Siemens 3RV2 Circuit Breaker
Siemens 3RV2 Circuit Breaker
Protection Devices
SIRIUS Innovations - SIRIUS 3RV2 Motor Starter Protectors
Manual
Gerätehandbuch
Edition 09/2014
Industrial Controls
___________________
Product description 3
___________________
Product combinations 4
Protection devices
SIRIUS Innovations - ___________________
5
Functions
SIRIUS 3RV2 motor starter
protectors
___________________
Configuration 6
Manual
___________________
Mounting 7
___________________
Connection 8
___________________
Operation 9
___________________
Accessories 10
___________________
Technical data 11
___________________
Circuit diagrams 12
___________________
Types of coordination A
___________________
References B
___________________
Dimension drawings
(dimensions in mm) C
___________________
Correction sheet D
09/2014
A5E03656507320A/RS-AA/002
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
1 Introduction ........................................................................................................................................... 11
2 Standards ............................................................................................................................................. 13
3 Product description ............................................................................................................................... 15
3.1 Introduction .............................................................................................................................15
3.2 Versions ..................................................................................................................................17
3.3 Applications .............................................................................................................................18
3.4 Motor starter protectors...........................................................................................................19
3.5 Performance features .............................................................................................................21
4 Product combinations............................................................................................................................ 23
5 Functions .............................................................................................................................................. 25
5.1 Overload and short-circuit protection ......................................................................................25
5.1.1 Tripping classes ......................................................................................................................26
5.1.2 Tripping characteristics ...........................................................................................................26
5.2 Phase loss sensitivity ..............................................................................................................29
5.3 Protecting single-phase loads or DC loads.............................................................................29
5.4 Test function ...........................................................................................................................29
6 Configuration ........................................................................................................................................ 31
6.1 SIRIUS Innovations system configurator ................................................................................31
6.2 Short-circuit protection ............................................................................................................31
6.3 Motor protection ......................................................................................................................32
6.4 System protection ...................................................................................................................32
6.5 Motor protection with overload relay function .........................................................................33
6.6 Use of 3RV2 motor starter protectors with highly energy-efficient motors (IE3) ....................34
6.6.1 General information on the startup characteristics of highly energy-efficient motors
(IE3) ........................................................................................................................................34
6.6.1.1 Short-circuit detection .............................................................................................................34
6.6.1.2 Making and breaking capacity of motor starter protectors......................................................35
6.6.1.3 Rated motor current/setting scale ...........................................................................................35
6.6.2 Optimizing 3RV2 motor starter protectors for IE3 motors.......................................................36
6.6.3 Technical modifications/restrictions of 3RV2 motor starter protectors ...................................37
6.7 Short-circuit protection for starter combinations .....................................................................38
6.8 Transformer protection............................................................................................................39
6.9 Main switch .............................................................................................................................39
6.10 Use in IT systems ...................................................................................................................40
The information in this manual enables you to configure and commission the motor starter
protectors.
Further documentation
To install and connect the motor starter protectors, you require the operating instructions of
the motor starter protectors used.
You can find a list of operating instructions and an overview of the manuals pertaining to
SIRIUS Innovations in the appendix "References (Page 185)".
Up-to-the-minute information
You can obtain further assistance by calling the following numbers:
Technical Assistance:
Telephone: +49 (911) 895-5900 (8 a.m. to 5 p.m. CET)
Fax: +49 (911) 895-5907
or on the Internet at:
E-mail: (mailto:[email protected])
Internet: (www.siemens.com/industrial-controls/technical-assistance)
Correction sheet
A correction sheet is included at the end of the manual. Please use it to record your
suggestions for improvements, additions and corrections, and return the sheet to us. This will
help us to improve the next edition of the manual.
Reference
Other standards that 3RV2 motor starter protectors conform to are listed in chapter
Technical data (Page 133). SIRIUS components have been approved by a whole range of
bodies for various sectors (shipbuilding, etc.). An up-to-date list of approvals is provided in
the appendix of the Siemens catalog IC 10 - "SIRIUS Industrial Controls". You will find more
information and downloadable certificates on the Internet
(http://www.siemens.com/automation/service&support).
Applications
3RV2 motor starter protectors are compact current-limiting devices which have been
optimized for load feeders. They are used for protecting and switching three-phase motors
and other loads. The scalable setting ranges mean that a suitable motor starter protector can
provide protection for all standard motors at ambient temperatures of ≤ 60 °C. 3RV2 motor
starter protectors are uniformly fitted with rotary operating mechanisms.
Reference
Functions
The motor starter protectors protect loads against overloads and short circuits. They also
feature a lockable rotary operating mechanism to facilitate manual switching on and off (e.g.
in the event of repair work).
System integration
In both electrical and mechanical terms the motor starter protectors are compatible with 3RT
contactors, 3RF solid-state contactors, and 3RW soft starters. They can be integrated in the
feeder by means of direct mounting. 3RV2 motor starter protectors are available in three
sizes, S00, S0 and S2.
Note
3RF solid-state contactors are available in two sizes, S00 and S0.
Connection systems
The motor starter protectors are available with the following connection system options (in
the main circuit):
● Screw-type connection system (up to 80 A)
● Spring-loaded connection system (3RV2 only, in sizes S00 and S0 up to 32 A)
● Ring cable lug connection system (3RV2 only, in sizes S00 and S0 up to 32 A)
Accessories
The accessories have been tailored to the motor starter protectors and they are available
with a screw-type connection system, spring-loaded connection system or ring cable lug
connection system. Accessories can be fitted easily and without the need for tools.
3.2 Versions
Device versions
● Motor starter protectors, standard version (3RV20)
Overload and short-circuit protection
● Motor starter protectors with relay function (3RV21)
Short-circuit protection and auto-RESET in the event of overload in one device
● MSP for starter combinations (3RV23)
Short-circuit protection only
Combined with solid-state overload relay, large setting ranges and auto-RESET
● MSP for transformer protection (3RV24)
Standard version for transformers
● Circuit breakers in accordance with UL489 (3RV27/3RV28)
Overload protection, short-circuit protection, and transformer protection
Sizes
3RV2 motor starter protectors are available in three sizes, S00, S0 and S2.
The table below lists the sizes and the corresponding maximum rated current at a voltage of
400 V AC. The last column of the table indicates the maximum power of the three-phase
motor which is suitable for the relevant size.
Number of poles
3RV2 motor starter protectors have 3 poles.
3.3 Applications
General
3RV2 motor starter protectors are used for protecting and switching the following loads:
● Three-phase motors up to 37 kW at 400 V AC
● Loads with rated currents of up to 80 A
Special applications
The various 3RV2 motor starter protectors are suitable for:
● Short-circuit protection
● Motor protection (also with overload relay function)
● System protection
● Short-circuit protection for starter combinations
● Transformer protection
● As main and EMERGENCY OFF switches
● Use in IT systems
● Switching direct current
● Hazardous areas (ATEX)
● Use as Branch Circuit Protection Device (BCPD) according to UL (3RV27/28)
Reference
1 Terminals:
Up to two conductors with different cross-sections can be connected for the main and auxiliary
circuits.
In the case of size S00 and S0 devices, the main circuit can be connected by screw-type,
spring-type and ring cable lug connection terminals. In the case of size S00 and S0 devices,
the auxiliary circuit can be connected using either screw terminals or spring-loaded terminals.
Some device versions are also available with ring cable lug connection.
2 Rotary operating mechanism:
For switching on and off, displaying a possible tripping operation, with integrated locking device
3 Label
4 Connection for mounting contactors, solid-state contactors, and soft starters in various connec-
tion systems:
• Direct mounting using link modules
• Separately using connecting cables
5 TEST function:
Enables testing of the release mechanism.
6 Motor current setting:
The large rotary button provides an easy means of setting the device to the rated motor cur-
rent.
A sealable transparent cover can be optionally mounted (accessory). The cover prevents the
motor setting being adjusted (this option is not available for 3RV23/3RV27/3RV28).
1 Terminals:
Up to two conductors with different cross-sections can be connected for the main and auxiliary
circuits.
In the case of size S2 devices, the main circuit can be connected by screw-type connection
terminals. In the case of size S2 devices, the auxiliary circuit can be connected using either
screw terminals or spring-loaded terminals. Some device versions are also available with ring
cable lug connection.
2 Rotary operating mechanism:
For switching on and off, displaying a possible tripping operation, with integrated locking device
3 Label
4 Connection for mounting contactors and soft starters in various connection systems:
• Direct mounting using link modules
• Separately using connecting cables
5 TEST function:
Enables testing of the release mechanism.
6 Motor current setting:
The large rotary button provides an easy means of setting the device to the rated motor cur-
rent.
A sealable transparent cover can be optionally mounted (accessory). The cover prevents the
motor setting being adjusted (this option is not available for 3RV23).
Reference
Overload protection
The rated current of the motor requiring protection (see rating plate) is set on the setting
scale. This sets the integrated overload protection to the motor current.
Short-circuit protection
The short-circuit release is factory-set to a multiple of the motor starter protector's rated
current (top value on the setting scale). The response value of the short-circuit release (in A)
is lasered onto the front of the device. This ensures problem-free ramping-up and safe
protection for the motor.
Release
3RV2 motor starter protectors are fitted with the following releases:
● Inverse-time delayed thermal overload release (exception: 3RV23)
The overload releases can be set on the load feeder (exception: 3RV27, 3RV28).
● Instantaneous short-circuit release
Note
Motor starter protectors for transformer protection
The short-circuit releases of motor starter protectors for transformer protection (3RV24,
3RV28) are set to a higher value than in the case of the 3RV20 motor starter protectors. This
avoids unintentional releases otherwise caused by high inrush currents. The response value
of the short-circuit release (in A) is lasered onto the front of the device.
Table 5- 1 Tripping times dependent upon tripping classes according to standard IEC 60947-4-1
The operating current for the short-circuit release increases by approx. 40% in the case of
direct voltage.
Note
The values for size S2 3RV2 motor starter protectors are available on request.
t Tripping time
I Multiple of current setting
① 3-pole load CLASS 10
② 2-pole load CLASS 10
Figure 5-1 Schematic circuit diagram of the time-current characteristic curve for 3RV20
The characteristic curve reproduced above for the motor starter protector relates to a specific
setting range. It is, however, also valid as a schematic circuit diagram for motor starter
protectors with other current ranges.
Reference
Time-current characteristics, current-limiting characteristics, and I2t characteristics can be
requested on the Internet (http://www.siemens.com/automation/service&support) via
"Technical Assistance".
Reference
To assist you with configuration, the "SIRIUS Innovations system configurator" is at your
disposal on the Internet. Here, you can gather together all necessary products before the
actual configuration process and you can realize complete projects virtually.
You can find the "SIRIUS Innovations system configurator" on the Internet
(http://www.siemens.com/sirius/configurators).
CAUTION
In the overload range the motor starter protector with overload relay function does not
protect itself. Provision has to be made, therefore, to ensure that the current is safely
disconnected by a downstream switching device such as a contactor.
Note
Fixed connection: Auxiliary contacts with motor starter protector
The auxiliary contacts are connected to the right-hand side of the motor starter protector. The
connection is fixed and cannot be removed.
This means that auxiliary releases cannot be mounted on the right-hand side of 3RV21 motor
starter protectors with overload relay function.
Reference
See also
Short-circuit detection (Page 34)
Selection example
Rated motor current: 15 A
Motor starter protector A: Setting scale 10 ... 16 A
Motor starter protector B: Setting scale 14 ... 20 A
→ Recommended motor starter protector 14 ... 20 A because of reduced power loss and
greater distance from response limits.
In the calculation example, the power loss in the case of motor starter protector B is lower by
about 35 % than in the case of motor starter protector A.
The short-circuit releases' response limits always refer to the maximum set value.
In the case of motor starter protector A, the short-circuit release's response value is 208 A
(13 · 16 A).
When the value 15 A is set, the distance from the short-circuit release's response limit is
13.86 times the current setting (208 A/15 A =13.86).
In the case of motor starter protector B, the short-circuit release's response limit is 260 A
(13 · 20 A). When the value 15 A is set, the distance from the short-circuit release's response
limit is 17.33 times the current setting (260 A/15 A = 17.33).
In this example, the distance from the response limit of 13.86 times the current setting in the
case of motor starter protector A increases to 17.33 times the current setting in the case of
motor starter protector B.
Additionally, in the case of size S0 motor starter protectors, the setting range variants "-4P"
(30 to 36 A) and "-4F" (34 to 40 A) are not suitable for use with IE3 motors. You are advised
to use size S2 motor starter protectors in these current ranges.
Size Article number Setting range for overload Setting range for overload
release release
Previously New
S00 3RV2.11-4A… 11 to 16 A 10 to 16 A
S0 3RV2.21-4A… 11 to 16 A 10 to 16 A
3RV2.21-4B… 14 to 20 A 13 to 20 A
3RV2.21-4C… 17 to 22 A 16 to 22 A
3RV2.21-4D… 20 to 25 A 18 to 25 A
Function
In the event of an overload, the overload relay opens the contactor. The motor starter
protector remains on. The motor starter protector will only trip as well in the event of a short
circuit in the feeder.
The short-circuit release is factory-set to a multiple of the motor starter protector's rated
current (top setting scale). The response value of the short-circuit release (in A) is lasered
onto the front of the device. This ensures problem-free ramping-up and safe protection for
the motor.
Advantage
In the event of tripping due to overload, an automatic or manual reset can be performed
without having to open the control cabinet.
Note
Using MSPs for starter combinations with IE3 motors
As described in the chapter "Use of 3RV2 motor starter protectors with highly energy-
efficient motors (IE3) (Page 34)", the integrated motor starting currents and inrush currents
can result in early tripping.
This is why it is recommended that you proceed analogously to when selecting motor starter
protectors when selecting a combination of thermal overload relays and MSPs for starter
combinations. The selection should be made in such a way that the devices are not operated
in the upper range of the setting scale. As a result, power loss is also reduced in the case of
the thermal overload relays.
4 AM control transformers
This version of motor starter protector is not necessary in the case of 4 AM control
transformers with low inrush current (e.g. Siemens control transformers). In such cases
3RV20 motor starter protectors can be used for motor protection.
Function
In the case of IT systems the first fault (ground fault) does not necessarily lead to the
immediate disconnection of the system. A second unrelated fault (ground fault) can reduce
the switching capacity of the motor starter protector.
This is the case specifically if both ground faults occur in different phases and if one of the
two ground faults is on the motor starter protector's input side and the other is on its outgoing
side.
To maintain the motor starter protector's short-circuit-protection function even in the case of
two separate ground faults (known as a double line-to-ground fault), the reduced short-circuit
breaking capacity for double ground faults in IT systems IcuIT has to be taken into account.
Detecting a ground fault when it occurs (ground-fault monitoring) and dealing with it quickly
can significantly reduce the risk of a double ground fault and, as a result, that of a reduced
short-circuit breaking capacity IcuIT.
Reference
Response values
The response values of the overload releases remain unchanged, while the response values
of the short-circuit releases increase by up to 40% with a DC current. The following table
contains suggested circuits for switching direct current:
Note
The values for switching direct current for size S2 motor starter protectors are available on
request.
Note
Double ground fault
In the case of the "2-pole switching, non-grounded system" circuit, it is assumed that safe
tripping will follow even in the event of a double ground fault which short-circuits two
contacts.
6.12.1.2 "Manual motor controller suitable for tap conductor protection in group installations"
(size S0 up to 80 A)
3RV20 motor starter protector as "Manual Motor Controller Suitable for Tap Conductor Protection in
Group Installations"
The "Manual Motor Controller Suitable for Tap Conductor Protection in Group Installations"
application is only applicable in the case of UL.
The CSA does not recognize this approval! Upstream short-circuit protection is always
implemented if the motor starter protector is used as a "Manual Motor Controller Suitable for
Tap Conductor Protection in Group Installations". This requires approved fuses (according to
UL 248) or a circuit breaker (according to UL 489).
These devices must be dimensioned according to the National Electrical Code installation
regulation.
3RV20 motor starter protectors are approved as "Manual Motor Controller Suitable for Tap
Conductor Protection in Group Installations" under the following file number:
● UL File No. 47705, CCN: NLRV
3RV2 motor starter protector as "Self-Protected Combination Motor Controller (Type E)" (up to 52 A1))
For approval according to UL 508 (UL 60947-4-1), a clearance of 1 inch and a creepage
distance of 2 inches are required on the line side for a "Self-Protected Combination Motor
Controller".
3RV20 motor starter protectors in size S00/S0 are therefore approved according to
UL 508 (UL 60947-4-1) together with the terminal block (article no. 3RV29 28-1H) or phase
barriers (article no. 3RV2928-1K).
By virtue of their design, some 3RV20 motor starter protectors in size S2 already fulfill the
required clearances and creepage distances at the input end:
● 3RV2.31-4S.1.
● 3RV2.31-4T.1.
● 3RV2.31-4B.1.
● 3RV2.31-4D.1.
● 3RV2.31-4E.1.
● 3RV2.31-4P.1.
● 3RV2.31-4U.1.
● 3RV2.31-4V.1.
The following motor starter protectors are approved with phase barriers (article no.
3RV2938-1K):
● 3RV2.31-4W.1.
● 3RV2.31-4X.1.
● 3RV2.31-4J.1.
● 3RV2.31-4K.1.
● 3RV2.31-4R.1.
● 3RV2431-4VA1.
● 3RV2.32-.....
CSA approval does not require extended clearances and creepage distances. The terminal
blocks or phase barriers can, therefore, be omitted for use as a "Self-Protected Combination
Motor Controller" according to the CSA.
3RV20 motor starter protectors are approved as "Self-Protected Combination Motor
Controller" under the following file numbers:
● UL File No. E156943, CCN: NKJH,
● CSA Master Contract 165071, Product Class: 3211 08.
1)Motor starter protectors as "Self-Protected Combination Motor Controller (Type E)" in
size S2 higher than 52 A are available on request.
Introduction
The following information must be taken into account when planning applications involving
3RV2 motor starter protectors.
Installation altitude
The motor starter protectors are approved for installation altitudes up to 2,000 m. The
reduced air density at altitudes higher than 2,000 meters affects the motor starter protectors'
electrical characteristics. The reduction factors which have to be taken into account when
using motor starter protectors at altitudes higher than 2,000 m can be obtained on request
on the Internet (http://www.siemens.com/automation/service&support).
Operating conditions
3RV2 motor starter protectors are climate-proof. They are intended for use in enclosed
spaces in which no severe operating conditions prevail (e.g. dust, caustic vapors, hazardous
gases). If they are to be installed in dusty and damp spaces, suitable enclosures must be
provided.
3RV2 motor starter protectors can optionally be fed from the top or from below.
Ambient temperatures/Derating
The permissible ambient temperatures, maximum switching capacity, tripping currents, and
other limiting conditions relevant to application are listed in the technical data. Technical
information is available on the Internet
(http://www.siemens.com/automation/service&support).
3RV2 motor starter protectors are temperature-compensating according to IEC 60947-4-
1/VDE 0660 Part 102 in the temperature range from –20 °C to +60 °C. At higher
temperatures, the upper setting value of the setting range has to be reduced by a specific
factor in accordance with the tables below.
Table 6- 2 Ambient temperatures for 3RV2 motor starter protectors (size S00/S0)
Ambient temperature in °C Reduction factor for the upper set value applies
to ...
Rated current Rated current 22 to 32
0.16 to 20 A A
+60 1,0 1,0
+65 0,94 0,97
+70 0,87 0,94
+75 0,81 0,90
+80 0,73 0,86
In accordance with the table, the reduction factor is 13% at 70 °C. This factor is so low that
due to the overlapping of the current setting ranges there are no gaps before the next setting
range. This means that the available current range spans from 0.11 A to 30.1 A at 70 °C.
Note
Ambient temperatures for size S0 motor starter protectors (36 A and 40 A)
The 36 A and 40 A versions in size S0 are compatible for use in ambient temperatures up to
a maximum of 40° C.
Table 6- 3 Ambient temperatures for 3RV2 motor starter protectors (size S2)
Ambient temperature in °C Reduction factor for the upper set value applies
to ...
Rated current 14 to 80 A
+60 1
+65 0,93
+70 0,87
In accordance with the table, the reduction factor is 13% at 70 °C. This factor is so low that
due to the overlapping of the current setting ranges there are no gaps before the next setting
range. This means that at 70 °C the available current range spans from 9.5 A to 69.6 A.
Explosion protection
Note
In the case of 2- and 3-pole loading, the permissible deviation of the tripping time with 300%
to 800% current setting is up to ± 20% maximum and as such meets the requirements of
DIN VDE 0165 and EN 50019.
3RV20, CLASS 10 motor starter protectors have ATEX approval according to EU Directive
94/9/EC (DMT certificate).
3RV20 motor starter protectors are suitable for overload protection of explosion-protected
motors with "increased safety" type of protection EEx e.
6.15.1 Effects of high-frequency currents on the thermal overload release (sizes S00
and S0)
The thermal overload release on motor starter protectors and overload relays usually
comprises a bimetal and a heating coil through which the motor current flows, causing heat
rise. Excessive deflection of the bimetal (caused by the motor current being too high) will
cause the motor current to be disconnected.
Releases of this type are adjusted with a 50 Hz alternating current. As such, the tripping
point will only be in the required normal range range for currents whose effective heat value
is the same as or similar to this adjustment current. This is the case for alternating currents
from 0 to 400 Hz and for direct currents.
Where high-frequency currents such as those occurring downstream of converters are
concerned, there is additional heat rise of the bimetal. This can be attributed on the one
hand to eddy currents induced by harmonics and on the other to the skin effect in the heating
coil. Both cause the overload release to trip, even at reduced currents (undesirable
premature tripping!).
The effects are dependent upon the frequency of the current. The higher the frequency of
the converter and the lower the setting range/rated current, the more the tripping current will
drop.
To return the tripping limits to the normal range, the setting of the overload release has to be
corrected. The following table shows the adjustment correction factors for the various setting
ranges dependent upon the converter's pulse frequency.
Application example
rms value of the motor current at rated load: 1.2 A. Frequency converter with a pulse
frequency of 8 kHz.
Set to: 1.2 A x 1.21 = 1.45 A
Recommended motor starter protector with setting range: 1.4 to 2 A.
Making this adjustment compensates the high-frequency currents. The tripping current is in
the normal range.
Note
Harmonics
The harmonics can cause the rms value of the motor current to be higher than the motor
rated current. In such cases, undesirable tripping can occur in spite of a correction being
made.
To rectify the situation, the rms value of the motor current has to be determined at rated load
and used as the base current for the correction described above. Only measuring
instruments which are able to reproduce the true rms value up to the prevailing frequencies
are suitable for determining the values. Good examples include hot-wire instruments.
Although moving-iron measuring instruments are in principle also rms instruments, they can
only be used for frequencies up to 1 kHz and, therefore, are not compatible with the majority
of the scenarios described above. Commercially available multimeters or clip-on ammeters
are generally not suitable for taking measurements in these cases.
6.15.2 Effects of high-frequency currents on the thermal overload release (size S2)
The values for the adjustment correction factors for size S2 motor starter protectors are
available on request.
Practical example
In a system supplied by an inverter with a 3 kHz pulse frequency, the motors are connected
with cables measuring 80 m in length. An analysis of the actual current flow shows that very
high-frequency currents (up to 150 kHz) are superimposed on the motor current with a peak
value of 1.5 A. In the case of these frequencies, the effect on the thermal overload release is
significantly greater than described in Effects of high-frequency currents on the thermal
overload release (sizes S00 and S0) (Page 48). Furthermore, capacitive leakage currents
occur in this system due to the cable length and the high frequency. These increase the
current flowing through the release and cause undesirable tripping.
An alternative approach is described below for cases in which high-frequency currents
significantly higher than 16 kHz occur and the procedure described in Effects of high-
frequency currents on the thermal overload release (sizes S00 and S0) (Page 48) no longer
rectifies the problem. When the motor is operating without overload, the overload release
has to be set so high that it will not trip. Once the motor has been running for approx.
1.5 hours at full load, the overload release has to be reduced to the tripping limit and then
this limit set value has to be increased by approx. 10%. This compensates the effects on the
system. The value hereby obtained can also be used as the correction factor for similar
systems.
Minimum clearances
The following clearances from grounded or live parts and from cable ducts made of molded
plastic must be observed in compliance with IEC 60947-2 when mounting motor starter
protectors.
Note
Terminal block type E
In conjunction with the type E terminal block 3RV2928-1H the applicable lateral clearance is
30 mm for all voltages.
Mounting position
The mounting position of 3RV2 motor starter protectors can be selected at will.
7.1.2 Mounting/Disassembly
Installation options
The motor starter protectors are mounted as follows:
● Snapping onto a 35 mm DIN rail according to DIN EN 60715
● Screwed onto a baseplate
Figure 7-2 Mounting/disassembling motor starter protectors (sizes S00 and S0)
Note
Push-in lugs (sizes S00 and S0)
The motor starter protectors can be mounted on a level surface with 2 screws. In the case of
size S00 and S0 motor starter protectors, 2 push-in lugs (3RV2928-0B) (supplied in packs of
10) are also required.
The following figures show snapping onto/removal from DIN rail (size S2).
Table 7- 4 Snapping motor starter protectors (size S2) onto DIN rail
Table 7- 5 Removing motor starter protectors (size S2) from DIN rail
Reference
Installation guidelines for motor starter protectors with limiter function (sizes S00 and S0)
When installing the motor starter protectors, the following clearances must be observed from
grounded or live parts, and from cable ducts:
Type Clearance
Limiter Circuit breaker Ue [V] X [mm] Y [mm] Z [mm]
3RV2321-4EC10 3RV2.1./3RV2.2. 500 90 40 10
690 90 60 30
3RV1331-4HC10 3RV2.1./3RV2.2. 690 140 60 10
Installation guidelines for motor starter protectors with limiter function (size S2)
The values for the minimum clearances for size S2 motor starter protectors are available on
request.
Connection types
The motor starter protectors are available with the following connection types:
● Screw-type connection system
● Spring-loaded connection system (3RV2 only, in sizes S00 and S0 up to 32 A)
● Ring cable lug connection system (3RV2 only, in sizes S00 and S0 up to 32 A)
Connection of terminals
Within the SIRIUS modular system, the conductor cross-sections are matched to one
another dependent upon size.
Reference
Conductor cross-sections
Due to SIRIUS being a modular system, the conductor cross-sections of all the devices of
one size are identical.
AWG
2 x (18 to 14)
2 x 12
*) The conductor cross-sections do not apply for the devices 3RV27 and 3RV28
*) The conductor cross-sections do not apply for the devices 3RV27 and 3RV28
3RV2.31-4S/T/B/D/E/P/U/V. 3RV2.31-4W/X/J/K/R.1.
1. 3RV2431-4VA1.
3RV2.32-...
Tools Pozidriv size PZ 2, Ø 5 to 6 mm
*) The conductor cross-sections do not apply for the devices 3RV27 and 3RV28
Reference
You can find additional information on the conductor cross-sections of the 3RV27 and
3RV28 devices in the sections entitled Conductor cross-sections main circuit (Page 147) and
Conductor cross-sections auxiliary and control circuits (Page 150) .
Note
The main terminals of size S2 motor starter protectors are only available with screw
connections.
AWG 2 x (18 to 8)
Connection cross-sections for ring cable lug connection systems (3RV2 only, in sizes S00 and S0)
The tables below define the permissible conductor cross-sections for main terminals and
auxiliary conductor connections in sizes S00 and S0 for ring cable lug connection systems.
Table 8- 8 Main conductors and auxiliary conductors of size S00 with M3 combination screws
SIRIUS devices
Tools Pozidriv size 2,
Ø 5 to 6 mm
Table 8- 9 Main conductors and auxiliary conductors of size S0 with M4 combination screws
SIRIUS devices
Tools Pozidriv size 2,
Ø 5 to 6 mm
1)The following ring cable lugs are approved for achieving the required clearances and
creepage distances:
● For applications according to IEC 60947-1:
– DIN 46237 (with insulating sleeve)
– JIS CS805 type RAV (with insulating sleeve)
– JIS CS805 type RAP (with insulating sleeve)
● For applications in compliance with UL 508 (UL 60947-4-1):
– DIN 46 234 (without insulating sleeve)
– DIN 46225 (without insulating sleeve)
– JIS CS805 (without insulating sleeve)
A shrink-on sleeve must be used to insulate ring cable lugs without an insulating sleeve. The
following conditions must be met:
● Application temperature: -55 °C to +155 °C
● UL 224 approved
● Flame-protected
DANGER
Hazardous voltage.
Will cause death or serious injury.
Only use approved ring cable lugs to meet the required clearances and creepage
distances.
Procedure
Use a screwdriver to set the load's rated current (current setting) Ie on the scale on the motor
starter protector.
In the context of this setting, a distinction is made between two fundamental designs:
1. Stand-alone assembly: No directly mounted contactor and clearance of at least 10 mm to
left and right.
2. Side-by-side design: Directly mounted contactor or clearance to left and right of less than
10 mm (commonly used design).
Note the two possible setting marks on the adjusting knob:
● Dash marking: Setting mark for the motor starter protector in stand-alone design.
● Triangular marking: Setting mark for the motor starter protector in side-by-side design.
In both cases you can use the full current range up to the scale mark at the top for size S00,
S0 and S2 motor starter protectors at ambient temperatures of up to + 60 °C.
Note
Restrictions in the case of motor starter protectors 3RV2.21-4PA10 (30 to 36 A) and
3RV2.21-4FA10 (34 to 40 A) in size S0
In the case of motor starter protectors with 30 to 36 A and 34 to 40 A, the maximum
permissible ambient temperature is 40 °C.
These motor starter protectors must not be operated side-by-side. A clearance of 9 mm at
the side must be observed. Direct mounting of contactors with link module is not permitted.
The motor starter protectors with 30 to 36 A and 34 to 40 A have only one setting mark (=
dash).
Set the relevant setting mark (dash or triangle) to the load current.
Current reduction
Current reduction is required at ambient temperatures above +60 °C. The maximum
permissible current setting for an ambient temperature of +70 °C is indicated on the scale by
a slightly longer mark on the scale. You can find more information about derating in the
chapter titled Application environment (Page 45).
Result
If the rotary button snaps into the tripped setting, the test was successful.
Result
The connected contactor disconnects.
9.4 Securing
Function
You can secure the motor starter protector against unauthorized closing, for example, if
repair work needs to be carried out.
Procedure
Move the rotary switch to the OFF position. Take the cylinder out of the rotary lever. (This
locks the rotary operating mechanism.) Secure the motor starter protector against
unauthorized closing by locking the rotary switch with a padlock (shackle diameter 3.5 to
4.5 mm).
Tripping
When the motor starter protector trips, the rotary switch moves to the tripped setting to
indicate that it has tripped.
An option is available (in the form of an accessory) to have a signaling switch report tripping
electrically.
Accessories
For maximum flexibility, accessories can be added to the motor starter protector as required,
easily, and without the need for tools.
Mountable accessories
The mountable accessories for size S00/S0 3RV2 motor starter protectors are illustrated
below.
1 Signaling switch
2 Lateral auxiliary switch with 2 contacts
3 Lateral auxiliary switch with 4 contacts
4 Disconnector module
5 Terminal block type E
6 Undervoltage release
7 Shunt release
8 Transverse auxiliary switch
Figure 10-1 Motor starter protector size S00/S0 with mountable accessories
The mountable accessories for size S2 3RV2 motor starter protectors are illustrated below.
Further accessories
● Phase barriers
● Door-coupling rotary operating mechanism
● Enclosures and mounting accessories
● Sealable cover
● Insulated 3-phase busbar system
● 8US busbar adapter
● 3RV2917 infeed system (3RV2 only, in sizes S00 and S0)
● Link modules for the installation of contactors, solid-state contactors or soft starters
For maximum flexibility, accessories can be added to the motor starter protector as required,
easily, and without the need for tools.
Maximum expansion
The maximum expansion of the 3RV2 motor starter protector is one transverse auxiliary
switch, one lateral auxiliary switch with 2 contacts, one signaling switch, and one auxiliary
release.
The lateral auxiliary switch 2 NO contacts + 2 NC contacts can also be used as an
alternative to a transverse auxiliary switch and a lateral auxiliary switch with 2 contacts.
However, in this case it will not be possible to add a signaling switch. Accordingly, a
maximum of 4 auxiliary contacts with auxiliary switches may be mounted on each motor
starter protector.
Possible combinations
The following auxiliary/signaling switch and auxiliary switch combinations are possible:
● The lateral auxiliary switch must be mounted to the left of the signaling switch.
● Transverse and lateral auxiliary switches can be combined.
● A maximum of 4 auxiliary contacts may be added.
● One auxiliary release can be mounted on the right of each motor starter protector. An
auxiliary release cannot be mounted on the 3RV21 motor starter protector.
● The signaling switch must be selected before the auxiliary switch.
● Once a signaling switch has been selected, only one lateral auxiliary switch with 2
contacts can be selected. It is not possible to select the lateral auxiliary switch with 4
contacts.
10.3.1 Description
Function
The contacts of the auxiliary switch open and close along with the main contacts on the
motor starter protector.
Versions
Note
• A maximum of four auxiliary contacts with auxiliary switches can be mounted on each
motor starter protector.
• Auxiliary switches (2 contacts) and signaling switches can be mounted individually or
together.
10.3.2 Mounting
Note
The auxiliary switches are mounted in the same way for all sizes.
Reference
10.3.3 Disassembly
Note
The auxiliary switches are disassembled in the same way for all sizes.
10.4.1 Description
Function
The signaling switch has two contact systems:
● One contact system (1 NO contact + 1 NC contact) signals general tripping irrespective of
whether this was caused by a short circuit, an overload, or an auxiliary release.
● The other contact system (1 NO contact and 1 NC contact) only switches in the event of
short-circuit release.
To be able to reclose the motor starter protector after a short circuit, once the cause of the
error has been dealt with, the signaling switch has to be reset by hand.
Versions
Note
• A signaling switch can be mounted on the side of the motor starter protector.
• An auxiliary switch (2 contacts) and a signaling switch can be mounted individually or
together.
• The signaling switch cannot be used with 3RV27 and 3RV28 circuit breakers.
10.4.2 Mounting
Reference
10.4.3 Disassembly
Overview
The signaling switch supplies two signals:
● A tripped signal (short circuit, overload or tripping by shunt release)
● A short-circuit signal (short circuit only)
1) Rectify the cause of tripping (short-circuit or overload) before resetting the signaling switch.
10.5.1 Description
Auxiliary release
The releases, which are not size-specific, are available in three versions:
● Undervoltage release
● Undervoltage release with leading auxiliary contacts (2 NO contacts)
● Shunt release
The releases are mounted on the right-hand side of the motor starter protector and have a
width of 18 mm. They are available for all commonly used voltages all over the world. They
can be installed inside molded-plastic enclosures.
Note
• One auxiliary release can be mounted on each motor starter protector.
• No accessories can be mounted on the right-hand side of 3RV21 motor starter protectors
with overload relay function.
WARNING
Hazardous Voltage. Risk of death or serious injury.
The function of the undervoltage release may be restricted following a short-circuit release.
Following a short-circuit release, check that the undervoltage release is correctly mounted
and carry out the function test for 3RV2902-1A..., 3RV2902-1C... again.
Shunt release
For remote-controlled tripping of the motor starter protector
● Via PLC: The release's coil should only be energized for a brief period.
Undervoltage release
The undervoltage release trips the motor starter protector in the event of voltage interruption
(e.g. if the power supply fails) and prevents the motor from being unintentionally restarted
when the voltage is restored. The motor starter protector then has to be reclosed by hand.
Particularly suitable for EMERGENCY OFF disconnection via corresponding EMERGENCY
OFF pushbutton according to IEC 60204-1 (VDE 0113)
*) A break of at least 2.5 s must be observed between the trip and switching the undervoltage release back on again.
10.5.3 Mounting
10.5.4 Disassembly
10.6.1 Description
Disconnector module
The disconnector module is mounted on the motor starter protector on the infeed side. The
disconnector module can be used to form a visible isolating distance. To set up the isolating
distance, the plug connector is removed from the enclosure. The isolating plug can only be
removed with the supply disconnected.
The touch-proof isolating point is clearly visible and is secured with a padlock so that the
plug connector cannot be inserted during maintenance work, for example.
Disconnector modules are available for motor starter protectors in sizes S00, S0 and S2.
Note
• The disconnector module cannot be used with 3RV27 and 3RV28 circuit breakers.
• The disconnector module covers the connection screws on the transverse auxiliary
switch. We therefore recommend using lateral auxiliary switches when using the
disconnector module.
• The disconnector module must not be used in conjunction with the 3-phase busbars
3RV1915 and 3RV1935.
• The disconnector module in size S2 can only be used together with motor starter
protectors with rated currents up to 65 A.
10.6.2 Mounting
Mounting sequence
Note
Mounting sequence for disconnector module and transverse auxiliary switch
The disconnector module covers the connection screws on the transverse auxiliary switch.
Therefore, we recommend that you use the lateral auxiliary switches or wait until the
transverse auxiliary switches have been wired before mounting the disconnector module.
10.7.1 Description
"Self-protected combination motor controller (type E)" according to UL 508 (UL 60947-4-1)
3RV20 motor starter protectors are approved as "Self-Protected Combination Motor
Controller" (Type E) according to UL 508 (UL 60947-4-1).
The increased clearances and creepage distances required for this application on the input
side of the device (1 inch and 2 inches respectively) are achieved by adding terminal blocks.
1. The 3RV2928-1H terminal block is screwed onto the basic unit (sizes S00 and S0 only).
2. The 3RV2928-1K (for 3RV2 in sizes S00 and S0) and 3RV2938-1K (for 3RV2 in size S2)
phase barriers are plugged onto the device.1)
1)The following motor starter protectors fulfill the extended clearances and creepage
distances for approval according to Type E without using a phase barrier:
● 3RV2.31-4S.1.
● 3RV2.31-4T.1.
● 3RV2.31-4B.1.
● 3RV2.31-4D.1.
● 3RV2.31-4E.1.
● 3RV2.31-4P.1.
● 3RV2.31-4U.1.
● 3RV2.31-4V.1.
The terminal block is recommended for the connection of larger conductor cross-sections.
Note
CSA
CSA approval does not require extended clearances and creepage distances.
Function
To ensure optimum protection against flashover between the connected conductors in the
event of a short circuit, phase barriers/terminals can be used. The phase barriers/terminals
are required to increase the clearances and creepage distances in conjunction with
prevailing switching overvoltages during motor starter protector switching. The phase
barriers/terminals increase the insulation strength between the motor starter protector's
connection contacts.
Restriction
The terminal block and phase barriers cannot be used simultaneously with 3RV19.5 3-phase
busbars. It is not possible to install the motor starter protector (size S0) with a phase barrier
onto a mounting plate.
Observe the following procedure when fitting the motor starter protector (size S2) with a
phase barrier onto a mounting plate.
1. Use a screwdriver to diagonally tighten the screws in the drilled holes on the motor starter
protector.
2. Attach the phase barrier to the motor starter protector from the front. Tilt the phase barrier
back until it snaps onto the motor starter protector.
Versions
The terminal block and the phase barriers are available in screw designs. They can only be
mounted on the motor starter protector using screw-type connection systems.
Table 10- 16 Mounting the UL 508 (UL 60947-4-1) "type E" terminal
10.8.1 Description
The 3RV2 motor starter protectors can be installed in the control cabinet and operated
externally by means of a door-coupling rotary operating mechanism. The mechanism
engages when the control cabinet door closes. If the motor starter protector is active, the
coupling locks, thereby preventing the door opening unintentionally. This lock can be
deactivated by maintenance personnel. In the OFF setting, the rotary operating mechanism
can be secured against reclosing with up to 3 padlocks. The padlocks prevent the door from
opening unintentionally.
Versions
10.8.2 Mounting
Note
Remember to observe the mechanical coding of the connecting rod!
Table 10- 18 Opening control cabinet doors with door-coupling rotary operating mechanism
Diagram Procedure
To open the control cabinet door, set the motor
starter protector to O (OFF). This will release the
extension shaft from the rotary operating mecha-
nism so that you can open the door.
Note
If the motor starter protector is set to ON and the door is opened with a force of
> 150 to 200 N, the extension shaft cap will break away from the rotary switch on the motor
starter protector to prevent irreparable damage to the motor starter protector. The motor
starter protector remains set to ON.
The extension shaft then needs to be re-attached to the motor starter protector and the door-
coupling rotary operating mechanism as described below:
Diagram Procedure
Switch off the motor starter protector (O) and turn
the rotary switch on the door-coupling rotary
operating mechanism to OFF.
Attach the extension shaft cap to the rotary
switch on the motor starter protector and then
insert the extension shaft into the cap.
Close the control cabinet door.
Locking
In the OFF position, the rotary operating mechanism can be secured by attaching up to
3 locks to the handle outside of the control cabinet, e.g. while maintenance work is carried
out on the system. In this case too, the motor starter protector must be set to the O position
first, before the locks are attached. The locking device on the handle is then pulled forward.
Up to three padlocks with a maximum shackle diameter of 8 mm can be attached to this
locking device.
10.8.4 Operating the door-coupling rotary operating mechanism for arduous conditions
Note
Opening the door with a force of ≥ 800 N when the motor starter protector is set to I can
damage the mechanism beyond repair. The motor starter protector remains active. The
mechanism will keep the door closed up to a force of 800 N.
Locking
The mechanism can be locked inside the control cabinet with a padlock. The motor starter
protector must be set to the O position first, before the lock is attached.
The mechanism can also be locked outside the control cabinet via the handle.
In this case too, the motor starter protector must be set to the O position first, before the
locks are attached. The locking device on the handle is then pulled forward. Up to five
padlocks with a maximum shackle diameter of 6 mm or three padlocks with a maximum
shackle diameter of 8.5 mm can be attached to this locking device.
10.9.1 Description
General
Plastic enclosures for surface mounting are available for the stand-alone assembly of size
S00 (In max = 16 A), S0 (In max = 32 A) and S2 motor starter protectors. Molded-plastic
enclosures for flush mounting are available in various dimensions for motor starter protectors
in sizes S00 and S0.
In the case of installation in molded-plastic enclosures the rated operational voltage Ue of the
motor starter protectors is 500 V.
The enclosures for surface mounting have the degree of protection IP55; the enclosures for
flush mounting also comply with the degree of protection IP55 at the front (the flush-mounted
section complies with IP20).
When installing motor starter protectors with spring-loaded connections (size S00/S0) in
enclosures for surface mounting, the rear cable entries cannot be used.
Motor starter protectors with spring-loaded connections (for 3RV2 in sizes S00 and S0 only)
cannot be used in enclosures for flush mounting.
Enclosures
All enclosures are equipped with N and PE terminals. They have 2 knockout cable entry
openings for cable glands at the top and 2 at the bottom, along with corresponding cable
entries scored on the rear. There is a knockout on the top of the enclosure for indicator lights
which are available as accessories.
The slim-line enclosure can accommodate a motor starter protector without accessories, with
transverse and lateral auxiliary switches. There is no provision for installing a motor starter
protector with signaling switch.
The enclosures are available either with a black rotary operating mechanism or with an
EMERGENCY STOP rotary operating mechanism with red/yellow handle.
In the OFF setting, all rotary operating mechanisms can be locked with up to three padlocks.
A certain derating must be observed when installing size S2 motor starter protectors in the
enclosure for surface mounting. The following table lists the maximum permitted
conventional thermal current.
Front plates
Many applications require motor starter protectors to be actuated in any type of enclosure.
Front plates equipped with a rotary operating mechanism are available for size S00, S0 and
S2 motor starter protectors for this purpose.
A holder for size S00 and S0 motor starter protectors is available for the front plates (the
motor starter protectors snap into the holder).
The front plates can also be used for 3RV2 motor starter protectors in sizes S00 and S0 with
spring-loaded connection.
10.9.2 Mounting
Various enclosures are available for the motor starter protectors.
Mounting the enclosure for flush mounting (for 3RV2 in sizes S00 and S0)
Note
Note that no holder is available for mounting the front plate of a motor starter protector in
size S2.
Position the motor starter protector and the mounted rotary operating mechanism on the
front plate in a suitable position.
10.10.1 Description
10.10.2 Mounting
Table 10- 23 Mounting the sealable cover on the motor starter protector
10.11.1 Description
Note
Exceptions
The 3RV19.5 3-phase busbars are generally unsuitable for 3RV21 motor starter
protectors (for motor protection with overload relay function) and for 3RV27 and 3RV28
circuit breakers (sizes S00 and S0). The devices must also not be used with 3RV29.8-1A
disconnector modules, 3RV2928-1H Type E terminals (for sizes S00 and S0) or 3RV29.8-1K
phase barriers.
Type E starters
The 3-phase busbar systems can also be used to construct "type E starters" in sizes S00, S0
and S2 according to UL/CSA. However, special infeed terminals have to be used for this
purpose.
10.11.2 Versions
Article no. Number of motor starter protectors that Incl. auxiliary re- Rated current In at
can be connected lease 690 V
Modular spacing Without lateral Incl. lateral auxilia-
[mm] accessories ry switch
3RV1915-1.. 45 2/3/4/5 - - 63
3RV1915-2.. 55 - 2/3/4/5 - 63
3RV1915-3.. 63 - - 2/4 63
1) Not suitable for 3RV21 motor starter protectors for motor protection with overload relay function and for 3RV27 and
3RV28 circuit breakers in accordance with UL 489/CSA C22.2 No.5-02.
Article no. Number of motor starter protectors that Incl. auxiliary re- Rated current In at
can be connected lease 690 V
Modular spacing Without lateral Incl. lateral acces-
[mm] accessories sories
3RV1935-1.. 55 2/3/4 - - 108
3RV1935-3.. 752) - 2/3/4 2/3/4 108
1) Not suitable for 3RV21 motor starter protectors for motor protection with overload relay function.
2) For motor starter protectors with lateral accessories.
Auxiliary releases and lateral auxiliary switches/signaling switches cannot be used in combination.
Note
Space requirement of the infeed terminal from below
The infeed terminal with connection from below is connected instead of a motor starter
protector. You will, therefore, need to take the space requirements into account when
configuring the 3-phase busbars.
10.11.3 Mounting
Note
Current carrying capacity
When extending the busbars, please take their current carrying capacity into account.
The diagrams below illustrate the mounting procedure for the 3-phase busbar system:
Sizes S00/S0
Size S2
10.12.1 Description
Reference
For other busbar adapters, see the Catalog Siemens Low-Voltage Power Distribution
LV10.1.
10.12.2 Versions
Article no. Size Rated current Connecting Adapter length Adapter width Rated voltage
cable
A AWG mm mm V
for motor starter protectors with screw terminals
8US1251-5DS10 S00/S0 25 12 200 45 690
8US1251-5NT10 S0 32 10 260 45 690
8US1261-5MS13 S2 80 4 200 55 690
8US1261-6MT10 S2 80 4 260 55 690
8US1211-6MT101) S2 80 4 260 118 690
for motor starter protectors with spring-loaded terminals
8US1251-5DS11 S00/S0 25 12 200 45 690
8US1251-5DT11 S00/S0 25 12 260 45 690
8US1251-5NT11 S0 32 10 260 45 690
1) Assembly kit for load feeders for reversing starters consisting of motor starter protectors and two contactors.
Accessories
The following accessories are available for busbar adapters:
● Device holder for lateral mounting on busbar adapters
● Lateral modules that can be attached on both sides for widening adapters
● Spacer to fix the feeder onto the busbar adapter (article no. 8US1998-1BA10)
● Vibration and shock kit (size S00/S0) for increased vibration and shock load (article no.
8US1998-1CA10)
● Vibration and shock kit (size S2) for increased vibration and shock load (article no.
8US1998-1DA10)
Reference
10.12.3 Mounting
Prerequisites
DANGER
Hazardous voltage!
Will cause death or serious injury.
Turn off and lock out all power supplying this device before working on this device.
10.12.4 Disassembly
Prerequisites
DANGER
Hazardous voltage!
Will cause death or serious injury.
Turn off and lock out all power supplying this device before working on this device.
Mounting sequence
Note
The motor starter protector/feeder can be disassembled from the 8US busbar adapter either
before or after the 8US busbar adapter has been removed from the busbars.
10.13.1 Description
Overview
The 3RV29 infeed system provides a convenient means of feeding in and distributing power
for a group of several motor starter protectors or complete load feeders with screw and
spring-loaded connections in size S00 and S0 (exception: this system cannot be used with
3RV21 motor starter protectors and 3RV27 and 3RV28 circuit breakers). .
The system is based on a basic module complete with a lateral infeed (3-phase busbar with
infeed). This infeed with spring-type terminals is mounted on the right or left depending on
the version and can be supplied with a maximum conductor cross-section of 25 mm2 (with
end sleeve). A basic module has two slots onto each of which a motor starter protector can
be snapped.
Expansion modules (3-phase busbars for system expansion) are available for expanding the
system. An expansion plug is used to connect the individual modules.
The electrical connection between the 3-phase busbars and the motor starter protectors is
established using connectors. The complete system can be mounted on a TH 35 standard
mounting rail to IEC 60715 and can be expanded as required up to a maximum current
carrying capacity of 63 A.
The simple and time-saving plug-in connections mean that the system can be set up easily
and in next to no time. The lateral infeed means that the system does not take up as much
space in the control cabinet either. The additional overall height required for the infeed unit is
only 30 mm. The option to have the infeed on both sides maximizes flexibility where the
configuration of the control cabinet is concerned: Infeed on left-hand or right-hand side as
well as infeed on one side and outfeed on the other side to supply further loads with power
are all possible. As well as the integration of SIRIUS motor starter protectors, a terminal
block with spring-loaded-connections in conjunction with a DIN rail also supports the
integration of 1-/2-/3-phase components such as 5SY miniature circuit breakers or SIRIUS
relay components.
The 3RV29 infeed system has UL approval, and is approved for assembling both the "Self-
Protected Combination Motor Controller" (type E starter), and the "Type F-Starter" (type E
and contactor).
Connector ⑤
The connectors are used to establish the electrical connection between the 3-phase busbar
and the 3RV2 motor starter protector. There are various versions:
● 3RV2 motor starter protector, size S00
– With screw terminals (3RV2917-5CA00)
– With spring-loaded terminals (3RV2917-5AA00)
● 3RV2 motor starter protector, size S0
– With screw terminals (3RV1927-5AA00)
– With spring-loaded terminals (3RV2927-5AA00)
10.13.3 Derating
Derating for fuseless load feeders S00/S0 in the 3RV (63 A) CC infeed system
Size Rated current Max. permissible rated operating Max. ambient temperature
Ie [A] current Ie [%] T [°C]
S00 ≤ 14 100 60
> 14 ... 16 87 60
> 14 ... 16 100 40
S0 ≤ 16 100 60
> 16 ... 25 87 60
> 16 ... 25 100 40
> 25 ... 32 87 40
> 32 Not permissible
10.13.4 Mounting
The diagram below shows an example mounting scenario based on the attachment of the
3RV2 motor starter protector with spring-loaded terminals, size S0, to the 3RV2917 infeed
system.
10.14.1 Description
10.14.2 Mounting
Reference
Select the "Technical Data" option box and a list of the contents of the product data sheet
will appear:
● Technical data
● Approvals/Certificates
● Dimension drawing
● Wiring diagram
● Internal circuit diagram
Using the "Create PDF" button on the right-hand side, you have the option of downloading
your selection in a PDF file.
All information on the product you have chosen is at your disposal free of charge around the
clock and you always get the current version.
• Motor protection ✓ -- -- -- -- --
• Starter combinations -- -- ✓ -- -- --
• Transformer protection -- -- -- ✓ -- ✓
Size S00, S0, S2 S00, S0, S2 S00, S0, S2 S00, S0, S2 S00, S0 S00, S0
Rated current In
• Size S00 A Up to 16 Up to 16 Up to 16 Up to 16 Up to 15 Up to 15
• Size S0 A Up to 40 Up to 32 Up to 40 Up to 25 Up to 22 Up to 22
• Size S2 A Up to 80 Up to 80 Up to 80 Up to 65 -- --
Rated operational voltage Ue V 690 AC2) 690 AC2) 690 AC2) 690 AC2) AC 690 AC 690
acc. to IEC
Rated frequency Hz 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
Tripping class CLASS 10 CLASS 10 -- CLASS 10 -- --
(S00 ... S2),
CLASS 20
(S2)
Thermal overload release A 0.11 to 0.16 0.11 to 0.16 Without3) 0.11 to 0.16 0,16 ... 22 0.16 to 22
to to to fixed setting fixed set-
70 to 80 70 to 80 54 to 65 ting
Overcurrent release 13x 13x 13x 20x 13x 20x
Multiple of the rated current
Short-circuit breaking capacity kA 20 / 55 / 65 55 / 65 / 100 20 / 55 / 65 / 55 / 65 / 100 4) 4)
11.3.1 3RV2.1. and 3RV2.2. motor starter protectors (sizes S00 and S0)
Number of poles 3
Max. rated current In max A 16 15 40
(= max. rated operational cur-
rent Ie)
Permissible ambient temperature
• Storage/transport °C -50 … +80
• +70 °C % 87
• +45 °C % --
• +60 °C % 87 (≤ 32 A)
Type 3RV2.3.
Size S2
Width 55 mm
Standards
• IEC 60947-1, EN 60947-1 (VDE 0660 Part 100) Yes
Number of poles 3
Max. rated current In max A 80
(= max. rated operational current Ie)
Permissible ambient temperature
• Storage/transport °C -50 … +80
• +70 °C % 87
• +45 °C % On request
• +60 °C % --
Type 3RV2.3.
Size S2
Width 55 mm
Utilization category
• IEC 60947-2 (motor starter protectors) A
Type 3RV2.3.
Size S2
Width 55 mm
Protective separation between the main circuit and
the auxiliary circuit necessary for PELV applica-
tions
acc. to DIN EN 60947-1
• Up to 400 V + 10% Yes
Permissible mounting position Any, acc. to IEC 60447 start command "I" right or top
Mechanical endurance Operating cycles 50 0004)
Electrical durability Operating cycles 50 0004)
Max. switching frequency per hour (motor 1/h 15
starts)
1) Current reduction above +60 °C
2) When using a 500 V molded-plastic enclosure.
3) Not applicable to 3RV233..
4) For rated current In = 52 A; on request (for rated current In = 80 A)
Type 3RV29 Lateral auxiliary switch with Signaling Transverse auxiliary switch with
1 NO contact + 1 NC contact, switch 1 CO contact 1 NO contact +
2 NO contacts, 2 NC contacts, 1 NC contact,
2 NO contacts + NC contacts; 2 NO contacts
Max. rated voltage
• Acc. to NEMA (UL) V AC 600 600 600 250
1 CO contact
Rated operational voltage Ue alternating voltage V 125
Rated operational current Ie/AC-14 at Ue = 125 V A 0.1
Rated operational voltage Ue direct voltage L/R 200 ms V 60
Rated operational current Ie /DC-13 at Ue = 60 V A 0.3
Minimum load capacity V 5
mA 1
• Specified tightening torque Nm 0,8 ... 1,2 2 ... 2,5 2,5 ... 3
Usable ring cable lugs mm d22) = min. 3.2, d22) = min. 4.3, --
d32) = max. 7.5 d32) = max. 12.2
• DIN 46234 without insulating sleeve
1) If two different conductor cross-sections are being connected to one clamping point, both cross-sections must be locat-
ed in the range indicated. If identical cross-sections are used, this restriction does not apply.
2)
3RV2.31-4U.1.
3RV2.31-4V.1.
Size S2
Width 55 mm
Connection type Screw connection
• Connection screw M6, Pozidriv size 2
1) If two different conductor cross-sections are being connected to one clamping point, both cross-sections must be locat-
ed in the range indicated. If identical cross-sections are used, this restriction does not apply.
2)
Table 11- 2 Short-circuit breaking capacity ICU, ICS acc. to IEC 60947-2 - Part 1
Table 11- 3 Short-circuit breaking capacity ICU, ICS acc. to IEC 60947-2 - Part 2
Motor start- Rated current Up to 440 V AC1) / 460 V AC2) Up to 500 V AC1) / 525 V AC2) Up to 690 V AC1)
er protector In Icu Ics Max. fuse Icu Ics Max. fuse Icu Ics Max.
(gL/gG)3) (gL/gG)3) fuse
(gL/gG)3)4)
Type A kA kA A kA kA A kA kA A
Size S00
3RV2.1 0,16 ... 1,25 100 100 -- 100 100 -- 100 100 -
1,6 100 100 -- 100 100 -- 100 100 -
2 100 100 -- 100 100 -- 10 10 25
2,5 100 100 -- 100 100 -- 10 10 25
3,2 100 100 -- 100 100 -- 10 10 32
4 100 100 -- 100 100 -- 6 4 32
5 100 100 -- 100 100 -- 6 4 32
6,3 100 100 -- 100 100 -- 6 4 50
8 50 50 63 42 42 63 6 4 50
10 50 50 80 42 42 63 6 4 50
12,5 50 50 80 42 42 80 6 4 63
16 50 10 80 10 5 80 4 4 63
Size S0
3RV2.2 16 50 10 80 10 5 80 4 2 63
20 50 10 80 10 5 80 4 2 63
22 50 10 100 10 5 80 4 2 63
25 50 10 100 10 5 80 4 2 63
28 30 10 125 10 5 100 4 2 100
32 30 10 125 10 5 100 4 2 100
36 12 8 125 6 3 100 3 2 100
40 12 8 125 6 3 100 3 2 100
Motor start- Rated current Up to 440 V AC1) / 460 V AC2) Up to 500 V AC1) / 525 V AC2) Up to 690 V AC1)
er protector In Icu Ics Max. fuse Icu Ics Max. fuse Icu Ics Max.
(gL/gG)3) (gL/gG)3) fuse
(gL/gG)3)4)
Type A kA kA A kA kA A kA kA A
Size S2
3RV2.31 14; 17 50 25 100 12 6 63 5 3 63
20 50 25 100 12 6 80 5 3 80
25 50 15 100 12 6 80 5 3 80
32; 36 50 15 125 10 5 100 4 2 100
40; 45 50 15 125 10 5 100 4 2 100
52 50 15 125 10 5 125 4 2 125
59 ... 80 On request
Size S2, with increased switching capacity
3RV2.32 14; 17 65 30 100 18 10 63 8 5 63
20; 25 65 30 100 18 10 80 8 5 80
32 ... 45 65 30 125 15 8 100 6 4 100
52 65 30 125 15 8 125 6 4 125
59 ... 80 On request
--- No back-up fuse required, since short-circuit resistant up to 100 kA.
1) 10 % overvoltage
2) 5% overvoltage
3) Back-up fuse only required if short-circuit current at installation location is > ICU
4) Alternatively, fuseless limiter combinations can be used for 690 V AC.
11.12.2 Short-circuit breaking capacity for motor starter protectors in the IT system
1 100 1) 100 1)
2 100 1) 8 25
2,5 100 1) 8 25
3,2 100 1) 8 32
4 100 1) 4 32
5 100 1) 4 32
6,3 100 1) 4 50
8 100 1), 4 50
10 100 1) 4 50
12,5 100 1) 4 63
16 55 80 4 63
Rated current Up to 440 V2)/460 V3) AC Up to 500 V2)/525 V3) AC Up to 690 V6) AC
In IcuIT Max. fuse IcuIT Max. fuse IcuIT Max.
(gL/gG)4), 5) (gL/gG)4), 5) fuse
(gL/gG)4)
A kA A kA A kA A
Size S00
3RV2.11 0,16 ... 0,4 100 1) 100 1) 100 1)
Rated current Up to 440 V2)/460 V3) AC Up to 500 V2)/525 V3) AC Up to 690 V6) AC
In IcuIT Max. fuse IcuIT Max. fuse IcuIT Max.
(gL/gG)4), 5) (gL/gG)4), 5) fuse
(gL/gG)4)
A kA A kA A kA A
Size S2
3RV2.31 14 ... 25 6 80 6 80 4 63
32 ... 45 4 100 4 100 3 80
52 3 125 3 125 2 100
59 ... 80 On request
Size S2, with increased switching capacity
3RV2.32 14 ... 25 6 80 6 80 4 63
32 ... 45 6 100 6 100 4 80
52 6 125 6 125 4 100
59 ... 80 On request
1) No backup fuse required, as short-circuit-proof up to 100 kA
2) 10 % overvoltage
3) 5 % overvoltage
4) Backup fuse only required if short-circuit current at installation location is > IcuIT
5) Alternatively, fuseless limiter combinations can be used for 690 V AC
6) Overvoltage category II applies for applications in IT systems > 600 V
11.12.3 Short-circuit breaking capacity for motor starter protectors with limiter function
Short-circuit breaking capacity for motor starter protectors with limiter function for 500 V AC and
690 V AC according to IEC 60947-2
Table 11- 6 Short-circuit breaking capacity for motor starter protectors with limiter function
Operating Voltage
current
115V/120 V 200/208 V 230/240 V 460/480 V 575/600 V
1-phase 3-phase 1-phase 3-phase 1-phase 3-phase 1-phase 3-phase 1-phase 3-phase
3RV2011/3RV2111/3RV2311/3RV2411 size S00
0,11...0,1 -- -- -- -- -- -- - -- -- --
6
0,14...0,2 -- -- -- -- -- -- - -- -- --
0,18...0,2 -- -- -- -- -- -- - -- -- --
5
0,22..0,32 -- -- -- -- -- -- - -- -- --
0,28...0,4 -- -- -- -- -- -- - -- -- --
0,35...0,5 -- -- -- -- -- -- -- -- -- --
0,45...0,6 -- -- -- -- -- -- -- -- -- --
3
0,55...0,8 -- -- -- -- -- -- -- -- -- --
0,7...1 -- -- -- -- -- -- -- -- -- 1/2
0,9...1,25 -- -- -- -- -- -- -- 1/2 -- 1/2
1,1...1,6 -- -- -- -- 1/10 -- -- 3/4 -- 3/4
1,4...2 -- -- -- -- 1/8 -- -- 3/4 -- 1
1,8...2,5 -- -- 1/6 1/2 1/6 1/2 -- 1 -- 1 1/2
2,2...3,2 1/10 -- 1/6 1/2 1/4 3/4 -- 1 1/2 -- 2
2,8...4 1/8 -- 1/4 3/4 1/3 3/4 -- 2 -- 3
3,5...5 1/6 1/2 1/3 1 1/2 1 -- 3 -- 3
4,4...6,3 1/4 1/2 1/2 1 1/2 1 1/2 -- 3 -- 5
5,5...8 1/3 3/4 3/4 2 1 2 -- 5 -- 5
7...10 1/2 1 1 2 1 1/2 3 -- 5 -- 7 1/2
9...12,5 1/2 1 1/2 1 1/2 3 2 3 -- 7 1/2 -- 10
11...16 1 2 2 3 2 5 -- 10 -- --
3RV2021/3RV2121/3RV2321/3RV2421 size S0
11...16 1 2 2 3 2 5 -- 10 -- --
14...20 1 1/2 3 3 5 3 5 -- 10 -- --
17...22 1 1/2 3 3 5 3 7 1/2 -- 15 -- --
20...25 2 3 3 5 (200 V) 3 7 1/2 -- 15 -- --
7 1/2 (208 V)
23...28 2 3 3 7 1/2 5 10 -- 20 -- --
27...32 2 5 3 (200 V) 7 1/2 (200 V) 5 10 -- 20 -- --
5 (208 V) 10 (208 V)
30...36 3 5 5 10 5 10 -- 25 -- --
34...40 3 5 5 10 7 1/2 10 -- 30 -- --
Operating Voltage
current 115V/120 V 200/208 V 230/240 V 460/480 V 575/600 V
1-phase 3-phase 1-phase 3-phase 1-phase 3-phase 1-phase 3-phase 1-phase 3-phase
3RV2031/3RV2032 size S2
9,5...14 1,5 3 3 5 3 5 -- 10 -- 15
12...17 1,5 3 3 5 3 7,5 -- 15 -- 15
14...20 1,5 3 3 7,5 3 7,5 -- 15 -- 20
18...25 2 5 3 7,5 5 10 -- 20 -- 25
22...32 3 5 5 10 5 10 -- 25 -- 30
28...36 3 7,5 5 / 7,5 15 7,5 15 -- 30 -- 40
32...40 3 7,5 5 / 7,5 15 7,5 15 -- 30 -- 40
35...45 3 7,5 7,5 15 10 15 -- 40 -- 50
42...52 5 10 7,5 15 10 20 -- 40 -- 50
49...59 On request
54...65
62...73
70...80
Note
The following values apply with Class J fuses only.
11.13.1.3 "Manual motor controller suitable for tap conductor protection in group installations"
(size S0 up to 80 A)
3RV20 motor starter protector as "Manual Motor Controller Suitable for Tap Conductor Protection in
Group Installations"
The "Manual Motor Controller Suitable for Tap Conductor Protection in Group Installations"
application is only applicable in the case of UL.
The CSA does not recognize this approval! Upstream short-circuit protection is always
implemented if the motor starter protector is used as a "Manual Motor Controller Suitable for
Tap Conductor Protection in Group Installations". This requires approved fuses (according to
UL 248) or a circuit breaker (according to UL 489).
These devices must be dimensioned according to the National Electrical Code installation
regulation.
3RV20 motor starter protectors are approved as "Manual Motor Controller Suitable for Tap
Conductor Protection in Group Installations" under the following file number:
● UL File No. 47705, CCN: NLRV
3RV2 motor starter protector as "Self-Protected Combination Motor Controller (Type E)" (up to 52 A1))
For approval according to UL 508 (UL 60947-4-1), a clearance of 1 inch and a creepage
distance of 2 inches are required on the line side for a "Self-Protected Combination Motor
Controller".
3RV20 motor starter protectors in size S00/S0 are therefore approved according to
UL 508 (UL 60947-4-1) together with the terminal block (article no. 3RV29 28-1H) or phase
barriers (article no. 3RV2928-1K).
By virtue of their design, some 3RV20 motor starter protectors in size S2 already fulfill the
required clearances and creepage distances at the input end:
● 3RV2.31-4S.1.
● 3RV2.31-4T.1.
● 3RV2.31-4B.1.
● 3RV2.31-4D.1.
● 3RV2.31-4E.1.
● 3RV2.31-4P.1.
● 3RV2.31-4U.1.
● 3RV2.31-4V.1.
The following motor starter protectors are approved with phase barriers (article no.
3RV2938-1K):
● 3RV2.31-4W.1.
● 3RV2.31-4X.1.
● 3RV2.31-4J.1.
● 3RV2.31-4K.1.
● 3RV2.31-4R.1.
● 3RV2431-4VA1.
● 3RV2.32-.....
CSA approval does not require extended clearances and creepage distances. The terminal
blocks or phase barriers can, therefore, be omitted for use as a "Self-Protected Combination
Motor Controller" according to the CSA.
3RV20 motor starter protectors are approved as "Self-Protected Combination Motor
Controller" under the following file numbers:
● UL File No. E156943, CCN: NKJH,
● CSA Master Contract 165071, Product Class: 3211 08.
1)Motor starter protectors as "Self-Protected Combination Motor Controller (Type E)" in
size S2 higher than 52 A are available on request.
Connection screw M4
Rear clamping point connected
• Solid mm² 1 ... 10
Connection screw M4
Both clamping points connected
• Front clamping point:
- Solid mm² 1 ... 10
- Finely stranded with end sleeve mm² 1 ... 10
- Stranded mm² 2,5 ... 10
- AWG cables, solid or stranded mm² 14 ... 6
- Connection screw M4
• Rear clamping point:
- Solid mm² 1 ... 10
- Finely stranded with end sleeve mm² 1 ... 10
- Stranded mm² 5 ... 25
- AWG cables, solid or stranded mm² 16 ... 3
- Connection screw M4
Reference
More information about accessories is available in the chapter titled Phase barriers/UL
508 (UL 60947-4-1) "type E" terminals (Page 93).
11.14 Accessories
Type 3RV29.7
Infeed system
General data
Standards IEC 60947-2
IEC 60947-4-1
Rated operational voltage Ue
IEC • 10% overvoltage V 500
• 5% overvoltage V 525
UL/CSA V 600
Rated insulation voltage Ui (pollution degree 3) V 500
Rated impulse withstand voltage Uimp kV 6
Rated frequency Hz 50/60
Rated current In A 63
Permissible ambient temperature • Operation °C -20 … + 60
• Storage/transport °C -50 … + 80
• 60 °C A 87%
• 60 °C A 87%
Type 3RV29.7
Infeed system
General data
Permissible rated current of the 3RV2.21 (S0) motor start-
er protector greater than 25 A to 32 A at internal control
cabinet temperature
• 40 °C A 87%
Motor starter protectors for motor protec- Motor starter protector for starter protection
tion/transformer protection/system protection
3RV20.1-...5, 3RV24.1-...5,
3RV20.2-...5
Motor starter protectors for motor protection/transformer protection with transverse auxiliary
switch
3RV21.1-...0
Motor starter protectors for motor protection with overload relay function
Auxiliary release
3RV2902-.A.. 3RV2922-.C.. 3RV2902-.D..
Signaling switch
Types of coordination
Standard DIN EN 60947-4-1 (VDE 0660 Part 102) or IEC 60947-4-1 distinguishes between
two types of coordination (type of coordination), which are referred to as coordination type
"1" and coordination type "2". In the case of both types of coordination, the short-circuit is
reliably mastered. the only differences are in the extent of the damage sustained by the
device following a short circuit.
Type of coordination 1
The load feeder may be non-operational after a short circuit has been cleared. Damage to
the contactor and the overload release is also permissible.
Type of coordination 2
After short-circuit disconnection, there must be no damage to the overload release or to any
other part. The load feeder can resume operation without needing to be renewed. Welding of
the contactor contacts only is permitted if these can be separated easily without significant
deformation.
Further references
You will find further information about the 3RV2 motor starter protectors on the Internet
(http://support.automation.siemens.com/WW/view/en/20358027/133300).
In addition to this manual, please refer to the operating instructions and manuals for any
accessories. You can download the relevant documentation from the Internet
(http://www.siemens.com/sirius/manuals). Simply enter the order number of the relevant item
into the search field.
Operating instructions
• 3RT2, 3RH2, and 3RA23/24 contactors and • "SIRIUS Innovations - SIRIUS 3RT2 Contactors / Contactor
contactor assemblies Assemblies"
(http://support.automation.siemens.com/WW/view/en/60306557)
manual
(Article number: 3ZX1012-0RT20-5AC1)
• 3RF34 solid-state switching devices • "SIRIUS Innovations - SIRIUS 3RF34 Solid-State Switching Devices"
(http://support.automation.siemens.com/WW/view/en/60298187)
manual
(Article number: 3ZX1012-0RF34-5AC1)
• 3RV2 motor starter protectors • "SIRIUS Innovations - SIRIUS 3RV2 Motor Starter Protector"
(http://support.automation.siemens.com/WW/view/en/60279172)
manual
(Article number: 3ZX1012-0RV20-5AC1)
• 3RU2, 3RB30/31 overload relays • "SIRIUS Innovations - SIRIUS 3RU2 / 3RB3 Overload Relays"
(http://support.automation.siemens.com/WW/view/en/60298164)
manual
(Article number: 3ZX1012-0RU20-5AC1)
• 3RB24 solid-state overload relays • "3RB24 Solid-State Overload Relay for IO-Link"
(http://support.automation.siemens.com/WW/view/en/46165627)
manual
(Article number: 3ZX1012-0RB24-0AC0)
• 3RS14/3RS15 temperature monitoring • "3RS14 / 3RS15 Temperature Monitoring Relays for IO-Link"
relays (http://support.automation.siemens.com/WW/view/en/54375463)
manual
(Article number: 3ZX1012-0RS14-0AC0)
• 3RA21/22 load feeders • "SIRIUS Innovations - SIRIUS 3RA21 / 3RA22 Load Feeders"
(http://support.automation.siemens.com/WW/view/en/60284351)
manual
(Article number: 3ZX1012-0RA21-5AC1)
• 3RA28 function modules for mounting on • Manual "SIRIUS Innovations - SIRIUS 3RA28 Function Modules for
contactors mounting on 3RT2 Contactors"
(http://support.automation.siemens.com/WW/view/en/60279150)
(Article number: 3ZX1012-0RA28-5AC1)
More information
More information is available from Siemens on the Internet via the following links.
● Product documentation
You will find a list of manuals/operating instructions, characteristic curves, and certificates
on the Internet (http://www.siemens.com/sirius/support).
● Product information
Catalogs and other informative documents can be obtained from the Information Center
and Download Center (http://www.siemens.com/sirius/infomaterial).
● Online ordering system
You will find the online ordering system with all the latest data on the ordering and
information platform (http://www.siemens.com/sirius/mall).
● Technical Assistance
Siemens supports you with all technical product and system enquiries – both before and
after delivery. You can access our Service & Support Portal on the Internet
(http://www.siemens.com/sirius/technical-assistance). You can also submit your question
directly to a technical consultant using our support request service.
C.1.1 Dimension drawings for 3RV2 motor starter protectors (sizes S00 and S0)
① 3RV2902, 3RV2922
② 3RV2111, 3RV2121
Figure C-1 Motor starter protectors with screw-type and spring-loaded connection, S00/S0
Figure C-2 Motor starter protector with screw-type connection system S00/S0
Figure C-3 Motor starter protector with spring-loaded connection system S00
Figure C-5 Motor starter protector with ring cable lug connection system S00/S0
Drilling plan
C.1.2 Dimension drawings for 3RV2 motor starter protectors (size S2)
Drilling plan
Size A B
S00/S0 119 70
Figure C-13 3RV1915-1..
Size A B
S00/S0 119 70
Figure C-14 3RV1915-2..
Size A B
S00/S0 119 70
Figure C-15 3RV1915-3..
3RV2925-5AB
Connection from above,
for motor starter protectors sizes S00 and S0
3RV2925-5EB
For installing "type E starters"
Connection from above,
for motor starter protectors sizes S00 and S0
3RV2915-5B
Connection from below,
for motor starter protectors sizes S00 and S0
Type a
3RV2.1 / 3RV2.2 23
3RV2935-5A
Connection from above,
for motor starter protectors size S2
3RV2935-5E
For installing "type E starters"
Connection from above,
for motor starter protectors size S2
3RV2926-0B, 3RV2926-0C
Short shaft3), for motor starter protectors sizes S00, S0 and S2
3RV2926-0K, 3RV2926-0L
Long shaft (with bracket)3), for motor starter protectors sizes S00, S0 and S2
3RV2926-2., 3RV2936-2.
for motor starter protector sizes S00, S0 and S2
Type Size A B C D E F G H J
3RV2926 S00/S0 125 111 50 77 112 50 27 9 42
-2..
3RV2936 S2 170 160 60 87 162 50 27 10 47
-2..
3RV2928-1H
For motor starter protectors sizes S00 and S0
3RV2928-1K
For motor starter protectors sizes S00 and S0
3RV2938-1K
for motor starter protectors size S2
3RV1923-1.A00
For motor starter protectors sizes S00 and S0
Type a
3RV1923-1CA00 85
3RV1923-1DA00 105
3RV1933-1DA00, 3RV1933-1GA00
for motor starter protectors size S2
3RV1923-1DA01, 3RV1923-1GA01
For motor starter protectors sizes S00 and S0
3RV1923-2DA00, 3RV1923-2GA00
For motor starter protectors sizes S00 and S0, not for devices with spring-loaded
connections
3RV1923-4B, 3RV1923-4E
for motor starter protectors sizes S00, S0 and S2;
3RV1923-4G bracket only for motor starter protectors sizes S00 and S0
_________________________________________________________________________________
Fax: +49 (0)9621-80-3337
Manual title:
Undervoltage release, 86
Voltage ranges, 87
3 Auxiliary switch blocks
Motor starter protector, 78, 79, 80
3-phase busbar system
Auxiliary switch blocks (motor starter protector)
Motor starter protector, 94, 111, 112, 114
Solid-state compatible, 78
3-phase busbar system (motor starter protectors)
3-phase infeed terminal, 113
Type E starters, 111, 113
B
3RV2917 infeed system
Motor starter protector, 123, 128, 129 Basic knowledge, 11
Busbar adapter
Motor starter
A protector, 116, 117, 119, 120, 121, 122
Accessories
Motor starter protector, 73
C
Accessories - motor starter protectors
Busbar adapter, 116, 117, 119, 120 Circuit breaker
Accessories - Motor starter protectors Motor starter protector, 44, 175
3-phase busbar system, 94, 111, 112, 114 Clearance, 93
3RV2917 infeed system, 123, 128, 129 Conductor cross-sections, 60
Auxiliary release, 85, 87, 88, 88 Configuration guidelines (motor starter protectors)
Auxiliary switch blocks, 78, 79, 80 Frequency converter, 48
Busbar adapter, 121, 122 Inverter with pulsed voltage, 48
Disconnector module, 89, 91, 92 Connection systems
Door-coupling rotary operating Motor starter protector, 16, 59
mechanism, 98, 99, 102 Correction sheet, 215
Enclosures and mounting accessories, 105, 107 Corrections, 12
Installation rules, 77 Coupling driver
Link module for contactor, 131 Motor starter protector, 96
Phase barriers/terminal block, 93, 95, 95 Creepage distance, 93
Sealable cover, 110, 110 CSA
Signaling switch, 81, 83 Motor starter protector, 42, 161
Signaling switches, 82, 84 Current reduction
Adjustment correction factors Motor starter protector, 68
Frequency converter, 48 Current setting
Advantages Motor starter protector, 68
Motor starter protector, 21
Ambient temperature
Motor starter protector, 46, 67 D
Applications
DC current
Motor starter protector, 18
Motor starter protector, 40
Auxiliary contacts (motor starter protector), 33
DC loads
Auxiliary release
Motor starter protector, 29
Motor starter protector, 85, 87, 88, 88
Derating
Auxiliary release (motor starter protector)
Motor starter protector, 46
EMERGENCY OFF disconnection, 86
Derating (motor starter protectors)
Shunt release, 85
3RV2917 infeed system, 128
www.siemens.com/automation
The primary benefits of using SIRIUS 3RV2 motor starter protectors include improved installation efficiency and enhanced operational reliability. The compact design and compatibility with different connection systems, such as screw-type, spring-loaded, and ring cable lug, allow for easy and flexible installation in various electrical systems . Operational reliability is enhanced by features such as overload and short-circuit protection, phase loss sensitivity, and compatibility with highly energy-efficient motors (IE3) through optimized short-circuit detection and settings . Moreover, they provide group installations and are compliant with relevant international standards, ensuring safety and performance in different environments .
The SIRIUS modular system is designed for seamless compatibility and flexibility, allowing 3RV2 motor starter protectors to be combined quickly and effectively with other components both electrically and mechanically. The system includes typical fuseless and fused design combinations that have been fully tested and approved. This compatibility minimizes the complexity of configuration, reduces stockkeeping requirements, and provides a straightforward method to upgrade or expand motor protection systems as needed .
The SIRIUS 3RV2 motor starter protectors ensure both motor and system protection according to international standards by providing overload protection, short-circuit protection, and phase loss sensitivity, in compliance with IEC 60947-2 / DIN VDE 0660-101 . Additionally, the short-circuit protection includes a release set to a multiple of the motor starter protector's rated current, facilitating problem-free ramping-up and safe motor protection . The adjustable inverse-time delayed thermal overload release and the factory-set instantaneous short-circuit release further contribute to reliable protection . These protectors also satisfy the features of main switches according to IEC 60947-2 , and their standard compliance ensures they meet various protection needs and operational reliability .
Mountable accessories for SIRIUS Innovations' motor starter protectors (sizes S00 and S0) enhance functionality by allowing integration with various connection systems and applications. These accessories support direct or separate mounting options for devices like solid-state contactors and soft starters, facilitating quick and error-free installations . Front plates with a rotary operating mechanism are available to enable actuation in diverse enclosures, providing flexibility in switching needs . Furthermore, the accessories offer compatibility with 3-phase busbar systems, promoting efficient power distribution and reducing installation complexity . Additionally, the spring-loaded and screw-type connection systems included in the accessories ensure reliable connections suitable for diverse operational environments ."}
Auxiliary switches in SIRIUS 3RV2 motor starter protectors enhance functionality by mirroring the state of the main contacts, providing feedback for the system operation . There are lateral and transverse types with various configurations, including NO, NC, and CO contacts, enabling versatile signaling options . Signaling switches add functionality by providing tripped and short-circuit signals, indicating when the motor starter protector requires resetting . Constraints include the mounting limitations: only one signaling switch can be used, and it's not compatible with 3RV27 and 3RV28 circuit breakers. Additionally, mounting a lateral auxiliary switch with 4 contacts is not possible if a signaling switch is used . Moreover, a total of four auxiliary contacts can be mounted on each protector, constraining expansion options .
The SIRIUS 3RV2 motor starter protector accommodates ambient temperature conditions through temperature compensation from -20 °C to +60 °C, ensuring optimal performance without derating within this range . Additionally, it requires current reduction for ambient temperatures above +60 °C, with specific reduction factors outlined up to +80 °C to maintain reliability . This significance lies in allowing the device to function efficiently in various climates, avoiding thermal overload, and ensuring stability and protection for motors in diverse settings .
When using motor starter protectors with highly energy-efficient motors (IE3), considerations include adapting to higher locked rotor and inrush currents, which can cause premature tripping if the motor starter protector's short-circuit detection is not properly set. It is recommended to select a motor starter protector with a setting scale that does not require the device to operate at its upper limit to avoid unintentional shutdowns . The making and breaking capacity of motor starter protectors should also be considered, as IE3 motors may lead to contact welding due to current spikes during startup . Additionally, using motor starter protectors that have been optimized with raised short-circuit detection thresholds helps prevent early tripping .
The use of 3RV2 motor starter protectors in North America has significant implications for compliance and safety in electrical systems. They conform to key standards like UL 489, which is crucial for allowing them as circuit breakers in North America, ensuring safety through overload and short-circuit protection . These motor starter protectors can also be used as Branch Circuit Protection Devices (BCPD) according to UL standards (3RV27/28), which broadens their suitable applications . Additionally, they are adaptable to a range of applications including transformer protection and as main or emergency off switches, suitable even for hazardous areas . This compatibility challenges system designers to choose appropriate configurations for varying loads and ambient conditions, especially since the devices must account for specific operational parameters like temperature and altitude . Thus, the integration of 3RV2 motor starter protectors into North American systems guarantees compliance with safety standards while providing versatile protection capabilities.
The SIRIUS 3RV2 motor starter protectors achieve system protection through features like overload and short-circuit protection, as well as phase loss sensitivity, ensuring protection against overloads, short circuits, and phase failure . These protectors use an inverse-time delay thermal overload release and an instantaneous short-circuit release to assure safety during motor start-up and operation . To prevent premature tripping due to phase loss sensitivity, which can occur if there is significant phase unbalance, the motor starter protector ensures timely tripping to prevent overcurrents, thus protecting the motor and system . This sensitivity does not include models 3RV23, 3RV27, and 3RV28, which lack phase loss protection ."}
3RV23 MSPs (Motor Starter Protectors) for starter combinations function exclusively for short-circuit protection and must be used in conjunction with an overload relay and contactor to provide a complete motor protection solution. They do not feature overload protection themselves, so the overload relay disconnects the motor by tripping the contactor in an overload situation, while the MSP remains engaged until a short circuit occurs . This design ensures reliable ramping-up and motor protection by having the short-circuit release preset to a multiple of the rated current . These protectors are necessary because their integration with other devices allows for comprehensive protection against both short circuits and overloads, thus ensuring motor safety and operational integrity ."}