Heat Load
Heat Load
Rev-0
PROJECT: PEE VEE TEXTILES LTD JAMB - DATE
ROOM Canteen FIRST FLOOR Prepared Approved 18.12.18
ROOM SIZE -IN MTR L 9.8 W 14.2 H 3 AK - SHEET
ROOM SIZE 139.16 m2 1498 ft2 Height = 10.0 ft 28312 ft2 4 of 5
Estimated for SUMMER MONSOON WINTER
CONDITIONS DB-F WB-F %RH GR/LB DB-F WB-F %RH GR/LB DB-F WB-F %RH GR/LB
OUTSIDE 112.0 75.0 20.0 74.7 95.0 83.0 60.0 153.00 45.0 41.0 70.0 32.0
INSIDE 86.0 74.8 60.0 112.7 77.0 67.0 60.0 83.60 68.0 62.1 71.8 73.7
DIFFERENCE 26.0 -38.02 18.0 69.40 -23.0 -41.70
OCCUPANCY 130 ft2/person 11.5 LIGHTING 15 Watts/m2
VENTILATION 217.8 CFM BASED ON: People AIR CHANGES SELECTED
250 PEOPLE 10.0 CFM/PER. 1.5 AC/H 2500 708 2500
Bypass Factor 0.12 Contact Factor 0.88
SUN GAIN/ [Link]. BTU/HR
ITEM AREA ft2 Factor
Summer Monsoon Winter Summer Monsoon Winter
ROOM HEAT LOAD
SOLAR GAIN -GLASS
Glass-N 0 ft2 33 11 7 0.56 0 0 0
Glass-NE 0 ft2 12 11 7 0.56 0 0 0
Glass-E 0 ft2 12 11 7 0.56 0 0 0
Glass-SE 0 ft2 12 11 7 0.56 0 0 0
Glass-S 323 ft2 12 11 74 0.56 2171 1990 13385
Glass-SW 0 ft2 73 113 139 0.56 0 0 0
Glass-W 0 ft2 160 165 118 0.56 0 0 0
Glass-NW 0 ft2 144 118 18 0.56 0 0 0
Sky Light 0 ft2 121 107 36 0.56 0 0 0
SOLAR & TRANS. GAIN - WALLS & ROOF
Wall-NE 0 ft2 28 9 -20 0.34 0 0 0
Wall-E 0 ft2 28 9 -20 0.34 0 0 0
Wall-SE 0 ft2 30 11 -18 0.34 0 0 0
Wall-S 138 ft2 40 21 -8 0.34 1877 985 -375
Wall-SW 0 ft2 54 35 6 0.34 0 0 0
WALL-W 0 ft2 54 35 6 0.34 0 0 0
WALL-NW 0 ft2 38 19 -10 0.34 0 0 0
WALL-N ft2 28 9 -20 0.34 0 0 0
Roof-Sun 1498 ft2 55 36 7 0.10 8239 5393 1049
Roof-Shaded 0 ft2 28 9 -20 0.10 0 0 0
TRANS. GAIN-EXCEPT WALLS & ROOF
ALL GLASS 323 ft2 26.0 18.0 -23.0 0.56 4703 3256 -4160
PARTITION-GLASS ft2 26.0 18.0 -23.0 0.56 0 0 0
PARTITION-WALL 1095 ft2 26.0 13.0 -28.0 0.32 9110 4555 -9811
CEILING 0 ft2 21.0 13.0 -28.0 0.33 0 0 0
FLOOR 1498 ft2 21.0 13.0 -28.0 0.36 11325 7011 -15100
INFILTRATION & OUTSIDE AIR
INFILTRATION 0 CFM 1.08 0 0 0
OUTSIDE AIR 2500 CFM 26.0 18.00 -23.00 0.12 1.08 8424 5832 -7452
INTERNAL HEAT
PEOPLE 250 Nos 270 BTU/P 67500 67500 67500
LIGHTS 2087 Watt 3.4 BTU/Watt 1.0 7097 7097 7097
APPLIANCES 0 Watt 3.4 BTU/Watt 0 0 0
ROOM SENSIBLE HEAT SUB-TOTAL 120446 103619 52133
ADD DUCT HEAT GAIN 1% 1204 1036 521
ROOM SENSIBLE HEAT SUB-TOTAL 121650 104655 52654
ADD SAFETY FACTOR 5% 6083 5233 2633
EFFECTIVE ROOM SENSIBLE HEAT TOTAL 127733 109888 55287 10.64
ROOM LATENT HEAT Summer Monsoon Winter
INFILTRATION 0 CFM 0 0.68 0 0 0
OUTSIDE AIR 2500 CFM -38.02 69.4 -41.7 0.12 0.68 -7756 14158 -8507
PEOPLE 250 Nos 205 BTU/P 51250 51250 51250
APPLIANCES 0 3.4 BTU/Watt 0 0 0
ROOM LATENT HEAT SUB-TOTAL 43494 65408 42743
ADD SAFETY FACTOR 5% 2175 3270 2137
EFFECTIVE ROOM LATENT HEAT 45669 68678 44880
EFFECTIVE ROOM TOTAL HEAT ( SENSIBLE + LATENT) 173402 178566 100167
OUTSIDE AIR Summer Monsoon Winter
SENSIBLE 2500 CFM 26.00 18.00 -23.00 0.88 1.08 61776 42768 -54648
LATENT 2500 CFM -38.02 69.40 -41.70 0.88 0.68 -56878 103822 -62383
GRAND TOTAL HEAT 178300 325156 -16864
CAPACITY TR 14.86 27.10 -1.41
Sensible Heat Factor & Appratus Dewpoint
Dehumified Rise Dehumified CFM Summer Monsoon Winter
[Link] [Link]
Summer 0.74 SHF 54.0 54 28.2 4200 CFM 283 185 -2947 cfm/tr
Monsoon 0.62 SHF 54.0 54 20.2 5027 CFM 101 55 -1062 sft/tr
Winter 0.55 SHF 54.0 54 12.3 4155 CFM 3.00 3.00 3.00 cfm/sft
SUMMER MONSOON WINTER
TONNAGE 14.86 TR TONNAGE 27.10 TR TONNAGE -1.41 TR
AIR QTY 4200 CFM AIR QTY 5027 CFM AIR QTY 4155 CFM
REHEAT 5.23 KW Pan Humidifier Capacity 65.98 LBS/HR
Winter Heating 12.62 KW
TORO WATT INDIA Rev-0
DELHI , INDIA DATE
PROJECT: PEE VEE TEXTILES LTD JAMB DOCUMENT NO. 18.12.18
SUMMARY OF HEAT LOAD CALCULATION FOR HOSPITAL - SHEET
F/C Full Fresh Equipme Lighting Calculated Load Reheat Humidifier 1 of 5
S. Area Occup
height Height air nt Load load Cooling Load (TR) AIR QTY (CMH) (KW) LBH/HR
No. (Sq.m) ancy Remarks
(m) (m) (CMH) (KW) (KW) Summer Monsoon Winter Summer Monsoon Winter Monsoon Winter
a) Canteen FIRST FLOOR 139.16 5.3 5.50 4250 250 0.00 2.09 14.86 27.10 -1.41 4200 5027 4155 5.23 65.98
Add 10% Margin = 1.49 2.71 -0.14 420 503 416 0.52 6.60
AHU 1 Total = 16.35 29.81 -1.55 4620 5530 4571 5.75 72.58
Page 16
GF LT PANEL DG & COMPRESSER
EFFECTIVE ROOM SENSIBLE HEAT TOTAL 46220 25375 -23109 3.85
Page 17
TORO WATT INDIA DELHI , INDIA DOCUMENT NO. Rev-0
PROJECT: PEE VEE TEXTILES LTD JAMB - DATE
ROOM CHIN STRAP & OTHER CONSUMABLES ROOM NO 4 Prepared Approved 18.12.18
ROOM SIZE -IN MTR L 12.4 W 9.2 H 3 AK - SHEET
ROOM SIZE 114.08 m2 1228 ft2 Height = 10.0 ft 23209 ft2 4 of 5
Estimated for SUMMER MONSOON WINTER
CONDITIONS DB-F WB-F %RH GR/LB DB-F WB-F %RH GR/LB DB-F WB-F %RH GR/LB
OUTSIDE 112.0 75.0 20.0 74.7 95.0 83.0 60.0 153.00 45.0 41.0 70.0 32.0
INSIDE 86.0 74.8 60.0 112.7 77.0 67.0 60.0 83.60 68.0 62.1 71.8 73.7
DIFFERENCE 26.0 -38.02 18.0 69.40 -23.0 -41.70
OCCUPANCY 130 ft2/person 9.4 LIGHTING 15 Watts/m2
VENTILATION 178.5 CFM BASED ON: People AIR CHANGES SELECTED
2 PEOPLE 10.0 CFM/PER. 1.5 AC/H 20 580 580
Bypass Factor 0.12 Contact Factor 0.88
SUN GAIN/ [Link]. BTU/HR
ITEM AREA ft2 Factor
Summer Monsoon Winter Summer Monsoon Winter
ROOM HEAT LOAD
SOLAR GAIN -GLASS
Glass-N 317 ft2 33 11 7 0.56 5858 1953 1243
Glass-NE 0 ft2 12 11 7 0.56 0 0 0
Glass-E 0 ft2 12 11 7 0.56 0 0 0
Glass-SE 0 ft2 12 11 7 0.56 0 0 0
Glass-S 0 ft2 12 11 74 0.56 0 0 0
Glass-SW 0 ft2 73 113 139 0.56 0 0 0
Glass-W 0 ft2 160 165 118 0.56 0 0 0
Glass-NW 0 ft2 144 118 18 0.56 0 0 0
Sky Light 0 ft2 121 107 36 0.56 0 0 0
SOLAR & TRANS. GAIN - WALLS & ROOF
Wall-NE 0 ft2 28 9 -20 0.34 0 0 0
Wall-E 0 ft2 28 9 -20 0.34 0 0 0
Wall-SE 0 ft2 30 11 -18 0.34 0 0 0
Wall-S 84 ft2 40 21 -8 0.34 1142 600 -228
Wall-SW 0 ft2 54 35 6 0.34 0 0 0
WALL-W 0 ft2 54 35 6 0.34 0 0 0
WALL-NW 0 ft2 38 19 -10 0.34 0 0 0
WALL-N 0 ft2 28 9 -20 0.34 0 0 0
Roof-Sun 0 ft2 55 36 7 0.10 0 0 0
Roof-Shaded 0 ft2 28 9 -20 0.10 0 0 0
TRANS. GAIN-EXCEPT WALLS & ROOF
ALL GLASS 317 ft2 26.0 18.0 -23.0 0.56 4616 3195 -4083
PARTITION-GLASS ft2 26.0 18.0 -23.0 0.56 0 0 0
PARTITION-WALL 995 ft2 26.0 13.0 -28.0 0.32 8278 4139 -8915
CEILING 1228 ft2 21.0 13.0 -28.0 0.33 8510 5268 -11347
FLOOR 1228 ft2 21.0 13.0 -28.0 0.36 9284 5747 -12378
INFILTRATION & OUTSIDE AIR
INFILTRATION 0 CFM 1.08 0 0 0
OUTSIDE AIR 580 CFM 26.0 18.00 -23.00 0.12 1.08 1954 1353 -1729
INTERNAL HEAT
PEOPLE 2 Nos 270 BTU/P 540 540 540
LIGHTS 1711 Watt 3.4 BTU/Watt 1.0 5818 5818 5818
APPLIANCES 0 Watt 3.4 BTU/Watt 0 0 0
ROOM SENSIBLE HEAT SUB-TOTAL 46000 28613 -31079
ADD DUCT HEAT GAIN 1% 460 286 -311
ROOM SENSIBLE HEAT SUB-TOTAL 46460 28899 -31390
ADD SAFETY FACTOR 5% 2323 1445 -1570
EFFECTIVE ROOM SENSIBLE HEAT TOTAL 48783 30344 -32960 4.07
ROOM LATENT HEAT Summer Monsoon Winter
INFILTRATION 0 CFM 0 0.68 0 0 0
OUTSIDE AIR 580 CFM -38.02 69.4 -41.7 0.12 0.68 -1799 3285 -1974
PEOPLE 2 Nos 205 BTU/P 410 410 410
APPLIANCES 0 3.4 BTU/Watt 0 0 0
ROOM LATENT HEAT SUB-TOTAL -1389 3695 -1564
ADD SAFETY FACTOR 5% -69 185 -78
EFFECTIVE ROOM LATENT HEAT -1458 3880 -1642
EFFECTIVE ROOM TOTAL HEAT ( SENSIBLE + LATENT) 47325 34224 -34602
OUTSIDE AIR Summer Monsoon Winter
SENSIBLE 580 CFM 26.00 18.00 -23.00 0.88 1.08 14332 9922 -12678
LATENT 580 CFM -38.02 69.40 -41.70 0.88 0.68 -13196 24087 -14473
GRAND TOTAL HEAT 48461 68233 -61753
CAPACITY TR 4.04 5.69 -5.15
Sensible Heat Factor & Appratus Dewpoint
Dehumified Rise Dehumified CFM Summer Monsoon Winter
[Link] [Link]
Summer 1.03 SHF 54.0 54 28.2 1604 CFM 397 244 481 cfm/tr
Monsoon 0.89 SHF 54.0 54 20.2 1388 CFM 304 216 -238 sft/tr
Winter 0.95 SHF 54.0 54 12.3 -2477 CFM 1.00 1.00 -2.00 cfm/sft
SUMMER MONSOON WINTER
TONNAGE 4.04 TR TONNAGE 5.69 TR TONNAGE -5.15 TR
AIR QTY 1604 CFM AIR QTY 1388 CFM AIR QTY -2477 CFM
REHEAT 5.40 KW Pan Humidifier Capacity 15.31 LBS/HR
Winter Heating 2.93 KW
TORO WATT INDIA DELHI , INDIA DOCUMENT NO. Rev-0
PROJECT: PEE VEE TEXTILES LTD JAMB - DATE
ROOM EPS STORE GF- ROOM NO -5 Prepared Approved 18.12.18
ROOM SIZE -IN MTR L 8.59 W 9.1 H 3 AK - SHEET
ROOM SIZE 78.17 m2 841 ft2 Height = 10.0 ft 15895 ft2 4 of 5
Estimated for SUMMER MONSOON WINTER
CONDITIONS DB-F WB-F %RH GR/LB DB-F WB-F %RH GR/LB DB-F WB-F %RH GR/LB
OUTSIDE 112.0 75.0 20.0 74.7 95.0 83.0 60.0 153.00 45.0 41.0 70.0 32.0
INSIDE 86.0 74.8 60.0 112.7 77.0 67.0 60.0 83.60 68.0 62.1 71.8 73.7
DIFFERENCE 26.0 -38.02 18.0 69.40 -23.0 -41.70
OCCUPANCY 130 ft2/person 6.5 LIGHTING 15 Watts/m2
VENTILATION 122.3 CFM BASED ON: People AIR CHANGES SELECTED
2 PEOPLE 10.0 CFM/PER. 1.5 AC/H 20 397 397
Bypass Factor 0.12 Contact Factor 0.88
SUN GAIN/ [Link]. BTU/HR
ITEM AREA ft2 Factor
Summer Monsoon Winter Summer Monsoon Winter
ROOM HEAT LOAD
SOLAR GAIN -GLASS
Glass-N 150 ft2 33 11 7 0.56 2772 924 588
Glass-NE 0 ft2 12 11 7 0.56 0 0 0
Glass-E 0 ft2 12 11 7 0.56 0 0 0
Glass-SE 0 ft2 12 11 7 0.56 0 0 0
Glass-S 0 ft2 12 11 74 0.56 0 0 0
Glass-SW 0 ft2 73 113 139 0.56 0 0 0
Glass-W 0 ft2 160 165 118 0.56 0 0 0
Glass-NW 0 ft2 144 118 18 0.56 0 0 0
Sky Light 0 ft2 121 107 36 0.56 0 0 0
SOLAR & TRANS. GAIN - WALLS & ROOF
Wall-NE 0 ft2 28 9 -20 0.34 0 0 0
Wall-E 0 ft2 28 9 -20 0.34 0 0 0
Wall-SE 0 ft2 30 11 -18 0.34 0 0 0
Wall-S ft2 40 21 -8 0.34 1958 1028 -392
Wall-SW 0 ft2 54 35 6 0.34 0 0 0
WALL-W 0 ft2 54 35 6 0.34 0 0 0
WALL-NW 0 ft2 38 19 -10 0.34 0 0 0
WALL-N 144 ft2 28 9 -20 0.34 1371 441 -979
Roof-Sun 0 ft2 55 36 7 0.10 0 0 0
Roof-Shaded 0 ft2 28 9 -20 0.10 0 0 0
TRANS. GAIN-EXCEPT WALLS & ROOF
ALL GLASS 150 ft2 26.0 18.0 -23.0 0.56 2184 1512 -1932
PARTITION-GLASS ft2 26.0 18.0 -23.0 0.56 0 0 0
PARTITION-WALL 843 ft2 26.0 13.0 -28.0 0.32 7014 3507 -7553
CEILING 841 ft2 21.0 13.0 -28.0 0.33 5828 3608 -7771
FLOOR 841 ft2 21.0 13.0 -28.0 0.36 6358 3936 -8477
INFILTRATION & OUTSIDE AIR
INFILTRATION 0 CFM 1.08 0 0 0
OUTSIDE AIR 397 CFM 26.0 18.00 -23.00 0.12 1.08 1338 926 -1183
INTERNAL HEAT
PEOPLE 2 Nos 270 BTU/P 540 540 540
LIGHTS 1173 Watt 3.4 BTU/Watt 1.0 3987 3987 3987
APPLIANCES 0 Watt 3.4 BTU/Watt 0 0 0
ROOM SENSIBLE HEAT SUB-TOTAL 33350 20409 -23172
ADD DUCT HEAT GAIN 1% 334 204 -232
ROOM SENSIBLE HEAT SUB-TOTAL 33684 20613 -23404
ADD SAFETY FACTOR 5% 1684 1031 -1170
EFFECTIVE ROOM SENSIBLE HEAT TOTAL 35368 21644 -24574 2.95
ROOM LATENT HEAT Summer Monsoon Winter
INFILTRATION 0 CFM 0 0.68 0 0 0
OUTSIDE AIR 397 CFM -38.02 69.4 -41.7 0.12 0.68 -1232 2248 -1351
PEOPLE 2 Nos 205 BTU/P 410 410 410
APPLIANCES 0 3.4 BTU/Watt 0 0 0
ROOM LATENT HEAT SUB-TOTAL -822 2658 -941
ADD SAFETY FACTOR 5% -41 133 -47
EFFECTIVE ROOM LATENT HEAT -863 2791 -988
EFFECTIVE ROOM TOTAL HEAT ( SENSIBLE + LATENT) 34505 24435 -25562
OUTSIDE AIR Summer Monsoon Winter
SENSIBLE 397 CFM 26.00 18.00 -23.00 0.88 1.08 9810 6792 -8678
LATENT 397 CFM -38.02 69.40 -41.70 0.88 0.68 -9032 16487 -9906
GRAND TOTAL HEAT 35283 47714 -44146
CAPACITY TR 2.94 3.98 -3.68
Sensible Heat Factor & Appratus Dewpoint
Dehumified Rise Dehumified CFM Summer Monsoon Winter
[Link] [Link]
Summer 1.03 SHF 54.0 54 28.2 1163 CFM 396 249 502 cfm/tr
Monsoon 0.89 SHF 54.0 54 20.2 990 CFM 286 211 -229 sft/tr
Winter 0.96 SHF 54.0 54 12.3 -1847 CFM 1.00 1.00 -2.00 cfm/sft
SUMMER MONSOON WINTER
TONNAGE 2.94 TR TONNAGE 3.98 TR TONNAGE -3.68 TR
AIR QTY 1163 CFM AIR QTY 990 CFM AIR QTY -1847 CFM
REHEAT 4.02 KW Pan Humidifier Capacity 10.48 LBS/HR
Winter Heating 2.00 KW
TORO WATT INDIA DELHI , INDIA DOCUMENT NO. Rev-0
PROJECT: PEE VEE TEXTILES LTD JAMB - DATE
ROOM SHELL FOR BUFFIN GF- ROOM NO -6 Prepared Approved 18.12.18
ROOM SIZE -IN MTR L 17 W 9.7 H 3 AK - SHEET
ROOM SIZE 164.90 m2 1775 ft2 Height = 10.0 ft 33548 ft2 4 of 5
Estimated for SUMMER MONSOON WINTER
CONDITIONS DB-F WB-F %RH GR/LB DB-F WB-F %RH GR/LB DB-F WB-F %RH GR/LB
OUTSIDE 112.0 75.0 20.0 74.7 95.0 83.0 60.0 153.00 45.0 41.0 70.0 32.0
INSIDE 86.0 74.8 60.0 112.7 77.0 67.0 60.0 83.60 68.0 62.1 71.8 73.7
DIFFERENCE 26.0 -38.02 18.0 69.40 -23.0 -41.70
OCCUPANCY 130 ft2/person 13.7 LIGHTING 15 Watts/m2
VENTILATION 258.1 CFM BASED ON: People AIR CHANGES SELECTED
20 PEOPLE 10.0 CFM/PER. 1.5 AC/H 200 839 839
Bypass Factor 0.12 Contact Factor 0.88
SUN GAIN/ [Link]. BTU/HR
ITEM AREA ft2 Factor
Summer Monsoon Winter Summer Monsoon Winter
ROOM HEAT LOAD
SOLAR GAIN -GLASS
Glass-N 402 ft2 33 11 7 0.56 7429 2476 1576
Glass-NE 0 ft2 12 11 7 0.56 0 0 0
Glass-E 0 ft2 12 11 7 0.56 0 0 0
Glass-SE 0 ft2 12 11 7 0.56 0 0 0
Glass-S 0 ft2 12 11 74 0.56 0 0 0
Glass-SW 0 ft2 73 113 139 0.56 0 0 0
Glass-W 167 ft2 160 165 118 0.56 14963 15431 11035
Glass-NW 0 ft2 144 118 18 0.56 0 0 0
Sky Light 0 ft2 121 107 36 0.56 0 0 0
SOLAR & TRANS. GAIN - WALLS & ROOF
Wall-NE 0 ft2 28 9 -20 0.34 0 0 0
Wall-E 0 ft2 28 9 -20 0.34 0 0 0
Wall-SE 0 ft2 30 11 -18 0.34 0 0 0
Wall-S ft2 40 21 -8 0.34 1999 1050 -400
Wall-SW 0 ft2 54 35 6 0.34 0 0 0
WALL-W 148 ft2 54 35 6 0.34 2717 1761 302
WALL-NW 0 ft2 38 19 -10 0.34 0 0 0
WALL-N 147 ft2 28 9 -20 0.34 1399 450 -1000
Roof-Sun 0 ft2 55 36 7 0.10 0 0 0
Roof-Shaded 0 ft2 28 9 -20 0.10 0 0 0
TRANS. GAIN-EXCEPT WALLS & ROOF
ALL GLASS 569 ft2 26.0 18.0 -23.0 0.56 8285 5736 -7329
PARTITION-GLASS ft2 26.0 18.0 -23.0 0.56 0 0 0
PARTITION-WALL 843 ft2 26.0 13.0 -28.0 0.32 7014 3507 -7553
CEILING 1775 ft2 21.0 13.0 -28.0 0.33 12301 7615 -16401
FLOOR 1775 ft2 21.0 13.0 -28.0 0.36 13419 8307 -17892
INFILTRATION & OUTSIDE AIR
INFILTRATION 0 CFM 1.08 0 0 0
OUTSIDE AIR 839 CFM 26.0 18.00 -23.00 0.12 1.08 2827 1957 -2501
INTERNAL HEAT
PEOPLE 20 Nos 270 BTU/P 5400 5400 5400
LIGHTS 2473 Watt 3.4 BTU/Watt 1.0 8410 8410 8410
APPLIANCES 0 Watt 3.4 BTU/Watt 0 0 0
ROOM SENSIBLE HEAT SUB-TOTAL 86163 62100 -26353
ADD DUCT HEAT GAIN 1% 862 621 -264
ROOM SENSIBLE HEAT SUB-TOTAL 87025 62721 -26617
ADD SAFETY FACTOR 5% 4351 3136 -1331
EFFECTIVE ROOM SENSIBLE HEAT TOTAL 91376 65857 -27948 7.61
ROOM LATENT HEAT Summer Monsoon Winter
INFILTRATION 0 CFM 0 0.68 0 0 0
OUTSIDE AIR 839 CFM -38.02 69.4 -41.7 0.12 0.68 -2603 4751 -2855
PEOPLE 20 Nos 205 BTU/P 4100 4100 4100
APPLIANCES 0 3.4 BTU/Watt 0 0 0
ROOM LATENT HEAT SUB-TOTAL 1497 8851 1245
ADD SAFETY FACTOR 5% 75 443 62
EFFECTIVE ROOM LATENT HEAT 1572 9294 1307
EFFECTIVE ROOM TOTAL HEAT ( SENSIBLE + LATENT) 92948 75151 -26641
OUTSIDE AIR Summer Monsoon Winter
SENSIBLE 839 CFM 26.00 18.00 -23.00 0.88 1.08 20732 14353 -18340
LATENT 839 CFM -38.02 69.40 -41.70 0.88 0.68 -19088 34843 -20936
GRAND TOTAL HEAT 94592 124347 -65917
CAPACITY TR 7.88 10.36 -5.49
Sensible Heat Factor & Appratus Dewpoint
Dehumified Rise Dehumified CFM Summer Monsoon Winter
[Link] [Link]
Summer 0.98 SHF 54.0 54 28.2 3005 CFM 381 291 383 cfm/tr
Monsoon 0.88 SHF 54.0 54 20.2 3013 CFM 225 171 -323 sft/tr
Winter 1.05 SHF 54.0 54 12.3 -2100 CFM 2.00 2.00 -1.00 cfm/sft
SUMMER MONSOON WINTER
TONNAGE 7.88 TR TONNAGE 10.36 TR TONNAGE -5.49 TR
AIR QTY 3005 CFM AIR QTY 3013 CFM AIR QTY -2100 CFM
REHEAT 7.47 KW Pan Humidifier Capacity 22.14 LBS/HR
Winter Heating 4.23 KW