ANNEXURE‐B
33 KV OIL IMMERSED OUTDOOR CURRENT TRANSFORMER
TECHNICAL SPECIFICATIO RATIO : 200/1‐1‐1 A
[Link]. PARAMETER VALUE
SINGLE PHASE, OIL IMMERSED,
1
TYPE OUTDOOR, DEAD TANK CT
2 RATED VOLTAGE/HIGHEST VOLTAGE 33KV/36KV
3 RATED PRIMARY CURRENT 200A
4 SECONDARY CORE DETAILS
4.A NO. OF CORE 3
CORE‐1 CORE‐2 CORE‐3
4.B RATED SECONDARY CURRENT 1A 1A 1A
4.C RATED OUTPUT IN VA 15VA 15VA 0VA
5.D CLASS OF ACCURACY 0.5 5P PS
6.E ACCURACY LIMIT FACTOR 10
7.F ISF <=5
METHOD OF RATIO CHANGE & SECONDARY CONNECTION SECONDARY TAP CHANGING
5
DETAIL METHOD
6 SHORT TIME THERMAL CURRENT & ITS DURATION 25 KA/3 SEC
7 RATED CURRENT DYNAMIC(PEAK VALUE) 62.5 KA
120 % OF RATED PRIMARY
8 RATED CONTINUOUS THERMAL CURRENT
CURRENT
9 IMPULSE WITHSTAND TEST VOLTAGE KV(PEAK) 170 KV
ONE MINUT POWER FREQUENCY DRY/WET WITHSTAND
10 70 KV
VOLTAGE ON PRIMARY KV(RMS)
ONE MINUT POWER FREQUENCY WITHSTAND TEST VOLTAGE
11 3 KV
ON SECONDARY KV(RMS)
12 MIN. CREEPAGE DISTANCE 25 MM/KV
13 TOTAL CREEPAGE DISTANCE OF THE BUSHING MIN. 900 MM
14 MAGNETISATION CURVE OF CT CORES ENCLOSED
15 QUANTITY/WEIGHT OF OIL 35 KG
16 TOTAL WEIGHT (KG) 120 KG
17 MOUNTING DETAILS 450X450
18 OVERALL DIMENSIONS 450X450X1180
19 THE INSULATION OIL SHALL CONFIRM TO THE STANDARD IS‐335‐1983
20 CONFIRMING TO STANDARD IS‐2705 (1992)