Project: CMT Date: 04-11-2020
Location: Phonm Penh, Cambodia
Subject H-PAU-F/24-05
Design Flowrate : 1200 L/s
Design ESP : 300 Pa
EXTERNAL STATIC PRESSURE DROP CALCULATION BY SECTIONS, H-PAU-F/24-05
Duct Duct Airflow Duct Size Velocity Velocity Duct Length Summary of Friction Loss Total Pressure Section Pressure
Reference
Section Element L/s W x H m/s Pressure, Pa m Fit. Loss Coef. Pa/m Loss, Pa Loss, Pa
SUPPLY AIR DUCT
Duct 1,205 550 X 350 6.3 23.6 21.5 1.065 22.90 2009 ASHRAE
1 Fitting 1,205 550 X 350 6.3 23.6 2.42 57.09 2009 ASHRAE
79.98
Duct 835 400 X 350 6.0 21.4 4.5 1.146 5.16 2009 ASHRAE
2 Fitting 835 400 X 350 6.0 21.4 0.31 6.64 2009 ASHRAE
11.80
Duct 660 450 X 300 4.9 14.4 6 0.823 4.94 2009 ASHRAE
3 Fitting 660 450 X 300 4.9 14.4 1.40 20.14 2009 ASHRAE
25.08
Duct 230 250 X 250 3.7 8.2 10 0.756 7.56 2009 ASHRAE
4 Fitting 230 250 X 250 3.7 8.2 0.49 3.99 2009 ASHRAE
11.55
Duct 150 250 X 150 4.0 9.6 2.5 1.269 3.17 2009 ASHRAE
5 Fitting 150 250 X 150 4.0 9.6 0.31 2.99 2009 ASHRAE
6.16
Duct 90 200 X 200 2.3 3.0 10 0.403 4.03 2009 ASHRAE
Fitting 90 200 X 200 2.3 3.0 0.27 0.82 2009 ASHRAE
6 Gill 90 250 X 250 7.00 2009 ASHRAE
Flexible 90 15.00 2009 ASHRAE
26.85
FRESH AIR DUCT
Louver 1,205 2300 X 2400 50.00
7
50.00
Sub-total Pressure Drop : 211
Safety Factor 15% : 32
TOTAL EXTERNAL STATIC PRESSURE DROP: 243
RECOMMENDED EXTERNAL STATIC PRESSURE :
Duct Fitting
Type of Fitting Fitting No. Parameters Loss Coefficient Reference
Section Number
1 Transition SR4-1 $R$ ș Σ 2009 ASHRAE
2 Elbow 1 CR3-15 r/W=1, H/W=0.63, ș=90º 0.25 2009 ASHRAE
3 Elbow 45 CD3-3 r/D=1.5, ș=45º 0.07 2009 ASHRAE
4 Elbow 45 CD3-3 r/D=1.5, ș=45º 0.07 2009 ASHRAE
5 Elbow 2 CR3-15 r/W=1, H/W=0.63, ș=90º 0.25 2009 ASHRAE
1
6 Elbow 3 CR3-15 r/W=1, H/W=0.63, ș=90º 0.25 2009 ASHRAE
7 Fire damper CR9-6 Co = 0.19 0.19 2009 ASHRAE
8 Elbow 4 CR3-15 r/W=1, H/W=0.63, ș=90º 0.25 2009 ASHRAE
9 Tee SR5-13 As/Ac=1, Qs/Qc=0.69 0.15 2009 ASHRAE
2.42
1 Transition ER4-3 $R$ ș Σ 2009 ASHRAE
2 2 Wye SR5-1 Ab/Ac=0.96, Qb/Qc=0.79 0.27 2009 ASHRAE
0.31
7 Fire damper CR9-6 Co = 0.19 0.19 2009 ASHRAE
2 Elbow 1 CR3-15 r/W=1, H/W=0.66, ș=90º 0.25 2009 ASHRAE
3 Elbow 45 CD3-3 r/D=1.5, ș=45º 0.07 2009 ASHRAE
3 4 Elbow 45 CD3-3 r/D=1.5, ș=45º 0.07 2009 ASHRAE
5 Tee 1 SR5-13 AsAc=1, Qs/Qc=0.69 0.15 2009 ASHRAE
6 Tee 2 SR5-13 As/Ac=1, Qs/Qc=0.5 0.67 2009 ASHRAE
1.40
1 Transition ER4-3 $R$ ș Σ 2009 ASHRAE
3 Elbow 45 CD3-3 r/D=1.5, ș=45º 0.07 2009 ASHRAE
4 4 Elbow 45 CD3-3 r/D=1.5, ș=45º 0.07 2009 ASHRAE
5 Tee SR5-13 As/Ac=1, Qs/Qc=0.65 0.31 2009 ASHRAE
0.49
1 Transition ER4-3 $R$ ș Σ 2009 ASHRAE
5 2 Tee SR5-13 As/Ac=1, Qs/Qc=0.6 0.31 2009 ASHRAE
0.31
1 Transition ER4-3 $R$ ș Σ 2009 ASHRAE
6 2 Elbow CR3-15 r/W=1, H/W=1, ș=90º 0.21 2009 ASHRAE
0.27
Note: All reference Data are from:
ASHRAE, 2009 FUNDAMENTAL, DUCT DESIGN
SMACNA, HVAC DUCT SYSTEM DESIGN
Stream Air Technical Data
Bell Duct Flexible Duct Data
Project: CMT Date: 27-10-2020
Location: Phonm Penh, Cambodia
Subject H-A-F/25-01
Design Flowrate: 4370 L/s
Design ESP: 350 Pa
EXTERNAL STATIC PRESSURE DROP CALCULATION BY SECTIONS, H-A-F/25-01
Duct Duct Airflow Duct Size Velocity Velocity Duct Length Summary of Friction Loss Total Pressure Section Pressure
Reference
Section Element L/s W x H m/s Pressure, Pa m Fit. Loss Coef. Pa/m Loss, Pa Loss, Pa
SUPPLY AIR DUCT
Duct 4,370 1200 X 500 7.3 31.9 10 0.775 7.75 2009 ASHRAE
1 Fitting 4,370 1200 X 500 7.3 31.9 1.86 59.40 2009 ASHRAE
67.15
Duct 1,940 900 X 350 6.2 22.8 6 0.847 5.08 2009 ASHRAE
2 Fitting 1,940 900 X 350 6.2 22.8 0.12 2.74 2009 ASHRAE
7.82
Duct 1,650 800 X 350 5.9 20.9 2.5 0.812 2.03 2009 ASHRAE
3 Fitting 1,650 800 X 350 5.9 20.9 0.70 14.63 2009 ASHRAE
16.66
Duct 900 500 X 350 5.1 15.9 5 0.767 3.84 2009 ASHRAE
4 Fitting 900 500 X 350 5.1 15.9 0.14 2.23 2009 ASHRAE
6.06
Duct 675 400 X 350 4.8 14.0 2.5 0.766 1.92 2009 ASHRAE
5 Fitting 675 400 X 350 4.8 14.0 0.20 2.80 2009 ASHRAE
4.71
Duct 450 400 X 250 4.5 12.2 6 0.854 5.12 2009 ASHRAE
6 Fitting 450 400 X 250 4.5 12.2 0.46 5.61 2009 ASHRAE
10.73
Duct 225 300 X 200 3.8 8.5 1.2 0.826 0.99 2009 ASHRAE
7 Fitting 225 300 X 200 3.8 8.5 0.73 6.18 2009 ASHRAE
7.17
Duct 113 250 X 200 2.3 3.0 2 0.355 0.71 2009 ASHRAE
Fitting 113 250 X 200 2.3 3.0 0.45 1.37 2009 ASHRAE
8 Flexible 113 Ø 250 5.00
Supply Grille 40.00
47.08
RETURN AIR DUCT
Duct 4,370 1200 X 500 7.3 31.9 9 0.775 6.98 2009 ASHRAE
Fitting 4,370 1200 X 500 7.3 31.9 0.29 9.26 2009 ASHRAE
9
Return Grille 4,370 90.00
106.24
Sub-total Pressure Drop: 274
Safety Factor 15% : 41
TOTAL EXTERNAL STATIC PRESSURE DROP: 315
RECOMMENDED EXTERNAL STATIC PRESSURE :
Duct Fitting
Type of Fitting Fitting No. Parameters Loss Coefficient Reference
Section Number
1 Transition SR4-1 $R$ ș Σ 0.68 2009 ASHRAE
2 Elbow 1 CR3-1 r/W=1, H/W=0.41, ș=90º 0.27 2009 ASHRAE
1 3 Elbow 2 CR3-1 r/W=1, H/W=0.41, ș=90º 0.27 2009 ASHRAE
4 Wye SR5-1 Ab/Ac=0.525, Qb/Qc=0.44 0.64 2009 ASHRAE
1 Tee 1 SR5-13 As/Ac=1, QS/Qc=0.95 0.04 2009 ASHRAE
2 Tee 2 SR5-13 As/Ac=1, QS/Qc=0.948 0.04 2009 ASHRAE
2
3 Tee 3 SR5-13 As/Ac=1, QS/Qc=0.945 0.04 2009 ASHRAE
0.12
1 Transition SR4-1 $R$ ș Σ 2009 ASHRAE
3 2 Wye SR5-1 Ab/Ac=0.53, Qb/Qc=0.45 0.64 2009 ASHRAE
0.70
1 Tee 1 SR5-13 As/Ac=1, QS/Qc=0.875 0.07 2009 ASHRAE
4 2 Tee 2 SR5-13 As/Ac=1, QS/Qc=0.85 0.07 2009 ASHRAE
0.14
1 Transition SR4-1 $R$ ș Σ 2009 ASHRAE
2 Tee 1 SR5-13 As/Ac=1, QS/Qc=0.83 0.07 2009 ASHRAE
5
3 Tee 2 SR5-13 As/Ac=1, QS/Qc=0.8 0.07 2009 ASHRAE
0.20
1 Transition SR4-1 $R$ ș Σ 2009 ASHRAE
2 Tee 1 SR5-13 As/Ac=1, QS/Qc=0.75 0.15 2009 ASHRAE
6
3 Tee 2 SR5-13 As/Ac=1, QS/Qc=0.66 0.31 2009 ASHRAE
0.46
1 Transition SR4-1 $R$ ș Σ 2009 ASHRAE
7 2 Tee SR5-13 As/Ac=1, QS/Qc=0.5 0.67 2009 ASHRAE
0.73
1 Transition SR4-1 $R$ ș Σ 2009 ASHRAE
2 Elbow CR3-1 r/W=1, H/W=0.8, ș=90º 0.21 2009 ASHRAE
8
3 Volume Damper CR9-4 C0 = 0.18 0.18 2009 ASHRAE
0.45
1 Elbow CR3-1 r/W=1, H/W=0.41, ș=90º 0.25 2009 ASHRAE
9 2 Volume Damper CR9-1 ș=0º, H/W=0.41 0.04 2009 ASHRAE
0.29
Note: All reference Data are from:
ASHRAE, 2009 FUNDAMENTAL, DUCT DESIGN
SMACNA, HVAC DUCT SYSTEM DESIGN
Stream Air Technical Data
Bell Duct Flexible Duct Data