DC Power Systems
PS48120/1800 for Business-Critical Continuity
Integrative DC Power Series Introduction
-48VDC PS48120/1800 system is optimized for access, transmission, railway station,
up to 6.96kW wireless base station power application. This system offers advanced
features, DSP control technology, intelligent battery monitoring, remote
monitoring and low voltage battery disconnection. The system comes fully
equipped with integrated AC and DC distribution.
Features
Cost-effective for possible demand and future-proof, flexible and scalable
Provide up to 6.96kW Max
system that can be configured to meet current demand and future expansion.
Front access design for installation
and maintenance
DPC48-3 can be selected for 6V,12V,24V output.
Wide input voltager range from
85Vac to 300Vac
Wide working temperature of PS48120/1800
rectifier module:-40 +70 System Electrical Specifications
Work in poor electric power Nominal Input Votage 220Vac/1 phase
environment Nominal Output Votage -48Vdc
Input Votage 85V-300Vac , two-way input, switched manually (X1, X6 System)
Rectifiers adopt DSP control 125V-285Vac , two-way input, switched automatically (X2 System)
technology, wtih high power density Frequency Range 45 - 65Hz
Low voltage battery disconnection Output Power(max) 6.96kW
to protect batteries
Easily expandable with more power
or/and feature when new demand AC Distribution
Input 2 63A/2P
arise
Rectifier MCB 4 16A/1P X1,X2 System (None in X6 System)
Self-contained surge protection for Output 1 16A/1P X2 System (None in X1, X6 System)
AC,DC and signal
Hot swap of rectifier and monitoring
modules DC distribution Remark
Battery 100A 2 Fuse
Utilize CE/UL approved rectifier R48-
DC Output 7 Output 1 63A/1P 2 32A/1P 1 10A/1P MCB
1800A 1 100A NT00,1 50A NT00,1 6A NT00 FUSE
DC/DC Converter DPC48-3
Input voltage range: 43VDC-60VDC
Output voltage(Nominal): 24V,12V,6V
Output voltage range: 22-28.5V,11-14.2V,5.5-7.1V
Output power: 6V 12V 24V
DPC48-3
0W 0W 0W
30W 100W 100W
60W 200W 200W
Notes: 1. 3 output voltage can be choosed discretionarily.
2. Only one output power can be choosed for each output voltage.
Mechanical Parameters
X1, X6 System 600W 600D 2000H(mm) 110kg (excluding rectifiers and SCU)
X2 System 600W 600D 2000H(mm) 120kg (excluding rectifiers and SCU)
PS48120/1800
PS48120/1800 DC Power Systems
for Business-Critical Continuity
M500D Monitoring module
Features
Intelligent batterymanagement
Visual and audible alarms
Alarm history log
RS232/Modem, User configurable digital inputs
Hot Swapable and dry contacts
M500D Monitoring Module
R48-1800A Rectifier module
General
Safety CE, UL UL/ EN/ IEC 60950-2000
EMC EN 55022 Class B
Dimensions 87.9 85.3 272mm H W D
Weight 2.0kg
Enclosure IP 20
Input characteristics Range Unit Comments
Voltage 85 300 power decrease linearly below 176Vac Vac Single phase
Line frequency 45 65 Hz
Power Factor 0.99
R48-1800A Rectifier module
Efficiency 91 %
Output characteristics
Voltage -42 -58 Vdc
Power 1740 W 30A@-58V Rectifier output power and
Current 0 33 A input voltage relationship
Load regulation 0.5 %
Output power
Line regulation 0.1 %
Load share 0.9 A 100%
Peak to peak noise 100 mV pk-pk (0 - 20 MHz)
Psophometric weighted noise 2 mV
THD 5 %
20%
0 85 176 300 Input voltage(V)
Environment conditions
Operating temperature -40 +70 (full power to +45 )
Storage temperature - 40 + 70
Relative humidity 90% RH
Output Current and Output
Elevation 2000 m voltage relationship
Output voltage
Protection characteristics
58
Short circuit protection at constant current
48.3
Output over-voltage protection, voltage set point selectable
Input over-voltage protection, automatically recoverable
Input under-voltage protection, automatically recoverable
Over-temperature protection , > 98 protection, automatically recover 0 30 33 Output current (A)
Emerson Network Power. AC Power Embedded Computing Outside Plant Racks and Integrated Cabinets
The global leader in enabling Connectivity Embedded Power Power Switching&Controls Services
business-critical continuity. DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power Co., Ltd. Emerson Network Power and the Emerson
No. 1 Kefa Rd., Science & Industry Park Network Power logo are trademarks and
Nanshan District 518057, Shenzhen, China service marks of Emerson Electric Co.
Phone: +86-755-8601-0808
2007 Emerson Electric Co.
Fax: +86-755-8601-0909
www.emersonnetworkpower.com.cn
www.emersonpower.com.cn 2007.06