Engineering Students' Refrigeration Study
Engineering Students' Refrigeration Study
BACHELOR OF ENGINEERING
IN
MECHANICAL ENGINEERING
By
MADIYA LOKANADHAM 314126520202
PAKKI RAVI 314126520198
VASAMSETTI SHARNU KUMAR 314126520164
YAKASIRI SUJAN KUMAR 314126520155
AGNANAM BRA
AHM*
ANITS
CERTIFICATE
This is to certify that the Project Report entitled EXPERIMENTAL
STUDY OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH
VARIOUS MASS FLOW RATES." being submitted by MADIYA
LOKANADHAM 314126520202, PAKKI RAVI 314126520198, VASAMSETTI
SHARNU KUMAR 314126520164, SUJAN KUMAR YAKASIRI 314126520155,
in partial fulfillments for the award of degree of BACHELOR OF
Y TECHNOLOG
in MECHANICAL ENGINEERING of ANDHRA UNIVERSITY. It is the work
of bona-fide, carried out under the guidance and supervision of Mr. G. Naresh,
Assistant Professor, Department Of Mechanical Engineering, ANITS during the
academie year of 2014-2018
Approved By
PROJECT GUIDE HEAD OF THE DEPARTMENT
INTERNAL EXAMINER:
kaju
Dr. B.MNaga
.Tech,M.E.,Ph.d
Professor & HOD
Engineering9
Mechanical
Dept of
ANITS.Sangivalasa.
isakhapatnam-53 1 162.
EXTERNAL EXAMINER:
ACKNOWLWDGEMENT
Nomenclature:
A surface area of tubes
C specific heat
COP coefficient of performance
h specific enthalpy
mr mass flow rate
M mass
P pressure
Q heat transfer rate
t temperature
U overall heat transfer coefficient
W power consumption of compressor
Subscripts
ac actual
b brine
c condenser
e evaporator
i inlet
isen isentropic
m mean
o outlet
r refrigerant
th theoretical
w water
ABSTRACT
A refrigerator is machine which cool and maintain a body at a temperature
below that of surrounding. Majority of refrigerator system works on vapour
compression refrigeration system.The performance of vapour compression
refrigeration system (VCRS) depends on the performance Of all its components like
compressor, condenser, expansion value and evaporator. To Improve the Coefficient
of Performance (COP), it is required to decrease the Compressor Work and increase
the Refrigerating Effect. Experimental analysis on vapour compression refrigeration
(VCR) system with R134A (Tetra Fluro Ethane) refrigerant was done and their
results were recorded.
The effects of the main parameters of performance analysis are mass flow rate of
refrigerant, suction pressure of compressor, delivery pressure of compressor,
temperature of evaporator and condenser. The results from vapour compression
refrigerant syatem was taken where the variables like suction pressure of
compressor, delivery pressure of compressor, temperature of evaporator and
condenser were noted and coefficient of performance (COP) was calculated.
The main objective of this project is to fabricate the vapour compression
refrigeration system with R-134a as refrigerant and To study the system by changing
the mass flow rate of the refrigerant for one ton of refrigeration at different
loads.This project is intended to address challenges faced in the real world and some
practical issues. Theoretical and experimental approaches used as a methodology in
this work.
LITERATURE REVIEW:
In study of applied thermo dynamics all the while we have been observing
heat transfer from a system at higher temperature to that at lower temperature. Now
in the study of refrigeration we will be observing various methods of coling the
objects and maintaining the temperatures of badies at values lower than surrounding
temperature.
According to American society of Heating, Refrigeration and Air-conditiong
engineers (ASHARE) “ Refrigeration is the science of providing and maintaining
temperature below that of the surrounding temperature”.
In the olden days around 2500 years B.c Indians, Egyptians. Etc... were
producing ice by keeping water in the porous posts open to cold atmosphere during
the night period. The evaporation of water in almost cool dry air accompanied with
recitative heat transfer in the clear night caused the formation of ice evan when the
ambient temperature was above the freezing temperature. Further reference are
available which support the use of ice in china 1000 years BC. Nero, the emperor.
Was using ice for cooling beverages further.the east Indians were able to produce
refrigeration by dissolving salt in water as early as 4th centyry A>D,. Of course , on
very small scale the use of evaporative cooling is another application of
refrigeration used olden days. The cooling of weater in earthen ports for drinking
purpose; is the most common example where the evaporation for water through the
pores of earthen pot is accompanied with cooling of water.produce refrigeration by
dissolving salt in water as early as 4th century AD,. Of course , on very small scale
the use of evaporative cooling is another application of refrigeration used olden
days. The cooling of weater in earthen ports for drinking purpose; is the most
common example where the evaporation for water through the pores of earthen pot is
accompanied with cooling of water.
M.S.Kim :
M.S.Kim have experimentally investigated the performance of a heat pump
with two azeotropic refrigerant mixtures of R290/R134a and R134a/R600a with the
mass fractions of 45%/55% and 80%/20%. The performance parameters of the
azeotropes were compared with pure R12, R134a, R290 and R22 at the both heating
and cooling conditions with suction-liquid heat exchanger. The COP of R134a/R290
was lower than that of R22 and R290, and R600a/R134a shows higher COP than
R12 and R134a. The capacity for R134a/R290a was higher than that for R290 and
R22, and R600a/R134a exhibits higher system capacity than R12 and R134a.
Experimental results show that the compressor discharge temperatures of the
considered azeotropic mixtures are lesser than those of the pure refrigerants i.e., R22
and R12.
H.M.Hughes:
H.M.Hughes have addressed the issues by blending the components of
zeotropic mixtures and subsequent packing. Assessment was carried out with the
blend of R32, R125 and R134a with the mass fraction of 23%, 25% and 52%
respectively. He focused on the issues related to blending equipment and techniques,
the number and quantity of components and the temperature of the blend. While
preparing the blends in the cylinder, introduce the individual components of the
mixture serially starting with the lowest vapour pressure component and progressing
to the highest.
2
1 INDEX
2 INTRODUCTION ........................................................................................................... 6
2.1 Introduction to refrigeration: ......................................................................... 6
2.2 Principle of Refrigeration: ............................................................................. 8
2.3 Definition of refrigeration: ............................................................................ 8
2.4 Unit of refrigeration: ..................................................................................... 8
2.5 Ton of refrigeration: ...................................................................................... 9
2.6 Coefficient of performance of refrigeration: ................................................ 9
2.7 Classification of Refrigerators:...................................................................... 9
2.7.1 Air refrigerators.............................................................................................. 10
2.8 Vapour refrigerators. ................................................................................... 10
2.8.1 Vapour compression refrigerator ................................................................... 10
2.8.2 Vapour absorption refrigerator....................................................................... 10
2.9 Methods of Refrigeration: ........................................................................... 10
2.9.1 Ice refrigeration .............................................................................................. 10
2.9.2 Dry Ice refrigeration....................................................................................... 10
2.9.3 Air expansion Refrigeration ........................................................................... 10
2.9.4 Evaporative refrigeration ............................................................................... 10
2.9.5 Gas throttling refrigeration............................................................................. 10
2.9.6 Steam jet refrigeration .................................................................................... 10
2.9.7 Liquid gas refrigeration.................................................................................. 10
2.9.8 Vapour compression refrigeration ................................................................. 10
2.9.9 Vapour absorption refrigeration. .................................................................... 10
2.10 Vapour compression refrigeration system: .................................................. 10
2.10.1 Principle : ....................................................................................................... 10
2.10.2 Pressure entyhalpy chart: ............................................................................... 11
2.10.3 Domestic Refrigerator: ................................................................................... 12
2.11 Components: ................................................................................................ 13
2.11.1 Compressor .................................................................................................... 13
2.11.2 Air-Cooled condens ....................................................................................... 13
2.11.3 Receiver ......................................................................................................... 13
2.11.4 Drier ............................................................................................................... 13
2.11.5 Evaporator ...................................................................................................... 13
3
2.11.6 Accumulator ................................................................................................... 13
2.11.7 Capillary tube. ................................................................................................ 13
2.12 Main Processes involved in the VCRS system: .......................................... 15
2.12.1 Compression : ................................................................................................ 16
2.12.2 Condensation : ............................................................................................... 16
2.12.3 Expansion ....................................................................................................... 16
2.12.4 Evaporation .................................................................................................... 16
2.13 Brief Study of basic components of vapour compression refrigeration
system (VCRS) ....................................................................................................... 17
2.13.1 Compressor: ................................................................................................... 17
2.13.2 Condenser: ..................................................................................................... 20
2.13.3 Evaporataor: ................................................................................................... 27
2.13.4 Capillary Tube: .............................................................................................. 34
2.13.5 Solenoid Valve: .............................................................................................. 35
2.14 Refrigerants: ................................................................................................ 36
2.15 Classification of refrigerants: ...................................................................... 37
3 FABRICATION ............................................................................................................. 38
3.1 Stages of fabrication: ................................................................................... 39
3.1.1 Brazing Process:............................................................................................. 39
3.1.2 Winding of Cu Tubes: .................................................................................... 39
3.1.3 Capillary Connection: .................................................................................... 40
3.1.4 Dehydrator: .................................................................................................... 40
3.1.5 Condenser Connections: ................................................................................ 40
3.1.6 Compressor Connection: ................................................................................ 42
3.1.7 Thermal Insulation: ........................................................................................ 42
3.1.8 Thermostat: .................................................................................................... 42
3.1.9 Gas Charging: ................................................................................................ 43
3.1.10 Fabrication Of Cabinet: .................................................................................. 43
3.1.11 Lubrication: .................................................................................................... 44
4 EXPERIMENTATION .................................................................................................. 45
4.1 Experimental data: ....................................................................................... 45
4.1.1 Condenser sizes:............................................................................................. 45
4.1.2 Evaporator ...................................................................................................... 46
4.1.3 Capillary:........................................................................................................ 46
4.1.4 Pressure Gauge (0 to 300 PSI.): ..................................................................... 46
4
4.1.5 Compound Gauge. (-30 to 250 PSI.):............................................................. 46
4.1.6 ¼ control valves: ........................................................................................... 47
4.1.7 Filter: .............................................................................................................. 48
4.1.8 Guage adopters:.............................................................................................. 48
4.1.9 Thermometers: ............................................................................................... 48
4.2 Equipement details: ..................................................................................... 49
4.3 Experimental procedure: ............................................................................ 50
4.4 Experimentation Readings : ....................................................................... 51
5 CALCULATIONS ......................................................................................................... 52
6 RESULTS AND DISCUSSION .................................................................................... 56
7 CONCLUSION .............................................................................................................. 66
8 REFERANCES AND BOOKS ...................................................................................... 67
5
2 INTRODUCTION
6
mechanical refrigeration the natural phenomena was used produce and maintain a
lower temperature in a space or product. The value of ice as a preservative was
known and put to use thousands of years ago. Natural ice from lakes and rivers was
often cut during the winter and stored in saw dust insulated buildings, and can be
used as required. In the Middle East and India water was cooled by evaporating it
through porous clay pots. In favourable conditions it could be made cold enough to
form ice.
The early machines the air system was probably the most successful until the
development of vapour compression and absorption system using ammonia as
refrigerant. In 1859 Ferdinand carre devised vapour absorption system. And
ammonia –water cyclel still used in absorption type domestic refrigerators .Thomas
Midgely and his associates Henne and McNary discovered dichlorodiflluoro
methane, CCL2F2(Freon-12 which was) confirmed as super refrigerant with low –
level of toxicity and non-flammable.
The vapour compression system is the most widely used refrigeration system
in practice. This refrigeration system adopts the vapour compression cycle. This
cycle requires the addition of external work for its operation.
Basically itconsists of four processes namely:
1).Isentropic compression
2).Constant pressure heat rejection
3).Isenthalpic expansion
4).Constant pressure heat addition
Vapour compression cycle is an improved type of air refrigeration cycle in
which a suitable working substance, termed as refrigerant, is used. The refrigerant
used, does not leave the system, but is circulated throughout the system alternately
condensing and evaporating.
7
2.2 Principle of Refrigeration:
Refrigeration is defined as the production of temperature lower than those of
the surrounding and maintain the lower temperature within the boundary of a given
space. The effect has been accomplished by non cyclic processes such as the melting
of ice (o)r sublimation of solid carbon dioxide . However, refrigeration effect is
usually produced by transferring heat from a low temperature source to a high
temperature source by spending mechanical work. To produce this effect requires
certain machinery , hence, the method is called mechanical refrigeration. The
working media of such machines are called refrigerants.
2.3 Definition of refrigeration:
Refrigeration is the process of removing heat from substance or space to
reduce its temperature and transferring that heat to another substance or
Refrigeration is providing and maintaining the temperature below that of the
surrounding temperature.
2.4 Unit of refrigeration:
The capacity of a Refrigeration unit is expressed in terms of Ton. One ton of
refrigeration is equivalent to the rate of heat transferred needed to produce 1000Kg
of ice at 0 water in 24 hours.
8
Secondary refrigerants are those which are cooled first by the primary
refrigerants and then employed for cooling purposes. Indirect method of cooling is
produced by absorption of sensible heat.
1. Natural methods.
2. Artificial or mechanical methods
9
2.7.1 Air refrigerators
2.7.1.1 Reversed carnot cycle
2.7.1.2 Bell coleman cycle
2.8 Vapour refrigerators.
2.8.1 Vapour compression refrigerator
2.8.2 Vapour absorption refrigerator
2.9 Methods of Refrigeration:
The refrigeration effect may be produced by bringing the substance to be
cooled in direct or indirect contact with cooling medium such as ice. The common
methods of refrigeration are as follows.
10
Vapour Compression Cycle
p-h diagram
11
2.10.3 Domestic Refrigerator:
The domestic refrigerator works on vapour compression cycle. It is compact
and more efficient in use of electric energy. The refrigerant used in this is Freon 12.
Its main function is to provide low temperature space for the preservation of food.
The domestic Refrigerators also used in medical shops, hospitals, hotels, offices,
laboratories etc.
The domestic refrigerators capacity is the internal volume of the unit and is
expressed in litres. The various common sizes of refrigerators available are
100,165,200 and 300 litres.
12
2.11 Components:
2.11.1 Compressor
2.11.2 Air-Cooled condens
2.11.3 Receiver
2.11.4 Drier
2.11.5 Evaporator
2.11.6 Accumulator
2.11.7 Capillary tube.
13
It consists a hermetically sealed compressor fitted at the base of the cabinet.
Condenser is air cooled coil. The evaporator is placed at the top of inside cabinet.
The evaporator produce low temperature about -15C and temperature around 7 to
10C can be maintained in the refrigerating space Heavy cold air from freezer moves
down wards and becomes warm air after cooling the products. This warm air moves
upward. Thus the air movement is maintained continuously in the refrigerated space.
The freezer is a mini cold storage in which ice-cubes , ice-creams , frozen foods,
meat poultry and fish can be preserved. A thermostat is provided to control the
temperature in the freezer. Chiller tray is provided below the freezer to prevent the
accumulation of water drops in the freezer. Below the freezer, it consists adjustable
shelves to preserve fruits, vegetables, cooked foodEtc. Egg tray, dairy bins ,bottle
shelves are provided in side the door of refrigerator. It should be placed in a clean
and well ventilated area and kept on the leveled place. It is important to check the
functioning of thermostat, door switch, light etc., and a separate plug must be
provided for the refrigerator.
14
The various functions of the components of domestic refrigerator
are:
1.11.1 Compresser:
In this, rotary type compressor is used and is sealed unit. It compresses the
refrigerant gas to high pressure and temperature .
1.11.2 Evaporator:
The evaporator cools the air in its surrounding in the cabinet. The cold air
being heavier moves downwards to cool the food stuff and becomes warm. This
warm air being lighter moves upward to take the place of cold air. The convection
currents are formed in the cabinet which enable the maintain of uniform temperature.
1.9.3. Drier :
A drier is connected between the receiver and the evaporator to eliminate the
traces of moisture, if any.
1.9.4. Accumulator :
It is connected between the evaporator and compressor, which accumulates
liquid droplets of the refrigerant and prevent the compressor from any possible
damage.
1.9.5. Capillary Tube:
The throttling device is a capillary tube. In this, the pressure equalizes
through out the system during off- cycle, and hence a low starting torque motor can
be used.
1.10.1. Compression
1.10.2. Condensation
1.10.3. Expansion
1.10.4. Evaporation
15
Vapour compression refrigeration system(VCRS)
2.12.1 Compression :
The low pressure vapour refrigerant in dry state is drawn from the evaporator
during the suction stroke of the compressor. During compression stroke pressure and
temperature of the refrigerant increases.
2.12.2 Condensation :
The high pressure and high temperature vapour refrigerant enters in to the
condenser through the discharge line . Heat will be rejected in to the cooling
medium and the refrigerant change its state from vapour to liquid.
2.12.3 Expansion
After condenser, the liquid refrigerant is stored in the liquid receiver until it
passes through expansion valve. The function of the expansion is to allow the liquid
refrigerant under controlled pressure in to the low pressure path of the system.
2.12.4 Evaporation
The low pressure liquid refrigerant after expansion in the expansion device
enters the Evaporator or Refrigerated space and absorbs its heat. Due to this heat, the
refrigerant changes its state from liquid to vapour and then sucked back by the
compressor during its suction stroke . The cycle is repeated till the required
temperature gets inside the refrigerator.
16
2.13 Brief Study of basic components of vapour compression
refrigeration system (VCRS)
2.13.1 Compressor:
A compressor is that part in mechanical refrigeration system which sucks the
refrigerant vapours at low temperature and at low pressure and compresses it to a
lower volume at higher temperature and at higher pressure. Moreover , it creates the
flow of refrigerant from one place to another. A Compressor consists of an
arrangement in which an electric motor drives it. The compressor is located near the
condenser.
17
2.13.1.1 Open type Compressor:
The projected end of crank shaft is connected directly or through the belt to
the driving motor. The compressor and motor can be mounted on the same base
plate. A seal must be used to prevent refrigerant leaking out or air from leaking in if
the crank case pressure is lower than the atmospheric pressure.
These compressors are used in the plants employed for ice making, cold
storage and food processing applications
18
The main parts of a sealed unit are:
1. Electric motor,
2. Compressor,
3. Muffler,
4. Dome.
The Hermetically sealed Reciprocating compressor
Advantages:
The advantages of hermetically sealed compressor s over ordinary type
compressors as follows:
Disadvantages:
19
3. The pressure of moisture in the refrigerant may harm the winding of the
motor.
4. A separate vaccum pump is required for evacuation and charging the
refrigerant.
The motor and compressor assembly is mounted in the unit in such way that
usually the motor is fitted on the top and the compressor on the bottom. But at
present in a specially designed sealed unit,for keeping the motor cool, it is dipped in
to the oil and bottom of the compressor is fitted at the top.The oil is forced to the
compressor, through the shaft of the motor. Some times the motor and compressor
and assembly is hung on the springs in the unit and sometimes it is press fitted.
As the motor is energised, it drives the compressor. The compressor sucks
the low temperature and low pressure gas, compresses it into high temperature and
high pressure gas and discharges it through the discharge line. Some of the examples
of refrigeration machines in which sealed units
are used are:
1. Refrigerator,
2. Bottle cooler,
3. Window-type Air conditioner,
4. Water cooler.
2.13.2 Condenser:
condenser is an heat exchanger in which heat transfer takes place from high
temperature vapour refrigerant to low temperature air or water which is used as
cooling medium. Its purpose is to covert all the vapour refrigerant to liquid
refrigerant delivered by the compressor.
20
Types of Condenser:
Air is used as the cooling medium in the air cooled condenser. Heat transfer
takes place air convection around the condenser surface.
In the Natural air cooled condensers large condensing surface area is required
as the circulated air quantity is less. This type of condensers are used in domestic
refrigerator, deep freezer , etc.,
21
These are cooled by natural air or atmospheric air. These are provided at the
back of the refrigerator.
These are commonly used for water coolers, bottle coolers and air conditioners.
22
Merits of Air Cooled Condensers:
1. Cheap due to simplicity of construction
2. Low maintenance cost.
3. No piping work involved.
4. Negligible corrosion effect.
5. Disposal of air is easier in comparison to disposal of water.
6. High flexibility.
Demerits of Air Cooled Condensers:
1. It is restricted to small capacity refrigeration units.
2. Rate of heat transfer is low.
3. Distribution of air on the condenser surface area is uneven.
4. Increase in ambient temperature causes reduction in the capacity Of the
condensers.
The air cooled condensers are preferred under the following circumstances
Minimum corrosion is the major requirement. Inadequate supply of cooling water
Expensive means of water disposal.
23
condensers have the capacity ranging from 2 ton to 1000 ton. Cooling water enters
through the heads which are baffled to make one or more passes through the tubes.
Refrigerant vapour from the compressor enters shell at the top and gives its heat to
cooling water. After the completion of condensation , the liquid refrigerant flows
down and remain in the lower part of the shell. Which act as a liquid receiver.
Shell and coil type condenser are used for small tonnage low pressure units.
It consists of shell that contains a coil for circulating the water . The shell ends are
not removable and the water side of the coil may ;be cleaned with chemicals. In case
of a coil leakage the entire coil must be replaced. These are preferable where clean
water is available because its coil cannot be cleaned easily.
These can be cleaned only by circulating acids or other chemicals through
them. In this, the water enters at the bottom and flows up through coil as shown in
fig. Vapour refrigerant from the compressor enters at the top and flows down, the
shell giving its heat to cool water. Refrigerant vapour gets
condensed and liquid refrigerant is collected at the bottom of the shell which
acts also as receiver. These are used upto 50 ton capacity plants. Shell and coil type
condenser
24
2.13.2.2.3 Double tube type Condenser:
A double type condenser has the condensing water tube in side the refrigerant
tube. The refrigerant flows in the space between the tubes while water is pumped
through inner tube. Water flows in the opposite direction to the refrigerant. The
refrigerant vapour from the compressor enters at the top and flows downwards in the
clearance space between the two tubes. As result of heat transfer from refrigerant to
water, the refrigerant gets condensed. The liquid refrigerant leaves the condenser at
the bottom. The scales formed in tubes are removed by chemical treatment. Since
copper tubes cannot be used with ammonia. These are made of steel pipes for
ammonia.
Shell and coil type condenser are used for small tonnage low pressure units.
It consists of shell that contains a coil for circulating the water . The shell ends are
not removable and the water side of the coil may ;be cleaned with chemicals. In case
of a coil leakage the entire coil must be replaced. These are preferable where clean
water is available because its coil cannot be cleaned easily.
These can be cleaned only by circulating acids or other chemicals through
them. In this, the water enters at the bottom and flows up through coil as shown in
25
fig. Vapour refrigerant from the compressor enters at the top and flows down, the
shell giving its heat to cool water. Refrigerant vapour gets condensed and liquid
refrigerant is collected at the bottom of the shell which acts also as receiver. These
are used upto 50 ton capacity plants.
26
The air carries away the heat taken from refrigerant by the water vapour at
about 3 to 5% of water circulated evaporates, make up water is admitted to tank
through float operated valve. Water treatment should also be used to reduce the scale
formation in the coil. The atmospheric air enters at the bottom and drawn over the
coils by a fan. The air flowing up words through the water spray carries out the heat
from the refrigerant .
These are used where there is scarcity of water, draining facilities are in
adequate. The use of cooling tower is un economical. It is suitable for refrigerant
plants above 100 ton capacity.
Evaporative Condenser
2.13.3 Evaporataor:
The Evaporator is a device in which the heat is removed from the substance
to be cooled . It is part of the system in which the refrigerant evaporates or boils; It is
the cooling unit and some times called the cooling coil Or freezing coil or liquid
cooler .
27
Classification of Cooling Evaporator:
There are many types of evaporators used in the refrigeration and Air
conditioning systems;
They may be classified:
2.13.3.1 According to the refrigerant feed
2.13.3.1.1 Flooded evaporator
2.13.3.1.2 Dry-Expansion evaporator
2.13.3.2 According to the type of construction
2.13.3.2.1 Bare tube coil evaporator
2.13.3.2.2 Finned tube evaporator
2.13.3.2.3 Plate evaporator
2.13.3.2.4 Shell and tube evaporator
2.13.3.2.5 Shell and coil
2.13.3.2.6 Tube- In-Tube evaporator or Double tube evaporator
2.13.3.3 According to the mode of heat transfer
2.13.3.3.1 Natural convection evaporator
2.13.3.3.2 Forced convection evaporator
2.13.3.4 According operative condition
2.13.3.4.1 Frosting evaporator
2.13.3.4.2 De-Frosting evaporator.
28
Dry - Expansion Evaporation
It is used in small capacity units of below 150 tons.
29
c). Bare tube Evaporator:
Bare tube evaporators are constructed of either steel pipe or copper tubing.
Steel pipe is used for large evaporators and copper tube is used for small evaporator.
Using Freon as refrigerant these are also used with secondary refrigerant as in the
case of water chiller and ice making plants. This is shown in fig These are used
where the temperature is maintained below 0C.
30
g). Shell and Tube Evaporator:
Shell and tube evaporator consists a steel cylindrical shell fitted with a large
number of parallel tubes. These are used for chilling water or brine. These are mainly
two types
1. Flooded shell and tube type
2. Non-Flooded shell and tube type.
These are used for refrigerating units of capacity at about 100 ton.
31
Non - Flooded Shell and Tube type Evaporator
These are used upto 50 ton capacity.
32
as the refrigerant flows through the annual space between the two tubes. This
arrangement improves the heat transfer. These are used in dairy, beverages
and oil plant
Functions:
It reduces the pressure of the refrigerant coming from condenser and
temperature as per the requirement of system It regulates the flow of refrigerant as
per the loan on the evaporator. The various types of evaporators are
a. Capillary tube
b. Pressure control or automatic expansion valve
c. Thermostatic expansion valve
d. High-side float valve
e. Low-Side float valve
f. Solenoid valve
33
2.13.4 Capillary Tube:
Capillary tube is a coil or length of fine tube that has a very small orifice
usually 0.5 to 2.25 mm inside diameter and length is about 1 to 6 m. It is a constant
restrict type expansion device,
Capillary tube
because the opening through which the refrigerant flow is constant. It controls the
flow of refrigerant in to the evaporator. It is used with smaller hermitic units such as
room Air-Conditioners and its application extends up to refrigerating capacity about
10 kw. The usual form of capillary tube installed in refrigerating plant is shown in
Fig 2.20 One end of capillary tube is connected to filler at the outlet of the
condenser. The other end is connected to evaporator. The capillary tube reduces the
pressure of the refrigerant from high-side pressure to low-side pressure. Liquid
refrigerant from condenser enters in to the capillary tubes and as it flow through the
tube pressure drops due to friction.
The capillary tube replaces thermostatic expansion valve for small units such
as Domestic Refrigerator, Room Air-Conditioner and deep Freezers
34
The advantages of capillary tubes are:
Disadvantages:
The refrigerant must be free from moisture and dirt other wise it will choke
the tube and stop the flow of refrigerant . It cannot be used with high fluctuating
loads.
The solenoid valve is shut off valve that is actuated by a electromagnetic coil
when the coil is energised .An armature or plunger placed inside the coil. A stem or
pin attached to plunger open or close. When the coil energised by passing current
through it , the magnetic field attracts the plunger up into the core of the coil which
causes the opening of the valve. When the coil is deenergised due to break in the
circuit, the plunger fall of its own weight and pin closes the valve. These valves
fitted vertical and allows the fluid flow in one direction.
Solenoid Valve
35
Solenoid valve is installed in the liquid line just a head of the expansion
valve. They are used to control the condensing fluid when ever solenoid valve is
used in a system, it is essential that the strainer should be installed ahead of it to
prevent the entry of any contaminants.
2.14 Refrigerants:
The refrigerant is a heat carrying medium which during their cycle in the
refrigerant system absorb heat from a low temperature system and discard the heat so
absorbed to a higher temperature system.
The natural ice and a mixture of ice and salt were the first refrigerants. In
1834, either, ammonia, sulphur dioxide, methyl chloride and carbon dioxide came
into use as refrigerant in compression cycle refrigerant machines. Most of the early
refrigerant materials have been discarded for safety reasons or for lack of chemicals
or thermal stability. In the present days, many new refrigerant including halo-carbon
compounds are used for air conditioning and refrigeration applications.
The suitability of a refrigerant for a certain application is determined by its physical,
thermodynamic, chemical properties and by various practical factors. There is no one
refrigerant which can be used for all types of applications. If one refrigerant has
certain good advantages, it will have some disadvantages also, Hence, a refrigerant is
chosen which has greater advantages and less disadvantages.
36
9. Low cost.
10. Easy to liquefy at moderate at pressure and temperature.
11. Easy of locating leaks by odder or suitable indicator.
12. Mixes well with oil.
The refrigerant may, broadly, be classified into the following two groups:
1. Primary refrigerants and
2. Secondary refrigerants.
The refrigerant which directly take part in the refrigerant system are called primary
refrigerants whereas the refrigerants which are first cooled by primary refrigerants
and then used for cooling purpose, are known as secondary refrigerants.
The primary refrigerant are further classified into the following four groups :
1. Halo-carbon refrigerant.
2. Azeotrope refrigerants.
3. Inorganic refrigerants.
4. Hydro-carbon refrigerants.
1.11. Applications of refrigeration system:
37
3 FABRICATION
This project focuses on heat rejection in the condenser this is only possible
either by providing a fan or by extending the surfaces. The extended surfaces are
called fins. The rate of heat rejection in the condenser depends upon the number of
fins attached to the condenser. In the present domestic refrigerator copper material
fins are used.
The performance of the condenser will also help to increase COP of the
system as the sub cooling region incurred at the exit of the condenser. The
performance of the condenser is also investigated by existing and modification
condenser. In general domestic refrigerators have no fans at the condenser and hence
extended surfaces like fins play a very vital role in the rejection of heat.
38
3.1 Stages of fabrication:
Once the internal container is repaired, it is soldered at its ends. Now 5/6"
copper tubes of length 22 feet was wound a round the outer surface of the sheet
metal internal container, with equal spacing between them. These "Cu" tubes were
positioned in their place firmly and rigidly with the help of soldering at place. Now
these assembly functions as our Evaporator and these coils are called as "Evaporator
Coils."
Both the ends of the Cu tubes Viz, the top and bottom of the internal container,
where left free or unwound the upper portion of the tube was taken below along the
external surface of the container and finally taken out of the bottom of the plastic
bucket through a small boring. The other end of the coil was connected to the
39
accumulator which is placed in between the bottoms of the bucket and the container.
Ten this end was also taken out of the same boring and connected to the capillary
tubes.
One end of the capillary was brazed inside the accumulator to prevent
leakage. The total length used for the purpose was 12feet. Initially, some portion of
the capillary was wound around the 5/16' tube coming out from the lop surface of the
container. Then, this capillary is made in the from of a uniform coil and was
suspended freely. This capillary tube acts as an expansion valve.
3.1.4 Dehydrator:
The dehydrator or the filter drier is located in the fluid line at the outlet end
of the condenser. Its purpose is to filter, trap minute particles of foreign materials
and absorb any moisture which may be in the system. Fine mesh screens filter out
foreign particles and the desiccant absorbs the moisture. The one used in this
refrigerator desiccants is silica gel (silicon dioxide).
Now a small piece of copper tubes id again brazed to the free end of he filter
drier, which is then connected to the condenser. The condenser used in this unit is of
air cooled type. In this the tube is bent in the shape of U and placed in conjunction
with the fins are responsible for holding the air in their gaps that extract heat from
the hot refrigerant flowing in the tubes of the condenser.
40
The evaporator coils surrounding the internal container absorb the heat from the hot
boy inside the container and this heat is taken by the refrigerant. This refrigerant
which is ultimate passing through the condenser radiates heat to the atmosphere with
help of the condenser fins.
In our unit the condenser is fixed to the rear side of the cabinet, facing the
atmosphere air.
41
3.1.6 Compressor Connection:
The 5/16' copper tube of the evaporator oil is connected to one end the
compressor with the help of brazing. The outgoing end of the compressor is brazed
to the condenser to complete the circuit.
The compressor used in this case is reciprocating type sealed unit. The
horsepower of the compressor is 1/6 HP. Compressor is used to establish a pressure
difference and thus cause the refrigerant to flow from one part of the system to the
other. At the same time the compressor raises the refrigerants pressure above the
condensing pint.
At the temperature of the room air, so it will condense. It is this difference in
pressure between the high low sides forces liquid refrigerant through the capillary
tube an into the evaporator.
1. Thermocoal
2. Glass Wool.
In this unit glass wool is used which was stuffed between the two surfaces of
the plastic bucket and sheet-metal container. The glass wool is tightly packed by
ramming heavily so that no air gap remains between the glass wool and hence
provides maximum operating efficiency.
3.1.8 Thermostat:
42
thermostat switch immediately breaks the circuit in the relay and thus gets Tripped
Off. The thermostat switch is connected to the relay. The rely thermostat has the
bimetal strips, which is responsible for the make and break of the circuit.
When the whole of the connections has been made then gas is charged with
the help of the charging cylinder and the value is closed. The whole is now checked
for the leakage by applying soap solution to the joints formed by brazing. Now when
no leakage was there then the gas was filled. The amount of gas by weight was 15
ibs. The gas used for this was refrigerant 12 or Freon 12 (CCl2F2 – Dichloro- Difluro
– Methane).
Wooden planks used to make the table of appropriate shape and size to
accommodate the bucket in the bucket in the top tier while the other components in
the basement.
43
The top plank is cut in the from of a round hole in which 2/3nd of the bucket
can go inside with remaining portion projecting outwards. It has got one more
bottom plank supporting the compressor, the condenser and other accessories. The
compressor is rigidly with the help of 4 bolts bolted to the base. This table-like
structure is mounted on four wheel making the whole unit mobile.
3.1.11 Lubrication:
44
4 EXPERIMENTATION
The main loop of the system under study was composed of five basic
components, i.e., a compressor, an evaporator, a condenser, capillary tubes and a
liquid line filter–drier, as shown in Fig..There was used a system of a three-phase,
220 V, reciprocating compressor originally designed for R134a refrigerant. The input
power of the compressor within the system varied between 230 and 300 W. The
major ingredient of the compressor lubricant was mineral oils. A silica gel drier filter
was used to absorb the moisture. Compact forced air cooled type condenser was used
for their good heat transfer performances. Capillary tubes of different internal
diameters were used to find the optimum operating points of the system. For
minimizing the heat loss, the evaporator cabinet was well insulated by foam and
thermocaol. The refrigerant used were R134a. Some other measuring and controlling
components were used in the system, that were, an electrical switch, an,valve for
controlling mass flow rate of the refrigerant, bourdon tube type pressure gauge and
compound pressure gauge, ‘J’ type thermocouples and indicator and gas flow
control valves.
45
4.1.2 Evaporator:
Length – 8.52 m
Diameter – 5.23 mm
4.1.3 Capillary:
Length - 2.428 m
Diameter - 0.8 mm
Bourdon type pressure gauge which shows both negative pressure (Vacuum)
as well as positive pressure in the VCR system. This is used to measure pressures at
suction point of compressor.
46
The pressure gauge in the high pressure line was installed just next to the filter/drier
and just before the capillary tube. Another pressure gauge was installed in the low
pressure return line to measure the pressure of the fluid returning back to the
compressor.. A digital thermometer was used to determine the temperatures that
were to be used in the analysis of the system. The readings of the temperature and
pressure of VCR were plotted on the P-H chart and the corresponding enthalpies
were noted down and from the values of the enthalpies obtained, the parameters such
as refrigeration effect and the compressor work were determined. The carnot or ideal
COP of the system was determined by using the temperature limits of the system and
the actual COP of the VCR system was calculated by considering the ratio of the
refrigeration effect and the compressor work obtained from the PH chart. Refrigerant
used for the analysis of VCR system is R134a.
47
4.1.7 Filter:
Smart ¼ filter is placed between tyhe condenser and capillary tube. Which
is used to filter the dust particles in refrigerant.
Adopters which are used to connect the pressure gauges to the circuit.
4.1.9 Thermometers:
Which are used to measure the temperature of the refrigerant at various sections.
48
4.2 Equipement details:
49
4.3 Experimental procedure:
50
4.4 Experimentation Readings :
Repeating the experimentation using the same refrigerant R134a, by
changing the valve arrangement and load, then observed readings are tabulated as
follows:
Pressure(psi) Temperature(*c)
Si Load(lts) Time
P1 P2 P3 P4 T1 T2 T3 T4
no
1 0 20 16 170 170 16 12 59 37.3 -5
0 16 14 195 190 14 13 58 39 -5
51
5 CALCULATIONS
As shown in P-h diagram (Moeller diagram) for refrigeration cycle with four
basic processes are frequently used in the analysis of vapour compression
refrigeration cycle, process 1to 2 is compression, process 2 to 3 heat rejection in the
condenser, process 3 to 4 expansion (Throttling) and process 4 to 1 is Evaporation
i.e. heat absorbed in the evaporator. [5-6] described the performance of air
conditioner components. The performance characteristics are can be computed for
compressor work (Wc), Refrigeration Effect (QE) and Coefficient of Performance
(COP) is expressed by the ratio of amount of heat taken by the cold body to the
amount of work supplied by the compressor; this ratio is called Coefficient of
performance.
52
The Coefficient of performance (C.O.P.) is the ratio of heat extracted in the
refrigerator to work done on the refrigerator.
Model calculations:
Temperatures:
Compressor suction temperature ,T 1= 12ᵒc
Compressor Discharge Temperature ,T2 = 59ᵒc
Condensing Temperature ,T3 = 37.3ᵒc
Evaporator Temperature ,T4 = -5
53
Pressure:
Compressor Suction pressure,P1= 16 psi
Compressor Discharge Pressure ,P2= 170 psi
Condensing Pressure,P3= 170 psi
Evaporator pressure, P4= 16 psi
Formulas used:
Enthalpy at superheated condition:
H=hg+cp(Tsup-Tsat)
Enthalpy at saturated condition:
H=hg
Enthalpy at saturated liquid condition:
H=hf
From pressure enthalpy Chart for r 134a, enthalpy values at state points 1, 2,
3, 4. The state points are fixed using pressure and temperature and each point.
h 1 = 265.20 KJ/Kg
h2 = 289.92 KJ/Kg
h3 = 104.210 KJ/Kg
h4 = 104.210 KJ/Kg
2. Circulating rate to obtain one tone of Refrigeration, kg/min. mᵣ= 210/ NRE =
210/160.99=1.3044Kg/min
54
3. Heat of compression = (h2 – h1 )= (289.92 – 265.20 )= 24.71 KJ/Kg
55
6 RESULTS AND DISCUSSION
the performance parameters for all the values are calculated and tabulated as
follows:
Parameter(lts) 0 0 0 1 1 1
Compressor 12 13 14.2 12 13.3 15.1
suction
temperature,T1(°C)
Compressor 59 58 58.6 56 57 62
discharge
temperature,T2(°C)
Condensing 37.3 39 45 39.1 55.3 40
temperature,T3(°C)
Evaporator -5 -5 -5 -5 -5 -5
temperature,T4(°C)
Compressor 16 14 12 15 14 10
suction
pressure,P1(psi)
Compressor 170 190 180 170 190 180
discharge
pressure,P2(psi)
Condenser 170 195 180 170 190 180
pressure,P3(psi)
Evaporator 16 14 12 15 14 10
pressure,P4(psi)
Enthalpy,h1 (kJ/kg) 265.20 264.1 264 263.52 262.84 266.08
Enthalpy,h2 (kJ/kg) 289.92 286.27 287.12 287.07 287.46 292.31
Enthalpy,h3 (kJ/kg) 104.21 106.74 119.78 114.8 117.8 109.6
Enthalpy,h4 (kJ/kg) 104.21 106.74 119.78 114.8 117.8 109.6
56
Load(lts) 0 0 0 1 1 1
Refrigeration 160.99 157.26 144.22 148 144.2 156.48
effect(kj/kg)
Circulating rate to 1.304 1.335 1.456 1.4185 1.45 1.342
obtain one tone of
Refrigeration(mr)
(kj/min)
Heat of 24.71 23.1 23.125 23.55 25.46 26.23
compression(kj/kg)
Heat Equivalent of 32.23 30.713 33.67 33.425 37.07 35.21
work of
compression(kj/min)
Compressor power 0.5372 0.511 0.56 0.5561 0.61 0.586
per ton of
refrigeration(kw)
Compressor power 6.51 6.837 6.23 6.28 5.66 5.96
Coefficient of
performance (COP
57
Load(lts) 2 2 2 3 3 3
Compressor 14.3 15.3 30 13.4 12.4 13.78
suction
temperature,T1(°C)
Compressor 61.1 60.3 57 55 61 62
discharge
temperature,T2(°C)
Condensing 44 47.1 44.6 43.2 47.2 42.5
temperature,T3(°C)
Evaporator -5 -5 -5 -5 -5 -5
temperature,T4(°C)
Compressor 16 13 10 16 14 10
suction
pressure,P1(psi)
Compressor 175 190 180 170 190 1750
discharge
pressure,P2(psi)
Condenser 170 190 180 170 190 180
pressure,P3(psi)
Evaporator 16 13 10 16 14 10
pressure,P4(psi)
Enthalpy,h1 (kJ/kg) 261.12 266.39 264.43 260.73 261.6 267.57
Enthalpy,h2 (kJ/kg) 291.49 288.24 285.93 288.31 287.57 291.25
Enthalpy,h3 (kJ/kg) 116.38 119.58 118.64 114.48 121.5 112.98
Enthalpy,h4 (kJ/kg) 116.38 119.58 118.64 114.48 121.5 112.98
58
Parameter(lts) 2 2 2 3 3 3
Refrigeration 144.74 146.81 146.1 146 138.01 154.59
effect(kj/kg)
Circulating rate to 1.45 1.43 1.45 1.435 1.51 1.36
obtain one tone of
Refrigeration(kj/min)
59
Results:
Effect of coefficient of performance with mass flow rate of refrigerant
for one ton of refrigeration:
coefficient of performance of a Vapour compression refrigeration system
with refrigerant R-134a is slightly decreases with increase of mass flow rate per one
ton of refrigeration.the variation of coefficient of performance with mass flow rate
as shown in graph-1.
6
cop
3
1.30 1.35 1.40 1.45 1.50
mass flow rate
Graph-1
60
mass flow rate vs refrigeration effect
165
160
150
145
140
135
1.30 1.35 1.40 1.45 1.50
mass flow rate
Graph-2
Effect of compressor work with mass flow rate for one ton of refrigeration:
Compressor work of a the system is increase with mass flow rate.the
variation in compressor work for different mass flow rates is shown in geaph-3.
50
compressor work
40
30
20
Graph-3
61
Effect of refrigeration effect with pressure ratio:
Refrigeration effect of the vapour compressor refrigeration system with r-
134a as refrigerant is increase with increase of pressure ratio.the variation in
refrigeration effect with different pressure ratios is shown in graph-4.
170
refrigeration effect
160
150
140
130
120
10 11 12 13 14 15 16 17 18
pressure ratio
Graph-4
Effect of coefficient of performance with refrigeration effect:
Coefficient of performance of a refrigeration system is the ratio of
refrigeration effect to the compressor work so that if increase of refrigeration effect
then the coefficient of performance will increase. In the present work the effect of
coefficient of performance of a refrigeration system with increase of refrigeration
effect is shown in graph-5. Observed that coefficient of performance is increases
with increase of refrigeration effect.
refrigeration effect vs cop
7
cop
3
140 145 150 155 160
refrigeration effect
Graph-5
62
Effect of coefficient of performance with compressor work:
Coefficient of performance of a refrigeration system is the ratio of
refrigeration effect to the compressor work so that if increase of refrigeration effect
then the coefficient of performance will decrease. In the present work the effect of
coefficient of performance of a refrigeration system with increase of compression
work is shown in graph-6. Observed that coefficient of performance is decreases
with increase of compressor work.
6
cop
30 32 34 36 38 40 42 44 46
compressor work
Graph-6
63
load vs compressor work
50
45
compressor work
40
35
30
25
20
Graph-7
210
heatrejection in condenser
200
190
180
170
160
150
140
130
1.30 1.35 1.40 1.45 1.50
mass flow rate
Graph-8
64
Effect of compressor work with pressure ratio:
In the present work The variation of compressor work with
different pressure ratios is shown in graph-9.observed that compressor
work will increase with increase of pressure ratio.in low pressure ratio
the compressor work will be high further increasing the pressure ratio
the compressor work will decreases upto some extent if further increase
the pressure ratio then the compressor work will increases
45
compressor work
40
35
30
10 11 12 13 14 15 16 17 18
pressure ratio
Graph-9
65
7 CONCLUSION
66
8 REFERANCES AND BOOKS
[1] P.G. Lohote, Dr. K. P. Kolhe Enhancement of COP by Using Spiral and
Microchannel Condenser instead of conventional Condenser of VCR System
Volume 3, Issue 7 JETIR (ISSN-2349-5162).
[2] B Santosh Kumar Dr.A.Raji reddy C.Ramanjaneyulu N.Jaya Krishna
Experimental Investigation of Vapour Compression Re-frigaation System with
Spiral Shaped Condenser Volume 2, Is-sue 02/2015 ISSN 2349-3860
[3] Vivek Sahu, Pooja Tiwari, K. K. Jain & Abhishek Tiwari Experi-mental
Investigation of the Refrigerator Condenser By Varying the Fins Spacing of the
Condenser International Journal on Me-chanical Engineering and Robotics (IJMER)
ISSN (Print): 2321-5747, Volume-1, Issue-1, 2013
[4] Wang zhiyuan Wangliu Fu weigang Sun yuxiang (College of Vehicle & Power,
Henan University of Science and Technology, Luoyang, 471003, China)
Performance Assessment for three kind of condenser in Refrigerating System
Proceedings of the 2013 International Conference on Advanced Mechatronic Sys-
tems, Luoyang, China, September 25-27,2013
[5] Mohan M. Tayde1, Lalit B. Bhuyar2, Shashank B. Thakre3 De-sign and
Development of Mini-Scale Refrigerator American In-ternational Journal of
Research in Science, Technology, Engi-neering & Mathematics ISSN (Print): 2328-
3491, ISSN (Online): 2328-3580, ISSN (CD-ROM): 2328-3629
[6] V. W. Bhatkar V. M. Kriplani G.K .AwarI experimental perfor-mance of r134a
and r152a using microchannel condenser Jour-nal of Thermal Engineering Yildiz
Technical University Press, Istanbul, Turkey Manuscript Received April 17, 2015;
Accepted July 05, 2015 Vol. 1, Special Issue 2, No. 7, pp. 575-582, February, 2015.
[7] Bilal A. Qureshi, Syed M. Zubair The impact of fouling on the condenser of a
vapor compression refrigeration system: An ex-perimental observation interational
journal of refrigeration38 (2014)260-266
[8] Robert J. Kee a,Berkeley B. Almand a, Justin M. Blasi a, Benja-min L. Rosen a,
Marco Hartmann a,Neal P. Sullivan a, Huayang Zhu a, Anthony R. Manerbino b,
67
Sophie Menzer b, W. Grover Coors b,Jerry L. Martin The design, fabrication, and
evaluation of a ceramic counter-flow Microchannel heat exchanger Applied Thermal
Engineering31(2011)2004-2012.
[9]Yajima. (1994), The Performance Evaluation of HFC Alternative Refrigerants for
HCFC-22, IIR Joint meeting, CFCs The Day After, Padova.
[10]K. Furuhama.(1994), Performance Evaluation of Residential Air Conditioner
with HFC32/125 Mixture, The International Symposium HCFC Alternative
Refrigerants, Kobe
[11]E. Johnson. (1998), Global warming from HFC, Environ. Impact Assessment
Rev. 18 485–492.
[12]M.A. Hammad, M.A. Alsaad. (1999), The use of hydrocarbon mixtures as
refrigerants in domestic refrigerators, Applied Thermal Engineering, 19 1181–1189.
[13]Douglas J D, Braun J E, Groll E A and Tree D R. (1999), A Cost Method
Comparing Alternative Refrigerant Applied to R-22 System, International Journal of
Refrigeration, Vol. 22, pp. 107-125.
[14]B. O. Bolaji. (2010), Experimental study of R152a and R32 to replace R134a in
a domestic refrigerator, Energy 35 3793–3798.
[15]B. O. Bolaji, M. A.Akintunde and T. O. Falade. (2011), Comparative Analysis
of Performance of three Ozone- Friends HFC Refrigerants in a Vapour Compression
Refrigerator, Journal of Sustainable Energy &Environment 2 61-64.
[16]Calm J.M, Hourahan G.C. (2001), Refrigerant data summery, Engineering
Systems 18, 74–88.
Choi, D.K, Domanski P.A, Didion D.A. (1996), Evaluation of flammable
refrigerants for use inwater-to-water residential heat pump.
68