Sound Attenuator Performance Test Sheet
Sound Attenuator Performance Test Sheet
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : MS-25 LOCATION IN BUILDING/ON SITE : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Signal Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR-PRO Minirator 1. Temp : 10.8 ℃
2. b&k 4189 2. Speaker (300W) 2.Humidity (%) : 43.5 %
3. Microphone ASSY 3. Power Amplifier (LEEM LPX-1200)
4. Personal Computer
2. BACKGROUND NOISE
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
BG [dB] 26.8 21.6 9.4 6.6 8.0 8.8 10.2 10.8 28.3
3. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 61.5 65.6 74.6 82.8 83.9 82.2 71.5 52.5 88.1
WITH EQUIPMENT 59.5 60.4 65.4 62.2 54.8 48.4 35.3 18.2 68.7
I.L [dB] 2.0 5.1 9.2 20.5 29.1 33.8 36.2 34.3 19.4
4. FLOW GENERATION
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
CMH Pa 63 125 250 500 1K 2K 4K 8K OA
50 10 25.9 20.7 9.7 5.6 6.1 8.3 11.2 15.1 27.6
100 48 38.1 27.2 27.7 19.1 13.9 10.8 11.3 15.0 38.9
150 110 45.3 34.6 36.6 30.1 25.6 18.1 14.8 15.1 46.3
200 200 48.3 42.7 43.6 37.8 35.5 29.7 26.8 22.0 50.8
250 295 53.2 46.7 48.3 42.2 41.1 37.0 35.8 31.6 55.6
300 430 57.2 50.9 52.7 46.8 45.5 41.9 40.1 36.1 59.7
5. PRESSURE LOSS(Pa)
500
400
300
Pa
200
100
0
50 100 150 200 250 300
Air Flow (cmh)
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : MS-35(M)-CO1 LOCATION IN BUILDING/ON SITE : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Signal Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR-PRO Minirator 1. Temp : 11.8 ℃
2. b&k 4189 2. Speaker (300W) 2.Humidity (%) : 62.0 %
3. Microphone ASSY 3. Power Amplifier (LEEM LPX-1200)
4. Personal Computer
2. BACKGROUND NOISE
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
BG [dB] 30.1 38.0 25.3 14.2 11.5 10.3 10.5 11.0 38.9
3. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 68.4 71.7 81.3 87.8 87.6 85.1 76.2 58.1 92.3
WITH EQUIPMENT 69.5 66.0 63.1 58.7 55.8 47.6 37.8 17.6 72.1
I.L [dB] -1.2 5.7 18.2 29.1 31.8 37.5 38.4 40.5 20.2
4. FLOW GENERATION
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
CMH Pa 63 125 250 500 1K 2K 4K 8K OA
100 18 35.3 38.1 23.4 14.0 9.3 9.3 11.4 15.3 40.1
150 40 43.5 38.7 28.9 22.4 17.4 10.7 11.4 15.2 44.9
200 72 49.1 40.0 34.2 30.9 27.5 18.3 12.4 15.2 49.8
250 113 56.1 41.7 39.5 37.1 35.2 27.4 17.6 15.3 56.4
300 165 56.4 46.3 43.7 41.9 40.9 34.6 25.4 16.3 57.3
350 231 59.3 49.7 48.3 45.9 45.4 40.4 32.2 20.0 60.4
400 301 63.5 53.6 51.7 49.3 49.1 45.1 37.8 25.7 64.5
5. PRESSURE LOSS(Pa)
400
300
Pa
200
100
0
100 150 200 250 300 350 400
Air Flow (cmh)
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : MS-65 LOCATION IN BUILDING/ON SITE : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Signal Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR-PRO Minirator 1. Temp : 11.6 ℃
2. b&k 4189 2. Speaker (300W) 2.Humidity (%) : 53.7 %
3. Microphone ASSY 3. Power Amplifier (LEEM LPX-1200)
4. Personal Computer
2. BACKGROUND NOISE
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
BG [dB] 35.3 35.9 27.3 17.1 14.2 14.5 16.2 18.6 39.0
3. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 73.5 72.0 82.4 87.9 87.5 85.1 76.0 57.1 92.4
WITH EQUIPMENT 73.8 72.2 72.7 64.4 62.7 57.7 46.4 19.4 78.1
I.L [dB] 0.0 0.0 9.7 23.5 24.8 27.4 29.6 37.7 14.3
4. FLOW GENERATION
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
CMH Pa 63 125 250 500 1K 2K 4K 8K OA
200 19 36.3 36.8 25.2 12.0 9.1 8.6 11.3 15.1 39.7
250 25 38.1 37.7 25.7 13.2 9.2 8.5 11.3 15.1 41.1
300 34 43.2 37.4 28.1 17.7 11.1 8.6 11.5 15.2 44.3
350 44 47.2 38.1 31.6 22.1 16.2 10.0 11.7 15.2 47.8
400 58 49.9 40.1 34.6 26.9 22.0 13.8 12.2 15.2 50.5
450 73 52.6 42.7 37.6 30.2 26.3 18.4 13.2 15.2 53.1
500 89 56.2 45.0 40.6 33.2 30.2 23.3 19.0 23.0 56.7
550 108 57.2 47.9 44.2 36.0 33.5 26.9 22.0 23.1 57.9
600 128 59.4 50.4 46.5 38.1 36.0 29.6 23.2 23.3 60.2
650 151 62.3 53.5 49.3 40.3 38.7 32.4 25.6 23.5 63.1
700 173 61.8 55.0 52.0 42.1 40.8 34.9 28.4 23.9 63.1
750 198 64.5 57.1 54.3 44.0 42.6 37.0 30.6 24.5 65.6
5. PRESSURE LOSS(Pa)
250
200
150
Pa
100
50
0
200 250 300 350 400 450 500 550 600 650 700 750
Air Flow (cmh)
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : HKR-DLQ-AG LOCATION IN BUILDING/ON SITE : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Signal Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR-PRO Minirator 1. Temp : 11.4 ℃
2. b&k 4189 2. Speaker (300W) 2. Humidity (%) : 30.1 %
3. Microphone ASSY 3. Power Amplifier (LEEM LPX-1200)
4. Personal Computer
2. BACKGROUND NOISE
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
BG [dB] 41.9 38.9 28.0 12.9 10.4 9.1 10.3 10.9 43.8
3. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 74.9 75.3 84.0 89.5 88.2 84.8 76.3 58.2 93.4
WITH EQUIPMENT 74.9 81.6 81.8 76.1 79.2 77.6 66.8 49.1 87.1
I.L [dB] 0.0 0.0 2.1 13.4 9.0 7.2 9.6 9.1 6.3
4. FLOW GENERATION
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
CMH Pa 63 125 250 500 1K 2K 4K 8K OA
200 12 42.2 40.9 26.0 10.7 8.4 8.7 11.3 15.2 44.7
250 14 41.7 42.3 26.9 12.2 8.9 8.6 11.3 15.2 45.1
300 17 42.7 44.5 29.6 17.0 11.2 8.8 11.3 15.2 46.8
350 19 43.2 45.4 31.8 21.9 15.4 9.3 11.4 15.2 47.6
400 22 46.5 43.3 36.4 27.2 21.7 12.4 11.5 15.2 48.5
450 25 45.8 44.0 37.9 30.9 26.3 17.1 12.1 15.2 48.5
500 28 47.3 45.1 40.7 34.5 31.1 22.2 13.7 15.3 50.1
550 33 49.6 46.4 43.3 37.2 34.4 27.2 17.9 16.5 52.1
600 36 50.4 48.3 45.6 39.8 37.6 31.6 22.9 19.5 53.6
650 40 52.3 50.0 47.7 41.9 40.3 34.7 26.3 24.0 55.5
700 45 53.1 50.8 48.9 43.8 42.2 37.6 29.5 26.8 56.5
750 49 54.9 51.5 50.6 45.3 44.3 39.6 31.5 28.9 58.0
800 58 55.6 52.9 52.6 47.6 46.8 42.2 34.4 33.0 59.4
850 62 56.7 54.5 54.0 49.1 48.5 44.4 37.0 35.2 60.8
900 66 57.3 55.2 55.2 50.5 49.9 46.0 38.3 36.8 61.7
80
60
Pa
40
20
0
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900
Air Flow (cmh)
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : RS-25 LOCATION IN BUILDING/ON SITE : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Signal Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR-PRO Minirator 1. Temp : 10.3 ℃
2. b&k 4189 2. Speaker (300W) 2.Humidity (%) : 32.5 %
3. Microphone ASSY 3. Power Amplifier (LEEM LPX-1200)
4. Personal Computer
2. BACKGROUND NOISE
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
BG [dB] 38.4 36.4 26.7 11.1 8.4 8.8 10.2 10.8 40.7
3. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 59.9 65.7 74.5 82.9 83.6 81.6 71.1 52.6 87.9
WITH EQUIPMENT 61.0 60.2 63.8 58.8 51.9 43.7 35.0 17.4 67.5
I.L [dB] -1.1 5.6 10.8 24.1 31.8 38.0 36.1 35.2 20.4
4. FLOW GENERATION
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
CMH Pa 63 125 250 500 1K 2K 4K 8K OA
50 20 40.9 25.5 20.4 6.7 6.1 8.3 11.2 15.0 41.1
100 52 42.4 28.4 25.4 15.5 9.7 8.5 11.2 15.1 42.7
150 114 45.6 34.6 32.4 26.0 21.4 16.2 12.4 15.1 46.2
200 181 47.8 39.8 37.5 31.5 27.4 24.9 19.2 15.3 48.9
250 289 51.1 43.3 42.6 37.1 34.2 33.2 32.3 29.3 52.6
300 400 52.7 45.5 45.8 40.8 37.7 34.8 32.8 27.4 54.5
350 544 58.7 49.5 49.7 45.0 42.3 38.9 37.1 33.6 59.9
5. PRESSURE LOSS(Pa)
600
500
400
Pa
300
200
100
0
50 100 150 200 250 300 350
Air Flow (cmh)
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : RS-35-CO1 LOCATION IN BUILDING/ON SITE : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Signal Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR-PRO Minirator 1. Temp : 11.1 ℃
2. b&k 4189 2. Speaker (300W) 2.Humidity (%) : 70.0 %
3. Microphone ASSY 3. Power Amplifier (LEEM LPX-1200)
4. Personal Computer
2. BACKGROUND NOISE
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
BG [dB] 39.8 37.4 28.4 16.8 14.5 10.2 10.4 10.9 42.0
3. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 70.5 71.8 80.7 87.7 87.7 85.5 76.2 58.3 92.3
WITH EQUIPMENT 65.7 65.1 62.8 61.7 57.9 52.8 45.0 20.4 70.5
I.L [dB] 4.8 6.7 17.9 25.9 29.8 32.7 31.2 37.9 21.9
4. FLOW GENERATION
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
CMH Pa 63 125 250 500 1K 2K 4K 8K OA
100 21 41.4 36.6 29.7 17.1 16.5 11.1 11.5 15.3 42.9
150 47 45.3 37.2 32.3 25.3 25.7 21.5 13.4 15.3 46.2
200 79 47.7 38.8 35.9 32.2 31.9 29.5 23.0 16.2 48.7
250 124 52.1 43.6 42.0 37.9 37.2 34.9 30.0 20.3 53.4
300 185 56.0 49.3 47.5 43.1 42.0 40.0 35.9 27.1 57.7
350 240 59.4 52.5 50.7 46.0 44.9 43.1 39.2 31.1 61.0
400 343 64.8 56.9 56.4 50.9 49.5 47.8 44.4 37.4 66.3
5. PRESSURE LOSS(Pa)
400
300
Pa
200
100
0
100 150 200 250 300 350 400
Air Flow (cmh)
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : RS-45 LOCATION IN BUILDING/ON SITE : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Signal Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR-PRO Minirator 1. Temp : 17.9 ℃
2. b&k 4189 2. Speaker (300W) 2.Humidity (%) : 66.3 %
3. Microphone ASSY 3. Power Amplifier (LEEM LPX-1200)
4. Personal Computer
2. BACKGROUND NOISE
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
BG [dB] 28.3 32.6 24.7 12.2 10.9 13.5 11.0 10.9 34.6
3. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 70.4 72.5 80.9 86.1 86.3 84.6 76.0 56.4 91.2
WITH EQUIPMENT 69.8 68.0 64.0 60.6 52.0 43.3 32.4 16.2 72.9
I.L [dB] 0.6 4.5 16.9 25.5 34.3 41.3 43.6 40.2 18.2
4. FLOW GENERATION
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
CMH Pa 63 125 250 500 1K 2K 4K 8K OA
100 7 30.6 31.7 22.4 10.0 8.6 8.9 11.4 15.2 34.6
150 11 38.0 32.0 24.0 11.3 9.0 9.0 11.5 15.3 39.1
200 23 35.9 32.3 26.1 19.5 15.8 9.9 11.6 15.3 37.9
250 37 43.0 33.7 31.0 28.6 26.4 17.2 12.2 15.3 43.9
300 50 46.9 36.3 35.0 33.3 31.9 23.7 15.2 15.3 47.8
350 69 52.3 40.0 38.6 37.8 37.5 30.2 21.5 15.7 53.0
400 91 55.0 43.1 42.6 41.3 41.4 35.4 27.5 17.2 55.9
450 120 59.6 47.0 46.0 45.2 45.4 40.4 33.4 21.3 60.3
500 147 61.5 49.8 49.1 48.3 48.4 44.2 38.0 26.0 62.4
550 173 62.4 52.0 50.7 50.4 50.6 46.9 40.9 29.4 63.6
600 200 64.1 54.0 53.0 52.5 52.5 49.1 43.4 32.5 65.5
5. PRESSURE LOSS(Pa)
300
200
Pa
100
0
100 150 200 250 300 350 400 450 500 550 600
Air Flow (cmh)
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park, Y.K.Oh, C.J.Choi, S.S.Ryu HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : HKR-MCJ60 LOCATION IN BUILDING/ON SITE : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Signal Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR-PRO Minirator 1. Temp : 29.9 ℃
2. b&k 4189 2. Speaker (300W) 2. Humidity (%) : 60.0 %
3. Microphone ASSY 3. Power Amplifier (LEEM LPX-1200)
4. Personal Computer
2. BACKGROUND NOISE
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
BG [dB] 42.2 29.8 24.3 19.5 17.5 15.7 14.4 13.4 42.5
3. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 73.7 76.3 82.0 85.2 86.1 84.1 74.0 54.3 91.0
WITH EQUIPMENT 72.0 75.6 76.3 66.4 56.1 51.0 41.9 22.1 80.0
I.L [dB] 1.7 0.8 5.7 18.8 30.0 33.1 32.1 32.2 11.0
5. PRESSURE LOSS(Pa)
90
60
Pa
30
0
100 150 200 250 300 350
Air Flow (cmh)
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : MLG-55 LOCATION IN BUILDING/ON SITE : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Signal Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR-PRO Minirator 1. Temp : 10.3 ℃
2. b&k 4189 2. Speaker (300W) 2.Humidity (%) : 39.1 %
3. Microphone ASSY 3. Power Amplifier (LEEM LPX-1200)
4. Personal Computer
2. BACKGROUND NOISE
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
BG [dB] 31.6 36.4 24.1 12.4 9.7 9.7 10.4 10.8 37.9
3. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 75.7 75.2 83.9 89.6 87.9 84.8 76.3 58.2 93.4
WITH EQUIPMENT 73.9 79.9 86.2 77.4 78.9 77.4 69.2 52.0 88.6
I.L [dB] 1.8 0.0 0.0 12.2 9.0 7.4 7.0 6.2 4.8
4. FLOW GENERATION
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
CMH Pa 63 125 250 500 1K 2K 4K 8K OA
200 21 32.4 35.6 25.0 10.4 6.6 8.4 11.2 15.1 37.6
250 22 37.7 36.3 26.3 12.0 7.0 8.4 11.3 15.1 40.3
300 23 37.4 37.8 30.2 17.5 9.4 8.5 11.2 15.1 41.0
350 24 37.9 42.0 36.3 23.4 14.5 9.0 11.3 15.1 44.3
400 26 41.6 38.4 39.5 29.1 21.1 11.3 11.5 15.1 44.9
450 28 42.6 39.5 40.9 33.5 31.3 16.5 12.0 15.1 46.4
500 30 44.5 41.1 42.3 35.0 37.0 21.2 13.6 15.2 48.2
550 33 47.6 42.2 44.0 36.8 39.6 25.0 16.4 15.3 50.6
600 36 48.9 43.8 45.9 39.0 42.4 29.3 20.5 15.6 52.2
5. PRESSURE LOSS(Pa)
40
30
Pa
20
10
0
200 250 300 350 400 450 500 550 600
Air Flow (cmh)
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : MLG-90 LOCATION : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Noise Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR PRO 1. Temp :
2. b&k 4189 2. Speaker 2.Humidity (%) :
3. Microphone ASSY
4. Personal Computer
2. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 73.8 75.1 83.8 89.1 88.0 86.4 77.4 58.4 93.5
WITH EQUIPMENT 72.9 79.7 83.9 78.5 77.8 77.5 69.0 49.1 87.4
I.L [dB] 0.9 0.0 0.0 10.7 10.2 8.9 8.4 9.3 6.1
3. FLOW GENERATION
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
500 CMH (8 Pa) 64.5 65.2 57.4 35.1 29.4 27.7 25.5 17.0 68.2
600 CMH (10 Pa) 65.4 62.9 55.7 34.3 28.9 26.5 23.9 16.1 67.6
700 CMH (10 Pa) 66.2 61.3 54.2 35.7 30.3 26.5 21.8 15.4 67.6
800 CMH (12 Pa) 65.7 60.8 53.2 36.3 31.6 27.1 22.0 18.1 67.1
900 CMH (16 Pa) 62.0 57.4 53.1 39.9 36.9 30.5 21.5 15.1 63.7
1000 CMH (20 Pa) 61.1 56.6 53.2 44.6 40.5 33.5 23.5 15.4 63.0
1100 CMH (38 Pa) 63.1 57.7 53.3 45.6 42.6 36.2 26.5 16.0 64.6
1200 CMH (38 Pa) 61.4 56.9 52.9 46.5 44.1 38.4 29.1 17.3 63.3
PROJECT : Room Unit Test ADDRESS : 1432-11, Daman-Ri, Jillye-Myeon, Gimhae-Si, Gyeongnam
MEASUREMENT BY : K.H.Park HOMEPAGE : http://www.hiairkorea.co.kr
ITEM NAME : PK-06 LOCATION : HI AIR KOREA R&D LAB
1. MEASUREMENT EQUIPMENT
Analyzer Calibrator Noise Generator Operation Condition
1. b&k 3106C 1. b&k 4231 1. MR PRO 1. Temp :
2. b&k 4189 2. Speaker 2.Humidity (%) :
3. Microphone ASSY
4. Personal Computer
2. INSERTION LOSS
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
WITHOUT EQUIPMENT 57.7 63.5 73.7 82.3 83.8 83.4 74.2 54.3 88.3
WITH EQUIPMENT 58.2 65.2 77.1 78.3 78.6 78.7 70.7 52.2 84.5
I.L [dB] 0.0 0.0 0.0 4.0 5.2 4.7 3.5 2.1 3.9
3. FLOW GENERATION
1/1 OCTAVE BAND CENTER FREQUENCY,Hz
63 125 250 500 1K 2K 4K 8K OA
70 CMH (5 Pa) 39.8 40.3 35.3 25.1 24.3 23.0 15.2 14.5 43.9
100 CMH (11 Pa) 40.2 38.3 40.2 28.5 28.0 25.5 15.6 14.5 44.7
150 CMH (22 Pa) 39.6 40.2 42.0 35.2 27.9 24.3 14.9 14.5 46.0
200 CMH (38 Pa) 41.1 41.8 44.1 39.8 30.7 24.8 16.0 14.6 48.1