SOFT31 (DN 40, 50)
Single Orifice Float Trap with SLR / TV
Description
The Forbes Marshall Single Orifice Float Trap, SOFT31, is a 2
single orifice condensate drain trap of cast iron body and 3
stainless steel internals. 4
9 10
8
Sizes and Pipe Connections 1
DN40 and 50 Screwed BSP/BSPT/NPT 5
Flange connection: #125, PN16 7
Note: Available Non-IBR only
6
Available Types
SOFT31 with Thermostatic air Vent (TV)
SOFT31 with Steam Lock Release (SLR)
Limiting Conditions
Screwed Version # 125 Flange PN16 Flange
PMA Maximum 13 bar g at 10.1 bar g at 13 bar g at
Allowable pressure 220°C 180°C 180°C
TMA Maximum 220°C at 180°C at 180 at
Allowable temperature 13 bar g 10.1 bar g 13 bar g Material
PMO Maximum 13 bar g 10.2 bar g 13 bar g
[Link]. Part Material Standard
Operating pressure
1. Body Cast Iron IS 210 FG 260
TMO Maximum 220°C at 180°C at 180°C at
2a. Cover bolts Carbon Steel ASTMA A193 B7
Operating temperature 13 bar g 10.1 bar g 13 bar g
2b. Cover nuts Carbon Steel ASTMA A194 2H
Minimum Operating 0°C 0°C 0°C
3. Cover gasket Reinforced exfoliated graphite
Temperature
4. Cover Cast Iron IS 210 FG 260
PMX Maximum differential pressure
5. Main valve assly. Stainless Steel BS 3148 Part 2
SOFT31-4.5 4.5 bar g with erosion ANC - 2
SOFT31-10 10 bar g deflector
6. Main valve assly. Reinforced exfoliated graphite
SOFT31-13 13 bar g gasket
Cold hydraulic test pressure 26 bar g 7. Main valve assly. Stainless Steel ASTM A276
studs & nuts Type 431
Operating range 8. Ball float Stainless Steel Type 304 ASTM A240
Temperature °C
A
9. Air vent assly. Stainless Steel Type 316 ASTM A240
Steam 10. Air vent seat Stainless Steel Type 410 ASTM A240
saturation
curve gasket
C B
*11. SLR unit Stainless Steel Type 316 ASTM A276
Pressure bar g
The product must not be used in this region. *12. SLR Seal Graphite
A-B Flanged EN 1092 PN16. *13. SLR seat Stainless Steel Type CA40 ASTM A743
A-C Flanged ASME 125.
*14. SLR seat gasket Stainless Steel Type 410 ASTM A240
A
15. Deflector plate Stainless Steel Type 304 ASTM A240
F
* Not shown in the drawing
B
Dimensions (approx.) in mm (Screwed Version)
C Size A B C D E F Weight
DN40 270 127 110 244 200 274 17.5 kg
D E Withdrawal Distance DN50 300 140 125 250 205 286 22 kg
(Screwed Version) General Tol : ±3
Energy Conservation | Environment | Process Efficiency [Link]
Servicing
With suitable isolation repairs can be carried out with
C
trap on the line. Undo cover bolts and lift off the cover.
When re-assembling, make sure that all joint faces are
clean. Always use a new gasket and apply a thin
coating of jointing paste. Tighten cover bolts uniformly.
D
Open up the isolating valve.
A B
(Flanged Version)
Recommended Tightening Torques
Dimensions (approx.) in mm (Flanged Version) Part Torque (Nm)
1. TV seat 45 – 55
Size(DN) A B C D Weight
2. SLR Seat 45 - 55
DN40 ASME 125 221 323 135 123 25 kg 3. SLR Body 60 - 70
DN40 PN10/16 230 323 135 123 25 kg 4. Valve Housing (Studs) 15 - 20
DN50 ASME 125 220 319 122 108 27 kg 5. Cover Bolts 65 - 75
DN50 PN10/16 230 319 122 108 27 kg
General Tol : ±3
Spare Parts
The spare parts available are shown in the figure in a
Capacity Chart heavy outline. Parts drawn in a broken line are not
supplied as spares.
30000
Available Spares
20000
Main valve assembly with erosion deflector A
Air vent assembly B
10000 ar
g Steam lock release unit C
9000
4 .5b Sets of gasket (pack of 5 sets) D
8000
7000 50-
DN Float E
Condensate kg / h
6000
5000
rg How to Order Spares
ba
4000
- 13 ar g Always order spares using the description given in the
g rg 50 0b
ar ba DN 0 - 1
3000 0b column above, headed “Available Spares”, and stating
0 -1 4 .5 4
5 - D N rg
DN 40 ba the size and type and differential pressure of the trap.
2000 DN - 13
40 For codes refer the user manual.
DN
1000
900
800
700
600
500
Steam Lock Release Unit Air Vent Assembly
400
0.1 0.2 0.3 0.4 0.5 0.8 1 2 3 4 5 6 7 8 910 13
l
D owe
Differential pressure bar g (x 100 = kPa)
How to Order
Example: DN40 Single Orifice Float Trap, SOFT31, 13 bar g, TV,
screwed BSPT
Installation emb
ly
Ass
The arrow on the name plate must point downwards. The arrow Main
Valv
e
on the casting indicates the flow direction. Refer detailed
installation and maintenance manual for more information.
Opp 106th Milestone B-85, Phase II, Chakan Indl Area A-34/35, MIDC H Block
Bombay Poona Road Sawardari, Chakan, Tal. Khed Pimpri, Pune - 411 018. INDIA.
Kasarwadi, Pune - 411 034. INDIA Dist. Pune - 410 501. INDIA Tel : 91(0)20-27442020, 39851199
Forbes Marshall Tel : 91(0)20-27145595, 39858555 Tel : 91(0)2135-393400 Fax : 91(0)20-27442040
Krohne Marshall Fax : 91(0)20-27147413 CIN No.: U28996PN1985PTC037806
Forbes Marshall Arca Email : seg@[Link], ccmidc@[Link] [Link]
Codel International © All rights reserved. Any reproduction or distribution in part or as a whole without written permission of Forbes Marshall Pvt Ltd, its associate companies
Forbes Solar or its subsidiaries (“FM Group”) is prohibited.
Forbes Vyncke Information, designs or specifications in this document are subject to change without notice. Responsibility for suitability, selection, installation, use,
operation or maintenance of the product(s) rests solely with the purchaser and/or user. The contents of this document are presented for informational
Forbes Marshall Steam Systems purposes only. FM Group disclaims liabilities or losses that may be incurred as a consequence of the use of this information.
ITEM CODE NO.- 99-003-1050391 DOC# FMSS/0319/TIS-SOFT31(DN40,50)/R2