MPI Wire Code

This document provides a wiring schedule for copper conductors for single phase, three phase, and three phase with neutral wiring. It lists the wire codes, ampacity ratings, required conductor sizes for lines, grounds, and neutrals, and minimum conduit sizes for different conductor configurations. It also includes notes on equipment grounding conductor sizes, parallel raceways, cable trays, circuit breaker ratings, solid wire terminations, approved wire and conduit types, motor circuit breakers, and related documents.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
507 views1 page

MPI Wire Code

This document provides a wiring schedule for copper conductors for single phase, three phase, and three phase with neutral wiring. It lists the wire codes, ampacity ratings, required conductor sizes for lines, grounds, and neutrals, and minimum conduit sizes for different conductor configurations. It also includes notes on equipment grounding conductor sizes, parallel raceways, cable trays, circuit breaker ratings, solid wire terminations, approved wire and conduit types, motor circuit breakers, and related documents.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

PROJECT NAME : LPD Paseo 25th Flr.

, Chatham House
OWNER : Alveo 116 Valero cor. V.A. Rufino Sts.
PROJECT NO. : MP2019 Salcedo Village, Makati City
LOCATION : Paseo De Roxas, Makati City 1227 Philippines
DATE PREPARED : 31-Aug-22 Tel. No. (632) 887 1391
Fax. No. (632) 887 1172
E-mail: [email protected]
WIRING SCHEDULE FOR COPPER CONDUCTORS

A.1 SINGLE PHASE 2W + G


LINE CONDUCTOR SIZE CONDUIT SIZE GENERAL NOTES:
AMPACITY
WIRE CODE LINE GROUND PVC IMC
FOR THWN
(A) mm² mm² mm F mm F 1. WIRING SCHEDULE TAG:
S2.0 20 2.0 2.0 20 15
S3.5 25 3.5 3.5 20 15 2 T125
S5.5 35 5.5 5.5 20 15
S8.0 50 8.0 5.5 25 20 WIRE CODE (SEE TABLE)
S14 65 14 5.5 25 20
S22 85 22 8.0 32 25 NUMBER OF PARALLEL SETS
S30 100 30 8.0 40 25
S38 115 38 8.0 40 32 2. THE MINIMUM SIZE OF EQUIPMENT GROUNDING CONDUCTOR IN EACH RACEWAY
S50 140 50 SEE TABLE 63 40 (CONDUIT) SHALL BE AS SHOWN IN THE TABLE BELOW BUT SHALL NOT BE
S60 155 60 SEE TABLE 63 50
S80 190 80 SEE TABLE 63 50 REQUIRED TO BE LARGER THAN THE PHASE CONDUCTOR SUPPLYING THE
S100 220 100 SEE TABLE 75 50 EQUIPMENT, UNLESS OTHERWISE SPECIFIED:
S125 255 125 SEE TABLE 75 65
RATING OF CIRCUIT PROTECTIVE SIZE OF
DEVICE AHEAD OF EQUIPMENT, COPPER
A.2 THREE PHASE 3W + G (COPPER CONDUCTORS) CONDUIT, ETC. NOT EXCEEDING CONDUCTOR,
LINE CONDUCTOR SIZE CONDUIT SIZE 3. (AMPERES) mm2 (mm dia)
AMPACITY
WIRE CODE LINE GROUND PVC IMC 15 2.0 (1.6)
FOR THWN
(A) mm² mm² mm F mm F 20 3.5 (2.0)
T2.0 20 2.0 2.0 20 15 4. 60 5.5 (2.6)
T3.5 25 3.5 3.5 20 15 100 8 (3.2)
T5.5 35 5.5 5.5 20 15 200 14
T8.0 50 8.0 5.5 25 20 5. 300 22
T14 65 14 5.5 32 25 500 30
T22 85 22 8.0 40 25 600 38
T30 100 30 8.0 40 32 6. 800 50
T38 115 38 8.0 50 32 1000 60
T50 140 50 SEE TABLE 63 40 1200 80
T60 155 60 SEE TABLE 63 40 1600 100
T80 190 80 SEE TABLE 63 50 2000 125
T100 220 100 SEE TABLE 75 50 2500 175
T125 255 125 SEE TABLE 75 65 3000 200
T150 285 150 SEE TABLE 90 65 4000 250
T175 305 175 SEE TABLE 90 80 5000 400
T200 325 200 SEE TABLE 90 80 6000 400
T250 375 250 SEE TABLE 100 80
3. FEEDERS HAVING MULTIPLE PARALLEL SETS OF RACEWAYS (CONDUITS) SHALL
BE PROVIDED WITH FULL SIZED EQUIPMENT GROUNDING CONDUCTOR FOR EACH
A.3 THREE PHASE 3W + N + G (COPPER CONDUCTORS) SETS OF RACEWAY (CONDUITS) IN ACCORDANCE WITH NOTE 2, UNLESS
LINE CONDUCTOR SIZE CONDUIT SIZE 3W + 2N + G OTHERWISE SPECIFIED.
AMPACITY
WIRE CODE LINE NEUTRAL GROUND PVC IMC
FOR THWN WIRE CODE
(A) mm² mm² mm² mm F mm F 4. FEEDERS ON CABLE TRAYS OR CABLE LADDERS SHALL BE PROVIDED WITH A
X2.0 20 2.0 2.0 2.0 20 15 Y2.0 SINGLE EQUIPMENT GROUNDING CONDUCTOR IRRESPECTIVE OF NUMBER OF
X3.5 25 3.5 3.5 3.5 20 15 Y3.5 PARALLEL SETS, UNLESS OTHERWISE SPECIFIED.
X5.5 35 5.5 5.5 5.5 25 15 Y5.5
X8.0 50 8.0 8.0 5.5 32 20 Y8.0 5. ALL LOW VOLTAGE CIRCUIT BREAKER SHALL BE RATED FOR 75 OC INSULATED
X14 65 14 14 5.5 32 25 Y14 COPPER CONDUCTORS.
X22 85 22 22 8.0 40 32 Y22
X30 100 30 30 8.0 50 32 Y30 6. ALL CONDUCTORS TERMINATING IN WIRING DEVICES
X38 115 38 38 8.0 63 40 Y38 (RECEPTACLE OUTLETS, SWITCHES, ETC) SHALL BE SOLID WIRE.
X50 140 50 50 SEE TABLE 63 50 Y50
X60 155 60 60 SEE TABLE 63 50 Y60 7. THE TYPE OF WIRE AND CONDUIT SHALL BE THWN OR THHN IN IMC CONDUIT
X80 190 80 80 SEE TABLE 75 50 Y80 UNLESS OTHERWISE NOTED.
X100 220 100 100 SEE TABLE 75 65 Y100
X125 255 125 125 SEE TABLE 90 65 Y125 8. USE CIRCUIT BREAKER WITH TYPE "D" TRIPPING CURVE CHARACTERISTICS
X150 285 150 150 SEE TABLE 90 80 Y150 OR EQUIVALENT FOR ALL MOTOR LOADS.
X175 305 175 175 SEE TABLE 100 80 Y175
X200 325 200 200 SEE TABLE 100 80 Y200 9. THIS DOCUMENT SHALL BE READ IN CONJUNCTION WITH THE SCHEMATIC
X250 375 250 250 SEE TABLE 110 90 Y250 DIAGRAMS AND RELEVANT SPECIFICATIONS AND DRAWINGS.