Gypsum Fire Plaster MP 75 L Data Sheet

This document provides information on MP 75 L Fire gypsum-based plaster for increased fire protection. It can provide fire resistance for concrete ceilings and walls up to REI 240, and for concrete supports and beams up to R 180. It is suitable for application by machine and offers high yield. The plaster comes in white and is designed for use on interior surfaces for passive fire protection of load-bearing building elements. Application thickness depends on the required fire resistance rating.

Uploaded by

anhnguyenhai
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
78 views4 pages

Gypsum Fire Plaster MP 75 L Data Sheet

This document provides information on MP 75 L Fire gypsum-based plaster for increased fire protection. It can provide fire resistance for concrete ceilings and walls up to REI 240, and for concrete supports and beams up to R 180. It is suitable for application by machine and offers high yield. The plaster comes in white and is designed for use on interior surfaces for passive fire protection of load-bearing building elements. Application thickness depends on the required fire resistance rating.

Uploaded by

anhnguyenhai
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Note on English translation / Hinweise zur englischen Fassung

This is a translation of the product data sheet valid in Germany.


All stated details and properties are in compliance with the regulations of the German standards
and building regulations. They are only applicable for the specified products, system components,
application rules, and construction details in connection with the specifications of the respective
certificates and approvals.
Knauf Gips KG denies any liability for applications outside of Germany as this requires changes
acc. to the respective national standards and building regulations.

Plaster and Façade Systems

P911.de
Product Data Sheet  2021-06

MP 75 L Fire
Gypsum-based plaster for increased fire protection

Product description Properties and added value


Composition ■ Fire resistance
MP 75 L Fire consists of gypsum as a binder in combination with a special ▪ for concrete ceilings and walls up to REI 240
mix of lightweight aggregates and additives to ensure good machine ▪ for concrete supports and beams up to R 180
application. ▪ for steel beams and columns up to R 120
▪ for profiled sheet metal with concrete up to REI 120
Storage
Store the bags frost-free on wooden pallets in a dry environment. Can be ■ Can be applied with machine
stored for approx. 6 months. Seal damaged and opened bags airtight and ■ Particularly high yield
use them first.
■ Gypsum-based
Quality
■ For interiors
In compliance with ETA-11/0229, the product is subject to initial type testing
and continuous factory production control and bears the CE marking. ■ Colour white

www.baubiologie-ibr.de/en/
P911.de MP 75 L Fire
Gypsum-based plaster for increased fire protection

Field of application
MP 75L Fire has been developed specially for passive fire protection in
interiors.
It is designed to protect the load bearing capacity of the coated structural
elements in the event of a fire for the duration of the fire resistance stipulated
by the building supervision authorities for:
■ Concrete slabs and walls
■ Concrete columns and beams
■ Steel columns and beams
■ Trapezoid sheet metal with concrete

Application
Substrate Pretreatment
Untreated steel and profiled sheet metal. Inspect for rust and remove if required. Sheet metal profiles must then be treated with an epoxy resin, alkyd or
zinc-silicate based corrosion-proof coating in accordance with the manufacturers instructions.
Steel and profiled sheet metal with Firmly adhering coatings on the basis of alkalis, epoxies or zinc silicates or on a galvanized basis are suitable
existing coatings as a substrate for MP 75 L Fire.
Remove other old coatings. A non-combustible plaster base can be used on firmly adhering coatings that
cannot be removed.
Uncoated concrete Remove film-forming concrete release agent as well as any existing sinter skin and other impurities by suitable
means. See also brochure P10.de Knauf Plaster Competence (Section: Substrate examination).
Concrete with an existing coating Remove the old coatings. A non-combustible plaster base can be used on firmly adhering coatings that cannot
be removed.

Substrate Plaster thickness


Check the substrate for compliance with VOB part C, DIN 18350, chapter 3.1 The necessary minimum application layer thickness is a factor that is
and/or according to VOB part B, DIN 1961 paragraph 4 section 3. All dependent on the fire resistance requirements (see brochure P91.de Fire
substrates must be stable, dry, even and free of grease and dust as well as Protection Gypsum Plaster Planning Guide).
free of any residual substances that may reduce the adhesion. Layer thickness on steel: minimum 6 mm up to approx. 40 mm
Pretreat the substrate in accordance with the table above. Layer chickness on concrete: minimum 7 mm up to approx. 25 mm
Cover easily-soiled building components before commencement in
Application temperature / climate
accordance with Code of Practice “Abklebe- und Abdeckarbeiten für Maler-
Do not apply with room and/or component temperatures under +5 °C or
und Stuckateurarbeiten - Masking and covering for painting and stucco work”
exceeding +40 °C. Protect freshly applied plaster against direct sunlight,
(German only) issued by the Bundesverband Ausbau und Fassade.
frost, rain and wind until it has fully dried.
Machines / equipment
Application time
Knauf PFT mixing pump G 4
About 180 to 300 minutes depending on the substrate.
■ Stator:  D4-3 or D6-3
■ Rotor:  D4-3 or D6-3 Drying
■ Mortar hoses:  Ø 25 mm Provide good ventilation to ensure quick drying of the plaster.
■ Spray nozzle:  Ø 10 or 12 mm If mastic asphalt screed is applied after plastering, sufficient transverse
■ Wet mortar pumping distance:  25 m ventilation is required to avoid thermal stresses.
■ Mixing screw:  G4/G5 Drying time: at 10 mm plaster thickness is an average of 14 days depending
Alternative: on the humidity, temperature and ventilation of the room. The drying time will
■ Insulation plaster mixing screw  G4/G5 be extended with unsuitable temperatures / air humidity.
For intricate components and/or a finer spray pattern, a spray gun as well as Surface
a stator with a reduced delivery output (l/min) can be used. The MP 75 L Fire finished surface is rough. If necessary, the concrete
■ Stator: D3-4 or D3-5 surfaces can be levelled and smoothed after spreading, setting and drying
with subsequent smoothing/pore sealing with Multi-Finish (M).
Application
The additional coatings may not be attributed to the effective fire protection
The required application consistence is set by gauging the water feed
layer thickness of the MP 75 L Fire.
accordingly (approx. 1.3 to 1.5 bar/metre of mortar hose). The spray pattern
is influenced by adjusting the air nozzle. The layer thicknesses specified in the P91.de Planning
The mortar is then applied evenly at a distance of approx. 30 cm from the Guide are minimum thicknesses that must be observed. It
substrate in uniform layers to the specified thickness so that a grainy surface is not permissible to apply a second layer after the plaster
is achieved. has hardened. For this reason, we recommend application
Caution of a layer thickness that is always 10 to 20 % more than the
Check the application thickness regularly during spray application.
minimum to avoid the risk of layer thicknesses that are too thin.
Depending on the temperature, breaks in spraying not exceeding 10 to 15
minutes are possible. Clean the machine and hoses with longer breaks / MP 75 L Fire is not suitable for structurally effective concrete
interruptions in application. renovations.
2
P911.de MP 75 L Fire
Gypsum-based plaster for increased fire protection

Technical data
Description Standard Unit MP 75 L Fire
Reaction to fire EN 13501-1 Class A1
Compressive strength EN 1015-11 N/mm2 ≥ 1.7
Bond strength EN 13279-2
▪ on concrete and steel N/mm2 ≥ 0.1
▪ on galvanized sheet metal N/mm2 ≥ 0.05
Water vapour diffusion resistance EN 12086 – 8
pH value – – 12 – 13
Initial setting time – min approx. 90 - 170
Final setting time – min approx. 180 - 300
Bulk density – kg/m3 500 – 600
Dry density EN 1015-10 kg/m3 approx. 750
The stated technical data were evaluated acc. to the respective test standards. Deviations under site conditions are possible.

Material requirement and efficiency


Application Consumption approx. Yield approx.
kg/m2 m²/bag m2/t
10 mm application thickness 6.7 3.0 150.0
All stated figures are approximate values and may deviate depending on the substrate conditions. The exact consumption can only be determined on the
individual object.

Product range
Description Application Packaging unit Material number EAN
MP 75 L Fire 20 kg / bag 24 bags / pallet 00466648 4003982315700

Sustainability and environment


Short description Value
Requirements of the German AgBB-scheme Compliant
Corresponds to the French emissions class A+
VOC content acc. to RL2004/42/EC Not relevant
Solvent-free and softener-free acc. to VdL-RL01 (Revision 4) Not relevant
Available certificates IBR
Environmental Product Declaration EPD-BVG-KNG-20140073-IAG1-DE

3
P911.de MP 75 L Fire
Gypsum-based plaster for increased fire protection

Observe safety data sheet!


For safety data sheets and CE marking see
pd.knauf.de

Videos for Knauf systems and products can be found under the The iPad App Knauf Infothek now provides all the current
following link: information and documents from Knauf Gips KG at any time and
EPD www.youtube.com/knauf in every location in a clear and comfortable way.
Knauf Infothek

Knauf Direct Knauf Gips KG Am Bahnhof 7, 97346 Iphofen, Germany


Technical Advisory Service:
All technical changes reserved. Only the current printed instructions are valid. The stated information represents current state-of-
the-art Knauf technology. The entire state of approved engineering rules, appropriate standards, guidelines, and rules of crafts-
[email protected] manship are not included herewith. These and all application instructions have to be adhered to separately by the installer. Our
warranty is expressly limited to our products in flawless condition. All application quantities and delivery amounts are based on
empirical data that are not easily transferable to other deviating areas.
www.knauf.de All rights reserved. All amendments, reprints and photocopies, including those of excerpts, require our expressed permission.

The stated constructional and structural design specifications and characteristics of building physics of Knauf systems can
P911.de/eng/06.21/0/TB only be ensured with the exclusive use of Knauf system components, or other products expressly recommended by Knauf.