0% found this document useful (0 votes)
60 views39 pages

DOAS Sizing for Electrical Room

The document provides a sizing summary for the ELECTRICAL air system located in NEOM, Saudi Arabia. It has one zone with a floor area of 7.8 square meters. The peak cooling load occurs in June at 1:00 PM with a total cooling load of 1.6 kW and peak sensible cooling load of 1.3 kW. The required outdoor air flow is 4.8 L/s.

Uploaded by

comekib310
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views39 pages

DOAS Sizing for Electrical Room

The document provides a sizing summary for the ELECTRICAL air system located in NEOM, Saudi Arabia. It has one zone with a floor area of 7.8 square meters. The peak cooling load occurs in June at 1:00 PM with a total cooling load of 1.6 kW and peak sensible cooling load of 1.3 kW. The required outdoor air flow is 4.8 L/s.

Uploaded by

comekib310
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Dedicated Outdoor Air System (DOAS) Sizing Summary for ELECTRICAL

Project Name: 1088-HAQL RECREATIONAL 09/25/2023


Prepared by: orion 12:58PM

Air System Information


Air System Name ELECTRICAL Number of zones 1
Equipment Class TERM Floor Area 7.8 m²
Air System Type SPLT-FC Location NEOM, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page 1 of 39


Zone Sizing Summary for ELECTRICAL
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Air System Information


Air System Name ELECTRICAL Number of zones 1
Equipment Class TERM Floor Area 7.8 m²
Air System Type SPLT-FC Location NEOM, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 1.6 1.4 23.2 / 17.6 14.5 / 14.0 - Jun 1300 17.07

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.3 19.7 / 21.3 - 133 0.039 0.031 5

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.3 Jun 1400 0.2 7.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
ELECTRICAL 1 1.3 Jun 1400 133 0.2 7.8 17.07

Hourly Analysis Program 5.10 Page 2 of 39


Ventilation Sizing Summary for ELECTRICAL
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s·m²)) (L/s) (% of supply) (L/s)
Zone 1
ELECTRICAL 1 7.8 1.0 133.1 2.50 0.30 0.0 0.0 4.8
Totals (incl. Space Multipliers) 133.1 4.8

Hourly Analysis Program 5.10 Page 3 of 39


Air System Design Load Summary for ELECTRICAL
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.1 °C / 29.1 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 6 m² 15 - 6 m² 7 -
Roof Transmission 8 m² 7 - 8 m² 5 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 576 - 2 m² 135 -
Floor Transmission 8 m² 0 - 8 m² 26 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 94 W 94 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 390 W 390 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 115 6 10% 17 0
>> Total Zone Loads - 1269 66 - 189 0
Zone Conditioning - 1245 66 - 201 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 5 L/s 121 142 5 L/s 84 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 31 - - -31 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1397 208 - 255 0
Terminal Unit Cooling - 1397 210 - 0 0
Terminal Unit Heating - 0 - - 255 -
>> Total Conditioning - 1397 210 - 255 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 4 of 39


Zone Design Load Summary for ELECTRICAL
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.7 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 6 m² 18 - 6 m² 7 -
Roof Transmission 8 m² 8 - 8 m² 5 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 580 - 2 m² 135 -
Floor Transmission 8 m² 0 - 8 m² 26 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 94 W 94 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 390 W 390 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 116 6 10% 17 0
>> Total Zone Loads - 1278 66 - 189 0

Hourly Analysis Program 5.10 Page 5 of 39


Space Design Load Summary for ELECTRICAL
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

TABLE 1.1.A. Component Loads For Space "ELECTRICAL" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.7 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 6 m² 18 - 6 m² 7 -
Roof Transmission 8 m² 8 - 8 m² 5 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 580 - 2 m² 135 -
Floor Transmission 8 m² 0 - 8 m² 26 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 94 W 94 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 390 W 390 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 116 6 10% 17 0
>> Total Zone Loads - 1278 66 - 189 0

TABLE 1.1.B. Envelope Loads For Space "ELECTRICAL" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 6 0.079 - 18 - 7
DOOR GLASS 2 4.420 0.880 198 382 135
H EXPOSURE
ROOF 8 0.044 - 8 - 5

Hourly Analysis Program 5.10 Page 6 of 39


System Psychrometrics for ELECTRICAL
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

June DESIGN COOLING DAY, 1300

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 43.1 0.01997 5 400 121 142
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 22.3 0.00995 133 43 1245 66
Return Plenum Outlet -17.8 0.00995 133 43 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.200 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2929.1 W/(L/s)
Site Altitude = 53.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 5 - - -
Cooling Coil Inlet - 23.2 0.01032 133 0 - -
Cooling Coil Outlet - 14.5 0.00979 133 0 1397 210
Heating Coil Inlet - 14.5 0.00979 133 0 - -
Heating Coil Outlet - 14.5 0.00979 133 0 0 -
Zone Air - 22.3 0.00995 133 0 1245 -

Hourly Analysis Program 5.10 Page 7 of 39


System Psychrometrics for ELECTRICAL
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5.5 0.00385 5 400 -84 0
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 20.0 0.00386 133 0 -201 0
Return Plenum Outlet -17.8 0.00386 133 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.200 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2929.1 W/(L/s)
Site Altitude = 53.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Deadband )
Ventilation Air - - - 5 - - -
Cooling Coil Inlet - 19.7 0.00386 133 0 - -
Cooling Coil Outlet - 19.7 0.00386 133 0 0 0
Heating Coil Inlet - 19.7 0.00386 133 0 - -
Heating Coil Outlet - 21.3 0.00386 133 0 255 -
Zone Air - 20.0 0.00386 133 0 -201 -

Hourly Analysis Program 5.10 Page 8 of 39


System Psychrometrics for ELECTRICAL
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page 9 of 39


Dedicated Outdoor Air System (DOAS) Sizing Summary for MECH ROOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Air System Information


Air System Name MECH ROOM Number of zones 1
Equipment Class TERM Floor Area 5.5 m²
Air System Type SPLT-FC Location NEOM, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page 10 of 39


Zone Sizing Summary for MECH ROOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Air System Information


Air System Name MECH ROOM Number of zones 1
Equipment Class TERM Floor Area 5.5 m²
Air System Type SPLT-FC Location NEOM, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 1.4 1.3 23.3 / 17.7 14.8 / 14.3 - Jun 1400 22.50

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.2 19.6 / 21.1 - 124 0.036 0.029 4

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.2 Jun 1400 0.2 5.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
MECH ROOM 1 1.2 Jun 1400 124 0.2 5.5 22.50

Hourly Analysis Program 5.10 Page 11 of 39


Ventilation Sizing Summary for MECH ROOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s·m²)) (L/s) (% of supply) (L/s)
Zone 1
MECH ROOM 1 5.5 1.0 123.7 2.50 0.30 0.0 0.0 4.2
Totals (incl. Space Multipliers) 123.7 4.2

Hourly Analysis Program 5.10 Page 12 of 39


Air System Design Load Summary for MECH ROOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.7 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 4 m² 11 - 4 m² 4 -
Roof Transmission 6 m² 6 - 6 m² 4 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 580 - 2 m² 135 -
Floor Transmission 6 m² 0 - 6 m² 18 -
Partitions 8 m² 290 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 66 W 66 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 55 W 55 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 108 6 10% 16 0
>> Total Zone Loads - 1188 66 - 176 0
Zone Conditioning - 1126 66 - 172 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 4 L/s 106 119 4 L/s 72 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 29 - - -29 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1261 185 - 215 0
Terminal Unit Cooling - 1261 186 - 0 0
Terminal Unit Heating - 0 - - 215 -
>> Total Conditioning - 1261 186 - 215 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 13 of 39


Zone Design Load Summary for MECH ROOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.7 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 4 m² 11 - 4 m² 4 -
Roof Transmission 6 m² 6 - 6 m² 4 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 580 - 2 m² 135 -
Floor Transmission 6 m² 0 - 6 m² 18 -
Partitions 8 m² 290 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 66 W 66 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 55 W 55 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 108 6 10% 16 0
>> Total Zone Loads - 1188 66 - 176 0

Hourly Analysis Program 5.10 Page 14 of 39


Space Design Load Summary for MECH ROOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

TABLE 1.1.A. Component Loads For Space "MECH ROOM" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.7 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 4 m² 11 - 4 m² 4 -
Roof Transmission 6 m² 6 - 6 m² 4 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 580 - 2 m² 135 -
Floor Transmission 6 m² 0 - 6 m² 18 -
Partitions 8 m² 290 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 66 W 66 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 55 W 55 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 108 6 10% 16 0
>> Total Zone Loads - 1188 66 - 176 0

TABLE 1.1.B. Envelope Loads For Space "MECH ROOM" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 4 0.079 - 11 - 4
DOOR GLASS 2 4.420 0.880 198 382 135
H EXPOSURE
ROOF 6 0.044 - 6 - 4

Hourly Analysis Program 5.10 Page 15 of 39


System Psychrometrics for MECH ROOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

June DESIGN COOLING DAY, 1400

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 43.7 0.01997 4 400 106 119
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 22.4 0.01016 124 46 1126 66
Return Plenum Outlet -17.8 0.01016 124 46 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.200 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2929.1 W/(L/s)
Site Altitude = 53.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 4 - - -
Cooling Coil Inlet - 23.3 0.01050 124 0 - -
Cooling Coil Outlet - 14.8 0.00998 124 0 1261 186
Heating Coil Inlet - 14.8 0.00998 124 0 - -
Heating Coil Outlet - 14.8 0.00998 124 0 0 -
Zone Air - 22.4 0.01016 124 0 1126 -

Hourly Analysis Program 5.10 Page 16 of 39


System Psychrometrics for MECH ROOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5.5 0.00385 4 400 -72 0
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 19.9 0.00386 124 0 -172 0
Return Plenum Outlet -17.8 0.00386 124 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.200 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2929.1 W/(L/s)
Site Altitude = 53.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Heating )
Ventilation Air - - - 4 - - -
Cooling Coil Inlet - 19.6 0.00386 124 0 - -
Cooling Coil Outlet - 19.6 0.00386 124 0 0 0
Heating Coil Inlet - 19.6 0.00386 124 0 - -
Heating Coil Outlet - 21.1 0.00386 124 0 215 -
Zone Air - 19.9 0.00386 124 0 -172 -

Hourly Analysis Program 5.10 Page 17 of 39


System Psychrometrics for MECH ROOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page 18 of 39


Air System Sizing Summary for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Air System Information


Air System Name PACU1 Number of zones 1
Equipment Class PKG ROOF Floor Area 257.9 m²
Air System Type SZCAV Location NEOM, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 52.7 kW Load occurs at Aug 2100
Sensible coil load 39.8 kW OA DB / WB 40.2 / 28.4 °C
Coil L/s at Aug 2100 3078 L/s Entering DB / WB 24.6 / 18.3 °C
Max block L/s 3078 L/s Leaving DB / WB 13.8 / 13.2 °C
Sum of peak zone L/s 3078 L/s Coil ADP 12.6 °C
Sensible heat ratio 0.755 Bypass Factor 0.100
L/(s kW) 58.4 Resulting RH 55 %
m²/kW 4.9 Design supply temp. 13.0 °C
W/m² 204.5 Zone T-stat Check 1 of 1 OK
Water flow @ 5.6 K rise N/A Max zone temperature deviation 0.0 K

Central Heating Coil Sizing Data


Max coil load 11.4 kW Load occurs at Des Htg
Coil L/s at Des Htg 3078 L/s W/m² 44.1
Max coil L/s 3078 L/s Ent. DB / Lvg DB 19.4 / 22.5 °C
Water flow @ 11.1 K drop N/A

Supply Fan Sizing Data


Actual max L/s 3078 L/s Fan motor BHP 1.49 BHP
Standard L/s 3058 L/s Fan motor kW 1.18 kW
Actual max L/(s·m²) 11.93 L/(s·m²) Fan static 250 Pa

Outdoor Ventilation Air Data


Design airflow L/s 338 L/s L/s/person 9.40 L/s/person
L/(s·m²) 1.31 L/(s·m²)

Hourly Analysis Program 5.10 Page 19 of 39


Zone Sizing Summary for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Air System Information


Air System Name PACU1 Number of zones 1
Equipment Class PKG ROOF Floor Area 257.9 m²
Air System Type SZCAV Location NEOM, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 3047 3047 11.81 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 31.8 Sep 2100 5.8 257.9

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
RECREATIONAL 1 25.6 Sep 2100 2375 5.1 220.0 10.79
LOBBY ENTRANCE 1 5.0 Oct 1500 462 0.5 15.6 29.65
CORRIDOR 1 2.3 Jun 1400 210 0.2 22.3 9.40

Hourly Analysis Program 5.10 Page 20 of 39


Ventilation Sizing Summary for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 338 L/s

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s·m²)) (L/s) (% of supply) (L/s)
Zone 1
RECREATIONAL 1 220.0 30.0 2374.8 3.80 0.90 0.0 0.0 312.0
LOBBY ENTRANCE 1 15.6 3.0 462.5 2.50 0.30 0.0 0.0 12.2
CORRIDOR 1 22.3 3.0 209.7 2.50 0.30 0.0 0.0 14.2
Totals (incl. Space Multipliers) 3047.0 338.4

Hourly Analysis Program 5.10 Page 21 of 39


Air System Design Load Summary for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.2 °C / 28.4 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 54 m² 9248 - 54 m² - -
Wall Transmission 130 m² 392 - 130 m² 161 -
Roof Transmission 258 m² 595 - 258 m² 178 -
Window Transmission 54 m² 4423 - 54 m² 3727 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 12 m² 2756 - 12 m² 821 -
Floor Transmission 258 m² 0 - 258 m² 631 -
Partitions 51 m² 1699 - 51 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3095 W 3095 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3483 W 3483 - 0 0 -
People 36 2894 2734 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2859 137 5% 276 0
>> Total Zone Loads - 31444 2870 - 5793 0
Zone Conditioning - 30886 2870 - 6089 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 3078 L/s 0 - 3078 L/s 0 -
Ventilation Load 338 L/s 7136 10040 338 L/s 6351 0
Supply Fan Load 3078 L/s 1184 - 3078 L/s -1184 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 2% 629 - 2% 116 -
>> Total System Loads - 39835 12910 - 11372 0
Central Cooling Coil - 39835 12911 - 0 0
Central Heating Coil - 0 - - 11372 -
>> Total Conditioning - 39835 12911 - 11372 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 22 of 39


Zone Design Load Summary for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.1 °C / 27.8 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 54 m² 9799 - 54 m² - -
Wall Transmission 130 m² 420 - 130 m² 161 -
Roof Transmission 258 m² 546 - 258 m² 178 -
Window Transmission 54 m² 4153 - 54 m² 3727 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 12 m² 2882 - 12 m² 821 -
Floor Transmission 258 m² 0 - 258 m² 631 -
Partitions 51 m² 1642 - 51 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3095 W 3095 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3483 W 3483 - 0 0 -
People 36 2894 2734 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2891 137 5% 276 0
>> Total Zone Loads - 31804 2870 - 5793 0

Hourly Analysis Program 5.10 Page 23 of 39


Space Design Load Summary for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

TABLE 1.1.A. Component Loads For Space "RECREATIONAL" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.1 °C / 27.8 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 54 m² 9799 - 54 m² - -
Wall Transmission 122 m² 402 - 122 m² 151 -
Roof Transmission 220 m² 465 - 220 m² 152 -
Window Transmission 54 m² 4153 - 54 m² 3727 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 3 m² 1037 - 3 m² 214 -
Floor Transmission 220 m² 0 - 220 m² 595 -
Partitions 18 m² 590 - 18 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2640 W 2640 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1760 W 1760 - 0 0 -
People 30 2463 2373 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2331 119 5% 242 0
>> Total Zone Loads - 25640 2492 - 5080 0

TABLE 1.1.B. Envelope Loads For Space "RECREATIONAL" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 38 0.079 - 139 - 47
WINDOW 1 12 4.420 0.811 924 2851 829
WINDOW 2 6 4.420 0.811 484 1495 435
DOOR GLASS 3 4.420 0.880 238 798 214
SW EXPOSURE
WALL 49 0.079 - 179 - 60
WINDOW 1 11 4.420 0.811 811 2502 727
SE EXPOSURE
WALL 34 0.079 - 82 - 42
WINDOW 1 6 4.420 0.811 484 888 435
NW EXPOSURE
WALL 1 0.079 - 2 - 1
WINDOW 1 6 4.420 0.811 481 685 432
WINDOW 2 13 4.420 0.811 969 1378 869
H EXPOSURE
ROOF 220 0.044 - 465 - 152

Hourly Analysis Program 5.10 Page 24 of 39


Space Design Load Summary for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

TABLE 1.2.A. Component Loads For Space "LOBBY ENTRANCE" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.6 °C / 27.1 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 5 m² 15 - 5 m² 6 -
Roof Transmission 16 m² 13 - 16 m² 11 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 7 m² 2241 - 7 m² 462 -
Floor Transmission 16 m² 0 - 16 m² 0 -
Partitions 11 m² 366 - 11 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 187 W 187 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 454 9 5% 24 0
>> Total Zone Loads - 4993 189 - 503 0

TABLE 1.2.B. Envelope Loads For Space "LOBBY ENTRANCE" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 5 0.079 - 15 - 6
DOOR GLASS 7 4.420 0.880 512 1730 462
H EXPOSURE
ROOF 16 0.044 - 13 - 11

Hourly Analysis Program 5.10 Page 25 of 39


Space Design Load Summary for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

TABLE 1.3.A. Component Loads For Space "CORRIDOR" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.7 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 4 m² 11 - 4 m² 4 -
Roof Transmission 22 m² 23 - 22 m² 15 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 571 - 2 m² 145 -
Floor Transmission 22 m² 0 - 22 m² 35 -
Partitions 21 m² 748 - 21 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 268 W 268 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 223 W 223 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 206 9 5% 10 0
>> Total Zone Loads - 2264 189 - 210 0

TABLE 1.3.B. Envelope Loads For Space "CORRIDOR" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 4 0.079 - 11 - 4
DOOR GLASS 2 4.420 0.880 189 382 145
H EXPOSURE
ROOF 22 0.044 - 23 - 15

Hourly Analysis Program 5.10 Page 26 of 39


System Psychrometrics for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

August DESIGN COOLING DAY, 2100

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 40.2 0.01973 338 400 7136 10040
Vent - Return Mixing Outlet 24.6 0.01071 3078 962 - -
Central Cooling Coil Outlet 13.8 0.00928 3078 962 39835 12911
Central Heating Coil Outlet 13.8 0.00928 3078 962 0 -
Supply Fan Outlet 14.1 0.00928 3078 962 1184 -
Cold Supply Duct Outlet 14.3 0.00928 3047 962 - -
Zone Air - 22.7 0.00960 3047 1032 30886 2870
Return Plenum Outlet 22.7 0.00960 3047 1032 0 -
Duct Leakage Air Outlet 14.1 0.00928 31 962 - -
Return Duct Outlet 22.6 0.00960 3078 1031 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.200 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2929.1 W/(L/s)
Site Altitude = 53.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 31444 Cooling 30886 22.7 3047 1032 0 0

Hourly Analysis Program 5.10 Page 27 of 39


System Psychrometrics for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5.5 0.00385 338 400 -6351 0
Vent - Return Mixing Outlet 19.4 0.00385 3078 478 - -
Central Cooling Coil Outlet 19.4 0.00385 3078 478 0 0
Central Heating Coil Outlet 22.5 0.00385 3078 478 11372 -
Supply Fan Outlet 22.8 0.00385 3078 478 1184 -
Cold Supply Duct Outlet 22.8 0.00385 3047 478 - -
Zone Air - 21.1 0.00385 3047 488 -6089 0
Return Plenum Outlet 21.1 0.00385 3047 488 0 -
Duct Leakage Air Outlet 22.8 0.00385 31 478 - -
Return Duct Outlet 21.1 0.00385 3078 488 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.200 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2929.1 W/(L/s)
Site Altitude = 53.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -5793 Deadband -6089 21.1 3047 488 0 0

Hourly Analysis Program 5.10 Page 28 of 39


System Psychrometrics for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Location: NEOM, Saudi Arabia


Altitude: 53.0 m.
Data for: August DESIGN COOLING DAY, 2100
1
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Duct Heat
6. Room Air
7. Return Duct Outlet
0.016

Specific Humidity ( kg/kg )


0.014

0.012
2

34 6 0.010
7
5
0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35 40
Temperature ( °C )

Hourly Analysis Program 5.10 Page 29 of 39


System Psychrometrics for PACU1
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Location: NEOM, Saudi Arabia


Altitude: 53.0 m.
Data for: WINTER DESIGN HEATING
0.020
1. Outdoor Air
2. Mixed Air
3. Central Heating Coil Outlet
4. Supply Fan Outlet 0.018
5. Duct Heat
6. Duct Heat
7. Room Air
8. Return Duct Outlet 0.016

Specific Humidity ( kg/kg )


0.014

0.012

0.010

0.008

0.006
1 26 78 3 4
0.004
5
0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program 5.10 Page 30 of 39


Dedicated Outdoor Air System (DOAS) Sizing Summary for TELECOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Air System Information


Air System Name TELECOM Number of zones 1
Equipment Class TERM Floor Area 9.0 m²
Air System Type SPLT-FC Location NEOM, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page 31 of 39


Zone Sizing Summary for TELECOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Air System Information


Air System Name TELECOM Number of zones 1
Equipment Class TERM Floor Area 9.0 m²
Air System Type SPLT-FC Location NEOM, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 1.7 1.5 23.5 / 17.8 14.8 / 14.2 - Jun 1400 16.11

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.3 19.5 / 20.9 - 145 0.042 0.033 5

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.4 Jun 1400 0.2 9.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
TELECOM 1 1.4 Jun 1400 145 0.2 9.0 16.11

Hourly Analysis Program 5.10 Page 32 of 39


Ventilation Sizing Summary for TELECOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows

2. Space Ventilation Analysis

2.1 Zone: Zone 1


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s·m²)) (L/s) (% of supply) (L/s)
Zone 1
TELECOM 1 9.0 1.0 145.0 2.50 0.30 0.0 0.0 5.2
Totals (incl. Space Multipliers) 145.0 5.2

Hourly Analysis Program 5.10 Page 33 of 39


Air System Design Load Summary for TELECOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.7 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 16 m² 45 - 16 m² 18 -
Roof Transmission 9 m² 10 - 9 m² 6 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 580 - 2 m² 135 -
Floor Transmission 9 m² 0 - 9 m² 39 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 108 W 108 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 450 W 450 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 126 6 10% 20 0
>> Total Zone Loads - 1391 66 - 218 0
Zone Conditioning - 1346 66 - 195 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 5 L/s 132 150 5 L/s 89 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 33 - - -33 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1512 216 - 251 0
Terminal Unit Cooling - 1512 217 - 0 0
Terminal Unit Heating - 0 - - 251 -
>> Total Conditioning - 1512 217 - 251 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 34 of 39


Zone Design Load Summary for TELECOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.7 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 16 m² 45 - 16 m² 18 -
Roof Transmission 9 m² 10 - 9 m² 6 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 580 - 2 m² 135 -
Floor Transmission 9 m² 0 - 9 m² 39 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 108 W 108 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 450 W 450 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 126 6 10% 20 0
>> Total Zone Loads - 1391 66 - 218 0

Hourly Analysis Program 5.10 Page 35 of 39


Space Design Load Summary for TELECOM
Project Name: 1088-HAQL RECREATIONAL
Prepared by: orion

TABLE 1.1.A.Component Loads For Space "TELECOM" In Zone "Zone 1"


DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.7 °C / 29.3 °C HEATING OA DB / WB 5.5 °C / 3.2 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 20.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 16 m² 45 - 16 m² 18 -
Roof Transmission 9 m² 10 - 9 m² 6 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 580 - 2 m² 135 -
Floor Transmission 9 m² 0 - 9 m² 39 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 108 W 108 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 450 W 450 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 126 6 10% 20 0
>> Total Zone Loads - 1391 66 - 218 0

TABLE 1.1.B. Envelope Loads For Space "TELECOM" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 7 0.079 - 21 - 8
DOOR GLASS 2 4.420 0.880 198 382 135
SE EXPOSURE
WALL 9 0.079 - 24 - 10
H EXPOSURE
ROOF 9 0.044 - 10 - 6

Hourly Analysis Program 5.10


System Psychrometrics for TELECOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

June DESIGN COOLING DAY, 1400

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 43.7 0.01997 5 400 132 150
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 22.5 0.01011 145 39 1346 66
Return Plenum Outlet -17.8 0.01011 145 39 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.200 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2929.1 W/(L/s)
Site Altitude = 53.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 5 - - -
Cooling Coil Inlet - 23.5 0.01047 145 0 - -
Cooling Coil Outlet - 14.8 0.00996 145 0 1512 217
Heating Coil Inlet - 14.8 0.00996 145 0 - -
Heating Coil Outlet - 14.8 0.00996 145 0 0 -
Zone Air - 22.5 0.01011 145 0 1346 -

Hourly Analysis Program 5.10 Page 37 of 39


System Psychrometrics for TELECOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5.5 0.00385 5 400 -89 0
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 19.8 0.00386 145 0 -195 0
Return Plenum Outlet -17.8 0.00386 145 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.200 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2929.1 W/(L/s)
Site Altitude = 53.0 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Heating )
Ventilation Air - - - 5 - - -
Cooling Coil Inlet - 19.5 0.00386 145 0 - -
Cooling Coil Outlet - 19.5 0.00386 145 0 0 0
Heating Coil Inlet - 19.5 0.00386 145 0 - -
Heating Coil Outlet - 20.9 0.00386 145 0 251 -
Zone Air - 19.8 0.00386 145 0 -195 -

Hourly Analysis Program 5.10 Page 38 of 39


System Psychrometrics for TELECOM
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page 39 of 39