Mds Series
Mds Series
Service Manual
Preface…………………………………………………………………………..…………………….iv
1.0 Introduction………………………………………………………………………………………....1
1.1 Digital Scroll Compressor………………………………………………………..………..1
1.2 Operating Range…………………………………………………………………………..2
1.3 Basic Layout of MDS System…………………………………………………………….3
1.4 Maximum Connectible Indoor………………………………………………………….....3
1.5 Maximum Piping Length…………………………………………………………………..4
1.6 Refnet and Distributor……………………………………………………………………..4
1.7 EXV Box………………………………………………………………………………….…6
6.0 Troubleshooting…………………………………………………………………………………..60
6.1 Locating Error Code……………………………………………………………………...60
6.2 Error Code for Decorative Type Indoor………………………………………………...61
6.3 Indoor Error Code for Wired Controller MC301……………………………………….63
6.4 Outdoor Error Code for MDOM PCB…………………………………………………...68
6.5 Outdoor Error Code for MDS-M PCB…………………………………………………..70
6.6 Troubleshooting Flow Chart……………………………………………………………..73
7.0 Appendix………………………………………………………………………………………..…90
7.1 Compatibility Chart for Indoor and Outdoor PCB……………………………………..90
7.2 Compatibility Chart for Wired Handset MC301………………………………………..91
7.3 Pressure Sensor Voltage and Resistance Value……………………………………..92
7.4 Character Reference for 7 Segment LED……………………………………………..93
7.5 Temperature Sensor Resistance Value………………………………………………..94
7.6 Hardware Configuration for 5MDS Outdoor…………………………………………...95
7.7 R22 MDS-A Series Cooling Cycle Reference…………………………………………96
7.8 R22 MDS B Series Cooling Cycle Reference…………………………………………98
7.9 R22 MDS A Series Heating Cycle Reference………………………………………102
7.10 R22 MDS B Series Heating Cycle Reference……………………………………105
7.11 R410A MDS B Series Cooling Cycle Reference…………………………………...109
7.12 R410A MDS B Series Heating Cycle Reference………………………………...116
7.13 R22 MDS BHC Series Cooling Cycle Reference…………………………………..123
7.14 Refrigerant Circuit Diagram…………………………………………………………..127
7.15 Key Card Access Feature……….…………………………………………………..155
7.16 Error Code for Phase Protector….…………………………………………………..157
This manual provides a guideline for service personnel to perform start-up/commissioning on the MDS system.
Besides providing the details on the system wiring method, termination connection and PCB setting, this manual
also consists of information and working instruction on the Smart Commander Service Version. This service
manual contains all the information needed (such as complete list of error code with troubleshooting flow chart
for possible root cause) to do necessary repair, maintenance and troubleshooting task for the MDS air
conditioner system.
This service manual is intended for and should only be used by qualified engineers/service personnel.
Installation and maintenance are to be performed only by qualified personnel who are familiar with local
codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning: Moving machinery and electrical power hazard may cause severe personnel injury
or death. Disconnect and lock off power before servicing equipment.
Compressor Quantity
Model Refrigerant Remark
Digital Scroll Fix Scroll
MDS 030A(R) 1 - R22
MDS 040A(R) 1 - R22
MDS 050A(R) 1 - R22
MDS 060A(R) 1 - R22
MDS 070A(R) 1 - R22
MDS 080B(R) 1 1 R22
MDS 100B(R) 1 1 R22
MDS 120B(R) 1 1 R22
MDS 150B(R) 1 2 R22
MDS 180B(R) 1 2 R22
MDS 200B(R) 1 3 R22
MDS 220B(R) 1 3 R22
MDS 240B(R) 1 3 R22
MDS 260B(R) 1 4 R22 MDS 120B(R)M + MDS 150B(R)S
MDS 280B(R) 1 5 R22 MDS 150B(R)M + MDS 130B(R)S
MDS 300B(R) 1 5 R22 MDS 150B(R)M + MDS 150B(R)S
MDS 320B(R) 1 5 R22 MDS 160B(R)M + MDS 160B(R)S
5MDS 050B(R) 1 - R410A
5MDS 060B(R) 1 - R410A
5MDS 070B(R) 1 - R410A
5MDS 080B(R) 1 1 R410A
5MDS 100B(R) 1 1 R410A
5MDS 120B(R) 1 1 R410A
5MDS 140B(R) 1 2 R410A
5MDS 160B(R) 1 2 R410A
5MDS 180B(R) 1 2 R410A
5MDS 200B(R) 1 3 R410A
5MDS 220B(R) 1 3 R410A
5MDS 240B(R) 1 3 R410A
5MDS 260B(R) 1 4 R410A 5MDS 120B(R)M + 5MDS 140B(R)S
5MDS 280B(R) 1 4 R410A 5MDS 120B(R)M + 5MDS 160B(R)S
5MDS 300B(R) 1 4 R410A 5MDS 120B(R)M + 5MDS 180B(R)S
5MDS 320B(R) 1 5 R410A 5MDS 180B(R)M + 5MDS 140B(R)S
5MDS 340B(R) 1 5 R410A 5MDS 180B(R)M + 5MDS 160B(R)S
5MDS 360B(R) 1 5 R410A 5MDS 180B(R)M + 5MDS 180B(R)S
5MDS 380B(R) 1 6 R410A 5MDS 240B(R)M + 5MDS 140B(R)S
5MDS 400B(R) 1 6 R410A 5MDS 240B(R)M + 5MDS 160B(R)S
5MDS 420B(R) 1 6 R410A 5MDS 240B(R)M + 5MDS 180B(R)S
5MDS 440B(R) 1 7 R410A 5MDS 240B(R)M + 5MDS 200B(R)S
5MDS 460B(R) 1 7 R410A 5MDS 240B(R)M + 5MDS 220B(R)S
5MDS 480B(R) 1 7 R410A 5MDS 240B(R)M + 5MDS 240B(R)S
5MDS 500B(R) 1 7 R410A 5MDS 250B(R)M + 5MDS 250B(R)S
Remark: M refers to Master unit and S refers to Slave unit. This combination cannot be changed.
PWM
Valve
Digital Scroll Compressor can be easily identified by the presence of PWM valve. On the other hand, Fix Scroll
Compressors do not have any PWM valve for modulation purpose. The combination of Digital and Fix Scroll
Compressor work according to the following principle:
Total Capacity
Required
1. Digital Scroll Compressor is the leading compressor which will turn ON first.
2. With assistance of PWM valve, Digital Scroll Compressor will modulate the refrigerant flow according to
the total indoor capacity required.
3. When the total indoor capacity exceeds the maximum capacity of Digital Scroll Compressor, Fix Scroll
Compressor will turn ON.
4. When Fix Scroll Compressor is ON, Digital Scroll Compressor will continue to modulate the refrigerant
flow accordingly.
50
43°CDB
40
30
20
16°CWB
10
0°CDB
0
-10 -15°CWB
-20
Heating Cycle
MDS unit is tested under standard condition (27°C DB/19°C WB Indoor and 35°C DB/24°C WB Outdoor for
cooling, 20°C DB/15°C WB Indoor and 7°C DB/6°C WB Outdoor for Heating) and should operate within the
range stated in diagram above.
Generally, MDS system consists of outdoor unit, indoor unit, refnet or distributor and EXV box.
R-22 R-410A
Length (m) 3-5HP 6-7 HP 8-32 HP 5HP 6-7 HP 8-50 HP
Total equivalent length 100 150 350 100 150 500
Maximum length of Actual piping length 50 70 125 50 70 150
Piping longest branch Equivalent length 60 80 150 60 80 175
Maximum equivalent length from first
25 30 40 25 30 65
branch to furthest unit
Maximum height
Maximum length of between indoor units
longest branch
Distributor MDS-C1
General Circuit
Diagram 2
Note: For more detailed refrigerant circuit diagram, please refer to Appendix 7.13.
PWM Valve PWM (Pulse Width Modulation) valve is an ON/OFF valve. When signal is send from
Control outdoor PCB, the pulse voltage will react on the coil and generate a rotating magnetic field.
This will allow the rotor to drives the valve to move up or down and hence opening or
closing the valve.
EXV4 Control EXV4 governs the sub-cool circuit of MDS system. It is controlled by the readings of
temperature sensor TH9 and TH10. The difference between TH9 and TH10 is normally
about 8 to 12ºC (cooling mode). For example, when the difference between TH9 and TH10
is very low, EXV4 will increase its opening step to maintain the sub-cool circuit.
Defrost Control
Protection MDS system has several sensor and pressure switch for protection purpose:
Devices Discharge pressure protection (switch)
Suction pressure protection (sensor)
Discharge temperature protection for Digital Scroll Compressor
Compressor overload protection
Fan motor overload protection
Sensor Location
2
Indoor coil sensors’ location and naming for cooling (left) and heating (right)
The indoor unit for MDS system is slightly different with indoor unit of ordinary split system.
For MDS indoor, there are additional sensors which allow precision control over
temperature.
EXV Control
The modulation of indoor EXV is controlled by the readings of T in and Tout of the indoor unit.
Generally, the opening/modulation of indoor EXV is described by the number of steps,
where each step refers to different EXV opening size. For example, if the indoor unit
requires more cooling, the EXV steps will increase to allow more refrigerant to flow into the
indoor.
Fan Speed
Control
The table above shows the fan speed modulation when indoor fan speed is set to AUTO. It
is applicable for both cooling and heating cycle. For heating mode, readings from sensor
Tmid is used to control the fan speed.
Anti-Freeze This protection is available during cooling and dry operation. Anti-freeze protection will
Protection activates when Tmid is ≤ -2ºC for 2 minutes. When anti-freeze protection activates, all EXV
valve will close. Indoor anti-freeze will end when T mid is ≥ 15ºC. All indoor unit will resume
operation (EXV valve open) when this condition is achieved.
1 Heater
Tr
-1 Ts 0.5
When the set temperature (T s) is higher than room temperature (T r) by 0.5°C, the heater will be
turned ON.
(Ts - Tr > 0.5)
When the set temperature (Ts) is lower than room temperature (T r) by 1°C, the heater will be
turned OFF.
(Ts - Tr < -1)
2 Heater
Tr
-1 -0.5 Ts 0.5 1
Heater 1
When the set temperature (T s) is higher than room temperature (T r) by 0.5°C, the heater will be
turned ON.
(Ts - Tr > 0.5)
When the set temperature (T s) is lower than room temperature (T r) by 0.5°C, the heater will be
turned OFF.
(Ts - Tr < -0.5)
Heater 2
When the set temperature (Ts) is higher than room temperature (T r) by 1°C, the heater will be
turned ON.
(Ts - Tr > 1)
When the set temperature (Ts) is lower than room temperature (T r) by 1°C, the heater will be
turned OFF.
(Ts - Tr < -1)
Other than installer, service personnel are often required to operate the ball valve during service and
maintenance work. Ball valves operation steps are as follow:
MDOM PCB 15
1 2 3 4 5 6 7
3 16
17
29
18
30 31 28
26
19
27
25
22
24
23
20 21 8 9 10 11 12 13 14
Remark:
No No
1 PWM - Pulse Width Modulation 17 NEUTRAL
2 4WV - Four way valve 18 TRAN-H
3 DIG - Digital compressor 19 TRAN-L
4 FIX - Fix compressor 20 Orange Connector (Bpc Apc)
5 HI FAN 21 Green Connector (Bin Ain)
6 MI FAN 22 Dipswitch J1
7 LO FAN 23 L-PRESS
8 DLT - Digital compressor discharge sensor 24 H-PRESS
9 OD - Outdoor ambient sensor 25 To LIVE
10 RTN - Return air temperature sensor 26 TO NEUTRAL
11 C_BTM - Compressor bottom sensor 27 PCB VERSION
12 INLET - Inlet coil temperature sensor 28 7 Segment LED Display
13 MIDLET - Midlet coil temperature sensor 29 Dipswitch J2
14 OUTLET - Outlet coil temperature sensor 30 K2 Button
15 MDOM PCB 31 K1 Button
16 LIVE
MDOM PCB is used in all MDS-A series outdoor unit and 5MDS 50/60/70B/BR. The figure
above shows the locations for all dipswitches, buttons, electrical connections and sensor
connections.
2
15
3
3
4
14 8 9
5
7 6
10
13 12 11
Remark:
No No
1 7 Segment LED Display 14 FX1-OL - Fix compressor overload
2 Reset Button DIG-OL - Digital compressor overload
3 PCB Software Version LP - Low pressure switch
4 MDS-M PCB HP - High pressure switch
5 Ain & Bin (To indoor) N - Neutral
6 Apc & Bpc (Centralize Control) L - Live
7 Dipswitch 1 (S1) 15 Transformer Output
rd
8 Dipswitch 2 (S2) 16 TH7 - Midlet coil temperature sensor (3 )
rd
9 Dipswitch 3 (S3) TH6 - Inlet coil temperature sensor (3 )
nd
10 K1, K2, K3 & K4 Buttons TH5 - Midlet coil temperature sensor (2 )
st
11 FIX - Fix compressor TH3 - Midlet coil temperature sensor (1 )
DIG - Digital compressor 17 TH12 - Return air temperature sensor
12 LO FAN TH11 - SCC bypass sensor
HI FAN TH10 - After SCC sensor
4WV - Four way valve TH9 - Before SCC sensor
13 PWM - Pulse Width Modulation 18 TH8 - Outdoor ambient sensor
nd
TH4 - Inlet coil temperature sensor (2 )
st
TH2 - Inlet coil temperature sensor (1 )
19 TH1 - Digital compressor discharge sensor
20 LOW-U - Low pressure
21 HI-U - High pressure
MDS-M PCB is used in all (5)MDS-B/BR series outdoor unit (except 5MDS 50/60/70B/BR). The
figure above shows the locations for all dipswitches, buttons, electrical connections and sensor
connections.
Remark: When K1 button is pressed, unit is forced to run defrost cycle. When K4 button is
pressed (when unit in standby condition), all EXV valve will open. To exit these states, simply
press on the Reset button.
MC200-C
1
2
3
3 4
8
7
6
9
11
10
12 13 14 15
Remark:
No No
1 NEUTRAL 10 Fan Motor - HI FAN, MI FAN, LO FAN
2 LIVE 11 T_IN - Inlet coil temperature
3 Dipswitch 1 (SW1) T_MID - Midlet coil temperature
4 Dipswitch 4 (SW4) T_OUT - Outlet coil temperature
5 Dipswitch 2 (SW2) 12 Apc & Bpc (Centralize Control)
6 Dipswitch 3 (SW3) 13 Ain & Bin (Outdoor Communication)
7 PCB Software Version 14 T_Room - Room temperature
8 MC200-C 15 Display Board & IR Receiver
9 Swing
MC200-C PCB is only used by M(5)WMD 20/25G indoor unit. This PCB can be easily recognized by
identifying the chamfered edge on the top right corner. The figure above shows the locations for all
dipswitches, buttons, electrical connections and sensor connections.
20
11
1
21
2 12 13
3
15
3
14
4 16
5 6 7 8 9
Remark:
No No
1 Steping Motor 11 Dipswitch 3 (SW3)
2 EXV2 12 Dipswitch 4 (SW4)
3 EXV1 13 Dipswitch 1 (SW1)
4 Apc & Bpc (Centralize Control) 14 Dipswitch 2 (SW2)
5 Ain & Bin (Outdoor Communication) 15 MC201-C PCB
6 T_Room - Room temperature 16 PCB Software Version
7 T_IN - Inlet coil temperature 17 Swing
T_MID - Midlet coil temperature 18 Pump
T_OUT - Outlet coil temperature 19 Fan Motor – HI FAN, MI FAN, LO FAN
8 MC301 Wired Hanset Connector 20 LIVE
9 Display Board & IR Receiver 21 NEUTRAL
10 Reset Button
MC201-C is a common PCB for all M(5)CKD-A/C, M(5)CMD-D/E, M(5)CCD-C, MDBD and
M(5)WMD-G (except M(5)WMD20/25G) indoor unit. The figure above shows the locations for all
dipswitches, buttons, electrical connections and sensor connections.
A screen cable is recommended because the screen cable will help to filter the electrical noise along the
communication wiring and thus help to maintain stability on the communication. For the MDS system, the
communication protocol is using RS485. The wire length between first outdoor to last outdoor must not exceed
1000m, and the wire length between outdoor to last indoor also must not exceed 1000m.
As the MDS system is a single outdoor multiple indoors system, it is required to have communication wiring
between the outdoor and all indoors. The wiring is required to be connected serially (Daisy chain) inside a
conduit. Please take note that the communication wiring cannot mix inside a same conduit with power supply.
A
Outdoor Indoor 1
B
A B
A
Indoor 2
B
For outdoor model, there are two type of outdoor board (MDOM PCB and MDS-M PCB). However, the wiring
connection for both PCB is basically the same. There are two wiring connectors located on the PCB, one of it is
green color and the other is orange color. For outdoor to indoor communication, the communication wires need
to be connected to the green terminal. The labels of the terminals are Ain and Bin.
For MDOM PCB, the communication terminals are already wired from the PCB to terminal
block. Connect the wire accordingly (Ain outdoor to Ain indoor, Bin outdoor to Bin indoor) on the
green color connector on indoor PCB.
MDS-M PCB
For MDS-M PCB, the communication terminals are also wired from the PCB to terminal block.
Current models are having the label of Ain and Bin on the terminal block. However, older model
has different terminal number (as shown below). Connect the wire accordingly (A in outdoor to
Ain indoor, Bin outdoor to Bin indoor) on the green color connector on indoor PCB.
R22 Model Terminal Number for Ain Terminal Number for Bin
MDS080/100/120/150B/BR 30 31
MDS180/200/220/240B/BR 45 46
R410A Model Terminal Number for Ain Terminal Number for Bin
5MDS080/100/120/140/160/180B/BR 30 31
5MDS200/220/240B/BR 45 46
Location of jumper JP1 on indoor PCB MC200-C (left) and MC201-C (right)
When more than one outdoor is to be connected together within a system, the wiring connection is connected as
shown in the figure above. For MDS-M PCB, the jumper JP6 of the last outdoor unit within the system needs to
be shorted (refer to figure below). This is to indicate to the software that this will be the last outdoor unit.
Master Slave
For master & slave model, the communication connection is slightly different. From the master unit Ain & Bin, the
communication wiring need to connect to the salve unit Apc & Bpc before connect to the indoors. Similarly, to ease
installation, these communication terminals are already wired from the PCB to terminal block. Different model
has different terminal number.
R22 Model (Master Unit) Terminal Number for Ain Terminal Number for Bin
MDS120/130/150/160BM/BRM 30 31
R22 Model (Slave Unit) Terminal Number for Apc Terminal Number for Bpc
MDS150/160BS/BRS 32 33
R410A Model (Master Unit) Terminal Number for Ain Terminal Number for Bin
5MDS120/180BM/BRM 30 31
5MDS240/250BM/BRM 45 46
R410A Model (Slave Unit) Terminal Number for Apc Terminal Number for Bpc
5MDS140/160/180BS/BRS 32 33
5MDS200/220/240/250BS/BRS 47 48
Note: For a large system which consist of a few units of Master and Slave MDS, it is advisable to short the
jumper JP6 (on MDS-M PCB) on the first outdoor master unit and the last outdoor slave unit.
1. Transmission Source
3. Temperature Setting
Temperature setting range is from 16°C to 30°C (optional setting 20°C to 30°C).
4. Personalize Setting
Press and hold for 3s, then will blink. Press again to cycle between and ..
Set the desire setting, then leave the handset for 4s without pressing any key and it will save the setting
into the program.
Press once to activate the P1 setting, press again to cycle between P1 and P2.
Press any key to deactivate the personalize setting.
8. Operating Mode
Press the MODE button to select the type of operating mode.
For cooling only unit, the available modes are: COOL, DRY and FAN.
1. ON/OFF Operation
Press “ON/OFF” key, the unit will be ON or OFF, and “ON” or “OFF” will display on the LCD.
2. Temperature Setting
Use “▲” or “▼” keyboard to increase or decrease by 1 °C/°F, temperature range is 16-30 °C (61-86°F).
Press “FAN” for 5s to alter between °C and °F.
4. Mode Setting
Press the “MODE” button, the current mode is twinkling. Press again to change mode as follows:
When the outdoor unit is OFF:
- Heat pump: COOL→HEAT→FAN→DRY
- Cooling only: COOL→FAN→DRY
When the outdoor unit is Cooling:
COOL→FAN→DRY
When the outdoor unit is Heating:
HEAT→FAN
5. Swing Setting
Press “HEATER/SWING” key to active swing function (Only for swing unit). “SWING” will display on LCD.
7. Sleep Setting
Press “SLEEP” key, “SLEEP” will display on LCD, which means this function is active.
8. Keyboard Lock
Press “SLEEP” for 5s, the keyboard will be changed between locked and unlocked.
When it is locked, the lock icon will be shown on the LCD. At this time, only the ON/OFF key is valid.
Remark 1: When using Wired Controller MC301 on decorative indoor, existing IR receiver and LED display
on the indoor PCB has to be removed.
Remark 2: Maximum wire length between unit and wired controller is 10m.
1. Address Register
After communication wire is completely connected, press “SETUP” key for 5s. Address will be
automatically registered and a number from 60 to 0 will be shown on the display LCD.
4. ON/OFF Operation
Press “ON/OFF” key to RUN or STOP the unit operation.
For Group On/Off, press “ON/OFF” key for 5s and the unit number is twinkling, “[ ]” is displayed on LCD
panel. Then press “ON/OFF” key to turn on/off all units.
5. Mode Setting
Press the “MODE” button, the current mode is twinkling. Press again to change mode as follows:
When the outdoor unit is OFF:
- Heat pump: COOL→HEAT→FAN→DRY
- Cooling only: COOL→FAN→DRY
When the outdoor unit is Cooling:
COOL→FAN→DRY
When the outdoor unit is Heating:
HEAT→FAN
6. Temperature Setting
Use “▲” or “▼” keyboard to increase or decrease by 1 °C/°F, temperature range is 16-30 °C (61-86°F).
Press “FAN” for 5s to alter between °C and °F.
9. Sleep Setting
Press “SLEEP” key, “SLEEP” will display on LCD, which means this function is active.
Remark: Timer is set to all indoor units. Individual indoor unit’s timer is unavailable.
For Central Controller MC303, wiring work is needed between indoor units and the controller for communication
purpose. The communication wire used should comply with UL2547 or UL2791 standard (refer to Section 3.3,
page 18). Communication wire is wired from the controller to indoor units (through the orange connector, A pc and
Bpc) through daisy chain connection. One end of the screen layer should be earthed to protect the signal
transmission. Kindly refer to the figure below for the illustration of the connection:
The length of the communication wire should not exceed 1000m. The Central Controller MC303 can be used
with both MC200-C and MC-201C indoor PCB. To ensure stable communication, jumper JP2 should be shorted
for the last indoor unit within the chain connection.
4.1 Introduction
Smart Commander is the MDS software use to perform commissioning and troubleshooting of MDS system. It is
recommended that service personnel to use this software while commissioning MDS system.
Inside the commissioning kit from factory, it consists of a CD (Smart Commander Service Version), a USB
Dongle Key (Purple), a MC501 gateway with power connection, a cable connected from the gateway to serial
port and a manual.
Step 1: To set up the software, insert the CD into CD-ROM and run it. Please note that do not
Prepare the CD plug in the USB Dongle Key to the computer yet.
4
After initiated the setup file, just follow through the instruction on the prompt up screen
to install the driver. Once the driver installation is completed, the following screen will
appear. Click “finish” to complete the installation.
Step 3: Initiating the Smart Commander installation file and follow the instruction on the prompt
Install Smart up screen. Once the software installation is completed, the prompt up screen will
Commander disappear. In order to confirm whether the software is already installed or not, the user
can checked it under the program location.
Step 4: To start up the software, user will need to insert the USB Dongle Key into the
Run the program computer. This USB Dongle key is crucial as every time the Smart Commander is
executed or in operation, the software will refer to this key. Only remove this after the
Smart Commander software is closed. Take note that the same USB port must be
used when running this key.
a) Wiring connection between outdoor and gateway (length must <1000m between last outdoor and gateway)
b) Wiring connection between gateway and computer (length must <2m)
For wiring connection between outdoor and gateway, the communication cable is directly connected from
outdoor terminal to the gateway, where Apc and Bpc (from outdoor) connect to A1 and B1 (on MC501 gateway)
respectively. For certain models, the outdoor terminal will be labeled with numbers instead of Apc and Bpc. The
corresponding numbers for Apc and Bpc are as follow:
R22 Model Terminal Number for Apc Terminal Number for Bpc 4
MDS80/100/120/150/260/280/300/320B/BR 32 33
MDS180/200/220/240B/BR 47 48
R410A Model Terminal Number for Apc Terminal Number for Bpc
5MDS80/100/120/140/160/180/260/280/300/320/340/360B/BR 32 33
5MDS200/220/240/380/400/420/440/460/480/500B/BR 47 48
The wiring connection between MC501 gateway and MDS system is as follow:
MC501
Gateway First Outdoor with MDOM PCB
Apc Bpc
Earth the
screen wire
Computer with
Smart
Commander
Apc Bpc
Outdoor with
MDS-M PCB
Earth the
screen wire
Computer
with Smart
Commander
Wiring connection for MDS system with more than one outdoor unit
For wiring connection between MC501 gateway and computer, it can be done by using the cable provided to
connect the gateway to serial port of computer. If serial port is not available in the computer, a RS232 (Serial
Port) to USB converter cable can be use. This converter cable can be obtained from any IT hardware outlet.
When user purchased the RS232 to USB converter cable, it will come together with a CD which consist the
driver. Kindly install the driver accordingly. (The interface will be different base on the supplier; hence this
manual cannot give any guideline or any indication).
Wiring connection from MC501 gateway to computer through RS232 to USB converter cable
Step 2 After click on the Control Panel, a new window will prompt up. Please select System.
Step 3 Once the system icon is selected, another new screen will prompt up. Click on the
Hardware on the tab menu. Once the window show the Hardware Menu, select Device
Manager.
If the COM port is less than 10, jump to step 6 and continue setting up the Smart
Commander. If the COM port goes more than 10, kindly follow the next step to change
the COM port number.
Step 5 Right click on the USB to RS232 or Serial Port and select Properties. Next, go to Port
Settings and select Advanced.
On the next window, you may change the COM Port Number to any number lower than
10. After the changes, click OK to save the setting.
Step 7 Once the software is finished initiated, the user will need to set the COM port setting. To
do this, please go to Function(E) and select Parameter Setting.
Step 8 A new window will prompt up for parameter setting. To change the communication port,
go to I/O Port and click on the down arrow. Select the appropriate COM port number
and click OK. Base on the previous example, the USB to RS232 Serial Port is COM3.
Hence, “COM3” is selected. Please note that the communication port (COM) on each
laptop will be different.
4 Once the software is connected to the system, all available parameter of the system
(Indoor and Outdoor) will be visible.
If the MDS units are connected in a network, user can observe all parameter of outdoor unit through the outdoor
set address in the PCB. Once the outdoor is selected, the relevant outdoor unit number will be highlighted with a
darker color.
The function and usage of these parts is shown in the following pages. Other than that, the Smart Commander
(Service Version) software allows advance users to modify outdoor unit parameters. This function will be shown
in the next section, 4.7 Software Additional Function.
Item Display
Identity : Type of model: Single / Master / Slave
Mode : Operating Mode: Cooling / Heating / Defrost
Edition : The program version of the outdoor
Cout : Outdoor Capacity (Unit: HP)
Tsh_out Outdoor unit superheat (Unit: °C)
Comp1/DIG : Digital compressor output percentage (Unit: %)
Comp2/3/4/FIX : Fixed compressor status. ON / OFF
FAN1/FAN2 : Outdoor fan status. STOP / LOW / HIGH
2
HS / LS : High pressure and low pressure reading (Unit: Bar, 1bar=0.1MPa 1bar=0.98kgf/cm )
TH : Temperature sensor reading. (Unit: °C)
TH1: Compressor discharge
TH2: Outdoor #1 condenser coil inlet
TH3: Outdoor #1 condenser coil midlet
TH4: Outdoor #2 condenser coil inlet
TH5: Outdoor #2 condenser coil midlet
TH8: Outdoor ambient temperature
TH9: Outdoor coil outlet temperature
TH10: Sub-cool outlet temperature
TH11: Sub-cool suction temperature
TH12: Outdoor suction temperature
EXV1/2/3 : Electronic Expansion Valve Opening Steps. Fully close during cooling & defrost cycle. Only
operate during heating cycle
EXV4 : Sub-cool circuit Electronic Expansion Valve. Operate during cooling cycle. Fully close
during heating cycle
SV1/2 : By-pass valve. For future provision
Remark: If the model does not have the respective sensor, it will display “――” after the parameter item.
Outdoor address
Outdoor Model
This allows the user to understand the refrigerant circuit within the outdoor unit. The different colors on the
refrigerant line indicate the type of mode the outdoor unit is operating. It also shows the sensors location which
helps if the user cannot remember the function of the sensor shows in the outdoor unit monitoring chart.
Indoor Data
Type of indoor and model
Tr : Return air temperature
To : Coil outlet temperature
Tm : Coil middle temperature
Ti : Coil inlet temperature
Ts : Set temperature
EXV : Indoor EXV opening
Indoor address
Take note that only 8 indoor units can be shown in the circuit monitor page. There are three ways to scroll to
other unit if it is not shown in the screen:
Click on the Up / Down button, the indoor unit will ascend or descend accordingly.
Click on the Back Page or Next Page button, the whole set indoors will be change.
Enter the indoor address number. This will directly display the indoor the user selected to view.
4 To change the setting on the indoor, user will need to click on the Ctrl button. After the button is clicked, a new
window will prompt out.
The top part of the new prompt window displays the information of the indoor.
Outdoor No : The outdoor address this particular indoor is connected to. If there is no outdoor
address set, the default value will be 0.
Indoor No : The address set on the indoor. This is based on the PCB setting.
Name : The indoor model and capacity.
Version : The Indoor PCB software version
In the State column, the current running mode, room temperature (°C), set temperature (°C) and fan speed for
the indoor unit is displayed. These setting may be changed in the Control column.
Mode : Operating model of the indoor unit (Stop, Cooling, Heating, Dry, Fan)
Fan Speed : The operating fan speed. Available speed: High / Medium / Low / Auto
Set Temp : To set the required temperature of the indoor. (Unit: °C), range from 16 °C to 30 °C
Sleep Mode : Indoor unit to operate in sleep mode
Auxiliary Heater : To activate additional heater (if any)
Swing : Air swing. Not applicable for conceal / ducted model
Locked : To forbidden the usage of handset. Reset when the indoor power is turned off.
There are 6 function buttons at the bottom of Service Monitor screen. The function of the buttons is as follow:
First page : Proceed to the first page of the graph
Back page : Proceed to the previous page of the graph
Next page : Proceed to next page of the graph
End page : Proceed to the last page or the graph
Set Param : A new window will prompt out allowing user to determine which parameter to plot.
Major unit
Tick to select ID
parameter to be
displayed
Unit setting may be modified by clicking Modify Outdoor Unit Parameter under Circuit Monitor screen. It is
advisable not to change any data unless under the instruction from the factory side. The default value set had
been decided after numerous testing conducted by R&D and should be suitable for most condition.
A new window will prompt out when the user click on the Modify Outdoor Unit Parameter button in circuit
monitor page.
Defrost curve A, B point: It is used to define defrost area. For the defrost curve A point, the outdoor ambient
is set at 6°C. User is only allowed to change the suction temperature. The allowable range is from -2°C to -
15°C (Default value is -6°C).
Defrost curve B point: The outdoor ambient is set at -15°C. User is only allowed to change the suction
temperature. The allowable range is from -30°C to -15°C (Default value is -24°C).
Note: If the value is smaller, the defrost area (shaded area I) will become smaller. This means that it is harder for
the system to enter the defrost cycle. After the system had enter the defrost cycle, the system will terminate the
defrost cycle faster.
TH12 (°C)
(Suction) -5
A (6,-6)
-10
-15
-20 Ⅰ
B Defrost Area
(-15,-24)
TH8 (°C)
-25 (Outdoor
Ambient)
-30
-30 -20 -10 0 10 20
Defrost Area Definition
Defrost Interval Time: The interval time between defrost cycle. The smaller the value, the shorter time
between the defrost cycle. The allowable range is from 25 minutes to 90 minutes. Default value is 45 minutes.
Defrost Operation Time: The duration of the defrost cycle. The smaller the value, the short the defrost
duration. The allowable range is from 5 minutes to 15 minutes. Default value is 10 minutes.
Defrost Delay Time: This option is for future provision. Currently is not available.
Sub-cool Circuit Parameter: The next parameter is TscA1, TscA2, TscT1, TscT2, TscT3 which located inside
a same box. These 5 setting is use to change the sub-cool circuit, which is only available in the MDS-B series 4
outdoor ((5)MDS 80-500 B/BR).
The main mechanism controlling the sub-cool circuit is the EXV 4. TscA1 & TscA2 is the reference temperature
for TH9, which is the refrigerant temperature before sub-cool circuit. TscT1, TscT2 & TscT3 is the Sub-cool target
temperature the system needs to achieve. The actual sub-cool temperature will be based on TH9-TH10.
TscA1 TscA2
TscT1 TscT2 TscT3 Target for Sub-cool temp
3 deg C 8 deg C 12 deg C
As the coil leaving temperature increase, the system will increase the sub-cool temperature
for better performance and long piping application.
Superheat degree: This is the parameter for controlling outdoor superheat (EXV 1). This option is only
applicable for heatpump model and EXV 1 is only used during heating cycle. The EXV 1 will open to achieve
the target set here. Default value will be 5°C for R22 and 3°C for R410A model.
EXV1, EXV2, EXV3 and EXV4: This is to manually control the opening of the EXV. It is only applicable for
MDS-B series outdoor ((5)MDS 80-500 B/BR). EXV1/2/3 is only use during heating cycle. It remains shut
during cooling or defrosts cycle. These EXV will not be available in cooling only model. EXV 4 is only use
during cooling cycle and remains shut during heating cycle.
Connection Param 2: Refers to compensation for long piping application. Default setting is 10 (Setting range
from 10 to 50). It is used to increase capacity of outdoor during low load condition (only a few indoors are
4
turned ON). For example, when it is set to 15, indoor capacity will be multiply by 1.5 times. When the piping is
long, the outdoor will increase the output capacity to match the losses along the piping to ensure the indoor
received the sufficient capacity.
Connection Param 3: Compensation for heating cycle. Default value is 37ºC. If indoor coil middle
temperature is too low, outdoor will increase capacity to achieve the set value.
Beside the Modify Outdoor Unit Parameter, there is another button called Special Order. Once the button is
selected, a new window will prompt.
Manual defrost special operation control order: Only applicable for heatpump model and can be activated
during heating cycle. Once the button is selected, the outdoor will automatically go into defrost cycle. The
duration for the defrost cycle will be 10 minutes.
Open valve control order when testing: Useful during commissioning. Once this button is selected, all EXV
will fully open (480 steps). This function is only valid for MDS-B series ((5)MDS 80-500 B/BR). To resume
normal operation, just press on the reset button located on the MDS-M PCB.
In order to commission MDS, there are some necessary steps to follow. These steps help to streamline the
possible problem that may occur during commissioning. The flow chart below provides a general guide line for
commissioning MDS system. This is useful whether for first timer as reference or experience technicians /
engineers as check list.
Piping Ensure both liquid and gas pipe are insulated according to the specification stated below. For hot
Routing and wet environment, it is recommended to increase the insulation thickness. If there is special
request due to customer requirement or country regulation, please follow the specification stated.
Pipe Specifications
Diameter (mm) 6.25 to 25.4 28.58 to 41.3
At least At least
Thickness
10mm 12mm
Heat insulation At least 100ºC
EXV Box Ensure that the orientation of the EXV box is in vertical condition.
Report from After using the Selection Software to choose the appropriate model and piping layout,
Selection Software user is allowed to generate the information into a report. From the report itself, the
proposed additional amount of refrigerant required are stated in the report.
Manual calculation To use this method, the user is required to get the whole piping schematic diagram.
After that, user will need to know the exact pipe length and their respective diameter.
Then, user will need to sum up the piping length used on the liquid pipe only base on
different diameter. Once the piping length of different diameter is obtained, apply the
length into the formula below to calculate additional refrigerant required.
Example
= (Piping Length for 15.88mm X Additional Charge Amount)
+ (Piping Length for 12.7mm X Additional Charge Amount)
+ (Piping Length for 9.52mm X Additional Charge Amount)
+ (Piping Length for 6.35mm X Additional Charge Amount)
Caution that, the additional charge amount of different pipe diameter varies base on
type of refrigerant.
The dipswitch location is different for indoor PCB MC200-C and MC201-C (Please refer to page 16 and 17).
Even though there are two types of indoor PCB, the dipswitch function is the same. For MDS indoor, there are 4
types of setting need to be determined:
a) Indoor Type
b) Indoor Capacity
c) Indoor Address
d) Indoor Function
Dipswitch 1 ON (1)
5 (SW1) S1
OFF (0)
1 2 3 4 5 6
Auxiliary Heater
Reserved
1&2 Water Pump
Dipswitch 1 (SW1) is to determine the special function of the indoor unit. There are 2 main
special functions that can be specified in MDS indoor unit. The first function is the heater
function. This heater option is only applicable for ducted model (using wired controller) and it will
function during heating cycle or fan mode.
Locating the dipswitch S1.1 and S1.2 to ON position will give the PCB ability to control the heater
relay. The PCB is allowed to connect to 2 heaters. If only 1 heater is available, just locate S1.1
to ON position. If 2 heaters are used, both S1.1 and S1.2 need to be located to ON position.
The control algorithm of the heaters is shown in page 12.
For dipswitch S1.3 (Water Pump), it will be set to ON position for all ceiling cassette unit. The
drain pump will operate when the indoor unit is turned ON. The water pump will stop operation if
the water level sensor is in OPEN condition.
For dipswitch S1.4 until S1.6, currently is reserve for future used.
Address
Dipswitch 2 is for address setting. Each indoor unit within the same outdoor unit must have
different address. The table below shows the indoor address setting.
S2.1 S2.2 S2.3 S2.4 S2.5 S2.6 Indoor Address S2.1 S2.2 S2.3 S2.4 S2.5 S2.6 Indoor Address
0 0 0 0 0 0 0 0 1 1 0 0 0 24
0 0 0 0 0 1 1 0 1 1 0 0 1 25
0 0 0 0 1 0 2 0 1 1 0 1 0 26
0 0 0 0 1 1 3 0 1 1 0 1 1 27
0 0 0 1 0 0 4 0 1 1 1 0 0 28
0 0 0 1 0 1 5 0 1 1 1 0 1 29
0 0 0 1 1 0 6 0 1 1 1 1 0 30
0 0 0 1 1 1 7 0 1 1 1 1 1 31
0 0 1 0 0 0 8 1 0 0 0 0 0 32
0 0 1 0 0 1 9 1 0 0 0 0 1 33
5
0 0 1 0 1 0 10 1 0 0 0 1 0 34
0 0 1 0 1 1 11 1 0 0 0 1 1 35
0 0 1 1 0 0 12 1 0 0 1 0 0 36
0 0 1 1 0 1 13 1 0 0 1 0 1 37
0 0 1 1 1 0 14 1 0 0 1 1 0 38
0 0 1 1 1 1 15 1 0 0 1 1 1 39
0 1 0 0 0 0 16 1 0 1 0 0 0 40
0 1 0 0 0 1 17 1 0 1 0 0 1 41
0 1 0 0 1 0 18 1 0 1 0 1 0 42
0 1 0 0 1 1 19 1 0 1 0 1 1 43
0 1 0 1 0 0 20 1 0 1 1 0 0 44
0 1 0 1 0 1 21 1 0 1 1 0 1 45
0 1 0 1 1 0 22 1 0 1 1 1 0 46
0 1 0 1 1 1 23 1 0 1 1 1 1 47
While setting the indoor address, there are a few rules need to follow. The rules are as follow:
a) Each indoor address must be unique and it must not duplicate within a system.
b) The first indoor address must be 0. Do not start the first indoor with address 1.
c) While setting the indoor address, the indoor address number cannot skip. For example, if
there are only 4 indoors in a system, the indoor address needs to be 0, 1, 2 and 3.
d) It is advisable that the indoor address follows the sequence of the communication wiring.
For example, for a 4 indoors in the system, the first indoor after the outdoor should have
address 0, the next indoor address should be 1 and the last indoor of the communication
wiring should be 3.
Example:
(1) ON
A Address: 0
Outdoor Indoor 1
B
A B (0) OFF
S2.1 S2.6
(1) ON
A Address: 1
Indoor 2
B
(0) OFF
S2.1 S2.6
(1) ON
A Address: 2
Indoor 3
B
(0) OFF
S2.1 S2.6
(1) ON
A Address: 3
Indoor 4
B
(0) OFF
S2.1 S2.6
Capacity Model
Dipswitch 3 is for model and capacity setting. It is advisable that the commissioner to check all
the indoors during every commissioning. The tables below show the respective setting for indoor
type and indoor capacity.
Example:
(1) ON (1) ON
MWMD015G MCKD020A/C
(0) OFF (0) OFF
S3.1 S3.8 S3.1 S3.8
(1) ON (1) ON
MCCD050C MCMD028E
(0) OFF (0) OFF
S3.1 S3.8 S3.1 S3.8
Dipswitch 4 Dipswitch 4 is reserved for software upgrade purpose. This dipswitch shall remain OFF all the
(SW4) time.
OFF
Remark: While changing the setting, please make sure the power supply of the indoor is
switch off. This dipswitch setting is not applicable for Central Controller MC303.
Auto-Random To enable auto random restart function on indoor unit using wireless handset, the process
Restart for will be slightly complicated. The indoor power supply must be available.
Wireless
Controller To enable Auto Random Restart, the steps are as follow:
1. Press the indoor PCB emergency ON/OFF button for 5 seconds to go into setting
mode. When the unit are in setting mode, all the LED of the indoor will be light up.
2. Use the wireless handset, select “Fan” mode.
3. Select “High Fan” speed.
4. Press the “ON/OFF” button on the wireless handset to complete the setting. Once
the setting is complete, all the indoor LED will be turned off and the unit will remain
in standby mode.
Remark: After entering the setting mode (all indoor LED is ON), if there is no operating for
60 seconds, it will automatically exit from setting mode
ON (1)
J1 S1
OFF (0)
1 2 3 4 5 6 7
MDS A Capacity
EXV Initial
Opening
Reserved
For dipswitch 1 (J1), the main function is to determine the outdoor capacity. Dipswitch J1.1 and
J1.2 (EXV Initial Opening) is only use by R&D for testing purpose. During site commissioning, it
is advisable not to alter the setting unless advice by factory side. Dipswitch J1.3 is reserved for
future used. Dipswitch J1.4 to J1.7 is to determine the outdoor unit capacity.
For dipswitch 2, there are 2 main functions. The first will be the type of model (J2.6) and the
second will be the outdoor address setting (J2.1 to J2.5). Dipswitch J2.7 is for refrigerant type
and J2.8 is reserved for future provision.
For dipswitches J2.6, model selection, it will determine whether the model is a cooling only
model or a heatpump model. The reason of the needs of this selection is because the PCB is
common for both cooling only model and heatpump model. To select a cooling only model, 5
position dipswitch J2.6 to ON position and for heatpump model, position it to OFF position.
If the outdoor is not connected to the central control monitoring software (Smart Commander)
or the Central Wired Controller (MC303), there is no need to set the address (address remain
as 0). If the outdoor is connected with these accessories, then the same rules on the indoor
setting apply here. The rules are as follow:
a) Each outdoor number must be unique. The outdoor address cannot duplicate.
b) The first outdoor address must be 0. Do not start the first outdoor with address 1.
c) While setting the outdoor address, the outdoor address number cannot skip. For
example, if there are only 4 outdoors in a system, the outdoor address needs to be 0,
1, 2 and 3.
d) It is advisable that the outdoor address follow the sequence of the communication
wiring. For example, for a 4 outdoors in the system, the first outdoor after the MC501
gateway should have address 0, the next outdoor address should be 1 and the last
outdoor of the communication wiring should be 3.
Remark: Please read first before you try on the PCB. If K1 or K2 is not press after 5 seconds, it
will exit from the setting mode automatically.
Set up ON (1)
Dipswitch 1 S1
OFF (0)
(S1)
1 2 3 4 5 6 7 8
For dipswitch 1, there are 3 functions. S1.1 is to determine whether the PCB is use in the MDS- 5
A series or a MDS-B series. S1.2 is to determineS1.1whether the modelMODEL
is a cooling only model or
0 MDS-B
heatpump model. Dipswitch S1.3-S1.8 are used to determine the quantity Series
of indoors connected
to the outdoor. 1 MDS-A Series
S1.3 S1.4 S1.5 S1.6 S1.7 S1.8 Indoor Quantity S1.3 S1.4 S1.5 S1.6 S1.7 S1.8 Indoor Quantity
S1.2 MODEL
0 0 0 0 0 0 1 0 1 1 0 0 0 25
0 00 0 0 0 Heatpump
1 2 0 1 1 0 0 1 26
0 01 0 0 1 Cooling
0 only 3 0 1 1 0 1 0 27
0 0 0 0 1 1 4 0 1 1 0 1 1 28
0 0 0 1 0 0 5 0 1 1 1 0 0 29
0 0 0 1 0 1 6 0 1 1 1 0 1 30
0 0 0 1 1 0 7 0 1 1 1 1 0 31
0 0 0 1 1 1 8 0 1 1 1 1 1 32
0 0 1 0 0 0 9 1 0 0 0 0 0 33
0 0 1 0 0 1 10 1 0 0 0 0 1 34
0 0 1 0 1 0 11 1 0 0 0 1 0 35
0 0 1 0 1 1 12 1 0 0 0 1 1 36
0 0 1 1 0 0 13 1 0 0 1 0 0 37
0 0 1 1 0 1 14 1 0 0 1 0 1 38
0 0 1 1 1 0 15 1 0 0 1 1 0 39
0 0 1 1 1 1 16 1 0 0 1 1 1 40
0 1 0 0 0 0 17 1 0 1 0 0 0 41
0 1 0 0 0 1 18 1 0 1 0 0 1 42
0 1 0 0 1 0 19 1 0 1 0 1 0 43
0 1 0 0 1 1 20 1 0 1 0 1 1 44
0 1 0 1 0 0 21 1 0 1 1 0 0 45
0 1 0 1 0 1 22 1 0 1 1 0 1 46
0 1 0 1 1 0 23 1 0 1 1 1 0 47
0 1 0 1 1 1 24 1 0 1 1 1 1 48
Outdoor address
Outdoor Capacity
Reserved
Master / Slave
For Dipswitch 2, the main function is to set the outdoor address if the outdoor is connected in a
network of outdoors or Central Wired Controller (MC303). Dipswitch S2.1 is to determine
whether the outdoor is a single unit, master unit or salve unit. Dipswitch S2.3 is related to
Dipswitch S3 which is used to determine the capacity of the outdoor. This will be cover in
dipswitch S3.
S2.1 Type of Model
5
0 Slave Module
1 Single/Master Module
If the outdoor is not connected to the central control monitoring software (Smart Commander) or
the Central Wired Controller (MC303), there is no need to set the address. If the outdoor is
connected with these accessories, then the same rules on the indoor setting is applied here
also. The rules are as follow:
a) Each outdoor number must be unique. The outdoor address cannot duplicate.
b) The first outdoor address must be 0. Do not start the first outdoor with address 1.
c) While setting the outdoor address, the outdoor address number cannot skip. For
example, if there are only 4 outdoors in a system, the outdoor address needs to be 0, 1,
2 and 3.
d) It is advisable that the outdoor address follow the sequence of the communication
wiring. For example, for a 4 outdoors in the system, the first outdoor after the gateway
should have address 0, the next outdoor address should be 1 and the last outdoor of the
communication wiring should be 3.
S2.4 S2.5 S2.6 S2.7 S2.8 Outdoor Address S2.4 S2.5 S2.6 S2.7 S2.8 Outdoor Address
0 0 0 0 0 0 1 0 0 0 0 16
0 0 0 0 1 1 1 0 0 0 1 17
0 0 0 1 0 2 1 0 0 1 0 18
0 0 0 1 1 3 1 0 0 1 1 19
0 0 1 0 0 4 1 0 1 0 0 20
0 0 1 0 1 5 1 0 1 0 1 21
0 0 1 1 0 6 1 0 1 1 0 22
0 0 1 1 1 7 1 0 1 1 1 23
0 1 0 0 0 8 1 1 0 0 0 24
0 1 0 0 1 9 1 1 0 0 1 25
0 1 0 1 0 10 1 1 0 1 0 26
0 1 0 1 1 11 1 1 0 1 1 27
0 1 1 0 0 12 1 1 1 0 0 28
0 1 1 0 1 13 1 1 1 0 1 29
0 1 1 1 0 14 1 1 1 1 0 30
0 1 1 1 1 15 1 1 1 1 1 31
For Dipswitch S3, the main function is to determine the MDS-B series outdoor capacity. Besides
this dipswitch, dipswitch S2.3 is also interrelated. The setting of the capacity is as follow:
After the outdoor unit setting has completed, we may power up the outdoor unit to see if the wiring connection is
correct. If the commissioning software (Smart Commander) is available, it is advisable to use it to run the
commissioning. Connect the outdoor unit to the commissioning software accordingly (refer to Section 4.4) and
run it. Go to drop down menu Function (E) and select Initiating to connect to the MDS system. Once the
software is connected to the system, all available parameter of the system (Indoor and Outdoor) will be visible.
By using the software, check whether all indoor and outdoor units are connected. Besides that, the capacity and
model of all indoor and outdoor units are verified. If there’s any problem such as communication error and etc,
kindly recheck the wiring of the communication cable and the setting of PCB. Error code will be recorded and
shown in the software itself.
During this time, we need to check and observe the system to ensure it is running normally without any error.
The 7 segment LED display located on the outdoor PCB will display related information such as running
parameters and error code (if any). The running parameters and error code shown for MDOM PCB and MDS-M
PCB are different. The running parameters for each of the PCB are shown below, while for error code, it will be
discussed further in the next Chapter 6.0.
MDOM PCB
Running Parameter
Outdoor Information / Reading
X--- YYYY
0 Compressor Discharge Temp
1 Ambient Temp
2 Compressor Suction Temp
3 Compressor Bottom Temp.
4 Condensing Coil Inlet Temp.
5 5 Condensing Coil Medium Temp.
6 Condensing Coil Outlet Temp.
7 EXV Opening Position
8 Modulation Percentage
9 PCB Control Time
For MDOM PCB, the readings of each information will continuously being displayed on
the 7 segment LED display, from 0 to 9. For example, if we need to check the ambient
temperature reading (number 1), wait for the display to show 1 and the following value
will be the sensor’s reading on ambient temperature.
MDS-M PCB
Running Parameter
For MDS-M PCB, the reading of sensors will not shown continuously like MDOM PCB.
On the other hand, it will display the current status or running mode of the outdoor unit.
For example, when the unit is on standby, it will display “NULL” on the 7 segment LED
display. When the outdoor unit is running cooling mode, “COOL” will be displayed.
Outdoor checking Check the compressor status (ON/OFF and its running capacity) as it should react
according to the system’s need.
Check the high side (HS) and low side (LS) pressure to ensure they do not exceed the
designed limit.
Check the readings of discharge temperature sensor (TH1) and ensure it do not
exceed the designed limit.
Check the opening of EXV4 and subcool temperature (TH9 – TH10) for cooling mode.
Check is there any error code from the outdoor unit.
5
Indoor checking Check the handset’s functionality for each indoor such as setting swing mode and see
whether or not the indoor unit is responding towards the handset’s signal.
Check the readings of indoor temperature sensor (T i, Tm, To and Tr) and ensure they
are normal.
Check the opening of the EXV box and ensure it is functioning normally.
Check is there any error code from the indoor unit.
These data will serve as a guide on the possible operating condition of the unit. Once the outdoor parameter
reach or close to the proposed data, the charging of the refrigerant can be stop. The commissioning personnel
will need to continue to monitor the outdoor parameter for some time (1/2 to 1 hour). If the outdoor parameters
remain constant or very small movement, the commissioning can be concluded.
For details, kindly refer to the following Appendix for the required model.
Appendix 7.7 - R22 MDS A Series Cooling Cycle Reference
Appendix 7.8 - R22 MDS B Series Cooling Cycle Reference
Appendix 7.9 - R22 MDS A Series Heating Cycle Reference
Appendix 7.10 - R22 MDS B Series Heating Cycle Reference
Appendix 7.11 - R410A MDS B Series Cooling Cycle Reference
Appendix 7.12 - R410A MDS B Series Heating Cycle Reference
Appendix 7.13 - R22 MDS BHC Series Cooling Cycle Reference
Blinking
LED
Error
code
Remark: For error code of phase protector (only applicable to 3 phase model), kindly refer to Appendix 7.16.
Possible causes
Indoor and outdoor communication wire broken
Indoor and outdoor communication wire loose
Indoor and outdoor communication wire A and B reversed
Communication wire too long, should less than 1000m
Outdoor PCB not power on
Indoor and outdoor jumper not correct, still on update status
Last indoor unit terminal resistance of communication wire not short-circuit
Indoor and outdoor PCB program not compatible
Indoor and outdoor PCB abnormal
6
Description Indoor sensor error
Possible causes
Water level switch broken
Indoor pump broken
Possible causes
Digital compressor’s operating current too high, overload protector on
Fixed compressor’s operating current too high, overload protector on
Possible causes
High pressure malfunction occur 3 times within 1 hour
Low pressure malfunction occur 3 times within 1 hour
Too high discharge temperature occur once
Compressor overload protector shut and occur 3 times
Description Others
Possible causes
Examine outdoor unit for error code.
Connect wired controller to the unit to retrieve exact error code.
E1 TH1 open/short circuit Outdoor discharge temperature sensor TH1 broken or loose 73
(discharge T.)
E2 TH2 open/short circuit Outdoor 1# condenser inlet coil temperature sensor TH2 broken or loose
(1# inlet coil)
E3 TH3 open/short circuit Outdoor 1# condenser midlet coil temperature sensor TH3 broken or loose
(1# midlet coil)
E4 TH4 open/short circuit Outdoor 2# condenser inlet coil temperature sensor TH4 broken or loose
(2# inlet coil)
E5 TH5 open/short circuit Outdoor 2# condenser midlet coil temperature sensor TH5 broken or loose
(2# midlet coil)
E8 TH8 open/short circuit Outdoor ambient temperature sensor TH8 broken or loose
(ambient T.)
E9 TH9 open/short circuit Outdoor outlet coil temperature sensor TH9 broken or loose
(outlet T.)
EA TH10 open/short circuit Outdoor sub-cool outlet temperature sensor TH10 broken or loose
(sub-cool outlet)
EB TH11 open/short circuit Outdoor sub-cool suction temperature sensor TH11 broken or loose
(sub-cool suction)
EF Emergency run On the premise that part of the indoor unit communication malfunction and either one (or 87
both) of the following error occurs (unit will shut down):
1. System sub heat <1ºC for 15 minutes
2. TH12 malfunctions
F0 Outdoor storage Outdoor PCB chip read faulty at the very beginning when power on 82
malfunction
Outdoor PCB chip broken
F1 Indoor inlet coil sensor Indoor units Tin sensor broken or loose 73
malfunction
F3 Indoor outlet coil sensor Indoor units Tout sensor broken or loose
malfunction
6 F4 Indoor return air sensor Indoor units Troom sensor broken or loose
broken
F5 Indoor supply air sensor Indoor units Troom sensor broken or loose
broken
F6 Indoor and controller Wired controller communication wire not connected or loose 83
communication
malfunction
Wired controller broken
Outdoor PCB broken
FA Wired controller storage Data read faultily at the very beginning when power on 85
broken
Chip broken
H0 Digital compressor Digital compressor operating current too high, overload protector OL4 on 77
overloaded
H1 Fixed compressor 1 Fixed compressor 1 operating current too high, overload protector OL1 on
overloaded
H2 Fixed compressor 2 Fixed compressor 2 operating current too high, overload protector OL2 on
overloaded
H3 Fixed compressor 3 Fixed compressor 3 operating current too high, overload protector OL3 on
overloaded
L3 Indoor and outdoor Outdoor work normal, but all indoor communication abnormal 76
communication
11 TH1 open/short-circuit Slave unit discharge temperature sensor TH1 broken or loose 73
(slave unit discharge)
12 TH2 open/short-circuit Slave unit 1# inlet coil temperature sensor TH2 broken or loose
(slave unit 1# inlet coil)
13 TH3 open/short-circuit Slave unit 1# midlet coil temperature sensor TH3 broken or loose
(slave unit 1# midlet
6 coil)
14 TH4 open/short-circuit Slave unit 2# inlet coil temperature sensor TH4 broken or loose
(slave unit 2# inlet coil)
15 TH5 open/short-circuit Slave unit 2# midlet coil temperature sensor TH5 broken or loose
(slave unit 2# midlet
coil)
18 TH8 open/short-circuit Slave unit ambient temperature sensor TH8 broken or loose
(slave unit ambient
temperature)
19 TH9 open/short-circuit Slave unit outlet coil temperature sensor TH9 broken or loose
(slave unit total outlet
coil)
1A TH10 open/short-circuit Slave unit sub-cooling outlet coil temperature sensor TH10 broken or loose
(slave unit sub-cooling
outlet)
1B TH11 open/short-circuit Slave unit sub-cooling suction temperature sensor TH11 broken or loose
(slave unit super
cooling suction
temperature)
1C TH12 open/short-circuit Slave unit suction temperature sensor TH12 broken or loose
(slave unit suction
temperature)
20 Outdoor storage Slave unit PCB chip data read failure by outdoor unit when power on 82
malfunction (slave unit)
Slave unit PCB chip broken
30 Digital compressor Fixed compressor 4 operating current too high, overload protector OL4 on 77
overloaded (slave unit)
31 Fixed compressor 1 Fixed compressor 1 operating current too high, overload protector OL1 on
overloaded (slave unit)
32 Fixed compressor 2 Fixed compressor 2 operating current too high, overload protector OL2 on
overloaded (slave unit)
33 Fixed compressor 3 Fixed compressor 3 operating current too high, overload protector OL3 on
overloaded (slave unit)
35 High pressure sensor Slave unit high pressure sensor connecting wire broken 74
malfunction (slave unit)
Slave unit PCB HS port broken
41 Low pressure too low Slave unit ball valve not open 78
(slave unit)
Slave unit heat exchanger efficiency too low when heating
Slave unit motor run abnormally when heating
Refrigerant leaked or insufficient charged
Slave unit PCB low pressure output port abnormal
Slave unit low pressure sensor broken
42 Low pressure sensor Slave unit low pressure sensor connecting wire broken 74
broken (slave unit)
Slave unit PCB LS port broken
CX “X” indoor no. Particular Indoor “X” and outdoor communication wire broken
indoor no
communication
Indoor “X” and outdoor communication wire loose
Indoor “X” and outdoor communication wire A B reverse
Indoor “X” and outdoor jump wire not correct, still on update status
Indoor “X” and outdoor PCB program not compatible
Indoor “X” and outdoor PCB abnormal
6
E0 Discharge temperature Outdoor discharge temperature sensor broken or loose 73
sensor malfunction
H2 Digital scroll Digital compressor operating current too high, overload protector on 77
compressor overload
H3 Fixed scroll compressor Fixed scroll compressor operating current too high, overload protector on
overload
R22 Wrong combination of PCB hardware is designed for R22 but software for R410A unit is installed into it. 88
PCB and software
R410 Wrong combination of PCB hardware is designed for R410A but software for R22 unit is installed into it. 88
PCB and software
EC00 00# - 47# indoor unit Indoor 00# - 47# and outdoor communication wire broken 76
- communication failure
EC47
Indoor 00# - 47# and outdoor communication wire loose
Indoor 00# - 47# and outdoor communication wire A B reverse
Indoor 00# - 47# and outdoor jump wire not correct, still on update status
Indoor 00# - 47# and outdoor PCB program not compatible
Indoor 00# - 47# and outdoor PCB abnormal
6 ER48 Digital compressor Digital compressor operating current too high, overload protector OL4 on 77
overload
ER49 Fixed compressor 1 Fixed compressor 1 operating current too high, overload protector OL1 on
overload
ER50 Fixed compressor 2 Fixed compressor 2 operating current too high, overload protector OL2 on
overload
ER51 Fix compressor 3 Fixed compressor 3 operating current too high, overload protector OL3 on
overload
ER54 Outdoor unit’s IC error Outdoor PCB chip read faultily at the very beginning when power on 82
Outdoor PCB chip broken
ER60 Emergency run On the premise that part of the indoor unit communication malfunction and either one (or 87
both) of the following error occurs (unit will shut down):
1. System sub heat <1ºC for 15 minutes
2. TH12 malfunctions
ER61 Super heat is beyond Indoor motor not working when cooling 86
the limit
Indoor EXV opening degree abnormal when cooling
Outdoor motor not working when heating
Outdoor EXV opening degree abnormal when heating
Low pressure sensor abnormal
Refrigerant over charged
ER64 TH1 temperature Outdoor discharge temperature sensor TH1 broken or loose 73
sensor failure
ER65 TH2 temperature Outdoor 1# condenser inlet coil temperature sensor TH2 broken or loose
sensor failure
ER66 TH3 temperature Outdoor 1# condenser midlet coil temperature sensor TH3 broken or loose
sensor failure
ER67 TH4 temperature Outdoor 2# condenser inlet coil temperature sensor TH4 broken or loose
sensor failure
6
ER68 TH5 temperature Outdoor 2# condenser midlet coil temperature sensor TH5 broken or loose
sensor failure
ER71 TH8 temperature Outdoor ambient temperature sensor TH8 broken or loose
sensor failure
ER72 TH9 temperature Outdoor outlet coil temperature sensor TH9 broken or loose
sensor failure
ER73 TH10 temperature Outdoor sub-cool outlet temperature sensor TH10 broken or loose
sensor failure
ER74 TH11 temperature Outdoor sub-cool suction temperature sensor TH11 broken or loose
sensor failure
ER75 TH12 temperature Outdoor suction temperature sensor TH12 broken or loose
sensor failure
ER76 High pressure sensor High pressure sensor communication wire broken 74
failure
Outdoor PCB HS port broken
ER77 Low pressure sensor Low pressure sensor connecting wire broken
failure
Outdoor PCB LS port broken
EC78 All indoor units Indoor and outdoor communication wire broken 76
communication failure
Indoor and outdoor communication wire loose
Indoor and outdoor communication wire A and B reversed
Communication wire too long, should less than 1000m
Outdoor PCB not power on
Indoor and outdoor jump wire not correct, still on update status
Last indoor unit terminal resistance of communication wire not short-circuit
Indoor and outdoor PCB program not compatible
Indoor and outdoor PCB abnormal
NO
Is the sensor correctly Connect correctly and operate
connected? again
YES
NO
Is the sensor resistance
Replace sensor
characteristics normal?
Refer Appendix 7.5 6
YES
Replace PCB
Remark:
OD : Outdoor
ID : Indoor
Spec : Specification
PCB : Control Module/Control Board
Is the wire connection YES Replace the wire and restart the
to pressure sensor broken? system
NO
YES
6
Is the resistance of the NO Replace the sensor and restart
pressure sensor normal? the system
Refer Appendix 7.3
YES
Replace PCB
NO
Check the water level switch. Replace the water level switch
Is it functioning normally?
YES
NO 6
NO
Is the indoor unit installed Align the indoor unit properly
properly? and restart the system
YES
NO
Is the PCB turned on? Check the power supply
YES
NO
NO
NO
NO
NO Short jumper JP1 and restart the
Is last indoor PCB
system
jumper JP1 shorted?
YES
Is the PCB dipswitch YES Reset the DIP switch and restart the
setting correct?
system
Is the Dipswitch in
update status?
NO
YES
NO
Is the overload protector Reset and restart the system
current setting correct?
Refer wiring diagram.
YES
Is the refrigerant NO
charge within spec? Recharge refrigerant accordingly
and restart the system
YES
6
Is the compressor NO
resistance normal? Replace compressor
YES
YES
YES
YES
Is the pressure port
on OD PCB abnormal? Fix the port/replace PCB
NO
NO
Is the pressure
switch functioning? Replace Pressure switch
YES
YES
YES
NO
Measure discharge / Check for any leakage. Release or
suction pressure. charge the unit with refrigerant
Within spec? according to specification
YES
Replace PCB
YES
6
NO
YES
YES
YES
Replace PCB
NO
Outdoor fan motor working? Replace outdoor fan motor
YES
YES
YES
Is the pressure NO
Replace Pressure switch
switch functioning?
YES
YES
YES
YES
YES YES
NO
6
Measure suction NO
pressure. Within Release or charge the unit with refrigerant
spec? according to specification.
YES
Replace PCB
TurnTurn on the
off the unitunit
Press the reset button. NO Restart the unit to confirm does the
Error still remains? error still persist
YES
NO
6 Replace PCB
NO
NO
6
Is the version of controller Change controller or upgrade the
NO
compatible with the indoor software for controller/indoor unit PCB.
PCB? Restart the system to verify
Refer Appendix 7.2
YES
YES
Replace PCB.
NO
6 NO
YES
Replace PCB.
YES
Replace wired
controller
YES
Is the sensor and pressure
sensor correctly connected?
YES
6
Is the sensors resistance NO
characteristics normal? Replace sensor
Refer Appendix 7.3 & 7.5
YES
NO
Is the indoor/outdoor
Replace EXV
EXV working properly?
YES
YES
Measure suction Replace PCB
pressure. Within spec?
NO
NO
YES
6
NO Recharge refrigerant
Check the refrigerant
charge. Is it within accordingly and restart the
specification? system
YES
YES
Is the sensor and pressure
sensor correctly connected?
NO
YES
Is the sensor and pressure
sensor correctly connected?
Legend:
Not compatible
Compatible
Legend:
Not compatible
Compatible
Remark: The marked wire should be connected only for R410A MDS model on outdoor MDS-M PCB.
MDS 70A
MDS 70AR
MDS 80/100/120BR
MDS 150BR
MDS 180BR
MDS 200/220/240BR
7
5MDS 50/60/70BR
5MDS 80/100/120BR
5MDS 140/160/180BR
5MDS 200/220/240BR
MDS 140BHC
7
MDS 200BHC
Kindly take note that indoor units produced from March 2012 onwards should comes with PCB version 2.7.
Kindly refer to the table below which indicates the starting batch number of indoor unit production that comes
with PCB version 2.7.
For the Junction Box, it can be purchased separately from spare part department. Alternatively, you may source
for a NC Relay locally in order to replace the usage of Junction Box. For the key card access contactor, it is to be
sourced locally according to specification required.
7
The diagram below shows the outline and dimension of the Junction Box:
Indoor PCB
KEYCARD
INTERCONNECTION
7 WIRE N1 MCB
Power Supply
L1 240V/50Hz/1Ph
240V/50Hz/1Ph
Contactor
Remark:
1. When the T_IDOUT2 connector is OPEN, the indoor unit can be operated by handset. When the T_IDOUT2
connector is CLOSED, the indoor unit will stop operates and goes into standby mode.
2. The “Key Card Access Feature” can be used for other functions such as turning off the indoor units when
window is open. The concept and wiring diagram will be similar to the diagram shown above.
3. Take note that the indoor unit will always be in standby condition (there’s power supply to the indoor PCB).
4. When the key card is inserted, the unit will not turn on directly unless Auto Restart has been set.
5. Once the key card is inserted, user can use the wired/wireless controller to control the indoor unit. When the
key card is not inserted, wired/wireless controller will not be able to control the indoor unit.
6. When key card is removed, indoor unit will stop operating (standby condition).
The following table shows the LED indicator light for phase protector under normal and fault conditions.
LED
Description PW P_R P_S P_T Actions
(Red) (Yellow) (Yellow) (Yellow)
Normal Operation ON OFF OFF OFF -
Reverse Phase BLINK BLINK BLINK BLINK
T Phase Missing BLINK OFF OFF BLINK Switch off the unit.
S Phase Missing BLINK OFF BLINK OFF Check the 3 phase wiring.
R Phase Missing BLINK BLINK OFF OFF