[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.
01
Release Notes
SpaceLogic IP Controller Firmware
for MP-C, MP-V, RP-C, IP-IO and
CRS Series
v4.00.01
This document is written for and on behalf of Schneider Electric and is supplied on the express
terms that it is to be treated as confidential and that it may not be copied, used or disclosed to others
except as authorized in writing by this Company. This document is intended for internal use only.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 1 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
About This Release
These release notes document details a new release of firmware (4.00.01) for:
• RP Series controllers including RP-C and RP-V
• MP Series controllers including MP-C and MP-V
• IP-IO Series IO expansion modules
• Connected Room Solution (CRS) Expansion Modules
This is a major release that contains new features, defect fixes, and the introduction of
additional modules for the Connected Room Solution (CRS), the new Zigbee CRS expansion
modules and many other features, please see section 2 for full details.
This firmware release is fully compatible with EcoStruxure™ Building Operation v4.0.1 and
therefore this document should be read in conjunction with the EcoStruxure Building
Operation v4.0.1 release note.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 2 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Table of contents
ABOUT THIS RELEASE ......................................................................................................................................................... 2
1. SPACELOGIC IP CONTROLLERS ................................................................................................................................ 5
1.1 Firmware Availability and Compatibility ............................................................................................... 5
1.2 New features summary ........................................................................................................................... 6
2. NEW FEATURES IN SPACELOGIC IP CONTROLLERS .............................................................................................. 7
2.1 Connected Room Solution (CRS) in this Release ................................................................................ 7
2.2 SpaceLogic IP Controller and SpaceLogic Servers ............................................................................. 7
2.3 RP-C Advanced ....................................................................................................................................... 8
2.4 RP-C Pro (Hardware launch 2022) ......................................................................................................... 8
2.5 RP Webservices ...................................................................................................................................... 9
2.5.1 Webservices .......................................................................................................................................................... 9
2.5.2 Certificate Configuration Tool ................................................................................................................................. 9
2.5.3 Secure Module ....................................................................................................................................................... 9
2.6 RP-V IP Controllers (Hardware launch 2022) ...................................................................................... 10
2.7 Zigbee Support ...................................................................................................................................... 10
2.7.1 RP Controller Expansion Zigbee Modules ............................................................................................................ 11
2.7.2 Device Support .................................................................................................................................................... 12
2.7.3 Forced Uprev of Zigbee........................................................................................................................................ 12
2.7.4 Force Associate ................................................................................................................................................... 13
2.7.5 New ADT format (Lib) .......................................................................................................................................... 13
2.8 Increased Application Memory ............................................................................................................ 13
2.8.1 Free Object System Memory (User Application Memory) ..................................................................................... 13
2.8.2 Persistent Memory (FRAM) Limitations and Availability Metric ............................................................................. 13
2.9 Compressed Firmware Support ........................................................................................................... 14
2.9.1 Overview .............................................................................................................................................................. 14
2.10 Insight Sensor (Hardware launch 2022) .............................................................................................. 14
2.10.1 Mask................................................................................................................................................................ 16
2.10.2 Adding an Inclusion Area ................................................................................................................................. 17
2.10.3 Adding an Exclusion Area ................................................................................................................................ 18
2.10.4 Segment People Count Inputs ......................................................................................................................... 19
2.11 DALI support for Input Devices ........................................................................................................... 19
2.11.1 Overview ......................................................................................................................................................... 19
2.11.2 Features available ........................................................................................................................................... 19
2.12 Additional properties for controlling blinds ....................................................................................... 22
2.13 BACnet MS/TP (Northbound) Support for IP Controllers (Hardware and Firmware launch 2022) . 22
3. KNOWN DEFECTS IN SPACELOGIC IP CONTROLLERS.......................................................................................... 23
4. FIELD DEFECTS FIXED IN ECOSTRUXURE BUILDING OPERATION V4.00.01 RELEASE ...................................... 33
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 3 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
5. IMPORTANT ENGINEERING INFORMATION ............................................................................................................. 36
5.1 SpaceLogic IP Series (MP-C/V, IP-IO, and RP-C) Factory Firmware ................................................. 36
5.2 SpaceLogic IP Series (MP-C/V, IP-IO, and RP-C) BACnet.................................................................. 36
5.3 Connected Room Solution – Light & Blind ......................................................................................... 36
5.4 Connected Room Solution – DALI Module ......................................................................................... 36
5.5 Connected Room Solution – DALI discovery ..................................................................................... 36
5.6 Zigbee Engineering ............................................................................................................................... 36
5.6.1 Zigbee Device import files clarification.................................................................................................................. 36
5.6.2 Downloading Zigbee Device import files ............................................................................................................... 37
5.6.3 Improved handling of Zigbee Device import files ............................................................................................ 37
5.6.4 New way to associate Zigbee physical device with logical device ......................................................................... 38
5.6.5 Zigbee configuration in the RP controller .............................................................................................................. 38
5.6.6 Discovering the Zigbee Green Powered sensors. ................................................................................................. 39
5.6.7 Removing and replacing Zigbee Device types ................................................................................................. 40
5.6.8 Decommissioning GP sensors from an existing Zigbee network ........................................................................... 40
5.6.9 Moving Zigbee USB adaptors............................................................................................................................... 41
5.7 BACnet ................................................................................................................................................... 41
5.7.1 Synchronize Bindings of Value and Default Priority Level ..................................................................................... 41
5.8 SMI Blind:............................................................................................................................................... 41
5.9 Restoring Optional Properties ............................................................................................................. 42
5.10 DALI Inputs Engineering ...................................................................................................................... 43
5.10.1 Discovery of Control Devices ........................................................................................................................... 43
5.10.2 Association of Control Devices ........................................................................................................................ 43
5.10.3 Setting instance ID........................................................................................................................................... 44
5.10.4 Analog Input conversion .................................................................................................................................. 44
5.10.5 Light Sensor conversion .................................................................................................................................. 45
APPENDIX A – SPACELOGIC IP CONTROLLER UPGRADE PROCEDURES ................................................................... 46
A1 Upgrading Controller Firmware.................................................................................................................. 46
A2 Upgrading CRS Module Firmware.............................................................................................................. 46
A3 Upgrading SpaceLogic Sensor Firmware.................................................................................................. 46
A4 Upgrading Remote-Control Firmware ........................................................................................................ 47
A5 Verifying All Firmware Versions................................................................................................................. 47
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 4 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
1. SpaceLogic IP Controllers
1.1 Firmware Availability and Compatibility
The firmware included in this release is available for download on Schneider Electric Exchange.
The firmware is delivered in a universal package file that contains all firmware files for all
SpaceLogic IP Controller products.
SpaceLogic_IP_Controller_4.[Link] Package
Product Version
SpaceLogic IP Controller – MP-C 4.00.01.00011
SpaceLogic IP Controller – MP-V 4.00.01.00011
SpaceLogic IP Controller – IP-IO 4.00.01.00011
SpaceLogic IP Controller – RP-C 4.00.01.00011
SpaceLogic IP Controller – RP-C Advanced 4.00.01.00011
Supporting Firmware
SpaceLogic Room Unit Application 1.04.18
SpaceLogic Room Unit Bootloader 0.03.04
MP-C Main Board 4.00.01.00002
MP-V Main Board 4.00.01.00002
RP-C Main Board 4.00.01.00002
RP-C EFR32 4.00.01.00001
CRS – Blind LV [Link]
CRS – Blind HV [Link]
CRS – Light 0 to 10V [Link]
CRS – Light 0 to 10V PD [Link]
CRS – Light DALI [Link]
CRS – Blind SMI LV [Link]
CRS – Blind SMI HV [Link]
CRS – Relay [Link]
CRS – Sensor expansion module [Link]
CRS – Insight Sensor module [Link]
Zigbee Adapter Firmware 1.22.0
1 Due to a defect, this will show as [Link] in the Device Report
Note: The SpaceLogic IP Controllers shipped from the factory may not have the latest
firmware installed. It is essential to verify that the controller has the firmware compatible
with EBO in use before programming the controller.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 5 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Supported EBO releases and IP Firmware
SpaceLogic IP MP/RP and IP-IO Series Controller Versions
EBO v4.00.0x
v1.00.0x v2.00.0x v3.01.0x v3.02.0x v3.03.01
Versions
v2.0.1/2/3 Supported Not supported Not supported Not supported Not supported Not supported
v2.0.4 Supported Supported Not supported Not supported Not supported Not supported
v3.0.x Not supported Supported Not supported Not supported Supported Supported
V3.1.x Not supported Supported Supported Supported Supported Supported
V3.2.x Not supported Supported Supported Supported Supported Supported
V3.3.1L Not supported Supported Supported Supported Supported Supported
V4.0.x Not supported Supported Supported Supported Supported Supported
* New v4.0 features are not supported when used with EBO v3.x.x.
Note: RP-C is only supported on EBO 3.0 and later
Note: The SpaceLogic IP Controllers shipped from the factory may not have the latest firmware
installed. It is essential to verify that the controller has the latest firmware build loaded for the
EcoStruxure Building Operation version build being used before programming the controller.
Down-Rev from a factory installed 4.0 firmware IP Controller to “earlier” versions
It is important to note that any Down-Rev should be undertaken after hosting and prior to connecting
any external equipment ( beyond power and Ethernet connection) and prior to downloading any
application or undertaking any other configuration of the controller.
Warning: Down-Rev is NOT supported between versions once the application is loaded on to the
controller.
1.2 New features summary
Release v4.00.01 of EcoStruxure Building Operation 2022 provides many new features for the
user in the following areas:
• New modules for Connected Room Solution (CRS)
• RP-C Advanced
• RP-C Pro (Hardware Launch 2022)
• RP Webservices
• RP-V (Hardware Launch 2022)
• Zigbee Support - RP Controller Expansion Zigbee Modules
• Increased Application Memory
• Compressed Firmware Support
• Insight Sensor (Hardware Launch 2022)
• Dali Support for Input devices
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 6 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
2. New Features in SpaceLogic IP Controllers
2.1 Connected Room Solution (CRS) in this Release
The following models are supported by this release:
• Insight-Sensor (NEW) – See section 2.10 for more details
• RP Controller Expansion Zigbee Modules – See section 2.7.1 for
more details
Existing modules:
• Blind High Voltage (4 groups) with power distribution
• DALI 4 groups (1 channel) with power distribution
• Sensor expansion module for infrared motion detection and
luminosity measurements
• Blind Low Voltage (2 groups) with power distribution
• Lighting 0 to 10v with power distribution
• Standard Motor Interface (SMI) high voltage with power
distribution (4 groups)
• Standard Motor Interface (SMI) low voltage with power
distribution (2 groups)
• DALI without power distribution (2 groups)
• Light 0v to 10v without power distribution (2 channel)
• Relay module high voltage with power distribution (4 channel)
2.2 SpaceLogic IP Controller and SpaceLogic Servers
Spacelogic CRS modules can be hosted by all IP Controllers with a Room Bus port.
The IP Controller can be hosted by Spacelogic servers:
• Spacelogic Automation Server (AS-P / AS-B)
• Enterprise Server
For additional information please refer to the user documentation which can be found on
EcoStruxure Building Webhelp.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 7 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
2.3 RP-C Advanced
The RP-C Advanced controller is the new designation for currently available RP controller hardware.
However, 2022 will see an updated version of the hardware with additional flash (internal file system
use only) and changes to the serial ports to facilitate BACnet MS/TP*.
In addition, the updated RP hardware also has an increased rating on COM-A from 2W to 3W to
handle up to 4 SpaceLogic Living space sensors, independent of room unit version.
As a direct replacement for the earlier hardware, the model shall remain the same but with a new
commercial reference, but the two hardware versions may be distinguished by their platform code.
The earlier version hardware will have a platform code of RPC-LCES1T1, whereas the newer hardware
has a platform code of RPC-LCES1T2.
*For more information on MS/TP Northbound support , refer to section 2.13.
2.4 RP-C Pro (Hardware launch 2022)
RP Pro controllers represent an evolution of the previous RP Advanced controllers and are based on
the more powerful MP platform, offering increased performance, and additional application space
(4MB) for the user (Free Object system Memory). The RP Pro retains all the features of previous RP
controllers including BLE radio, Zigbee USB dongle support and two serial bus ports, supporting
Sensor Bus, CRS Room Bus, Modbus and MS/TP Northbound*. The RP-C Pro has a platform code of
RPC-LCES2T2
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 8 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
*For more information on MS/TP Northbound support , refer to section 2.13.
2.5 RP Webservices
2.5.1 Webservices
A REST API has been implemented to allow secure HTTPS communications to allow the reading and
writing of values in the RP application. Prior to enabling Webservices, it is required that the controller
is loaded with the necessary keys and certificate to facilitate secure communication. This is achieved
using the SpaceLogic Certificate Configuration Tool
2.5.2 Certificate Configuration Tool
The Certificate Configuration Tool is a Windows-based application that allows the configuration of
keys and certificates in the controller. This process ensures secure communication to the
webservices and until the configuration is complete, the webservices feature cannot be enabled.
Before the Certificate Configuration Tool can access the controller, the IP address of the
configuration tool needs to be entered into the Settings object of the controller.
2.5.3 Secure Module
The necessary keys and certificates are encrypted by a secure module on the controller.
WARNING: When the secure module is used for the first time, it will take 10-15 seconds to initialize.
The secure module may be rendered non-operational and non-recoverable if this process is disturbed
or interrupted. DO NOT power-cycle, restart or in any other way interact with the controller during
this initialization period.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 9 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
2.6 RP-V IP Controllers (Hardware launch 2022)
RP-V controllers are a VAV controller, similar to the MP-V but based on the RP-C controller
architecture. They share the features of previous RP-C controllers including BLE radio, Zigbee USB
dongle support and two serial bus ports, supporting Sensor Bus, CRS Room Bus, Modbus and MS/TP
Northbound*.
The RP-V room bus supports up to four connected RP controller expansion modules with the
following restrictions:
• Maximum of one DALI light module
• Maximum of one SMI blind module
• Maximum of two Multi-sensors or SpaceLogic Insight-Sensors
*For more information on MS/TP Northbound support , refer to section 2.13.
2.7 Zigbee Support
The SpaceLogic Zigbee Adapter enables Zigbee3.0 wireless connectivity for SpaceLogic RP-C
controllers as well as SpaceLogic AS-P and AS-B servers, extending its point count and bringing
flexibility in retrofit applications.
With EcoStruxure Building Operation 2022, the Zigbee Adapter will enable Zigbee 3.0 wireless
connectivity for the SpaceLogic RP-V controller. It can communicate over the Zigbee wireless
protocol with more wireless devices, including SpaceLogic Zigbee Expansion Modules (RP-C-EXT-ZB-
DALI Zigbee-to-DALI module and RP-C-EXT-ZB-0-10V Zigbee-to-0-10Vmodule) and PowerLogic Power
Tag Energy Sensors, and as a certified Zigbee device, will allow interoperability with third-party
Zigbee devices.
With an open Zigbee device support capability, support for new Schneider Electric and third-party
Zigbee devices can now be added to EcoStruxure Building Operation 2022 or later through a service
that is provided by the Digital Buildings Centre of Excellence. See the Zigbee Adapter Specification
Sheet for more information on the new features and the supported wireless devices for the
SpaceLogic RP controllers and/or SpaceLogic servers.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 10 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
2.7.1 RP Controller Expansion Zigbee Modules
The RP controller expansion Zigbee modules provide devices that can be used to form a connected
room solution. The RP controller expansion Zigbee modules are connected to the RP-C room
controllers through the Zigbee TM wireless protocol and provide the controllers with I/O expansion
that enable lighting control.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 11 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
RP-C-EXT-ZB-DALI
The RP-C-EXT-ZB-DALI Zigbee DALI module communicates with the RP-C room controller over the
Zigbee TM wireless protocol and provides I/O expansion for lighting control with DALI (Digital
Addressable Lighting Interface).
For more information, see RP-C-EXT-ZB-DALI .
RP-C-EXT-ZB-0-10V
The RP-C-EXT-ZB-0-10V Zigbee 0-10V module communicates with the RP-C room controller over the
Zigbee TM wireless protocol and provides I/O expansion for 0-10V lighting control.
For more information, see RP-C-EXT-ZB-0-10V .
2.7.2 Device Support
For list with supported sensors please visit the Schneider BMS Applications page, devices are listed
as Zigbee Device Import Files.
New import files can be requested at the BMS Applications Portal.
Warning: Do not move the adaptors between RP-C’s or AS-P’s, as for this release, once plugged in
and recognized by the device they will not be recognized again if moved between devices, without
deleting the complete Zigbee network.
2.7.3 Forced Uprev of Zigbee
In most cases, dependent firmware’s delivered via the IP controller are upgraded automatically
where the available version is higher than the current version. In some cases, where components
within the firmware are updated, the broader Zigbee adapter firmware version may not be
incremented. In these limited cases the user may be required to use the manually trigger the upgrade
by selecting the Upgrade Zigbee firmware command from the Zigbee network context menu. If a
downgrade of firmware is required, this command will also be required to force the downgrade to
the Zigbee dongle. Note that it is recommend that downgrades of system are undertaken under the
guidance of product support.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 12 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
2.7.4 Force Associate
Discovery and association of device on a Zigbee network may be performed using standard drag and
drop. However, in some cases, a single ADT may be used to create multiple models with a device
family, e.g. SE/VT8000 thermostats, even where the physical model may not match the ADT model.
In these cases, a forced association action may be used. This action is similar to the standard drag
and drop association but is carried out with the shift key depressed. Caution should be used when
force associating as it removes validation of suitability between logical and physical device.
2.7.5 New ADT format (Lib)
Previous Zigbee device ADTs have been deprecated and replaced by Custom Type Library versions,
prefixed “RP_Lib”, e.g. RP_Lib_ZB-[Link]. These ADTs should be imported as
Custom Types and instantiated from the Custom Type Library.
2.8 Increased Application Memory
2.8.1 Free Object System Memory (User Application Memory)
The memory available for creating applications has been increased to 4MB on MP-C, MP-V and IP-IO
controllers to allow the creation of larger applications and to allow for additional trendlog buffer
sizes.
2.8.2 Persistent Memory (FRAM) Limitations and Availability Metric
The increase in the user application memory has created the potential for additional consumption of
persistent memory that retains controller runtime data during restarts, and it is possible to exhaust
persistent memory before the full 4MB of application memory is fully consumed. To assist the user
in monitoring their memory use, both Free memory and Free persistent memory metrics are
available on the device object.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 13 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
2.9 Compressed Firmware Support
2.9.1 Overview
Firmware downloads to the controller may be compressed to reduce the transmission time of the
firmware files. Due to the unzipping in the controller, the activation may take slightly longer when
this feature is enabled. The selection, “Compress for transmission” is selected by default and will
ensure that firmware is compressed for controllers that support the feature. If the selection is made
for unsupported controllers, the firmware will be downloaded uncompressed. The checkbox should
only be deselected for troubleshooting purposes and it is recommended that it remains checked at
all other times.
2.10 Insight Sensor (Hardware launch 2022)
The Insight Sensor has the following objects as default for monitoring the ambient condition.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 14 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
The commissioning parameters for the ambient light sensor are:
Constant lighting reference property should be set to the maximum level of lighting required in
normal conditions. This value then becomes the setpoint for the light level control.
The commissioning parameters for the passive infrared sensor are:
Sensitivity setting, Higher value = less sensitive
Reset time, is the time between detections
SpaceLogic™ Insight-Sensor supports people counting through a thermal imaging sensor.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 15 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Thermal Image Sensor
The sensor is designed to detect and count people standing and sitting in an area inside a building.
The sensor periodically transmits :– The number of people.
The commissioning parameters for the people counting sensor are :
Camera mode – Normal and Degraded
Normal means that the background image has been refreshed.
Degraded indicates that the background image has not been refreshed either automatically or
through command.
Refresh Background Mode – It can be set to automatic or manual.
Refresh Background Time – The time at which the background image is refreshed in automatic mode.
Minimum no motion time – The amount of time no motion must be detected before the background
image is refreshed.
Refresh Background Image Command – Refreshes the background image , accounting to minimum
no motion time. Right click on Insight Sensor – Device->Advanced->Refresh Background Image
Like the Multisensor , the insight sensor has an option to create an iBeacon and Remote-control
functionality.
2.10.1 Mask
In EcoStruxure Building Operation, rezoning makes it easy to adapt your configuration to changes in
the building's floor plan when walls are added or removed. When physical spaces are dynamic, room
sizes change and the camera’s field of view needs to be adjusted accordingly.
In such situations, you use masks to configure which part of the thermal imaging area in the
SpaceLogic Insight-Sensor’s People Count sensor to include. For example, you may originally start
with a larger area and now need to reduce it to allow for people counting in a much smaller setting.
Before working with mask objects, there are several terms and concepts you may want to become
familiar with.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 16 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
• Mask: Defines the areas of the camera's field of view to use when counting and ignoring people
(that is, the inclusion and exclusion areas)
• Inclusion area: Specifies the portion of the camera's view to use when counting people.
• Exclusion area: Identifies a portion of an inclusion area that the camera should ignore.
• Point: Includes an X and Y coordinate. Three or more points define an inclusion or exclusion
polygon.
• Polygon: Identifies an inclusion or exclusion area. Formally, it is a closed area with at least 3
points.
2.10.2 Adding an Inclusion Area
Click the provided button on the Basic Tab to add an Inclusion Area. For more information,
see Creating an Insight-Sensor Mask topic on WebHelp.
Once you click the button to add an inclusion area, you will see a rectangular area display by default
with a table of 4 X and Y coordinate values. You enter and remove values from that inclusion area
table as necessary to specify the area that the camera will cover. You also need to modify the points
that were created.
If you do not add any areas in the mask object, the sensor then uses the maximum field of view range
in which to count people.
The Insight-Sensor appears as a green circle at location X=0, Y=0.
You cannot save the mask with any less than 3 points in the table. Once you define a valid area, the
Save button displays and you can now click Save.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 17 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
2.10.3 Adding an Exclusion Area
Within the inclusion area, you can add another area that you wish to exclude from the camera’s field
of vision. For instance, you may wish to click the button to create an Exclusion Area of any shape
within the original inclusion area.
Removing an area from people counting using an exclusion area within an inclusion area.
Once you have created a valid exclusion area, you can click the Save button.
You can create multiple inclusion and exclusion areas. As a result, you can right-click the inclusion
area or exclusion area text to display a context menu for that area. Click the Clear all points command
in that menu to clear the points from the selected area. In this example, the command clears the
points from the exclusion area.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 18 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
You can then start to rebuild the exclusion area by clicking the Add a Point command in the context
menu. Finally, you can also delete the entire area or figure by clicking the Delete area command.
2.10.4 Segment People Count Inputs
The thermal imaging camera in the sensor takes an image every two minutes and that image is
compared to the background image to allow people count calculation.
In the EcoStruxure BMS configuration, the segment people count input binds to the Value property
of the people count sensor. From a run-time standpoint, the segment people count input is an integer
data type in the EcoStruxure BMS that displays the people count.
For more information, see webhelp topic Configuring Segment People Count Inputs in the RP
Controller .
2.11 DALI support for Input Devices
2.11.1 Overview
This is the first release that supports the DALI Inputs Devices.
In addition to the DALI gears (Lights), the 2 following CRS DALI modules supports Electronic Control
Devices (ECD):
• DALI with power distribution: RP-C-EXT-DALI-1-PD
• DALI without power distribution: RP-C-EXT-DALI-1
A CRS DALI module can support up to 16 devices (ECDs) on the DALI bus
Each ECD can support up to 4 inputs (DALI instance).
4 types of inputs are supported:
• Push buttons (IEC 62386-301)
• Absolute input devices (IEC 62386-302)
• Occupancy sensor (IEC 62386-303)
• Light sensor (IEC 62386-304)
2.11.2 Features available
Control Device:
• “Discovery All” control devices connected on the DALI bus in the Device Discovery
• “Discovery New” control devices connected on the DALI bus in the Device Discovery
• Can create up to 16 “Control Devices” object for a CRS DALI module and associate them
with discovered devices
• Select the Operating Mode of the ECD (default value is 0).
Note: with some devices, the default Operating Mode (0) is not supporting DALI instance
and need to be modified in order to use the device.
• View device traceability information (HW, FW version, S/N) and status
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 19 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Push Button instance:
• Define the instance ID corresponding to the Push Button (information provided in the ECD
manufacturer documentation)
• Enable/Disable the instance on the ECD
• Allow to set the time a button should be pressed before the ECD considers it as stuck (10s
steps)
• The value of the inputs corresponds to the state of the push button: Pressed
(True)/Released (False). When the state of the push button changes, it triggers an event on
the DALI bus that is received by the DALI CRS module and then update the push button
value in the server.
Absolute Input
• 2 different types of inputs can be created in EBO:
o Binary input (2 position switch)
o Analog input (Slider, rotary, switch...)
• Define the instance ID corresponding to the input (information provided in the ECD
manufacturer documentation)
• Enable/Disable the instance on the ECD
• When the value of the input changes, it triggers an event on the DALI bus that is received
by the DALI CRS module and then update the input value in the server.
• It is possible to modify the deadtime period during which the Device will not trigger any
new event. It is also possible to enable the device to periodically send an event on the DALI
when the input value is not changing.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 20 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
• For the Analog Input, it is possible to convert the raw value received from the Device using
top/bottom scale conversion settings.
Occupancy Sensor
• Define the instance ID corresponding to the occupancy sensor (information provided in the
ECD manufacturer documentation)
• Enable/Disable the instance on the ECD
• When the state of the sensor changes, it triggers an event on the DALI bus that is received
by the DALI CRS module and then update the sensor state in the server.
State of the sensor is Occupied (True) / Vacant (False)
• It is possible to modify the deadtime period during which the Device will not trigger any
new event. It is also possible to enable the device to periodically send an event on the DALI
when the sensor state is not changing.
• The DALI events sent by the sensor on the bus can be filtered.
“Occupant/Vacant” events: should be enabled for a presence sensor
“Movement/No Movement” events: should be enabled for a movement sensor
“Repeat” events: can be enable to allow the device to periodically send the sensor state.
• For a movement sensor, a reset timer allows to define how long the occupancy state
should be kept after a movement detection.
Light Sensor
• Define the instance ID corresponding to the occupancy sensor (information provided in the
ECD manufacturer documentation)
• Enable/Disable the instance on the ECD
• When the value of the sensor changes, it triggers an event on the DALI bus that is received
by the DALI CRS module and then update the sensor value in the server.
• It is possible to modify the deadtime period during which the Device will not trigger any
new event. It is also possible to enable the device to periodically send an event on the DALI
when the sensor state is not changing.
An hysteresis (absolute value or percentage) can be set to limit the events on DALI bus
when the light value fluctuates.
• The raw value received from the Device should be converted into a value in Lux using the
light value step and offset settings (corresponding information is provided in the light
sensor manufacturer documentation)
• To allow to calibrate a light sensor, a gain, an offset and a maximum light value properties
are available (similar to Ambien Light Sensors from a Multi sensor or from an Insight
sensor)
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 21 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
2.12 Additional properties for controlling blinds
Three CRS modules have received additional properties for controlling Blinds
• Blind HV
• Blind LV
• Relay10
The additional properties are:
• Up/Down Wiring can be used if the cabling to the up and down motors have been
reversed.
• Endstop at down position for additional control of blind movement
• Up/Down command synchronization to combine with end stop property.
2.13 BACnet MS/TP (Northbound) Support for IP Controllers
(Hardware and Firmware launch 2022)
BACnet MS/TP Northbound properties is visible in the EBO configuration of the RP, supported
hardware and IP controller firmware will not be available until 2022.
BACnet MS/TP will not be supported in currently available hardware models, i.e. those with the RPC-
LCES1T1 platform code. It shall be supported in the RP Pro (platform code RPC-LCES2T2) and next
generation RP Advanced controllers with the RPC-LCES1T2 platform code.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 22 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
3. Known Defects in SpaceLogic IP Controllers
The table below lists all known defects that effect the IP Controller firmware (MP-C, MP-V, RP-C, or
IP-IO controllers, CRS Modules, SpaceLogic sensors and Remote Control).
Defect ID preceded by a ‘*’ is new for this release.
Defect Known Defects
ID Functionality Description Workaround/Solution
Program Execution Overrun
Acknowledge or Recheck the alarm to
40351 Alarm Alarms occasionally show up in
clear it.
the Alarms view
When creating a new alarm, Ignore. This property is
38318 Alarm there may be an error displayed unimplemented in MP Series (MP-
on the Shunt variable property C/V) 1.00.01 firmware.
EBO BACnet Event Enrolment Do not configure an EBO Event
accepts Command Failure Event Enrolment with Event Parameters
41537 BACnet Parameters when written from that specify the Command Failure
3'rd-party device, but doesn't Event Type, when using a 3’rd-party
support them B-OWS
Although it is no longer
permissible to set the Retain
Level on the Value and Priority
Array properties of
“commandable” Value objects in
SpaceLogic IP Controllers, a
scenario was discovered in which
Remove the Retain Level setting for
the system does not prevent this
either the Value or the Priority Array
configuration. This scenario can
properties for the affected objects.
occur when an image file for a
43522 BACnet Alternatively, perform a Download All
SpaceLogic IP Controller is
command, which will remove the
created using a Standard
Retain Level setting for the Value
Application file, and the image is
property.
used to perform a Bottom-up
Deploy operation. When the
SpaceLogic IP Controller is
subsequently hosted in the
EcoStruxure Building Operation
database, the invalid
configuration was allowed.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 23 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Defect Known Defects
ID Functionality Description Workaround/Solution
When users directly modify the
Value property of MP/RP
“commandable” Value objects,
the Value property is not
retained in the EBO database,
even when Retained is set to
Warmstart or Coldstart.
42939 BACnet None
Although the MP/RP controller
will still retain the value written
to the Value property when the
controller restarts, EBO will not
re-write this value when a
Download or Download All
command is later executed.
MPC: RPC: Download may fail on
a daisychain network when a
41634 BACnet multi-stage uprev is required for Repeat uprev on failed controllers
supplementary firmware file
download.
In EBO 3.1, “commandable”
Value objects in MP/RP may no
longer have a Retain Level set on Users should not attempt to set the
the Value property, while Retain Retain Level on both the Value
43338 BACnet
Level is also set of any of the property and the Priority Array
Priority Array elements. This is property.
true for Analog, Binary, and
Multistate Value objects.
Association of existing blind is
removed when another blind
45423 Blind None
with same address is connected
and discovered
45119 Other Blind HV SMI: Controlling blind Leave off for at least 10 seconds
does not always work if certain
blinds (Warema,
Dunkermotoren) is power
interrupted for a short time
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 24 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Defect Known Defects
ID Functionality Description Workaround/Solution
Blind SMI: If two blinds with
same addresses are discovered, Re-run discovery or do not reset CRS
45438 Blind SMI the result shows one additional module (do not disconnect 24V of
record with Keyid =0 and CRS)
manufacturer as 'Unknown'
Re-run discovery in case of incorrect
Blind HV SMI: Discovery gives results.
45508 Blind SMI incorrect results for blinds with If the association is removed,
same address ' 0' manually associated again by
comparing KeyId.
Wait a little between each step,
unable to reproduce issue when
Blind HV SMI: Blind position and waiting approximately a second
angle is set to incorrect value between steps.
45528 Blind SMI
intermittently when changed Avoid setting blind values with chains
using Room Unit of quick commands, such as
workstation where you can set the
value to 50 in a single step.
SMI: Duplicate records shown in
45342 Blind SMI discovery if motors with same Re-run the discovery.
address are connected.
CRS: On performing Upload on a
dissociated proxy, keyid is
45367 Other populated in the drive keyid and None
manufacturer fields of blind
property
When using the EBO binding tool
to make a binding to a DALI Light
Double-click the object in the
or DALI Colour Light, the object
browser to display the properties of
42911 CRS browser does not display the
the object rather than using the
properties of the object when
down arrow.
the down arrow is clicked as it
does for other objects.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 25 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Defect Known Defects
ID Functionality Description Workaround/Solution
The tool tip for the Current value
(%) property in Blind objects
indicates that a value is out of
43468 CRS range if the value is greater than None
100%, although this condition is
expected in cases where Blinds
are resynchronized.
When using the Save As
command to save a CRS Module
Diagnostic File (Crash Report,
Alternatively, uses may choose to
System Information, Trace Log),
open the file in a text editor, then
EBO does not present progress
save the file. Although Workstation
indication as it prepares to save
43494 CRS will still not accept user input for the
the file to disk. When using the
same amount of time as when the
Save As command to save a
Save As command is used, users will
Diagnostic File, Workstation may
receive a progress indicator.
be unresponsive as the file is
being saved. This time is typically
less than 2 minutes.
Light DALI: Error in Light
discovery if MAC is not upreved
45067 DALI None
during the module/application
uprev
CRS: Starting CRS DALI module
with DALI bus disconnected Restart the module after the DALI
43362 DALI
never recovers when the DALI cable is connected.
bus is reconnected
Some settings object properties
do not persist through an Erase
database operation. Affected
properties are: Display network Re-configure these properties after
41468 Erase db.
information, Hand override doing an Erase database.
control, Sensor bus, Ethernet
port 2, Bluetooth and Whitelist
settings object properties.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 26 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Defect Known Defects
ID Functionality Description Workaround/Solution
The behavior of MP Series (MP-
C/V) and AS-B supervised input
reliability is not consistent with
CIO:
The CIO 10k NC series/parallel
supervised input reliability is
open circuit for resistance >60k
and is unreliable for resistance
between 12k and 60k.
The MP Series (MP-C/V) and as-B
10k NC series/parallel supervised
input reliability is open circuit for
resistance >12k.
The CIO 10k NC series/parallel
supervised input reliability is
36189 IO None
short circuit for resistance <300
ohms and is unreliable for
resistance between 300 ohms
and 4.2k.
The MP Series (MP-C/V) and as-B
10k NC series/parallel supervised
input reliability is short circuit for
resistance < 4.2k.
Same behavior for NO
series/parallel and similar
behavior for NO series, NC
series, NO parallel and NC
parallel when value is not On or
Off
IO points locally configured using
front panel display are
37136 IO None
unconfigured when an IO point is
created using EBO
Loop object - unable to bind to Use the Binding Editor and bind
Loop
38274 the Setpoint Reference property directly to the Setpoint property
Object
(disabled). shown under the Variables group.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 27 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Defect Known Defects
ID Functionality Description Workaround/Solution
Use a value object bound to the Loop
The value of Loop object
Loop setpoint reference and set the retain
41005 Setpoint does not persist
Object level of the value object to cold start
through warm start or cold start
retained.
If there is not enough memory
the MP Series (MP-C/V) goes
Reduce the size of the application
37134 MP offline instead of showing an
and download again.
error message
Loss of the MP-V Actuator Auto-
calibrate Mode From Factory Is
If possible, always do initial power up
not recovered By Factory Reset.
after the controller is mounted on the
This could be a problem if the
38151 MP-V VAV box. Or invoke the stroke
controller is powered up before
calibration through the VAV object
it is correctly mounted on a VAV
using WorkStation.
box.
RP-C using Custom Type crashes
43680 MPX after upgrade to firmware None
package 3.01.01.00631
MP-C/V: In a multi-server Import, assign and download
environment, the list of available firmware logged on either on top
35232 MPX firmware is not specific to any server OR directly on the child server.
one server, this can cause Don’t mix and switch between
download failures servers for different operations.
StrToNum() failure in MP Series
(MP-C/V) script programs when
38319 Script None, but probably a rare use case.
converting the Current line
property of the same program.
Event driven script can be saved Delete the script and make sure you
42820 Script and downloaded to older RPC use the 'Script Program' type not
version that does not support it. 'Script Event' Program type
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 28 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Defect Known Defects
ID Functionality Description Workaround/Solution
Trace Log entries like the
following appear in the
EcoStruxure Building Operation
Server Trace Log when a
SpaceLogic IP Controller is
downloaded, corresponding to
the built-in SpaceLogic Series
System Alarm objects:
Trace
43534 [Link] None
Log
MpxEventEnrollmentProxy failed
to write ResetDelay. Property
may not exist in the current
device firmware version
(AsyncCommands)
These Trace Log entries do not
indicate any operational
problem.
After a restart, the trend logs
37723,
show property changed by a None
37770 Trends
huge number of seconds
Set the buffer size down to 100.
Error changing Trend Log buffer
33140 Enable\Disable and then set the
Trends size
buffer size back up to 50K
Extended trend logs monitoring
MP Series (MP-C/V) BACnet There is no impact on reports if a
trend logs contain duplicate record with same date-time is read
records (two records for the from ES. If a duplicate record (with
same date and time same date and time) is read again by
37737
Trends stamp). NOTE: in all cases there the Reporting agent, then existing
are no duplicate records in the record in reports database that
BACnet trends in the MP Series matches the date-time would be
(MP-C/V) that the ETLs are updated.
monitoring.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 29 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Defect Known Defects
ID Functionality Description Workaround/Solution
Trend logs could be truncated
after a power cycle or an
upgrade. This should be a very
Use the Extended trend logging
rare case due to the circular
feature in the server to back up
backup storage in flash wraps
critical log data. Ensure that the
37756 and starts to overwrite older
Trends Extended trend log is configured for a
data. This should usually take a
relatively short maximum transfer
very long time to happen. For
interval – perhaps a day or less.
example, a controller with 40
logs, at 10 minute intervals,
would take 13 days to roll over.
Trend Log records that have
been cleared by setting the
37771 Trends Record count property to 0 are Delete and re-create the trend log.
added back to Log Buffer after a
restart.
Deleting trend log can take a
significant and variable amount
of time depending on how much
data they have accumulated. A
37826 Trends None
new trend log with little or no
data may take much longer than
a trend log that has been
running a long time.
First value after warm start for
41554 Trends Room unit temperature trend None
log is incorrect.
RPC: Error saving a BACnet Trend
Log when monitoring the RP-C
45520 Trends None
Free memory or CPU%
properties
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 30 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Defect Known Defects
ID Functionality Description Workaround/Solution
The new firmware files are sent to
each of the selected controllers
sequentially. Activation of the new
firmware takes place only after all
controllers have received the new
firmware files. When all files are
transferred the Upgrade status will
Upgrading a group of MP Series
be “Active firmware scheduled” and
(MP-C/V) controllers with the
38309 Upgrade the Firmware activation time will be
Immediate option does not seem
the current time. Then the Upgrade
to take place immediately.
status will become “Active firmware
in progress” and the Firmware
activation time will become blank.
Then the Upgrade status will become
“Upgrade completed successfully”
and the Firmware activation time will
become 01/01/1970 [Link].
Uprev of firmware may
Perform a Warm start command and
40653 Upgrade occasionally end with a
do the uprev again.
Download Failed error.
Uprev of firmware may
Perform a Warm start command and
41284 Upgrade occasionally end with an
do the uprev again.
Activation failed error.
Internal testing revealed an
intermittent problem when
monitoring the System Status
property of SpaceLogic Sensor
43137 RU No known workaround.
devices when monitored in the
Watch Window of EBO
Workstation. The System Status
could appear as “Invalid”.
RU: Disabling Allow scene button
45241 RU doesn't work, and the buttons None
are still available
RPC RU (LCD touch screen):
None, this is a new design for CRS
When upgrading to 3.01/02 the
43451 RU light and blinds to provide consistent
user experience is completely
behavior.
different from previous versions
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 31 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Defect Known Defects
ID Functionality Description Workaround/Solution
List of firmware packages is
40935 empty if Firmware folder is Use Control Panel
Work-Station
selected in System Tree
Custom Type: Importing a CT
that contains a Zigbee device Create a dummy Zigbee network,
Zigbee
45563 and the Zigbee Type does not import the required Zigbee UDT's
Custom Type
exist in the server, the import then do the import.
fails
Zigbee RP-C: Permit join and
Use the buttons "Permit join" or
Zigbee Stop joining operations from the
45387 "Stop joining" from the Device
(RP-C) context menu in system tree
Discovery menu
don't work
ZGB: Two green power devices
Caused by swapping Zigbee adaptors
(SED_CO2_G_5045) detected as
between RP-C’s. If you need to do
45286 Zigbee offline and have not yet
this you’ll need to delete the Zigbee
recovered after 18 hours when
network and re engineer.
connected to the RPC
After a FW upgrade of the DALI
module, one of the DALI color
Manual edit of light value after a FW
*43387 DALI lights go to 100% and remains
upgrade
there until the application
changes the light level.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 32 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
4. Field Defects Fixed in EcoStruxure Building Operation
v4.00.01 Release
The table below lists all SpaceLogic IP Controller Series fixes, (MP-C, MP-V, RP-C, or IP-IO
controllers, CRS Modules, SpaceLogic sensors and Remote Control).
Note: a PSS Ticket ID off 99 = Alpha / Beta, 97 = Bench testers
Functionality Fixed in Defect ID PSS
Summary EBO/IP Ticket ID
IP
MP-C: download all fails with "property write access
denied" error 43579 65979069
IP
Documentation Defect RSTP Max Age and Maximum
controller count in an RSTP ring 45237 70673142
IP
RPC: Inconsistency between device report and manifest
file 45577 99
DALI: When the value is outside of the minimum and IP
maximum properties the Current Value property shows
the requested value not the current value 45585 99
Architectural guidelines should provide a warning for the IP
number of trend log records used in SmartX IP
controllers 45656 72472518
IP 72936452
75339876
76771344
76921160
76914601
78264895
78988568
83525821
RU: Cover Model not being read correctly 46054 79543373
IP
10Ch relay blinds: Cannot open or close twice in a row 46664 99
IP
Zoning : Incorrect calculation of average luminosity for
an area when a Multisensor is out of order 47046 99
IP
Issue in FBP after restart of RP-C 47453 80706363
IP
BACnet name gets truncated from 32 to 16 characters
upon controller restart. 47553 81322019
IP
RPC-DALI - Dali light stays at 100% after a 230Vac
power cycle of the CRS Dali module 47577 99
IP
FBP: Updating PVB InitValue while bound values are
forced causes incorrect output 47584 77641611
Incorrect value on a second digital input on RPC when IP
associated with an input DI on Dali ,Blind, Light 1-10V
module 47639 99
IP
MP/RP BACnet Trend fail with Boolean and Multistate
variables 47677 81897871
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 33 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Functionality Fixed in Defect ID PSS
Summary EBO/IP Ticket ID
IP
DALI Lights: ramp time not considered after an OFF
command with a light group 47727 99
IP
Current Color temperature does not change when color
setpoints is set to light all lights 47776 99
IP
THRX : RPC v1 in bootloop after a uprev from RTXC
3.03.01.00010 to THRX 4.00.00.20086 47861 97
DALI Color performance: It can take about 6 seconds IP
between the time the 1st light is switched on and the
time the last light is switched on (with 8 lights) in the
same room 47956 99
Power ON level: After power cycle some lights are IP
switched on even though the power on level in EBO is
always set to 0% for a dali color light 47962 99
CRS: Dali Color Light : RPC send the wrong value to the IP
DALI module when we unforce the Color Value Control
on the DALI Color temp Light 47987 99
IP
Script Event Program not triggered when sending a light
command through the room unit . 48069 97
Segment Analog input using Max, Min , Average should IP
not consider the local inputs that are offline as part of its
calculation 48114 99
IP
DALI Performance - It takes 2 seconds to switch on/off 8
lights connected to one CRS DALI module 48115 99
Dali Group : When I send the command 100% the light IP
switches to 100% but when I send 0% the light stay à
30% and never switch to 0%. 48144 97
FBP RI object output displays NaN if room sensor is IP
disconnected from sensor bus of RP-C and doesn’t reset
when room sensor reconnects. 48149 83171014
IP
RPC Pro - Uprev to 4.00.00.20133 universal package
due to failed EFR32 update 48153 97
IP
I-S : Insight Sensor crashed on automatic background
refresh 48193 97
Erroneous signal value ( ZigBee) , offline value IP
impacting segment inputs and causing negative impact
on operation 48198 99
IP
THRX: Uprev Timestamp is incorrect in recent Uprev
Log section of Device Report 48257 97
IP
BNP Application - Download all objects fail and takes the
device offline 48553 97
IP
Creating an external reference don't work using Swedish
Language in Workstation 48560 85727204
IP
Zigbee RP - 7 commissioned ZigBee devices ( MTH +
Green power) went offline after 6 days during runtime 48577 99
EBO
MPX Controllers do not retain the default priority level
when point is duplicated, or Custom Type changed. 41776 58348668
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 34 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Functionality Fixed in Defect ID PSS
Summary EBO/IP Ticket ID
EBO
MPX: Unable to create a generic image despite
controller being attached to a custom type 43600 66092633
CRS: Relay CRS Module Relay output Current status, EBO
Last result, Max retries, Error count and Failure count
status registers not working 44471 99
CRS Zoning: Digital segment setting, if the EBO
active/Inactive texts are used, after zoning the bind is in
error. 45965 99
RPC Search: Selecting 'Include types' in the Search EBO
takes 18 to 24 seconds to populate the list view with a
typical CRS-HVAC application 46045 99
EBO
CT MVS: It should be possible yo instantiate a RP with
new builtin objects in CRS module to 3.2 46736 99
EBO
SmartX Controller: Unable to relinquish digital output 46107 73964188
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 35 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
5. Important Engineering Information
Important engineering information with regard to the EcoStruxure Building Operation IP Controller
(MP-C/V, IP-IO, and RP-C) is listed below.
5.1 SpaceLogic IP Series (MP-C/V, IP-IO, and RP-C) Factory
Firmware
When first powering up a new SpaceLogic IP Series Controller it is important to verify that the
controller has the latest firmware build loaded for the version of EcoStruxure Building Operation
build being used. Please see the compatibility matrix in section 2 and section 8.1 for details on
applying the latest firmware.
5.2 SpaceLogic IP Series (MP-C/V, IP-IO, and RP-C) BACnet
When a user imports an SpaceLogic IP Series Controller with Value or Output objects, they may
observe a warning in the import dialog (in addition to the yellow progress bar):
2018-06-07 [Link] WARNING: Property "RelinquishDefault" in object "~/BACnet Interface/IP
Network/DeviceName/Application/ObjectName" was configured RetainLevel, but target version
does not allow that.
This warning does not indicate a failure and may be safely ignored.
5.3 Connected Room Solution – Light & Blind
The Lights and Blinds connected to the CRS modules should be tested for compatibility / verified
with CRS.
5.4 Connected Room Solution – DALI Module
If moving a DALI module that has been configured from one RP-C to another RP-C, upon
discovering new lights on the second RP-C will have unpredictable results, use discover all.
5.5 Connected Room Solution – DALI discovery
Before attempting to discover DALI lights it is important to ensure that the CRS module (LV or HV)
has been powered up for at least five minutes to allow the system to stabilise.
5.6 Zigbee Engineering
5.6.1 Zigbee Device import files clarification
Each Zigbee physical devices supported by EBO need a dedicated Zigbee Device Import File. This file
describes functions and abilities specific to the physical device. You can think of it like a logical device
(driver) that EBO needs to be able to setup the physical device under a Zigbee network.
There are two variants of Zigbee Device import files. Automation Server (AS) files and RP Controller
(RP) files. If you intend to setup a Zigbee Physical device under AS choose file names with prefix AS.
If your Zigbee device runs under a RP choose file names with prefix RP. Zigbee Device Import Files
can be downloaded from Schneider BMS Application site.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 36 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Above picture shows two variants of same Zigbee physical device as you can find then on Schneider
BMS site. Note the prefix difference AS or RP.
5.6.2 Downloading Zigbee Device import files
Zigbee device types are not included in the EBO installation. They must be downloaded to your PC
and imported to the Type Library as “Zigbee Device import files”, before the corresponding Physical
Zigbee device can be configured in EBO. Zigbee Device Import File can be downloaded from
Schneider BMS Application site.
5.6.3 Improved handling of Zigbee Device import files
In EBO 4.0 the handling of Zigbee Device import files has been improved. The files are still imported
to EBO, but now the device type is imported to the Type Library instead. To add a Zigbee Device
Import file to the Type Library simply download the file to your hard drive and point to the location
by pressing the icon and navigate to the directory where the files were downloaded, select the
downloaded file, press OK. The file will be imported to the Type Library.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 Type Library
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 37 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Warning: Engineering with Custom Types pane must be chosen to make Type Library visible.
5.6.4 New way to associate Zigbee physical device with logical device
Drag the logical device from the Type Library to the Zigbee network in the System Tree.
Choose the physical device in Device Discovery and drag it to the logical device in System Tree. Click
on the save icon.
5.6.5 Zigbee configuration in the RP controller
The Zigbee network is created in the IO Resources folder of the RPC.
When creating a Zigbee network select the ‘Zigbee standard security network’, enabling automatic
Zigbee channel detection, this will find the best available channel available.
For the RP-C make sure the Port
reference is set to USB.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 38 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
If the Zigbee channel has been set to ‘Best available’ when the Zigbee interface was created, you
will need to upload to see what channel has been found and the PAN ID.
If the Zigbee network is not set to automatic in the creation wizard it will be necessary to manually
set one, then after a minute do an upload to see the PAN ID to confirm operation.
If all is well the Network status should be ‘online’.
5.6.6 Discovering the Zigbee Green Powered sensors.
First you need to set the Sensors into pairing mode, 1 quick press should be followed shortly by 3
green flashes, meaning it’s been discovered, if you get three red flashes the paring has failed, check
you are in range of the USB adaptor and try again. Also check the sensor is in the decommissioned
mode by doing a long press, you will see 2 orange flashes followed by 2 red flashes, release the
push button after the first red flash.
When the sensor is in paring mode use EBO to discover the devices:
You are not able to create a
sensor object by discovery and
dragging the discovered sensor
object to the Zigbee network,
instead you must use create
New to create the required
sensor object type, then drop on
the sensor object.
Note; it can take some considerable time for all the properties of the SE Green Power sensor to be
obtained, an upload generally speeds things up.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 39 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Also, some object properties are not implemented such as the Green Power and Basic objects.
5.6.7 Removing and replacing Zigbee Device types
By removing all logical device objects of a specific Zigbee device type, you will remove the type
object as well and the device will be removed from the device list in the New device wizard.
Device types cannot be upgraded. If a new version of a “Zigbee Device import file” is released, and
you want to use it in your configuration, you must either import it in parallel or replace the
previous version manually. An already created device cannot be “re-typed”.
5.6.8 Decommissioning GP sensors from an existing Zigbee network
It is essential when decommissioning a Zigbee device i.e. GP sensor (for use on another AS or RP)
that the ‘Remove association’ command is performed from EBO while the Zigbee device is
operating normally (i.e. online and connected to its parent controller).
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 40 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
If you decommission the Zigbee device by pressing the service button on the GP sensor or via the
EBO command ‘Leave’ while it is commissioned but not connected with its host controller, it will
not be possible to re-commission it to the same EBO or RP host.
This is due to cyber security requirements.
The work-around to re-using a GP sensor that has been blocked is to delete the Zigbee network on
the host AS or RP device and re-create it.
5.6.9 Moving Zigbee USB adaptors
Do not swap the Zigbee USB adaptors between RP-C’s or AS-P’s/AS-B’s, for this release, once
plugged in and recognised by the device they will not be recognised again if moved between
devices, without deleting the complete Zigbee network.
5.7 BACnet
5.7.1 Synchronize Bindings of Value and Default Priority Level
Previous EBO versions allowed users to modify the Value property of a BACnet object when a
binding exists on the default Command priority (typically, 16), and vice-versa. As some customers
found this confusing, the system now makes each property read-only when the other contains a
binding.
For users who wish to maintain the previous behaviour, a new system setting was added. This
setting is found in <Server>-System-Interface manager-BACnet called ‘Synchronize bindings of
value and default priority level’. When changed from True (default) to False, the system behaves as
before. The setting applies to all BACnet objects in all types of devices – EBO, IP Field Controller,
3’rd-party, etc.
Please see the Technical guide for more detail.
5.8 SMI Blind:
• The hot-plug of motors is not supported in this release. This means that the 230V
supply to the CRS module needs to be off when motors are plugged into the module.
• If a motor needs to be replaced then a new discovery needs to be done. This because
the repair function is not available in 3.2.
• There can be a problem related to discovery of SMI blind motors when it comes to
blinds with the same address . This typically will occur when many new blind motors
are being commissioned due to them defaulting to an address of Zero.
Just re-run the discovery usually resolves.
See also known defect #45423- Association of existing blind is removed when another
blind with same address is connected and discovered
See also known defect #45438- If two blinds with same addresses are discovered, the
result shows one additional record with Keyid =0 and manufacturer as 'Unknown'
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 41 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
5.9 Restoring Optional Properties
This function has now been moved to the IP Controller level so optional properties that are not
available after upgrade can be restored. In particular for this release is the Bluetooth settings,
occupant App white list for the RP-C and for the Sensor expansion module and Room unit
properties.
Please note that if the object is a custom type it will need to be checked out before running this
command.
Any new object created with this release will contain the new properties, this command is only
applicable when upgrading from an earlier release.
Once run it is essential to Download all objects.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 42 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
5.10 DALI Inputs Engineering
5.10.1 Discovery of Control Devices
Using the Device Discovery menu, there are 2 new commands for the Control Devices:
• “Discovery All” to discover all control devices connected on the DALI bus (addressing and
association of existing control device will be reinitialized)
• “Discovery New” to discover only the control devices connected on the DALI bus but not
yet discovered.
5.10.2 Association of Control Devices
Once a device has been discovered it can be associated to a Control Device already created using
drag and drop from the device discovery menu or it is possible to create and associate it.
The association can take up to a minute to complete (depending on the number of devices to
associate and the number of inputs pre-configured).
Then the device traceability information (HW, FW version, S/N) and status are available:
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 43 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
Note: with some devices, the default Operating Mode (0) is not supporting DALI instance and need
to be modified in order to use the inputs.
5.10.3 Setting instance ID
Modifying the instance ID of the input requires for the system to push all configuration up to the
DALI device and this takes a few seconds to complete.
5.10.4 Analog Input conversion
For the Analog Input, it is possible to convert the raw value received from the Device using
top/bottom scale conversion settings.
For instance, with a rotary switch: 8 bits resolution (sending value between 0 and 255) in order to
get a value between 0 and 100, the following settings is required:
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 44 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
5.10.5 Light Sensor conversion
The raw value received from the Device should be converted into a value in Lux using the light
value step and offset settings (corresponding information is provided in the light sensor
manufacturer documentation)
For instance, for a sensor 15 bit (0.125 lux/bit, 0-4000 lux):
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 45 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
APPENDIX A – SpaceLogic IP Controller Upgrade Procedures
A1 Upgrading Controller Firmware
Warning for MP controllers and IP-IO: If upgrading from an IP controller that is currently at
[Link] the upgrade might fail the first time, if it does wait until the controller has restarted
and repeat the upgrade a second time.
Down-Rev from a factory installed 4.0 firmware IP Controller to “earlier” versions
It is important to note that any Down-Rev should be undertaken after hosting and prior to connecting
any external equipment ( beyond power and Ethernet connection) and prior to downloading any
application or undertaking any other configuration of the controller.
Warning for IP controllers: Down-Rev is NOT supported between versions once the application is
loaded on to the controller.
Ensure EBO is upgraded first to build v4.0.1.86 before proceeding to upgrade the firmware. If
upgrading an alpha/beta site or alpha/beta CRS hardware please read section A7 first.
Using WorkStation, you can update the firmware of multiple BACnet/IP devices and their attached
SpaceLogic Sensor devices, RP controller expansion modules, and multi-sensors at the same time
with minimum downtime. In particular, the universal upgrade package simplifies the update
process and requires minimal user involvement and coordination. See BACnet/IP Device Firmware
Management for more information.
For more information on updating firmware , see Updating Firmware in BACnet/IP Controllers .
A2 Upgrading CRS Module Firmware
The firmware for the CRS modules is contained within the RP-C firmware package. Online CRS
modules will be updated automatically once the RP-C firmware has been applied.
To view the upgrade status/progress, select the Room Bus folder and add properties as below:
The upgrade is complete once the Firmware upgrade status returns to Normal, when it is queued
for upgrading the status shows ready and when downloading a percentage is shown. Should the
upgrade fail a warm start of the RP-C should be performed.
A3 Upgrading SpaceLogic Sensor Firmware
The SpaceLogic Sensor firmware is upgraded automatically as needed after the host controller
firmware is upgraded. There is new SpaceLogic Sensor firmware for this release as shown below. It
can be verified in the properties of the Room unit device or in the Device Report.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 46 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
WARNING: SpaceLogic IP controllers updates the SpaceLogic Sensor firmware in the background
after the upgrade process seems to be complete as viewed in the Firmware Upgrade Viewer. It can
take several minutes per SpaceLogic Sensor to transfer files and restart them. During this time,
SpaceLogic Sensor may appear offline and sensor data will be unavailable.
Once the upgrade is complete, please refer to section 5.9 above regrading restoring optional
properties.
A4 Upgrading Remote-Control Firmware
The Remote Control will automatically update its firmware when paired to the Multi Sensor and
any key is pressed, after the Multi Sensor has finished upgrading.
A5 Verifying All Firmware Versions
If there is any question about what individual firmware versions are installed in a given controller,
the version information in the firmware package metadata file can be verified against information
in the controller’s device report. Note the relay module uses the same firmware as the Light10V.
Device Report for IP Controller Package 4.00.01.00015 in an RP-C:
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 47 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved
Internal
[ Release Notes ] SpaceLogic IP Controller Firmware – Release Notes v4.00.01
NOTE: The BootApplet version is only upgraded if the current boot BootApplet doesn’t exceed the
minimum Boot Applet required to support the incoming firmware, consequently the BootApplet
version might not match to what is shown in the package meta data file.
To see all the versions in a package, select the following in the Firmware File Manager list and
navigate to Actions Tab and click on Open meta data file to view the Meta Data File:
Change history:
Revision Date Author Description/Change
A 2021-12-20 R. Yanappa Final Version
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800
[Link]
RN_IP Controller (MP/IP-IO/RP/CRS) v4.00.01 RevA– Dec 2021 Page 48 of 48 Company Confidential
© 2021 Schneider Electric, all rights reserved