Annexure B 33 KV Oil Immersed Outdoor Current Transformer Value

The document provides the technical specifications for a 33kV oil immersed outdoor current transformer. It has a ratio of 200/1-1-1A with 3 cores, with core 1 and 2 rated at 1A and core 3 rated at 0VA. It has a rated primary current of 200A, rated continuous thermal current of 120% of rated primary current, and can withstand a short time thermal current of 25kA for 3 seconds. The overall dimensions are 450x450x1180mm.

Uploaded by

sankalptiwari
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
0% found this document useful (0 votes)
61 views1 page

Annexure B 33 KV Oil Immersed Outdoor Current Transformer Value

The document provides the technical specifications for a 33kV oil immersed outdoor current transformer. It has a ratio of 200/1-1-1A with 3 cores, with core 1 and 2 rated at 1A and core 3 rated at 0VA. It has a rated primary current of 200A, rated continuous thermal current of 120% of rated primary current, and can withstand a short time thermal current of 25kA for 3 seconds. The overall dimensions are 450x450x1180mm.

Uploaded by

sankalptiwari
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.

ANNEXURE‐B

33 KV OIL IMMERSED OUTDOOR CURRENT TRANSFORMER
TECHNICAL SPECIFICATIO   RATIO : 200/1‐1‐1 A
[Link]. PARAMETER VALUE
SINGLE PHASE, OIL IMMERSED, 
1
TYPE OUTDOOR, DEAD TANK CT
2 RATED VOLTAGE/HIGHEST VOLTAGE 33KV/36KV
3 RATED PRIMARY CURRENT 200A
4 SECONDARY CORE DETAILS
4.A NO. OF CORE 3
CORE‐1 CORE‐2 CORE‐3
4.B RATED SECONDARY CURRENT 1A 1A 1A
4.C RATED OUTPUT IN VA 15VA 15VA 0VA
5.D CLASS OF ACCURACY 0.5 5P PS
6.E ACCURACY LIMIT FACTOR 10
7.F ISF <=5
METHOD OF RATIO CHANGE & SECONDARY CONNECTION  SECONDARY TAP CHANGING 
5
DETAIL METHOD
6 SHORT TIME THERMAL CURRENT & ITS DURATION 25 KA/3 SEC
7 RATED CURRENT DYNAMIC(PEAK VALUE) 62.5 KA
120 % OF RATED PRIMARY 
8 RATED CONTINUOUS THERMAL CURRENT
CURRENT
9 IMPULSE WITHSTAND TEST VOLTAGE KV(PEAK) 170 KV
ONE MINUT POWER FREQUENCY DRY/WET WITHSTAND 
10 70 KV
VOLTAGE ON PRIMARY KV(RMS)
ONE MINUT POWER FREQUENCY WITHSTAND TEST VOLTAGE 
11 3 KV
ON SECONDARY KV(RMS)
12 MIN. CREEPAGE  DISTANCE 25 MM/KV
13 TOTAL CREEPAGE DISTANCE OF THE BUSHING MIN. 900 MM
14 MAGNETISATION CURVE OF CT CORES ENCLOSED
15 QUANTITY/WEIGHT OF OIL 35 KG
16 TOTAL WEIGHT (KG) 120 KG
17 MOUNTING DETAILS 450X450
18 OVERALL DIMENSIONS 450X450X1180
19 THE INSULATION OIL SHALL CONFIRM TO THE  STANDARD  IS‐335‐1983
20 CONFIRMING TO STANDARD IS‐2705 (1992)