Authority usually identifies associated standpipe outlets
by number. Members operating in a tube should notify the IC of the standpipe outlet
number, in order to identify the incident location (Figure 1).
45
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Figure 1
[Link] Required maintenance for SPT is to change the 9-volt battery in the amplifier semi-
annually.
A. To change the battery, remove the amplifier wire by loosening the locking collar,
then pull the wire connection straight out. Next, remove the two screws that
secure the cover and slide the cover off. Remove the rubber bumper and
rubber band from battery. Ensure that the new battery is tightly connected. To
reassemble, reverse the procedure ensuring that the rubber band, black rubber
pad, and the orange gasket around the wire connector are in place.
[Link] If the amplifier is not working at any time, check to see if the battery has slipped from the
connectors by removing the amplifier cover. If the amplifier does not work after
troubleshooting, contact Research and Development for repair and replacement of
equipment and/or technical information.
46
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
8. MISCELLANEOUS EMERGENCIES:
Caution: No open lights or smoking, sparks etc. Keep area clear of people.
47
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
NOTE: If wires are connected to house electric: pull plug, pull fuse, or turn off power
48
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
♦ A ladder will spread out and diminish the weight on a specific area of ice to allow
greater safety and enhance the possibility of removing someone from ice or icy
water.
Actions:
♦ Ladder extended with rope tied on shoreward rung. Rope will serve as an
extension.
♦ Rescuer crawls out on ladder to assist victim if necessary.
If ice breaks ladder will angle upwards and can be drawn back to safety.
Hook can be extended to victim. (Hook of necessary length.)
49
FDNY Probationary Firefighters Manual
Chapter Seventeen EMERGENCIES
Other devices to use are buoys, ropes, sticks, poles or even a human chain
lying prone on the ice.
Be prepared to give Rescue Breathing and treat for shock.
9. CONCLUSION
This chapter has covered some of the most common emergencies (outside fire
emergencies) that the FDNY is called to respond to. As mentioned earlier, fire calls
account for roughly 20 to 25% of FDNY responses. Recognizing this, it’s critical that
firefighters are proficient at providing assistance at other types of incidents in addition to
fires. To operate proficiently actions taken should always be based on sound principles
regarding effectiveness and safety. Without regards for such, even the smallest incident
can escalate quickly to disastrous consequences.
50
Probationary Firefighters Manual
Chapter 18
ELEVATOR EMERGENCIES
REFERENCE:
18
ELEVATOR OPERATIONS
T he function of the Fire Department at elevator operations is limited to the safe removal of
persons trapped in the elevator car or hoistway. Repairs to and reactivation of elevators
are not carried out by members of this department. Contact shall be made with
responsible building management personnel for any information and assistance that will
aid the operation. However the first units at the scene should start operations at once without
awaiting arrival of the management personnel.
1. INTRODUCTION:
♦ INCIDENT:
♦ EMERGENCY:
1
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
♦ Communicate with passengers- they may be able to give their approximate
location.
♦ Open the hoistway door at first floor with elevator key and look up shaft. Key
devices are usually required at the lower levels and may be present at all
levels.
Note: If the hoistway door has a glass panel check the shaft before
opening the door. Using a flash light, look for the governor ropes
and the counterweight. Movement of either one of these is an
indication that the car is in motion, do not open the hoistway door.
The governor rope is generally located on either side near one of
the far corners of the shaft.
♦ Enter a car in the same bank and open top hatch if no damage will be done to
the elevator car.
♦ Use the floor selector in the machinery room, it indicates the exact location of
elevator car.
3.1 Problems with elevators often arise from defective or non-functioning electrical or
mechanical devices and equipment.
3.2 Primary removal procedures are simple approaches performed without turning off
the elevator power. There are two types of primary removal procedures- the order
in which they are tried is not important.
Have a passenger press Door Open Button. If the car is level with the
landing this may open both the car and hoistway door.
Press lobby call button.
Instruct passengers to insure the car door is fully closed. Have a
person push the door towards the closed position.
Have members physically close all hoistway doors on the shaft. Air
movement in shaft may have opened an interlock cutting power to the
car. Check the hoistway doors in the vicinity of the stuck car first.
3
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
If Primary Removal Procedures fail summon an elevator mechanic. The
telephone number of the mechanic is required to be posted in the machinery room
near the elevator power switch. Consider the possibility of an elevator mechanic
on duty in a nearby building. Secondary Removal Procedures may be initiated
prior to the arrival of the mechanic.
♦ Two members are to be dispatched to the elevator machinery room to shut off
the power to the stalled car. These members are to:
b) Shut off power to the stalled car when directed. Each elevator is
controlled by its own power switch. Elevator power switch boxes and
motors are required to be labeled in a manner which relates motor to
switch. (Ex. Switch #1, Motor #1). If any doubt exists, open as many
elevator power switches as required to insure a safe operation. Allow
passengers to exit a serviceable car before removing power.
Notes:
4
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
♦ Members are not to enter the shaft or remove passengers from the car until
assured power has been removed.
♦ When passengers are removed from a car between floors they should be taken
UP AND OUT of the car if practical. This eliminates the possibility of a
passenger falling down the shaft after exiting the elevator. If they are
removed to the lower landing, the shaft opening must be protected.
♦ Members shall not normally be permitted to enter the shaft below the elevator
car. During a rescue necessitating members entering the shaft below the car,
the power switch must be turned off.
♦ All efforts must be made to remove passengers via elevator car and hoistway
door using an elevator tool or key.
♦ Passengers of the stuck car can assist in their removal. Direct the passenger of
the car to attempt to open the car door by physically exerting pressure toward
the open position. If they succeed in opening the car door instruct them to lift
the locking arm on sliding hoistway type doors, or to depress or lift the roller
on hinge type hoistway doors.
♦ If the elevator has a two speed system, commonly found in buildings over 10
stories, sometimes the system can be reset by shutting and then restoring
power. If the car is to restart it will do so within 10 seconds. If Emergency
5
FDNY Probationary Firefighters Manual
Chapter 18 FDNY ELEVATOR EMERGENCIES
Stop Button has been activated have passengers deactivate it (this should have
already been done prior to attempting PRIMARY procedures).
Note: This is the only circumstance in which the elevator power may be
restored by members of this department. If this procedure fails, power must
be shut off and members are not to restore power at completion of operations.
♦ If stuck car is in a multi car hoistway "POLING" can be used to remove the
passengers:
Have member work from an adjacent car which is nearest the leading
edge side of hoistway door of the stuck car.
Have one member remain on the landing at the hoistway door of the
stuck car.
Member in the adjacent car inserts pole or hook between the striking
post and the hoistway door and trips the lock by either depressing the
roller or pushing on the locking arm.
Member on the landing near hoistway door of the stuck car opens
hoistway door when the lock is disengaged.
6
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
♦ Swing Doors:
7
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
♦ Two Speed Elevator Doors:
This section outlines procedures which may only be used during an EMERGENCY (as
defined in this chapter), or when directly advised by an elevator mechanic. Primary and
secondary procedures are usually quicker and more efficient than the methods outlined in
this section. The decision of what method to use will be based on the size-up of the
officer in command.
Power to the stuck elevator must be off when you use Emergency Removal Procedures.
This should have been done before trying Secondary Removal Procedures.
An elevator car will have a top hatch or a side exit - sometimes both. One of these may
provide a route by which you can remove trapped passengers.
Although the law prohibits welding or bolting top hatches shut on elevators, it
does happen and it can make this procedure very time consuming.
♦ Open a hoistway door or access panel (required in single car blind hoistways)
on floor above the stuck car.
8
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
♦ Lower a portable ladder to the elevator roof. Use straight ladder if possible.
If an extension ladder is used tie the halyard around the rungs of both sections
of the ladder. This will prevent the lower section from dropping on to the car
roof.
♦ Climb down to the car roof. Maximum of two firefighters are to be permitted
on the roof of the car at one time.
♦ All members working in the shaft are to be secured with a life saving rope.
♦ One member equipped with a handie talkie enters car. Member in the car
must determine the order of removal. Secure each person with a life saving
rope.
♦ Members are to remain in physical contact with trapped persons while they
are being removed.
Useful under conditions of partial power loss in multi-car hoistways. It may not
be useful where a structural beam blocks a side exit or the rescue car can't be
brought level with the stuck car.
♦ Members must work from a car that is in the same bank and is adjacent to the
stuck car. This will become the rescue car.
♦ Bring rescue car even with stuck elevator. If mechanic is present, use his
operating key to bring the car level with stuck car.
♦ Remove power to rescue car. Power to the stuck car was previously removed.
♦ Open side exit in rescue car. A key or forcible entry is required to open panel
from inside the car.
♦ Open side exit of stuck car. It is openable by hand from the shaft side.
♦ Member equipped with a handie talkie and secured with life saving rope
crosses planks to the stuck car.
9
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
♦ Member determines the order of removal. Secure each passenger with a life
saving rope and assist them to the rescue car.
Forcible entry of hoistway and elevator car doors should only be attempted under
the direct advisement of an elevator mechanic or as a last resort during
EMERGENCY REMOVAL PROCEDURES. The deformation of the doors and
locks may add to the problem and delay the rescue. Upon completion of forcible
entry operations have maintenance personnel secure the hoistway door or have
police or security warn people of the danger.
Choose one of the following procedures based on the type of hoistway door.
♦ Hinged door:
Knock out glass panel if present. If not, breach hoistway shaft above
hoistway door.
Push down roller, located near side opposite hinges, on shaft wall.
Maxi Force Air Bag System- this is the preferred forcible entry
method because it is less likely than the others to push the door off its
hangers or out of its track.
10
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
Rabbit Tool
2) Insert the jaws of the Rabbit Tool between the jamb and
the leading edge of the hoistway door, as high as
possible.
Note: Care must be taken not to tilt the door too much. It
may dislodge from hanger and drop into the shaft.
♦ Blind hoistway.
11
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
6. ELEVATOR PIT OPERATIONS
6.1 The Elevator Pit is the lowest portion of the elevator shaft. There are two types of
Elevator Pits:
♦ Jump Pits:
♦ Walk In Pit:
Usually 6' to 10' from lowest landing to base of pit.
Car descends to the floor level above bottom of shaft. A high buffer
and lower limit switch prevent the car from entering the pit.
Access to the pit is via a door located at the bottom of the shaft.
o Door is not required to have an interlock switch.
o Door is opened by a regular key. Emergency elevator keys are
not usable.
6.2 Operations in Elevator Pits
♦ Jump Pit.
For additional safety, trip lower limit switch and secure it in an open
position.
♦ Walk In Pit.
7. FIREMEN SERVICE
All Fire Department personnel should be familiar with the operating procedure and
limitations of Firemen Service. This section describes Firemen Service components and
operational procedures.
A switch at the street floor or terminal floor for each bank of elevators.
Terminal floor is the lowest landing above the street floor of any
elevator that does not serve the street lobby floor, also known as a Sky
Lobby. (Fig. 1)
The key switch is required to be within 4 feet of the lobby call button.
The key switch is operated by use of the Fire Department 1620 key, or
by city wide standard elevator 2642 key.
Switch Configurations:
The Normal and Firemen Service position in the keyed switch permit
the removal of the key. The key is not removable in the door open
position.
13
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
Figure 1
Elevator
Configuration
Door
Open
Button
Emergency- FD Use Only
Figure 2A Figure 2B
14
FDNY Probationary Firefighters Manual
Chapter Eighteen FDNY ELEVATOR EMERGENCIES
Note: Elevators approved for installation after March 1991 are required to be
equipped with a three position switch:
HOLD
o Permits the firefighter to remove the 1620 key from the switch.
o A firefighter with a 1620 key can move the car by changing the
switch position from HOLD to FIREMAN SERVICE.
To operate the car, the switch must be placed in the Firemen Service
position while the car is at the landing where the lobby keyed switch is
located.
The lobby keyed switch must be in the Firemen Service position prior
to placing the car keyed switch to Firemen Service.
Once the car switch is in the Firemen Service position it can not be
overridden by the lobby keyed switch.
The 1620 key is not removable from the elevator car keyed switch
when it is in the Firemen Service position.
15
FDNY Probationary Firefighters Manual
Chapter 18 FDNY ELEVATOR EMERGENCIES
7.2 Operation of Firemen Service.
The recall of ALL elevators in the bank to the street or terminal floor. This recall
is done automatically (via sensors and/or detectors associated with certain
building systems) or manually. Manual recall is accomplished by the use of the
1620 key at the keyed switches located in the elevator lobby at the street floor or
terminal floor.
An elevator traveling away from the street floor or from its lowest
landing floor will reverse direction at the next landing without opening
its doors, and return non-stop to the street lobby or terminal floor.
Doors opened at any floor will immediately close and the elevator
shall return non-stop to the street or terminal floor.
When the elevator car reaches its terminal floor, one of the following
will occur:
o All car and hoistway doors open. The doors remain open for at
least 8 seconds and no more than one minute and then close.
o All elevator car and hoistway doors open and remain open.
The car lights in the Firemen Service elevator cars remain on
and the lights in the Non Firemen Service cars go off.
Caution: Do not return the switch to the "normal" position at this time.
♦ Phase II - Operational Phase: The actual operation of the elevator car by use
of the controls located within the car.
16
FDNY Probationary Firefighters Manual
Chapter 18 FDNY ELEVATOR EMERGENCIES
Place the 1620 key in the car Firemen Service switch and turn to the
Firemen Service position.
Press the car "Door Close" button and select a floor. It is not
important which floor button is pressed first. In some elevator cars
there may be two floor selection panels. The one to use for Firemen
Service is the one nearest to or the one with the Firemen Service keyed
switch.
As soon as the car begins to move, press the "Call Cancel" button to
verify the operation of the "Call Cancel" button.
o If the car does not stop at the next available floor in response to
the "Call Cancel" button, look to abandon the elevator.
Immediately select the next available safe floor. If the car does
not stop at the next available floor, attempt to stop the car by
forcing the car doors open, thus interrupting the interlock relay
switch. Notify the officer in command and initiate emergency
evacuation procedures.
If more than one floor selection is made, the elevator car will stop at
the nearest floor selection in the direction of travel.
If the car is operating normally when you reach the selected floor,
press the "Door Open" button. You must keep your finger on this
constant pressure button until the door is fully open, otherwise the
door will close on its own. This is a built in safety feature.
If the doors open on heat and smoke, the simple removal of the finger
from the "Door Open" button should enable the doors to close.
o If the car doors still fail to close, don Mask facepiece, evacuate
the elevator and proceed to the nearest safe stairway.
When the elevator doors have fully opened, the elevator car will
remain at the selected floor, with the doors open.
The elevator car shall not be returned to the lobby street floor until the
officer has determined that the unit has arrived at the proper location.
To move from any floor, the "Door Close" button must be pushed, and
another floor selected.
♦ Account for all elevators serving the fire floor, checking them for victims.
♦ When it is confirmed that the fire is on the 7th floor or below units should
avoid the use of elevators. It is safer to utilize the stairway to reach the fire
floor.
♦ Do not use an elevator in a bank which services the fire floor if a lower bank
of elevators reaches within five floors of the fire floor.
♦ When it is necessary to use an elevator in a bank which serves the fire floor:
Select a floor at least two floors below the fire floor or two floors
below the lower level of an access stair in the fire area, whichever is
lowest.
♦ A service elevator shall not be used until it is declared safe for use by the
officer in command of the fire. Be aware that in many high rise office
buildings the service elevators have been converted for Firemen Service. Use
of such an elevator must be avoided until declared safe by the officer in
command.
18
FDNY Probationary Firefighters Manual
Chapter 18 FDNY ELEVATOR EMERGENCIES
♦ Before entering the elevator car, all members shall have donned their mask.
The facepiece shall be maintained in the standby position.
♦ Not more than six members are to be permitted in any elevator car. This
precaution is required to prevent overloading.
In the event the car does not stop at the selected floor, a tool may be
used to pry the elevator car door open disengaging the car door
interlock.
In the event the car should become disabled a tool may be needed to
extricate the members.
♦ Before leaving the lobby and at each precautionary stop direct a flashlight up
between the elevator car and the hoistway shaft to determine if there is any
accumulation of smoke in the elevator shaft.
♦ The relationship of the elevator to the stairway should be noted. This can be
accomplished by inspecting the "YOU ARE HERE" sign which is required to
be posted at each floor near the call button. This should be done at the first
and last precautionary stop. Floor configurations may change.
♦ Determine as soon as possible if the location of the fire could affect the
elevator operation.
♦ Members must be careful during any emergency stop. They should prepare
themselves for the jolt of a fast moving elevator car stopping abruptly.
♦ If you are in a smoke filled hallway, remember, elevator doors will swing
toward you and apartment doors will swing away from you. If the electric
interlock malfunctions it might be possible to open the elevator door and not
have the car on that floor.
Some elevator doors are of the sliding type. If forced by mistake due to smoke
conditions, they may pop inward and be mistaken for an apartment door.
19
FDNY Probationary Firefighters Manual
Chapter 18 FDNY ELEVATOR EMERGENCIES
8.2 Affects of Fire on Elevator Components:
During fire operations do not straddle elevator doors to hold the car.
Use Firemen Service if available or folded lengths of hose to hold car.
If the elevator moves leaving the door open, close the hoistway door
manually if possible.
♦ Hoistway door can become warped by heat. This can render the elevator in
the particular shaft out of service due to the opening of interlocks. To prevent
any complications involved with this, members if possible, should avoid
using elevator cars that service the fire floor.
♦ If elevator car door opens on fire floor (heat, smoke), attempt to close the door
either by pushing the Door Close Button or by forcing the door closed. Then
select a lower floor.
20
FDNY Probationary Firefighters Manual
Chapter 18 FDNY ELEVATOR EMERGENCIES
If necessary use side emergency exit for rope slide to the safety of
lower floor. Have power removed to the adjacent car if this is to be
attempted.
Members can be lowered to the hoistway door interlock and exit at the
floor landing below the fire.
Hose line on the floor below can be used to spray a fog stream
between the car and the hoistway door. A 30 degree fog pattern
should be used to cool and protect trapped persons during the rescue
operation.
♦ Assure the elevators serving the affected areas have been placed on Firemen
Service.
♦ When Firemen Service is available use the elevator cars so equipped.
♦ First arriving units should, if possible, initially avoid a Firemen Service
elevator which is capable of stopping at all floors. Many of the converted
“Service” freight elevators are so arranged, and therefore are capable of being
affected by fire on any floor. Only after the officer in command has
determined that the fire is not adjacent to the shaft should these elevators be
utilized. (Experience indicates that many fires in high-rise office buildings
have been found in the service elevator lobby, in piles of collected rubbish.
Heat and flames have affected the doors and control wiring of nearby service
elevators).
♦ Members shall never take a Firemen Service elevator which services all floors
to go above the fire. When assigned to go above the fire via an elevator,
choose an elevator which has a blind shaft on the fire floor. Remember a
"Firemen Service" elevator is not necessarily a "safe" elevator. It can still be
affected by heat, smoke or water entering the shaft. If there is no blind shaft
elevator to go above the fire, stairs shall be used.
Note: Use a fire tower or a stairway other than the attack stair.
♦ There are situations in which units will encounter "exceptions to the rules".
Time must be taken to become familiar with particular elevators before
leaving the lobby. Utilize stairs whenever possible, and try to limit elevator
use to those in banks that cannot be affected by the fire.
♦ If Firemen Service elevators have not been installed in the building, Fire
Department operations shall be conducted using elevators that have been
placed in the "Manual Mode" if possible. When using elevators in the
"Manual Mode" all the applicable sections of this procedural guide shall
apply.
21
FDNY Probationary Firefighters Manual
Chapter 18 FDNY ELEVATOR EMERGENCIES
9. ELEVATOR TERMS AND DEFINITIONS
Alarm button (switch) - Button (switch) in elevator car which activates the alarm bell.
Car Door Contact - An electrical device used to prevent the operation of the car unless the car
door is in the closed position.
Car Safeties - Stop car in the event of an emergency. Controlled by car governor.
Elevator Car Selector - Panel inside car containing emergency stop button, alarm button, door
open button, floor selection buttons and Firemen Service key switch if required.
Elevator Control Panel - A visual display unit located in the lobby which indicates the status
and location of all elevator cars and the necessary controls for the operation of the cars.
Common in High-Rise buildings.
Elevator Door Vane - The connection between the elevator car doors and the hoistway doors. It
allows the elevator car door to drive the hoistway door.
Elevator Machinery Room - Area where the equipment that raises and lowers the elevator is
located. Usually located at the top of the shaft, machinery room may also be found at shaft
bottom or two floors above the highest floor serviced by the elevator.
Elevator Motor - Turns winding drum raising and lowering elevator car.
Emergency Stop Button - Elevator car button which when activated cuts power to car and
sounds alarm bell. Note: Do not rely on this button, elevator power switch must be used to
insure motor power is off.
Emergency Escape Ladder - On the top of some elevator cars used to assist in top hatch
removal operations.
Final Lower Limit Switch - A switch located in the elevator pit which prevents the elevator
from descending too low in the shaft. When tripped by elevator it cuts the power to elevator
motor. Acts as a backup to lower limit switch.
Firemen Service - A feature required in many elevators which enables the department to gain
control of the elevators
Floor Call Button - Located at elevator floor landing, used to call car to the floor when service
is desired.
22
FDNY Probationary Firefighters Manual
Chapter 18 FDNY ELEVATOR EMERGENCIES
Floor Selector - Located in the machinery room can be used to determine the exact location of
the elevator.
Governor - Regulates elevator car speed. Also engages car safeties and shuts off electrical
power in the event of free fall or over speed.
Governor Rope - A wire rope or cable which travels with the car. If engaged by the governor it
mechanically activates the car safeties.
Hoistway - The shaft the elevator moves in. Types: Single car (local service), multi car (local
service), single car blind (express service), multi - car blind (express service).
Hoisting Cable - Cable (cables) used to raise and lower the elevator.
Interlock - A switch on hoistway door, and some emergency exits that will prevent the elevator
from moving when in open position.
Key 2642 - Standard key used by elevator industry. This key is interchangeable with 1620 key
for operation of Firemen Service elevators
Limit Switch - A mechanical electrical device which is located at the top or bottom of the shaft.
Its purpose is to prevent over extension of elevator car in an upward or downward direction.
Lower Limit Switch - A switch which stops the car in pit area, below lowest landing.
Main Electrical Power Switch - Located in machinery room, each switch controls the operation
of one elevator.
Terminal Landing - lowest landing for discharge of passengers, may be at ground floor or
above in which case it is known as a Sky Lobby.
Ventilation Opening - "Smoke hole" - opening providing for the movement of air in the shaft
caused by the movement of the elevator.
23
Probationary Firefighters Manual
Chapter 19
NON-STRUCTURAL FIRES
19
PART ONE
INCINERATORS & COMPACTORS
2 INCINERATOR OPERATIONS.................................................2
T he FDNY spends many hours at emergencies and minor fires that involve incinerators,
compactors, autos, manholes, etc. We must know how to deal with them in a professional
and safe way.
1.1 New York City Regulations encourage the use of compactors rather than incinerators,
and require that incinerators be used only with safeguards. This policy reduces the risk of
fire or smoke emergencies occurring, but does not eliminate them. New incinerators can
be installed in hospitals and in municipal buildings. In existing buildings, an incinerator
must either be converted to a compactor or be updated by adding a scrubber, an auxiliary
gas or fuel burning mechanism and oversized fans. New buildings (except hospitals and
municipal buildings) are permitted to install only compactors.
B. Extension is unlikely but is much more probable in the case of a compactor than
in the case of an incinerator, since compactor chutes are not designed for burning.
Therefore the operational priorities are different, viz:
1) Compactor - Put the fire out.
2) Incinerator - Clear the blockage.
A. You may know ahead of time, perhaps through BISP whether the building has an
incinerator or a compactor.
D. In City Housing Projects, the chute door on the first floor may be color coded:
RED for incinerator, GRAY for compactor.
1
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
2. INCINERATOR OPERATIONS
Fig 19-1
2.1 Officer, FE team, and OVM of the ladder company will generally operate inside the
building to ventilate, search, and to locate the blockage.
A. Examples of ventilation.
1) Vent windows in halls, if there are windows.
2) Chock open doors to stairwells on floors with smoke conditions to allow
vertical ventilation up stairwells.
NOTE: The roof firefighter (see below) can vent stairways by opening the
door of the bulkhead and securing it.
B. Search floors above and below the source of the smoke where heavy smoke
conditions call for this.
2
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
2.2 Locating the blockage.
A. If you open a chute door on a floor and smoke comes out, the blockage is
generally above that floor. Refer to Fig 19-1
B. If instead, when you open it, a draft goes inward or there is little smoke, the
blockage is generally below that floor or the blockage has freed itself.
NOTE: If smoke is present on the uppermost floor, there may be a clogged
or blocked spark arrester or fly ash collector.
F. The roof firefighter of the ladder company proceeds to roof to ventilate stairways
and to check spark arrester for blockage. As stated above, the bulkhead door can
be opened and secured in order to vent stairways.
NOTE: It is very important that, before the roof firefighter leaves the lobby
he chocks open the stairwell door at the ground floor level. This
will provide for maximum draft and vertical ventilation when the
roof bulkhead door is opened.
3
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
H. If there is a fly ash collector, there may be blockage inside the incinerator chute,
at the top. If there is, the roof firefighter should notify his officer for assistance
and start to force entry into the collector and clear the blockage.
NOTE: A fly ash collector is an area near top of the incinerator vent shaft
for collecting fly ash that results from incomplete combustion of
the waste material. It can be as small as an enlarged area in the
shaft or as large as a small room. It is always equipped with a
means of access cleaning (generally a steel door). Use caution in
the larger collectors because there may be an open hole in the floor
large enough to fall into. Also, if the area is small, hot ash may
come down on member when opening door.
2.4 The duties of the chauffeur of the ladder company will vary dependent upon conditions.
The chauffeurs duties may be:
3 INCINERATOR SAFETY
3.1. Pay special attention to safety whenever you open a chute door. When chute doors are
opened, dust explosions, exploding aerosol cans, and the eruption of fire are real
possibilities.
A. Be sure you are wearing full firefighting gear, including gloves and eye shields
down. Consider using a mask if necessary.
B. Stand to the side of the hopper door. If the door is hinged, stand on the hinged
side.
E. Shining a flashlight up or down the chute may aid in locating the blockage or
observing smoke movement.
3.3 Members attempting to clear a blockage from the base of the incinerator should shut off
the auxiliary burner before commencing operations. Gas explosions of some
consequence involving the auxiliary gas burners, while infrequent events, have occurred.
4
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
4 ENGINE COMPANY OPERATIONS
A. There are buildings with incinerators and compactors that do not have standpipes.
This will necessitate a hand stretch if a line is needed.
5. COMPACTOR OPERATIONS
5.1 The air quality standards for New York City were revised by Local Laws 14 of 1966 and
49 of 1971 to improve the air pollution situation. In compliance with these laws, new
buildings were equipped with compactors and many existing incinerators were converted
to compactors.
6. COMPACTOR DESCRIPTION
6.2 A compactor is designed to reduce the volume of raw refuse. The refuse is dropped down a
chute from the floors above, and guided by a shaped hopper into the compactor chamber.
When the chamber is full, a photo electric beam is broken, initiating a ram that forces the
refuse through a nozzle leading to a bag or container. This photo electric mechanism oper-
ates on a delayed time principle. An object must block the beam for four seconds before the
compactor starts. The time factor may be either consecutive or accumulative.
6.3 The type of compactor that FDNY units most frequently encounter is the incinerator
conversion, installed at the base of the original incinerator chute. It is usually located in a
separate room, accessible from the rear of the building.
5
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
6.4 Diagram of Typical Compactor
FIG. 19-2
7.1 The compactor room should be fire resistive, protected by a fire door and supplied with
an automatic sprinkler.
7.2 A water outlet and a hose are required in the compactor room.
7.4 A small O. S. & Y. valve, controlling both the automatic head within the compactor and
any heads within the compactor room, is usually found on the water line in or near the
compactor room.
6
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
OS&Y for sprinkler is located in the supply line. It can be either inside or outside of
compactor room. Sprinkler heads are not only in the compactor room but also in the
compactor unit and in the chute. If they are not operating, they may have been previously
shut down by maintenance or the heads may be insulated from heat by the garbage.
NOTE: The FDNY does not replace sprinkler heads.
7.5 In refuse chutes constructed in new construction, sprinklers shall be provided spaced not
more than two stories apart for the height of the chute. They shall be recessed and so
arranged that fused sprinkler heads may be readily replaced unless electrically operated.
8.1 The operations at compactor fires will be governed by the location of the fire. There are
three categories of compactor fires: in the chute, in the unit, or in the compactor room.
7
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
D. The chauffeur's duties will vary and will generally be as directed by the officer to:
1) Provide special tools in the compactor room or assist in search and
venting, etc.
8
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
9. SAFETY PRECAUTIONS
9.1 Members working in area of compactor unit should make sure they have gloves on, eye
shields down, and keep arms and hands out of unit. Bottles, spray cans and other
potentially dangerous debris may be falling down chute.
9.2 Electrical
Compactors are powered by high voltage electrical lines (approximately 210 Volts). To
eliminate the potential hazard, disconnect power at electrical shut off.
9.3 Mechanical
Compactor ram has a packing force of approximately 50,000 pounds, depending on size
of the unit and the manufacturer. It is triggered by a photo electric circuit. When the
electric power is shut off, the hydraulic ram is also deactivated, eliminating the danger of
injury from the ram.
9.4 Hydraulic
If the hydraulic lines rupture, the escaping flammable fluid adds to the potential of the
fire. This would also create a slippery condition for members operating in the area.
9
10
PART TWO
MOTOR VEHICLE FIRES
2 PURPOSE……………………………………………………….13
3 DEFINITIONS .............................................................................14
5 RESPONSE..................................................................................16
12 CONCLUSION …………………………………………………..26
REFERENCES…………………………………………………...26
11
12
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
1. INTRODUCTION
1.1 The dangers associated with present day traffic conditions have demonstrated a need for
this Department to reassess and modify its operations on all roadways, especially express
highways and other high-speed thoroughfares, as well as many secondary roadways.
Traffic hazards formerly associated with only a few dangerous locations are now
encountered throughout the city. These hazards include, but are not limited to:
• Distracted drivers, (e.g., cell phones, audio and visual entertainment devices.)
• Tailgating.
• Tourists and others traveling unfamiliar routes making sudden stops, lane changes or
other unexpected maneuvers.
• Rubbernecking.
2. PURPOSE
13
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
3. DEFINITIONS
3.1 Express Highways: Limited access highways and parkways, (e.g., Long Island
Expressway, Belt Parkway, Cross Bronx Expressway, Staten Island Expressway.)
3.2 Divided Boulevards: Main primary routes, usually with service roads. The main road
may have a physical center divider, or the center divider may be painted on the road
surface, (e.g., Queens Boulevard, Grand Concourse, Kings Highway, Pelham Parkway.)
3.3 Main Arteries: Those with posted speed limits higher than 25 mph, such as Union
Turnpike, Northern Boulevard, Hylan Boulevard.
3.4 Secondary Roadways: Other city streets, avenues, not falling into one of the categories
above.
3.5 Known Speedways: Roadways where local experience shows frequent or regular
disregard for speed limits. These "known speedways" may fall into any of the categories
above.
3.6 Secondary Collisions: A "Secondary Collision" is one between a vehicle traveling in the
vicinity of the fire or emergency and any other vehicle, object or person - happening at
the time of the arrival of the Fire Department or thereafter.
4.1 Some important points to be considered are: At a highway operation, the FDNY has an
obligation to its members and to the civilian population to prevent further injury and to
provide a safe working area, consistent with conditions.
4.2 Immediately upon arrival at an operation on a highway, the officer in command must take
steps to prevent escalation of the incident in the form of a secondary collision.
A. The cause of a secondary collision can be related to the original fire or operation.
Examples:
• Civilian car strikes an apparatus; or,
• Civilian car strikes a firefighter, because vision is obscured by smoke, etc.
B. This may be avoided by completely stopping traffic flow in all lanes of the
highway on the side where the fire or emergency has occurred, at least until
arrival of the police department to control traffic. This should be done, when
necessary, by using apparatus to stop traffic and then blocking traffic in the
immediate working area. The Incident Commander shall coordinate which lane
closures are necessary to control the scene with the ranking police officer.
14
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
C. On arrival, the officer in command must assess the potential for secondary
collision based upon:
• Traffic flow: the volume and speed of the moving traffic on the highway or
street. The greatest danger of secondary collision occurs during periods of
light to moderate traffic volume with the usual accompanying high speed.
During this type of traffic flow we can expect speeds of 70 mph or more,
despite posted speeds of 50 mph on express highways.
• Visibility of roadway: Weather conditions, topographical layout, curves and
hills, buildings, overpasses, shrubbery and trees as well as smoke from the fire
all affect the ability of oncoming drivers to perceive a dangerous condition in
the roadway ahead in time for them to take proper and timely evasive action.
• A very important fact which must be considered is that on DRY pavement
with GOOD brakes a fully loaded tractor-trailer combination will need over
500 feet to stop at 50 mph AFTER THE DRIVER PERCEIVES THE
DANGER! Unfortunately, many trucks of this type do not have good brakes.
A passenger car traveling at 70 mph will need over 500 feet to stop. Wet
pavement and other weather factors can double the stopping distance!
4.4 Police Assistance: Upon arrival at the scene of the incident on a highway, the dispatcher
shall be notified to request response of police department and if required, authorized tow.
4.5 Sanitation Assistance: During freezing weather, water should be used judiciously to
minimize formation of icing conditions. Where necessary, Sanitation Department should
be promptly requested through the dispatcher for spreading of salt or sand.
4.7 Where weather conditions (snow, rain, fog, sleet, etc.) or smoke blowing across highway
limit visibility, highway must be closed.
15
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
5. RESPONSE
5.1 One engine and one ladder from each direction, and a Battalion Chief will be assigned to
all express highway incidents. No fewer than two units shall operate at an incident on an
express highway or other potentially dangerous roadway.
At least one vehicle, other than the pumper being used to extinguish the fire, shall be used
to divert or block oncoming traffic for the duration of the operation or until the police
department arrives on scene and assumes traffic control. There may arise occasions
where additional units are necessary to establish a proper area of safety. Example: Both
units operating, handline stretched and extrication tools in operation. High Visibility
Safety Vests shall be donned as per Section 7.
5.3 All fires and emergencies involving motor vehicles on other than express highways shall
receive a minimum response of one engine company and one ladder company.
6. PLACEMENT OF APPARATUS
6.1 Apparatus shall usually be placed to the rear of the incident or emergency in a manner
that reduces the chance of a vehicle being struck by oncoming traffic. The apparatus
should be positioned to shield the operational area and place the pump panel in the
protected area. Apparatus should be placed at an angle to the incident when feasible to
maximize safety (between the fire or emergency and the oncoming traffic).
However, an obvious exception will be a fire in a flammable liquids tank truck or other
hazardous material carrier located on a grade. In such a case, the highway will have to be
closed at a sufficient distance from the incident to prevent civilian vehicles becoming
involved if a container should rupture or develop a leak. Apparatus will have to be
located uphill of the involved vehicles.
6.2 Where placement of apparatus will expose it to the possibility of fire extension, pumper
may be placed beyond the fire vehicle, but second apparatus, and third if necessary, shall
always be placed between oncoming traffic and the operating forces.
16
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
6.3 Where the fire or emergency occurs near a curve, or beyond a hill, the second apparatus
shall be located where it will be visible to oncoming traffic and furnish a warning to such
traffic in sufficient time to avoid a secondary collision.
6.4 At times, particularly when fire is small and a period of examination and overhaul is
necessary, it may be possible to move the fire vehicle and the fire apparatus off the
roadway to a safe location. Even when the operation occurs off the roadway, an
apparatus must be placed to provide a safe working environment.
6.5 Blocking apparatus shall be placed at least fifty (50) feet behind the first operating unit to
create a safe working area.
6.6 Members shall avoid standing on highway pavement to the rear of second apparatus,
unless placing flares, cones or signs, and traffic is stopped.
7.1 Department policy requires all members to wear high visibility safety vests when
operating on all highways at all times, day or night. This includes, but is not limited to,
incidents such as vehicle collisions, extrications, fluid spills, dangerous conditions,
vehicle fires, and at any operation that the Incident Commander deems necessary.
The scene must also be protected from the hazards of moving traffic by utilizing
apparatus blocking or total lane closure.
7.1.1 Exemptions from wearing high visibility safety vests are for members directly
involved and in the immediate vicinity of firefighting, hazardous material
mitigation, or technical rescue. Some examples include:
• Members operating with donned bunker gear and SCBA working in close
proximity to a source of heat during fire suppression.
• Members operating with donned hazardous material personal protective
equipment.
• Members operating with donned technical rescue PPE and/or equipment for a
technical rescue incident.
7.1.2 Once members complete their activities in fire suppression, hazardous materials
mitigation, or technical rescue, or when they leave the immediate vicinity of the
incident, they are required to don a high visibility safety vest.
17
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
B. Except as stated in subsection D, flares shall be used at night or periods of reduced
visibility and cones shall be used during both day and nighttime operations.
C. Flares and cones may be used at any time where, in the judgment of the officer in
command, their use would add to the safety of operation.
D. Flares shall not be used in cases of flammable or combustible liquid or gas leak
where their use would create a danger of fire or explosion.
19
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
D. Also, at times the preferred route (in the same traffic lanes as the fire) will be
unattainable because of the complete blockage of the roadway by vehicles. Therefore,
an alternate will be taken
E. Where it is necessary to stop the flow of traffic, the dispatcher shall be notified to
relay the information to the Police Department.
F. Notification should include recommended response instructions.
G. When response of EMS is requested, similar recommended response instruction
should be offered.
H. At times the practice of gaining access to an express highway incident from a
service road, across a grassy slope, avoids placing the apparatus on the highway
proper. However, firefighters operating on/from a service roadway must be
extremely careful and warning devices have to be placed as soon as possible at
both locations.
I. Where access to an elevated or depressed roadway is obtained by use of ladders,
extreme caution shall be observed in placing and using the ladders. Aerial or
Tower Ladder shall not be extended beyond shoulder where they could be
exposed to moving traffic. Aerial and/or tower ladder should be cantilevered
parallel to the elevated roadway.
10. QUICK SAFETY TIPS AT MOTOR VEHICLE EMERGENCIES
• Do not trust moving traffic.
• Never take a partial lane.
• Never assume traffic will behave the way you expect.
• Proper apparatus positioning is the first step to providing safety of the working
crews at the scene of an incident.
• Many motorists and truck drivers have no regard or respect for emergency
vehicles or personnel on the scene. In many cases, they don’t even slow down
near an accident scene.
• Never allow traffic to come around both sides of an accident scene.
• Request police assistance ASAP.
• Company officers should be given the discretion to summon additional resources
as necessary.
• Ensure scene is controlled before commencing operations.
• Start operations at highway incidents defensively.
• Do not allow personnel to “wander” around the scene.
The following is a summary of results taken from case studies conducted nationally of
firefighter fatalities on highways.
A. Reduced-vision driving conditions: Although firefighters may be struck by vehicles in
virtually any condition, the chances of an incident occurring are greater during
obscured vision conditions, including darkness, fog, rain, snow, and blinding sunshine.
B. Lack of situational awareness: Responders fail to recognize the dangers associated
with a particular roadway situation they are facing due to insufficient training or
lack of experience.
20
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
C. Careless, inattentive, or impaired drivers: Even when we try to do everything correctly, we must
be cognizant of the fact that there are drivers out there who will not react correctly to the altered
traffic pattern that occurs at a roadway incident. This may result in them driving into our
workspace.
D. Improper positioning of apparatus: Numerous cases have been cited where
apparatus were not positioned to the fullest advantage of the incident. In some
cases the apparatus was not positioned in a manner that protected the work area.
In other cases apparatus was unnecessarily positioned in the roadway.
E. Failure to use PPE and high-visibility apparel and safety equipment: Responders
working in the roadway must wear appropriate protective garments and use all
available traffic control devices in order to prevent being struck by oncoming
traffic.
F. Altered traffic patterns: Drivers may be confused by the traffic control measures
used at an incident scene or those being employed in a construction zone.
11. FIREFIGHTING OPERATIONS AT MOTOR VEHICLE FIRES
• Ladder company members may be used to operate a second line to either protect
victims or to protect extrication procedure.
• Exposures such as buildings or other vehicles should be checked for extension.
• The possibility of damage to overhead wires or downed wires from damaged
utility poles should be considered.
• When opening the hood during fire operations utilize the following guidelines:
a. A charged line should be in place during this operation.
b. Try the passenger compartment hood release first.
c. Use vise grips if the handle is burned away.
d. Pry up the side of hood for access to fires in engine compartments.
e. Operate handline streams through hood openings to extinguish the fire.
f. Stand back when opening the hood. (There may be a burst of flames).
g. Bolt cutters may be needed to cut locks or chains.
h. Use a 6' hook to support the hood once it is opened.
• Vans.
a. Engine cover in the passenger compartment should be removed after the fire
is knocked down.
b. Stand to one side of the cover when removing it. Do not open it from the
rear. (A sudden flare up could cause burns to the face and neck area.)
• Pneumatic pistons, which are used to hold up the hood in the open position, have
become a serious danger at vehicle fires. The danger is the result of exploding
hood pistons. When heated due to a fire in the engine compartment the rods have
become projectiles penetrating the hood and grill. This could cause serious injury
to anyone standing in front of the vehicle.
• The trunk must always be examined for victims or extension. Hazards which may
be found in trunks include gas cans, pressurized containers, booby traps, glass
containers, ammunition / guns, etc.
• The methods of opening the trunk include:
a. Drive in the cylinder with the point of a halligan tool, and unlock the trunk
with a screwdriver.
b. Pull out the cylinder with a Bam-Bam tool and use a screw driver to turn the
lock.
c. Cut around the bezel ring on the cylinder (with an ax or a screwdriver), then
turn the cylinder with a screwdriver.
1/6/21
22
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
23
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
24
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
A Hybrid vehicles are becoming a more common sight on roads today. In some
hybrids, the car starts out in a full electric mode to save gas, then starts the engine
and switches to gasoline mode when the vehicle reaches a certain speed. Other
hybrids do not have a full electric mode. Instead, they use their hybrid battery
and electric motor primarily for the engine start/stop system that saves gas when
the vehicle is stopped in traffic, or to boost engine power when accelerating or
passing. Though hybrids get better fuel economy than conventional vehicles, they
also present some unique hazards. The high voltage hybrid battery and hybrid
powertrain components create a potential shock hazard.
B. The voltage in most hybrid batteries can deliver a lethal shock, much like that of
an electric chair. The voltage from a hybrid battery is Direct Current (DC).
Hybrid vehicles can be rated between 144 and 330 volts DC. The threshold
voltage where DC becomes dangerous can be as low as 55 to 60 volts, compared
to 110 volts for AC.
25
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
12. CONCLUSION
12.1 When operating at incidents (especially on highways), all personnel must be continually
alert to the ever present danger of oncoming traffic, and must be vigilant and ready for
the unexpected. The collective safety of the entire fire force depends on the individual
safety contributions of each member. If one member should let down his/her guard, all
members may be jeopardized in a moment.
Reference 1
It has been reported that in order to sell junk cars to be crushed and sold as scrap metal,
automotive junk yards must remove the gas tanks. Consequently, some unscrupulous
automotive junk yard owners are indiscriminately dumping the gas tanks in vacant lots
on streets and just about anywhere. Often, these tanks still contain varying amounts of
gasoline. Incidents have been reported involving as many as forty of these tanks in ADV
vans. Should these vans or any vehicle or container holding these partially filled gas
tanks take fire, they are potential bombs.
Units responding to large vehicle or rubbish fires shall approach the fire with caution
using the reach of the hose stream to their full advantage as well as the shielding effect of
any object between the fire and the nozzle.
Members should be aware of the dangers present at car fires equipped with shock
absorbing bumpers. The heat of the fire increasing the pressure in the shock absorbing
mechanism could reach a point where the bumper is actually blown off the car.
The above incident indicates that cars that have had their shock absorbing bumpers
removed could be more dangerous than those with bumpers still in place. The shock
absorbing mechanism could become a bullet-like projectile capable of inflicting very
serious injury.
The recommendation to use the reach of the hose stream to its full advantage is
reinforced in this type situation. Whenever possible, avoid standing directly in front of or
in the rear of vehicle fires. Attack from the flanks. Keep onlookers from standing in
front of or to the rear of vehicle fires for a distance of at least one hundred feet.
26
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
Reference 2
27
Reference 3
1.1 At a recent motor vehicle fire, units encountered a potentially hazardous situation.
The fire began in the engine compartment and extended through the dashboard into the
interior of the vehicle. The fire was extinguished without incident. During overhaul, a
six gallon can of kerosene was found between the seats.
1.2 The vehicle contained a machine for steam cleaning carpets. The machine is fueled by
the kerosene. Vehicles used as dog grooming services may also contain a heater fueled
by kerosene. The purpose is to warm water for bathing pets.
2. PRECAUTIONS
2.1 It should be noted that the above-mentioned vehicle was not marked, and members
were unaware that the vehicle was used for such a purpose.
2.2 When a fire occurs in these types of vehicles, exercise extreme caution.
2.3 As a final note, members should also be cognizant of vehicles that are used to carry
power washing machinery, tree services, stump grinding, etc. These vehicles may house
machinery containing gasoline as fuel. They may also be carrying a can for refueling.
28
Reference 4
29
Reference 5
1. INTRODUCTION
1.1 “OZ-12” is a product which is presently being sold in our area as a replacement for
auto freon (R-12) in automobile air conditioners. Unlike R12 Freon which is non-
flammable, and non-toxic, OZ-12 is extremely flammable and toxic. OZ-12 is a
compressed hydrocarbon mixture that is composed of 70% LP gas. OZ-12 is
manufactured by OZ Technology, Inc. of Post Falls, Idaho.
1.2 Despite the fact that on July 13, 1995, the U. S. Environmental Protection Agency
declared the use of OZ-12 as a replacement for R-12 (auto freon) in automobile air
conditioners illegal, the sale of such product was not. OZ-12 is used as a replacement for
refrigerant in industrial processes.
1.3 The use of OZ-12 in automobile air conditioners is very desirable to the user for
reasons of convenience and economics. OZ-12 is significantly less expensive and
requires no retrofitting of the auto’s air conditioning system.
2.1 Based on the above, it is apparent that the use of OZ-12 in an automobile air
conditioning system is likely to be found.
2.2 Units operating at automobile fires shall exercise extreme caution when fire is
confined to the engine compartment, especially when a unit is opening the hood for
extinguishment.
2.3 Officers of units operating at such incidents are reminded that automobile fires shall
not be taken as routine. Strict control and proper supervision are the keys to a safe
operation.
30
Reference 6
Incidents involving garbage truck fires have been reported to the Safety Command for
information and dissemination to field units. The following is one account:
PARTICULARS:
An Engine and Ladder Co. responded to a fire involving a "commercial" garbage truck. On
arrival, the trash container of the truck was found to be fully involved. The truck was parked in
the garage. In order to preclude extension to the structure, the truck driver was ordered to drive
the truck onto the street. This was done. Without the knowledge of the officers and members
operating at the scene, the driver then attempted to raise the back portion of the truck. In doing
this, he placed pressure on the hydraulic system of the truck. He was unaware of the possibility
that the hydraulic lines may have been burned. In this case, they were. When hydraulic pressure
was applied, it forced fluid out of the burned lines. Two bursts of fluid passed through the
burning trash, out of the rear of the truck, and were ignited. In both instances, a fire ball, similar
to that from a military flame-thrower, was hurled approximately forty feet.
CORRECTIVE ACTION:
If the truck is not equipped with a 2 1/2" female inlet coupling then the rear of the truck will
have to be raised in order to extinguish the fire.
Certain precautions should be used when using a hydraulic system to raise the rear of the truck.
B. Position the truck so that the rear does not face an exposure that could cause
additional problems.
E. No one shall be allowed to work or stand under a raised section of the truck
.
F. No one shall be permitted to enter the garbage storage section of the truck.
G. Hydraulic systems are under pressure and usually contain flammable oils.
H. Garbage storage section could contain pressurized cans that could explode.
31
THIS PAGE WAS INTENTIONALLY LEFT BLANK
32
PART THREE
MANHOLE FIRES
33
34
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
1. GENERAL CONSIDERATIONS
1.1 The Officer in Command at the scene shall determine the cause and severity of the fire or
emergency. Using signal 10-25, this officer shall transmit particulars to the dispatcher for
immediate notification to the utility company concerned:
10-25 Manhole or Transformer Fire or Emergency
Any type of manhole or transformer fire or emergency.
Without Code: Situation other than as described in Codes 1, 2, 3, or 4.
Code 1: Fire has extended from a manhole, conduit, or transformer
into a building.
Code 2: Fire has blown one or more manhole covers, or smoke is
issuing from a manhole under pressure.
Code 3: Smoke is seeping from a manhole.
Code 4: Fire or smoke condition from a transformer at any location,
i.e., pole, vault, room, etc.
Note: Utility Company will dispatch an emergency crew
immediately upon receipt of a Code 1 or Code 4 signal.
1.2 Should conditions change after original report, a supplementary report shall be
Transmitted immediately to describe the existing conditions in accordance with the
above code.
1.3 Utility company will dispatch an emergency crew immediately upon receipt of a Code 1 or
Code 4 signal. If all crews are engaged, utility company will detach a crew operating at other
than a Code 1 or Code 4 signal and direct such crew to respond immediately.
1.4 Units should be alert to the possibility that a manhole/transformer incident could have
damaged the adjacent gas piping. If an odor of natural gas is encountered at these incidents,
the dispatcher must be notified to request the immediate response of a utility's gas crew in
addition to their electric crew. Additionally, downed overhead primary and secondary wires
have the potential to damage underground gas piping. All gas piping (plastic, steel, cast iron
and copper) can be impacted by burning, arching or smoldering electric cables.
2. OPERATIONAL GUIDELINES
2.1 The area shall be cordoned off to vehicular and pedestrian traffic. All apparatus shall be
clear of the area in a safe location.
Area shall be taped off. This marks the danger area for civilians and FD personnel.
2.2 Inspect electrical services in surrounding buildings. Units should use carbon monoxide
meters when performing these inspections.
• Possible extension.
• This may also be the cause of the problem.
2.3 Members shall not attempt to move vehicles located in the danger area.
35
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
2.4 Precautionary hose lines shall be stretched as necessary. Units should not operate into
manholes unless requested by a Con Edison employee at the scene. If requested to place
water into a manhole, do not direct the stream directly into the manhole. Instead, let water
flow or pour into the manhole. Use a fog nozzle to reduce or prevent any shock hazard.
2.5 The Officer in Charge shall order response of a utility company emergency crew and
shall request the expected time of arrival.
2.6 When operations are within the capability of a single unit, the Officer in Command may
leave one unit (preferably an Engine Company) to await the arrival of the emergency
crew. If the expected time of arrival is more than 30 minutes, the Officer in Charge,
based on evaluation of existing conditions, may order one of the following:
A. The unit remaining on the scene may respond to assigned alarms received via
department radio; one member shall be left at the scene.
B. One member shall be left at the scene and the unit shall return to quarters.
Company officers shall provide relief for members.
C. When a member is left at the scene, the company officer shall at frequent intervals
contact the dispatcher for re-notification of the utility company.
D. The manhole shall be protected by traffic cones and tape, and all units placed in
service.
2.7 During periods of multiple incidents within an area, the following actions may be
authorized by the deputy chief in charge:
One or more units shall be relieved from response assignments and utilized as follows:
B. The officer and the chauffeur shall remain with the apparatus to perform
surveillance of the incident locations.
D. Deputy Chiefs may authorize the use of messenger vans and spare cars for travel
and shelter of members at incident locations.
A. Be alert to changing conditions and shall call for assistance when necessary.
D. Obtain information necessary for required reports, under the direction of the
immediate superior officer.
36
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
NOTES:
1. Members are reminded that explosions in manholes are not uncommon and that they have
caused serious burns to members of this department.
2. Members should not pull covers off electrical manholes at manhole fires or if a manhole
fire is in the area. It is the responsibility of utility crews to open manhole covers at these
incidents. Pulling covers may cause an explosion by mixing air with the gaseous products
of combustion in the presence of an ignition source e.g., manhole fire and/or electric
arcing.
Note: This does not change Department policy of pulling electric manhole covers under
certain circumstances at gas emergencies.
Be cautious of the PELLET EFFECT from the dirt and gravel that is trapped on the sides
of the cover if an explosion occurs.
3. Explosions can take place after considerable time has elapsed and when the conditions in
the manhole appear dormant. When a cover blows, do not run. Keep your eyes on the
cover so you can approximate where it will land.
4. Serious explosions have also occurred in adjacent manholes that are connected by conduits
with the originally involved manhole.
5. When operating at manhole emergencies, the location of traffic control boxes must be
taken into consideration when deciding the size and location of the "AREA OF
DANGER". The smoke and gases from a manhole incident can travel up the hollow pole
of a nearby light stanchion and at times accumulate with considerable pressure.
The gaseous mixture may be ignited by a spark inside the control box.
6. Hose lines stretched in the street to prevent involvement of adjacent properties should be
positioned at a point beyond the predictable limits of fire or explosion damage.
7. Close and continuous supervision is required to keep citizens and Fire Department
personnel at a safe distance and avoid injuries.
8. Where conditions indicate the electric lines in a building are becoming hot, hose lines shall
be stretched and a thorough examination made.
9. Fire Department representation at the scene shall continue until all dangerous conditions
are alleviated, or until informed by utility company emergency crew at scene that Fire
Department presence is no longer required. Information for the required reports shall be
obtained from the utility company personnel at the scene.
37
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
3. TRANSFORMER VAULTS
Members of this Department must recognize that underground transformer vaults present
a highly volatile situation when encountered. All members must exercise extreme
caution when these incidents occur. The use of full Personal Protection Clothing and
SCBA, even in light smoke conditions, should be stressed when operating.
38
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
C. The possibility of asbestos may also be present, although the Environmental
Protection Agency has mandated that any asbestos present must be removed in
electrical vault systems.
D. The greatest hazard of course is the amount of electricity that is contained in these
vaults.
A. Units are to operate in accordance with the guidelines as set forth in this bulletin and
AUC 266 “ PCB Incidents”.
3.4 Remember the primary consideration at these types of incidents is the safety of civilians
and fire personnel.
39
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
Reference 1
1. INTRODUCTION
The following narrative is an excerpt from a report on an unusual fire incident involving
a Con Ed transformer vault.
“On Arrival Units Found A Light Smoke Condition Issuing From A Sidewalk
Transformer Vault Adjacent To A 40 Story High Rise Office Building. Conditions At The
Vault Deteriorated Rapidly With A Heavy Smoke Condition And Two Explosions
Emanating From The Vault. After The Explosions, Conditions Some What Subsided And
A Smoldering Fire Resulted Until Con Edison Cut The Power. Electricity To The High
Rise Office Building Was Cut And An Examination Revealed No Extension.
Units Stood By While Con Ed Made An Examination Of The Vault. Con Ed Found
That The Cause Of The Fire Was The Theft Of Copper Bus Bars In The Vault.
The Fire Involving The Vault Was Routine. The Cause Of The Fire Is Unusual In
That Someone Entered This Vault And Remove Con Edison Equipment With The Power
Still On. A Con Edison Official At The Scene Stated That The Theft Of These Copper Bus
Bars Has Taken Place In The Past.”
2. CONSIDERATIONS
2.1 Units arriving at the above incidents should be aware that there is a possibility that the
perpetrator of these crimes has been trapped and/or electrocuted in the vault during the
theft.
2.2 Units shall be guided by A.U.C. 180. For operational procedures for fires and
emergencies in this type of installation.
2.3 Members are not to enter these vaults until Con Edison has made their examination.
2.4 Con Edison will make the determination that the vault is safe for entry, if necessary, by
F.D. personnel.
2.5 F.D. personnel receiving this authorization will conduct a cursory search of the vault for
victims.
40
FDNY Probationary Firefighters Manual
Chapter Nineteen NON STRUCTURAL FIRES
Reference 2
Con Edison does not test pole mounted transformers for PCB content.
Almost all of Con Edison's overhead transformers are not, or were not, designed to be
PCB liquid filled. They are mineral oil transformers. However, due to past storage
and/or servicing practices some of these transformers have become PCB contaminated,
i.e., 50-499 PPM PCB. A small percentage of these transformers have attained levels of
500 PPM PCB or greater which classifies them as PCB transformers.
All new transformers being installed by Con Edison as replacements for existing ones
and/or new installations are non PCB transformers.
All officers at operations involving overhead pole transformers shall insure that all proper
precautions are taken to provide for the safety of all members on the scene as outlined in
All Units Circular No. 266 (Revised) and Fire Tactics and Procedures, Hazardous
Materials 2.
41
Probationary Firefighters Manual
Chapter 20
FOAM
FOAM
CONTENTS
1. INTRODUCTION .............................................................................................................. 1
2. CHARACTERISTICS OF FOAM ...................................................................................... 1
3. TYPES OF LOW EXPANSION FOAM ............................................................................ 4
4. IDENTIFICATION ............................................................................................................. 5
5. FOAM PROPORTIONING ................................................................................................ 6
6. FOAM EQUIPMENT ......................................................................................................... 6
7. FOAM DELIVERY SYSTEM ........................................................................................... 7
8. STRATEGIC AND TACTICAL CONSIDERATIONS ..................................................... 8
9. MAINTENANCE ............................................................................................................. 10
10. HIGH EXPANSION FOAM............................................................................................. 11
DEFINITIONS ............................................................................................................. 16
ADDENDUMS
1. INTRODUCTION
1.1 This bulletin will explain the use of foam on flammable and combustible liquid fires and
spills. The topics that will be addressed include foam concentrates, foam equipment and
the foam delivery system. Strategic and tactical considerations, as well as training in the
use of foam, are essential components of a successful operation. Proper foam storage,
replenishment of supplies and maintenance of equipment is necessary to keep the foam
delivery system operational and effective.
2. CHARACTERISTICS OF FOAM
2.1 Foam is a fire-extinguishing agent designed for certain unusual-type incidents. There are
two main categories of foam in use in the Department - low expansion foam and high
expansion foam (Hi-Ex). Low expansion foams are useful on Class “B” fires and spills
involving flammable and combustible liquids. They provide extinguishment and vapor
control when properly selected and applied. High expansion foams are intended to fight
fires of Class "A" combustible materials in areas that are inaccessible to firefighters, such
as cellars and ship-holds. High expansion foam is not suitable for use on outdoor,
flammable liquid fires.
1
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
2
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
3
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
• Finished firefighting foams are designed to be lighter than the fuels they are placed
on and thus float on the surface of the fuel. This results in four primary methods of
extinguishment:
o Smothers - prevents air from mixing with the flammable vapors given off by the
liquid.
o Suppresses - stops or reduces the generation and release of flammable vapors.
o Separates - separates the flame from the surface of the fuel, which reduces the
tendency of the fuel to boil, thus giving off fewer vapors.
o Cools - water content of the foam cools the fuel, further reducing vapor
generation. It also extinguishes burning Class "A" materials in the spill area and
cools adjacent metal surfaces such as tank walls.
• Extinguishing Characteristics
o AR-AFFF foam concentrate is designed to fulfill two specific functions. The first is
to form a protective membrane between the fuel and the foam. The second is to make
the foam much more stable and heat-resistant, which provides better burn-back
resistance.
o AR-AFFF is freeze/thaw stable. If the product is frozen, upon thawing there is no
performance loss.
o AR-AFFF should not be mixed with any other type of foam product.
o AR-AFFF can be used side-by-side with other foam products on the same fire,
when necessary.
o AR-AFFF foam can be generated with either fresh or salt water.
o Properly stored, AR-AFFF can remain effective for up to 25 years.
• Distribution
o AR-AFFF foam is the most widely used concentrate in the Department and is
currently allotted as follows:
Three (3) red-banded five-gallon containers issued to every Engine company.
Two (2) red-banded five-gallon containers issued to every Ladder company.
1500 gallons stored on each of the Department’s five (5) Foam Tankers.
Stored in 55 gallon drums at each of the Foam Tanker locations.
Stored in five-gallon containers at each of the 19 Foam Depots citywide.
Marine Division carries 3300 gallons in both the “343” and “Firefighter 2.”
“The Bravest” holds 200 gallons and each of the 10 - 33’ boats carry 25 gallons.
4
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
• Extinguishing Characteristics
o AFFF spreads rapidly over the surface, leading to faster knockdown of fire than
protein-based foams. This permits use of a lower application rate and results in
less concentrate used.
o AFFF can be used through a standard fog nozzle where the reach of the stream is
a consideration, or in other specialized circumstances.
o AFFF’s rapid drainage time causes poor resistance to flashback and burn-back.
o AFFF is not suitable for use on Reformulated Gasoline, Gasohol or polar
solvents. Its use should be restricted to hydrocarbon fuels which do not contain
any polar additives. It is excellent for fuel oil, kerosene and jet fuel products.
o AFFF has little fuel-shedding ability and it should not be used for sub-surface
injection.
o AFFF has trouble sealing against hot metal tank surfaces. Additional cooling lines
on the tank exterior or higher application rates may be required to overcome this.
o Wind, water spray and extended pre-burn times affect the stability of the blanket.
• Distribution
o FDNY's use of AFFF is limited to a 2 ½-gallon hand-held extinguisher, through a
straight bore nozzle, on small oil burner fires either in or out of the pit.
4. IDENTIFICATION
4.1 It is imperative that the correct foam concentrate is used for the situation encountered.
To ensure that foam concentrates are not mixed, containers are color-coded (banded)
around the top, as follows:
• AR-AFFF RED
• Hi-Expansion YELLOW
• AFFF BLACK
5
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
• At times, the Department will intentionally apply two different types of finished
firefighting foam at an incident. This is routinely done at aircraft incidents.
Port Authority crash trucks are mandated by the Federal Aviation Administration to
use AFFF, due to its fast knockdown capability on jet fuels. Either prior to or after
the evacuation has occurred, FDNY units will arrive and may be faced with the task
of overhauling the scene. This could involve entering a foam blanket that is floating
on jet fuel. Prior to and throughout the entry into this area, a blanket of aerated
AR-AFFF foam should be applied to provide maximum security to our members.
• Modern foams do not have an adverse reaction with dry chemical, but the force of a
high velocity stream of dry chemical can mechanically disrupt a foam blanket. It may
be necessary to utilize a dry chemical extinguisher to extinguish spot fires around the
edges of a tank. Dry chemical must be used to extinguish a three-dimensional fire
when the burning fuel is dropping down. Apply dry chemical in combination with
the foam stream so that any disruption is immediately recovered. This can be
accomplished by discharging the dry chemical into the foam stream using hand-held
extinguishers or one of the Department’s six Dry Chemical Units. The foam stream
will carry the dry chemical to where it is needed.
5. FOAM PROPORTIONING
5.1 Premixed solutions provide little additional benefit and should be restricted to the
following:
• Premixing of AFFF should be limited to the 2 ½-gallon hand-held extinguisher.
5.2 The FDNY purchases low expansion foam concentrate that is used in 1% - 3%
proportioning ratios. Units shall identify the foam to be used in order to set operating
equipment at the correct flow rate.
6. FOAM EQUIPMENT
6.1 Eductors are the most common way to produce foam solution. Every Engine company in
the Department is equipped with a foam nozzle and eductor that can be used with a 1 ¾"
or a 2 ½” hoseline.
6.2 Handlines with foam nozzles may be used in conjunction with an eductor and are very
useful at a small operation like an oil burner with fire outside the pit, gas pump knocked
over, car fire with a ruptured gas tank, a small spill (approximately 600 square feet) or
similar situation.
6
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
6.3 Self-Educting Nozzles have the eductor built into the nozzle. They have a greater
capacity than hand-held nozzles and are very useful at facilities with stationary monitors
or when attached to apparatus with a supply of foam concentrate. The Department uses
these nozzles in conjunction with its Foam Tankers. The Foam Tanker is a self-contained
unit capable of supplying foam concentrate, or finished firefighting foam when supplied
with water. This method of supplying finished firefighting foam is a fast and efficient
way of producing an effective knockdown at a medium-sized flammable/combustible
liquid incident such as a spill over 600 square feet, tanker truck mishap, loading rack
incident or similar situation.
6.4 Master Stream Nozzles are used at the largest-type operations such as oil tank farms,
large spills over 2,000 square feet or a large capacity tank truck that has spilled its
product. In order to perform this operation the foam delivery system must be activated.
7.1 The FDNY Foam Delivery System is a multi-tiered approach, which provides different
levels of response to various sized incidents.
7
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
8.1 The FDNY has the ability to deal with all types of incidents requiring foam application.
The strategy for dealing with many of these incidents includes stopping the leak and
covering the spill surface with foam. In some cases, covering the spill will not allow the
owner to recover the product. If there is no hazard with leaving a spill uncovered it will
greatly assist in recovery, however, if the Incident Commander has any doubts about a
product, cover it with foam.
8.2 General considerations when dealing with any type of flammable/combustible liquid
incident include the following:
• Position apparatus upwind.
• Position apparatus uphill.
• Identify the product.
• Transmit a 10-80 with appropriate code.
• Ensure the correct foam is present. Transmit additional alarms and/or signal 10-86 if
the incident is beyond the first alarm assignment capability.
• Stretch a foam handline (SEE ADDENDUM 1) and put it into operation if upon
arrival the following is observed:
o The product is on fire.
o It is a flammable liquid.
o Members will be operating in the area.
o The product causes an exposure problem.
• Eliminate all sources of ignition starting with the area downwind and downhill.
• Remember that many of these vapors are heavier than air and will collect in
basements and depressions.
• Have the appropriate unit(s) (e.g. Rescue, Squad, HMTU, Haz-Mat Company 1, etc.)
take explosive readings.
• Evacuate as per prescribed distances in the DOT Emergency Response Guidebook.
8
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
• With tanks of this magnitude it is imperative that enough foam concentrate is on
scene before any foam operation is started. This cannot be stressed enough.
If enough concentrate is not on scene before starting foam operations and the fire is
not extinguished, it will burn back and involve the entire tank again. All of the
concentrate that was used will have been wasted.
• If the tank is filled to the top, bulk oil personnel will have to remove some product
via the bottom of the tank. If planning to extinguish the fire, ensure that the product
level is within five feet of the top of the tank. If too much product is removed a large
"chimney" will form and carry away much of the foam. Also, the lower the product
level in the tank, the more likely the top of the tank is to curl in, making application
of foam more difficult. Apply the foam as gently as possible to the surface of the
tank. Try to apply the foam into the "WINDOW". This is an area in the plume,
which is located on the upwind side of the tank. It is a small area where the flames
aren't as tall. There are less convection currents in this area, which allows more foam
to reach the surface of the fuel.
8.4 Spills
• If the spill has ignited, stretch a foam handline and extinguish the fire.
The amount of concentrate available on a first alarm assignment is 13 five-
gallon containers. With one handline in operation, you will be able to extinguish
approximately 600 square feet (20’X30’) of fire. This supply will last approximately
17 minutes at a 3% setting. Using two handlines simultaneously will increase the
area covered, but reduce operational time. Both criteria are important for a successful
operation. Anything more than a small spill may require additional alarms as well as
the transmission of signal 10-86.
Note: NFPA 11 recommends having a 15-minute supply of concentrate on hand for
spill fires.
• If the spill is contained or not flowing:
o Direct a foam stream on the ground ahead of the fire in such a manner as to
bounce the foam onto the fire. This will achieve the widest pattern at the lowest
velocity.
o Try to deflect the stream against something and allow the foam to slide down and
work its way across the burning liquid.
o If the above methods are not possible, then direct the foam stream skyward in a
slow back and forth motion, allowing the foam to fall as gently as possible over
the surface. This will cover the spill and reduce disruption at the blanket.
• If the spill is flowing and not contained:
o Work against the run of the spill, either directly or from the flanks, towards the
source of the spill, directing a foam stream on the ground ahead of the fire in such
a manner as to bounce the foam onto the fire. If the burning liquid is running
down a ditch, gutter or depression, it is best to establish a heavy foam blanket
below the point of fire, so that when the burning liquid reaches the blanket it will
flow underneath it and be extinguished. A hole dug or an earthen dike erected to
collect burning liquid, then covered with a foam blanket, can be utilized under
certain conditions to prevent further flow.
9
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
o Determine if the product entered the sewer system. If not, dike and dam the spill
to prevent it from doing so. If the leak has entered the sewer, the sewer must be
included in the spill area. If the product is burning in the sewers and there is no
exposure problem, it may be beneficial to let the product burn off. If the fire is
extinguished, the product may reach another source of ignition and cause a larger
problem. The Incident Commander shall notify DEP if any product enters the
sewer system.
o Try to find the source of the leak and shut it down, if possible. This should be
performed under the protection of a charged handline. A fog stream can be used
if the runoff will not interfere with the foam blanket and the valve is remote from
the leak.
o Entry into a foam blanket should be limited to the rescue of trapped or injured
victims. All precautions should be taken to provide the most stable foam blanket
possible and additional foam should be applied, as required, to maintain the foam
blanket if members are required to enter. When members move through foam,
potentially disrupting the stability of the foam blanket, a charged foam handline
should be prepared to operate and cover the exposed area. This will add a level of
protection for the advancing members.
8.5 Additional Considerations
• Additional foam must be applied to maintain the foam blanket. Drainage time of the
blanket will depend on the type of concentrate used. The faster the drainage rate, the
more frequent the application necessary. If personnel are working in the blanket
reapplication should be constant.
• Avoid disturbing the foam blanket; this is especially true when walking through it.
There will be instances (i.e. rescue) where members will have to enter the blanket.
All members that enter the blanket shall wear all personal protective clothing,
including a donned facepiece. Personnel working in a foam blanket should be kept to
a minimum. All personnel that are not needed to maintain this blanket should be
withdrawn to an area that could not become involved in the incident.
9. MAINTENANCE
9.1 Foam concentrate can have a severe, debilitating effect on the equipment used to generate
it. Foam eductors, pick-up tubes, FIMMs, generators, hose, pumps, etc. are to be washed
out and cleaned after every use. Anything that comes in contact with foam requires
flushing. When cleaning an eductor, water should be educted through it until clean water
flows through the eductor.
9.2 All valves, pumps and gates of foam pumpers need to be operated on a regular basis to
maintain functionality.
10
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
10. HIGH EXPANSION FOAM
10.1 High expansion foam concentrate is a detergent-based product designed for use in special
generators that blow large quantities of air through a screen, which is being sprayed with
solution. This results in the production of large quantities of very large, light foam
bubbles. These bubbles have much less resistance to disruption by wind, water spray,
heat or fire than do other foams. Hi-Ex foam is best suited for use in confined areas on
Class “A” fires. It is not recommended for use on flammable liquid incidents because the
foam blanket can become permeated with vapors, which can subsequently ignite.
10.2 Hi-Ex foam is primarily used to control fires that are inaccessible or difficult to approach
due to excessive heat. It is particularly suited for use on Class “A” fires in confined
spaces. Hi-Ex foam can confine and suppress the fire to a point where final
extinguishment can be achieved with less debilitating effect on members. Under certain
conditions Hi-Ex foam has been found effective on:
o Liquid Natural Gas (LNG) fires.
o Suppressing or minimizing the release of toxic or flammable vapors with the
exception of Liquefied Petroleum Gas (LPG).
10.3 Expansion is dependent upon the type of Hi-Ex foam concentrate and generator used.
An expansion ratio of 200/1 to 1000/1 is necessary to be classified as Hi-Ex foam.
10.4 Bubbles are much larger and consistencies considerably lighter than low expansion foam.
10.5 The size and consistency of Hi-Ex foam bubbles are determined by:
• Type of foam concentrate.
• Type of generator.
• Water pressures at eductor and generator.
• Contents of foam bubbles (fresh air, smoke, CO2, CO, etc.).
• Eductor mixture setting.
• Use and configuration of foam chute.
10.7 The effectiveness of a Hi-Ex foam blanket depends on the expansion ratio, eductor
mixture setting and thickness of the blanket, and drainage time characteristics.
Increasing the setting on the eductor can increase the thickness of the blanket, increase
the foam’s resistance to heat and fire and improve drainage time. The amount of
concentrate used will also increase.
11
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
10.8 Components of the Hi-Ex Foam System:
• Foam concentrate in five-gallon containers with yellow band.
• Water supply line. The length of the line should be kept as short as possible by
placing the pumper or manifold as close to the operation as conditions permit. Fresh
or salt water can be used to develop Hi-Ex foam.
• In-line proportioning device (eductor) with a pick-up tube affixed to it.
This device employs a venturi action to pick up foam concentrate from a container
and introduce it into the stream.
o Only the eductor supplied with the Hi-Ex generator should be used.
This eductor should have a 1" yellow band painted around the throat.
o Each eductor is designed to operate at a pre-determined amount of water flow.
o The metering valve, if present, may be adjusted from 1% to 6%. The dial can be
set at any point to give a more diverse selection of foam consistency. These
calibrations are relative and do not necessarily indicate the actual percentage of
solution that will be formed. The higher the setting, the heavier the resulting
body of foam and the quicker the rate of foam concentrate consumption.
o The balance between the eductor intake pressure and the pressure at the foam
generator is critical. Any factor that would upset the balance (e.g. friction loss in
the line, head pressure, etc.) could affect the formation of foam.
o Insufficient pressure at the eductor may prevent pick up of foam concentrate or
supply inadequate pressure at the foam generator. The generator’s distance from
the eductor, as well as the grade difference between the generator and eductor,
also affects the pressure at the foam generator.
10.9 Although a relatively small flow of water is required in Hi-Ex foam operations (60
GPM), high pump pressure is necessary to overcome the pressure loss at the eductor.
Maintain between 200 PSI and 220 PSI at the inlet of the eductor to deliver sufficient
water under proper pressure to the foam generator.
10.10 Eductor placement is dependent on the conditions encountered in the field. It may be
placed one length from the pumper or at the generator. Placement one length from the
pumper is the recommended position for most fire situations. This location affords better
control of:
• Water flow rates.
• Metering valve settings.
• Foam supply (reduces distance foam concentrate must be transported).
10.11 The eductor is equipped with a ball check. If the generator is shut down or there is a
restriction in the hoseline, the ball check prevents water from flowing into the foam
container.
12
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
10.12 At the completion of foam operations, the ECC should remove the eductor pick-up tube
from the foam container, place it into a pail of fresh, clean water and run the system at
the same pressure used during operations for 15 minutes to adequately flush foam from
all components of the system. If the eductor is not flushed thoroughly, foam concentrate
may dry inside it, causing the unit to malfunction.
10.13 The foam generator converts foam solution into Hi-Ex foam.
• Foam solution is supplied to the inlet of the generator at a pressure specific for the
generator.
• A nozzle-like orifice sprays solution into the body of the generator.
• Air is forcibly introduced into the spray by a water or electric-powered fan mounted
on the rear of the generator.
• Aerated spray is forced through a screen on the front of the generator and expands
into Hi-Ex foam.
10.14 The Foam Chute Applicator is a plastic sleeve used to deliver Hi-Ex foam from the
generator to the fire.
• The generator should be used with the delivery chute. The chute used should be one
foot larger in diameter than the mouth of the generator. It fits over the generator
screen and is secured by means of a metal band or rope.
• Eliminate kinks or bends in the chute as much as possible.
• The chute cannot be placed to deliver foam to a level higher than that of the
generator. The generator cannot overcome the backpressure of the foam. Foam will
flow back down the chute and out through the generator, ceasing foam generation.
• The generator can also be used as a smoke ejector. Turning the generator around will
accomplish this.
14
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
10.17 Operational Considerations
• Fires may be brought under control in inaccessible areas, collapse areas and areas
where toxic materials are stored. For example, in storage areas containing toxic
materials (e.g. fertilizers, pesticides, insecticides, etc.) use of Hi-Ex foam would limit
water runoff that could cause widespread contamination to people, terrain, sewers,
manholes, waterways, etc. Its use would reduce exposure of toxic substances to
members since a minimum number of properly-equipped personnel would be required
to operate in the exposed area.
o Hi-Ex foam is a firefighting tool that uses a minimum amount of water and should
be considered for use when water is at a premium.
o Hi-Ex foam chutes of various lengths allow personnel to apply foam from a safe
distance. This is particularly advantageous during operations involving buildings
in danger of collapse.
15
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
DEFINITIONS
Angus Modified Foam Cannon – A large capacity (1000 GPM) aerating foam nozzle used to
apply large quantities of foam.
Aerated Foam – Foam produced by nozzles that force air into the flow of foam solution.
Application Rate – The rate in GPM of foam solution that is needed to extinguish a flammable
or combustible liquid fire or to cover a fuel spill.
Back-Flow Prevention Valve – A 4 ½" check valve designed to prevent foam solution from
backing up into the domestic water supply. This valve must be attached to the hydrant supply
when the pumper is involved in a FIMM operation. This includes any pumper used to augment
the FIMM pumper.
Backup Pumper – A 1000 GPM pumper that responds when a Satellite 2000 GPM pumper is
not available for a foam operation. It is assigned to transport the Satellite apparatus with its tools
and equipment.
Boiling Point – The temperature at which vapor pressure equals atmospheric pressure.
The lower the boiling point, the faster the liquid will change to a vapor.
Burn-back Resistance – The ability of a foam blanket to resist direct flame contact.
Drainage Time – Amount of time it takes for the water to drain from a finished foam blanket.
Eductor – A proportioning device that employs a venturi action to pick up foam concentrate
from a container and introduce it into a stream of water, thus producing foam solution.
The eductor must match the rated flow from the nozzle (GPM).
Fire Point – The temperature to which a vapor has to be heated to sustain combustion.
This temperature is usually no more than three degrees above the flash point.
Flammable Liquid – A liquid with a flash point below 100 degrees F. and a vapor pressure of
40 PSIG at 100 degrees F.
Flammable Range (Explosive Range) – The percent of a flammable vapor mixed in air to form
an ignitable mixture.
16
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
Flash Point – The minimum temperature to which a liquid must be heated to produce enough
vapors to allow a vapor flash when an ignition source is present.
Flashback Resistance – The ability of a foam blanket to resist ignition by the flammable vapors
coming in contact with a hot surface or a spark.
Foam (Finished Firefighting Foam) – An unstable air/foam solution emulsion used for
firefighting.
Foam Tanker – A tanker which carries 1500 gallons of AR-AFFF foam concentrate. This unit
is equipped with a foam deck gun.
Foam Chute – A plastic sleeve used to deliver Hi-Ex foam from the generator to the fire.
Foam Concentrate – A liquid which, when mixed with water, creates a foam solution.
Foam Coordinator – A Battalion Chief trained in the operation of the foam system.
All Battalion Chiefs are trained to function in this role.
Foam Depot – A unit that stores at least 50 five-gallon containers of AR-AFFF, 50 five-gallon
containers of Hi-Ex foam concentrate and additional containers of AFFF.
Foam Injection Metering Module (FIMM) – A device that attaches to the gated inlet of a
pumper and proportions foam concentrate into the pumps as it is supplied by the Foam Tanker.
It is ejected under pressure into water, creating a foam solution.
Foam Nozzle (Aerating) – A nozzle used to discharge foam solution, mixing air into the
solution to produce finished firefighting foam.
Foam Solution – A mixture containing foam concentrate and water. Solution is pumped
through hoselines with foam nozzles where it is mixed with air to produce finished firefighting
foam.
Foam System – The Department's foam system consists of the Satellite System (six 2000 GPM
pumpers along with their corresponding Satellite apparatus), backup pumpers, Foam Tankers,
the Foam Tender, Foam Depots, Foam Coordinators and Marine units.
Frothing – The production of a mass of bubbles in or on a liquid. This occurs when foam
concentrate is transferred at a rapid rate or is allowed to splash into a container.
Hi-Ex Foam Concentrate – A detergent-based liquid which, when mixed with water and
deployed with an aerating device, produces lightweight foam with an expansion ratio of 200/1 to
1000/1.
Hydrocarbons – Compounds that only contain carbon and hydrogen. Examples are methane,
ethane, butane and propane. Gasoline, diesel, home heating oil and crude oil are hydrocarbons
that contain additives.
17
FDNY Probationary Firefighters Manual
Chapter Twenty FOAM
Methyl Tertiary Butyl Ether (MTBE) – A slightly polar additive, added to gasoline to meet
Federal Air Standards.
Non-Aerated Foam – Foam produced by a nozzle that does not force air through the foam
solution. A foam nozzle that is non-aerating generally has a greater reach than an aerating
nozzle; the tradeoff is a foam blanket that is not as stable as one that is produced with aerated
foam.
Pick-up Tube/Hose – A tube or hose in which the foam concentrate is moved from the source
(container) to the eductor.
Polar Solvent – Water-soluble chemicals that readily combine with water in a foam blanket,
thus destroying it. Examples are alcohol, ether, lacquer, thinner and acetone. Alcohol resistant
foam needs to be used on these substances.
Pour Point – The minimum useable temperature at which foam concentrate can be proportioned.
Satellite System – Six 2000 GPM pumpers (along with their corresponding Satellite apparatus)
that are equipped with a FIMM incorporated into the pump control panel.
Vapor Density – A measure of density in vapors compared to air. Refers to whether a gas will
rise or fall when mixed with air. A substance with a vapor density greater than 1.0 will sink
while a substance with a vapor density of less than 1.0 will rise, when mixed in air.
Vapor Pressure – The pressure of a confined vapor in equilibrium with its liquid. Increasing
the temperature of a liquid will produce more vapors and increase the vapor pressure.
Venturi Action – As water flows through an eductor, negative pressure is created in the pick-up
tube. The foam concentrate is suctioned from the container to the appliance.
Water Supply Pumper – An Engine company assigned the duty of supplying water to a FIMM
pumper. This water supply pumper must use a Back-Flow Prevention Valve.
18
FDNY Probationary Firefighters Manual
Chapter Twenty ADDENDUM 1 FOAM
1. PROCEDURE
1.3 Ensure a sufficient quantity of AR-AFFF (red band) foam concentrate (five-gallon
containers) is at the location of the operating pumper.
1.4 The officer gives the command to start water. The member at the pumper places the pick-
up tube into the container and the ECC starts water, providing 200 PSI at the eductor.
The foam nozzle shall then be fully opened and directed at the fire.
• Upon opening the nozzle, foam solution will immediately flow from the nozzle.
Avoid opening and closing the nozzle as this interrupts the educting process and
causes an intermittent flow of foam.
• After charging the line, the ECC shall monitor the go-gauge to ensure that, with the
nozzle fully open and water flowing, the go-gauge needle remains in the green. If the
needle enters the red, this will indicate a flow problem which the ECC needs to
correct. When the needle is in the red the following could be the cause of the
problem:
o Kink in the line - Ensure there are no kinks in the supply line.
o Elevation - When operating uphill, head pressure is created and will have minimal
effect on foam production; however, this could cause the needle on the go-gauge
to approach the red.
o Nozzle not fully open - In order for the eductor to function properly, the nozzle
should be opened fully when in use.
o Nozzle shut down.
NOTE: Always use the matching GPM foam nozzle and eductor.
19
FDNY Probationary Firefighters Manual
Chapter Twenty ADDENDUM 2 FOAM
1. DESCRIPTION
1.1 The 125 GPM Foam Eductor has been issued to all Engine and Squad companies. It is
housed in a protective pelican case which includes the following equipment:
• 125 GPM Foam Nozzle with pistol grip (adjustable fog/straight stream)
• Extra-long pick-up tube
• Go-gauge (with Red and Green indicators)
• Metering head (meters at 1% - 3% - 6%)
1.2 The 125 GPM Foam Eductor shall be used with Universal Gold 1%-3% AR-AFFF foam
concentrate (red band container).
1.3 The 125 GPM Foam Eductor and Foam Nozzle combination provide the following
benefits:
• Allow for longer stretches, when required
• Greater reach of the stream
• Faster foam on the fire
• Faster clean-up
1.4 The go-gauge needle has two positions; green and red. The needle in the green indicates
proper foam proportioning. The needle in the red indicates there is a problem such as the
following:
• Kink in the line
• Burst length
• Nozzle not fully open
• Nozzle shut
• Elevation problem
20
FDNY FOAM, ADDENDUM 2
Chapter Twenty 125 GPM FOAM EDUCTOR AND NOZZLE
Figure 2: Go-Gauge
21
FDNY FOAM, ADDENDUM 2
Chapter Twenty 125 GPM FOAM EDUCTOR AND NOZZLE
2. OPERATION
2.1 The eductor is to be operated at the pumper outlet only and is not to be operated in-line.
• Place the eductor onto the pumper outlet.
• Connect the metering head to the eductor.
• Place the pick-up tube into the foam bucket.
• Eductor is to be operated with either 1 ¾” hose or 2 ½” hose. The stretches are not to
be combined. When stretching 1 ¾” hose not more than six (6) lengths are to be used
off of the eductor. When using 2 ½” hose not more than ten (10) lengths of 2 ½” hose
are to be used off of the eductor.
• When foam is called for, the ECC supplies the foam line with 200 PSI/125 GPM.
• The nozzle is to be maintained completely open.
• The nozzle is capable of providing fog or straight stream and is equipped with a flush
position.
• The go-gauge needle should be in the green position. If the needle is in the red, a
problem exists and foam is not being produced at the desired percentage.
22
FDNY FOAM, ADDENDUM 2
Chapter Twenty 125 GPM FOAM EDUCTOR AND NOZZLE
23
Probationary Firefighters Manual
Chapter 21
Portable fire extinguishers are classified according to their intended use on the four classes of
fires (A, B, C, and D). In addition to the letter classification, extinguishers also receive a
numerical rating. The number preceding the letter designates the potential size fire the
extinguisher can be expected to extinguish (Figure 2-1).
Extinguishers suitable for more than one class of fire should be identified by multiples of the
symbols previously described. Most present-day extinguishers have these markings on them
when they are purchased. If a new extinguisher is not properly marked, the seller should be
requested to supply the proper decals.
The “picture-symbol” labeling system now in use is designed to make the selection of fire
extinguishers easier and their use more effective and safe. The system also emphasizes when not
to use an extinguisher on certain types of fires. Examples of this labeling system are shown in
Figures 2-2 and 2-3.
Figure 2-1
1
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
Figure 2-2
Figure 2-3
Class A Fire Class A fires, listed under the green pyramid involve such things as wood, cloth,
paper, rubber and many plastics. Generally, these ordinary combustibles require
cooling with water or certain dry chemicals that also retard combustion.
Class B Fire Class B fires, listed under the red square involve flammable liquids, flammable
gases, greases. Exclusion of air by smothering, or inhibiting the combustible chain
reaction with a chemical are the most efficient methods of extinguishment for
Class B fires,
Class C Fire Class C fires, listed under the blue circle, involve live electrical equipment, and
for safety reasons, a non-conductive agent must be used to extinguish these fires.
Class D Fire Class D fires, listed under the yellow star, involve burning metals such as
magnesium, sodium, or potassium. These fires require an extinguishing agent that
does not react with the burning metal to give off dangerous gases or cause
explosions
2
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
Hand
Pump
Assembly
CAP
Container
HOSE
Shoulder
Harness
3
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
Freeze: Yes
Electricity: Conductor
Maintenance:
Wash flush head and container after use. Examine container
for rust etc. Check head assembly, strainer, gasket, hose
coupling, hose for brittleness, nozzle clogged, head coupled
properly. After recharging check gauge reading and for
leakage. If hydrostatic test date is greater than 5 years,
extinguisher must be placed out of service.
To Operate:
Hold upright, pull pin, grasp hose, squeeze lever, direct
stream at base of fire.
4
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
5
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
CHARGE ADAPTER
6
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
ADAPTER IN PLACE
Note: The apparatus has a one way valve in the airline to prevent water from entering the
brake system.
7
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
.
PRESSURIZED AFFF FOAM EXTINGUISHER
1. Container Or Shell
2. Discharge Lever
3. Pressure Gauge
4. Head Assembly
5. Hose Nozzle
6. Siphon Tube
7 Bottom Screen
8. Locking Ring Pin
9. Air Valve
It is not necessary to play AFFF against a backboard or the side of the tank to form a film on the
surface. It can be applied gently on the surface of the oil by placing a finger over the nozzle.
However, the stream SHOULD NOT be driven directly through the surface due to the
possibility of causing a steam explosion or splashing hot oil back on the operator.
8
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
CO2 EXTINGUISHER
1. Cylinder
2. Discharge Lever
3. Locking Ring Pin
4. High Pressure Hose
5. Insulated Handle
6. Discharge Horn
Extinguishing Agent: CO2 gas (heavier than
air) smothers fire
Use: Class B Fires
Class C Fires
Class A Fires – Small surface fires only
Capacity: 2 to 20lb. (net weight of gas)
Range: About 4’
Pressure Source: Liquefied CO2 at pressure of
900 psi
Examine: EachTour,i.e.9x6&6x9
Recharge: When expended loss of 10% of
weight, check every 6 months
Freeze: Will operate at -40 F
Maintenance: Keep clean; check for damage;
weigh to determine if it is filly charged; don’t
drop.
~-
9
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
To Operate: Pull pin, squeeze lever, direct discharge at base of fire. On flammable liquid fires,
discharge as directed at the near side of the fire, moving the nozzle rapidly side to side and
gradually progressing forward as the flames are extinguished.
10
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
PURPLE K EXTINGUISHER
Extinguishing Agent: Potassium bicarbonate
base dry chemical
Use: Class B fires. Particularly effective in
combating methanol fires.
Operation:
11
FDNY Probationary Firefighters Manual
Chapter Twenty One PORTABLE EXTINGUISHERS
12
Probationary Firefighters Manual
Chapter 22
HOUSEWATCH
22
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
T he member performing housewatch duty is responsible during the assigned watch for the
receipt of all communications directed to all units assigned or relocated to quarters.
The most important communications received by the housewatch are those which direct
units to respond to alarms of fire and emergencies.
The receipt of the alarm and the communication of that alarm information to the units assigned is
the responsibility of the member assigned to housewatch.
Appearance
♦ The member assigned to housewatch duty is an official representative of the Fire Department
and his assigned unit to other members of the department and to the general public.
♦ As such a representative the member assigned shall present a neat and clean appearance. The
member assigned to housewatch duty shall insure that the housewatch area is maintained in a
clean and orderly fashion.
♦ All visitors to quarters shall be addressed by the housewatch. Members of the department
shall be addressed officially and the reason for their visit ascertained and relayed to the
officer on duty. Other visitors shall be addressed with courtesy, the reason for their visit
ascertained and relayed to the officer on duty.
Alarm Receipt
When an alarm is received it shall be promptly acknowledged and the Company turned out. The
particulars of the alarm shall be read aloud and addressed to the members of the units responding
when they have reached the apparatus floor.
Communications
♦ Official department phone lines in quarters shall be kept open during the hours 0800-0900
and 1700-1800 to facilitate any changes in manning assignments for the ensuing tour.
♦ The member assigned to house watch duty is assigned to monitor the department telephone
and is responsible for the receipt and transmission of all telephone messages.
1
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
♦ The members assigned to housewatch duty shall answer the department phone in the
following manner:
Company Journal
♦ The member assigned to housewatch duty is responsible to maintain entries in the Company
Journal in accordance with “The Guide to Company Journal Entries”.
♦ The Company Journal shall be kept neat and up to date at all times.
♦ There are still some of the traditional BARS alarm boxes in use.
A BARS alarm box is an electromechanical device which, when activated, will send a
coded signal to a Borough Communications Office. These boxes are non-interfering which
means that several boxes can be pulled on the same circuit simultaneously without
interfering with each other's signals.
♦ The ERS alarm box allows the caller to establish direct voice contact with the Fire or Police
Department to report a fire or other emergency.
Each ERS alarm box contains two channels identified by the words "Fire" and "Police" on
the outside of the alarm box. Depressing the push button beneath the appropriate handle
will activate the system.
2
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
TELEPHONE ALARMS
♦ A civilian may transmit an alarm by telephone by dialing either the seven-digit number of
the Borough Communications Office, 911 or 0. The first alternative is preferred. It is
important to know that the alarm was transmitted by telephone since statistically these are
more likely to represent legitimate alarms.
♦ Special building alarm systems are located in buildings and tunnels and on bridges,
highways and on Randall’s and Wards Islands. These alarm systems are installed,
maintained and monitored by either the Fire Department or by private fire alarm
companies. They are referred to collectively as Class 3 alarms because 3 was the
preliminary telegraph signal used to announce such alarms.
Under provisions of the City's high rise fire safety code, Local Law 5, all high rise
buildings (occupancy group E) are required to have Class E private alarm systems installed.
These systems include various types of manual and automatic alarms connected to a fire
command station in the building lobby. Alarms are automatically transmitted to the private
fire alarm company from the fire command station.
♦ These alarms are transmitted via recording or pre-dialed machines either directly to the Fire
Department or to a private fire alarm company for relay to Fire Department.
VERBAL ALARMS
♦ Verbal alarms are fires or emergencies reported to or observed by units while in or out of
quarters.
3
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
♦ The Computer Assisted Dispatch System (CADS) within the Bureau of Communications
helps the Fire Department by facilitating the dispatch of units; maintaining coverage; and
organizing information. Every unit in the Department is linked to CADS via a Personal
Computer/Alarm Teleprinter Selector (PC/ATS) which:
o provides concise information in printout form relative to response
(retained printouts serve as the basis for reports, etc.)
o transmits administrative messages
o provides information relative to hazardous situations contained in the
Critical Information Dispatch System (CIDS).
Figure 2-1
4
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
♦ Selector Panel
The PC/ATS interface (Figure 2 - 2) provides a convenient means of reporting a unit's status
or acknowledging a response. The PC/ATS interface is composed of Unit Identification
Buttons, Status Buttons and Function Buttons.
The screen is a touch screen. Most objects (finger, pen, glove, etc) can be used to select a
button. Touching the screen on the button or anywhere within the border surrounding the
button will select the button. The button can also be selected by pressing the underlined
character on the keyboard. When a button is selected, the border surrounding the button will
change to red.
Figure 2-2
5
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
♦ Status Buttons
♦ Function Buttons
6
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
7
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
Immediately upon return to quarters, and if "available", update status by bringing unit "in
service"
EXAMPLE: L123 AQ SEND
After the SEND button is depressed, the computer will return, in small print, an
acknowledgment of the status entered.
Note: All units in the same quarters can make themselves AQ simultaneously
unless:
a. Units responded to different boxes.
b. Unit(s) did not go 10-8.
c. One unit is a relocated unit.
♦ Verbal Alarms
8
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
♦ RCP Button
Units that are granted R&R shall not go 10-8 when leaving the scene of an incident. Upon
return to quarters, place unit on R&R via selector panel in the following manner:
At the conclusion of recuperative time, the unit will bring itself back into service in the
following manner:
Note: The unit’s officer shall ensure that the unit comes back in service at the appropriate
time via the PC/ATS.
A. The relocated unit must use the ACT'G button at all times to identify itself.
Indicates relocated unit is in service as E033, either initially or returning from the scene
of an incident.
Note: The ACT'G button can only be used by the first relocator into the original unit. If
subsequent relocations are made into that unit, the ACT'G button can no longer be used.
Thereafter acknowledgments and status reports must be done via Voice Alarm, radio or
telephone.
9
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
D. Units must be 10-8 in order to go AQ via the PC/ATS in their quarters. If not, an error
message will be generated to that unit to call the dispatcher via telephone to verify and
update their status.
If the original unit goes 10-8 while the first relocator is in their quarters, a RETURN
FROM RELOCATION ticket will be sent to that firehouse informing the relocated unit
to return to its own quarters. This message must be acknowledged by using the ACT'G,
UNIT, 10-4 and SEND buttons. If the ticket is not forthcoming, the relocated unit shall
call the dispatcher by telephone. Under no circumstances should a unit leave before
receiving a teleprinter message to do so.
♦ Interchange
Units leaving quarters for interchange shall call the dispatcher by telephone for
instructions.
♦ Error Handling
When the wrong identifying or status buttons (or both) are pressed, merely press the
CLR/TEST button. All borders will turn red. Take finger off the CLR/TEST button and the
red borders will turn off. Start over again in the proper sequence to complete the message. If
the mistake involves a response, and is not noticed until after the SEND button is pressed,
immediately notify the officer who in turn will call the dispatcher, by department radio, and
give particulars.
Note: The status buttons are self-correcting, so if a mistake is made in that phase,
pressing the correct button resolves the problem.
10
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
There are two types of teleprinter messages: Response messages and Administrative messages.
Two types of printing are used to differentiate between the two types of messages. Response
messages are in EXPANDED print and require an acknowledgment. Administrative messages
appear in smaller print and do not require an acknowledgment.
o Response Messages
Response messages include messages to respond, relocate and return from relocation.
Only the units affected receive these messages. All messages requiring a unit response
contain information as to the type of alarm, unit(s) assigned, source of alarm, the nearest
box number and location, an incident number and the date and time the message was
transmitted (the "time out"). In addition, information on hazardous materials may be
provided through CIDS.
If an alarm is received by telephone or from an ERS box, information about the address,
type of structure (residential, commercial) and location of fire (apartment number,
basement, etc.) may be provided.
For an explanation of the coded numerical signals used in teleprinter messages, see
FDNY Communications Manual: section 2.5.1.
11
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
B. Class 3
This message indicates that the source of the alarm is a Class 3 Special Building Alarm.
These alarms are described in Chapter 1, Section 1.4 of this Manual.
W HOUSTON ST BLEECKER ST
1=STRUCTURAL AFA VALVE
INCIDENT# 7
09/15/03 224815
Line 3. Initial signal 3 indicates a private fire alarm box; 342 is the box number and 42 is
the terminal number which designates a specific area within the building.
Line 5. AFA is the abbreviation for one of several private fire alarm companies. Valve
indicates the type of special alarm.
12
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
E 14 ST E 13 ST
B=STORE BASEMENT
INCIDENT# 21
09/15/03 233120
D. Greater Alarm
SIG 2 - 2
2ND ALARM
E055 E015 E028 L008 ST01 FC01 E009 SB01
NASSAU ST WILLIAM ST
C=OTHER COMMRCL 5 FLOOR
INCIDENT# 17
09/15/03 232117
13
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
E. Phone Alarm
This message designates an alarm originating with a telephone call to the dispatcher.
NASSAU ST WILLIAM ST
C=OTHER COMMRCL 5 FLOOR
INCIDENT# 17
09/15/03 231846
F. Relocation
Units being relocated must acknowledge this message as they would a run and notify the
dispatcher by radio when they reach the response district of the unit they have been relocated
to.
07/05/03 210525
14
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
Units must wait for a Return from Relocation ticket before returning to their own quarters. If
both the original and relocated units are AQ in the same quarters and a Return from
Relocation ticket is not received, contact the dispatcher by telephone for instructions. A
relocated unit must not return to their own quarters without being instructed to do so.
This message is to be acknowledged using: UNIT I.D., ACT'G, 10-4 and SEND buttons (first
relocator only).
07/05/03 203603
H. Administrative Messages
Administrative messages appear in small print on the PC/ATS. They do not require
acknowledgment.
This message will be transmitted if a second relocated unit uses the PC/ATS to report
its status. A call to the dispatcher is required as an answer to this message. To avoid
confusion, second relocators must report in service by telephone or, if that isn't
possible, by Voice Alarm.
ACT'G UN2 AQ
07/05/83 202854
07/05/03 202855
15
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
♦ The company journal records chronologically the day-to-day events of a unit. In it are
entered vital particulars of alarms, accidents, deaths, injuries, other matters requiring an entry
for proper record keeping. As such, it forms an official enduring record to be retained for 20
years. Therefore, it is incumbent upon all members to exercise the utmost care in the main-
tenance, use and preservation of this journal.
♦ The purpose of this guide is to:
a. Set up simple standardized procedures for company journal entries, making them as
concise, yet as informative as possible.
b. Assure entries which will aid in the continuity of supervision providing incoming officers
with a chronological resume of activities since the last working tour.
c. Increase the efficiency of all units.
GENERAL INSTRUCTIONS
♦ Entries shall be neat, accurate and properly indexed. Entries by member on housewatch shall
be in blue or black ink. Entries by other members shall be in red ink. No line shall be left
blank between entries. Each line shall be started at left in a uniform manner.
♦ Entries omitted shall not be forced. They shall be made at time of discovery of omission by
member responsible for entry and include full particulars that would have been made in
omitted entry.
♦ Entries by members, other than member on housewatch, are to begin with rank and surname,
thereby eliminating signature. However this shall not apply to roll call entries.
♦ When member, other than member on housewatch, makes an entry in a unit to which they are
not assigned, member shall write unit number after their name. Members making entries in a
company journal shared by two (2) or more companies shall write number of their unit after
their respective names.
♦ When articles are received or delivered the housewatch entry shall begin with the word
"received" or "delivered."
♦ In quarters housing two (2) or more companies the officer in command of each unit shall
write a separate roll call.
16
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
♦ At the beginning of each calendar day, immediately following 2400 hrs. and before taking
over of housewatch duties, the day and date shall be written across the page on line directly
below last entry of the previous calendar day. Also, on same line in "Time Column" 0001
shall be written.
♦ Members beginning housewatch duties at time of a roll call shall not make an entry of that
fact until particulars of roll call have been duly entered by the officer in command.
♦ Entries of members reporting for duty shall be limited to one such member per line.
♦ Incoming member reporting for duty and finding unit out of quarters shall record his entry in
company journal. Officer on duty shall call the roll, make entry of departure and proceed as
per Section 11.1.6, Regulations. Particulars of roll call shall be duly recorded upon return
from operations.
♦ Civilian employees of the Department shall make entries in their own handwriting in
company journal when entering and leaving quarters.
♦ Members returning from alarms during their assigned housewatch tour shall record return as
"RESUMING HOUSEWATCH".
♦ If return is beyond their assigned housewatch tour, the relieving housewatch shall record
return as "ASSUMING HOUSEWATCH".
♦ Military Time shall be used when making entries except that the terms 9x6 and 6x9 shall be
used to designate tours of duty.
♦ If a unit is required to respond to an alarm while the officer is in the process of writing the
roll call, members shall be permitted to make necessary entries in company journal e.g. OT
entries.
♦ The officer shall when returning to quarters from the response, continue the roll call.
Members are not to skip any lines when making their entries.
♦ Entries concerning events or conditions requiring notifications shall include the name,
rank/title and unit of persons(s) notified.
17
FDNY Probationary Firefighters Manual
Chapter Twenty Two HOUSEWATCH
LAYOUT OF JOURNAL
♦ Pages 500 running backward to 498 shall be ruled and indexed to record chief's visits in
accordance with Regulations.
♦ Pages 497 running backwards to 495 shall be ruled and indexed to record company drills,
using the following columnar headings: Date; Training Subject; Conducted By; Groups on
Duty.
♦ Individual Page
Across top of first line shall be legibly written the complete date.
For example: Monday, May 30, 1965
1st column from left (time column) shall be used to record time of each entry. No mark
other than time shall be entered in this column.
2nd column shall be known as "Flagging Column" and used to rapidly locate and
emphasize entries of an unusual or serious nature, or entries of special interest that affect
the administration of the unit. The use of "Flagging Code Letters" shall be limited to
those specified in this guide.
Where the journal supplied does not have a flagging column, unit commanders shall
cause a red line to be drawn 3/8" to the left of the existing red line to provide for such
column.
3rd column shall be used to record the complete journal entry.
♦ Rear pages of company journal shall contain a record of chief's visits and company drills. All
other records, statistics, etc., shall be maintained in Office Record Journal. The receipt and
dispensing of fuel etc., shall be recorded in company journal chronologically at time of this
activity.
18
Probationary Firefighters Manual
Chapter 23
DECONTAMINATION PROCEDURES
23
FDNY Probationary Firefighters Manual
Chapter Twenty Three DECONTAMINATION PROCEDURES
1. PURPOSE
1.1 After a hazardous materials release, vapor or aerosol hazards can still exist on victims
even after they have left the area of the release. Toxic levels of a material may be
trapped inside clothing, which can vaporize (off-gas) and continue to harm people even
after they have left the scene. Rapid physical removal of the material from the victims is
the single most important action associated with effective decontamination. Reasons for
decontaminating exposed victims are:
1. Removal of the agent from the victim's skin and clothing to prevent any additional
exposure.
2. Protecting responders and medical personnel from cross contamination.
3. Providing psychological comfort to the victims by removing contamination.
2.1 In New York City, an incident may result in a large number of contaminated victims that
need to be rapidly decontaminated. The Fire Department must have procedures in place
to ensure that a simple and effective method of performing gross Decon can be set up and
operational as quickly as possible. Our ability to deliver large volumes of water quickly
is the key to reducing exposure times and saving lives by rapidly removing
contamination.
2.2 All exposed people must be immediately removed from the area of the release to an area
of safe refuge. This area of safe refuge is considered to be in the warm zone, but is
physically removed from any contamination and thus prevents any additional exposure to
the released agent. The concept of the Mass Decontamination Procedure is to establish a
"Gross Decontamination Corridor". Process the contaminated victims from the hot zone
or area of safe refuge to the cold zone, where they can safely be released or transported to
a medical facility for further care. The purpose of the corridor is to remove the
contamination from the victim. This process is accomplished in two steps:
2. Wash the victims down with water – soap can be added to the process if available.
1
FDNY Probationary Firefighters Manual
Chapter Twenty Three DECONTAMINATION PROCEDURES
Ideally, removal of victims' outer clothing should be the first step in the Decon
process after removing people from the contaminated area. Studies have shown
that removing a victim's clothing removes up to ninety percent of the
contamination. Street clothing will absorb liquids, which will continue to
vaporize and further expose the wearer. Quickly removing outer clothing vastly
reduces the exposure time, and thus the total dose received, of any contaminant.
Also, a stream of water, even in a fog spray, will drive any liquid contaminant
further inside clothing towards a victim's body, increasing the likelihood of skin
absorption. Civilians must be informed of the benefits of removing their outer
clothing and encouraged to do so. There will be some people who will not
remove their clothing, regardless of the circumstances or the benefits. Such
persons should be encouraged to remove what they will, and continue through the
Decon process. (For a firefighter wearing bunker gear, SCBA, gloves, and a
hood, the percentage of contamination eliminated by removing outer clothing is
even higher than ninety percent. The bunker gear should be removed while
continuing to wear the SCBA with the facepiece to protect the respiratory tract.
The SCBA is removed, with the facepiece remaining on, and the member holding
the SCBA via the strap. Another member should then remove the bunker gear.
After the bunker gear has been removed, the facepiece is then taken off and the
firefighter sent to the gross Decon.)
2.3.1 Fire Department units should use resources that are immediately available and
start gross decontamination as soon as possible. The most expedient approach is
to use our standard firefighting equipment to provide emergency low-pressure
streams supplying high volumes of water, allowing for large amounts of people to
be deconned quickly.
2.3.2 After the removal of clothing, the victims should be moved through a "Gross
Decontamination Corridor" which utilizes water spray to remove the remaining
contamination. There are several options available to the decontamination officer
for delivering this water spray. Several factors that will affect the choice of
decontamination procedures include: number of victims involved, type of material
that has been released, impact of weather conditions on the use of water sprays for
decontamination, and personal protective equipment (PPE) available to members
performing the decontamination process.
2.3.3 One option for setting up a mass Decon is to stretch a 2½" handline equipped with
an Aquastream fog nozzle. The nozzle team should operate the nozzle in the fog
position and the victims should be directed through the fog spray, rinsing any
remaining contamination off them. The members should avoid contact with the
victims until the proper PPE is in use. They must monitor the operating pressure
of their line to ensure that it is not too forceful for the victims. The recommended
operating pressure range is between 50 to 80 psi. Additional handlines can be
deployed as necessary. Consideration can be given to the use of two handlines
operating opposite each other, approximately 25' – 30' apart, to form a large
shower area that multiple victims can move through at the same time. Care must
taken to avoid pushing the contamination across to the opposing nozzle team.
(See Figure 1 and Figure 2)
2
FDNY Probationary Firefighters Manual
Chapter Twenty Three DECONTAMINATION PROCEDURES
Aquastream
Fog Nozzles
Figure 1
Figure 2
3
FDNY Probationary Firefighters Manual
Chapter Twenty Three DECONTAMINATION PROCEDURES
2.3.4 A second option involves the use of two pumpers and greatly increases our
decontamination capabilities (See Figure 3):
a. Position two pumpers parallel to each other approximately 25 feet apart with
the control panels facing the outside.
d. Monitor the operating pressure to ensure the stream is not too forceful. The
recommended operating pressure is 50 to 80 psi.
Figure 3
4
FDNY Probationary Firefighters Manual
Chapter Twenty Three DECONTAMINATION PROCEDURES
2.3.5 Other options include positioning a tower ladder with a Turbomaster fog nozzle or an
aerial ladder with a ladder pipe and Aquastream fog nozzle at the edge of the water spray
formed from the pumpers. If a tower ladder or aerial ladder is not available or will be
delayed, a 3rd pumper with an Aquastream fog nozzle attached to the apparatus mounted
multiversal nozzle can be positioned parallel to and in line with one of the first two
pumpers as shown in figure 5. This configuration should produce a water spray shower
area approximately 20 feet wide by 30 feet long, which the victims can now be directed
to pass through. (See Figure 4 and Figure 5)
Figure 4
5
FDNY Probationary Firefighters Manual
Chapter Twenty Three DECONTAMINATION PROCEDURES
DIAGRAM FOR TWO ENGINES AND ONE LADDER CONFIGURATION
Figure 5
CASUALTY
COLLECTION
AREA
25'
NOTE: Pumpers will set up with control panels facing outside of the spray area, approximately
25’ feet apart, and a tower ladder with a Turbomaster fog nozzle, or aerial ladder with
Aquastream fog nozzle aimed down on the spray area.
6
FDNY Probationary Firefighters Manual
Chapter Twenty Three DECONTAMINATION PROCEDURES
2.3.6 In immediately life threatening exposures where emergency decontamination is
necessary, fog nozzles can be attached to the multiversal on an engine, or to a
tower ladder outlet, for a very quick gross Decon setup. As time permits, the
configuration shown in fig. #3 should be implemented and the tower ladder (as
per figure #4) added, as the resources become available.
2.3.7 As the victims exit from the water spray shower area EMS Haz-Tac personnel or
other EMSC units, who will evaluate the victims to determine further needs,
should meet them. Haz Tac personnel are qualified to operate in chemical
protective clothing, and can also operate in a hot zone if necessary and would be
the primary unit for this task.
2.3.8 The SOC Decon Support Unit can supply disposable clothing, which can be
issued as victims exit gross decontamination for matters of privacy and weather
related exposures.
2.3.9 Victims can then proceed to a holding area where EMS can evaluate them.
A secondary personal decontamination may be warranted. Refer to section 3 for
FDNY assets available for secondary/personal decontamination. After this
secondary decontamination, the victims should be considered clean and they can
be removed from the scene.
7
FDNY Probationary Firefighters Manual
Chapter Twenty Three DECONTAMINATION PROCEDURES
2.3.11 The threat of a hazardous materials release, be it accidental or intentional,
affecting large amounts of victims is real. The Hazardous Materials Emergency
Response Plan is in place to deal with this occurrence. The Mass
Decontamination Procedure is just one more tool for the Incident Commander to
help control the situation. The basic rule of protection from hazardous materials
is time, distance, and shielding. The Mass Decontamination Procedure is the key
to reducing the amount of time that the victims are exposed to the hazard.
The faster we can reduce their exposure to the harmful effects of the hazardous
material, the better the chances they will not be injured as a result of their
exposure.
3. SECONDARY/PERSONAL DECONTAMINATION
3.2 Water containment tubs and low volume garden hose equipment are carried by CPC
Ladder Companies, the HMTU's, and HMC1. (See Figure 6)
Figure 6
8
FDNY Probationary Firefighters Manual
Chapter Twenty Three DECONTAMINATION PROCEDURES
3.3 Air inflatable tents, with designed in shower hoses, and portable water heaters, are carried
by several HMTU's and the SOC Decon Support Unit. (See Figure 7)
Figure 7
3.4 Decontamination trailers and attached tractors for delivery to incidents anywhere in the
city. These units are self-contained, delivered and set-up by assigned companies, and
operated by Squad personnel. (See Figure 8)
Figure 8
9
Probationary Firefighters Manual
Chapter 24
EMERGENCY OPERATIONS
OBJECTIVE:
24
PART ONE
Vehicle Disentanglement and Patient
Extrication
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
1. INTRODUCTION
1.1 Motor vehicle accidents (MVA) with victims pinned pose a unique challenge to
our members. Medical authorities refer to the first hour from the beginning of an
accident with critical injuries as the Golden Hour. A victim delivered to a
surgical team within this first hour has the best chance of survival. Because of
this, our operations must be well coordinated in order to achieve efficient victim
removal without compromising member safety. Our knowledge of
disentanglement procedures, new vehicle technology, tool capabilities, medical
considerations and tactical procedures will aid us in achieving this goal. Each
accident scene will be unique. Factors that will play a role in determining the
appropriate actions taken and the order in which they are carried out will be the
type and number of vehicles involved, their positions, number and condition of
patients and any external hazards at the scene. This bulletin should serve as a
source of information that will assist you in determining a proper course of action
to be taken when you arrive at the scene of a MVA.
2.1 Today’s cars save lives by wrapping occupants in reinforced alloys, impact
absorbing crumple zones and as many as sixteen air bags. Safety features vary
from year to year in their design and location amongst the different makes and
models. It is paramount to know how these safety features could possibly affect
our disentanglement and extrication operations. Listed below are some of the
advancements made in the construction of new vehicles.
2.2 Reinforced wheel and engine deflection systems that upon impact, deflect the
wheels and motor under the car away from the passenger compartment.
2.3 Crumple zones that absorb the energy of the impact, preventing it from being
absorbed into the passenger compartment. While this has drastically increased the
ability of occupants to survive the impact, it can complicate the disentanglement
effort due to the strength of the deformed metal structures.
2.4 Reinforced dashboards have been developed to protect the occupants in case of a
front or side impact. The transverse dash beam located behind the dashboard ties
into the A posts and the floor pan making dashboard lifts more difficult.
2.5 High-Strength Low-Alloy and boron steel is used in vehicles for improved
strength to weight ratio. The side door beam, when driven into the frame upon
impact, will make door removal more difficult due to its strength. These
lightweight, high strength materials are used to reinforce roof and post structures
hindering our cutting operations.
1
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
2.6 Airbags located in the steering wheel, dashboard, under the dashboard, and now
any combination of the doors, seats, roof rails and even some seat belt systems
present several challenges. Airbag systems are equipped with an energy storage
feature that enables them to deploy even when the battery has been destroyed in
an accident. Airbags can either be deployed electronically or mechanically.
Disconnecting the battery will start the drain time, which varies, for an
electronically activated device, but not a mechanically activated one. All airbag
systems are not alike but do contain similar components. Exact location, volume
and mechanism of deployment will vary. Newer systems include the use of dual
stage inflators which basically means that just because an airbag has deployed it
does not mean that there cannot be a second deployment. In the large majority of
our responses the airbags will have already deployed. However our members
should always treat the area around the airbag as if they have not deployed. The
rule of 5-10-20 should be observed; at least 5” from side airbags, 10” from driver
airbags and 20” from passenger airbags.
2.7 Seatbelt pretensioners are designed to reduce blunt force trauma as well as impact
with airbags. These devices are either mechanically or electrically activated using
a spring mechanism or a pyrotechnic device to deploy. The mechanically
activated pretensioner will remain live even after the battery is disconnected.
Removal of the seatbelt from a patient as soon as practical is recommended.
Accidental deployment during extrication can cause serious injury to both
rescuers and occupants alike.
2.8 High impact plastic, carbon fiber, aluminum and other composite materials are
replacing sheet metal in all or parts of the exterior bodies. Composite materials
and carbon fiber can be difficult to cut. Plastic tends to crumple or shatter instead
of bending making it hard to find a purchase point for leverage.
2.9 Tempered glass is being replaced on side and rear windows by laminated glass or
rigid plastics due to it being highly resistant to breaking. This new type of glass
presents a formidable barrier in gaining access to the occupants inside of the
vehicle. Conventional methods used in the past will not work on these newer
types of glass.
2.10 Unibody construction results in a vehicle that is made from many pieces welded
together to make a lightweight but strong vehicle. This construction is such that
the body and chassis is one unit. The outer surface of the vehicle adds to the
overall strength of the vehicle.
2.11 Space frame construction usually does not depend on the exterior surface of the
vehicle for strength. The body panels are attached to the frame to provide an
outer surface many times consisting of plastic or a composite material.
2
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
2.12 The seats in vehicles today are generally stronger, some wrapping around the
occupant, and are mounted more firmly to the floor pan making seat displacement
more difficult. Many new design vehicles have airbag components mounted in
the seats upholstery. Avoid cutting through airbag sensors, gas cylinders and the
airbags themselves. Removing the upholstery prior to cutting might be a good
practice.
2.13 Automatic roll-over protection systems deploy as the vehicle begins to roll over.
They are typically stowed behind the seats in convertibles in the rear deck area.
This presents a risk to members operating when deployment accidentally occurs
during the rescue operation. Disconnecting the battery and avoiding its
deployment path are steps to follow. In some newer vehicles these systems can
be manually deployed. When this is the case, manually deploying it would be a
course of action.
2.14 The pillars and posts contain components that should be avoided. Reinforcement
for the mounting of seatbelts, pretensioner systems and airbag inflators as well as
the advances in construction presents more of a challenge during cutting
operations. Exposing the posts rails and pillars prior to cutting will allow
members to see where these components are located so that they can be avoided.
2.15 The batteries can be in many different locations. Under the hood, in the wheel
well, under seats or in the trunk are some of the areas they may be found. Some
vehicles may have more than one battery.
3
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
3. TACTICAL PROCEDURES
3.1 Personnel at the scene of an MVA with victim(s) pinned must have a specific
strategy for overall safety and efficient victim removal. First arriving officers
must immediately notify the dispatcher when a person is pinned in the vehicle.
3.3 Operations
3.3.2 Extrication - The physical removal of the victim from the vehicle.
3.3.3 The power unit should be placed in the front or rear of the vehicle. This
will allow flexibility to operate on both sides of vehicle without having to
reposition. The spreaders and cutters are the tools of choice and should be
used to compliment each other at an operation. While one member is
operating the spreaders, have other member holding cutters prepared to
assist when needed. Always be in control of the tool and never position
any part of your body between the tool and the vehicle. A coordinated
team effort is key when operating the Hurst tool. Every member should be
aware of its capabilities and limitations. This will be accomplished
through continuous training and actual operations.
4
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
4. ASSIGNMENTS
4.1 Engine Company Operations - Officer should divide the company into two teams.
The Officer and two CFR trained Firefighters (equipped with trauma bag and
cervical collars) proceed to the scene of the accident. Firefighters shall gain access
to the victim so that critical trauma assessment can be made and treatment
initiated/augmented. Be prepared to allow ladder company members inside vehicle
for disentanglement evaluation, if not already on scene. The remaining members
shall stretch and charge a precautionary handline.
4.1.1 When fire or hazardous condition exists upon arrival, stretching and
charging a hose line is paramount. Consider a foam handline.
4.2 Ladder Company Operations - These assignments are only a guide and should
be evaluated by the company officer at roll call and distributed according to
experience and staffing.
4.2.1 Officer and inside team proceed to scene of accident to initiate a perimeter
survey, chock the vehicle and gain access to victim. Inside team will
ensure car is in park, windows are opened, seats are moved back and
seatbelts removed before shutting down ignition. If an engine or EMS is
not on scene, members shall stabilize the patient. Once an engine or EMS
arrives, the inside team can pass off patient stabilization and assist the
outside team with disentanglement.
4.2.2 Roof and OV bring Hurst tool equipment to scene of accident and initiate
operation.
4.2.3 Chauffeur initially uses the apparatus to block off traffic and can be used
to bring additional equipment to scene.
4.2.4 The Officer should ensure the disconnection of the battery. When
disconnecting the battery, remove the negative terminal first.
5. VEHICLE STABILIZATION
5.1 The goal of vehicle stabilization is to prevent rocking of the vehicle. Placing step
chocks, shutting down the engine, engaging the parking brake, putting the
transmission into park and disconnecting the battery are all part of the
stabilization process. Before disconnecting the battery, open power windows and
adjust power seats to assist with extrication. Stabilization options will vary
depending on the available equipment. Ropes, chains, hooks, and Halligans, in
addition to step chocks and wedges, can all be used for this purpose.
5
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
5.3 Check under the vehicle for victims before any stabilization methods are taken.
5.4 Vehicles on all four wheels are best-stabilized using step chocks and wedges.
Place chocks just behind front wheels and in front of rear wheels, step side down.
They should be positioned so as to not interfere with the door swing. Place the
chocks so they make a snug contact with the rocker panel. A wedge may be
required to fill the gap between the step chock and the rocker panel (Figures 1 and
2).
Figure 1 Figure 2
5.5 When further stabilization is required deflate the tires so that the vehicle rests
totally on the step chocks. Though this is not always necessary it will afford the
best possible stabilization. Keep in mind that once this is done you will be unable
to reposition the step chocks when necessary. When deflating tires use vise grips
or pliers to remove the valve stems (Figure 3).
Figure 3
6
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Figure 4 Figure 5
Figure 6 Figure 7
7
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
6. DOOR REMOVAL
6.1 When removing a door, the first point of attack may vary. There are two options,
Nader pin/staple or hinge side. Whatever method is chosen, the victim must be
protected from any flying debris, and the window opened or the glass removed.
While attacking the Nader pin/ staple first has been successful in the past, the
hinge side may be an improved approach with new car construction. Both
techniques should be mastered.
Figure 8 Figure 9
C. Cut top and bottom hinges using cutters in that order (Figure 10).
When a hinge has a spring, it must be removed prior to cutting the
hinge. Use a Halligan or Officers tool to remove it (Figure 11).
Figure 10 Figure 11
8
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Figure 12
E. Close spreaders on door and force door open, using spreaders for
leverage exposing Nader pin/staple (Figure 13).
F. Cut Nader pin/staple with cutters and remove the door (Figure 14).
Figure 13 Figure 14
Note: Door may break free from Nader pin / staple when forcing it open. Keep
the area clear beneath the door being removed.
C. After exposing hinges, follow the steps listed in Section 6.2.1 for
cutting hinges and the Nader pin/staple.
Figure 15
9
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
A. Place the adz end of the Halligan tool in the seam between the
front fender and door in the vicinity of the top hinge.
C. After exposing the top hinge, follow the steps listed in Section
6.2.1 for cutting hinges and the Nader pin/staple.
6.2.4 The spreaders may be used in place of the cutters when attacking the hinge
side of the door for complete door removal. Use one of the above
methods to establish a purchase (Figure 16).
Figure 16
10
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
B. Keep spreaders in vertical position. The outer arm should fall over
the outside door handle or close to it, with the tips about midway
down the door.
C. Close the tool on the door, forcing the outer edge of the door to roll
out exposing the Nader pin/staple.
E. Push the door away from the car to expose the hinges. When
necessary close the spreaders on the door using them for leverage
(Figure 17).
F. Cut the top and bottom hinges, in that order, with the cutters.
When a hinge has a spring it must be removed prior to cutting
using a Halligan or Officers tool.
Figure 17
A. Place the adz end of the Halligan tool in the seam between the door
and the post just above the midway point of the door (Figure 18).
C. With the spreaders in the closed position, place the tips at a level just
above the Nader pin/staple. Inch your way into position by opening
and closing the spreaders to avoid tearing or shredding the door. This
action may force the door.
D. When the above does not force the door use the cutters to cut the
Nader pin/staple.
11
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
A. Using the vertical push to establish a purchase point may force the
door from the Nader pin/staple. This method works best on older
vehicles. On newer type vehicles (lightweight construction), the
possibility exists of the door splitting, losing the integrity of the
door. In order for this method to be successful, the roof must be
intact.
B. Insert tips of the spreaders into the window opening close to the B
post (Figure 21). Keep top arm of spreaders horizontal with tips
inside of vehicle.
C. When the above does not force the door use the cutters to cut the
Nader pin/staple.
12
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
6.3.4 The spreaders may be used in place of the cutters when attacking the
Nader pin/staple side of the door for complete door removal. Use one of
the above methods to establish a purchase.
Figure 21
6.4 When any of the methods listed in Section 6 do not provide enough of a gap to
insert the tool additional space can be gained in the following manner. Open the
spreader tips about one inch.
6.4.1 Place the edge of the door on the inside of the spreader tips.
6.4.2 Close the spreaders pinching the edge of the door in between the tips
(Figure 22).
6.4.3 Using the spreaders pry out and away from the vehicle enlarging the gap
(Figure 23).
6.4.4 This will work on both the Nader pin/staple or the hinge side of the door.
Figure 22 Figure 23
13
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
7.1 This procedure is used when a victim is pinned in the back seat of a two-door
vehicle. The third door will provide better access to remove the victim(s).
14
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Figure 24
7.2.5 Once the four cuts are made, insert the spreaders on an angle, midway on
the door and make a crease (Figure 25).
7.2.6 Readjust the jaws to grasp the top right corner (Figure 26).
Figure 25 Figure 26
Figure 27 Figure 28
7.2.7 Once the jaws are secured onto the top right corner, pry outward and down
(Figures 27 and 28).
15
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
8. ROOF REMOVAL
8.1 The large majority of the time victims are removed via the doors. Roof removal
may be necessary for victim access or possibly even victim removal. The first
step in removing the roof of a car is to decide which method of removal to
employ.
8.2.1 Cut low on the A Post and high on the B, C and D Posts with cutters
(Figures 29 - 30). When cutting the A and D Posts, cut a portion of the
windshield and rear window to allow access to cut the glass, if necessary.
Cut all posts on one side before passing the tool to cut the posts on the
opposite side of the vehicle.
Figure 29 Figure 30
8.2.2 Cut across the bottom of the windshield using the sawzall with wood
cutting blade (Figure 31) or the Beluga Auto Glass Knife. End the cut
at the A Post on both sides of the vehicle. The windshield hand saw
or axe can also be used to cut windshield.
8.2.3 After completing cuts, slowly carry the roof toward the front of the
vehicle. This will prevent dragging the cut windshield over victims in
vehicle (Figure 32).
Figure 31 Figure 32
16
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
8.3.1 Make all of the cuts at the same locations as for the total roof removal Section
8.2.1.
8.3.3 After cutting posts, have members on both sides of vehicle lift roof and
walk towards front of vehicle folding roof onto hood of car (Figure 33).
Figure 33
8.4.1 Cut low on the A Post and high on the B Post with cutters. When cutting
the A Post, cut a portion of the windshield to allow access to cut the glass,
if necessary.
8.4.2 Make a hinge cut on both sides of the roof at a point just before the last
post and place a hook in between the cuts (Figure 34).
8.4.3 With members on each sides of the roof, slowly lift it back over the hook
placing over trunk of vehicle (Figure 35). Always secure a partially
removed roof
(Figure 36). Before cutting the roof posts, be sure the support of the roof
in not needed to force the doors.
Hinge Cuts
Figure 34 Figure 35
17
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Figure 36
9. DASHBOARD DISPLACEMENT
9.1 In the past rams were the tools of choice for dashboard displacement. Today
using cutters and spreaders which are already in operation will usually suffice.
The rams are another option.
9.2 Spreaders
9.2.1 Make sure that the vehicle is properly stabilized with a chock under the
rocker panel where the cuts are made.
9.2.2 Make two cuts in the bottom portion of the A Post. The lower cut is made
below the hinge, parallel to rocker panel. The second cut is made
approximately 6-8 inches above first cut (Figure 37). A metal hook
should be positioned between the cutters and the rocker panel to prevent
the tool from moving in towards the passenger compartment (Figure 38).
Figure 37
9.2.3 Make a third cut, low on the upper portion of the A Post (Figure 39).
18
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Figure 38 Figure 39
9.2.4 Grip the section of the A post between the two cuts with the inside of the
spreader arms and peel away (Figures 40 - 41).
Figure 40 Figure 41
9.2.5 Insert tips of spreaders into void created in A Post ensuring tips rest just
inside of rocker panel (Figure 42). Open spreaders and lift
dashboard (Figure 43).
Figure 42 Figure 43
9.2.6 A relief cut in the front fender may assist the dashboard displacement by
relieving front end resistance. When making this cut, avoid
cutting through front shock assemblies (Figure 44).
19
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Figure 44
9.3 Rams
9.3.2 With the ram in the closed position, place the butt end on the rocker panel
and the tip of the extending end on an upper portion of the A post.
9.3.3 Tightly close the spreaders on the rocker panel just behind the ram. The
spreaders will act as a substantial object for the ram. Place a chock under
the spreader tips.
Figure 45
Figure 46
20
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
9.3.6 The ram may be removed to allow full access to the displaced dash area.
To do this a second step chock should be placed under the rocker
panel below the A post (Figure 47). A wooden wedge should also be
placed in the gap that has been formed at the relief cut on the bottom
portion of the A post (Figure 48). Exercise care when retracting the ram
so the displaced dash does not come down on the victim.
Figure 47 Figure 48
Figure 49 Figure 50
9.4.2 The metal straps are bolted to the hump in the floor pan and the underside
of the dash and will vary in size and shape.
9.4.3 These straps can be accessed from the opposite side of the trapped
occupant by breaking the plastic covering the side of the center console.
9.4.4 Even cutting one of the straps will assist in the operation. When starting
to lift the dash the other strap may break free from the force.
21
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
10.1 Although this procedure is an accepted way to displace a seat backwards, it must
be used with caution. Always try to move the seat backwards by normal methods
(e.g. manual lever, electric buttons) before committing to hydraulics. To avoid
potential problems, seat displacement procedures should only be used for short
distances.
10.2 Ram
10.2.1 Place the butt end of the ram on the base of the "A" post.
10.2.2 Place the extending end of the ram on the sliding portion of the seat track
(Figure 51). Make certain the extending end is not placed on the
fixed base of the seat track or on the cushion portion of the seat. The part
of the tool that is placed against the “A” post should be slightly higher
than the opposite end.
Figure 51 Figure 52
10.3 Spreaders
10.3.1 Place one tip of the spreaders on the base of the "A" post.
10.3.2 Place the opposite tip of the spreader on the sliding portion of the seat
track (Figure 51). Make certain the spreader tip is not placed on the fixed
base of the seat track or on the cushion portion of the seat. The part of the
tool that is placed against the “A” post should be slightly higher than the
opposite end.
22
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Figure 53
11.4 Side/Rear Windows: The center-punch or halligan can be used to break tempered
glass. When using the halligan, insert the adz end between door frame (Figure
54) and glass exerting downward pressure (Figure 55). This will generally keep
glass from shattering all over victim. Keep in mind that on the newer types of
glass these methods may be ineffective.
23
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Figure 54 Figure 55
11.5 When encountering a vehicle that has side or rear windows that are laminated or
rigid plastic, a sawzall may be used to gain access.
12.1 Access to the passenger compartment for a vehicle on its side can usually be made
from the front or rear windows when the roof is intact. When the roof is crushed,
access and extrication can be achieved by cutting the roof posts and hinging the
roof down. The above methods of gaining access to the passenger compartment
can only be attempted after the vehicle is firmly stabilized.
12.2.2 Make sure victims are not against the interior of the roof in vicinity of
cutting operation.
Figure 56 Figure 57
24
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
13.1 Access to the passenger compartment for a vehicle on its roof can usually be
made from the front or rear windows when the roof is intact. Door removal can
be accomplished when the vehicle is in this position. Attacking the hinge side
would be the preferred method of removing the door.
13.2.1 Crush the wheel well section of the fender in between the spreader arms
creating a purchase point (Figure 58).
Figure 58 Figure 59
13.2.3 Cut top and bottom hinges using cutters in that order. Be advised the
lower hinge would now be the top hinge. When a door spring is present it
must be removed prior to cutting using a Halligan or Officers tool
(Figure 60).
13.2.4 Cut door stop when present.
13.2.5 Close spreaders on door and force door open using spreaders for leverage
exposing the Nader pin/staple (Figure 61).
Figure 60 Figure 61
25
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
13.4 An alternate method of establishing a purchase point would be to attack the seam
between the bottom of the door and the rocker panel of the vehicle using either
the spreaders or Halligan tool to expose the bottom hinge (Figures 62 and 63).
Figure 62 Figure 63
14. SAFETY
14.1 The operator(s) must wear all required protective clothing. The operator(s) and
any member working in close proximity to the operator(s) must wear eye
protection (e.g., eye shields, safety glasses, or helmet-mounted eye shields).
14.2 An area of safety measuring the fully opened length and width of the jaws must
be maintained. Do not place any portion of the body within this zone when
opening or closing the jaws.
14.3 Avoid cutting through hydraulic pistons or rods on hatchback style vehicles. A
sudden release of pressurized fluid could cause injury.
14.4 Always treat airbags as if they are live, observe the rule of 5–10–20. The rule of
5-10-20 is at least 5” from side airbags, 10” from driver airbags and 20” from
passenger airbags.
26
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
14.5 When possible, cover cut post or sharp edges of the vehicle with a car mat or
other suitable material to prevent injury.
14.6 Keep the working area around the vehicle free of loose tools.
14.7 Eye and hand protection should always be worn when connecting and
disconnecting hose couplings. A good practice would be to point the couplings
down when disconnecting.
14.8 Whether using the spreaders or cutters always remove the top hinge first.
14.9 Rear end collisions might not activate safety systems such as airbags and seatbelt
pretensioners. This can even be the case in some side impact collisions due to
smart systems that will only deploy/activate due to a persons weight. These
systems that have not deployed will still remain live and could possibly activate
once the rescuers weight is sensed.
14.10 Avoid crushing/cutting areas that might contain live airbags, cylinders and
sensors that will activate any of the safety systems. The cylinders may contain up
to 9,500 psi of stored gas pressure. Removing the interior trim inside of a vehicle
might help in determining the locations of these devices.
14.11 Always be aware of the unsupported end when using the cutters.
14.12 Never position any part of your body between the tool and the vehicle.
14.13 The hydraulic hose lines may be coupled or uncoupled with the power unit
running, provided the bypass valve is in the backward or dump position. On the
low pressure hose, align the slot with the pin before you connect or disconnect the
coupling. These couplings are provided with seals and rings compatible with
hydraulic fluid. Because there is a ball check, they can be disconnected under
pressure, but caution must be exercised since some fluid may spray out.
14.14 Prolonged and repeated contact with the hydraulic fluid may be irritating to the
skin. If a member gets hydraulic fluid in their eyes, the member should flush their
eyes with clean water for at least 20 minutes and immediately seek medical
attention.
27
28
PART TWO
Water Rescue Operations
29
30
FDNY Probationary Firefighters Manual
Chapter 24 EMERGENCY OPERATIONS
1. INTRODUCTION
1.2 The untrained and inexperienced potential rescuer could become a victim.
Preplanning, proper equipment and training will ensure the safest outcome in
these types of incidents.
1.3 The FDNY has equipped some ladder and engine companies as well as all special
units with ice/cold water and surf rescue equipment. These units have been
trained in the proper use of this equipment as well as safe standard operating
procedures.
1.4 It is the goal of these procedures to familiarize all members with this equipment
and to explain the capabilities, limitations and standard guidelines to follow when
responding to, and operating at these incidents.
2. LIMITATIONS
2.1 It should be emphasized that any entry into the water or onto ice be considered as
a last resort. The safety of our members is paramount. The Incident Commander
will have to weigh the risk vs. reward when attempting a water rescue.
2.2 When it is determined that a water entry rescue is not safe for a surface rescue
unit, the Incident Commander will need to request the assistance of a Rescue
company dive unit.
2.3 All procedures described in this bulletin will deal with Surface rescue. The Cold
Water Suit (CWS) and Personal Flotation Device (PFD) are not designed for
underwater operations.
2.4 The CWS has considerable buoyancy. Any attempts at underwater operations
will cause the rescuer to immediately surface, possibly trapping the rescuer under
an ice shelf, under a pier, or inside a submerged automobile.
3. RESCUER SELECTION
3.1 A member who has been trained in the suit and is familiar with its capabilities and
limitations should be designated as the Primary Rescuer. A member with
lifeguard experience or a trained scuba diver should be considered for this
assignment.
31
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
3.2 It would not be good practice to assign your primary water rescuer as a riding
position. Example, nozzle firefighter is always the primary rescuer. This member
may not feel comfortable in the water and you may have someone with more
training for that duty. Positions should be discussed and determined at roll call.
4. SAFETY
4.1 The primary concern is the safety of our rescuers. 10% of drowning victims are
would-be rescuers. All members must use extreme caution and good judgment
with any ice or water rescue.
4.2 There will be times when we should not enter the water. This goes for drill as
well as a rescue situation. Some factors that would affect this decision are:
4.2.2 Location of Victim- how far out the victim is and if they can be reached
safely.
4.2.3 Skill level of rescuer - can the rescuer reach the victim under the above
circumstances or will the rescuer eventually become a victim.
4.2.4 Night operations - Members should not be allowed past the line of sight
from the shore. Portable lights should be brought to the scene.
4.3 Bunker gear does not float. Tests have shown that members wearing Bunker Gear with
or without an SCBA will sink instantaneously.
32
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
5. MEDICAL CONSIDERATIONS
5.1 Treatment
5.1.2 Remove the victim to a warm shelter to prevent further body cooling. The
victim should be transported carefully to avoid heart fibrillation and stress.
Do not massage or rub the victim because rough handling could cause
cardiac arrest.
5.1.3 Remove wet clothing and wrap the person in warm blankets. Perform a
patient assessment and treat the patient according to CFR protocols, if EMS is
not on-scene.
5.1.4 Remember: Cold water victims look dead. However, people have been
submerged in cold water for long periods of time and made complete
recoveries.
5.2 Hypothermia
5.2.1 The loss of body heat occurs 25 times faster in cold water than in air.
Hypothermia (subnormal body temperature) begins when the body’s core
(brain, spinal chord, lungs and vital organs) temperature falls below the
level of 98.6 degrees Fahrenheit. Cold water cools the body’s skin and
outer tissues very quickly. In approximately 7 to 15 minutes, core body
temperature begins to drop significantly, affecting utilization of the arms
and legs. Blood pressure, pulse and respiration rates all decrease.
Muscles tense and shiver. Irrational behavior (resisting help) is a good
indicator of hypothermia.
5.2.2 When the body’s core temperature begins to drop below 90 degrees
Fahrenheit, the victim transgresses from non-ambulatory into
unconsciousness. Low core temperature, in conjunction with stress and
shock, can cause cardiac and respiratory failure.
33
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
5.3.2 It reduces the heart rate (bradycardia), increases blood pressure and shuts
down blood circulation to all the body’s core, resulting in a lower
metabolism. MDR also protects the victim from the rapid inhalation of
water into the stomach and lungs.
5.3.3 MDR is more pronounced in young people and, therefore, they are the best
candidates for resuscitation. The colder the water and the younger the
victim, the better chance they have of survival.
34
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
6. TIDES
6.1 There are 4 tides in 24 hours: 2 tides are coming in (High) and 2 are going out
(Low). Slack tide is 45 minutes between High and Low tides.
6.2 Rip Tides or Currents - occur when the tide is going out. Rip currents are the
primary source of distress in drowning victims. Rip currents pull people into deep
water very quickly. This causes the victim to panic which is the leading cause of
drowning.
6.2.1 To escape a rip current you should swim parallel to the shore line.
Swimming back to shore into the rip will not help and only make
victim tired (Figure 1).
Figure 1
6.3.1 Sweep Tides can also be present in a rescue situation. This tide runs
parallel to the beach. It is more pronounced on out-going tides. The
waves are diagonal to the beach and can sweep swimmers into a rip
current.
6.3.2 Rescuer should enter the water upstream of the sweep. This will pull the
rescuer towards the victim. Contact with the victim will be difficult if the
rescuer takes a straight on approach because they will be swimming
against the sweep to get to the victim (Figure 2).
35
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Figure 2
36
Addendum 1
37
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
38
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
1. INTRODUCTION
1.1 Inflatable water rescue hose may be used during ice and water rescue
incidents/emergencies involving any number of conscious victims.
2. EQUIPMENT
2.1 The following equipment shall be used to deploy inflatable hose for ice / water
rescue:
• Spanner Wrenches
Photo 1 Photo 2
3.1 Members shall deploy the required lengths of hose, attach the water rescue fittings
and ensure that all connections are spanner tight prior to filling with air.
39
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
3.2 To fill the hose using a SCBA or Fast-Pak, members shall disconnect the low
pressure hose at the Hansen fitting (Photo 3). Attach air hose to male connection
of hose fitting (Photo 4). Inflate the hose until it is completely filled and possesses
rigidity similar to a charged hoseline. One 45 minute cylinder can fill five lengths
of 2 ½” hose in approximately 1 minute.
Photo 3 Photo 4
3.3 To fill the hose using the apparatus air outlet, members shall connect the male
connection from hose directly to the air outlet on apparatus. The apparatus air
outlet can fill five lengths of hose in approximately 1 minute (Photo 5).
Photo 5
4. OPERATIONS
4.1 Inflatable water rescue hose can be deployed in either a straight line or loop.
Straight line deployment can be used in incidents from a pier or shore involving
only a few individuals who are close to shore (Photo 6). The loop deployment
increases buoyancy and can be used for multiple victims. (Photo7)
40
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Photo 6 Photo 7
4.2 More than two lengths of hose can be used for larger operations. Each length of 2
½” hose filled with air can keep afloat approximately 10 people.
4.3 Units should have air filled hose secured with Life Saving Rope (Photo 8). Take
note of water current as it may be necessary to deploy hose into the anticipated
path of travel.
Photo 8
5. DEFLATION
6. CLEANING
6.1 Rinse all ropes and hose after each use. The Life Saving Rope shall be examined
and maintained according to the procedures outlined in Training Bulletin, Rope 1.
41
THIS PAGE WAS INTENTIONALLY LEFT BLANK
42
Ice and Cold Water Rescue
43
THIS PAGE WAS INTENTIONALLY LEFT BLANK
44
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
1.1 Each ice/cold water rescue company is issued the following equipment along with
two gear bags. Each set of gear is intended for the Primary and Secondary rescue
teams. The bags are large enough to hold one complete set of gear for each
rescue team including one PFD.
ITEM QUANTITY
Binoculars-waterproof 1
Megaphone 1
Stretcher – stainless steel 1
Stretcher – lifting bridle 1
Stretcher – flotation collar 1
Lifting bridal – Carabineer 1
Cold Water Suit (CWS) 2
Turtle fins (set) 2
Mask 2
Snorkel 2
Survival knife 2
Personal strobe light 2
Waterproof flashlight 2
Ice awls (set) 2
Water rescue torpedo 2
Tether rope 200 feet 2
Rope reel 2
Small carabineer 2
Large carabineer (Ice Rescue) 2
Flotation sling 2
Red gear bag 2
Personal flotation device (PFD) 2
45
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
2. EQUIPMENT SET-UP
2.1 Ice Awls - A set of ice awls should be secured to each suit and used for mobility on
the ice.
2.2 200 Foot Tether Reel – The 200 Foot Tether Reel (Photo 1) shall have the small
carabineer (Photo 2) secured at the end of the tether line using a Figure 8 on a
Bight (Photo 3). The large ice rescue carabineer (Photo 4) is placed in-line on the
tether rope 4 feet from the small carabineer using the Butterfly Knot (Photo 5).
Photo 1 Photo 2
Photo 3 Photo 4
Photo 5
46
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
2.3 Stainless Steel Stretcher and Four-Point Lifting Bridle – The lifting bridal
issued with the stretcher can be used in either the four-point (Photo 6) or two-point position
(Photo 7).
Photo 6 Photo 7
Photo 8
3. POSITIONS
3.1 Rescue Coordinator – The Company Officer assumes this position and shall be
located where they can observe and direct the whole operation. In a 4-Firefighter
Engine Company, the Officer will also assume the responsibilities of the Spotter
until an additional unit arrives.
47
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
3.3.1 Primary Rescuer - Member will don the Cold Water Suit (CWS),
establish and maintain communication with the victim and implement
rescue procedures. This is the only member that will approach the victim.
3.3.2 Primary Tether - Member will assist the Primary Rescuer in donning the
CWS and attach tether line to the suit’s harness. Feed and control the
tether line. Pull rescuer and victim back to safety.
3.4.1 Secondary Rescuer - Don the second CWS and be tethered to a second
line in the stand-by position.
3.4.2 Secondary Tether - Assist the Secondary Rescuer in donning the CWS
and ensure the second tether line is attached to the suit harness.
4. GENERAL PROCEDURES
4.1 All members except the Primary and Secondary Rescuers will be equipped with
Handie-Talkies. The Primary and Secondary Tethers shall wear PFDs.
4.2 When arriving at the scene, communicate with the victim to see if they can rescue
themselves. The victim may not be able to due to hypothermia. Once it has been
confirmed that there is a victim to be rescued, notify the dispatcher and request
additional resources.
4.3 Generally, there are three methods used for cold water/ice rescue.
• Reach
• Throw
• Go
4.4 The Reach method is used when a victim is ambulatory and can assist in their
own rescue. The rescuer uses a hook, pole or other device extended to the victim.
When the victim has gained a hold on the object, rescuers can pull the victim to
safety.
48
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
4.5 The Throw method is used when the reach method is not feasible. Using a throw
rope, the rescuer hurls the rope to the victim. The victim should wrap the rope
around their arm to be pulled to safety.
4.6 The Go method is used for a non-ambulatory victim (unable to assist in their
rescue) or is too far from shore. Victims exposed to cold water will have
problems with their motor skills and manual dexterity, making them unable to
hold a pole or a rope. This should be the last method tried since it is the most
dangerous.
4.6.1 During the Go method, rescuer must have properly donned the CWS and
be properly tethered.
4.6.2 Approach the victim with caution. Most likely, a victim will be extremely
anxious and panicky. It’s likely that the victim will try to grab a rescuer if
the rescuer is too close. This could result in a life and death struggle.
4.6.3 The Primary Rescuer should be the only member communicating with the
victim.
4.6.4 The Secondary Rescuer should be properly dressed with a CWS and ready
to assist if the Primary Rescuer gets in trouble. All tether persons should
be wearing a personal flotation device (PFD) and rescuers should always
be on a tether line. Remember, the safety of the rescuer is paramount.
5.1 Tether line is attached to the D-ring on the rear harness of the suit. (Photo 9)
Photo 9 Photo 10
5.2 Water rescue torpedo is attached to the front of the suit’s harness. (Photo 10)
49
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
5.3 The rescuer is wearing turtle fins and enters water in a controlled manner. The
rescuer holds torpedo with both hands and kicks to victim while keeping victim in
sight. (Photo 11)
5.4 Upon reaching an ambulatory victim, the rescuer passes torpedo to victim while
keeping a safe distance, if possible. (Photo 12)
Photo 11 Photo 12
5.5 Upon reaching a non-ambulatory victim, the rescuer reaches under the victims
armpits and places torpedo on victim’s chest and holds onto the torpedo. (Photo
13)
Photo 13
5.6 Rescuer signals to the tether team and both rescuer and victim get pulled to safety.
6.1.1 Rescuer wearing a CWS is equipped with a pole or hook and a throw rope.
The tether shall be attached to the front of the suit’s chest harness. (Photo
14)
50
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
6.1.2 Rescuer crawls onto ice and reaches pole out to the victim and instructs
the victim to grab onto hook and to kick their legs as if they were
swimming (Photo 15). The rescuer helps pull the victim onto the ice.
Photo 14 Photo 15
6.2.1 Remove the loop from bag and place loop onto non-throwing hand.
Dominant hand throws bag while other hand holds the rope. (Photo 16)
Photo 16
51
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
6.2.3 Have the victim wrap the rope around their arm and hold the rope, pull the
victim to safety. (Photo 17)
Photo 17
6.3.1 The Primary Rescuer should be the only member to approach the victim
unless assistance from the Secondary Rescuer is needed.
6.3.2 The Primary Rescuer should approach the victim from the side.
Approaching from the front may cause the already weakened ice to break
causing the victim to become aggressive and impede the rescue.
6.3.3 The Secondary Rescuer is suited up and ready to assist. The Secondary
Rescuer should stay off the ice. When needed, the Secondary Rescuer will
approach from a different angle, as not to break ice that is already
weakened by the Primary Rescuer and victim.
52
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Photo 18
6.3.4 For an ice rescue, the tether is attached by the small carabineer at the end
of the rope to the front of the rescuers chest harness. (Photo 19)
Photo 19 Photo 20
53
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
6.3.5 The flotation sling is used to assist an ambulatory victim. The tethered
rescuer crawls across ice with rescue sling attached to the large carabineer.
A. Upon reaching the victim, the rescuer reaches through sling and
grasps victim’s hand firmly, while positioning sling under victim’s
arm and over the shoulder. The rescuer places sling over victim’s
head then brings victim’s other arm through the sling. (Photo 20)
6.3.6 For a non-ambulatory victim, the reach around method is used. This
method requires the rescuer to enter the water. For this technique, the
rescuer should be wearing fins.
A. The rescuer keeps the large carabineer in one hand with the tether
line in the other hand. This will keep rescuer from getting tangled
up in the rope.
B. The rescuer crawls across the ice and instructs victim to remain on
ice shelf. The rescuer enters the water feet first, reassuring the
victim, and approaches the victim from the side or back.
C. From the back of the victim, the rescuer will reach under the
victim’s armpits and attach the large carabineer onto the tether
line. (Photo 21)
Photo 21
6.3.7 Rescuer signals to the tether team and both rescuer and victim get pulled to safety.
54
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
7. STRETCHER PROCEDURES
7.1 Members shall use the stretcher to remove victims when other techniques are
unsuccessful or may cause injury to the victim. Placing a victim in the stretcher
requires both rescuers.
7.1.1 The victim is brought to the stretcher where both rescuers will maneuver the
victim so the victim’s head is loaded into the end of the stretcher with the
floatation collar. The victim shall be secured to the stretcher as follows:
(Photo 22)
A. The top strap gets attached under the victim’s armpits, and across
chest.
B. The middle strap gets attached across the waist of the victim.
C. The bottom strap gets attached under one leg and over the other.
Photo 22
7.2 Retrieving a stretcher from below grade (e.g., pier, jetty, dock) can be a difficult
and delicate operation. Extreme caution should be used as not to further injure
the victim, and to make the operation as safe as possible to our rescuers and shore
personnel. A team effort will be needed to ensure a successful operation.
7.2.1 A portable ladder and utility ropes shall be used to assist in this operation.
Ladder hooks shall be used to support the ladder if possible. Securing the
ladder in this manner at the start of the operation will ensure control of the
ladder.
55
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
7.2.2 Secure utility rope to top rung of ladder and then to a substantial object.
(Photos 23 and 24)
Photo 23 Photo 24
7.2.3 The Life Saving Rope shall be used to establish a 2-to-1 mechanical
advantage prior to the stretcher being lowered into position.
7.2.4 The stretcher is not intended to be brought out to the victim. It will be
more effective to bring the victim to the stretcher. Upon retrieval of the
victim, the stretcher can be passed down to the rescuers where the victim
will loaded onto stretcher.
7.2.5 The rescuers should guide stretcher onto ladder rails while members above
grade hoist on working end of rope until victim can be carried off to a
safe location. (Photos 25 and 26)
Photo 25 Photo 26
56
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
8. COMMUNICATIONS
8.1 Pre-determined hand signals have been established to allow the Rescuer and Tether
to communicate. All members of the rescue team should be familiar with these
hand signals.
8.1.1 One hand placed on top of the rescuer’s head indicates the rescuer is
ready to be pulled to shore. (Photo 27)
8.1.2 One arm waving in the air indicates stop pulling. (Photo 28)
Photo 27 Photo 28
9.1 Rinse and air-dry all ropes and suits after each use. The Lifesaving Rope shall be
examined and maintained according to the procedures outlined in Training Bulletin,
Rope 1.
9.2 All ice and cold water equipment shall be inspected during January, April, July
and October. In January and July, the suit should be removed from the carrying
bag and hung on a broad shouldered hanger for at least 48 hours to allow moisture
inside the suit to dry out, prevent mildew and help extend the service life of the
suit.
9.2.1 Before repacking the suit into its carrying bag, the zipper should be
lubricated. Close the zipper and run a lubricating stick (candle wax) up
and down the outside of the zipper. Open and close the zipper 2-3 times.
Store the suit with the zipper in the open position.
9.2.2 Repack the suit by laying it on a flat surface with the front of the suit
upward. Tuck in the hood/head support, cross the arms over the
hood/head support, then roll the suit from the feet upwards. Slip the suit
into the carrying bag and close.
57
FDNY Probationary Firefighters Manual
Chapter 24 EMERGENCY OPERATIONS
9.2.3 If the suit should become soiled or contaminated with oil, scrub with a
mild soap solution (dish soap), rinse with fresh water and allow drying
before repacking. Do not use solvents or dry clean. Some solvents may
degrade seams and suit material.
9.3 Damaged equipment can be sent to Tech Services through normal RT-2
procedures.
58
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Secondary Tether In line with second Tether line. PFD. Help rescuer don suit Ensure
TEAM # 2 rescuer. Handi- suit’s harness is
Remains on land or in a talkie. fastened.
safe area. Attach tether line to harness.
Operate tether.
59
THIS PAGE WAS INTENTIONALLY LEFT BLANK
60
Surf Rescue
61
THIS PAGE WAS INTENTIONALLY LEFT BLANK
62
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
1.1 Each surf rescue company is issued the following equipment (Photo 1)
ITEM QUANTITY
Binoculars-waterproof 1
Megaphone 1
Fins (set) 2
Mask 1
Snorkel 1
Personal flotation device (PFD) 3
Water rescue torpedo 1
600’ Rope and Harness 1
Carry Bag 1
Surfboard (Photo 2) 1
Photo 1
63
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Photo 2
2. POSITIONS
2.1 Rescue Coordinator – The Company Officer assumes this position and shall be
located where they can observe and direct the whole operation. In a 4-Firefighter
Engine Company, the Officer will also assume the responsibilities of the Spotter
until an additional unit arrives.
2.3 Primary Rescuer – The member will don a PFD, fins and be equipped with the
torpedo. This will be the first member to approach the victim.
2.4 Secondary Rescuer - The member will don a PFD and fins. The member will be
equipped with the tether line only or a tethered surfboard depending on water
conditions.
2.5 Tether Firefighter- Member will assist the Rescuers in donning equipment.
Feeds and controls the tether line. Pull rescuers and victim back to safety.
3. PROCEDURE
3.1.1 The Primary Rescuer enters the water walking backwards and swims out
to victim letting torpedo drag behind on the down sweep side. The rescuer
should keep the victim in sight.
64
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
3.1.2 The Primary Rescuer comes to a stop before reaching victim. Keep the
torpedo between rescuer and victim. This will allow the rescuer to assess
and reassure the victim. An anxious victim will attempt to grab the
rescuer and not the torpedo.
3.1.4 The Primary Rescuer establishes buoyancy and awaits the Secondary
Rescuer with the tether line.
3.1.5 The Secondary Rescuer enters water with tether line and harness swims
out to Primary Rescuer and victim. The Tether Firefighter feeds the tether
line from shore.
3.1.6 Upon arrival at Primary Rescuer and victim, the Secondary Rescuer
removes the harness and hands it to Primary Rescuer. Both rescuers hold
victim under the arms position with one hand and the other hand holding
the harness.
3.1.7 Both rescuers and victim get pulled to shore by the Tether Firefighter.
3.2.1 The Surfboard rescue procedures for the Primary Rescuer remain the same
as the Line Rescue procedure.
3.2.2 The Secondary Rescuer enters water with tether line attached to the
surfboard and paddles out to Primary Rescuer and victim. The Tether
Firefighter feeds the tether line from shore.
3.2.3 Both rescuers load the victim onto the surfboard. Both rescuers and
victim get pulled to shore by the Tether Firefighter.
4. OPERATIONAL CONSIDERATIONS
4.1 Once it has been confirmed that there is a victim to be rescued, notify the
dispatcher and request additional resources.
4.2 All members entering water are to wear life preservers. If the surf board is used it
must be tethered.
4.3 Members pulling in the tether line are to time the waves when pulling victim and
rescuers to shore.
65
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
4.4 The victim should be removed from the waves before beginning medical
treatment including spinal immobilization.
66
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Part 3
Steam
System
Emergencies
67
68
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
1. INTRODUCTION
1.1 Con Edison supplies high pressure steam to nearly 2,000 buildings from 96th
Street to the
Battery in Manhattan through more than 100 miles of buried high pressure steam
pipe. It
is generated in plants located in Manhattan, Brooklyn and Queens and is piped
underground to the end users in Manhattan. Steam pipes run under streets and
sidewalks
with manholes providing access to the underground steam system. (Photo 1)
1.2 Con Edison is not the only entity generating high pressure steam in New York
City. High pressure steam, generated for use in housing complexes, hospitals and
various commercial locations, can be found in any borough. These District Steam
systems will have the same hazards as the Con Edison system but will not be run
or maintained by the Con Edison. When discovered, district steam systems shall
be entered into the CIDS Program.
2.1 Steam is invisible. The white mist seen is the condensate that forms when steam
cools.
69
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
2.2 Steam pressures in generating plants can be as high as 2,000 psi with
temperatures reaching 900ºF. Steam pressures in the buried supply piping and in
supplied buildings can be as high as 170 psi and temperatures as high as 350ºF.
2.3 High Pressure steam is used in buildings for a number of purposes e.g., to
provide heat and hot water, to heat food, run air conditioners.
3.1 When water comes into contact with the outside of a high pressure steam pipe,
the water boils and steam is generated. This water may come from a heavy rain or
a leaking water main. If enough water contacts the pipe, it can cool the steam
inside the pipe, causing it to condense into water. Normally, this water is drained
off by a series of drains called “Traps.” If not drained off, a water slug will form
which can damage piping in a number of ways. Water slugs can be pushed
through the piping by the steam at speeds as high as 200 mph. If this steam slug
encounters a bend in the piping, the impact can cause the pipe to rupture, resulting
in a release of high pressure steam. It is also possible for the slug of water to
suddenly flash to steam resulting in a damaging concussion that can rupture the
steam pipe, again releasing the high pressure steam. Another possible cause for
pipe rupture is a contractor or some other physical damage to the pipe. Con
Edison workers refer to a steam pipe rupture as a High Energy Line Break
(HELB).
Hazards
High temperature and high pressure steam.
Leaking steam will condense quickly filling the plant, obscuring vision.
Asbestos release. Asbestos pipe insulation can be found in the plant, on pipes
buried under the street and in buildings supplied with steam.
A high pressure steam leak will make verbal communications difficult.
A pinhole leak in a high pressure steam pipe, though invisible near the source,
is capable of instantly cutting through a steel bolt.
General Hazards
Heavy machinery and moving equipment.
Sumps filled with near boiling water.
High pressure natural gas lines, other flammable gases under pressure and
compressed gas cylinders including oxygen, acetylene and hydrogen.
High voltage electric, up to 345,000 volts.
Fuel oil.
Acids and caustics.
70
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Tactics
Never enter a Con Edison generating plant without Con Ed personnel. Instead,
respond to the designated mustering site outside the plant.
Plant personnel will mitigate the emergency. FDNY should only enter the plant to
perform search and rescue for missing plant personnel.
a) When entering the plant, stay close to the provided escort and be guided
by their advice.
Contact the Con Edison White Hat who can:
a) Provide critical information and an escort if FD entry is necessary.
b) Provide a personnel accountability report to see if anyone is missing.
c) Remain at the Command Post as a Technical Specialist.
Hazards
Underground steam pipes are most commonly wrapped in asbestos insulation and
a HELB will likely result in an asbestos release that spreads over a large area. A
steam main break is a haz-mat incident.
a) Asbestos has been removed from Con Edison steam manholes but
remains on
most of the underground piping.
b) Asbestos may be drawn into structures by a building’s ventilation
system.
71
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Photo 1a
Debris covers the street in the aftermath of a steam pipe rupture.
The noise of escaping steam will make radio and verbal communication
ineffective in the immediate vicinity of the release.
Condensing steam will obscure the vision of escaping civilians and responding
firefighters.
a) The force of escaping steam can project manhole covers into the air.
Missing manhole covers and the crater and debris resulting from the
HELB may not be visible.
People may be trapped in vehicles, buildings and subways by the escaping steam.
Tactics
Approach an outdoor HELB from upwind and stay clear of the vapor plume.
Establish the Staging Area where units will not become contaminated by asbestos
and where communications are effective.
Consult with the Con Edison White Hat. They may be supervising the shutting of
numerous steam valves.
Limit the number of firefighters exposed to probable asbestos contamination.
Isolate exposed responders, civilians and equipment in order to limit the spread
of asbestos contamination.
72
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
Hazards
High pressure steam risers can be found in the walls on all floors of supplied
buildings. The failure of a high pressure steam pipe inside of a building can be
deadly to anyone in the vicinity of the release. It can force sheetrock and plaster
off of the wall, move furniture and fill rooms with superheated steam that scalds
73
FDNY Probationary Firefighters Manual
Chapter Twenty Four EMERGENCY OPERATIONS
occupants and makes the atmosphere oxygen deficient. Occupants in the vicinity
of a steam release may not have the opportunity to escape. High pressure steam
pipes inside of buildings are typically insulated with asbestos and a HELB in a
building will likely release asbestos inside the building.
Tactics
The high heat may make it impossible to enter the affected area for search and
rescue until the steam is shut and the area vented.
Operating in live steam is debilitating and relief will be necessary to minimize
member exposure time.
Buildings supplied with steam will have a steam control room filled with pipes.
There will be a number of valves to control the supply of steam. Do not randomly
shut steam valves inside of a supplied building. Shutting the wrong valve can
cause damage to the system creating other hazardous conditions. (Photo 4)
b) Once a steam valve is shut, do not reopen it. The system will have to be
drained before reopening the valve.
Adjoining areas to the steam leak must be searched, as steam can infiltrate these
areas.
74
Probationary Firefighters Manual
Chapter 25
BISP WORKBOOK
CONTENTS: • NOV
• VO
• C-Summons
• Residential Inspection
A-119
A-118
IF-1
• Mercantile Inspection
A-119
CIDS
IF-1
IF-6
FDNY REFERENCE: • BISP Manual
25
1
2
Violation Order
3
Violation Order
4
Criminal Court Summons
5
Criminal Court Summons
6
Residential Inspection
BUILDING
RECORD
CARD
Inspection
Classification A Administrative
Unit Block #
58
Location 29-08 31 Ave. NYC Univ. Bl. # 588 Lot # 38
Construction Class 3 Height 75 Stories 5 Area 200x150
OWNERSHIP
DATE NAME ADDRESS TELEPHONE
1928 Josiah Wells 41-27 14 St NY, NY 212 543 2708
1989 Donald Trump 1508 W 81 St NY, NY 212 360 4455
7
Residential Inspection
8
Residential Inspection
9
Div: ____ BN: ____ Unit: _____ Date: __________
If the building/occupancy contains Fire Protection Systems, use the Fire Protection Systems
Supplement Sheet and attach it to the inspection form.
BIN# _________________
Building Address: ____________________________________________
Occupancy Name: ____________________________________________
Inspected Building Inspected Occupancy
Are address numbers plainly legible and visible from the street fronting the property?
Compliant N/A Non-Compliant
Action: Refer to SFO (M-1)
Certificate of Occupancy:
C of O #:______________________________________________________________
Roof:
Bulkhead door unlocked. Note: Door should be provided with slide bolt, hook and eye, or
panic bar. Door can not be locked with a key; if found locked ensure door is unlocked
immediately.
10
FDNY BISP MANUAL
September 1, 2015 FDNY Inspection Form
It shall be unlawful to store rubbish or other combustible waste in a manner that creates a fire hazard.
All fire escapes shall be maintained in good order or repair and structurally safe.
Note: If the structural stability of the fire escape is in question, request DOB to the scene or
forward a DOB Referral Report (High Priority)
Exit Requirements:
Every exit shall be maintained in an unobstructed condition.
Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made
inoperable, if present.
All stairways should be labeled with an alphabetical letter on the occupancy side of the stair.
Housekeeping:
Combustible material shall not be stored in a manner that obstructs egress from any building,
structure or premises.
It shall be unlawful to store rubbish or other combustible waste in a manner that creates a fire hazard.
Extinguishers:
If portable fire extinguishers are provided they should be serviced annually and have a current
service tag attached. See Fire Code guide for requirements.
Compliant N/A Non-Compliant
Action: Refer to SFO (FE-11)
Boiler Room:
Note: Boiler rooms are not always required. Refer to Chapter 5 in order to determine when boiler
room is required.
Boiler rooms are required to have a fireproof self-closing door.
Boiler rooms are required to be segregated, vertically and horizontally, from surrounding spaces by a
fire-resistive rating and maintained in good order.
Compliant N/A Non-Compliant
Action: Refer to SFO (GP-9)
Extinguisher should be provided outside heating room, (2-A: 40-B:C) dry chemical extinguisher
shall be ordered. (Pails of sand are not acceptable)
12
FDNY BISP MANUAL
September 1, 2015 FDNY Inspection Form
Machinery on Roof, Light Weight Construction, Number of Fire Escapes, Courts, Shafts,
Cell Sites:
HVAC system locations, Machinery Room locations, Fire Command Stations, Fire Pumps,
Elevator Machinery Rooms, Cellar Access:
Window bars, Number and Type of Stairways, Labeling of Stairways, Access Stair
locations, Fire Towers:
Haz-Mat/ Miscellaneous:
Additional Violations:
Please list the violation type, location, and enforcement action on any items found in
violation and not preprinted on this form.
Remarks:
If enforcement action is not taken on any item not compliant with the provisions on this
form, please indicate the special circumstances and/or reasons which prevented the
appropriate action:
Endorsements:
I certify that the above information is true and accurate to the best of my knowledge and ability.
Was a Fire Protection Supplement Sheet prepared? Yes No; if yes what type of Fire
Protection System(s) does the building/occupancy have? _____________________________
______________________________________________________________________________
13
Mercantile Inspection
BUILDING
RECORD
CARD
Inspection
Classification A Administrative
Unit Block #
22
Location 20-35 25 Ave NYC Univ. Bl. # 221 Lot # 12
Construction Class 3 Height 30 Stories 1 Area 200x200
OWNERSHIP
DATE NAME ADDRESS TELEPHONE
1985 Home Depot Corp. 41-27 14 St NY, NY 212 543 2708
14
Mercantile Inspection
15
Mercantile Inspection
16
Div: ____ BN: ____ Unit: _____ Date: __________
If the building/occupancy contains Fire Protection Systems, use the Fire Protection Systems
Supplement Sheet and attach it to the inspection form.
BIN# _________________
Building Address: ____________________________________________
Occupancy Name: ____________________________________________
Inspected Building Inspected Occupancy
Are address numbers plainly legible and visible from the street fronting the property?
Compliant N/A Non-Compliant
Action: Refer to SFO (M-1)
Certificate of Occupancy:
C of O #:______________________________________________________________
Roof:
Bulkhead door unlocked. Note: Door should be provided with slide bolt, hook and eye, or
panic bar. Door can not be locked with a key; if found locked ensure door is unlocked
immediately.
17
FDNY BISP MANUAL
September 1, 2015 FDNY Inspection Form
It shall be unlawful to store rubbish or other combustible waste in a manner that creates a fire hazard.
All fire escapes shall be maintained in good order or repair and structurally safe.
Note: If the structural stability of the fire escape is in question, request DOB to the scene or
forward a DOB Referral Report (High Priority)
Exit Requirements:
Every exit shall be maintained in an unobstructed condition.
Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made
inoperable, if present.
All stairways should be labeled with an alphabetical letter on the occupancy side of the stair.
Housekeeping:
Combustible material shall not be stored in a manner that obstructs egress from any building,
structure or premises.
It shall be unlawful to store rubbish or other combustible waste in a manner that creates a fire hazard.
Extinguishers:
If portable fire extinguishers are provided they should be serviced annually and have a current
service tag attached. See Fire Code guide for requirements.
Compliant N/A Non-Compliant
Action: Refer to SFO (FE-11)
Boiler Room:
Note: Boiler rooms are not always required. Refer to Chapter 5 in order to determine when boiler
room is required.
Boiler rooms are required to have a fireproof self-closing door.
Boiler rooms are required to be segregated, vertically and horizontally, from surrounding spaces by a
fire-resistive rating and maintained in good order.
Compliant N/A Non-Compliant
Action: Refer to SFO (GP-9)
Extinguisher should be provided outside heating room, (2-A: 40-B:C) dry chemical extinguisher
shall be ordered. (Pails of sand are not acceptable)
19
FDNY BISP MANUAL
September 1, 2015 FDNY Inspection Form
Machinery on Roof, Light Weight Construction, Number of Fire Escapes, Courts, Shafts,
Cell Sites:
HVAC system locations, Machinery Room locations, Fire Command Stations, Fire Pumps,
Elevator Machinery Rooms, Cellar Access:
Window bars, Number and Type of Stairways, Labeling of Stairways, Access Stair
locations, Fire Towers:
Haz-Mat/ Miscellaneous:
Additional Violations:
Please list the violation type, location, and enforcement action on any items found in
violation and not preprinted on this form.
Remarks:
If enforcement action is not taken on any item not compliant with the provisions on this
form, please indicate the special circumstances and/or reasons which prevented the
appropriate action:
Endorsements:
I certify that the above information is true and accurate to the best of my knowledge and ability.
Was a Fire Protection Supplement Sheet prepared? Yes No; if yes what type of Fire
Protection System(s) does the building/occupancy have? _____________________________
______________________________________________________________________________
20
Div: ____ Bn: ____ Unit: _____ Date: _____________
Signs must be posted at site containing Name, Address and Phone Number of General Contractor
and Owner.
Site Safety:
See the Construction Guide to determine when a Site Safety Manager/Coordinator and a
Construction Site Fire Safety Manager is required, or call the BISP Hotline.
Site Safety Manager/Coordinator and Construction Site Fire Safety Manager Name(s)
_____________________________________________________________
The Site Safety Manager/Coordinator must be present at the site at all times during working
hours. If the Site Safety Manager/Coordinator is not present, a certified alternate must be present
in case of his/her absence and log entries made indicating same.
21
FDNY BISP MANUAL
December 19, 2016 Buildings Under Construction and Demolition Form
When a Construction Site Fire Safety Manager is required, they shall conduct an inspection of
the construction site and all fire safety measures on at least a daily basis, and maintain a record of
same in a bound log book or other approved means.
Compliant Non-Compliant N/A Not Inspected-Abatement Area
Action: Serve Immediate Summons,
Refer to SFO (FSC-29) and/or (FSC-30)
Notify DOB to respond.
Note: The owner shall designate a person to be the Construction Site Fire Safety Manager. It is
possible that this person can also be both the Site Safety Manager and Site Safety Coordinator.
A telephone not requiring a coin to operate, or other approved clearly identified means to notify
the department, shall be provided at an approved location. The street address of the construction
site and the emergency telephone number of the Fire Department shall be posted in a
conspicuous area.
Compliant Non-Compliant N/A Not Inspected-Abatement Area
Action: Refer to SFO (FSC-3)
Approved vehicle access for fire apparatus shall be provided at all construction sites. Vehicle
access shall be provided to within 100 feet of temporary or permanent Fire Department
connections.
Compliant Non-Compliant N/A Not Inspected-Abatement Area
Action: Refer to SFO (M-3)
Combustible waste, including rubbish and construction and demolition material, shall not be
accumulated within buildings and shall be removed from buildings at the end of each work
shift, but at least once a day.
Compliant Non-Compliant N/A Not Inspected-Abatement Area
Action: Refer to SFO (HK-1)
22
FDNY BISP MANUAL
December 19, 2016 Buildings Under Construction and Demolition Form
Combustible waste, including rubbish and construction and demolition material, shall be
removed from the site or stored in noncombustible containers.
Note: Combustible waste material in excess of 15 cubic yards shall be removed daily from
the site before the close of the day’s work, no exceptions.
At all times, there shall be safe access to and egress from every building and every floor in every
building in course of construction or demolition by means of unobstructed hallways, stairways or
ladder runs so enclosed or so located as to protect persons using them from falling materials.
If construction work reaches a height greater than 75 feet, at least one elevator or hoist shall be
kept in readiness at all times for use by the Fire Department.
23
FDNY BISP MANUAL
December 19, 2016 Buildings Under Construction and Demolition Form
Standpipe Systems
Standpipes are required when in the course of construction or alteration the work reaches a
height greater than 75 feet, the standpipe risers should be capped. The system can be dry if
subject to freezing.
Note: Concrete Construction: Standpipe must be capped and maintained up to one floor below
the stripping floor (3 floors below recently poured floor).
Example: Floor being poured (10th fl.)>Frame work (9th fl.)>Stripping Floor (8th fl.)>
Standpipe maintained Capped (7th fl)
Steel Construction: Standpipe capped and maintained on floor below the walking floor.
This could be considered tacked Q-Decking.
When demolition is started the standpipe risers should be capped on the floor immediately below
where the work is being performed. The standpipe shall be maintained as a dry system until
demolition is complete.
Note: Fire Units should pay particular attention to the condition of piping in below grade
areas, siamese connections, section valves on each floor, and the riser in general.
All exposed standpipe and sprinkler piping, except branch piping, must be painted red. Dedicated
standpipe valve handles must be painted red. Combination standpipe valve handles must be
painted yellow. Dedicated sprinkler valve handles must be painted green.
24
FDNY BISP MANUAL
December 19, 2016 Buildings Under Construction and Demolition Form
Sprinkler Systems
In structures undergoing demolition that have existing sprinkler systems with Siamese
connections, such systems shall be maintained as a non-automatic sprinkler system.
Note: Existing systems are any systems with a Siamese, because a Siamese is required
when any fire area requires more than 36 heads. Partial systems are not required to
be maintained during demolition. Partial systems will not have a Siamese.
See Chapter 5 for additional information.
Compliant Non-Compliant N/A Not Inspected-Abatement Area
Action: Refer to SFO (FSC-11)
Request Battalion Chief to respond
Notify DOB to respond
When demolition starts, the sprinkler risers shall be capped immediately below the floor being
demolished to maintain the sprinkler system on all lower floors for Fire Department use until
demolition is complete.
Compliant Non-Compliant N/A Not Inspected-Abatement Area
Action: Refer to SFO (FSC-9)
A metal sign must be present at the Siamese connection for the sprinkler system reading
“SPRINKLER SIAMESE CONNECTION” with a red light over the sign. The red light must
be lit at night.
Compliant Non-Compliant N/A Not Inspected-Abatement Area
Action: Refer to SFO (FSC-12) and/or (FSC-12A)
Note: List the name of the Site Safety Manager/Coordinator or responsible person on site
(owner, general contractor, construction foreman) that confirmed the standpipe
and/or sprinkler system is in service.
Name/Title: _________________________________________________________________
Note: For ordinary hazards (combustible materials such as wood, cloth, paper, rubber, and
many plastics) one 2A extinguisher is required in the above locations. One 2A extinguisher
can cover a maximum floor area of 1,500 square feet. 2A = one 2.5 gallon water
extinguisher, the 2A should be indicated on the extinguisher label.
The handling and use of portable fueled space heaters shall be under the personal supervision of
a person holding a Certificate of Fitness. The storage of portable fueled space heaters and the
fuel therefore, shall be under the general supervision of a Certificate of Fitness holder.
Compliant Non-Compliant N/A Not Inspected-Abatement Area
Action: Refer to SFO (C-21), and/or SFO (C-22)
Note: Personal supervision = must be on site at all times when heaters are being handled or used.
General supervision = not required to be on site at all times.
26
FDNY BISP MANUAL
December 19, 2016 Buildings Under Construction and Demolition Form
Additional Violations:
Please list the violation type, location, and enforcement action on any items found in
violation and not preprinted on this form.
CIDS
Is a CIDS entry required: Yes NO DATE ENTERED:_________________
Example: lightweight construction, Standpipe risers/Siamese locations, key box locations:
Remarks:
If enforcement action is not taken on any item not compliant with the provisions on this
form, please indicate the special circumstances and/or reasons which prevented the
appropriate action:
Endorsements:
I certify that the above information is true and accurate to the best of my knowledge and ability.
Inspected Construction/Demo Inspected Alteration Inspected Abatement
27
Mercantile Inspection
129
28
Probationary Firefighters Manual
Chapter 26
1. INTRODUCTION
1.1 The Probationary Firefighters Development Program ensures that apprentice firefighters
continue their education after graduation from Probationary Firefighter School. Field
training that utilizes reading assignments, training videos, company drills, fire critiques,
cross unit details and the input of senior firefighters is an essential component of the
probationary firefighter professional development.
1.2 Company officers play a vital role in the ongoing educational process. Their guidance is
indispensable in helping probationary firefighters obtain the knowledge and skill needed
to become proficient.
1.3 Company officers should be flexible and take advantage of training opportunities as they
arise. Training can take place during hydrant inspection, after an incident or anytime the
officer feels there are lessons to be learned.
2. PROCEDURES
2.1 Probationary firefighters are provided with monthly training modules consisting of
reading assignments and training videos that emphasize the fundamentals of firefighting.
The Probationary Firefighter can access the training modules by going to the “Probie
Corner” section on the DiamondPlate Home Page. At the end of each monthly training
module is a twenty (20) question quiz that must be completed. When practical, reading
assignments should be coordinated with discussion periods, hands on drills and
familiarization drills. While company officers generally lead the drill periods, the
participation of all members, in particular senior members, is necessary to pass on the
lessons learned and the considerable experience of these members.
Probationary firefighters get three (3) attempts to pass each quiz. If a passing mark is not
attained after the third attempt, the program will be temporarily locked and will require
the company officer to contact the Probationary Firefighters Development Program
Group via email to 323PDPGrp@[Link] to re-activate.
2.2 Company commanders should continue to assign additional reading assignments that
emphasize familiarization of their unit type (Engine or Ladder), Apparatus (Tiller,
Rearmount, TL) and predominant building construction for that company's response area.
This will afford the firefighter an opportunity to apply the knowledge gained during
training sessions.
1 Rev. 06/29/15
FDNY Probationary Firefighters Manual
Chapter 26 (AUC323) PROBATIONARY FF DEVELOPMENT PROGRAM
2.3 There are several addenda to the program to assist the company commanders when new
firefighters are assigned to their units:
• Probationary Firefighter Control Sheet............................Addendum 1
• Probationary Firefighter Training Notebook ...................Addendum 2
Probationary Firefighter- Enter and date in blue or black ink when subject matter has
been read and/or video has been viewed. When Probationary Firefighters have
successfully completed the quiz at the end of the module they will print their completion
receipt and staple it in their notebook.
Officer on Duty - Initial and date in red ink when the subject matter has been reviewed or
drilled on.
Company Commander - Initial and date in red ink once a month. Company Commanders
must ensure that modules and quizzes are being completed in a timely manner.
This process guides probationary firefighters through the training program and ensures
each topic is covered and reviewed. Each tour, probationary firefighters shall make an
entry in the training notebook relating to lessons learned, experience gained, or
information gathered from senior members during their tour. (See Addendum 2)
2.5 The Probationary Firefighter Control Sheet shall be affixed to the inside cover of the
Probationary Firefighters folder (BP-90) when received for continuity within unit.
(See Addendum 1)
2.6 Cross unit details of Probationary Firefighters shall be initiated by the Company
Commander, in consultation with the Battalion Training Coordinator, after the
Probationary Firefighter has completed 90 days of service in the firehouse. Probationary
Firefighters assigned to engine companies shall be detailed to ladder companies, and
those assigned to ladder companies shall be detailed to engine companies. Prior to
commencement of the detail, Company Commanders shall ensure Probationary
Firefighters have familiarized themselves with FDNY Firefighting Procedures/Bulletins
relevant to the area in which they will be detailed. Cross unit details shall be for a period
of 90 days. During this period, Probationary Firefighters shall not be detailed out of the
cross training unit unless absolutely necessary. OSA-2 (Detail More Than 30 Days) shall
be forwarded to the Bureau of Operations.
3. SUMMARY
3.1 The Probationary Firefighters Development Program ensures the initial training provided
by the Bureau of Training continues after the probationary firefighter is assigned to the
field. The ability to establish a positive attitude, encourage adherence to safety standards
and promote a culture of learning are best accomplished early in a firefighter’s career.
2
Probationary Firefighters Manual
Chapter 26, Addendum 1
NAME:
1
Probationary Firefighters Manual
Chapter 26, Addendum 2
(AUC323)
1. PROCEDURES
The senior member gave me some tips on how to maneuver a portable ladder.
(LIST THEM)
1.3 Members shall ensure a tool list from their current unit is attached to the first page
of the notebook. The list provides a ready reference and ensures familiarization with the
tools carried on the apparatus.
1.4 The training notebook is intended to be used as a positive motivational tool in the
development of firefighting skills. Company officers should address any errors or
inconsistent entries made in the book by conducting constructive reviews with the
firefighter. To maximize the effectiveness of the training notebook, members should:
• Bring the training notebook to all drills held in quarters.
• Make entries in the training notebook either during the drill or as soon as possible
after the knowledge has been obtained.
1
FDNY Probationary Firefighters Manual
Chapter 26, Addendum 2 (AUC 323) PROBATIONARY FF DEVELOPMENT PROGRAM
• Review their training notebooks weekly to ensure that their questions are
answered and that the new information is fresh in their minds. An entry should be
made at the time of this review.
• Keep their training notebooks in the company office when not in use.
1.5 Monthly training module receipt should be printed and stapled to current training
notebook page at time of completion. A training module is finished when all material
has been read, videos viewed and monthly quiz successfully completed.
1.6 If the training notebook is lost or destroyed, the company commander must forward
a report through the chain of command to the administrative Division within 30
days, outlining the details of the loss or destruction of the training notebook. The
training notebook must be replaced at the members' expense and a notation of the
replacement must be made in the report forwarded to the administrative Division. The
loss or destruction of the training notebook will be noted in the subsequent evaluation
report of the member and may result in disciplinary action.
1.7 Probationary firefighters shall document all leaves, other than regular leaves in
their training notebook. An entry shall be made in the notebook listing the date the
leave started and ended. On the first tour after the leave has concluded, the officer-on
duty will verify the dates and sign the entry.
1.8 Officers reviewing or evaluating training notebooks shall initiate corrective action
whenever deficiencies are noted. Examples of deficiencies that would result in a
notebook being considered unsatisfactory include, but are not limited to:
• Long, unexplained time gaps between entries
• One word answers or extremely brief entries
• Insufficient number of entries for the time span
• Failure to change format or correct deficiencies noted by company or chief officers.
1.9 Members, who have had their probationary period extended, shall continue to
maintain their training notebooks for a period of time equal to their extended probation.
2.1 Probationary firefighters shall ensure the training notebook is reviewed on a regular
basis according to the following schedule:
• Probationary Firefighter- Review weekly. Initial and date in blue or black ink.
• Officer on Duty- Review each tour the member works. Initial and date in red ink.
• Company Commander- Review monthly. Initial and date in red ink.
• Chief Officers- Review during company drill visits. Initial and date in red ink.
2
FDNY Probationary Firefighters Manual
Chapter 26, Addendum 2 (AUC 323) PROBATIONARY FF DEVELOPMENT PROGRAM
2.2 Company commanders shall ensure Training Notebooks are forwarded for evaluation
as follows:
• 13th Month- Forward Training Notebook to the Battalion and Division
Training Coordinator. Books will be returned to the member upon completion of
evaluation.
2.3 Battalions shall maintain an accurate and up to date list of all firefighters with notebooks
to assist in monitoring compliance.