Zero-Emission SF6 Gas Analyzer

3-038R-R... V0
SF6 Multi-Analyzer with built-in recovery system
This device allows users to determine whether SF6 contaminant levels exceed the value established by equipment
manufacturers and/or national standards organizations (Cigre, IEEE, IEC, etc.).
DILO’s latest SF6-Multi-Analyzer model continues to drive innovation by taking the original world-leading design and
adding even more convenience while remaining Emission-Free! First, the all-new battery power supply allows users
to operate in more remote and/or less power accessible areas. Add to this smaller dimensions and lighter overall
weight and you’ll now have greater ease in handling than ever before! Lastly, we’ve added the ability to change
sensors in the field, so service down time is minimized to minutes!

Intuitive 7” color touch panel interface


Battery or plug power supply
Compact & lightweight
Inlet pressures up to 500 psig (no need for external regulators!)
Zero-Emission gas testing principle
Field-replaceable sensors
Data storage for up to 500 tests
USB & LAN connections for data transfer to Excel© spreadsheet
Integrated calibration warning system
Sensor Controlled Testing (SCT) (reduces test durations!)

Technical data:
Weight & Dimensions: 55 lbs. / L 16”, W 21”, H 10.5”
Input pressure: 4 – 507 psig (pe 0.3 - 35 bar)
Operating temperature: 14 °F to 122 °F
Operating voltage: 100-240 VAC, 50/60Hz or battery operation

Sensor data:
Vol. % Moisture SO2
Measuring principle Velocity of sound Dry out method (capacitive) Electrochemical reaction

Measuring range 0 - 100 vol-% -60 to +20 °C 0 - 500 ppmV


Measuring accuracy ±0.5 vol.-% ±2 °C (at > -40 °C) < ±2 % of measuring range
±3 °C (at < -40 °C)
Reaction time < 1 min < 1 min < 20 s

Purity options:
An alternative purity sensor is available for SF6/CF4 gas mixtures (measuring accuracy: ±2.0 vol. -%). 3-038R-R313V0 option.
Subject to change without notice.

Optional accessories:
In-Line compressor for low pressure environments (pressures < 5 psig) 3-826-R004
© Copyright DILO

Analyzer Discharge Recovery Bag ADRB1


Analyzer adapter kit Adapter Kit Analyzer
20 ft. (6m) long connecting hose with self-closing couplings (extension hose) 3-531-R060
Refilling device with analyzer quick-disconnect fitting 3-393-R068
Long term maintenance program D-916-R…